ATT_3_-_250806_IFB_Packge_New_Sunshine_Sub_-_Station_BoM.pdf

PDF 176 KB Posted

Attached to
New Sunshine Substation Construction
Solicitation number
2025/2026/02
Issued by
Quay County, New Mexico

About this file

The document is a Bill of Materials for the COG New Sunshine Substation Bid Package dated 8/5/2025, detailing comprehensive equipment and infrastructure requirements for a new electrical substation. The bill of materials encompasses a wide range of electrical components including structures, transformers, circuit breakers, switches, surge arresters, conductors, cables, conduits, grounding equipment, control building, battery systems, and associated installation materials. The project involves procuring and specifying detailed technical components across multiple electrical system categories, with specific catalog numbers, quantities, and technical specifications for each item.

The bill of materials provides extensive technical details for a complete substation infrastructure, including major material items like a 15/20/25/28 MVA main power transformer, 125 VDC battery bank, station control building, and numerous electrical connection and support components. The document suggests a comprehensive electrical infrastructure project with precise engineering specifications, indicating a significant electrical grid expansion or renovation effort. Notably, the bill includes provisions for future installations, spare parts, and detailed grounding and connection specifications, reflecting a thorough and forward-looking approach to substation design and equipment procurement.

View the file

Other files

Show all 20

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

COG New Sunshine Substation

Bill of Material

Bid Package ‐ 8/5/2025

A1 1 2 Each X ‐ No

115kV A‐Frame Deadend & Switch Structure ‐ Galvanized steel per steel drawings & details.

Major Material Item

A2 ‐ ‐ ‐ ‐ ‐ ‐ Not Used

A3 1 2 Each X ‐ No

115 kV Breaker Support Structure ‐ Galvanized steel per steel drawings & details.

Provided by Breaker Manufacturer

A4 ‐ ‐ ‐ ‐ ‐ ‐ Not Used

A5 1 1 Lot X ‐ No

Main Power Transformer Oil Containment Steel Support Structure & grating – Galvanized steel grating and supports per steel drawings & details.

Major Material Item

A6 1 1 Lot X ‐ No

Alternate Power Transformer Oil Containment Steel Support

Structure & Grating – Galvanized steel grating and supports per steel drawings & details.

Major Material Item

A7 1 3 Each X ‐ No

Bus Disconnect Switch Stand ‐ Galvanized steel per steel drawings & details.

Major Material Item

A8 1 1 Each X ‐ No Diag. Bus Support Structure ‐ Galvanized steel per steel drawings & details. Major Material Item

A9 1 ‐ ‐ ‐ ‐ ‐ Not Used

A10 1 1 Lot X ‐ No

Distribution Bay Support Structure ‐ 6 bays in horizontal configuration ‐ Galvanized steel per steel drawings & details.

Major Material Item

A11 ‐ ‐ ‐ ‐ ‐ ‐ Not Used

A12 1 7 Each X ‐ No Feeder Breaker Support Structure ‐ Provided by breaker vendor.

Major Material Item

A13 1 1 Each X ‐ No

Express Feeder Riser Structure (Noe Feeder) ‐ Galvanized steel per steel drawings & details.

Major Material Item

A13 2 2 Each X ‐ No

Alternate Feed Riser Structure ‐ Galvanized steel per steel drawings

& details.

Major Material Item

A13 3 4 Each X ‐ No

Distribution Feeder Riser Structure ‐ Galvanized steel per steel drawings & details.

Major Material Item

A14 1 3 Each X ‐ No

Pull Box Cover ‐ Steel, Painted Safety Yellow, per drawings and details.

Major Material Item

A15 1 5 Each X ‐ No Static Mast ‐ Galvanized steel per steel drawings & details.

Major Material Item

A16 1 7 Each X ‐ No

Switch Operator Platforms – Galvanized steel per steel drawings & details.

Major Material Item

A17 1 1 Lot X ‐ No

Control Building Support Structure & Pier Angles – Provided by building vendor.

Major Material Item

A18 1 2 Each X ‐ No Access Platforms ‐ Galvanized steel per steel drawings & details.

Major Material Item

A99 1 1 Lot X ‐ No

Anchor Bolts & Templates ‐ Galvanized and black steel per steel drawings & details. See (Drawings SS‐303 & SS‐305 for details)

Major Material Item

A10 10 25 Feet ‐ X Yes Conductor ‐1/0 ACSR, 6/1 strand "Raven"

A10 11 4 Each ‐ X Yes

1/0 ACSR Pin terminal for jumpers to PT's and Station Service

Transformer.

Burndy Catalog Number: YE25R25

A10 12 4 Each ‐ X Yes Terminal ‐ Compression type,1/0 ACSR to 2‐hole, 2" wide NEMA pad.

SEFCOR Catalog Number AL‐398‐2B or approved equivalent.

Bid Package ‐ 8/5/2025

A20 10 6 Each Insulator – 115 kV suspension type, 550 kV BIL, Y‐Clevis ‐ Y‐Clevis.

SEE T‐line BoM

A20 20 6 Each Compression Deadend – double tongue with NEMA 2 hole pads. See

T‐line BoM.

A25 10 72 Each X ‐ No Insulator ‐ 25 kV, 150 kV BIL, Cypoxy, 3" bolt circle, S&C catalog number PA‐7253R1. (Includes 2 Spares)

A38 10 N/A Feet Shield wire – 3/8” H.S.S. Rated breaking strength 10,800 lbs. See T‐ line BoM.

A38 12 4 Each

Terminal – Compression type for 4/0 Tinned Cu, to 2‐hole, 2" wide

NEMA pad. Hubbell catalog number:

VAUL‐4/0‐12BN or approved equivalent. See T‐line BoM.

A47 10 950 Feet ‐ X Yes Conductor ‐ 477 MCM ACSR, 26/7 strand “Hawk” for jumpers and bus damper wire.

A47 12 100 Each ‐ X Yes

Terminal – Compression type for 477 MCM ACSR to 2‐hole, 2" wide

NEMA pad. SEFCOR catalog number AL‐858‐2B or approved equivalent.

A47 13 24 Each ‐ X Yes

Terminal – Compression type for 477 MCM ACSR to 90 deg, 2‐hole, 2" wide NEMA pad. SEFCOR catalog number AL‐858‐2B‐90 or approved equivalent.

A47 14 94 Each ‐ X Yes

Terminal – Compression type for 477 MCM ACSR to 4‐hole, 4" wide

NEMA pad. SEFCOR catalog number AL‐858‐4B or approved equivalent.

A47 15 6 Each ‐ X Yes

Terminal – Compression type for 477 MCM ACSR to 90 degree 4‐ hole, 4" wide NEMA pad. SEFCOR catalog number AL‐858‐4B‐90 or approved equivalent.

A47 16 12 Each ‐ X Yes

Terminal – Compression type for 477 MCM ACSR to 45 degree 2‐ hole, 2" wide NEMA pad. SEFCOR catalog number AL‐858‐2B‐45 or approved equivalent.

A47 17 3 Each ‐ X Yes

Fitting – Aluminum Bolted conductor support for 477 MCM with 3" bolt circle mounting. Travis Pattern catalog number 19‐399 or approved equivalent.

A47 18 3 Each ‐ X Yes

Terminal – Bolted pass‐through terminal for 477 MCM on 4‐hole

NEMA pad spacing, tinned. SEFCOR catalog number SXR‐34‐SND or approved equivalent.

A47 24 6 Each ‐ X Yes

Terminal – Bolted type for two (2) 477 MCM ACSR conductors to 4‐ hole, 3" wide NEMA pad. Travis Pattern catalog number 11‐250 or approved equivalent.

A47 40 3 Each ‐ X Yes

Cable Spacer ‐ Bolted type for 477 MCM ACSR to 4‐hole, 4" wide

NEMA pad with 4" spacing between conductors. SEFCOR catalog number ASPC‐22‐4‐4B or approved equivalent.

A61 10 280 Feet ‐ X Yes

Bus Pipe ‐ 1" Aluminum seamless IPS tube, Schedule 40, 6063‐T6 electrical grade in 20' & 40' lengths. Alcoa catalog number

100S40YT6B or approved equivalent. See SS‐24 for bus cutting schedule.

A61 12 30 Each ‐ X Yes

Terminal – Compression type for 1” Al tubing to 2‐hole, 2" wide

NEMA pad. DMC catalog number PLK1855D16 or approved equivalent.

A61 90 60 Each ‐ ‐ ‐ Bus Elbow ‐ Field bend ninety to coordinate with terminal pad and bus tee locations as shown in the drawings.

A62 10 520 Feet ‐ X Yes

Bus Pipe ‐ 2" Aluminum seamless IPS tube, Schedule 40, 6062‐T6 electrical grade in 20' & 40' lengths. Alcoa catalog number

200S40YT6B or approved equivalent. See SS‐24 for bus cutting schedule.

A62 11

(OR AS REQ'D)

Each ‐ X Yes

Splice ‐ Compression type for 2" Al tubing to 2" Al tubing. DMC catalog number PLK1000D32 or approved equivalent. (Quantity is based on 40' bus lengths. Increase if shorter lengths are procured)

A62 12 30 Each ‐ X Yes

Terminal ‐ Compression type for 2" Al tubing to 2‐Hole, 2" wide

NEMA pad. DMC catalog number PLK1855D32 or approved equivalent

A62 14 6 Each ‐ X Yes

Terminal ‐ Compression type for 2" Al tubing to 4‐Hole, 4" wide

NEMA pad. DMC catalog number PLK1850D32B or approved equivalent

A62 19 9 Each ‐ X Yes Drive‐On Corona End Cap ‐ For 2" Al pipe bus. SEFCOR catalog number DP‐58‐AL or approved equivalent.

By Others

By Others

By Others

By Others

Bid Package ‐ 8/5/2025

A62 20 60 Each ‐ X Yes Bus Support ‐ Slip/fixed type for 3" bolt circle to 2" Al tube. SEFCOR catalog number ASTI‐58‐3 or approved equivalent.

A62 28 30 Each ‐ X Yes Tee – Compression type for 2” Al tubing to 1" Al tubing DMC catalog number PLK1500D1632E1 or approved equivalent.

A62 29 3 Each ‐ X Yes Bus Support ‐ Vertical slide support for 2" bus pipe. SEFCOR Catalog

Number: WVTSI‐58‐3

A62 90 3 Each ‐ X Yes Bus Elbow ‐ Compression 90 degree type for 2" Al tube to 2" Al tube.

DMC catalog number PLK1400D32E4 or approved equivalent

A62 94 9 Each ‐ X Yes

Tee – Compression, Straight type for 2” Al tube to 4‐hole, 4" wide

NEMA pad. DMC catalog number: PLK1100D32E2 or approved equivalent

A62 99 3 Each ‐ X Yes Bus Support – Expansion type for 3” bolt circle to 2” Al. tube. DMC catalog number PLK2700D32E1 or approved equivalent

A90 10 9 Each ‐ X No

Spline Ball Ionizer ‐ Lightning Eliminator Consultants. Furnish with

48” threaded shaft, 48” diameter, 120 points. LEC catalog number

SBI‐48‐48 with option D (3" long, 5/8‐11 threaded mounting shaft).

A96 1A 1 Lot ‐ X Yes Bolt ‐ 1/2"‐13 UNC, C651 Silicon Bronze. Various lengths as needed.

A96 2A 1 Lot ‐ X Yes Flat Washer ‐ 1‐3/8" diameter SAE standard for 1/2" fasteners, 316

Stainless Steel.

A96 3A 1 Lot ‐ X Yes

Belleville Washer ‐ for 1/2" fasteners, diameter not to exceed 1 1/4", 3800lb flatload (4000 lb load), stainless steel finish painted red. Key

Belleville part number 1250‐E‐125‐S.

A96 4A 1 Lot ‐ X Yes Nut ‐ 1/2"‐13 UNC, Silicon Bronze.

A159 10 100 Feet ‐ X Yes Conductor 1590 MCM ACSR, 45/7 strand “Lapwing” conductor.

A159 14 50 Each ‐ X Yes

Terminal – Compression type for 1590 MCM ACSR to 4‐hole, 4" wide NEMA pad. SEFCOR catalog number AL‐1506‐4B or approved equivalent.

A159 15 10 Each ‐ X Yes

Terminal – Compression type for 1590 MCM ACSR to 90 degree 4‐ hole, 4" wide NEMA pad. SEFCOR catalog number AL‐1506‐4B‐90 or approved equivalent.

A159 17 1 Each ‐ X Yes

Fitting – Aluminum Bolted conductor support for 1590 MCM with 3" bolt circle mounting. Travis Pattern catalog number 19‐403 or approved equivalent.

A159 40 3 Each ‐ X Yes Tee‐ Bolted type for 1590 MCM ACSR to 477 MCM ACSR. SEFCOR catalog number ACRCT‐491139 or approved equivalent.

A954 10 80 Feet ‐ X Yes Conductor ‐ 954 MCM ACSR, 54/7 strand “Cardinal” for jumpers and bus damper wire.

A954 12 9 Each ‐ X Yes

Terminal – Compression type for 954 MCM ACSR to 2‐hole, 2" wide

NEMA pad. SEFCOR catalog number AL‐130‐2B or approved equivalent.

A954 13 6 Each ‐ X Yes

Terminal – Compression type for 954 MCM ACSR to 90 deg, 2‐hole, 2" wide NEMA pad. SEFCOR catalog number AL‐130‐2B‐90 or approved equivalent.

A954 14 6 Each ‐ X Yes

Terminal – Compression type for 954 MCM ACSR to 4‐hole, 4" wide

NEMA pad. SEFCOR catalog number AL‐130‐4B or approved equivalent.

A954 16 3 Each ‐ X Yes

Terminal – Compression type for 954 MCM ACSR to 45 degree 2‐ hole, 2" wide NEMA pad. SEFCOR catalog number AL‐130‐2B‐45 or approved equivalent.

B15 10 2 Each X ‐ No

115 kV Group Operated Air Break Switch – 115 kV, 1200 amp, 550 kV

BIL. Center Break Vee Switch, configured for vertical mounting and

NEMA 4‐hole tinned pads. Mounting centerline height, 26 feet.

Royal catalog number AV11512STD. Major Material Item

B25 10 3 Each X ‐ No

Bus Disconnect Switch ‐ 25 kV, 150 kV BIL, vertical break 1200 amp, group operated switch S&C catalog number 135814R2‐E‐Z5

Engineering Drawing ED‐151R1

Major Material Item

Bid Package ‐ 8/5/2025

C15 10 24 Each X ‐ No

Surge Arrester ‐ Station class, polymer housed, metal oxide, 10kV rated, 8.4 kV MCOV Surge arrester with 4‐hole NEMA terminal and eyebolt grounding terminal, Spade Top, Tripod base 7.88"‐10” bolt circle. Hubbell type EVP catalog number EVP000900‐3001. Includes

Three spares Major

Material Item

C15 20 3 Each X ‐ No

Surge Arrester ‐ Station class, polymer housed, metal oxide, 10kV rated, 8.4 kV MCOV Surge arrester with 4‐hole NEMA terminal and eyebolt grounding terminal, Spade Top, Tripod base 7.88"‐10” bolt circle. Hubbell type EVP catalog number EVP000900‐3001

Major Material Item included with Transformer H10/10

C90 10 9 Each X ‐ No

Surge Arrester ‐ Station class, polymer housed, metal oxide, 90 kV rated, 74 kV MCOV Surge arrester with 4‐hole NEMA terminal and eyebolt grounding terminal, Spade Top, Tripod base 7.88"‐10” bolt circle. Hubbell type EVP catalog number EVP007400‐3001. Includes

Three spares.

Major Material Item

C90 20 3 Each X ‐ No

Surge Arrester ‐ Station class, polymer housed, metal oxide, 90 kV rated, 74 kV MCOV Surge arrester with 4‐hole NEMA terminal and eyebolt grounding terminal, Spade Top, Tripod base 7.88"‐10” bolt circle. Hubbell type EVP catalog number EVP007400‐3001

Major Material Item included with Transformer H10/10

D10 10 1 Each ‐ X Yes

Switch Stick ‐ 18’ fiberglass extendable type hook stick with

Aluminum container and PVC or neoprene liner. Hastings Tel‐O‐Pole style with NEMA disconnect head, catalog number 3118 with container 01‐3352 and mounting kit 01‐3200‐41 or approved equivalent. Contractor to field install in accessible location on station security fence with an angle on the container that places the end cap lower to allow for drainage of moisture.

D25 10 4 Each X ‐ No

Fused Disconnect Switch ‐ 25kV, 150 kV BIL, 200A with tin plated terminals and Cypoxy insulators. S&C SMD‐20 catalog number:

192223R2‐E‐Z5

Major Material Item

D25 11 2 Each X ‐ No

Fuse ‐ For item D25‐10 (Station Service XFMR), K speed, rated 6A, S&C SMU‐20, #703006. Quantity includes one extra fuse.

Major Material Item

D25 12 6 Each X ‐ No

Fuse ‐ For item D25‐10 (Bus PT's), K speed, rated 3A, S&C SMU‐20, #703003. Quantity includes one extra fuse for each switch.

Major Material Item

D25 20 30 Each X ‐ No

Disconnect Switch ‐ 35 kV, 150 kV BIL, 900 A, vee‐type, vertical mount, hookstick operated. S&C series catalog number 4873R2‐E‐

B90. Major Material Item

D25 21 15 Each X ‐ No

Disconnect Switch ‐ 35 kV, 150 kV BIL, 900 A, vee‐type, inverted mount, hookstick operated. S&C series catalog number 4893R2‐E‐

B90. Major Material Item

E1 1 2 Each X ‐ No

115 kV SF6 Dead Tank Circuit Breaker – GE Grid Solutions 3‐Ph, 145 kV rated, 650 kV BIL, 3 cycle, 1200 Amp, 40 kAIC with auxiliary contacts, two sets of 1200/5 MR CTs on 1,3,5; two sets of 1200/5 MR

CTs on 2,4,6, mild steel enclosure, 125 VDC control power, 120 VAC auxiliary power, low voltage control breakers, includes NEMA 4 hole pads. Alstom‐GE type DT1‐145FK‐40‐F1. (Alt Feed is future install, by others)

Major Material Item

Bid Package ‐ 8/5/2025

F1 1 5 Each X ‐ No

27kV Circuit Breaker ‐ ABB R‐MAG 3‐Ph, 125 kV BIL, 1200 Amp, 3.0 cycle, 25 kAIC with eight 'a' and eight 'b' auxiliary contacts, one set of 1200/5 MR CTs on each side, mild steel + NEMA 4 enclosure, 125

VDC control power, 120/240 VAC auxiliary power, knife switches, basic control and no panel. Includes NEMA 4 hole pads. ABB

Catalog Number MB22146GGCH2SBL4

Major Material Item

F1 2 2 Each X ‐ No

27kV Circuit Breaker ‐ ABB R‐MAG 3‐Ph, 125 kV BIL, 2000 Amp, 3.0 cycle, 25 kAIC with eight 'a' and eight 'b' auxiliary contacts, one set of 1200/5 MR CTs on 135, and two sets of 2000/5 MR CTs on 246, mild steel + NEMA 4 enclosure, 125 VDC control power, 120/240

VAC auxiliary power, knife switches, basic control and no panel.

Includes NEMA 4 hole pads. ABB Catalog Number

MB22246LUCH2SBL4

Major Material Item

G1 10 3 Each X ‐ No

Voltage Transformer ‐ 15.5 kV, 110 kV BIL, 7620/13200GY/120V, 63.5:1, 0.3 WXY, Ritz type VEF‐15‐09. Catalog number 121531009‐

395004 Major Material Item

G2 10 3 Each X ‐ No

Current Transformer – 15.5 kV, 110 kV BIL, 400/800:5 amps, 0.3B‐

0.9/1.8, Ritz type GIFU‐15‐03. Catalog number 111553003‐149028

Major Material Item

G2 20 12 Each X ‐ No

Current Transformer – 15.5 kV, 110 kV BIL, 200/400:5 amps, 0.3B‐

0.9/1.8, Ritz type GIFU‐15‐03. Catalog number 111553003‐149026

Major Material Item

G2 30 1 Each X ‐ No

Current Transformer – 25.5 kV, 150 kV BIL, 1000/2000:5 amps, 0.3B‐

2.0, C200/C400. Ritz Instrument type GIFU‐25‐01. Catalog number

112053001‐45931

Major Material Item

G90 10 4 Each X ‐ No Relay Panels ‐ Per Protection and Controls drawings and specifications. Major Material Item

G90 11 1 Each X ‐ No SCADA/Comm panel ‐ Per Protection and Controls drawings and specifications. Major Material Item

H10 10 1 Each X ‐ No

Main Power Transformer – 15/20/25/28 MVA, ONAN/ONAF, three phase, 60 Hz, 55/65 Degree Rise, 115 kV DELTA to 13.2/7.62 kV

Grounding Wye with LTC. WEG PEP number 150‐2400680‐2.

Major Material Item

H10 11 3 Each X ‐ No

Connector – Bushing stud to 4‐hole NEMA pad for H1, H2 and H3 transformer bushings. Hubbell HDSF‐14‐1‐D‐12‐12 TP

Item furnished with transformer

H10 12 3 Each X ‐ No

Connector – Bushing stud to 4 Hole pad for X1, X2, and X3 transformer bushings. Delta Connectors PM60C12‐1‐4N4‐E. Item furnished with Transformer

H10 13 1 Each X ‐ No Connector – Bushing stud to NEMA 4‐hole pad for X0 bushing. Delta

Connectors PM60C12‐1‐4N4‐E. Item furnished with Transformer

H10 20 1 Each X ‐ No

Alternate Power Transformer – 15/20/25/28 MVA, OA/FA/FOA, three phase, 60 Hz, 55/65 Degree Rise, 115 kV DELTA to 13.2/7.62 kV

Grounding Wye with LTC. GE Catalog number F‐961446B (Existing

Mendoza Station Unit ‐ Future Installation by others)

Major Material Item

H10 21 1 Lot X ‐ No

Alternate Power Transformer Air Terminal Chamber for installation on Item H10/20. See drawings for details. (Future Installation by others)

Major Material Item

H20 10 1 Each X ‐ No

Station Service Transformer – 25 kVA, single phase, 60 Hz, 7.967kV to 120/240V. Pole mount style with DETC.

Owner Material Item

Bid Package ‐ 8/5/2025

J50 10 n/a n/a

URD Conductor ‐ 500 MCM Al, 220 mil insulation, 15kV with jacketed concentric 1/3 neutral (overall OD = 1.72"/insulation OD = 1.39").

Okonite Catalog number 162‐23‐3093

J50 20 12 Each

Cable Terminator – 3M Quick Term type QT‐III order number 7655‐S‐

4 with 4 skirts, for jacketed concentric neutral cable, rated for 150 kV BIL. 12.25" in length, Insulation OD range 1.05" ‐ 1.80". Include two hole termination lug for 500 AL and suitable cold shrink sealing kit for jacket. (includes one complete spare)

Major Material Item

J50 21 12 Each ‐ X Yes

Cable Mounting Bracket ‐ 3M double clamp type mounting bracket for use on jacketed cables. Provide with stainless steel mounting hardware. For use with cable OD ranges from 1.45" ‐ 1.95". Catalog number MBS‐5 or approved equivalent.

J50 40 15 Each

Cable Terminator – For 500 MCM Al, underground cable, Slip‐on type rated for 25kV, 150kV BiL. G&W Part No. PAT‐1872 with adapter"K2‐G3" ‐ kit, compression connector A50860000C00 and aluminum vertical flat NEMA 4‐hole pad Part No. A5076‐192A.

(Quantity shown includes three spares)

Major Material Item

J100 10 Feet

URD Conductor ‐ 1000 MCM Al, 220 mil insulation, 15kV with jacketed concentric 1/3 neutral (overall OD = 2.16"/insulation OD =

1.77"). Okonite Catalog number 162‐23‐3099

J100 20 18 Each

Cable Terminator – 3M Quick Term type QT‐III order number 7655‐S‐

4 with 4 skirts, for jacketed concentric neutral cable, rated for 150 kV BIL. 12.25" in length, Insulation OD range 1.05" ‐ 1.80". Include two hole termination lug for 1000 AL and suitable cold shrink sealing kit for jacket. (includes one complete spare)

Major Material Item

J100 21 24 Each ‐ X Yes

Cable Mounting Bracket ‐ 3M double clamp type mounting bracket for use on jacketed cables. Provide with stainless steel mounting hardware. For use with cable OD ranges from 1.80" ‐ 2.40". Catalog number MBS‐6 or approved equivalent. Includes one complete spare

K1 2 470 Feet ‐ X Yes Cable ‐ Single conductor #2, Cu, XHHW‐2

K1 40 1400 Feet ‐ X Yes Cable ‐ Single conductor 4/0 Cu, XHHW‐2

K1 40R 40 Feet ‐ X Yes Cable ‐ Single conductor 4/0 Cu, DLO (Flexible Welding), RED

K1 40BK 40 Feet ‐ X Yes Cable ‐ Single conductor 4/0 Cu, DLO (Flexible Welding), BLACK

K2 8 1020 Feet ‐ X Yes Cable ‐ Two conductor #8, TC, XHHW‐2, E2 Color

K2 10 5900 Feet ‐ X Yes Cable ‐ Two conductor #10, TC, XHHW‐2, E2 Color

K3 1 350 Feet ‐ X Yes Cable – Three conductor #1, TC, XHHW‐2, E1 Color or numbered conductors

K3 8 270 Feet ‐ X Yes Cable – Three conductor #8, TC, XHHW‐2, E1 Color

K3 10 1750 Feet ‐ X Yes Cable ‐ Three conductor #10, TC, XHHW‐2, E1 Color

K4 10 7110 Feet ‐ X Yes Cable ‐ Four conductor #10, TC, XHHW‐2, E2 Color

K12 10 2800 Feet ‐ X Yes Cable ‐ Twelve conductor #10, TC, XHHW‐2, E2 Color, Shielded

K12 12 120 Feet ‐ X Yes Cable ‐ Twelve conductor #12, TC, XHHW‐2, E2 Color

K12 16 3480 Feet ‐ X Yes Cable ‐ Twelve conductor #16, TC, XHHW‐2, E2 Color, Shielded

K10 1 200 Feet ‐ X Yes Conduit ‐ 1" Rigid Galvanized Steel.

‐ X

K20 1 800 Feet ‐ X Yes Conduit – 2” Rigid Galvanized Steel.

K20 3 4600 Feet ‐ X Yes Conduit – 2" Schedule 40 PVC.

K20 4 130 Each ‐ X Yes Conduit – 2” PVC schedule 80, standard radius (16") sweep.

K25 1 10 Feet ‐ X Yes Conduit – 2.5” Rigid Galvanized Steel.

K25 3 80 Feet ‐ X Yes Conduit – 2.5" Schedule 40 PVC.

K25 4 2 Each ‐ X Yes Conduit – 2.5” PVC schedule 80, standard radius (30") sweep.

K40 3 920 Feet ‐ X Yes Conduit – 4" Schedule 40 PVC .

K40 5 40 Each ‐ X Yes Conduit – 4” PVC schedule 80, 48” long sweep.

Provided & Installed by Others

Provided & Installed by Others

Provided & Installed by Others

Provided & Installed by Others

Provided & Installed by Others

Bid Package ‐ 8/5/2025

K50 11 1 Each ‐ X Yes

Combination Service Entrance Device (Meter‐Main Combo) ‐

Ringless type, without bypass, 22 kA rated, with 200 amp main breaker for service disconnect. Includes 8 spaces for up to 16 circuits. NEMA 3R Enclosure, for 120/240 VAC application. Supply breakers as shown on drawing AC‐250. Include A200 Hub kit.

Schneider/ Square D catalog number QC816F200C or approved equivalent.

K50 12 1 Each Station Service Meter ‐ 120/240 Vac, 200 Amp rated form 2S.

Owner Furnished Item

K50 20 4 Each ‐ X Yes

Junction Box ‐ For use on A‐Frame structure for lighting electrical conduits, 8"x8"x4", screw cover, type 3R nVent/Hoffman Catalog Number: A8R84

K50 30 6 Each ‐ X Yes

Junction Box ‐ For use on CT/PT Connections. 16"X12"x6", NEMA 3R, Lift Off Cover nVent/Hoffman part number A16R126HCLO with

A14P12 back panel, APMK3RL016 panel mounting kit, and

AMFK3RL016 mounting bracket kit.

K60 3 1500 Feet ‐ X Yes Conduit – 6" Schedule 40 PVC

K60 5 14 Each ‐ X Yes Conduit – 6” PVC schedule 80, 60” long sweep.

K60 8 100 Feet ‐ X Yes Conduit – 6" Rigid Aluminum.

K60 9 10 Each ‐ X Yes Top Cable Support Vent ‐ 6"

Adalet Catalog Number: CV60

K60 10 10 Each ‐ X Yes Bottom Ventalator ‐ 6"

Adalet Catalog Number: BCV60

K70 0 1 Each ‐ X No Dummy Fuse ‐ Bussmann catalog number NNB‐R

K70 1 4 Each ‐ X Yes Fuse Holder Block – one fuse position and screw terminals for use with type "midget" fuses. Bussmann CHCC1DU or equivalent.

K70 2 6 Each ‐ X Yes Fuses ‐ Bussmann LP‐CC‐20 20 Amp Class CC Fuses

(Includes 3 spares)

K70 3 6 Each ‐ X Yes Ground Bar ‐ 14 AWG to 2 AWG. Minimum 7 position. Siemens

EC1GB82 or similar.

K70 4 15 Each ‐ X No Terminal Block ‐ 4‐point, shorting terminal block, GE‐27. GE Caralog number EB27B04S or approved equivalent.

K78 1 1 Lot ‐ X Yes Misc communications cables per Communications Cable Schedule on SS‐290

K80 10 22 Each ‐ X Yes

Yard Light ‐ set for 240 V, Lithonia 'D series' LED family. Six LED engines, 4000 K performance, flood type with integral slip fitter (for

2 3/8" OD pipe) and natural aluminum (gray) finish. Catalog number:

DSXF3 LED 6 P2 40K 70CRI FL MVOLT IS DNAXD

K80 11 1 Each ‐ X Yes

Dusk/Dawn Area Light ‐ Yard Light ‐ set for 120 V, Lithonia ESXF LED

Floodlight. Switchable output plus photo control. 4000 K performance, flood type with integral slip fitter (for 2 3/8" OD pipe) and standard finish with upper/bottom visor accessory

283G2KESXF5UBV DDB. Luminare Catalog number: ESXF3 ALO

SWW2 YS DDB

K90 1 1 Lot ‐ X Yes

Conduit fittings and accessories for Rigid, Aluminum, Galvanized

Steel, and PVC conduits as needed and in such variety, size and correct application as will be in accordance with neat and workmanlike installation practices.

K90 2 1 Lot ‐ X Yes

Cable Accessories ‐ Including miscellaneous wire and cable labels, Nylon insulated ring lugs, 3M Constant Force Springs for Grounding jacketed cables and any other material needed to complete the job according to the prints and in accordance with industry accepted practices.

K90 10 26 Each ‐ X Yes Signs ‐ "Warning” with graphics according to drawings – English

(includes one spare)

K90 11 26 Each ‐ X Yes Signs ‐ "Warning” with graphics according to drawings – Spanish

(includes one spare)

Provided by Others

Bid Package ‐ 8/5/2025

L1 1 8 Each ‐ X No 115 kV A‐Frame Switch Structure Foundations ‐ Complete per detail

L1‐1 & concrete specifications.

L2 ‐ ‐ ‐ ‐ Not Used

L3 1 2 Each ‐ X No 115 kV Breaker/Bus Support Foundation ‐ Complete per detail L3‐1

& concrete specifications.

L4 1 ‐ ‐ ‐ Not Used

L5 1 1 Each ‐ X No Power Transformer Oil Containment Foundation –Complete per detail L5‐1 & concrete specifications.

L6 1 1 Each ‐ X No Alternate Power Transformer Oil Containment Foundation –

Complete per detail L6‐1 & concrete specifications.

L7 1 3 Each ‐ X No Bus Disconnect Switch Stand Foundation ‐ Complete per detail L7‐1

& concrete specifications.

L8 1 1 Each ‐ X No 3‐Phase Diag. Bus Support Foundation ‐ Complete per detail L8‐1 & concrete specifications.

L9 1 ‐ ‐ ‐ ‐ ‐ Not Used

L10 1 14 Each ‐ X No Distribution Bay Support Foundation ‐ Complete per detail L10‐1 & concrete specifications.

L12 1 7 Each ‐ X No Feeder Breaker Foundation ‐ Complete per detail L12‐1 & concrete specifications.

L13 1 1 Each ‐ X No Express Feed Riser Foundation ‐ Complete per detail L13‐1 & concrete specifications.

L13 2 2 Each ‐ X No Alternate Feed Riser Foundation ‐ Complete per detail L13‐2 & concrete specifications.

L13 3 4 Each ‐ X No Distribution Feed Riser Foundation ‐ Complete per detail L13‐3 & concrete specifications.

L14 1 3 Each ‐ X No Pull Box Foundation ‐ Complete per detail L14‐1 & concrete specifications.

L15 1 5 Each ‐ X No Static Mast Foundation ‐ Complete per detail L15‐1 & concrete specifications or precast with prior approval.

L16 1 7 Each ‐ X No Switch Operator Platform Curb Sets – Complete per detail L16‐1 & concrete specifications.

L17 1 13 Each ‐ X No Control Building Pier Foundation ‐ Complete per detail L17‐1 & concrete specifications.

L18 1 2 Each ‐ X No Control Building Door Stoops ‐ Complete per detail L18‐1 & concrete specifications.

M1 1 1 Lot ‐ X No

Site Work ‐ Includes over‐excavation, eng. fill, soil removal for foundations, conduits and ground grid, recompaction, fine grading & leveling project area and application of gravel sufacing materials.

N1 1 1 Lot ‐ X No Chain Link Fence ‐ Furnish and install according to the drawings and the fence specifications.

O1 1 1500 Feet ‐ X Yes Grounding Conductor – 4/0 tinned Cu, soft drawn wire, 19 strand

O1 2 5400 Feet ‐ X Yes Grounding Conductor – 4/0 tinned Cu, soft drawn wire, 7 strand

O1 3 750 Feet ‐ X Yes Grounding Conductor – #2 solid Cu, tinned

O2 1 37 Each ‐ X Yes Ground Rod ‐ 3/4" X 10', 10 mil stainless steel. ERICO part number

683400.

O3 2 7 Each ‐ X Yes

Connector – Tinned U‐bolt type for one or two 4/0 Strand to 4" IPS gate post, SEFCOR catalog number GUR‐6414‐SND or approved equivalent.

O3 3 5 Each ‐ X Yes Connector – Tinned U‐bolt type for flexible braid to gate frame.

SEFCOR catalog number GBR‐54‐SND or approved equivalent.

O3 4 5 Each ‐ X Yes Flexible braid – Cu, tinned, 1‐1/16"x24", for grounding gates to gate posts. SEFCOR XBG76‐D‐24 or approved equivalent.

O3 5 20 Each ‐ X Yes Connector – for #2 AWG to 1‐1/4" IPS top rail. SEFCOR catalog number 1‐OC‐2548‐SND or approved equivalent.

O3 5A 4 Each ‐ X Yes Connector – for #2 AWG to 1‐1/2" IPS top rail. SEFCOR catalog number 1‐OC‐2648‐SND or approved equivalent.

Bid Package ‐ 8/5/2025

O3 6 4 Each ‐ X Yes

Connector – Tinned U‐bolt type for one or two 4/0 Strand to 6" IPS gate post, SEFCOR catalog number GUR‐6914‐SND or approved equivalent.

O3 7 6 Each ‐ X Yes Connector ‐ Tinned U‐bolt type for one 4/0 to 2" IPS fence line post, SEFCOR catalog number GUR‐5814‐SND or approved equivalent.

O3 8 1 Lot ‐ X Yes

Connector – Tinned split‐bolt for single #2 AWG to fence fabric and barbed wire. Burndy catalog number KSU23 or approved equivalent.

O3 9 9 Each ‐ X Yes

Connector – 4/0 strand To 5/8” threaded rod for spline ball grounding. SEFCOR catalog number 1‐OC‐2151, or approved equivalent.

O3 10 4 Each ‐ X Yes

Connector ‐ 4/0 strand to bolted 4‐Hole tinned NEMA Pad. For control building grounding connections. SEFCOR catalog number

FNCT‐12‐4A‐SND or approved equivalent.

O3 11 1 Lot ‐ X Yes Connector – for 4/0 strand to flat, galvanized.

SEFCOR GTC‐14 or approved equivalent.

O3 12 1 Lot ‐ X Yes Connector – for two parallel 4/0 strand, galvanized. SEFCOR GTC2‐

14 or approved equivalent.

O3 13 1 Lot ‐ X Yes Connector – for one #2 Cu solid, to one‐hole pad. SEFCOR FNCT‐12‐

1A or approved equivalent.

O3 14 8 Each ‐ X Yes

Terminal ‐ Compression for 4/0 Cu to 4" 4‐hole NEMA pad, copper.

X0 bushing connection. SEFCOR catalog number CL‐11‐4A or approved equivalent.

O3 17 8 Each ‐ X Yes Ground terminals on power transformer ‐ Anderson/Hubbell SWHD‐

050‐B2. (2 hole)

O3 18 1 Lot ‐ X Yes

Ground terminal ‐ 1 hole tinned compression for 4/0 bare copper ground wire for containment steel grounding connections. Burndy catalog number YA‐28 or approved equivalent

O3 19 1 Lot ‐ X Yes

Ground terminal ‐ 'narrow' 2 hole tinned compression for 4/0 bare tinned copper ground wire. Burndy catalog number YAZ‐28‐2N or approved equivalent

O3 20 125 Each ‐ X Yes Exothermic Tee – 4/0 Cu main to 4/0 Cu tap. Erico mold number TAC‐

2Q2Q, or approved equivalent. (150# weld)

O3 21 50 Each ‐ X Yes Exothermic Tee – 4/0 Cu to 3/4" ground rod. Erico mold number

GTC‐332Q or approved equivalent. (115# weld)

O3 22 100 Each ‐ X Yes Exothermic Cross – 4/0 Cu to 4/0 Cu. Erico mold number XBM‐

2Q2Q or approved equivalent. (250# weld)

O3 23 8 Each ‐ X Yes Exothermic Tee – 4/0 Cu to #4 rebar. Erico mold number RJC‐522Q or equivalent. (150# weld)

O3 24 8 Each ‐ X ‐ Grounding Plate ‐ 4 hole NEMA pad for concrete embedment, with

15’ 4/0 Cu pigtail. Erico part number B530D2Q180.

O3 25 27 Each ‐ X Yes Ground Rod ‐ 3/4" X 10', 10 mil stainless steel with threaded ends.

ERICO part number 683400SS.

O3 26 18 Each ‐ X Yes Ground Rod Threaded Coupler ‐ 3/4" UNC threads. ERICO part number CR34SS.

O3 27 10 Each ‐ X Yes Ground Rod Driving Stud ‐ 3/4" UNC threads. ERICO part number

DS34.

O3 30 1 Lot ‐ X Yes Miscellaneous grounding accessories, brushes, lighters, mold handles, wear plates, rebar sleeves, etc.

O3 31 1 Lot ‐ X Yes

Miscellaneous C‐crimps for grounding accessories cabinets. Burndy part numbers: YC28C28TN (4/0 to 4/0), YC28C2TN (4/0 to #2) or approved equivalent.

O3 42 14 Each ‐ X Yes

Exothermic Terminal ‐ 4/0 to offset NEMA 2‐hole lug. For breakers, and switch platform grounding. ERICO mold number LAC‐2QEG (90# weld), 1/4" x 1 1/2" lug number B‐102‐EG‐OL.

P1 1 1 Each X ‐ No

Station Control Building ‐ includes floor and internal accessories for placement on piers. Exterior dimensions: 15'8" x 32' x 12' MODCON

Job # MCP1660‐MC5613 Major Material Item

Bid Package ‐ 8/5/2025

R1 1 1 Lot X ‐ No

Battery Bank ‐ 125 Vdc nominal 150 AmpHour with 95 cells of NiCad sealed recombinant batteries. ALCAD VTX1M150‐4 (4‐6 Cells/Block).

Major Material Item

R2 1 1 Each X ‐ No

Battery Charger ‐ 25 Amp, 120 Vdc output, 240 Vac single phase input with battery eliminator filtering, AC lightning arrester, in

NEMA 1 wall mount cabinet.

SENS EnerGenius IQ2 catalog number: Q120025TL512C

Major Material Item

R3 1 1 Each X ‐ No

Battery Rack ‐ 2 step, 2 tier and spill contaiment sytem to fit with item R1/1. ALCAD Rack Catalog Number: E‐SGL 2‐17 SL2175; Eagle

Spill Containment EAGLE‐K‐24‐69

Major Material Item

R4 1 2 Each ‐ X Yes Battery Fuses Holder with box lugs. Bussmann part number

RM25200‐1CR

R4 2 2 Each X ‐ No

Indoor Enclosure – For item R4‐1, Flat Clear Cover with Latches, Type 4X

Hoffmann Catalog Number: CHJ1412HWPL2LG

Item Furnished with Building

R4 3 2 Each ‐ X Yes

Battery Fuses ‐ 125 A class RK1 for battery short circuit protection.

Bussmann part number LPN‐RK‐125SP. (Include two spare fuses.)

Questions regarding equipment erection, material callouts, etc. should be brought to the attention of the Engineer for clarification or direction. Note that the bill of materials listing is a means of establishing identification of items shown on the drawings and the qualities of the materials required. Counts and/or lengths are best estimates and should be verified prior to purchase. Discrepancies in counts and/or lengths should be brought to the attention of the Engineer for clarification and review but do not relieve the Contractor of the requirement to supply material in adequate quantities and types to complete the project.