ATT_3_-_250806_IFB_Packge_New_Sunshine_Sub_-_Station_BoM.pdf
PDF 176 KB Posted
- Attached to
- New Sunshine Substation Construction
- Solicitation number
- 2025/2026/02
- Issued by
- Quay County, New Mexico
About this file
This document is a Bill of Material for the COG New Sunshine Substation Bid Package dated 8/5/2025, detailing comprehensive equipment and material specifications for a substation construction project. The bill of materials encompasses a wide range of electrical infrastructure components, including steel structures, transformers, circuit breakers, disconnect switches, surge arresters, conductors, cables, grounding equipment, control building, battery systems, and associated accessories. The document provides extensive technical details for each item, specifying quantities, catalog numbers, manufacturer specifications, and whether the items are major material items or to be provided by others.
The bill of materials covers multiple voltage levels and system components, with items ranging from 115kV transmission-level equipment to 25kV distribution-level switches and 125VDC battery systems. Major material items include a main power transformer (15/20/25/28 MVA), alternate power transformer, station control building, battery bank (125 VDC, 150 AmpHour), battery charger, and various structural supports and foundations. The document notes that quantities and lengths are best estimates and should be verified prior to purchase, with discrepancies to be brought to the engineer's attention. The comprehensive nature of the bill suggests a complex substation project with multiple interconnected systems and equipment from various manufacturers.
View the file
Other files
Show all 20
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
COG New Sunshine Substation
Bill of Material
Bid Package ‐ 8/5/2025
A1 1 2 Each X ‐ No
115kV A‐Frame Deadend & Switch Structure ‐ Galvanized steel per steel drawings & details.
Major Material Item
A2 ‐ ‐ ‐ ‐ ‐ ‐ Not Used
A3 1 2 Each X ‐ No
115 kV Breaker Support Structure ‐ Galvanized steel per steel drawings & details.
Provided by Breaker Manufacturer
A4 ‐ ‐ ‐ ‐ ‐ ‐ Not Used
A5 1 1 Lot X ‐ No
Main Power Transformer Oil Containment Steel Support Structure & grating – Galvanized steel grating and supports per steel drawings & details.
Major Material Item
A6 1 1 Lot X ‐ No
Alternate Power Transformer Oil Containment Steel Support
Structure & Grating – Galvanized steel grating and supports per steel drawings & details.
Major Material Item
A7 1 3 Each X ‐ No
Bus Disconnect Switch Stand ‐ Galvanized steel per steel drawings & details.
Major Material Item
A8 1 1 Each X ‐ No Diag. Bus Support Structure ‐ Galvanized steel per steel drawings & details. Major Material Item
A9 1 ‐ ‐ ‐ ‐ ‐ Not Used
A10 1 1 Lot X ‐ No
Distribution Bay Support Structure ‐ 6 bays in horizontal configuration ‐ Galvanized steel per steel drawings & details.
Major Material Item
A11 ‐ ‐ ‐ ‐ ‐ ‐ Not Used
A12 1 7 Each X ‐ No Feeder Breaker Support Structure ‐ Provided by breaker vendor.
Major Material Item
A13 1 1 Each X ‐ No
Express Feeder Riser Structure (Noe Feeder) ‐ Galvanized steel per steel drawings & details.
Major Material Item
A13 2 2 Each X ‐ No
Alternate Feed Riser Structure ‐ Galvanized steel per steel drawings
& details.
Major Material Item
A13 3 4 Each X ‐ No
Distribution Feeder Riser Structure ‐ Galvanized steel per steel drawings & details.
Major Material Item
A14 1 3 Each X ‐ No
Pull Box Cover ‐ Steel, Painted Safety Yellow, per drawings and details.
Major Material Item
A15 1 5 Each X ‐ No Static Mast ‐ Galvanized steel per steel drawings & details.
Major Material Item
A16 1 7 Each X ‐ No
Switch Operator Platforms – Galvanized steel per steel drawings & details.
Major Material Item
A17 1 1 Lot X ‐ No
Control Building Support Structure & Pier Angles – Provided by building vendor.
Major Material Item
A18 1 2 Each X ‐ No Access Platforms ‐ Galvanized steel per steel drawings & details.
Major Material Item
A99 1 1 Lot X ‐ No
Anchor Bolts & Templates ‐ Galvanized and black steel per steel drawings & details. See (Drawings SS‐303 & SS‐305 for details)
Major Material Item
A10 10 25 Feet ‐ X Yes Conductor ‐1/0 ACSR, 6/1 strand "Raven"
A10 11 4 Each ‐ X Yes
1/0 ACSR Pin terminal for jumpers to PT's and Station Service
Transformer.
Burndy Catalog Number: YE25R25
A10 12 4 Each ‐ X Yes Terminal ‐ Compression type,1/0 ACSR to 2‐hole, 2" wide NEMA pad.
SEFCOR Catalog Number AL‐398‐2B or approved equivalent.
Bid Package ‐ 8/5/2025
A20 10 6 Each Insulator – 115 kV suspension type, 550 kV BIL, Y‐Clevis ‐ Y‐Clevis.
SEE T‐line BoM
A20 20 6 Each Compression Deadend – double tongue with NEMA 2 hole pads. See
T‐line BoM.
A25 10 72 Each X ‐ No Insulator ‐ 25 kV, 150 kV BIL, Cypoxy, 3" bolt circle, S&C catalog number PA‐7253R1. (Includes 2 Spares)
A38 10 N/A Feet Shield wire – 3/8” H.S.S. Rated breaking strength 10,800 lbs. See T‐ line BoM.
A38 12 4 Each
Terminal – Compression type for 4/0 Tinned Cu, to 2‐hole, 2" wide
NEMA pad. Hubbell catalog number:
VAUL‐4/0‐12BN or approved equivalent. See T‐line BoM.
A47 10 950 Feet ‐ X Yes Conductor ‐ 477 MCM ACSR, 26/7 strand “Hawk” for jumpers and bus damper wire.
A47 12 100 Each ‐ X Yes
Terminal – Compression type for 477 MCM ACSR to 2‐hole, 2" wide
NEMA pad. SEFCOR catalog number AL‐858‐2B or approved equivalent.
A47 13 24 Each ‐ X Yes
Terminal – Compression type for 477 MCM ACSR to 90 deg, 2‐hole, 2" wide NEMA pad. SEFCOR catalog number AL‐858‐2B‐90 or approved equivalent.
A47 14 94 Each ‐ X Yes
Terminal – Compression type for 477 MCM ACSR to 4‐hole, 4" wide
NEMA pad. SEFCOR catalog number AL‐858‐4B or approved equivalent.
A47 15 6 Each ‐ X Yes
Terminal – Compression type for 477 MCM ACSR to 90 degree 4‐ hole, 4" wide NEMA pad. SEFCOR catalog number AL‐858‐4B‐90 or approved equivalent.
A47 16 12 Each ‐ X Yes
Terminal – Compression type for 477 MCM ACSR to 45 degree 2‐ hole, 2" wide NEMA pad. SEFCOR catalog number AL‐858‐2B‐45 or approved equivalent.
A47 17 3 Each ‐ X Yes
Fitting – Aluminum Bolted conductor support for 477 MCM with 3" bolt circle mounting. Travis Pattern catalog number 19‐399 or approved equivalent.
A47 18 3 Each ‐ X Yes
Terminal – Bolted pass‐through terminal for 477 MCM on 4‐hole
NEMA pad spacing, tinned. SEFCOR catalog number SXR‐34‐SND or approved equivalent.
A47 24 6 Each ‐ X Yes
Terminal – Bolted type for two (2) 477 MCM ACSR conductors to 4‐ hole, 3" wide NEMA pad. Travis Pattern catalog number 11‐250 or approved equivalent.
A47 40 3 Each ‐ X Yes
Cable Spacer ‐ Bolted type for 477 MCM ACSR to 4‐hole, 4" wide
NEMA pad with 4" spacing between conductors. SEFCOR catalog number ASPC‐22‐4‐4B or approved equivalent.
A61 10 280 Feet ‐ X Yes
Bus Pipe ‐ 1" Aluminum seamless IPS tube, Schedule 40, 6063‐T6 electrical grade in 20' & 40' lengths. Alcoa catalog number
100S40YT6B or approved equivalent. See SS‐24 for bus cutting schedule.
A61 12 30 Each ‐ X Yes
Terminal – Compression type for 1” Al tubing to 2‐hole, 2" wide
NEMA pad. DMC catalog number PLK1855D16 or approved equivalent.
A61 90 60 Each ‐ ‐ ‐ Bus Elbow ‐ Field bend ninety to coordinate with terminal pad and bus tee locations as shown in the drawings.
A62 10 520 Feet ‐ X Yes
Bus Pipe ‐ 2" Aluminum seamless IPS tube, Schedule 40, 6062‐T6 electrical grade in 20' & 40' lengths. Alcoa catalog number
200S40YT6B or approved equivalent. See SS‐24 for bus cutting schedule.
A62 11
(OR AS REQ'D)
Each ‐ X Yes
Splice ‐ Compression type for 2" Al tubing to 2" Al tubing. DMC catalog number PLK1000D32 or approved equivalent. (Quantity is based on 40' bus lengths. Increase if shorter lengths are procured)
A62 12 30 Each ‐ X Yes
Terminal ‐ Compression type for 2" Al tubing to 2‐Hole, 2" wide
NEMA pad. DMC catalog number PLK1855D32 or approved equivalent
A62 14 6 Each ‐ X Yes
Terminal ‐ Compression type for 2" Al tubing to 4‐Hole, 4" wide
NEMA pad. DMC catalog number PLK1850D32B or approved equivalent
A62 19 9 Each ‐ X Yes Drive‐On Corona End Cap ‐ For 2" Al pipe bus. SEFCOR catalog number DP‐58‐AL or approved equivalent.
By Others
By Others
By Others
By Others
Bid Package ‐ 8/5/2025
A62 20 60 Each ‐ X Yes Bus Support ‐ Slip/fixed type for 3" bolt circle to 2" Al tube. SEFCOR catalog number ASTI‐58‐3 or approved equivalent.
A62 28 30 Each ‐ X Yes Tee – Compression type for 2” Al tubing to 1" Al tubing DMC catalog number PLK1500D1632E1 or approved equivalent.
A62 29 3 Each ‐ X Yes Bus Support ‐ Vertical slide support for 2" bus pipe. SEFCOR Catalog
Number: WVTSI‐58‐3
A62 90 3 Each ‐ X Yes Bus Elbow ‐ Compression 90 degree type for 2" Al tube to 2" Al tube.
DMC catalog number PLK1400D32E4 or approved equivalent
A62 94 9 Each ‐ X Yes
Tee – Compression, Straight type for 2” Al tube to 4‐hole, 4" wide
NEMA pad. DMC catalog number: PLK1100D32E2 or approved equivalent
A62 99 3 Each ‐ X Yes Bus Support – Expansion type for 3” bolt circle to 2” Al. tube. DMC catalog number PLK2700D32E1 or approved equivalent
A90 10 9 Each ‐ X No
Spline Ball Ionizer ‐ Lightning Eliminator Consultants. Furnish with
48” threaded shaft, 48” diameter, 120 points. LEC catalog number
SBI‐48‐48 with option D (3" long, 5/8‐11 threaded mounting shaft).
A96 1A 1 Lot ‐ X Yes Bolt ‐ 1/2"‐13 UNC, C651 Silicon Bronze. Various lengths as needed.
A96 2A 1 Lot ‐ X Yes Flat Washer ‐ 1‐3/8" diameter SAE standard for 1/2" fasteners, 316
Stainless Steel.
A96 3A 1 Lot ‐ X Yes
Belleville Washer ‐ for 1/2" fasteners, diameter not to exceed 1 1/4", 3800lb flatload (4000 lb load), stainless steel finish painted red. Key
Belleville part number 1250‐E‐125‐S.
A96 4A 1 Lot ‐ X Yes Nut ‐ 1/2"‐13 UNC, Silicon Bronze.
A159 10 100 Feet ‐ X Yes Conductor 1590 MCM ACSR, 45/7 strand “Lapwing” conductor.
A159 14 50 Each ‐ X Yes
Terminal – Compression type for 1590 MCM ACSR to 4‐hole, 4" wide NEMA pad. SEFCOR catalog number AL‐1506‐4B or approved equivalent.
A159 15 10 Each ‐ X Yes
Terminal – Compression type for 1590 MCM ACSR to 90 degree 4‐ hole, 4" wide NEMA pad. SEFCOR catalog number AL‐1506‐4B‐90 or approved equivalent.
A159 17 1 Each ‐ X Yes
Fitting – Aluminum Bolted conductor support for 1590 MCM with 3" bolt circle mounting. Travis Pattern catalog number 19‐403 or approved equivalent.
A159 40 3 Each ‐ X Yes Tee‐ Bolted type for 1590 MCM ACSR to 477 MCM ACSR. SEFCOR catalog number ACRCT‐491139 or approved equivalent.
A954 10 80 Feet ‐ X Yes Conductor ‐ 954 MCM ACSR, 54/7 strand “Cardinal” for jumpers and bus damper wire.
A954 12 9 Each ‐ X Yes
Terminal – Compression type for 954 MCM ACSR to 2‐hole, 2" wide
NEMA pad. SEFCOR catalog number AL‐130‐2B or approved equivalent.
A954 13 6 Each ‐ X Yes
Terminal – Compression type for 954 MCM ACSR to 90 deg, 2‐hole, 2" wide NEMA pad. SEFCOR catalog number AL‐130‐2B‐90 or approved equivalent.
A954 14 6 Each ‐ X Yes
Terminal – Compression type for 954 MCM ACSR to 4‐hole, 4" wide
NEMA pad. SEFCOR catalog number AL‐130‐4B or approved equivalent.
A954 16 3 Each ‐ X Yes
Terminal – Compression type for 954 MCM ACSR to 45 degree 2‐ hole, 2" wide NEMA pad. SEFCOR catalog number AL‐130‐2B‐45 or approved equivalent.
B15 10 2 Each X ‐ No
115 kV Group Operated Air Break Switch – 115 kV, 1200 amp, 550 kV
BIL. Center Break Vee Switch, configured for vertical mounting and
NEMA 4‐hole tinned pads. Mounting centerline height, 26 feet.
Royal catalog number AV11512STD. Major Material Item
B25 10 3 Each X ‐ No
Bus Disconnect Switch ‐ 25 kV, 150 kV BIL, vertical break 1200 amp, group operated switch S&C catalog number 135814R2‐E‐Z5
Engineering Drawing ED‐151R1
Major Material Item
Bid Package ‐ 8/5/2025
C15 10 24 Each X ‐ No
Surge Arrester ‐ Station class, polymer housed, metal oxide, 10kV rated, 8.4 kV MCOV Surge arrester with 4‐hole NEMA terminal and eyebolt grounding terminal, Spade Top, Tripod base 7.88"‐10” bolt circle. Hubbell type EVP catalog number EVP000900‐3001. Includes
Three spares Major
Material Item
C15 20 3 Each X ‐ No
Surge Arrester ‐ Station class, polymer housed, metal oxide, 10kV rated, 8.4 kV MCOV Surge arrester with 4‐hole NEMA terminal and eyebolt grounding terminal, Spade Top, Tripod base 7.88"‐10” bolt circle. Hubbell type EVP catalog number EVP000900‐3001
Major Material Item included with Transformer H10/10
C90 10 9 Each X ‐ No
Surge Arrester ‐ Station class, polymer housed, metal oxide, 90 kV rated, 74 kV MCOV Surge arrester with 4‐hole NEMA terminal and eyebolt grounding terminal, Spade Top, Tripod base 7.88"‐10” bolt circle. Hubbell type EVP catalog number EVP007400‐3001. Includes
Three spares.
Major Material Item
C90 20 3 Each X ‐ No
Surge Arrester ‐ Station class, polymer housed, metal oxide, 90 kV rated, 74 kV MCOV Surge arrester with 4‐hole NEMA terminal and eyebolt grounding terminal, Spade Top, Tripod base 7.88"‐10” bolt circle. Hubbell type EVP catalog number EVP007400‐3001
Major Material Item included with Transformer H10/10
D10 10 1 Each ‐ X Yes
Switch Stick ‐ 18’ fiberglass extendable type hook stick with
Aluminum container and PVC or neoprene liner. Hastings Tel‐O‐Pole style with NEMA disconnect head, catalog number 3118 with container 01‐3352 and mounting kit 01‐3200‐41 or approved equivalent. Contractor to field install in accessible location on station security fence with an angle on the container that places the end cap lower to allow for drainage of moisture.
D25 10 4 Each X ‐ No
Fused Disconnect Switch ‐ 25kV, 150 kV BIL, 200A with tin plated terminals and Cypoxy insulators. S&C SMD‐20 catalog number:
192223R2‐E‐Z5
Major Material Item
D25 11 2 Each X ‐ No
Fuse ‐ For item D25‐10 (Station Service XFMR), K speed, rated 6A, S&C SMU‐20, #703006. Quantity includes one extra fuse.
Major Material Item
D25 12 6 Each X ‐ No
Fuse ‐ For item D25‐10 (Bus PT's), K speed, rated 3A, S&C SMU‐20, #703003. Quantity includes one extra fuse for each switch.
Major Material Item
D25 20 30 Each X ‐ No
Disconnect Switch ‐ 35 kV, 150 kV BIL, 900 A, vee‐type, vertical mount, hookstick operated. S&C series catalog number 4873R2‐E‐
B90. Major Material Item
D25 21 15 Each X ‐ No
Disconnect Switch ‐ 35 kV, 150 kV BIL, 900 A, vee‐type, inverted mount, hookstick operated. S&C series catalog number 4893R2‐E‐
B90. Major Material Item
E1 1 2 Each X ‐ No
115 kV SF6 Dead Tank Circuit Breaker – GE Grid Solutions 3‐Ph, 145 kV rated, 650 kV BIL, 3 cycle, 1200 Amp, 40 kAIC with auxiliary contacts, two sets of 1200/5 MR CTs on 1,3,5; two sets of 1200/5 MR
CTs on 2,4,6, mild steel enclosure, 125 VDC control power, 120 VAC auxiliary power, low voltage control breakers, includes NEMA 4 hole pads. Alstom‐GE type DT1‐145FK‐40‐F1. (Alt Feed is future install, by others)
Major Material Item
Bid Package ‐ 8/5/2025
F1 1 5 Each X ‐ No
27kV Circuit Breaker ‐ ABB R‐MAG 3‐Ph, 125 kV BIL, 1200 Amp, 3.0 cycle, 25 kAIC with eight 'a' and eight 'b' auxiliary contacts, one set of 1200/5 MR CTs on each side, mild steel + NEMA 4 enclosure, 125
VDC control power, 120/240 VAC auxiliary power, knife switches, basic control and no panel. Includes NEMA 4 hole pads. ABB
Catalog Number MB22146GGCH2SBL4
Major Material Item
F1 2 2 Each X ‐ No
27kV Circuit Breaker ‐ ABB R‐MAG 3‐Ph, 125 kV BIL, 2000 Amp, 3.0 cycle, 25 kAIC with eight 'a' and eight 'b' auxiliary contacts, one set of 1200/5 MR CTs on 135, and two sets of 2000/5 MR CTs on 246, mild steel + NEMA 4 enclosure, 125 VDC control power, 120/240
VAC auxiliary power, knife switches, basic control and no panel.
Includes NEMA 4 hole pads. ABB Catalog Number
MB22246LUCH2SBL4
Major Material Item
G1 10 3 Each X ‐ No
Voltage Transformer ‐ 15.5 kV, 110 kV BIL, 7620/13200GY/120V, 63.5:1, 0.3 WXY, Ritz type VEF‐15‐09. Catalog number 121531009‐
395004 Major Material Item
G2 10 3 Each X ‐ No
Current Transformer – 15.5 kV, 110 kV BIL, 400/800:5 amps, 0.3B‐
0.9/1.8, Ritz type GIFU‐15‐03. Catalog number 111553003‐149028
Major Material Item
G2 20 12 Each X ‐ No
Current Transformer – 15.5 kV, 110 kV BIL, 200/400:5 amps, 0.3B‐
0.9/1.8, Ritz type GIFU‐15‐03. Catalog number 111553003‐149026
Major Material Item
G2 30 1 Each X ‐ No
Current Transformer – 25.5 kV, 150 kV BIL, 1000/2000:5 amps, 0.3B‐
2.0, C200/C400. Ritz Instrument type GIFU‐25‐01. Catalog number
112053001‐45931
Major Material Item
G90 10 4 Each X ‐ No Relay Panels ‐ Per Protection and Controls drawings and specifications. Major Material Item
G90 11 1 Each X ‐ No SCADA/Comm panel ‐ Per Protection and Controls drawings and specifications. Major Material Item
H10 10 1 Each X ‐ No
Main Power Transformer – 15/20/25/28 MVA, ONAN/ONAF, three phase, 60 Hz, 55/65 Degree Rise, 115 kV DELTA to 13.2/7.62 kV
Grounding Wye with LTC. WEG PEP number 150‐2400680‐2.
Major Material Item
H10 11 3 Each X ‐ No
Connector – Bushing stud to 4‐hole NEMA pad for H1, H2 and H3 transformer bushings. Hubbell HDSF‐14‐1‐D‐12‐12 TP
Item furnished with transformer
H10 12 3 Each X ‐ No
Connector – Bushing stud to 4 Hole pad for X1, X2, and X3 transformer bushings. Delta Connectors PM60C12‐1‐4N4‐E. Item furnished with Transformer
H10 13 1 Each X ‐ No Connector – Bushing stud to NEMA 4‐hole pad for X0 bushing. Delta
Connectors PM60C12‐1‐4N4‐E. Item furnished with Transformer
H10 20 1 Each X ‐ No
Alternate Power Transformer – 15/20/25/28 MVA, OA/FA/FOA, three phase, 60 Hz, 55/65 Degree Rise, 115 kV DELTA to 13.2/7.62 kV
Grounding Wye with LTC. GE Catalog number F‐961446B (Existing
Mendoza Station Unit ‐ Future Installation by others)
Major Material Item
H10 21 1 Lot X ‐ No
Alternate Power Transformer Air Terminal Chamber for installation on Item H10/20. See drawings for details. (Future Installation by others)
Major Material Item
H20 10 1 Each X ‐ No
Station Service Transformer – 25 kVA, single phase, 60 Hz, 7.967kV to 120/240V. Pole mount style with DETC.
Owner Material Item
Bid Package ‐ 8/5/2025
J50 10 n/a n/a
URD Conductor ‐ 500 MCM Al, 220 mil insulation, 15kV with jacketed concentric 1/3 neutral (overall OD = 1.72"/insulation OD = 1.39").
Okonite Catalog number 162‐23‐3093
J50 20 12 Each
Cable Terminator – 3M Quick Term type QT‐III order number 7655‐S‐
4 with 4 skirts, for jacketed concentric neutral cable, rated for 150 kV BIL. 12.25" in length, Insulation OD range 1.05" ‐ 1.80". Include two hole termination lug for 500 AL and suitable cold shrink sealing kit for jacket. (includes one complete spare)
Major Material Item
J50 21 12 Each ‐ X Yes
Cable Mounting Bracket ‐ 3M double clamp type mounting bracket for use on jacketed cables. Provide with stainless steel mounting hardware. For use with cable OD ranges from 1.45" ‐ 1.95". Catalog number MBS‐5 or approved equivalent.
J50 40 15 Each
Cable Terminator – For 500 MCM Al, underground cable, Slip‐on type rated for 25kV, 150kV BiL. G&W Part No. PAT‐1872 with adapter"K2‐G3" ‐ kit, compression connector A50860000C00 and aluminum vertical flat NEMA 4‐hole pad Part No. A5076‐192A.
(Quantity shown includes three spares)
Major Material Item
J100 10 Feet
URD Conductor ‐ 1000 MCM Al, 220 mil insulation, 15kV with jacketed concentric 1/3 neutral (overall OD = 2.16"/insulation OD =
1.77"). Okonite Catalog number 162‐23‐3099
J100 20 18 Each
Cable Terminator – 3M Quick Term type QT‐III order number 7655‐S‐
4 with 4 skirts, for jacketed concentric neutral cable, rated for 150 kV BIL. 12.25" in length, Insulation OD range 1.05" ‐ 1.80". Include two hole termination lug for 1000 AL and suitable cold shrink sealing kit for jacket. (includes one complete spare)
Major Material Item
J100 21 24 Each ‐ X Yes
Cable Mounting Bracket ‐ 3M double clamp type mounting bracket for use on jacketed cables. Provide with stainless steel mounting hardware. For use with cable OD ranges from 1.80" ‐ 2.40". Catalog number MBS‐6 or approved equivalent. Includes one complete spare
K1 2 470 Feet ‐ X Yes Cable ‐ Single conductor #2, Cu, XHHW‐2
K1 40 1400 Feet ‐ X Yes Cable ‐ Single conductor 4/0 Cu, XHHW‐2
K1 40R 40 Feet ‐ X Yes Cable ‐ Single conductor 4/0 Cu, DLO (Flexible Welding), RED
K1 40BK 40 Feet ‐ X Yes Cable ‐ Single conductor 4/0 Cu, DLO (Flexible Welding), BLACK
K2 8 1020 Feet ‐ X Yes Cable ‐ Two conductor #8, TC, XHHW‐2, E2 Color
K2 10 5900 Feet ‐ X Yes Cable ‐ Two conductor #10, TC, XHHW‐2, E2 Color
K3 1 350 Feet ‐ X Yes Cable – Three conductor #1, TC, XHHW‐2, E1 Color or numbered conductors
K3 8 270 Feet ‐ X Yes Cable – Three conductor #8, TC, XHHW‐2, E1 Color
K3 10 1750 Feet ‐ X Yes Cable ‐ Three conductor #10, TC, XHHW‐2, E1 Color
K4 10 7110 Feet ‐ X Yes Cable ‐ Four conductor #10, TC, XHHW‐2, E2 Color
K12 10 2800 Feet ‐ X Yes Cable ‐ Twelve conductor #10, TC, XHHW‐2, E2 Color, Shielded
K12 12 120 Feet ‐ X Yes Cable ‐ Twelve conductor #12, TC, XHHW‐2, E2 Color
K12 16 3480 Feet ‐ X Yes Cable ‐ Twelve conductor #16, TC, XHHW‐2, E2 Color, Shielded
K10 1 200 Feet ‐ X Yes Conduit ‐ 1" Rigid Galvanized Steel.
‐ X
K20 1 800 Feet ‐ X Yes Conduit – 2” Rigid Galvanized Steel.
K20 3 4600 Feet ‐ X Yes Conduit – 2" Schedule 40 PVC.
K20 4 130 Each ‐ X Yes Conduit – 2” PVC schedule 80, standard radius (16") sweep.
K25 1 10 Feet ‐ X Yes Conduit – 2.5” Rigid Galvanized Steel.
K25 3 80 Feet ‐ X Yes Conduit – 2.5" Schedule 40 PVC.
K25 4 2 Each ‐ X Yes Conduit – 2.5” PVC schedule 80, standard radius (30") sweep.
K40 3 920 Feet ‐ X Yes Conduit – 4" Schedule 40 PVC .
K40 5 40 Each ‐ X Yes Conduit – 4” PVC schedule 80, 48” long sweep.
Provided & Installed by Others
Provided & Installed by Others
Provided & Installed by Others
Provided & Installed by Others
Provided & Installed by Others
Bid Package ‐ 8/5/2025
K50 11 1 Each ‐ X Yes
Combination Service Entrance Device (Meter‐Main Combo) ‐
Ringless type, without bypass, 22 kA rated, with 200 amp main breaker for service disconnect. Includes 8 spaces for up to 16 circuits. NEMA 3R Enclosure, for 120/240 VAC application. Supply breakers as shown on drawing AC‐250. Include A200 Hub kit.
Schneider/ Square D catalog number QC816F200C or approved equivalent.
K50 12 1 Each Station Service Meter ‐ 120/240 Vac, 200 Amp rated form 2S.
Owner Furnished Item
K50 20 4 Each ‐ X Yes
Junction Box ‐ For use on A‐Frame structure for lighting electrical conduits, 8"x8"x4", screw cover, type 3R nVent/Hoffman Catalog Number: A8R84
K50 30 6 Each ‐ X Yes
Junction Box ‐ For use on CT/PT Connections. 16"X12"x6", NEMA 3R, Lift Off Cover nVent/Hoffman part number A16R126HCLO with
A14P12 back panel, APMK3RL016 panel mounting kit, and
AMFK3RL016 mounting bracket kit.
K60 3 1500 Feet ‐ X Yes Conduit – 6" Schedule 40 PVC
K60 5 14 Each ‐ X Yes Conduit – 6” PVC schedule 80, 60” long sweep.
K60 8 100 Feet ‐ X Yes Conduit – 6" Rigid Aluminum.
K60 9 10 Each ‐ X Yes Top Cable Support Vent ‐ 6"
Adalet Catalog Number: CV60
K60 10 10 Each ‐ X Yes Bottom Ventalator ‐ 6"
Adalet Catalog Number: BCV60
K70 0 1 Each ‐ X No Dummy Fuse ‐ Bussmann catalog number NNB‐R
K70 1 4 Each ‐ X Yes Fuse Holder Block – one fuse position and screw terminals for use with type "midget" fuses. Bussmann CHCC1DU or equivalent.
K70 2 6 Each ‐ X Yes Fuses ‐ Bussmann LP‐CC‐20 20 Amp Class CC Fuses
(Includes 3 spares)
K70 3 6 Each ‐ X Yes Ground Bar ‐ 14 AWG to 2 AWG. Minimum 7 position. Siemens
EC1GB82 or similar.
K70 4 15 Each ‐ X No Terminal Block ‐ 4‐point, shorting terminal block, GE‐27. GE Caralog number EB27B04S or approved equivalent.
K78 1 1 Lot ‐ X Yes Misc communications cables per Communications Cable Schedule on SS‐290
K80 10 22 Each ‐ X Yes
Yard Light ‐ set for 240 V, Lithonia 'D series' LED family. Six LED engines, 4000 K performance, flood type with integral slip fitter (for
2 3/8" OD pipe) and natural aluminum (gray) finish. Catalog number:
DSXF3 LED 6 P2 40K 70CRI FL MVOLT IS DNAXD
K80 11 1 Each ‐ X Yes
Dusk/Dawn Area Light ‐ Yard Light ‐ set for 120 V, Lithonia ESXF LED
Floodlight. Switchable output plus photo control. 4000 K performance, flood type with integral slip fitter (for 2 3/8" OD pipe) and standard finish with upper/bottom visor accessory
283G2KESXF5UBV DDB. Luminare Catalog number: ESXF3 ALO
SWW2 YS DDB
K90 1 1 Lot ‐ X Yes
Conduit fittings and accessories for Rigid, Aluminum, Galvanized
Steel, and PVC conduits as needed and in such variety, size and correct application as will be in accordance with neat and workmanlike installation practices.
K90 2 1 Lot ‐ X Yes
Cable Accessories ‐ Including miscellaneous wire and cable labels, Nylon insulated ring lugs, 3M Constant Force Springs for Grounding jacketed cables and any other material needed to complete the job according to the prints and in accordance with industry accepted practices.
K90 10 26 Each ‐ X Yes Signs ‐ "Warning” with graphics according to drawings – English
(includes one spare)
K90 11 26 Each ‐ X Yes Signs ‐ "Warning” with graphics according to drawings – Spanish
(includes one spare)
Provided by Others
Bid Package ‐ 8/5/2025
L1 1 8 Each ‐ X No 115 kV A‐Frame Switch Structure Foundations ‐ Complete per detail
L1‐1 & concrete specifications.
L2 ‐ ‐ ‐ ‐ Not Used
L3 1 2 Each ‐ X No 115 kV Breaker/Bus Support Foundation ‐ Complete per detail L3‐1
& concrete specifications.
L4 1 ‐ ‐ ‐ Not Used
L5 1 1 Each ‐ X No Power Transformer Oil Containment Foundation –Complete per detail L5‐1 & concrete specifications.
L6 1 1 Each ‐ X No Alternate Power Transformer Oil Containment Foundation –
Complete per detail L6‐1 & concrete specifications.
L7 1 3 Each ‐ X No Bus Disconnect Switch Stand Foundation ‐ Complete per detail L7‐1
& concrete specifications.
L8 1 1 Each ‐ X No 3‐Phase Diag. Bus Support Foundation ‐ Complete per detail L8‐1 & concrete specifications.
L9 1 ‐ ‐ ‐ ‐ ‐ Not Used
L10 1 14 Each ‐ X No Distribution Bay Support Foundation ‐ Complete per detail L10‐1 & concrete specifications.
L12 1 7 Each ‐ X No Feeder Breaker Foundation ‐ Complete per detail L12‐1 & concrete specifications.
L13 1 1 Each ‐ X No Express Feed Riser Foundation ‐ Complete per detail L13‐1 & concrete specifications.
L13 2 2 Each ‐ X No Alternate Feed Riser Foundation ‐ Complete per detail L13‐2 & concrete specifications.
L13 3 4 Each ‐ X No Distribution Feed Riser Foundation ‐ Complete per detail L13‐3 & concrete specifications.
L14 1 3 Each ‐ X No Pull Box Foundation ‐ Complete per detail L14‐1 & concrete specifications.
L15 1 5 Each ‐ X No Static Mast Foundation ‐ Complete per detail L15‐1 & concrete specifications or precast with prior approval.
L16 1 7 Each ‐ X No Switch Operator Platform Curb Sets – Complete per detail L16‐1 & concrete specifications.
L17 1 13 Each ‐ X No Control Building Pier Foundation ‐ Complete per detail L17‐1 & concrete specifications.
L18 1 2 Each ‐ X No Control Building Door Stoops ‐ Complete per detail L18‐1 & concrete specifications.
M1 1 1 Lot ‐ X No
Site Work ‐ Includes over‐excavation, eng. fill, soil removal for foundations, conduits and ground grid, recompaction, fine grading & leveling project area and application of gravel sufacing materials.
N1 1 1 Lot ‐ X No Chain Link Fence ‐ Furnish and install according to the drawings and the fence specifications.
O1 1 1500 Feet ‐ X Yes Grounding Conductor – 4/0 tinned Cu, soft drawn wire, 19 strand
O1 2 5400 Feet ‐ X Yes Grounding Conductor – 4/0 tinned Cu, soft drawn wire, 7 strand
O1 3 750 Feet ‐ X Yes Grounding Conductor – #2 solid Cu, tinned
O2 1 37 Each ‐ X Yes Ground Rod ‐ 3/4" X 10', 10 mil stainless steel. ERICO part number
683400.
O3 2 7 Each ‐ X Yes
Connector – Tinned U‐bolt type for one or two 4/0 Strand to 4" IPS gate post, SEFCOR catalog number GUR‐6414‐SND or approved equivalent.
O3 3 5 Each ‐ X Yes Connector – Tinned U‐bolt type for flexible braid to gate frame.
SEFCOR catalog number GBR‐54‐SND or approved equivalent.
O3 4 5 Each ‐ X Yes Flexible braid – Cu, tinned, 1‐1/16"x24", for grounding gates to gate posts. SEFCOR XBG76‐D‐24 or approved equivalent.
O3 5 20 Each ‐ X Yes Connector – for #2 AWG to 1‐1/4" IPS top rail. SEFCOR catalog number 1‐OC‐2548‐SND or approved equivalent.
O3 5A 4 Each ‐ X Yes Connector – for #2 AWG to 1‐1/2" IPS top rail. SEFCOR catalog number 1‐OC‐2648‐SND or approved equivalent.
Bid Package ‐ 8/5/2025
O3 6 4 Each ‐ X Yes
Connector – Tinned U‐bolt type for one or two 4/0 Strand to 6" IPS gate post, SEFCOR catalog number GUR‐6914‐SND or approved equivalent.
O3 7 6 Each ‐ X Yes Connector ‐ Tinned U‐bolt type for one 4/0 to 2" IPS fence line post, SEFCOR catalog number GUR‐5814‐SND or approved equivalent.
O3 8 1 Lot ‐ X Yes
Connector – Tinned split‐bolt for single #2 AWG to fence fabric and barbed wire. Burndy catalog number KSU23 or approved equivalent.
O3 9 9 Each ‐ X Yes
Connector – 4/0 strand To 5/8” threaded rod for spline ball grounding. SEFCOR catalog number 1‐OC‐2151, or approved equivalent.
O3 10 4 Each ‐ X Yes
Connector ‐ 4/0 strand to bolted 4‐Hole tinned NEMA Pad. For control building grounding connections. SEFCOR catalog number
FNCT‐12‐4A‐SND or approved equivalent.
O3 11 1 Lot ‐ X Yes Connector – for 4/0 strand to flat, galvanized.
SEFCOR GTC‐14 or approved equivalent.
O3 12 1 Lot ‐ X Yes Connector – for two parallel 4/0 strand, galvanized. SEFCOR GTC2‐
14 or approved equivalent.
O3 13 1 Lot ‐ X Yes Connector – for one #2 Cu solid, to one‐hole pad. SEFCOR FNCT‐12‐
1A or approved equivalent.
O3 14 8 Each ‐ X Yes
Terminal ‐ Compression for 4/0 Cu to 4" 4‐hole NEMA pad, copper.
X0 bushing connection. SEFCOR catalog number CL‐11‐4A or approved equivalent.
O3 17 8 Each ‐ X Yes Ground terminals on power transformer ‐ Anderson/Hubbell SWHD‐
050‐B2. (2 hole)
O3 18 1 Lot ‐ X Yes
Ground terminal ‐ 1 hole tinned compression for 4/0 bare copper ground wire for containment steel grounding connections. Burndy catalog number YA‐28 or approved equivalent
O3 19 1 Lot ‐ X Yes
Ground terminal ‐ 'narrow' 2 hole tinned compression for 4/0 bare tinned copper ground wire. Burndy catalog number YAZ‐28‐2N or approved equivalent
O3 20 125 Each ‐ X Yes Exothermic Tee – 4/0 Cu main to 4/0 Cu tap. Erico mold number TAC‐
2Q2Q, or approved equivalent. (150# weld)
O3 21 50 Each ‐ X Yes Exothermic Tee – 4/0 Cu to 3/4" ground rod. Erico mold number
GTC‐332Q or approved equivalent. (115# weld)
O3 22 100 Each ‐ X Yes Exothermic Cross – 4/0 Cu to 4/0 Cu. Erico mold number XBM‐
2Q2Q or approved equivalent. (250# weld)
O3 23 8 Each ‐ X Yes Exothermic Tee – 4/0 Cu to #4 rebar. Erico mold number RJC‐522Q or equivalent. (150# weld)
O3 24 8 Each ‐ X ‐ Grounding Plate ‐ 4 hole NEMA pad for concrete embedment, with
15’ 4/0 Cu pigtail. Erico part number B530D2Q180.
O3 25 27 Each ‐ X Yes Ground Rod ‐ 3/4" X 10', 10 mil stainless steel with threaded ends.
ERICO part number 683400SS.
O3 26 18 Each ‐ X Yes Ground Rod Threaded Coupler ‐ 3/4" UNC threads. ERICO part number CR34SS.
O3 27 10 Each ‐ X Yes Ground Rod Driving Stud ‐ 3/4" UNC threads. ERICO part number
DS34.
O3 30 1 Lot ‐ X Yes Miscellaneous grounding accessories, brushes, lighters, mold handles, wear plates, rebar sleeves, etc.
O3 31 1 Lot ‐ X Yes
Miscellaneous C‐crimps for grounding accessories cabinets. Burndy part numbers: YC28C28TN (4/0 to 4/0), YC28C2TN (4/0 to #2) or approved equivalent.
O3 42 14 Each ‐ X Yes
Exothermic Terminal ‐ 4/0 to offset NEMA 2‐hole lug. For breakers, and switch platform grounding. ERICO mold number LAC‐2QEG (90# weld), 1/4" x 1 1/2" lug number B‐102‐EG‐OL.
P1 1 1 Each X ‐ No
Station Control Building ‐ includes floor and internal accessories for placement on piers. Exterior dimensions: 15'8" x 32' x 12' MODCON
Job # MCP1660‐MC5613 Major Material Item
Bid Package ‐ 8/5/2025
R1 1 1 Lot X ‐ No
Battery Bank ‐ 125 Vdc nominal 150 AmpHour with 95 cells of NiCad sealed recombinant batteries. ALCAD VTX1M150‐4 (4‐6 Cells/Block).
Major Material Item
R2 1 1 Each X ‐ No
Battery Charger ‐ 25 Amp, 120 Vdc output, 240 Vac single phase input with battery eliminator filtering, AC lightning arrester, in
NEMA 1 wall mount cabinet.
SENS EnerGenius IQ2 catalog number: Q120025TL512C
Major Material Item
R3 1 1 Each X ‐ No
Battery Rack ‐ 2 step, 2 tier and spill contaiment sytem to fit with item R1/1. ALCAD Rack Catalog Number: E‐SGL 2‐17 SL2175; Eagle
Spill Containment EAGLE‐K‐24‐69
Major Material Item
R4 1 2 Each ‐ X Yes Battery Fuses Holder with box lugs. Bussmann part number
RM25200‐1CR
R4 2 2 Each X ‐ No
Indoor Enclosure – For item R4‐1, Flat Clear Cover with Latches, Type 4X
Hoffmann Catalog Number: CHJ1412HWPL2LG
Item Furnished with Building
R4 3 2 Each ‐ X Yes
Battery Fuses ‐ 125 A class RK1 for battery short circuit protection.
Bussmann part number LPN‐RK‐125SP. (Include two spare fuses.)
Questions regarding equipment erection, material callouts, etc. should be brought to the attention of the Engineer for clarification or direction. Note that the bill of materials listing is a means of establishing identification of items shown on the drawings and the qualities of the materials required. Counts and/or lengths are best estimates and should be verified prior to purchase. Discrepancies in counts and/or lengths should be brought to the attention of the Engineer for clarification and review but do not relieve the Contractor of the requirement to supply material in adequate quantities and types to complete the project.