Att 2.2 - Fort Harrison EHRM - Drawings Vol 2 Part 2 of 2.pdf

PDF 6 MB Posted

Attached to
Y1DZ--EHRM Infrastructure Upgrades Construction Fort Harrison 436-21-700
Solicitation number
36C77623B0001
Issued by

About this file

This federal contract solicitation seeks construction services for infrastructure upgrades at the Fort Harrison VA Medical Center in Montana. The scope of work includes architectural, structural, electrical, HVAC, plumbing, data communication, and civil site upgrades across multiple buildings. Specific upgrades involve electrical panels and distribution; building automation systems; fire suppression and alarm systems; and physical security systems. Bidders must be prepared to complete demolition, new construction, and renovation work. The contract also involves asbestos and lead paint abatement, as well as firestopping and caulking for wall and floor penetrations. The solicitation does not specify response or award dates. Pricing terms and set-asides are also unspecified. The Department of Veterans Affairs Technology Acquisition Center in Austin is the contracting agency.

View the file

Other files

File Type Posted
DBA Wage Rates - Lewis and Clark County - 01-20-23.pdf PDF
Tech Questions Tracker - Fort Harrison - Responses 1-23-23.pdf PDF
36C77623B0001 0006.pdf PDF
36C77623B0001 0005.pdf PDF
DBA Wage Rates - Lewis and Clark County - 01-13-23.pdf PDF
DBA Wage Rates - Lewis and Clark County - 01-06-23.pdf PDF
36C77623B0001 0004.pdf PDF
Tech Questions Tracker - Fort Harrison - Responses 1-10-23.pdf PDF
Limitations on Subcontracting - 852.219-75.docx DOCX document
DBA Wage Rates - Lewis and Clark County - 12-09-22.pdf PDF
Site Visit Sign-In Sheet - Fort Harrison EHRM - 12-12-2022.pdf PDF
36C77623B0001 0003.pdf PDF
36C77623B0001 0002.pdf PDF
36C77623B0001 0001.pdf PDF
Site Visit Sign-In Sheet - Fort Harrison EHRM - 11-30-2022.pdf PDF
Att 1.3 - Fort Harrison EHRM - Drawings Vol 1 Part 3 of 5.pdf PDF
Att 5 - Fort Harrison EHRM - Specification Appendix A.pdf PDF
Att 6 - Fort Harrison EHRM - Specification Appendix B.pdf PDF
Contractor Safety and Environmental Record.docx DOCX document
Limitations on Subcontracting.docx DOCX document
Att 1.1 - Fort Harrison EHRM - Drawings Vol 1 Part 1 of 5.pdf PDF
Att 1.5 - Fort Harrison EHRM - Drawings Vol 1 Part 5 of 5.pdf PDF
Att 7 - Fort Harrison EHRM - Narrative.pdf PDF
Att 2.1 - Fort Harrison EHRM - Drawings Vol 2 Part 1 of 2.pdf PDF
Fort Harrison - IFB 36C77623B0001 - 11-16-22.pdf PDF
Att 8 - Fort Harrison EHRM - Submittal Register.xlsx XLSX spreadsheet
Att 1.4 - Fort Harrison EHRM - Drawings Vol 1 Part 4 of 5.pdf PDF
DBA Wage Rates - Lewis and Clark County - 09-09-22.pdf PDF
Att 3 - Fort Harrison EHRM - Specification Vol 1.pdf PDF
Brand Name Justification - Fort Harrison.pdf PDF
Att 4 - Fort Harrison EHRM - Specification Vol 2.pdf PDF
VHA Supp Contract Reqs COVID-19 - 12-14-21.pdf PDF
Att 1.2 - Fort Harrison EHRM - Drawings Vol 1 Part 2 of 5.pdf PDF
Att 9 - Infrastructure Standard for Telecom Spaces v3.1.pdf PDF
436-21-700 - Ft Harrison EHRM - Scope of Work 9-21-2022.pdf PDF
Show all 35

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

J

169-ED-011

169-ED-011

169-ED-011

ATS '1'

ATS '2'

SWITCHBOARD 'MDB'

PANEL 'LEM'PANEL 'MECH 1 SEC 1'

PANEL 'MECH 1 SEC 2'

PANEL 'L1A'

+24"

SR

LEM 24

LEM 20,22

SR

SR +48"

+24"

+24"

RACK

MOUNTED

+9' AFF

+9' AFF

2'X4' PENDANT

2 LAMP, T8,

TYP OF 2

COOLING UNIT 2

ACCESS CONTROL

DOOR CONTROL POWER

3TYP OF 2

1'X4', 2 LAMP, T8

1'X4'

2 LAMP, T8

+8' AFF

PROJECT KEY PLAN

VA MEDICAL CENTER

FORT HARRISON, MT

NORTH

U.S. Department of Veterans Affairs

PROJECT NUMBER

BUILDING NUMBER

DRAWING NUMBER

PROJECT TITLE

LOCATION

ISSUE DATE CHECKED BY DRAWN BY

DRAWING TITLE

APPROVED:

VA FORM 08 - 6231

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PHASE

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

FLS

PROGRAM

CONTRACTING

ACTIVITY

CENTRAL (PCAC)

JEREMY A. MAXIE

5/18/2022

EE-113847

B

IM

/2

V A

M e d ic a l C e n te r

F t H a rr is o n

M T

/E S

E R

IE

S

B

L D

G r2

.r v t

/1

/2

:3

:0

P

M

169-ED-011

ELECTRICAL DEMOLITION PLAN -

BLDG 169GDM

1000 W STEUBEN ST. UNIT 3

BINGEN, WA 98605

541.436.4723

ADAM GOODIN, PE

EHRM INFRASTRUCTURE

UPGRADES

FORT HARRISON, MONTANA

436-21-700

BLDG 169

Project Director

CSZJAM05/20/2022

100% CONSTRUCTION

DOCUMENTS

A/E:

FULLY SPRINKLERED

GENERAL NOTES:

A. CONTRACTOR SHALL COORDINATE ALL OUTAGES WITH THE COR PRIOR

TO BEGINNING WORK. GREAT CARE SHALL BE TAKEN TO MINIMIZE

OUTAGE DURATION TO SHORTEST EXTENT POSSIBLE. NO DEMOLITION

SHALL OCCUR ON THE UPS SYSTEM, LIFE SAFETY SYSTEM,

TELECOMMUNICATIONS SYSTEM, OR ANY OTHER CRITICAL SYSTEM UNTIL

THE NEW/REPLACEMENT SYSTEMS ARE IN PLACE AND READY FOR

SWITCHOVER.

B. THE INFORMATION SHOWN ON THIS DRAWING IS TAKEN FROM AS-BUILT

DRAWINGS AND A NON-DESTRUCTIVE WALK THROUGH OF THE FACILITY.

THERE IS NO WARRANTY OR GUARANTEE AS TO THE ACCURACY OF THE

INFORMATION SHOWN HERE-IN. THE CONTRACTOR SHALL FIELD VERIFY

ALL ITEMS SCHEDULED FOR DEMOLITION PRIOR TO START OF WORK.

C. THE OWNER SHALL HAVE FIRST RIGHT OF REFUSAL ON ALL SALVAGEABLE

MATERIALS. THE CONTRACTOR SHALL DELIVER SALVAGED MATERIALS TO

A WAREHOUSE AS DIRECTED BY THE OWNER. THE CONTRACTOR SHALL

DISPOSE OF, OFF SITE, ALL UNWANTED MATERIALS.

D. DASHED OR DOTTED LINES INDICATE ITEMS TO BE REMOVED. SOLID LINES

INDICATE EXISTING ITEMS TO REMAIN.

E. COORDINATE WITH THE OTHER DISCIPLINE DRAWINGS FOR AREAS OF

DEMOLITION AND NEW WORK. PROVIDE MINOR RELOCATION OF LIGHT

FIXTURES AND DEVICES TO ACCOMMODATE NEW MECHANICAL AND

TELECOM EQUIPMENT LOCATIONS.

F. FOR WALL/CEILINGS SCHEDULED TO BE DEMOLISHED, DEMOLISH ALL

CONDUIT, WIRE, DEVICES, BOXES, ETC. BACK TO THE EXTENT PRACTICAL

TO ACCOMODATE DEMOLITION. RELOCATE EXISTING LIGHT FIXTURES,

DEVICES, CONDUIT, AND WIRE AS REQUIRED. PROVIDE EXTENSION OF

CONDUIT AND WIRE AS REQUIRED TO ACCOMMODATE RELOCATED ITEMS.

G. LIGHTING AND RECEPTACLES SHALL REMAIN IN EXISTING TELECOM

ROOMS. NO DEMOLITION UNLESS OTHERWISE NOTED.

SHEET NOTES:

1. DEMOLISH SWITCHES, LIGHTING, AND RECEPTACLES IN ROOM. DEMOLISH

CIRCUITS TO UPSTREAM JUNCTION BOX TO ALLOW FOR NEW CIRCUITING.

UPDATE PANELBOARD CIRCUIT DIRECTORY TO REFLECT CHANGES.

2. DEMOLISH MECHANICAL EQUIPMENT CIRCUITS TO UPSTREAM JUNCTION

BOX. UPDATE PANELBOARD CIRCUIT DIRECTORY TO REFLECT CHANGES.

3. DEMOLISH ELECTRICAL EQUIPMENT AND CIRCUITS TO UPSTREAM

JUNCTION BOX. UPDATE PANELBOARD CIRCUIT DIRECTORY TO REFLECT

CHANGES.

3/32" = 1'-0"1 ELECTRICAL DEMOLITION PLAN - BLDG 169 FIRST FLOOR

1/2" = 1'-0"3 ENLARGED ROOM - 164 ELECTRICAL DEMOLITION

1/2" = 1'-0"2 ENLARGED ROOM - 224 ELECTRICAL DEMOLITION

1/2" = 1'-0"4 ENLARGED ROOM - 173A ELECTRICAL DEMOLITION

NORTH

NORTH

NORTH

NORTH

Revisions: Date:

CR

J

4" CONDUIT STUB-UPS

2'x2', 2 LAMP, T8

COOLING UNIT

+84"

TE

78 SF

ACCESS CONTROL

DOOR CONTROL POWER

+60"

WH1 SECTION 1-17WH1 SECTION 1-15

170-ED-011

TE

OFFICE

RESTROOM

JANITOR

SHIPPING

RECEIVING

WAREHOUSE

PHARMACY

CARE

DOCK

PANEL 'WH1

SECTION 2'

PANEL 'WH1

SECTION 1'

CONDENSING UNIT

PROJECT KEY PLAN

VA MEDICAL CENTER

FORT HARRISON, MT

NORTH

U.S. Department of Veterans Affairs

PROJECT NUMBER

BUILDING NUMBER

DRAWING NUMBER

PROJECT TITLE

LOCATION

ISSUE DATE CHECKED BY DRAWN BY

DRAWING TITLE

APPROVED:

VA FORM 08 - 6231

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PHASE

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

FLS

PROGRAM

CONTRACTING

ACTIVITY

CENTRAL (PCAC)

JEREMY A. MAXIE

5/18/2022

EE-113847

B

IM

/2

V A

M e d ic a l C e n te r

F t H a rr is o n

M T

/E S

E R

IE

S

B

L D

G r2

.r v t

/1

/2

:0

:2

P

M

170-ED-011

ELECTRICAL DEMOLITION PLAN -

BLDG 170GDM

1000 W STEUBEN ST. UNIT 3

BINGEN, WA 98605

541.436.4723

ADAM GOODIN, PE

EHRM INFRASTRUCTURE

UPGRADES

FORT HARRISON, MONTANA

436-21-700

BLDG 170

Project Director

CSZJAM05/20/2022

100% CONSTRUCTION

DOCUMENTS

A/E:

FULLY SPRINKLERED

GENERAL NOTES:

A. CONTRACTOR SHALL COORDINATE ALL OUTAGES WITH THE COR PRIOR

TO BEGINNING WORK. GREAT CARE SHALL BE TAKEN TO MINIMIZE

OUTAGE DURATION TO SHORTEST EXTENT POSSIBLE. NO DEMOLITION

SHALL OCCUR ON THE UPS SYSTEM, LIFE SAFETY SYSTEM,

TELECOMMUNICATIONS SYSTEM, OR ANY OTHER CRITICAL SYSTEM UNTIL

THE NEW/REPLACEMENT SYSTEMS ARE IN PLACE AND READY FOR

SWITCHOVER.

B. THE INFORMATION SHOWN ON THIS DRAWING IS TAKEN FROM AS-BUILT

DRAWINGS AND A NON-DESTRUCTIVE WALK THROUGH OF THE FACILITY.

THERE IS NO WARRANTY OR GUARANTEE AS TO THE ACCURACY OF THE

INFORMATION SHOWN HERE-IN. THE CONTRACTOR SHALL FIELD VERIFY

ALL ITEMS SCHEDULED FOR DEMOLITION PRIOR TO START OF WORK.

C. THE OWNER SHALL HAVE FIRST RIGHT OF REFUSAL ON ALL SALVAGEABLE

MATERIALS. THE CONTRACTOR SHALL DELIVER SALVAGED MATERIALS TO

A WAREHOUSE AS DIRECTED BY THE OWNER. THE CONTRACTOR SHALL

DISPOSE OF, OFF SITE, ALL UNWANTED MATERIALS.

D. DASHED OR DOTTED LINES INDICATE ITEMS TO BE REMOVED. SOLID LINES

INDICATE EXISTING ITEMS TO REMAIN.

E. COORDINATE WITH THE OTHER DISCIPLINE DRAWINGS FOR AREAS OF

DEMOLITION AND NEW WORK. PROVIDE MINOR RELOCATION OF LIGHT

FIXTURES AND DEVICES TO ACCOMMODATE NEW MECHANICAL AND

TELECOM EQUIPMENT LOCATIONS.

F. FOR WALL/CEILINGS SCHEDULED TO BE DEMOLISHED, DEMOLISH ALL

CONDUIT, WIRE, DEVICES, BOXES, ETC. BACK TO THE EXTENT PRACTICAL

TO ACCOMODATE DEMOLITION. RELOCATE EXISTING LIGHT FIXTURES,

DEVICES, CONDUIT, AND WIRE AS REQUIRED. PROVIDE EXTENSION OF

CONDUIT AND WIRE AS REQUIRED TO ACCOMMODATE RELOCATED ITEMS.

G. FOR THE RENOVATED TELECOMMUNICATIONS ROOMS WITH NEW

PAINTED PLYWOOD WALLS, CONTRACTOR SHALL DISCONNECT AND

TEMPORARILY REMOVE ALL ELECTRICAL DEVICES, BOXES, CONDUIT, AND

WIRE TO ALLOW FOR PLYWOOD INSTALLATION. REINSTALL ALL DEVICES

BACK IN SAME LOCATIONS AND PROVIDE BOX EXTENSIONS, CIRCUIT

EXTENSIONS, ETC. AS REQUIRED TO ACCOMMODATE RENOVATION.

H. RECEPTACLES SHALL REMAIN IN EXISTING TELECOM ROOMS. NO

DEMOLITION UNLESS OTHERWISE NOTED.

SHEET NOTES:

1. DEMOLISH SWITCHES AND LIGHTING IN ROOM. SALVAGE CIRCUITS FOR

EXTENSION TO NEW SWITCHING AND LIGHTING IN ROOM.

2. SALVAGE MECHANICAL EQUIPMENT CIRCUIT FOR EXTENSION TO NEW

EQUIPMENT IN NEW LOCATION.

1/2" = 1'-0"2 ENLARGED ROOM - 103 ELECTRICAL DEMOLITION

1/8" = 1'-0"1 ELECTRICAL DEMOLITION PLAN - BLDG 170 FIRST FLOOR

NORTH NORTH

PANEL 'B'

PANEL 'A'

TRANSFER

SWITCH

MDP

171-ED-011

PROJECT KEY PLAN

VA MEDICAL CENTER

FORT HARRISON, MT

NORTH

6" DIA SURFACE

MTD INCANDESCENT

U.S. Department of Veterans Affairs

PROJECT NUMBER

BUILDING NUMBER

DRAWING NUMBER

PROJECT TITLE

LOCATION

ISSUE DATE CHECKED BY DRAWN BY

DRAWING TITLE

APPROVED:

VA FORM 08 - 6231

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PHASE

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

FLS

PROGRAM

CONTRACTING

ACTIVITY

CENTRAL (PCAC)

JEREMY A. MAXIE

5/18/2022

EE-113847

B

IM

/2

V A

M e d ic a l C e n te r

F t H a rr is o n

M T

/E S

E R

IE

S

B

L D

G r2

.r v t

/1

/2

:4

:1

P

M

171-ED-011

ELECTRICAL DEMOLITION PLAN -

BLDG 171 FIRST FLOORGDM

1000 W STEUBEN ST. UNIT 3

BINGEN, WA 98605

541.436.4723

ADAM GOODIN, PE

EHRM INFRASTRUCTURE

UPGRADES

FORT HARRISON, MONTANA

436-21-700

BLDG 171

Project Director

CSZJAM05/20/2022

100% CONSTRUCTION

DOCUMENTS

A/E:

FULLY SPRINKLERED

1/4" = 1'-0"1 ELECTRICAL DEMOLITION PLAN - BLDG 171 FIRST FLOOR

GENERAL NOTES:

A. CONTRACTOR SHALL COORDINATE ALL OUTAGES WITH THE COR PRIOR

TO BEGINNING WORK. GREAT CARE SHALL BE TAKEN TO MINIMIZE

OUTAGE DURATION TO SHORTEST EXTENT POSSIBLE. NO DEMOLITION

SHALL OCCUR ON THE UPS SYSTEM, LIFE SAFETY SYSTEM,

TELECOMMUNICATIONS SYSTEM, OR ANY OTHER CRITICAL SYSTEM UNTIL

THE NEW/REPLACEMENT SYSTEMS ARE IN PLACE AND READY FOR

SWITCHOVER.

B. THE INFORMATION SHOWN ON THIS DRAWING IS TAKEN FROM AS-BUILT

DRAWINGS AND A NON-DESTRUCTIVE WALK THROUGH OF THE FACILITY.

THERE IS NO WARRANTY OR GUARANTEE AS TO THE ACCURACY OF THE

INFORMATION SHOWN HERE-IN. THE CONTRACTOR SHALL FIELD VERIFY

ALL ITEMS SCHEDULED FOR DEMOLITION PRIOR TO START OF WORK.

C. THE OWNER SHALL HAVE FIRST RIGHT OF REFUSAL ON ALL SALVAGEABLE

MATERIALS. THE CONTRACTOR SHALL DELIVER SALVAGED MATERIALS TO

A WAREHOUSE AS DIRECTED BY THE OWNER. THE CONTRACTOR SHALL

DISPOSE OF, OFF SITE, ALL UNWANTED MATERIALS.

D. DASHED OR DOTTED LINES INDICATE ITEMS TO BE REMOVED. SOLID LINES

INDICATE EXISTING ITEMS TO REMAIN.

E. COORDINATE WITH THE OTHER DISCIPLINE DRAWINGS FOR AREAS OF

DEMOLITION AND NEW WORK. PROVIDE MINOR RELOCATION OF LIGHT

FIXTURES AND DEVICES TO ACCOMMODATE NEW MECHANICAL AND

TELECOM EQUIPMENT LOCATIONS.

F. FOR WALL/CEILINGS SCHEDULED TO BE DEMOLISHED, DEMOLISH ALL

CONDUIT, WIRE, DEVICES, BOXES, ETC. BACK TO THE EXTENT PRACTICAL

TO ACCOMODATE DEMOLITION. RELOCATE EXISTING LIGHT FIXTURES,

DEVICES, CONDUIT, AND WIRE AS REQUIRED. PROVIDE EXTENSION OF

CONDUIT AND WIRE AS REQUIRED TO ACCOMMODATE RELOCATED ITEMS.

NORTH

1/2" = 1'-0"2 ENLARGED ROOM - ELECTRICAL DEMOLITION

NORTH

SHEET NOTES:

1. DEMOLISH SWITCHES, LIGHTING, AND RECEPTACLES IN ROOM. DEMOLISH

CIRCUITS TO UPSTREAM JUNCTION BOX TO ALLOW FOR NEW CIRCUITING.

UPDATE PANELBOARD CIRCUIT DIRECTORY TO REFLECT CHANGES.

EHED

CR

DC

K

PLAN VIEW

SECURED SIDE

UNSECURED SIDE

44"

ELEVATION VIEW

ROUTE CABLE FROM BOX BACK TO

ACCESS CONTROL PANEL. CABLE

PATHWAY SHALL BE J-HOOKS THROUGH

ACCESSIBLE CEILING AREAS AND IN

CONDUIT IN AREAS WITH INACCESSIBLE

CEILINGS. SEE SPECIFICATIONS FOR

ADDITIONAL ROUTING REQUIREMENTS.

INSTALL 1-GANG CUT-IN BOX FOR CARD

READER FLUSH MOUNT ROUGH-IN.

MOUNT CARD READER ON WALL ON

UNSECURED SIDE OF DOOR, AS SHOWN

ON PLANS. MOUNT FLUSH IN WALL. CUT

AND PATCH WALL AS REQUIRED.

CONTINUE UP TO READER CONTROLLER

JUNCTION BOX ABOVE DOOR. WHERE

NOTED IN SCHEDULE, PROVIDE MULLION

CARD READER.

ALL CONDUIT/WIRE SHALL BE

CONCEALED IN WALLS OR ABOVE

ACCESSIBLE CEILING AS MUCH AS

POSSIBLE.

ACCESS CONTROL JUNCTION BOX

INSTALLED CONCEALED WITHIN

ACCESSIBLE CEILING. WHERE CEILING

IS INACCESSIBLE, MOUNT BOX ON WALL

WITHIN NEAREST STORAGE ROOM,

JANITOR CLOSET, MECHANICAL ROOM,

ETC. JUNCTION BOXES SHALL NOT BE

INSTALLED ON WALLS WITHIN PUBLIC

SPACES.

NEW RECESSED DOOR CONTACT.

ELECTRIC KEY SWITCH ON THE

INSIDE OF THE BUILDING.

NEW ELECTRIC HINGE.

NEW ELECTRIFIED EXIT DEVICE

WITH LATCHBOLT MONITORING AND

REQUEST-TO-EXIT SWITCH.

U.S. Department of Veterans Affairs

PROJECT NUMBER

BUILDING NUMBER

DRAWING NUMBER

PROJECT TITLE

LOCATION

ISSUE DATE CHECKED BY DRAWN BY

DRAWING TITLE

APPROVED:

VA FORM 08 - 6231

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PHASE

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

FLS

PROGRAM

CONTRACTING

ACTIVITY

CENTRAL (PCAC)

JEREMY A. MAXIE

5/18/2022

EE-113847

B

IM

/2

V

A M e d ic a l C e n te r

F t H a rr is o n M

T /E

S E

R

IE

S G

E N

E R

A L I N

F O r2

.r v t

/1

/2

:5

:2

P

M

EK-001

POWER AND ELEVATIONS AND

DETAILSGDM

1000 W STEUBEN ST. UNIT 3

BINGEN, WA 98605

541.436.4723

ADAM GOODIN, PE

EHRM INFRASTRUCTURE

UPGRADES

FORT HARRISON, MONTANA

436-21-700

GEN INFO

Project Director

CSZJAM05/20/2022

100% CONSTRUCTION

DOCUMENTS

A/E:

FULLY SPRINKLERED

NOT TO SCALE1 CONTROLLED DOOR - SINGLE DOOR, ELECTRIFIED EXIT DEVICE

NOT TO SCALE2 TYPICAL POWER ELEVATION AND SCHEMATIC FOR A ONE RACK TR

NOT TO SCALE3 TYPICAL POWER ELEVATION AND SCHEMATIC FOR A TWO RACK TR

NOT TO SCALE4 TYPICAL POWER ELEVATION AND SCHEMATIC FOR A THREE RACK TR

100-4

60-4

60-4

60-4

60-4

100-4

100-4

100-4

100-4

400-4

400-4

1600-4

200-4

400-4

60-4

60-4

60-4

100-4

150-4V 100-4V

400-4N

400-4N

1000-4V

1000-4V

1000-4V

175-4

100-4

125-4

100-4

400-4N

400-4N

100-4

125-4

200-4V400-4V

60-4V

60-4V

1000-4V 2500-4

100-4N

800-4

60-4

100-4

1200-4

800-4

60-4

800-4

1200-4

400-4

150-4

400-4N

200-4

100-4

60-4V

100-4V

200-4V

150-4V

400-4V

1600-4

2500-4

175-4

125-4

1000-4V

100-4N

NEW

PANEL

'141-NB-T1'

1600/3

100/3

60/3

NEW

PANEL

'141-N1-T1'

60/3

NEW

PANEL

'141-N2-T1'

150/3

NEW

PANEL

'141-N3-T1'

60/3

TRANSFORMER 141

500KVA,

12470:120/208V, 3Ø, 4W

E

400/3

PRIORITY #2 ATS

E

TO GENERATOR

SYSTEM

NEW

PANEL

'141-EQB-T1'

200/3

100/3

NEW

PANEL

'141-EQ1-T1'

100/3

NEW

PANEL

'141-EQ2-T1'

100/3

NEW

PANEL

'141-EQ3-T1'

100/3

4TYP

EXISTING

'PNL #141 DPL', 400A

120/208V,3Ø,4W

EXISTING

'141-SWBD-MDP', 1600A,

120/208V,3Ø,4-WIRE

TO EXISTING PRIMARY

DISTRIBUTION SYSTEM

400/3

175/3

100/3

125/3

100/3

TO EXISTING

GENERATOR

NEW

PANEL

'154-EQ4-T1'

NEW

PANEL

'154-EQ3-T1'

NEW

PANEL

'154-EQ2-T1'

NEW

PANEL

'154-EQ1-T1'

150/3

'154-SWBP1', 2500A,

120/208V, 3Ø, 4-WIRE

EXISTING

100/3

60/3

60/3

60/3

XFMR 154

750KVA, 120/208V, 3Ø, 4-WIRE

NEW

PANEL

'154-N4-T1'

NEW

PANEL

'154-N3-T1'

NEW

PANEL

'154-N2-T1'

NEW

PANEL

'154-N1-T1'

2500/3

100/3

60/3

60/3

NEW

PANEL

'154A-N1-T1'

NEW

PANEL

'154A-NB-T1'

3 TYP

200/3

125/3

100/3

NEW

PANEL

'154A-EQ1-T1'

NEW

PANEL

'154A-EQB-T1'

TO EXISTING PRIMARY

DISTRIBUTION SYSTEM

4TYP

'154GSBD', 1200A,

120/208V, 3Ø, 4-WIRE

EXISTING

1000/3

1000A, NEW 'ATS-TSTR'

1000/3

'154-DP-TR1', 1000A

120/208V, 3Ø, 4-WIRE

400/3

NEW 100KVA

UPS

'UPS-B' BLDG

154 RM B-13A

NEW

PANEL

'UPS-B'

PM

NEW 100KVA

UPS

'UPS-A' BLDG

154 RM B-13A

NEW

PANEL

'UPS-A'

PM

E

ST

ST

R

400/3

1000/3

NEW

'ATS-TSTR'

BREAKER

100/3

EXISTING

PANEL

'B1A-2'

NEW

PANEL

'169-N1-T1'

1200/3 60/3

800/3

EXISTING

'SWITCHBOARD MDB', 1200A,

120/208V, 3Ø, 4-WIRE

800/3 100/3

NEW

PANEL

'169-EQ1-T1'

TO GENERATOR

EXISTING

'MECH 1-SEC 1', 800A,

120/208V, 3Ø, 4-WIRE

ATS '1'

TO EXISTING SERVICE

TRANSFORMER

E

1"C, 3#6, 1#4 NEUTRAL, 1#10 GND

(2) 3.5"C, 4#500 KCMIL, 1#1/0 GND

FEEDER SCHEDULE

3 PHASE COPPER CONDUCTORS, NEUTRAL

AND GROUND (TAG #100-4, FOR EXAMPLE)

TAG

(4) 3.5"C, 4#350 KCMIL, 1#3/0 GND

CONDUCTOR AMPS BREAKER SIZE

760A 800A

55A 60A

1240A 1200A

400A 400A (2) 2"C, 4#3/0, 1#3 GND

150A 150A 2"C, 3#1/0, 1#2/0 NEUTRAL, 1#6 GND

380A 400A 4"C, 3#500KCMIL, 2#500KCMIL NEUTRAL, 1#3 GND

200A 200A 2"C, 3#3/0, 1#4/0 NEUTRAL, 1#6 GND

1.25"C, 3#2, 1#1 NEUTRAL, 1#8 GND95A 100A

1.25"C, 3#4, 1#3 NEUTRAL, 1#8 GND70A 60A

2"C, 3#3/0,1#4/0 NEUTRAL, 1#2 GND200A 100A

760A 200A (2) 3.5"C, 3#500KCMIL, 1#600KCMIL NEUTRAL, 1#3/0 GND

510A 150A (2) 2.5"C, 3#250KCMIL, 1#300KCMIL NEUTRAL, 1#1/0 GND

460A 400A (2) 2.5"C, 3#250KCMIL, 1#300KCMIL NEUTRAL, 1#2 GND

(5) 3"C, 4#400 KCMIL, 1#4/0 GND1675A 1600A

(6) 5"C, 4#600 KCMIL, 1#350KCMIL GND2500A 2500A

175A 175A 2"C, 3#2/0, 1#3/0 NEUTRAL, 1#6 GND

130A 125A 1.5"C, 3#1, 1#1/0 NEUTRAL, 1#6 GND

(4) 3.5"C, 3#500 KCMIL, 1#600KCMIL NEUTRAL, 1#350KCMIL GND1520A 1000A

2"C, 3#2/0, 1#3/0 NEUTRAL, 1#4 GND175A 100A

U.S. Department of Veterans Affairs

PROJECT NUMBER

BUILDING NUMBER

DRAWING NUMBER

PROJECT TITLE

LOCATION

ISSUE DATE CHECKED BY DRAWN BY

DRAWING TITLE

APPROVED:

VA FORM 08 - 6231

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PHASE

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

FLS

PROGRAM

CONTRACTING

ACTIVITY

CENTRAL (PCAC)

JEREMY A. MAXIE

5/18/2022

EE-113847

B

IM

/2

V

A M e d ic a l C e n te r

F t H a rr is o n M

T /E

S E

R

IE

S G

E N

E R

A L I N

F O r2

.r v t

/1

/2

:5

:2

P

M

EK-002

POWER ONE-LINE DIAGRAMS

GDM

1000 W STEUBEN ST. UNIT 3

BINGEN, WA 98605

541.436.4723

ADAM GOODIN, PE

EHRM INFRASTRUCTURE

UPGRADES

FORT HARRISON, MONTANA

436-21-700

GEN INFO

Project Director

CSZJAM05/20/2022

100% CONSTRUCTION

DOCUMENTS

A/E:

FULLY SPRINKLERED

NOT TO SCALE1 PARTIAL ONE-LINE DIAGRAM BUILDING 141

12" = 1'-0"2 PARTIAL ONE-LINE DIAGRAM BUILDING 154

12" = 1'-0"3 PARTIAL ONE-LINE DIAGRAM BUILDING 169

SHEET NOTES:

1. INSTALL NEW CIRCUIT BREAKER IN SPACE AVAILABLE IN THE EXISTING

PANEL. THE EXISTING PANEL IS A SQUARE D TYPE QED, 1600A, 120/208V,

3Ø, 4 WIRE WITH MAIN LUGS ONLY. THE NEW CIRCUIT BREAKERS SHALL

BE COMPATIBLE WITH AND LISTED FOR USE IN THE EXISTING PANEL AND

SHALL BE HAVE A MINIMUM SHORT CIRCUIT AIC RATING TO MATCH THE

LOWEST RATED EXISTING DEVICE IN THE PANEL, WHICH EVER IS LARGER.

2. INSTALL NEW CIRCUIT BREAKER IN SPACE AVAILABLE IN THE EXISTING

PANEL. THE EXISTING PANEL IS A SQUARE D TYPE I-LINE, 600A, 120/208V,

3Ø, 4 WIRE WITH MAIN LUGS ONLY. THE NEW CIRCUIT BREAKERS SHALL

BE COMPATIBLE WITH AND LISTED FOR USE IN THE EXISTING PANEL AND

SHALL BE HAVE A MINIMUM SHORT CIRCUIT AIC RATING TO MATCH THE

LOWEST RATED EXISTING DEVICE IN THE PANEL, WHICH EVER IS LARGER.

3. INSTALL NEW CIRCUIT BREAKER IN SPACE AVAILABLE IN THE EXISTING

PANEL. THE EXISTING PANEL IS A SQUARE D TYPE QED-6, 2500A, 120/208V,

3Ø, 4 WIRE WITH MAIN LUGS ONLY. THE NEW CIRCUIT BREAKERS SHALL

BE COMPATIBLE WITH AND LISTED FOR USE IN THE EXISTING PANEL AND

SHALL BE HAVE A MINIMUM SHORT CIRCUIT AIC RATING TO MATCH THE

LOWEST RATED EXISTING DEVICE IN THE PANEL, WHICH EVER IS LARGER.

4. TAP FEEDER IN ACCORDANCE WITH NEC 240.21(B)(2).

5. INSTALL NEW CIRCUIT BREAKER IN SPACE AVAILABLE IN THE EXISTING

SWITCHBOARD. THE EXISTING SWITCHBOARD IS A SQUARE D TYPE QED,

1200A, 120/208V, 3Ø, 4 WIRE WITH MAIN LUGS ONLY. THE NEW CIRCUIT

BREAKER SHALL BE COMPATIBLE WITH AND LISTED FOR USE IN THE

EXISTING PANEL AND SHALL BE HAVE A MINIMUM SHORT CIRCUIT AIC

RATING TO MATCH THE LOWEST RATED EXISTING DEVICE IN THE PANEL.

6. INSTALL NEW CIRCUIT BREAKER IN SPACE AVAILABLE IN THE EXISTING

PANEL. THE EXISTING PANEL IS A SQUARE D TYPE I-LINE, 800A, 120/208V,

3Ø, 4 WIRE WITH MAIN LUGS ONLY. THE NEW CIRCUIT BREAKER SHALL BE

COMPATIBLE WITH AND LISTED FOR USE IN THE EXISTING PANEL AND

SHALL BE HAVE A MINIMUM SHORT CIRCUIT AIC RATING TO MATCH THE

LOWEST RATED EXISTING DEVICE IN THE PANEL.

7. TAP BUS AT SPARE LUGS IN EXISTING DISTRIBUTION PANEL FEED TO NEW

ENCLOSED BREAKER.

8. UPS IS SPECIFIED WITH DUAL BATTERY CABINET INPUTS AND

PARALLELING CABINET INPUT TO PROVIDE N+1 CONFIGURATION.

9. PROVIDE PANEL WITH INTEGRAL POWER METERING.

10. PROVIDE 1/2"C, WITH 3#12 FOR CONNECTION TO POWER SHUT OFF PUSH

BUTTON IN BUILDING 154 ROOM B-09, SEE 154-EP-0B1.1.

GENERAL NOTES:

A. FOR FEEDERS UPSIZED FOR VOLTAGE DROP PROVIDE LUG REDUCERS OR

SPLICE CONDUCTORS SUCH THAT PANEL LUGS MAY ACCEPT

CONDUCTORS.

OS

T

K

M

FCP

FRA

SCP

OS

A

X

MS

DC

ST

CR

PM

XX-XX

ED

ED

ELECTRICAL LEGEND

ROUND LIGHT FIXTURE - PENDANT OR SURFACE MTD CLG, EM,

LIGHT FIXTURE - SURFACE MTD ON WALL, EM

LIGHT FIXTURE - RECESSED DOWNLIGHT, EM

EMERGENCY EXIT SIGN - SURFACE MTD CLG, EXISTING

EMERGENCY LIGHT - SURFACE MTD WALL, EXISTING

LINEAR EMERGENCY FIXTURE

LINEAR LIGHT FIXTURE - RECESSED MTD

LINEAR LIGHT FIXTURE - SURFACE MTD CLG

LINEAR LIGHT FIXTURE - PENDANT MTD

STRIPLIGHT - PENDANT OR SURFACE MTD CLG, EM

STRIPLIGHT - WALL MTD, EM

SINGLE POLE SWITCH

OCCUPANCY SENSOR WALL SWITCH (DUALTECH)

, EMERGENCY EXIT SIGN - SURFACE MTD WALL, EXISTING

OCCUPANCY SENSOR - CEILING MOUNTED (DUALTECH)

CONDUIT, CONCEALED

NUMBER AND SIZE OF WIRES (NO MARKS = 3 #12)

HOMERUN TO PANEL (PANEL AND CIRCUIT No.)

SURFACE RACEWAY

EXISTING, NEW PANEL

DUPLEX RECEPTACLE

DUPLEX RECEPTACLE WITH GROUND FAULT CIRCUIT INTERRUPTER

QUADRAPLEX RECEPTACLE

SPECIAL PURPOSE OUTLET

JUNCTION BOX

EMERGENCY PUSHBUTTON SWITCH

MOTOR (SIZED AS SHOWN)

NATIONAL ELECTRICAL CODE

DENOTES EXISTING ITEM THAT HAS BEEN RELOCATED

TELEPHONE TERMINAL BACKBOARD

TRANSIENT VOLTAGE SURGE SUPPRESSION

TYPICAL

UNLESS OTHERWISE NOTED

WIRELESS ACCESS POINT

WEATHERPROOFWP

WAP

UON

TYP

TVSS

TTB

R

NEC

MAIN LUGS ONLYMLO

MAIN CIRCUIT BREAKERMCB

LUMENSLM

LIGHT EMITTING DIODELED

KELVINK

GALVANIZED RIGID STEEL CONDUITGRSC

GROUND FAULT CIRCUIT INTERRUPTERGFCI

DENOTES EMERGENCY POWEREM

DENOTES EXISTING ITEME

DENOTES ITEM LOCATED ON THE CEILINGCLG

CONDUITC

ABOVE FINISHED GRADEAFG

ABOVE FINISHED FLOORAFF

EQUIPMENT TAG (No. INDICATES TYPE)

NOTE TAG (No. INDICATES NOTE)

DUPLEX RECEPTACLE TO BE REMOVED (DASHED OR DOTTED LINES

INDICATE ITEMS TO BE REMOVED TYPICAL)

FRACTIONAL HORSEPOWER MOTOR STARTER

DISCONNECT SWITCH

DISCONNECT SWITCH (FUSED)

COMBINATION DISCONNECT/MAGNETIC MOTOR STARTER

TELECOMMUNICATION OUTLET (COMBINATION TELEPHONE & DATA)

POWER METERING

PROXIMITY CARD READER

SECURITY KEYPAD

SHUNT TRIP

DOOR POSITION CONTACT

SECURITY MOTION SENSOR

SECURITY CONTROL PANEL

SR

MAGNETIC HOLD OPEN

CLOSED CIRCUIT TELEVISION CAMERA (CEILING MOUNTED)

FIRE ALARM CONTROL PANEL

FIRE ALARM REMOTE ANNUNCIATOR PANEL

FIRE ALARM PULL STATION

FIRE ALARM HORN (WALL, CLG MOUNTED)

FIRE ALARM HORN/STROBE LIGHT (WALL, CLG MOUNTED)

FIRE ALARM STROBE LIGHT (WALL, CLG MOUNTED)

HEAT DETECTOR 135° & RATE OF RISE (OR FIXED °F IF NOTED)

PHOTOELECTRIC SMOKE DETECTOR

, C

, C

FIXTURE TAG (LETTER INDICATES TYPE)

, C

CIRCUIT TAG (No. INDICATES CIRCUIT)

A-2

#10

EXIT DEVICE

ELECTRIC HINGE

CONTRACTING OFFICER'S REPRESENTATIVECOR

LIGHT FIXTURE SCHEDULE

TYPE LOCATION

MANUFACTURER AND CATALOG NUMBER

(OR APPROVED EQUAL)

LUMINAIRE DESCRIPTION

MOUNTING

LAMPS BALLAST/DRIVER TOTAL INPUT

WATTSTYPE HEIGHT

A

AS SHOWN LITHONIA

#CLX-L48-7000LM-SEF-FDL-MVOLT-

EZ1-40K-90CRI

(E10WLCP-SPD)

4' LINEAR LED STRIP WITH FLAT DIFFUSER.

PROVIDE WITH E10WLCP EM DRIVER WHERE NOTED AS

EMERGENCY ON PLANS.

SURFACE PENDANT MTD

AT 9' AFF OR

CEILING MTD

4,000K LED

6,810LM

90 CRI

120/277V, 0-10V

DIMMABLE DRIVER

DOWN TO 1%

A1

MCR LITHONIA

#CLX-L48-7000LM-SEF-WDL-MVOLT-

EZ1-40K-90CRI

(E10WLCP-SPD)

SAME AS TYPE 'A' EXCEPT WITH WIDE DIFFUSER.

PROVIDE WITH E10WLCP EM DRIVER WHERE NOTED AS

EMERGENCY ON PLANS.

SURFACE PENDANT MTD

AT 8' AFF OR

CEILING MTD

4,000K LED

6,810LM

90 CRI

120/277V, 0-10V

DIMMABLE DRIVER

DOWN TO 1%

A2

MCR LITHONIA

#CLX-L48-5000LM-SEF-WDL-MVOLT-

EZ1-40K-90CRI

(E10WLCP-SPD)

SAME AS TYPE 'A' EXCEPT WITH LOWER LUMEN PACKAGE AND

WIDE DIFFUSER.

PROVIDE WITH E10WLCP EM DRIVER WHERE NOTED AS

EMERGENCY ON PLANS.

SURFACE PENDANT MTD

AT 7' AFF OR

CEILING MTD

4,000K LED

4,620LM

90 CRI

120/277V, 0-10V

DIMMABLE DRIVER

DOWN TO 1%

B

BUILDLING 65 LITHONIA

#2BLT4-48L-ADP-EZ1-LP840

2'X4' RECESSED LED TROFFER WITH CURVED RIBBED DIFFUSER. RECESSED CEILING 4,000K LED

5,039LM

82CRI

120/277V, 0-10V

DIMMABLE DRIVER

DOWN TO 1%

C

BUILDLING 154,

RM B-09

STRATALUME CONNECTS

#AUCLED-S-MW-16L40K-36-120

3' LED UNDERCABINET LIGHT WITH MATTE WHITE FINISH. SURFACE UNDER CABINET 4000K LED

1,631LM

120V 18

D

AS SHOWN LITHONIA

#2BLT2-40L-ADP-EZ1-LP840

2'X2' RECESSED LED TROFFER WITH CURVED RIBBED DIFFUSER. RECESSED CEILING 4,000K LED

4,105LM

82CRI

120/277V, 0-10V

DIMMABLE DRIVER

DOWN TO 1%

X

AS SHOWN LITHONIA

#LHQM-LED-R-SD

EXIT SIGN WITH WHITE HOUSING AND RED LETTER COLOR. WALL ABOVE DOOR - 120-277V DRIVER 4

U.S. Department of Veterans Affairs

PROJECT NUMBER

BUILDING NUMBER

DRAWING NUMBER

PROJECT TITLE

LOCATION

ISSUE DATE CHECKED BY DRAWN BY

DRAWING TITLE

APPROVED:

VA FORM 08 - 6231

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PHASE

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

FLS

PROGRAM

CONTRACTING

ACTIVITY

CENTRAL (PCAC)

JEREMY A. MAXIE

5/18/2022

EE-113847

B

IM

/2

V

A M e d ic a l C e n te r

F t H a rr is o n M

T /E

S E

R

IE

S G

E N

E R

A L I N

F O r2

.r v t

/1

/2

:5

:2

P

M

EK-003

ELECTRICAL LEGEND AND

FIXTURE SCHEDULEGDM

1000 W STEUBEN ST. UNIT 3

BINGEN, WA 98605

541.436.4723

ADAM GOODIN, PE

EHRM INFRASTRUCTURE

UPGRADES

FORT HARRISON, MONTANA

436-21-700

GEN INFO

Project Director

CSZJAM05/20/2022

100% CONSTRUCTION

DOCUMENTS

A/E:

FULLY SPRINKLERED

PM

250A POWER FEED UNIT WITH

INTEGRAL POWER METERING

3-FOOT DROP CORD WITH STRAIN

RELIEF AND L21-20R RECEPTACLE, TYP

BUSWAY 'BUS-A1' (TYPICAL FOR BUSWAY 'BUS-B1'),

250A, 120/208V, 3Ø, 4W WITH 50% GROUND BUS.

BUSWAY TAP BOX WITH SINGLE

20A/3P BREAKER, TYP OF 14.

PM

BUSWAY 'BUS-A2' (TYPICAL FOR BUSWAY 'BUS-B2'),

60A, 120/208V, 3Ø, 4W WITH 50% GROUND BUS.

3-FOOT DROP CORD WITH STRAIN

RELIEF AND L21-20R RECEPTACLE, TYP

60A POWER FEED UNIT WITH

INTEGRAL POWER METERING

BUSWAY TAP BOX WITH SINGLE

20A/3P BREAKER, TYP OF 6.

2"C, 4 #4/0, AND 1 #6 GND

1.25"C, 4 #4, AND 1 #8 GND

BUS-A2 :

TO PANEL 'UPS-A'

BUS-B2 :

TO PANEL 'UPS-B'

BUS-A2 :

TO PANEL 'UPS-A'

BUS-B2 :

TO PANEL 'UPS-B'

U.S. Department of Veterans Affairs

PROJECT NUMBER

BUILDING NUMBER

DRAWING NUMBER

PROJECT TITLE

LOCATION

ISSUE DATE CHECKED BY DRAWN BY

DRAWING TITLE

APPROVED:

VA FORM 08 - 6231

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PHASE

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

FLS

PROGRAM

CONTRACTING

ACTIVITY

CENTRAL (PCAC)

JEREMY A. MAXIE

5/18/2022

EE-113847

B

IM

/2

V

A M e d ic a l C e n te r

F t H a rr is o n M

T /E

S E

R

IE

S G

E N

E R

A L I N

F O r2

.r v t

/1

/2

:5

:2

P

M

EK-004

MCR ELECTRICAL DETAILS

GDM

1000 W STEUBEN ST. UNIT 3

BINGEN, WA 98605

541.436.4723

ADAM GOODIN, PE

EHRM INFRASTRUCTURE

UPGRADES

FORT HARRISON, MONTANA

436-21-700

GEN INFO

Project Director

CSZJAM05/20/2022

100% CONSTRUCTION

DOCUMENTS

A/E:

FULLY SPRINKLERED

NOT TO SCALE1 DATA CENTER BUSWAY DETAILS

BUILDING 141 LOAD CALCULATION

EXISTING NORMAL POWER SWITCHBOARD '141-SWBD-MDP' IS A 1200A

120/208V, 3Ø SWITCHBOARD

SEE PANEL SCHEDULES FOR LOAD CALCULATION FOR INDIVIDUAL PANELS.

NEW LOAD ADDED TO PANEL '141 DPL' 64,982 VA = 180 A

EXISTING DEMAND LOAD ON PANEL '141 DPL' 50,400 VA = 139.89641 A

NEW CALCULATED DEMAND LOAD ON PANEL '141 DPL' 115,382 VA = 320 A

NEW LOAD ADDED TO PANEL '141 SWBD-MDP' 70,922 VA = 197 A

EXISTING DEMAND LOAD ON '141-SWBD-MDP' 194,400 VA = 540 A

NEW CALCULATED DEMAND LOAD ON PANEL 265,322 VA = 736 A

EXISTING SERVICE AND DISTRIBUTION EQUIPMENT HAVE ADEQUATE

CAPACITY FOR NEW LOAD ADDED.

BUILDING 154 & 154A LOAD CALCULATION

EXISTING NORMAL POWER SWITCHBOARD '154-SWBP1' IS A 2500A

120/208V, 3Ø SWITCHBOARD

SEE PANEL SCHEDULES FOR LOAD CALCULATION FOR INDIVIDUAL PANELS.

NEW LOAD ADDED TO PANEL '154-DP-TR1' 318,532 VA = 884 A

CALCULATED DEMAND LOAD ON

PANEL '154-DP-TR1' 309,506 VA = 859 A

NEW LOAD ADDED TO PANEL '154-SWBP1' 320,401 VA = 889 A

EXISTING DEMAND LOAD ON '154-SWBP1' 352,080 VA = 977 A

NEW CALCULATED DEMAND LOAD ON PANEL 672,481 VA = 1,867 A

EXISTING SERVICE AND DISTRIBUTION EQUIPMENT HAVE ADEQUATE

CAPACITY FOR NEW LOAD ADDED.

BUILDING 169 LOAD CALCULATION

EXISTING NORMAL POWER SWITCHBOARD 'SWITCHBOARD MDP' IS A 1200A

120/208V, 3Ø SWITCHBOARD

SEE PANEL SCHEDULES FOR LOAD CALCULATION FOR INDIVIDUAL PANELS.

NEW DEMAND LOAD ADDED TO PANEL '169-EQ1-T1' 17,082 VA = 47 A

EXISTING DEMAND LOAD ON 'MECH 1-SEC 1' 48,600 VA = 134.90011A

NEW CALCULATED DEMAND LOAD ON PANEL 'MECH 1-SEC 1' 65,682 VA = 182 A

NEW DEMAND LOAD ADDED TO PANEL 'SWITCHBOARD MDP' 18,702 VA = 52 A

EXISTING DEMAND LOAD ON 'SWITCHBOARD MDP' 82,080 VA = 227.8313A

NEW CALCULATED DEMAND LOAD ON PANEL 100,782 VA = 280 A

EXISTING SERVICE AND DISTRIBUTION EQUIPMENT HAVE ADEQUATE

CAPACITY FOR NEW LOAD ADDED.

U.S. Department of Veterans Affairs

PROJECT NUMBER

BUILDING NUMBER

DRAWING NUMBER

PROJECT TITLE

LOCATION

ISSUE DATE CHECKED BY DRAWN BY

DRAWING TITLE

APPROVED:

VA FORM 08 - 6231

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PHASE

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

FLS

PROGRAM

CONTRACTING

ACTIVITY

CENTRAL (PCAC)

JEREMY A. MAXIE

5/18/2022

EE-113847

B

IM

/2

V

A M e d ic a l C e n te r

F t H a rr is o n M

T /E

S E

R

IE

S G

E N

E R

A L I N

F O r2

.r v t

/1

/2

:5

:3

P

M

EK-005

ELECTRICAL LOAD

CALCULATIONSGDM

1000 W STEUBEN ST. UNIT 3

BINGEN, WA 98605

541.436.4723

ADAM GOODIN, PE

EHRM INFRASTRUCTURE

UPGRADES

FORT HARRISON, MONTANA

436-21-700

GEN INFO

Project Director

CSZJAM05/20/2022

100% CONSTRUCTION

DOCUMENTS

A/E:

PANEL 'A'

MFR/MODEL: SQUARE 'D' TYPE NQ VOLTS: 120/208V,3PH,4W ENCLOSURE: NEMA 1 60 A

VOLT-AMPS MTG: SURFACE

N

O T

E

C

IR

C

P O

LE

A M

P S

SERVICE TYPE A B C TYPE SERVICE A

M

P S

P O

LE

C

IR

C

N O

T E a 1 1 20 N. DAN RM - RECP/LTG PANEL 'B' * 3 2 a,b a 3 1 20 LTG - BOILER & TRAINING RM ^^^ * 3 4 a,b a 5 1 20 RECP - OFFICE - KIT- LIVING ^^^ * 3 6 a,b a 7 2 30 AC UNITS WATER HEATER 30 1 8 a a 9 2 30 ^^ ^^ 30 1 10 a a 11 1 20 UH-1 BOILER CONTROL PANEL 20 1 12 a a 13 1 20 ILLEGIBLE NEW LTG/RECP LIVING RM 20 1 14 a a 15 2 30 EXTERIOR RECP APAK RM 20 1 16 a a 17 2 30 ^^ RECP - QUARTERS 20 1 18 a a 19 1 20 TEL. BELL OUTSIDE & SIRENS BR EXHAUST FAN 20 1 20 a a 21 1 20 ALARM PANEL RLS RECP - SHOP & NEW MICROWAVE 20 1 22 a a 23 1 20 LED EXTERIOR LTG A/C ROLL UP DOOR 20 1 24 a

25 2 25 16-ACUC-1 MOTR 1955 1920 SPEC RK-106-1A 20 1 26

27 2 25 ^^ MOTR 1955 180 RECP 16-RECP-1 20 1 28

29 2 25 16-CUAC-1 MOTR 1258 360 RECP RECP - TE 106 20 1 30

31 2 25 ^^ MOTR 1258 200 MISC 16-ACP-1 20 1 32

33 1 15 16-DDC-1 MISC 50 SPARE 20 1 34

35 1 - SPACE SPACE - 1 36

37 1 - SPACE SPACE - 1 38

39 1 - SPACE SPACE - 1 40

41 1 - SPACE SPACE - 1 42

TOTAL V-A 5334 2185 1618 9,137 VA

TOTAL AMPS 44 18 13 25 A

A.I.C. RATING: 22,000

LTG RECP MOTR LG.MT MISC KIT HEAT SPEC TOTAL AMPS

CONNECTED LOAD IN KVA (THIS PANEL): 0.00 0.54 6.43 0.98 0.25 0.00 0.00 1.92 9.1 KVA 25 A

CONNECTED LOAD IN KVA (BRANCH PANELS): 0.0 KVA 0 A

TOTAL CONNECTED LOAD IN KVA: 0.00 0.54 6.43 0.98 0.25 0.00 0.00 1.92 9.1 KVA 25 A

DEMAND LOAD IN KVA: 0.00 0.54 6.43 0.98 0.25 0.00 0.00 1.92 10.1 KVA 28 A

PANEL NOTES: PANEL OPTIONS:

a EXISTING LOAD RELOCATED TO NEW PANEL. PROVIDE EXTENSION OF EXISTING CIRCUIT. MAIN LUGS ONLY PROVIDE JUNCTION BOXES, CONDUIT, AND WIRE AS REQUIRED. SEE 16-EP-011. PROVIDE WITH CONTINUOUS HINGED TRIM b SEE ONE-LINE ON SHEET 16-EP-011 FOR BREAKER SIZE.

EXISTING PANEL 'E'

MFR/MODEL: SQUARE 'D' TYPE NQ VOLTS: 120/208V,3PH,4W ENCLOSURE: NEMA 1 60 A

VOLT-AMPS MTG: SURFACE

N O

T E

C

IR

C

P O

LE

A M

P S

SERVICE TYPE A B C TYPE SERVICE A

M

P S

P O

LE

C

IR

C

N O

T E a 1 1 20 DOOR OPENER GARAGE - LTG 20 1 2 a a 3 1 20 DOOR OPENER GARAGE - LTG 20 1 4 a a 5 1 20 DOOR OPENER GARAGE - LTG 20 1 6 a a 7 1 20 DOOR OPENER GARAGE - LTG 20 1 8 a c 9 1 20 RK-106-1B SPEC 1920 SPARE 20 1 10

11 1 20 SPARE SPARE 20 1 12

13 1 20 SPARE SPARE 20 1 14

15 1 20 SPARE SPARE 20 1 16

17 1 20 SPARE SPARE 20 1 18

19 1 20 SPARE SPARE 20 1 20

21 1 20 SPARE SPARE 20 1 22

23 1 20 SPARE SPARE 20 1 24

25 1 - SPACE SPACE - 1 26

27 1 - SPACE SPACE - 1 28

29 1 - SPACE SPACE - 1 30

TOTAL V-A 0 1920 0 1,920 VA

TOTAL AMPS 0 16 0 5 A

LTG RECP MOTR LG.MT MISC KIT HEAT SPEC TOTAL AMPS

CONNECTED LOAD IN KVA (THIS PANEL): 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.92 1.9 KVA 5 A

CONNECTED LOAD IN KVA (BRANCH PANELS): 0.0 KVA 0 A

TOTAL CONNECTED LOAD IN KVA: 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.92 1.9 KVA 5 A

DEMAND LOAD IN KVA: 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.92 1.9 KVA 5 A

PANEL NOTES: PANEL OPTIONS:

a EXISTING LOAD. 30A MAIN CIRCUIT BREAKER b NEW LOAD ON EXISTING BREAKER

EXISTING PANEL '20-PNL'

MFR/MODEL: SQUARE 'D' TYPE QOC VOLTS: 120/208V,3PH,4W ENCLOSURE: NEMA 1 200 A

VOLT-AMPS MTG: SURFACE

N O

T E

C

IR

C

P O

LE

A M

P S

SERVICE TYPE A B C TYPE SERVICE A

M

P S

P O

LE

C

IR

C

N O

T E a 1 2 50 FS PANEL EXISTING LOAD 20 2 2 a a 3 2 50 ^^ ^^ 20 2 4 a a 5 1 20 CCTV RACK EXISTING LOAD 20 1 6 a a 7 3 30 AIR COMPRESSOR TRASH CAN WASHER 20 1 8 a a 9 3 30 ^^^ RECP- ATTIC & NORTH RM 20 1 10 a a 11 3 30 ^^^ TOOL ROOM 20 1 12 a a 13 1 20 LTG - HALLWAY & STOR. RM WATER HEATER #2 20 2 14 a a 15 1 20 RECP-BOOM TRUCK & PASSAGE ^^ 20 2 16 a a 17 1 20 PAINT & CARP. STORAGE RECP - WELDER 60 3 18 a a 19 1 20 LTG - INCINERATOR RM ^^^ 60 3 20 a a 21 2 20 WATER HEATER #1 ^^^ 60 3 22 a a 23 2 20 ^^ RECP - IRM 20 1 24 a a 25 1 20 VEEDER ROOT RECP-EAST RM, LTG- DOOR 20 1 26 a a 27 1 20 LTG-CENTER & S. GARAGE NO LABEL 30 2 28 a a 29 1 20 RECP - WEST, LTG - NORTH ^^ 30 2 30 a a 31 1 20 RECP - OUTDOOR RECP-SOUTH SIDE GARAGE 20 1 32 a b 33 1 20 RK-100B-1B SPEC 1920 RECP - PARKING OUTDOOR 20 1 34 a

35 1 - SPACE SUB PANEL WEST END 100 3 36 a a 37 1 20 VEEDER ROOT ALARM ^^^ 100 3 38 a a 39 1 20 GAS PUMP ^^^ 100 3 40 a

TOTAL V-A 0 1920 0 1,920 VA

TOTAL AMPS 0 16 0 5 A

LTG RECP MOTR LG.MT MISC KIT HEAT SPEC TOTAL AMPS

CONNECTED LOAD IN KVA (THIS PANEL): 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.92 1.9 KVA 5 A

CONNECTED LOAD IN KVA (BRANCH PANELS): 0.0 KVA 0 A

TOTAL CONNECTED LOAD IN KVA: 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.92 1.9 KVA 5 A

DEMAND LOAD IN KVA: 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.92 1.9 KVA 5 A

PANEL NOTES: PANEL OPTIONS:

a EXISTING LOAD. 200A MAIN CIRCUIT BREAKER b INSTALL NEW CIRCUIT BREAKER IN SPACE AVAILABLE IN THE PANEL. THE NEW CIRCUIT

BREAKER SHALL BE COMPATIBLE WITH AND LISTED FOR USE IN THE EXISTING PANEL AND

SHALL HAVE A MINIMUM SHORT CIRCUIT AIC RAITING TO MATCH THE LOWEST RATED EXISTING

DEVICE IN THE PANEL.

PANEL 'WEST END'

MFR/MODEL: SQUARE 'D' TYPE QOC VOLTS: 120/208V,3PH,4W ENCLOSURE: NEMA 1 100 A

VOLT-AMPS MTG: SURFACE

N O

T E

C

IR

C

P O

LE

A M

P S

SERVICE TYPE A B C TYPE SERVICE A

M

P S

P O

LE

C

IR

C

N O

T E a 1 a 20 NO LABEL RECP/LTG - CARPENTER OFFCE 20 1 2 a a 3 a 20 RECP - GRINDER 20, 3PH RECP 20 3 4 a a 5 a 20 RECP - POLISHER ^^^ 20 3 6 a a 7 a 20 RECP - WALL ^^^ 20 3 8 a a 9 a 20 RECO - LEFT OF PANEL TABLE SAW 20 2 10 a a 11 a 20 RECO - LEFT OF PANEL ^^ 20 2 12 a a 13 a 20 RECO - LEFT OF PANEL RECP - PAINT SHOP 20 1 14 a a 15 a 20 RECP - CARPENTER OFFICE BELT SANDER 20 2 16 a a 17 a 20 RECP - PAINT SHOP ^^ 20 2 18 a

19 1 20 RK-100B-1A SPEC 1920 1258 MOTR 20-CUAC-1 25 2 20

21 1 20 20-RECP-1 RECP 180 1258 MOTR ^^ 25 2 22

23 1 20 20-ACP-1 MISC 200 1955 MOTR 20-ACUC-1 25 2 24

25 1 20 RECP - TE 100B RECP 360 1955 MOTR ^^ 25 2 26

27 1 20 20-DDC-1 MISC 50 SPARE 20 1 28

29 1 - SPACE SPACE - 1 30

TOTAL V-A 5494 1488 2155 9,137 VA

TOTAL AMPS 46 12 18 25 A

A.I.C. RATING: 22,000

LTG RECP MOTR LG.MT MISC KIT HEAT SPEC TOTAL AMPS

CONNECTED LOAD IN KVA (THIS PANEL): 0.00 0.54 6.43 0.98 0.25 0.00 0.00 1.92 9.1 KVA 25 A

CONNECTED LOAD IN KVA (BRANCH PANELS): 0.0 KVA 0 A

TOTAL CONNECTED LOAD IN KVA: 0.00 0.54 6.43 0.98 0.25 0.00 0.00 1.92 9.1 KVA 25 A

DEMAND LOAD IN KVA: 0.00 0.54 6.43 0.98 0.25 0.00 0.00 1.92 10.1 KVA 28 A

PANEL NOTES: PANEL OPTIONS:

a EXISTING LOADS ON NEW PANEL. PROVIDE EXTENSION OF EXISTING CIRCUITS AS REQUIRED MAIN LUGS ONLY PROVIDE JUNCTION BOXES, CONDUIT, AND WIRE AS REQUIRED. PROVIDE WITH CONTINUOUS HINGED TRIM

U.S. Department of Veterans Affairs

PROJECT NUMBER

BUILDING NUMBER

DRAWING NUMBER

PROJECT TITLE

LOCATION

ISSUE DATE CHECKED BY DRAWN BY

DRAWING TITLE

APPROVED:

VA FORM 08 - 6231

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PHASE

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

FLS

PROGRAM

CONTRACTING

ACTIVITY

CENTRAL (PCAC)

JEREMY A. MAXIE

5/18/2022

EE-113847

B

IM

/2

V

A M e d ic a l C e n te r

F t H a rr is o n M

T /E

S E

R

IE

S G

E N

E R

A L I N

F O r2

.r v t

/1

/2

:5

:3

P

M

EK-006

BUILDINGS 16 & 20 - PANEL

SCHEDULESGDM

1000 W STEUBEN ST. UNIT 3

BINGEN, WA 98605

541.436.4723

ADAM GOODIN, PE

EHRM INFRASTRUCTURE

UPGRADES

FORT HARRISON, MONTANA

436-21-700

GEN INFO

Project Director

CSZJAM05/20/2022

100% CONSTRUCTION

DOCUMENTS

A/E:

PANEL '141-EQB-T1'

MFR/MODEL: SQUARE 'D' TYPE NQ VOLTS: 120/208V,3PH,4W ENCLOSURE: NEMA 1 100 A

VOLT-AMPS MTG: SURFACE

N

O T

E

C

IR

C

P O

LE

A M

P S

SERVICE TYPE A B C TYPE SERVICE A

M

P S

P O

LE

C

IR

C

N O

T E

1 3 20 RK-B-20A-1B SPEC 1167 98 LTG TELECOM RM - B-20A LTG 20 1 2

3 3 20 ^^^ SPEC 1167 1778 MOTR 141-CU-1 35 2 4

5 3 20 ^^^ SPEC 1167 1778 MOTR ^^ 35 2 6

7 1 20 141-ACP-1 MISC 200 3557 MOTR 141-ACUC-1 45 2 8

9 1 15 141-DDC-1 MISC 50 3557 MOTR ^^ 45 2 10

11 3 40 141-DC-1 MOTR 2844 84 RECP 141-GT-1 20 1 12

13 3 40 ^^^ MOTR 2844 SPARE 20 1 14

15 3 40 ^^^ MOTR 2844 SPARE 20 1 16

17 1 20 SPARE SPARE 20 1 18

19 1 - SPACE SPACE - 1 20

21 1 - SPACE SPACE - 1 22

23 1 - SPACE SPACE - 1 24

25 1 - SPACE SPACE - 1 26

27 1 - SPACE SPACE - 1 28

29 1 - SPACE SPACE - 1 30

31 1 - SPACE SPACE - 1 32

33 1 - SPACE SPACE - 1 34

35 1 - SPACE SPACE - 1 36

37 1 - SPACE SPACE - 1 38

39 1 - SPACE SPACE - 1 40

41 1 - SPACE SPACE - 1 42

TOTAL V-A 7865 9396 5873 23,134 VA

TOTAL AMPS 66 78 49 64 A

A.I.C. RATING: 22,000

LTG RECP MOTR LG.MT MISC KIT HEAT SPEC TOTAL AMPS

CONNECTED LOAD IN KVA (THIS PANEL): 0.10 0.08 19.20 2.13 0.25 0.00 0.00 3.50 23.1 KVA 64 A

CONNECTED LOAD IN KVA (BRANCH PANELS): 0.0 KVA 0 A

TOTAL CONNECTED LOAD IN KVA: 0.10 0.08 19.20 2.13 0.25 0.00 0.00 3.50 23.1 KVA 64 A

DEMAND LOAD IN KVA: 0.12 0.08 19.20 2.13 0.25 0.00 0.00 3.50 25.3 KVA 70 A

PANEL NOTES: PANEL OPTIONS:

MAIN CIRCUIT BREAKER (SEE ONE-LINE FOR SIZE)

PROVIDE WITH CONTINUOUS HINGED TRIM

PANEL '141-NB-T1'

MFR/MODEL: SQUARE 'D' TYPE NQ VOLTS: 120/208V,3PH,4W ENCLOSURE: NEMA 1 60 A

VOLT-AMPS MTG: SURFACE

N O

T E

C

IR

C

P O

LE

A M

P S

SERVICE TYPE A B C TYPE SERVICE A

M

P S

P O

LE

C

IR

C

N O

T E

1 3 20 RK-B-20A-1B SPEC 1167 720 RECP TR - NORTH RECP 20 1 2

3 3 20 ^^^ SPEC 1167 720 RECP TR - SOUTH RECP 20 1 4

5 3 20 ^^^ SPEC 1167 SPARE 20 1 6

7 1 20 141-RECP-1 RECP 180 SPARE 20 1 8

9 1 20 SPARE SPARE 20 1 10

11 1 - SPACE SPACE - 1 12

13 1 - SPACE SPACE - 1 14

15 1 - SPACE SPACE - 1 16

17 1 - SPACE SPACE - 1 18

19 1 - SPACE SPACE - 1 20

21 1 - SPACE SPACE - 1 22

23 1 - SPACE SPACE - 1 24

25 1 - SPACE SPACE - 1 26

27 1 - SPACE SPACE - 1 28

29 1 - SPACE SPACE - 1 30

31 1 - SPACE SPACE - 1 32

33 1 - SPACE SPACE - 1 34

35 1 - SPACE SPACE - 1 36

37 1 - SPACE SPACE - 1 38

39 1 - SPACE SPACE - 1 40

41 1 - SPACE SPACE - 1 42

TOTAL V-A 2067 1887 1167 5,120 VA

TOTAL AMPS 17 16 10 14 A

A.I.C. RATING: 22,000

LTG RECP MOTR LG.MT MISC KIT HEAT SPEC TOTAL AMPS

CONNECTED LOAD IN KVA (THIS PANEL): 0.00 1.62 0.00 0.00 0.00 0.00 0.00 3.50 5.1 KVA 14 A

CONNECTED LOAD IN KVA (BRANCH PANELS): 0.0 KVA 0 A

TOTAL CONNECTED LOAD IN KVA: 0.00 1.62 0.00 0.00 0.00 0.00 0.00 3.50 5.1 KVA 14 A

DEMAND LOAD IN KVA: 0.00 1.62 0.00 0.00 0.00 0.00 0.00 3.50 5.1 KVA 14 A

PANEL NOTES: PANEL OPTIONS:

MAIN CIRCUIT BREAKER (SEE ONE-LINE FOR SIZE)

PROVIDE WITH CONTINUOUS HINGED TRIM

PANEL '141-EQ1-T1'

MFR/MODEL: SQUARE 'D' TYPE NQ VOLTS: 120/208V,3PH,4W ENCLOSURE: NEMA 1 100 A

VOLT-AMPS MTG: SURFACE

N O

T E

C

IR

C

P O

LE

A M

P S

SERVICE TYPE A B C TYPE SERVICE A

M

P S

P O

LE

C

IR

C

N O

T E

1 3 20 RK-128-1A SPEC 1167 147 LTG TELECOM RM -128 LTG 20 1 2

3 3 20 ^^^ SPEC 1167 1778 MOTR 141-CU-2 35 2 4

5 3 20 ^^^ SPEC 1167 1778 MOTR ^^ 35 2 6

7 1 20 141-ACP-2 MISC 200 3557 MOTR 141-ACUC-2 45 2 8

9 1 20 SPARE 3557 MOTR ^^ 45 2 10

11 1 20 SPARE 50 MISC 141-DDC-2 15 1 12

13 1 20 SPARE SPARE 20 1 14

15 1 - SPACE SPARE 20 1 16

17 1 - SPACE SPACE - 1 18

19 1 - SPACE SPACE - 1 20

21 1 - SPACE SPACE - 1 22

23 1 - SPACE SPACE - 1 24

25 1 - SPACE SPACE - 1 26

27 1 - SPACE SPACE - 1 28

29 1 - SPACE SPACE - 1 30

31 1 - SPACE SPACE - 1 32

33 1 - SPACE SPACE - 1 34

35 1 - SPACE SPACE - 1 36

37 1 - SPACE SPACE - 1 38

39 1 - SPACE SPACE - 1 40

41 1 - SPACE SPACE - 1 42

TOTAL V-A 5070 6502 2995 14,567 VA

TOTAL AMPS 42 54 25 40 A

A.I.C. RATING: 22,000

LTG RECP MOTR LG.MT MISC KIT HEAT SPEC TOTAL AMPS

CONNECTED LOAD IN KVA (THIS PANEL): 0.15 0.00 10.67 1.78 0.25 0.00 0.00 3.50 14.6 KVA 40 A

CONNECTED LOAD IN KVA (BRANCH PANELS): 0.0 KVA 0 A

TOTAL CONNECTED LOAD IN KVA: 0.15 0.00 10.67 1.78 0.25 0.00 0.00 3.50 14.6 KVA 40 A

DEMAND LOAD IN KVA: 0.18 0.00 10.67 1.78 0.25 0.00 0.00 3.50 16.4 KVA 45 A

PANEL NOTES: PANEL OPTIONS:

MAIN CIRCUIT BREAKER (SEE ONE-LINE FOR SIZE)

PROVIDE WITH CONTINUOUS HINGED TRIM

PANEL '141-N1-T1'

MFR/MODEL: SQUARE 'D' TYPE NQ VOLTS: 120/208V,3PH,4W ENCLOSURE: NEMA 1 60 A

VOLT-AMPS MTG: SURFACE

N O

T E

C

IR

C

P O

LE

A M

P S

SERVICE TYPE A B C TYPE SERVICE A

M

P S

P O

LE

C

IR

C

N O

T E

1 3 20 RK-128-1B SPEC 1167 720 RECP TR - NORTH RECP 20 1 2

3 3 20 ^^^ SPEC 1167 720 RECP TR - SOUTH RECP 20 1 4

5 3 20 ^^^ SPEC 1167 SPARE 20 1 6

7 1 20 SPARE SPARE 20 1 8

9 1 20 SPARE SPARE 20 1 10

11 1 20 SPARE SPARE 20 1 12

13 1 - SPACE SPACE - 1 14

15 1 - SPACE SPACE - 1 16

17 1 - SPACE SPACE - 1 18

19 1 - SPACE SPACE - 1 20

21 1 - SPACE SPACE - 1 22

23 1 - SPACE SPACE - 1 24

25 1 - SPACE SPACE - 1 26

27 1 - SPACE SPACE - 1 28

29 1 - SPACE SPACE - 1 30

31 1 - SPACE SPACE - 1 32

33 1 - SPACE SPACE - 1 34

35 1 - SPACE SPACE - 1 36

37 1 - SPACE SPACE - 1 38

39 1 - SPACE SPACE - 1 40

41 1 - SPACE SPACE - 1 42

TOTAL V-A 1887 1887 1167 4,940 VA

TOTAL AMPS 16 16 10 14 A

A.I.C. RATING: 22,000

LTG RECP MOTR LG.MT MISC KIT HEAT SPEC TOTAL AMPS

CONNECTED LOAD IN KVA (THIS PANEL): 0.00 1.44 0.00 0.00 0.00 0.00 0.00 3.50 4.9 KVA 14 A

CONNECTED LOAD IN KVA (BRANCH PANELS): 0.0 KVA 0 A

TOTAL CONNECTED LOAD IN KVA: 0.00 1.44 0.00 0.00 0.00 0.00 0.00 3.50 4.9 KVA 14 A

DEMAND LOAD IN KVA: 0.00 1.44 0.00 0.00 0.00 0.00 0.00 3.50 4.9 KVA 14 A

PANEL NOTES: PANEL OPTIONS:

MAIN CIRCUIT BREAKER (SEE ONE-LINE FOR SIZE)

PROVIDE WITH CONTINUOUS HINGED TRIM

U.S. Department of Veterans Affairs

PROJECT NUMBER

BUILDING NUMBER

DRAWING NUMBER

PROJECT TITLE

LOCATION

ISSUE DATE CHECKED BY DRAWN BY

DRAWING TITLE

APPROVED:

VA FORM 08 - 6231

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PHASE

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

FLS

PROGRAM

CONTRACTING

ACTIVITY

CENTRAL (PCAC)

JEREMY A. MAXIE

5/18/2022

EE-113847

B

IM

/2

V

A M e d ic a l C e n te r

F t H a rr is o n M

T /E

S E

R

IE

S G

E N

E R

A L I N

F O r2

.r v t

/1

/2

:5

:4

P

M

EK-007

BUILDING 141 - PANEL

SCHEDULESGDM

1000 W STEUBEN ST. UNIT 3

BINGEN, WA 98605

541.436.4723

ADAM GOODIN, PE

EHRM INFRASTRUCTURE

UPGRADES

FORT HARRISON, MONTANA

436-21-700

GEN INFO

Project Director

CSZJAM05/20/2022

100% CONSTRUCTION

DOCUMENTS

A/E:

PANEL '141-EQ2-T1'

VOLT-AMPS MTG: SURFACE

N O

T E

C

IR

C

P O

LE

A M

P S

SERVICE TYPE A B C TYPE SERVICE A

M

P S

P O

LE

C

IR

C

N O

T E

1 3 20 RK-218A-1A SPEC 1167 98 LTG TELECOM RM -218A LTG 20 1 2

3 3 20 ^^^ SPEC 1167 1778 MOTR 141-CU-3 35 2 4

5 3 20 ^^^ SPEC 1167 1778 MOTR ^^ 35 2 6

7 1 20 141-ACP-3 MISC 200 3557 MOTR 141-ACUC-3 45 2 8

9 1 15 141-DDC-3 MISC 50 3557 MOTR ^^ 45 2 10

11 1 20 SPARE SPARE 20 1 12

13 1 20 SPARE SPARE 20 1 14

15 1 20 SPARE SPARE 20 1 16

17 1 - SPACE SPACE - 1 18

19 1 - SPACE SPACE - 1 20

21 1 - SPACE SPACE - 1 22

23 1 - SPACE SPACE - 1 24

25 1 - SPACE SPACE - 1 26

27 1 - SPACE SPACE - 1 28

29 1 - SPACE SPACE - 1 30

31 1 - SPACE SPACE - 1 32

33 1 - SPACE SPACE - 1 34

35 1 - SPACE SPACE - 1 36

37 1 - SPACE SPACE - 1 38

39 1 - SPACE SPACE - 1 40

41 1 - SPACE SPACE - 1 42

TOTAL V-A 5021 6552 2945 14,518 VA

TOTAL AMPS 42 55 25 40 A

A.I.C. RATING: 22,000

LTG RECP MOTR LG.MT MISC KIT HEAT SPEC TOTAL AMPS

CONNECTED LOAD IN KVA (THIS PANEL): 0.10 0.00 10.67 1.78 0.25 0.00 0.00 3.50 14.5 KVA 40 A

CONNECTED LOAD IN KVA (BRANCH PANELS): 0.0 KVA 0 A

TOTAL CONNECTED LOAD IN KVA: 0.10 0.00 10.67 1.78 0.25 0.00 0.00 3.50 14.5 KVA 40 A

DEMAND LOAD IN KVA: 0.12 0.00 10.67 1.78 0.25 0.00 0.00 3.50 16.3 KVA 45 A

PANEL NOTES: PANEL OPTIONS:

MAIN CIRCUIT BREAKER (SEE ONE-LINE FOR SIZE)

PROVIDE WITH CONTINUOUS HINGED TRIM

PANEL '141-N2-T1'

MFR/MODEL: SQUARE 'D' TYPE NQ VOLTS: 120/208V,3PH,4W ENCLOSURE: NEMA 1 60 A

VOLT-AMPS MTG: SURFACE

N O

T E

C

IR

C

P O

LE

A M

P S

SERVICE TYPE A B C TYPE SERVICE A

M

P S

P O

LE

C

IR

C

N O

T E

1 3 20 RK-218A-1A SPEC 1167 720 RECP TR - NORTH RECP 20 1 2

3 3 20 ^^^ SPEC 1167 720 RECP TR - SOUTH RECP 20 1 4

5 3 20 ^^^ SPEC 1167 SPARE 20 1 6

7 1 20 SPARE SPARE 20 1 8

9 1 20 SPARE SPARE 20 1 10

11 1 - SPACE SPACE - 1 12

13 1 - SPACE SPACE - 1 14

15 1 - SPACE SPACE - 1 16

17 1 - SPACE SPACE - 1 18

19 1 - SPACE SPACE - 1 20

21 1 - SPACE SPACE - 1 22

23 1 - SPACE SPACE - 1 24

25 1 - SPACE SPACE - 1 26

27 1 - SPACE SPACE - 1 28

29 1 - SPACE SPACE - 1 30

31 1 - SPACE SPACE - 1 32

33 1 - SPACE SPACE - 1 34

35 1 - SPACE SPACE - 1 36

37 1 - SPACE SPACE - 1 38

39 1 - SPACE SPACE - 1 40

41 1 - SPACE SPACE - 1 42

TOTAL V-A 1887 1887 1167 4,940 VA

TOTAL AMPS 16 16 10 14 A

A.I.C. RATING: 22,000

LTG RECP MOTR LG.MT MISC KIT HEAT SPEC TOTAL AMPS

CONNECTED LOAD IN KVA (THIS PANEL): 0.00 1.44 0.00 0.00 0.00 0.00 0.00 3.50 4.9 KVA 14 A

CONNECTED LOAD IN KVA (BRANCH PANELS): 0.0 KVA 0 A

TOTAL CONNECTED LOAD IN KVA: 0.00 1.44 0.00 0.00 0.00 0.00 0.00 3.50 4.9 KVA 14 A

DEMAND LOAD IN KVA: 0.00 1.44 0.00 0.00 0.00 0.00 0.00 3.50 4.9 KVA 14 A

PANEL NOTES: PANEL OPTIONS:

MAIN CIRCUIT BREAKER (SEE ONE-LINE FOR SIZE)

PROVIDE WITH CONTINUOUS HINGED TRIM

PANEL '141-EQ3-T1'

MFR/MODEL: SQUARE 'D' TYPE NQ VOLTS: 120/208V,3PH,4W ENCLOSURE: NEMA 1 100 A

VOLT-AMPS MTG: SURFACE

N O

T E

C

IR

C

P O

LE

A M

P S

SERVICE TYPE A B C TYPE SERVICE A

M

P S

P O

LE

C

IR

C

N O

T E

1 3 20 RK-315A-1A SPEC 1167 98 LTG TELECOM RM -315A LTG 20 1 2

3 3 20 ^^^ SPEC 1167 1778 MOTR 141-CU-4 35 2 4

5 3 20 ^^^ SPEC 1167 1778 MOTR ^^ 35 2 6

7 1 20 141-ACP-4 MISC 200 3557 MOTR 141-ACUC-4 45 2 8

9 1 15 141-DDC-4 MISC 50 3557 MOTR ^^ 45 2 10

11 1 20 SPARE SPARE 20 1 12

13 1 20 SPARE SPARE 20 1 14

15 1 - SPACE SPACE - 1 16

17 1 - SPACE SPACE - 1 18

19 1 - SPACE SPACE - 1 20

21 1 - SPACE SPACE - 1 22

23 1 - SPACE SPACE - 1 24

25 1 - SPACE SPACE - 1 26

27 1 - SPACE SPACE - 1 28

29 1 - SPACE SPACE - 1 30

31 1 - SPACE SPACE - 1 32

33 1 - SPACE SPACE - 1 34

35 1 - SPACE SPACE - 1 36

37 1 - SPACE SPACE - 1 38

39 1 - SPACE SPACE - 1 40

41 1 - SPACE SPACE - 1 42

TOTAL V-A 5021 6552 2945 14,518 VA

TOTAL AMPS 42 55 25 40 A

A.I.C. RATING: 22,000

LTG RECP MOTR LG.MT MISC KIT HEAT SPEC TOTAL AMPS

CONNECTED LOAD IN KVA (THIS PANEL): 0.10 0.00 10.67 1.78 0.25 0.00 0.00 3.50 14.5 KVA 40 A

CONNECTED LOAD IN KVA (BRANCH PANELS): 0.0 KVA 0 A

TOTAL CONNECTED LOAD IN KVA: 0.10 0.00 10.67 1.78 0.25 0.00 0.00 3.50 14.5 KVA 40 A

DEMAND LOAD IN KVA: 0.12 0.00 10.67 1.78 0.25 0.00 0.00 3.50 16.3 KVA 45 A

PANEL NOTES: PANEL OPTIONS:

MAIN CIRCUIT BREAKER (SEE ONE-LINE FOR SIZE)

PROVIDE WITH CONTINUOUS HINGED TRIM

PANEL '141-N3-T1'

MFR/MODEL: SQUARE 'D' TYPE NQ VOLTS: 120/208V,3PH,4W ENCLOSURE: NEMA 1 60 A

VOLT-AMPS MTG: SURFACE

N O

T E

C

IR

C

P O

LE

A M

P S

SERVICE TYPE A B C TYPE SERVICE A

M

P S

P O

LE

C

IR

C

N O

T E

1 3 20 RK-315A-1B SPEC 1167 720 RECP TR - NORTH RECP 20 1 2

3 3 20 ^^^ SPEC 1167 720 RECP TR - SOUTH RECP 20 1 4

5 3 20 ^^^ SPEC 1167 SPARE 20 1 6

7 1 20 SPARE SPARE 20 1 8

9 1 20 SPARE SPARE 20 1 10

11 1 - SPACE SPARE 20 1 12

13 1 - SPACE SPACE - 1 14

15 1 - SPACE SPACE - 1 16

17 1 - SPACE SPACE - 1 18

19 1 - SPACE SPACE - 1 20

21 1 - SPACE SPACE - 1 22

23 1 - SPACE SPACE - 1 24

25 1 - SPACE SPACE - 1 26

27 1 - SPACE SPACE - 1 28

29 1 - SPACE SPACE - 1 30

31 1 - SPACE SPACE - 1 32

33 1 - SPACE SPACE - 1 34

35 1 - SPACE SPACE - 1 36

37 1 - SPACE SPACE - 1 38

39 1 - SPACE SPACE - 1 40

41 1 - SPACE SPACE - 1 42

TOTAL V-A 1887 1887 1167 4,940 VA

TOTAL AMPS 16 16 10 14 A

A.I.C. RATING: 22,000

LTG RECP MOTR LG.MT MISC KIT HEAT SPEC TOTAL AMPS

CONNECTED LOAD IN KVA (THIS PANEL): 0.00 1.44 0.00 0.00 0.00 0.00 0.00 3.50 4.9 KVA 14 A

CONNECTED LOAD IN KVA (BRANCH PANELS): 0.0 KVA 0 A

TOTAL CONNECTED LOAD IN KVA: 0.00 1.44 0.00 0.00 0.00 0.00 0.00 3.50 4.9 KVA 14 A

DEMAND LOAD IN KVA: 0.00 1.44 0.00 0.00 0.00 0.00 0.00 3.50 4.9 KVA 14 A

PANEL NOTES: PANEL OPTIONS:

MAIN CIRCUIT BREAKER (SEE ONE-LINE FOR SIZE)

PROVIDE WITH CONTINUOUS HINGED TRIM

U.S. Department of Veterans Affairs

PROJECT NUMBER

BUILDING NUMBER

DRAWING NUMBER

PROJECT TITLE

LOCATION

ISSUE DATE CHECKED BY DRAWN BY

DRAWING TITLE

APPROVED:

VA FORM 08 - 6231

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PHASE

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

FLS

PROGRAM

CONTRACTING

ACTIVITY

CENTRAL (PCAC)

JEREMY A. MAXIE

5/18/2022

EE-113847

B

IM

/2

V

A M e d ic a l C e n te r

F t H a rr is o n M

T /E

S E

R

IE

S G

E N

E R

A L I N

F O r2

.r v t

/1

/2

:5

:4

P

M

EK-008

BUILDING 141 - PANEL

SCHEDULESGDM

1000 W STEUBEN ST. UNIT 3

BINGEN, WA 98605

541.436.4723

ADAM GOODIN, PE

EHRM INFRASTRUCTURE

UPGRADES

FORT HARRISON, MONTANA

436-21-700

GEN INFO

Project Director

CSZJAM05/20/2022

100% CONSTRUCTION

DOCUMENTS

A/E:

DISTRIBUTION PANEL '154-DP-TR1'

MFR/MODEL: SQUARE 'D' TYPE I-LINE VOLTS: 120/208V,3PH,4W ENCLOSURE: NEMA 1 1200 A

MTG SPACE: AS REQUIRED VOLT-AMPS MTG: SURFACE

N

O T

E

C

IR

C

P O

LE

A M

P S

SERVICE TYPE A B C TYPE SERVICE A

M

P S

P O

LE

C

IR

C

N O

T E a 1 3 * 154-EQ1-T1 FEDR 15682 8115 FEDR 154A-EQB-T1 * 3 2 a a 3 3 * ^^^ FEDR 17362 13004 FEDR ^^^ * 3 4 a a 5 3 * ^^^ FEDR 18892 7803 FEDR ^^^ * 3 6 a a 7 3 * 154-EQ2-T1 FEDR 6237 7202 FEDR 154A-EQ1-T1 * 3 8 a a 9 3 * ^^^ FEDR 7719 10513 FEDR ^^^ * 3 10 a a 11 3 * ^^^ FEDR 4112 8934 FEDR ^^^ * 3 12 a a 13 3 * 154-EQ3-T1 FEDR 9081 6237 FEDR 154-EQ4-T1 * 3 14 a a 15 3 * ^^^ FEDR 10563 7719 FEDR ^^^ * 3 16 a a 17 3 * ^^^ FEDR 6956 4112 FEDR ^^^ * 3 18 a

19 3 100 B1A-2 FEDR 5833 26533 FEDR PANEL-UPS-B * 3 20 a

21 3 100 ^^^ FEDR 5833 26533 FEDR ^^^ * 3 22 a

23 3 100 ^^^ FEDR 5833 26533 FEDR ^^^ * 3 24 a

25 1 - SPACE 14304 MOTR 154-ACUC-2 200 3 26

27 1 - SPACE 14304 MOTR ^^^ 200 3 28

29 1 - SPACE 14304 MOTR ^^^ 200 3 30

31 1 - SPACE 1104 MOTR 154-CUAC-2 15 3 32

33 1 - SPACE 1104 MOTR ^^^ 15 3 34

35 1 - SPACE 1104 MOTR ^^^ 15 3 36

37 1 - SPACE 1656 MOTR 154-ECO-2 20 3 38

39 1 - SPACE 1656 MOTR ^^^ 20 3 40

41 1 - SPACE 1656 MOTR ^^^ 20 3 42

TOTAL V-A 101985 116308 100239 318,532 VA

TOTAL AMPS 850 969 835 884 A

AIC RATING: 22,000

LTG REC MOTR LG MTR MISC KIT HEAT SPEC TOTAL AMPS

CONNECTED LOAD IN KVA (THIS PANEL) 0.00 0.00 51.19 10.73 0.00 0.00 0.00 0.00 51.2 KVA 142 A

CONNECTED LOAD IN KVA (BRANCH PANELS) 0.98 0.08 114.88 3.89 81.40 0.00 0.00 70.00 267.3 KVA 753 A

TOTAL CONNECTED LOAD IN KVA: 0.98 0.08 166.07 10.73 81.40 0.00 0.00 70.00 318.5 KVA 884 A

DEMAND LOAD IN KVA: 1.23 0.08 166.07 10.73 81.40 0.00 0.00 50.00 309.5 KVA 859 A

PANEL NOTES: PANEL OPTIONS:

a SEE ONE-LINE ON SHEET EK002 FOR BREAKER SIZE AND RATING. MAIN LUGS ONLY b RELOCATED LOAD FROM EXISTING PANEL 'TELE. B13'. PROVIDE WITH CONTINUOUS HINGED TRIM

RELOCATED PANEL '154-DEE2'

MFR/MODEL: EATON PRL-1A VOLTS: 120/208V,3PH,4W ENCLOSURE: NEMA 1 400 A

VOLT-AMPS MTG: SURFACE

N O

T E

C

IR

C

P O

LE

A M

P S

SERVICE TYPE A B C TYPE SERVICE A

M

P S

P O

LE

C

IR

C

N O

T E

1 1 20 SPARE SPARE 30 1 2 a a 3 1 20 LTG COMPUTER RM SPARE 30 1 4 a a 5 1 20 CP PUMP SPARE 30 1 6 a a 7 1 20 SPARE LTG COMPUTER RM 30 1 8 a a 9 1 20 SPARE SPARE 30 2 10 a a 11 1 20 LTG RM - B-10 ^^ 30 2 12 a a 13 3 20 SPARE SPARE 20 3 14 a a 15 3 20 ^^^ ^^^ 20 3 16 a a 17 3 20 ^^^ ^^^ 20 3 18 a b,c 19 1 20 CONDENSATE PUMPS MOTR SPACE - 1 20

21 1 - SPACE SPACE - 1 22

23 1 - SPACE SPACE - 1 24

a 25 2 20 SPARE SPARE 50 1 26 a a 27 2 20 ^^ ^^^ 50 3 28 a a 29 1 20 SPARE ^^^ 50 3 30 a a 31 1 20 SPARE SPARE 20 1 32 a a 33 1 20 SPARE SPARE 20 1 34 a a 35 1 20 SPARE SPARE 20 1 36 a a 37 1 - SPACE SPARE 20 1 38 a a 39 1 - SPACE SPARE 20 1 40 a a 41 1 - SPACE SPARE 20 1 42 a

TOTAL V-A 0 0 0 0 VA

TOTAL AMPS 0 0 0 0 A

A.I.C. RATING: 10,000

SPCE LTG RECP MOTR LG.MT MISC KIT HEAT SPEC TOTAL AMPS

CONNECTED LOAD IN KVA (THIS PANEL): 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.0 KVA 0 A

CONNECTED LOAD IN KVA (BRANCH PANELS): 0.0 KVA 0 A

TOTAL CONNECTED LOAD IN KVA: 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.0 KVA 0 A

DEMAND LOAD IN KVA: 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.0 KVA 0 A

PANEL NOTES: PANEL OPTIONS:

a EXISTING LOAD. PROVIDE EXTENSION OF EXISTING CIRCUIT. PROVIDE JBOX, CONDUIT AND WIRE AS REQUIRED. MAIN CIRCUIT BREAKER 400A b RELOCATED LOAD FROM PANEL '154-2' c INSTALL NEW CIRCUIT BREAKER IN SPACE AVAILABLE IN THE PANEL. THE NEW CIRCUIT

BREAKER SHALL BE COMPATIBLE WITH AND LISTED FOR USE IN THE EXISTING PANEL AND

SHALL HAVE A MINIMUM SHORT CIRCUIT AIC RAITING TO MATCH THE LOWEST RATED

EXISTING DEVICE IN THE PANEL.

PANEL 'UPS-A'

MFR/MODEL: SQUARE 'D' TYPE NQ VOLTS: 120/208V,3PH,4W ENCLOSURE: NEMA 1 400 A

VOLT-AMPS MTG: SURFACE

N O

T E

C

IR

C

P O

LE

A M

P S

SERVICE TYPE A B C TYPE SERVICE A

M

P S

P O

LE

C

IR

C

N O

T E

1 3 * BUS-A1 MISC 21867 4667 MISC BUS-A2 60 3 2

3 3 * ^^^ MISC 21867 4667 MISC ^^^ 60 3 4

5 3 * ^^^ MISC 21867 4667 MISC ^^^ 60 3 6

7 1 15 154-DDC-1 MISC 200 SPARE 20 1 8

9 1 15 154-SP-1 MOTR 624 SPARE 20 1 10

11 1 20 SPARE SPARE 20 1 12

13 1 - SPACE SPACE - 1 14

15 1 - SPACE SPACE - 1 16

17 1 - SPACE SPACE - 1 18

19 1 - SPACE SPACE - 1 20

21 1 - SPACE SPACE - 1 22

23 1 - SPACE SPACE - 1 24

25 1 - SPACE SPACE - 1 26

27 1 - SPACE SPACE - 1 28

29 1 - SPACE SPACE - 1 30

31 1 - SPACE SPACE - 1 32

33 1 - SPACE SPACE - 1 34

35 1 - SPACE SPACE - 1 36

37 1 - SPACE SPACE - 1 38

39 1 - SPACE SPACE - 1 40

41 1 - SPACE SPACE - 1 42

TOTAL V-A 26733 27157 26533 80,424 VA

TOTAL AMPS 223 226 221 223 A

A.I.C. RATING: 22,000

LTG RECP MOTR LG.MT MISC KIT HEAT SPEC TOTAL AMPS

CONNECTED LOAD IN KVA (THIS PANEL): 0.00 0.00 0.62 0.16 79.80 0.00 0.00 0.00 80.4 KVA 223 A

CONNECTED LOAD IN KVA (BRANCH PANELS): 0.0 KVA 0 A

TOTAL CONNECTED LOAD IN KVA: 0.00 0.00 0.62 0.16 79.80 0.00 0.00 0.00 80.4 KVA 223 A

DEMAND LOAD IN KVA: 0.00 0.00 0.62 0.16 79.80 0.00 0.00 0.00 80.6 KVA 224 A

PANEL NOTES: PANEL OPTIONS:

a FED FROM 'UPS-A' MAIN CIRCUIT BREAKER (SEE ONE-LINE FOR SIZE)

PROVIDE WITH 200% RATED NEUTRAL

PROVIDE WITH CONTINUOUS HINGED TRIM

* 250A, 3-POLE BREAKER

PANEL 'UPS-B'

MFR/MODEL: SQUARE 'D' TYPE NQ VOLTS: 120/208V,3PH,4W…