Att 03 - Drawings.pdf
PDF 4 MB Posted
- Solicitation number
- 1333ND26RNB190028
About this file
Summary
This document is a set of architectural and engineering construction drawings for Building 2, Room 1330 Walk-In Fume Hood project at the National Institute of Standards and Technology (NIST) in Boulder, Colorado. The project involves the demolition of existing laboratory equipment and installation of new mechanical, plumbing, and electrical systems to support a walk-in fume hood facility.
The mechanical scope includes removal of the existing fume hood, exhaust ductwork, and exhaust fan, followed by installation of a new walk-in fume hood (model 02-LFH-1330-1), 12-inch PVC exhaust ductwork with enlarged plexiglass opening, and a new exhaust fan (02-EF-LFH-1330-1) on the roof with guy wire anchoring for wind loads up to 128 mph. The plumbing work requires removal and replacement of the existing sink, with new domestic cold water (DCW) and waste connections, plus installation of an instantaneous water heater (02-WH-1330-01) for hot water supply. The electrical scope includes providing three new 120V, 20-ampere dedicated circuits from panel 1300 for user equipment, a 208V, 20-ampere single-phase connection to the water heater from panel PP6, new cable tray routing with water falls and elbow sections, relocation of existing light fixtures to avoid conflict with the fume hood door travel, and rework of the existing lightning protection system for the new exhaust stack. All work must comply with NIST standards, applicable national codes, and include proper bonding of new equipment with a minimum #6 AWG bonding conductor connected to the existing grounding bar. The contractor is responsible for complete demolition, removal of all asbestos-containing materials per state and federal regulations, and coordination with fire alarm and lightning protection contractors for final connections and certifications.
View the file
Other files
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Spine Rd
Compton Rd
2A
Wing 6
Lawrence Rd
Floor 4
BOULDER SITE PLAN
Wing 1 Floor 2
Wing 3
Compton Rd
N.T.S.
Floor 3
Curie Circle
Anderson Ditch
Millikan Rd
Wing 5
3A
Compton Rd Magnetic North
PLAN NORTH
Appleton Rd
11Kusch Rd
12, 28, Green Mtn
Security Center
Source Transfer Switch
Broadway - State Hwy 93
Medical Ctr Access Rd
Green Mtn Cemetary
NOAA Bldg
C.U.P.
Skaggs
SITE ENTRANCE
Broadway - State Hwy 93 Broadway - State Hwy 93
Floor 4
W ilson Rd
Broadway - State Hwy 93
Marconi Rd th
W ay
Wing 2
Wing 4
Floor 2
Floor 3
24A
VIEWNUMBER
SHEETNUMBER
AutoCAD SHX Text
DB
AutoCAD SHX Text
PARTS PER MILLION
AutoCAD SHX Text
PPM
AutoCAD SHX Text
DRY-BULB
AutoCAD SHX Text
HR
AutoCAD SHX Text
HOUR(S)
AutoCAD SHX Text
TSP
AutoCAD SHX Text
TOTAL STATIC PRESSURE
AutoCAD SHX Text
LF
AutoCAD SHX Text
LINEAR FEET
AutoCAD SHX Text
INSIDE DIAMETER
AutoCAD SHX Text
INVERT ELEVATION
AutoCAD SHX Text
KILOWATT
AutoCAD SHX Text
KILOWATT HOUR
AutoCAD SHX Text
LEAVING AIR TEMPERATURE
AutoCAD SHX Text
HOT WATER CIRCULATING (DOMESTIC)
AutoCAD SHX Text
INCHES WATER COLUMN
AutoCAD SHX Text
KWH
AutoCAD SHX Text
LAT
AutoCAD SHX Text
LBS OR #
AutoCAD SHX Text
IN W.C.
AutoCAD SHX Text
KW
AutoCAD SHX Text
POUNDS
AutoCAD SHX Text
HWC
AutoCAD SHX Text
ID
AutoCAD SHX Text
IN
AutoCAD SHX Text
IE
AutoCAD SHX Text
HZ
AutoCAD SHX Text
INCHES
AutoCAD SHX Text
HERTZ
AutoCAD SHX Text
WB
AutoCAD SHX Text
WT
AutoCAD SHX Text
VOL
AutoCAD SHX Text W
AutoCAD SHX Text V
AutoCAD SHX Text
VAV
AutoCAD SHX Text
VERT
AutoCAD SHX Text
VEL
AutoCAD SHX Text
TONS
AutoCAD SHX Text
TSTAT
AutoCAD SHX Text
WEIGHT
AutoCAD SHX Text
WET-BULB
AutoCAD SHX Text
VOLUME
AutoCAD SHX Text
WATT
AutoCAD SHX Text
VOLT
AutoCAD SHX Text
TONS OF REFRIGERATION
AutoCAD SHX Text
VARIABLE AIR VOLUME
AutoCAD SHX Text
VELOCITY
AutoCAD SHX Text
VERTICAL
AutoCAD SHX Text
THERMOSTAT
AutoCAD SHX Text
RLA
AutoCAD SHX Text
FT
AutoCAD SHX Text
FOOT OR FEET
AutoCAD SHX Text
FIXTURE UNITS
AutoCAD SHX Text
GALLONS PER HOUR
AutoCAD SHX Text
HORSEPOWER
AutoCAD SHX Text
MERCURY
AutoCAD SHX Text
GALLONS PER MINUTE
AutoCAD SHX Text
HORIZONTAL
AutoCAD SHX Text
HGT
AutoCAD SHX Text
HORZ
AutoCAD SHX Text
HP
AutoCAD SHX Text
HG
AutoCAD SHX Text
HD
AutoCAD SHX Text
HEIGHT
AutoCAD SHX Text
HEAD
AutoCAD SHX Text
GAL
AutoCAD SHX Text
GPH
AutoCAD SHX Text
GPM
AutoCAD SHX Text
GA
AutoCAD SHX Text
FU
AutoCAD SHX Text
GALLONS
AutoCAD SHX Text
GAUGE
AutoCAD SHX Text
TD
AutoCAD SHX Text
TEMP
AutoCAD SHX Text
SP
AutoCAD SHX Text
SA
AutoCAD SHX Text
STD
AutoCAD SHX Text
SENS
AutoCAD SHX Text
SQ
AutoCAD SHX Text
SPEC
AutoCAD SHX Text
SL
AutoCAD SHX Text
RPM
AutoCAD SHX Text
FEET PER MINUTE
AutoCAD SHX Text
FULL LOAD AMPS
AutoCAD SHX Text
ENTERING AIR TEMP.
AutoCAD SHX Text
EFFICIENCY
AutoCAD SHX Text
ELEVATION
AutoCAD SHX Text
FAHRENHEIT
AutoCAD SHX Text
FEET PER SECOND
AutoCAD SHX Text
EXISTING
AutoCAD SHX Text
EXTERNAL STATIC PRESSURE
AutoCAD SHX Text
FLA
AutoCAD SHX Text
FPS
AutoCAD SHX Text
EXIST
AutoCAD SHX Text
FPM
AutoCAD SHX Text F
AutoCAD SHX Text
EXISTING
AutoCAD SHX Text
EFF
AutoCAD SHX Text
ELEV
AutoCAD SHX Text (E)
AutoCAD SHX Text
EAT
AutoCAD SHX Text
ESP
AutoCAD SHX Text
RH
AutoCAD SHX Text
RECIRC
AutoCAD SHX Text
PRESS
AutoCAD SHX Text
RA
AutoCAD SHX Text
PSIG
AutoCAD SHX Text
PSF
AutoCAD SHX Text
PSIA
AutoCAD SHX Text
PSI
AutoCAD SHX Text
PH OR %%C
AutoCAD SHX Text
AutoCAD SHX Text
RUNNING LOAD AMPS
AutoCAD SHX Text
STATIC PRESSURE
AutoCAD SHX Text
TEMPERATURE DIFFERENCE
AutoCAD SHX Text
TEMPERATURE
AutoCAD SHX Text
STANDARD
AutoCAD SHX Text
SUPPLY AIR
AutoCAD SHX Text
REVOLUTIONS PER MINUTE
AutoCAD SHX Text
SENSIBLE
AutoCAD SHX Text
SPECIFICATION
AutoCAD SHX Text
SQUARE
AutoCAD SHX Text
SEA LEVEL
AutoCAD SHX Text
RELATIVE HUMIDITY
AutoCAD SHX Text
RECIRCULATE
AutoCAD SHX Text
PSI GAUGE
AutoCAD SHX Text
PRESSURE
AutoCAD SHX Text
RETURN AIR
AutoCAD SHX Text
PHASE (ELECTRICAL)
AutoCAD SHX Text
POUNDS PER SQUARE INCH
AutoCAD SHX Text
POUNDS PER SQUARE FOOT
AutoCAD SHX Text
PSI ABSOLUTE
AutoCAD SHX Text
PERCENT
AutoCAD SHX Text
COEFFICIENT, VALVE FLOW
AutoCAD SHX Text
CUBIC FEET
AutoCAD SHX Text
CUBIC INCH
AutoCAD SHX Text
CUBIC FEET PER MINUTE
AutoCAD SHX Text
CFM, STANDARD CONDITIONS
AutoCAD SHX Text
DOMESTIC COLD WATER
AutoCAD SHX Text
DIAMETER
AutoCAD SHX Text
DOMESTIC HOT WATER
AutoCAD SHX Text
DEG OR %%D
AutoCAD SHX Text
DCW
AutoCAD SHX Text
DIA
AutoCAD SHX Text
DHW
AutoCAD SHX Text dB
AutoCAD SHX Text
DEGREE
AutoCAD SHX Text
DECIBEL
AutoCAD SHX Text
CU FT
AutoCAD SHX Text
CU IN
AutoCAD SHX Text
CFM
AutoCAD SHX Text
SCFM
AutoCAD SHX Text Cv
AutoCAD SHX Text
OD
AutoCAD SHX Text
OA
AutoCAD SHX Text
NTS
AutoCAD SHX Text
NO
AutoCAD SHX Text
NIC
AutoCAD SHX Text N.O.
AutoCAD SHX Text N/A
AutoCAD SHX Text N.C.
AutoCAD SHX Text
NC
AutoCAD SHX Text
MIN
AutoCAD SHX Text
%%UABBREVIATIONS
AutoCAD SHX Text
ABOVE FINISHED FLOOR
AutoCAD SHX Text
BRAKE HORSEPOWER
AutoCAD SHX Text
BRITISH THERMAL UNIT
AutoCAD SHX Text
AFF
AutoCAD SHX Text
ALT
AutoCAD SHX Text
BHP
AutoCAD SHX Text
BTU
AutoCAD SHX Text
ALTITUDE
AutoCAD SHX Text
MCA
AutoCAD SHX Text
MBH
AutoCAD SHX Text
MAX
AutoCAD SHX Text
LRA
AutoCAD SHX Text
LWT
AutoCAD SHX Text
BTU PER HOUR (THOUSAND)
AutoCAD SHX Text
OUTSIDE DIAMETER
AutoCAD SHX Text
NOT IN CONTRACT
AutoCAD SHX Text
OUTSIDE AIR
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
NUMBER
AutoCAD SHX Text
NORMALLY OPEN
AutoCAD SHX Text
NORMALLY CLOSED
AutoCAD SHX Text
NOT APPLICABLE
AutoCAD SHX Text
NOISE CRITERIA
AutoCAD SHX Text
MINIMUM
AutoCAD SHX Text
LOCKED ROTOR AMPS
AutoCAD SHX Text
MINIMUM CIRCUIT AMPS
AutoCAD SHX Text
LEAVING WATER TEMPERATURE
AutoCAD SHX Text
MAXIMUM
AutoCAD SHX Text
AFG
AutoCAD SHX Text
ABOVE FINISHED GRADE
AutoCAD SHX Text
DN
AutoCAD SHX Text
DOWN
AutoCAD SHX Text
COMMON PORT
AutoCAD SHX Text C
AutoCAD SHX Text
DRAIN VALVE W/ HOSE END
AutoCAD SHX Text
FLOW CONTROL VALVE W/ CHECK
AutoCAD SHX Text
PLUG OR BALANCING SHUT-OFF VALVE
AutoCAD SHX Text
STRAINER W/ BLOW-OFF VALVE
AutoCAD SHX Text
SAFETY OR RELIEF VALVE
AutoCAD SHX Text
PRESSURE - TEMP. TAP
AutoCAD SHX Text
TEMPERATURE CONTROL VALVE, 3-WAY
AutoCAD SHX Text
TEMPERATURE CONTROL VALVE, 2-WAY
AutoCAD SHX Text
PRESSURE GAUGE W/ PIG TAIL & COCK
AutoCAD SHX Text
VACUUM BREAKER
AutoCAD SHX Text
THERMOMETER
AutoCAD SHX Text
AIR VENT
AutoCAD SHX Text
%%UVALVES & SPECIALTIES
AutoCAD SHX Text
CHECK VALVE
AutoCAD SHX Text
SHUT-OFF VALVE
AutoCAD SHX Text
GLOBE VALVE
AutoCAD SHX Text
FLOW INDICATOR
AutoCAD SHX Text
FLEXIBLE PIPE CONNECTOR
AutoCAD SHX Text
FLEXIBLE EQUIPMENT CONNECTOR
AutoCAD SHX Text
PIPE GUIDE
AutoCAD SHX Text
PIPE EXPANSION JOINT
AutoCAD SHX Text
PIPE ANCHOR
AutoCAD SHX Text
PIPE UNION
AutoCAD SHX Text
PIPE CAP
AutoCAD SHX Text
PIPE ELBOW DOWN 90 OR 45
AutoCAD SHX Text
PIPE ELBOW UP 90 OR 45
AutoCAD SHX Text
PIPE TEE DOWN
AutoCAD SHX Text
PIPE TEE UP
AutoCAD SHX Text
ARROW INDICATES DOWNWARD PITCH OF PIPES
AutoCAD SHX Text S
AutoCAD SHX Text NATIONAL INSTITUTE OF STANDARDS AND TECHNOLOGY UNITED STATES DEPARTMENT OF COMMERCE BOULDER COLORADO
AutoCAD SHX Text
%%UMECHANICAL LEGEND
AutoCAD SHX Text
1. MANUFACTURER'S CATALOG NUMBERS ARE FOR SPECIFICATION PURPOSES. NIST MANUFACTURER'S CATALOG NUMBERS ARE FOR SPECIFICATION PURPOSES. NIST ACCEPTED EQUIVALENTS SHALL BE ACCEPTED EXCEPT WHERE OTHERWISE INDICATED. SUPPLY NIST ENGINEERING WITH MFR'S CUT-SHEETS FOR APPROVAL PRIOR TO PURCHASE OF SUBSTITUTE EQUIPMENT. 2. CONTRACTOR TO FIELD VERIFY EXISTING CONDITIONS PRIOR TO CONSTRUCTION. CONTRACTOR TO FIELD VERIFY EXISTING CONDITIONS PRIOR TO CONSTRUCTION. 3. EXISTING MECHANICAL SYSTEMS SHOWN LIGHT LINE WEIGHT. NEW MECHANICAL EXISTING MECHANICAL SYSTEMS SHOWN LIGHT LINE WEIGHT. NEW MECHANICAL SYSTEMS SHOWN HEAVY LINE WEIGHT. MECHANICAL SYSTEMS TO BE REMOVED ARE SHOWN CROSS-HATCHED OR DESCRIBED IN SYSTEM DEMOLITION NOTES. 4. CONTRACTOR IS TO PROVIDE COMPLETE CONNECTIONS TO ALL NEW AND RELOCATED CONTRACTOR IS TO PROVIDE COMPLETE CONNECTIONS TO ALL NEW AND RELOCATED OWNER FURNISHED EQUIPMENT. 5. CONTRACTOR SHALL MAKE ARRANGEMENTS FOR PARKING, COORDINATE ANY CONTRACTOR SHALL MAKE ARRANGEMENTS FOR PARKING, COORDINATE ANY EQUIPMENT DOWNTIME, AND COORDINATE GENERAL WORK SCHEDULE WITH THE COR. 6. THE DRAWINGS INDICATE THE GENERAL ARRANGEMENT OF THE EXISTING EQUIPMENT THE DRAWINGS INDICATE THE GENERAL ARRANGEMENT OF THE EXISTING EQUIPMENT LOCATIONS, EXISTING PIPE ROUTING AND EXISTING DUCT ROUTING. CONTRACTOR IS TO INSTALL NEW EQUIPMENT, DUCTS, AND PIPING IN LOCATIONS REQUIRED TO AVOID INTERFERENCE WITH EXISTING FACILITIES, EQUIPMENT, DUCTS AND PIPING. CONTRACTOR IS RESPONSIBLE FOR RAISING AND LOWERING EXISTING EQUIPMENT AND MAKING PROPER OFFSETS IN DUCTS AND PIPING TO AVOID CONFLICTS. 7. CONTRACTOR SHALL VISIT THE SITE BEFORE SUBMITTING BID, AND VERIFY CONTRACTOR SHALL VISIT THE SITE BEFORE SUBMITTING BID, AND VERIFY DIMENSIONS AND EXISTING CONDITIONS RELATED TO THE WORK. 8. MECHANICAL DRAWINGS ARE DIAGRAMMATIC AND DO NOT NECESSARILY INDICATE MECHANICAL DRAWINGS ARE DIAGRAMMATIC AND DO NOT NECESSARILY INDICATE EVERY REQUIRED OFFSET, FITTING, ETC. DRAWINGS ARE NOT TO BE SCALED FOR DIMENSIONS. TAKE ALL DIMENSIONS FROM CERTIFIED EQUIPMENT DRAWINGS AND FROM THE STRUCTURE ITSELF BEFORE FABRICATING ANY WORK, VERIFY ALL SPACE REQUIREMENTS COORDINATING WITH OTHER TRADES, AND INSTALL THE SYSTEMS IN THE SPACE PROVIDED WITHOUT EXTRA CHARGES TO THE OWNER. 9. ALL WORK SHALL BE INSTALLED IN ACCORDANCE WITH ALL APPLICABLE STATE ALL WORK SHALL BE INSTALLED IN ACCORDANCE WITH ALL APPLICABLE STATE CODES, LOCAL CODES AND OWNER'S STANDARDS INDICATED BY THE CONSTRUCTION DOCUMENTS.
AutoCAD SHX Text
%%UGENERAL NOTES:
AutoCAD SHX Text
ARE NOT NECESSARILY USED
AutoCAD SHX Text
NOTE: ALL SYMBOLS SHOWN ON LEGEND
AutoCAD SHX Text
%%UPIPING
AutoCAD SHX Text
SECTION CUT
AutoCAD SHX Text
POINT OF CONNECTION NEW TO EXISTING
AutoCAD SHX Text
UNDERCUT DOOR 1"
AutoCAD SHX Text U.C. 1"
AutoCAD SHX Text
CHILLED WATER RETURN
AutoCAD SHX Text
CHILLED WATER SUPPLY
AutoCAD SHX Text
COMPRESSED AIR PIPE
AutoCAD SHX Text
%%UMISCELLANEOUS
AutoCAD SHX Text
HEATING WATER SUPPLY
AutoCAD SHX Text
HEATING WATER RETURN
AutoCAD SHX Text HIGH PRESSURE STEAM SUPPLY (700 kPa AND ABOVE)
AutoCAD SHX Text
HIGH PRESSURE STEAM RETURN
AutoCAD SHX Text LOW PRESSURE STEAM SUPPLY (BELOW 200 kPa)
AutoCAD SHX Text
LOW PRESSURE STEAM RETURN
AutoCAD SHX Text
CONDENSATE PUMP DISCHARGE
AutoCAD SHX Text
NATURAL GAS PIPE
AutoCAD SHX Text
STEAM TRAP (SEE SCHEDULE FOR TYPE)
AutoCAD SHX Text
PUMP
AutoCAD SHX Text
SHUT OFF VALVE IN RISER
AutoCAD SHX Text
PLUG OR BALANCING SHUT OFF VALVE
AutoCAD SHX Text
N.O. VALVE WITH LOCKING COVER
AutoCAD SHX Text
%%UCONTROLS
AutoCAD SHX Text
THERMOSTAT/SENSOR
AutoCAD SHX Text T
AutoCAD SHX Text
%%UHVAC DUCTWORK
AutoCAD SHX Text
COMBINATION FIRE/SMOKE DAMPER
AutoCAD SHX Text
TURNING VANE SHOWN IN 90%%D ELBOW
AutoCAD SHX Text
OPPOSED BLADE DAMPER
AutoCAD SHX Text
SECTION THRU SUPPLY AIR DUCT
AutoCAD SHX Text
4 WAY SUPPLY DIFFUSER (UNLESS OTHERWISE NOTED)
AutoCAD SHX Text
BACKDRAFT DAMPER
AutoCAD SHX Text
RETURN AIR GRILLE
AutoCAD SHX Text
SECTION THRU OA, RA OR EXH DUCT
AutoCAD SHX Text
FS
AutoCAD SHX Text
CFM
AutoCAD SHX Text
SIZE
AutoCAD SHX Text
BD
AutoCAD SHX Text
NIGHT THERMOSTAT
AutoCAD SHX Text
HUMIDISTAT SENSOR
AutoCAD SHX Text
STARTER
AutoCAD SHX Text T
AutoCAD SHX Text N
AutoCAD SHX Text H
AutoCAD SHX Text
PRESSURE SWITCH
AutoCAD SHX Text
PS
AutoCAD SHX Text
DIFFERENTIAL AIR PRESSURE SENSOR
AutoCAD SHX Text
SWITCH
AutoCAD SHX Text
APS
AutoCAD SHX Text S
AutoCAD SHX Text
FM
AutoCAD SHX Text
FLOW METER
AutoCAD SHX Text
LOW LIMIT THERMOSTAT
AutoCAD SHX Text
DIFFERENTIAL PRESSURE GAUGE
AutoCAD SHX Text
FLOW SWITCH
AutoCAD SHX Text
FS
AutoCAD SHX Text
LT
AutoCAD SHX Text
DP
AutoCAD SHX Text S
AutoCAD SHX Text
FIRE DAMPER
AutoCAD SHX Text
SMOKE DAMPER
AutoCAD SHX Text
FLEXIBLE CONNECTION
AutoCAD SHX Text
TEMPURATURE CONTROL DAMPER
AutoCAD SHX Text
CFM
AutoCAD SHX Text
SIZE
AutoCAD SHX Text
SUPPLY DIFFUSER
AutoCAD SHX Text
SHEET NUMBER
AutoCAD SHX Text
PROJECT NAME
AutoCAD SHX Text of
AutoCAD SHX Text
325 BROADWAY BOULDER, COLORADO 80305-3328
AutoCAD SHX Text
NATIONAL INSTITUTE OF STANDARDS AND TECHNOLOGY
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DESIGN
AutoCAD SHX Text
APPROVAL
AutoCAD SHX Text ENGINEERING, MAINTENANCE and SUPPORT SERVICES
AutoCAD SHX Text
DATE
AutoCAD SHX Text
SUPV.
AutoCAD SHX Text
BY
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
REVISION
AutoCAD SHX Text
DRAFTING
AutoCAD SHX Text B2 - Room 1330 Walk-In Fume Hood
AutoCAD SHX Text
COOK
AutoCAD SHX Text
MECHANICAL
AutoCAD SHX Text Room 1330 Walk-In Fume Hood
AutoCAD SHX Text
BUILDING 2
AutoCAD SHX Text M-0
AutoCAD SHX Text
WIERSMA
AutoCAD SHX Text
PLANT WATER
AutoCAD SHX Text
LCA
AutoCAD SHX Text
CWR
AutoCAD SHX Text
CWS
AutoCAD SHX Text
HWS
AutoCAD SHX Text
HWR
AutoCAD SHX Text
HPS
AutoCAD SHX Text
HPR
AutoCAD SHX Text
LPS
AutoCAD SHX Text
LPR
AutoCAD SHX Text
CPD
AutoCAD SHX Text
NG
AutoCAD SHX Text
PW
AutoCAD SHX Text
BALL VALVE
AutoCAD SHX Text
BUTTERFLY VALVE
AutoCAD SHX Text
PRESSURE REDUCING VALVE
AutoCAD SHX Text
PRESSURE REDUCING VALVE
1125A
GAS STORAGE
VISCOMETERS
VAPOR
PRESSURE LAB1331
OFFICE
OFFICE
THERMAL
CONDUCTIVITY
LAB
DVME
CHROMATOGRAPHY
COVERED STAIR
DN
FE
FE
FEFE
(E) 15/7 SA
(TYP.)
"Ø
S A
"Ø
S A
(E) 15/13 RA
ABOVE
15/9 RA BELOW
10"Ø CD-SCD
24/24 (TYP.)
20/20
EG-LVR
(TYP.)9/7 SA
18/6 SG-LVR
(TYP. 3)
12"Ø EA
(E) 3" VTR
(E)3" VTR
1 REMOVE FUME HOOD AND BASE CABINET
COMPLETELY
2 REMOVE 10" PVC EXHAUST DUCT
COMPLETELY, TEMPORARILY SEAL
OPENING IN PLEXIGLAS.
MECHANICAL DEMO NOTES:
3 REMOVE EXHAUST FAN ON ROOF
COMPLETELY, INCLUDING ALL
SUPPORTS AND PVC DUCT .
4 REMOVE COUNTER TOP, BASE AND SINK
COMPLETELY.DHW, DCW AND WASTE TO
REMAIN FOR NEW SINK. ROUGH BLACK
SINK BASIN UNDERCOATING IS 3%
NON-FRIABLE ASBESTOS. CONTRACTOR
SHALL DISPOSE OF THE SINK PER STATE
AND FEDERAL REGULATIONS.
SCALE: 1/4" = 1'
FIRST FLOOR DEMO PLAN
PROJECT
AREA
BLDG 2 KEY PLAN
N
N.T.S.
KEYNOTES
1. KEYNOTES
AutoCAD SHX Text
SHEET NUMBER
AutoCAD SHX Text
PROJECT NAME
AutoCAD SHX Text of
AutoCAD SHX Text
325 BROADWAY BOULDER, COLORADO 80305-3328
AutoCAD SHX Text
NATIONAL INSTITUTE OF STANDARDS AND TECHNOLOGY
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DESIGN
AutoCAD SHX Text
APPROVAL
AutoCAD SHX Text ENGINEERING, MAINTENANCE and SUPPORT SERVICES
AutoCAD SHX Text
DATE
AutoCAD SHX Text
SUPV.
AutoCAD SHX Text
BY
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
REVISION
AutoCAD SHX Text
DRAFTING
AutoCAD SHX Text B2 - Room 1330 Walk-In Fume Hood
AutoCAD SHX Text
COOK
AutoCAD SHX Text
MECHANICAL
AutoCAD SHX Text
DEMOLITION
AutoCAD SHX Text Room 1330 Walk-In Fume Hood
AutoCAD SHX Text
BUILDING 2
AutoCAD SHX Text M-1
AutoCAD SHX Text
WIERSMA
AutoCAD SHX Text
NORTH
PLAN
1125A
GAS STORAGE
VISCOMETERS
VAPOR
PRESSURE LAB1331
OFFICE
OFFICE
THERMAL
CONDUCTIVITY
LAB
DVME
CHROMATOGRAPHY
COVERED STAIR
DN
FE
FE
(E) 15/7 SA
(TYP.)
"Ø
S A
(E) 15/13 RA
ABOVE
15/9 RA BELOW
10"Ø CD-SCD
24/24 (TYP.)
9/7 SA
18/6 SG-LVR
(TYP. 3)
(E) 3" VTR
(E)3" VTR
1 PROVIDE WALK-IN FUME HOOD 02-LFH-1330-1
2 PROVIDE 12" PVC DUCTWORK, RE-USE &
ENLARGE OPENING IN PLEXIGLAS.
REPLACE PLEXIGAS IF EXISTING
OPENING CAN NOT BE RE-USED.
MECHANICAL NEW WORK NOTES:
3 EXHAUST FAN 02-EF-LFH-1330-1 ON
ROOF, REFER TO DWG M-4 & M-6.
4 PROVIDE COUNTER TOP , SINK AND BASE
PER SCHEDULE. CONNECT TO EXISTING
DHW, DCW AND WASTE.
SCALE: 1/4" = 1'
FIRST FLOOR PLAN
PROJECT
AREA
BLDG 2 KEY PLAN
N
N.T.S.
KEYNOTES
1. KEYNOTES
AutoCAD SHX Text
SHEET NUMBER
AutoCAD SHX Text
PROJECT NAME
AutoCAD SHX Text of
AutoCAD SHX Text
325 BROADWAY BOULDER, COLORADO 80305-3328
AutoCAD SHX Text
NATIONAL INSTITUTE OF STANDARDS AND TECHNOLOGY
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DESIGN
AutoCAD SHX Text
APPROVAL
AutoCAD SHX Text ENGINEERING, MAINTENANCE and SUPPORT SERVICES
AutoCAD SHX Text
DATE
AutoCAD SHX Text
SUPV.
AutoCAD SHX Text
BY
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
REVISION
AutoCAD SHX Text
DRAFTING
AutoCAD SHX Text B2 - Room 1330 Walk-In Fume Hood
AutoCAD SHX Text
COOK
AutoCAD SHX Text
MECHANICAL
AutoCAD SHX Text
NEW WORK
AutoCAD SHX Text Room 1330 Walk-In Fume Hood
AutoCAD SHX Text
BUILDING 2
AutoCAD SHX Text M-2
AutoCAD SHX Text
WIERSMA
AutoCAD SHX Text
NORTH
FERROMAGNETIC
RESONANCE
LAB
HIGH RATE
TESTING
LIGHT
SCATTERING
LAB
MEMS
ASSEMBLY
MAGNETIC
FORCE
MICROSCOPY
CUSTODIAL
OFFICE
CONFERENCE
MAGNETOMETRY
LAB
MICROSCALE
MECH
TESTING
3/4"
3/4"
1/2"
W
3/4"
G
3/4"
C.O.
4"
1/2"
1-1/2" 1-1/2"
V
2" 1-1/2"
1" 3/4"
2"
G
2-1/2"
4"
2"
1-1/2"
V 2-1/2"
BD
4"
BD
V V
BD
BD
4"
2"
1/2" DCW
3/4"
LOCATION OF NEW SINK
ABOVE, PROVIDE NEW
DCW AND W PIPING AS
NEEDED TO
ACCOMODATE NEW SINK
LOCATION
PROJECT
AREA
BLDG 2 KEY PLAN
N
N.T.S.
KEYNOTES
1. KEYNOTES
AutoCAD SHX Text
SHEET NUMBER
AutoCAD SHX Text
PROJECT NAME
AutoCAD SHX Text of
AutoCAD SHX Text
325 BROADWAY BOULDER, COLORADO 80305-3328
AutoCAD SHX Text
NATIONAL INSTITUTE OF STANDARDS AND TECHNOLOGY
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DESIGN
AutoCAD SHX Text
APPROVAL
AutoCAD SHX Text ENGINEERING, MAINTENANCE and SUPPORT SERVICES
AutoCAD SHX Text
DATE
AutoCAD SHX Text
SUPV.
AutoCAD SHX Text
BY
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
REVISION
AutoCAD SHX Text
DRAFTING
AutoCAD SHX Text B2 - Room 1330 Walk-In Fume Hood
AutoCAD SHX Text
COOK
AutoCAD SHX Text
MECHANICAL
AutoCAD SHX Text
BASEMENT
AutoCAD SHX Text Room 1330 Walk-In Fume Hood
AutoCAD SHX Text
BUILDING 2
AutoCAD SHX Text M-3
AutoCAD SHX Text
WIERSMA
AutoCAD SHX Text
NORTH
WALKWAY PADS
ROOF
18'-6 1/2"
ROOF
22'-8"
02-FAN-0004 02-FAN-0003
02-FAN-0001
12"Ø EA
12"Ø EA THROUGH
PLEXIGLAS, SEAL WATER
TIGHT 20/20 EA DN
02-FAN-0002
20/20 EA DN
12"Ø EA
20/20 EA DN 20/20 EA DN
02-EF-LFH-1330-1
FIELD VERIFY FINAL
LOCATION, COORDINATE
WITH NIST SAFETY FOR
DISTANCE FROM ROOF
EDGE.
(E) (E)
(E) (E)
SCALE: 1/4" = 1'
ROOF PLAN
PROJECT
AREA
BLDG 2 KEY PLAN
N
N.T.S.
KEYNOTES
1. KEYNOTES
AutoCAD SHX Text
SHEET NUMBER
AutoCAD SHX Text
PROJECT NAME
AutoCAD SHX Text of
AutoCAD SHX Text
325 BROADWAY BOULDER, COLORADO 80305-3328
AutoCAD SHX Text
NATIONAL INSTITUTE OF STANDARDS AND TECHNOLOGY
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DESIGN
AutoCAD SHX Text
APPROVAL
AutoCAD SHX Text ENGINEERING, MAINTENANCE and SUPPORT SERVICES
AutoCAD SHX Text
DATE
AutoCAD SHX Text
SUPV.
AutoCAD SHX Text
BY
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
REVISION
AutoCAD SHX Text
DRAFTING
AutoCAD SHX Text B2 - Room 1330 Walk-In Fume Hood
AutoCAD SHX Text
COOK
AutoCAD SHX Text
MECHANICAL
AutoCAD SHX Text
ROOF PLAN
AutoCAD SHX Text Room 1330 Walk-In Fume Hood
AutoCAD SHX Text
BUILDING 2
AutoCAD SHX Text M-4
AutoCAD SHX Text
WIERSMA
AutoCAD SHX Text
NORTH
PROJECT
AREA
BLDG 2 KEY PLAN
N
N.T.S.
KEYNOTES
1. KEYNOTES
AutoCAD SHX Text
SHEET NUMBER
AutoCAD SHX Text
PROJECT NAME
AutoCAD SHX Text of
AutoCAD SHX Text
325 BROADWAY BOULDER, COLORADO 80305-3328
AutoCAD SHX Text
NATIONAL INSTITUTE OF STANDARDS AND TECHNOLOGY
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DESIGN
AutoCAD SHX Text
APPROVAL
AutoCAD SHX Text ENGINEERING, MAINTENANCE and SUPPORT SERVICES
AutoCAD SHX Text
DATE
AutoCAD SHX Text
SUPV.
AutoCAD SHX Text
BY
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
REVISION
AutoCAD SHX Text
DRAFTING
AutoCAD SHX Text B2 - Room 1330 Walk-In Fume Hood
AutoCAD SHX Text
COOK
AutoCAD SHX Text
MECHANICAL
AutoCAD SHX Text
SCHEDULES
AutoCAD SHX Text Room 1330 Walk-In Fume Hood
AutoCAD SHX Text
BUILDING 2
AutoCAD SHX Text M-5
AutoCAD SHX Text
WIERSMA
AutoCAD SHX Text
NORTH
TERMINATE 10' ABOVE CURB
UNLESS INDICATED OTHERWISE.
DISCHARGE STACK PROVIDED BY
FAN MANUFACTURER.
DRAIN
SECURE FAN TO EQUIPMENT
SUPPORTS PER MANUFACTURER
DIRECTIONS
EQUIPMENT SUPPORTS AND SPRING
ISOLATORS PROVIDED BY FAN
MANUFACTURER. CUT AND PATCH
ROOF TO COMPLY WITH ROOF
WARRANTY.
ANCHOR EQUIPMENT
SUPPORTS TO ROOF
STRUCTURE PER
MANUFACTURERS
DIRECTIONS. ANCHORS
SHALL BE ABLE TO
WITHSTAND A WIND LOAD
OF 128 MPH.
GUY WIRE, TYP OF 3
RE-USE EXISTING PLEXIGLASS PANEL
IN WINDOW FRAME.
CUT OUT PENETRATION FOR NEW
DUCT AND PROVIDE CONTINUOUS
SILICONE SEALANT AROUND
PENETRATION AND FRAME.
GUY WIRES
12"Ø PVC EXHAUST
WALK IN FUME HOOD
02-LFH-1330-1
LAB FLOOR
EXHAUST FAN
02-EF-LFH-1330-1
RUBBER FLEX
CONNECTOR
(TYP. OF 2)
FLEXICRAFT
SLV FLEXIBLE
COUPLING OR
APPROVED
EQUAL
LOWER ROOF
UPPER ROOF
NEW 1" Ø GALV. EYEBOLT
WELDED TO TOP OF 4" GALV. PIPE,
ANCHORED TO ROOF. FLASH
AROUND PERIMETER OF PIPE
SUPPORT. WELD TO BASE AND CAP.
ANCHORS SHALL WITHSTAND A
WIND LOAD OF 128 MPH
EXISTING ROOF DECK
CONTRACTOR TO FIELD VERIFY
DEPTH OF EXISTING P.U.F
ROOFING AND MATCH
120V. DUPLEX
OUTLET (1) PER
POST
LOW FLOW ALARM
PROVIDE (3) 2" PASS
THROUGHS ON SIDE,
LOCATION TO BE VERIFIED
WITH COR
12" PVC EXHAUST DUCT
KEYED FAN
SWITCH
PANIC BUTTON
NITROGEN GAS
HELIUM GAS
- IN ORDER TO COMPLY WITH STATE CODES, THE USE OF A VACUUM BREAKER
IS REQUIRED WITH ALL HAND HELD EYE/FACE WASH
- COMPLY WITH ANSI Z358.1-2009
- ASSEMBLE EYE/FACE WASH ASSEMBLY TO HOSE; ORIENT TAB ON ASSEMBLY
AWAY FROM USER.
FIBER WASHER
DECK FLANGE
RUBBER WASHER
8' HOSE
FRONT
VIEW
SIDE
VIEW
2" SUPPLY FROM
WATER HEATER
EXIST. 2" W, VERIFY LOCATION AND SIZE.
RE-LOCATE AS NEEDED ON FLOOR
BELOW FOR NEW LAYOUT
(E) 2"V TO REMAIN,
RELOCATE AS
NEEDED FOR NEW
LAYOUT
CONNECT TO
EXIST. 2" W,
VERIFY LOCATION
AND SIZE.
FAUCET
EXIST. 34" DHW &DCW, VERIFY LOCATION
AND SIZE. RE-LOCATE AS NEEDED ON
FLOOR BELOW FOR NEW LAYOUT. CAP
DHW. PROVIDE NEW BALL VALVE IF
EXISTING VALVES DO NOT HOLD.
SINK
CONNECT TO
EXIST. 34" DCW,
VERIFY LOCATION
AND SIZE.
1/2" DCW
EYE/FACE WASH
3/4" DHW
02-WH-1330-01
3/4" DHW
THERMOSTATIC
MIXING VALVE
. CUT AND PATCH ROOF TO COMPLY
WITH ROOF WARRANTY.
3/4" DHW
PROJECT
AREA
BLDG 2 KEY PLAN
N
N.T.S.
KEYNOTES
1. KEYNOTES
SCALE: NONE
EXHAUST FAN DETAIL
SCALE: NONE
FUME HOOD DETAILSCALE: NONE
GUY WIRE ANCHOR DETAIL
SCALE: NONE
FUME HOOD DETAIL
SCALE: NONE
DECK MOUNT EYE/FACE WASH DETAIL
SCALE: NONE
LAB SINK DETAIL
AutoCAD SHX Text
SHEET NUMBER
AutoCAD SHX Text
PROJECT NAME
AutoCAD SHX Text of
AutoCAD SHX Text
325 BROADWAY BOULDER, COLORADO 80305-3328
AutoCAD SHX Text
NATIONAL INSTITUTE OF STANDARDS AND TECHNOLOGY
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DESIGN
AutoCAD SHX Text
APPROVAL
AutoCAD SHX Text ENGINEERING, MAINTENANCE and SUPPORT SERVICES
AutoCAD SHX Text
DATE
AutoCAD SHX Text
SUPV.
AutoCAD SHX Text
BY
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
REVISION
AutoCAD SHX Text
DRAFTING
AutoCAD SHX Text B2 - Room 1330 Walk-In Fume Hood
AutoCAD SHX Text
COOK
AutoCAD SHX Text
MECHANICAL
AutoCAD SHX Text
DETAILS
AutoCAD SHX Text Room 1330 Walk-In Fume Hood
AutoCAD SHX Text
BUILDING 2
AutoCAD SHX Text M-6
AutoCAD SHX Text
WIERSMA
AutoCAD SHX Text
NORTH
POWER
FS
ABBREVIATIONS (MAY BE COMBINED)
+ - RECEPTACLE TYPE DESIGNATION OR NEMA
CONFIGURATION (APPLIES TO ALL DEVICES)
AC - ABOVE COUNTER
C, C# -CONTROLLED
CL - CLOCK HANGAR
H - HORIZONTALLY MOUNTED
HD - HEAVY DUTY
IG - ISOLATED GROUND
GF - GFCI PROTECTED OUTLET
RC - RECESSED
SW - SWITCHED
TR -TAMPER RESISTANT
USB - USB
WP - WEATHER RESISTANT, WEATHER PROOF
NOTE: ALL RECEPTACLES TO BE NEMA 5-20R UNO
- NEMA PLUG TYPE AS SHOWN
POWER ONLY FLOORBOX CONFIGURATIONS
POWER AND TELECOM FLOORBOX CONFIGURATIONS
POKE THRU DEVICE - REFER TO PLANS FOR CONFIGURATION
J
SIMPLEX
DUPLEX
QUADRUPLEX
GENERATOR BACKED
SPECIAL NEMA TYPE RECEPTACLE
CEILING MOUNTED
FLOOR MOUNTED
RECESSED CLOCK RECEPTACLE
POWER POLE
JUNCTION BOXES: WALL AND CEILING MOUNTED
WM SURFACE MOUNT RACEWAY - WIREMOLD 3000 SERIES
CONDUIT UP, CONDUIT DOWN, CONDUIT STUB OUT
THERMOSTAT
J
T
C
DISCONNECT ABBREVIATIONS:
+ DISCONNECT TAG DESIGNATIONS (APPLIES TO
ALL DISCONNECTING TYPE DEVICES)
TO - THERMAL OVERLOAD
FH - FRACTIONAL HORSEPOWER
FA - FACTORY APPLIED
M - MANUAL MOTOR STARTER
OL - SIZE INDICATED ON ONE-LINE
3R - NEMA 3R RATING
4X - NEMA 4X RATING
12X - NEMA 12X RATING
XP - EXPLOSION PROOF
WP - WEATHER PROOF
FUSED AND NON-FUSED DISCONNECT
XX/X/XX/X =
AMPS/POLES/(FUSE SIZE/TYPE)/ENCLOSURE RATING
ENCLOSED CIRCUIT BREAKER
XX/X/X/X = FRAME/POLES/TRIP/ENCLOSURE RATING
S+
FUSED DISCONNECT
ELECTRICAL EQUIPMENT
NON-FUSED DISCONNECT
ENCLOSED CIRCUIT BREAKER
F XX/X/XX/X
XX/X/XX/X
C XX/X/XX/X
PNL
PNL
MM M
T TX-
DISCONNECT
WIRING DEVICES
RECEPTACLES
SURFACE OR FLUSH MOUNT ELECTRICAL PANEL
RECESSED ELECTRICAL PANEL
DISTRIBUTION PANELBOARD
SWITCHBOARD
MOTOR CONTROL CENTER
SWBD
D. PNL
MCC MCC
TRANSFORMER
MGB
MAIN GROUNDING BAR, GROUNDING BAR
FS
FS
FS
FS
VFD
SSRV
VARIABLE FREQUENCY DRIVE
STARTER, SOLID STATE REDUCED VOLTAGE STARTER
EMERGENCY POWER OFF PUSH BUTTON, PUSH BUTTON
HAND ON-OFF AUTO, PUSH BUTTON STOP-START
INDICATING LIGHT
TELECOMMUNICATIONS
IN-WALL TV BOX
WALL MOUNTED TELECOMMUNICATIONS OUTLET
TELECOMMUNICATIONS FLOORBOX OUTLET
TELECOMMUNICATIONS POKE-THRU DEVICE
CEILING MOUNTED TELECOMMUNICATIONS OUTLET
WIRELESS ACCESS POINT
LOW VOLTAGE PUSH BUTTON
SPEAKER
TV
WAP
XXX ELECTRICAL EQUIPMENT
TMGB TGB
TELECOM MAIN GROUND BAR, TELECOM GROUND BAR
TELECOMMUNICATIONS BACKING BOARDTB
CR
GB
PN
ELECTRICAL METERS
CARD READER
GLASS BREAK SENSOR
PUBLIC NOTIFICATION SPEAKER
SECURITY & LOW VOLTAGE DEVICES
S
ABBREVIATIONS
AF AMPERE FUSE SIZE
AFC ABOVE FINISHED CEILING
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHJ AUTHORITY HAVING JURISDICTION
AHU AIR HANDLING UNIT
AIC AMPERE INTERRUPTING CAPACITY
AS AMPERE SWITCH SIZE
AT AMPERE TRIP SETTING
ATS AUTOMATIC TRANSFER SWITCH
AV AUDIO VISUAL
BAS BUILDING AUTOMATION SYSTEM
BKR BREAKER
C CONDUIT
CAT CATEGORY
CATV CABLE TELEVISION SYSTEM
CCTV CLOSED CIRCUIT TELEVISION
CD CANDELA
CKT CIRCUIT
CODE APPLICABLE CODE ADOPTED BY
JURISDICTION
CT CURRENT TRANSFORMER
CTR CENTER
CTRL CONTROL/CONTROLLED
CVD CUMULATIVE VOLTAGE DROP
D/DEMO DEMOLITION
DPDT DOUBLE-POLE,DOUBLE-THROW
DPST DOUBLE-POLE, SINGLE-THROW
E/ETR/EX EXISTING TO REMAIN
EC ELECTRICAL CONTRACTOR
EF EXHAUST FAN
EM EMERGENCY
EMS ENERGY MANAGEMENT SYSTEM
ELV ELECTRONIC LOW-VOLTAGE
ERMS ENERGY REDUCING MAINTENANCE SWITCH
EWC ELECTRIC WATER COOLER
FAAP FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FBO FURNISHED BY OTHERS
FCA FAULT CURRENT AMPS AVAILABLE
FCU FAN COIL UNIT
FF FINISHED FLOOR
FLA FULL LOAD AMPS
FLR FLOOR
GC GENERAL CONTRACTOR
GEC GROUNDING ELECTRODE CONDUCTOR
GES GROUNDING ELECTRODE SYSTEM
GFR GROUND FAULT RELAY
G GROUND
IG ISOLATED GROUND
ISC SHORT CIRCUIT CURRENT
JB/J-BOX JUNCTION BOX
LF LINEAR FEET
LRA LOCKED ROTOR AMPS
LTG/LTS LIGHTING/LIGHTS
MAU MAKE-UP AIR UNIT
MAX MAXIMUM
MCA MINIMUM CIRCUIT AMPACITY
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MFR MANUFACTURER
MIN MINIMUM
MLO MAIN LUGS ONLY
MLV MAGNETIC LOW-VOLTAGE
MOCP MAXIMUM OVERCURRENT PROTECTION
MTD MOUNTED
N/A NOT APPLICABLE
NF NON-FUSED
NL NIGHT LIGHT (24HR ON)
NIC NOT IN CONTRACT
NIS NOT IN SCOPE
NIST NATIONAL INSTITUTE OF STANDARDS &
TECHNOLOGY
NRTL NATIONALLY RECOGNIZED TESTING
LABORATORY(CSA,ETL,NSF,UL)
NTS NOT TO SCALE
OFPM NIST OFFICE OF FACILITIES &PROPERTY
MAINTENANCE
OS OCCUPANCY SENSOR
OSHE OFFICE OF SAFETY, HEALTH & ENVIRONMENT
P POLE
PART PARTIAL CIRCUIT
PH/Ø PHASE
PNL PANEL
PNLBD PANELBOARD
PROVIDE FURNISH AND INSTALL
PT POTENTIAL TRANSFORMER
QTY QUANTITY
R/REL RELOCATE
RCPT RECEPTACLE
RLA RUNNING LOAD AMPS
RTU ROOFTOP UNIT
SCCR SHORT-CIRCUIT CURRENT RATING
SD SMOKE DUCT DETECTOR
SF SQUARE FEET
SPDT SINGLE-POLE,DOUBLE-THROW
SPST SINGLE-POLE,SINGLE-THROW
SSBJ SUPPLY-SIDE BONDING JUMPER
ST SHUNT TRIP
SWBD SWITCHBOARD
SWGR SWITCHGEAR
TBB TELECOMMUNICATIONS BONDING
BACKBONE
TBD TO BE DETERMINED
TGB TELECOMMUNICATIONS GROUND BUS BAR
TL TWISTLOCK
TMGB TELECOMMUNICATIONS MAIN GROUND BUS
BAR
TX/XFMR TRANSFORMER
TYP TYPICAL
UF UNDERFLOOR
UG UNDERGROUND
US UNDERSLAB
UH UNIT HEATER
UNO UNLESS NOTED OTHERWISE
UPS UNINTERRUPTIBLE POWERSUPPLY
VD VOLTAGE DROP
VFD VARIABLE FREQUENCY DRIVE
VS VACANCY SENSOR
W WIRE
W/ WITH
WP/WR WEATHER PROOF/WEATHER RESISTANT
WT WATERTIGHT
XP EXPLOSION-PROOF
NOTE: LIST IS NOT EXHAUSTIVE, NOT ALL ABBREVIATIONS SHOWN WILL BE USED
UTILIZATION EQUIPMENT
NAMEPLATE DETAIL
EXHAUST FAN #1
FED FROM H1A
480V 3¢ HP
SCALE: FULL
NOTES:
1. SEE SPECIFICATIONS FOR ADDITIONAL NAMEPLATE INFORMATION.
2. REWORD NAMEPLATE FOR FIELD CONDITIONS.
3. HP SHALL INDICATE HORSEPOWER
SUB-DISTRIBUTION CENTER
AND BRANCH PANELBOARD
NAMEPLATE DETAIL
EQUIPMENT NAME
FED FROM X-XXXX-XX
120/208V 3¢ 4W 225A
22,000 AIC
PH A - BLACK; PH B - RED; PH C - BLUE
GROUND - GREENNEUTRAL - WHITE;
SCALE: FULL
NOTES:
1. SEE SPECIFICATIONS FOR NAMING CONVENTIONS AND ADDITIONAL
2. NAMEPLATE COLOR AND INFORMATION REQUIREMENTS.
3. REWORD NAMEPLATE FOR FIELD CONDITIONS.
4. AMP RATING SHALL INDICATE BUS RATING.
T
TYPICAL 9'-0 " CLNG OR HIGHER
TYPICAL 8'-0" CEILING
FlNISHED FLOOR
BOTTOM OF DEVICE
TOP OF CABINET
TOP OF CABINET
TOP OF CABINET
TOP OF DEVICE
TYPICAL DEVICE MOUNTING HEIGHTS
" U
N O
" U
N O
" U
N O
" U
N O
" U
N O
" U
N O
" U
N O
" U
N O
FACP
FAA TC GZM TV
S FS FS
T.O.D.
SCALE: NONE
NOTES:
1. HEIGHTS SHOWN ARE TYPICAL TO CENTERLINE OF BOX UNLESS NOTED OTHERWISE.
2. WHENEVER DEVICES ARE INDICATED TO BE ABOVE DOORS, DEVICE SHALL BE CENTERED BETWEEN THE DOOR
TRIM AND THE CEILING LINE.
3. MOUNTING HEIGHTS SHOWN ON ARCHITECTURAL ELEVATIONS SHALL GOVERN OVER THOSE SHOWN ABOVE.
4. ALL DEVICES INDICATED TO BE INSTALLED AT DIFFERENT MOUNTING HEIGHTS AND LOCATED WITHIN ONE
STUD SPACE FROM EACH OTHER SHALL ALIGN VERTICALLY, ON THE SME SIDE OF THE STUD. WHERE WALL MOUNTED TELEPHONE OCCUR OVER LIGHT SWITCHES, VOLUME CONTROLS, ETC. OFFSET ONE STUD SPACE.
PNL
LCP
CR
XX
x
XX
x
H LF V
F
CONTROL
PANELS
LIFE SAFETY SPEAKER, LIFE SAFETY SPEAKER/STROBE
HORN, HORN STROBE, STROBE
PULL STATION
SMOKE DETECTOR: TYPE DESIGNATIONS ABBREVIATIONS
P - PHOTOELECTRIC
I - IONIZATION
T - COMBINATION
TF - COMPENSATION
PT - PHOTOELECTRIC AND THERMAL
TF165 - COMBINATION 165 DEGREES
TF165 - COMPENSATION 165 DEGREES
T190 - COMBINATION 190 DEGREES
TF190 - COMPENSATION 190 DEGREES
FIRE ALARM DEVICES
L
H
F P
F
FACP
L
F V
FIRE ALARM CONTROL PANEL, FIRE ALARM ANNUNCIATOR
PANEL
FAAP
F MAGNETIC FIRE DOOR HOLDERS
NEW CONNECTION TO EXISTING CIRCUIT
USER EQUIPMENT TAG
ANNOTATIONS
FLAG NOTE
E-XX
UPPER - DETAIL NUMBER
LOWER - SHEET NUMBER
X1.0
# REVISION DELTA
SYMBOLS USING THESE LINE WEIGHTS INDICATE PHASING RELATIVE OTHER
DEVICES ON SHEET. THIS DOES NOT INDICATE ALL CONSTRUCTION PHASING,
CONTRACTOR IS RESPONSIBLE FOR ALL CONSTRUCTION PHASING IN THE PROJECT.
DEMOLISH
NEW
LINE TYPE, CIRCUITING AND HATCHING LEGEND
EXISTING
FUTURE
NIC - NOT IN CONTRACT
OR
NIS - NOT IN SCOPE
HOME RUN
UNDER FLOOR/UNDERGROUND CONDUIT
CIRCUIT CONTINUATION OR PARTIAL CIRCUIT
LOW VOLTAGE CONDUCTORS
CONNECTION POINT/EQUIP. TERMINATION
LUMINAIRES AND LIGHTING CONTROLS
SHADING INDICATES EMERGENCY LIGHT
XX = FIXTURE TYPE, REFERENCE LUMINAIRE SCHEDULE
x = SWITCH LEG DESIGNATION
LIGHT FIXTURES
XX
x
XX
x
XX
x
SURFACE MOUNTED LENSED FIXTURES
XX
x
XX
x
X
XX
x
XX
x
RECESSED LENSED FIXTURES
SUSPENDED LENSED FIXTURES
RECESSED DOWNLIGHTS
RECESSED DIRECTIONAL DOWNLIGHTS
LINEAR STRIP FIXTURE
XX
x
WALL MOUNTED SCONCE
CEILING MOUNTED DECORATIVE PENDENT FIXTURE
BOLLARD
POLE MOUNTED SITE LIGHTING (UP TO 4 HEADS)
EMERGENCY LIGHTING UNIT
CEILING MOUNTED EXIT SIGN (NOT ALL CONFIG. SHOWN)
WALL MOUNTED EXIT SIGN (NOT ALL CONFIG. SHOWN)
WALL MOUNTED LINEAR SCONCE
REFER TO LIGHT FIXTURE SCHEDULE FOR MORE INFORMATION
CAMERA
DOOR-IN-DOOR PANEL FRONT
SCALE: NONE
NOTES:
1. ALL BOLTS SHALL HAVE LARGE (3/8") ROUND HEAD. NO WASHERS ALLOWED.
2. TYPICAL FOR ALL 120/208V AND 277/480V BRANCH PANELBOARDS.
3. DETAIL IS FOR REFERENCE ONLY AND DOES NOT REFLECT ALL AVAILABLE
4. MANUFACTURER'S PANELBOARD CONSTRUCTION OR ORIENTATION(S).
PANELBOARD NAMEPLATE
SIDEMOUNTED HINGE FOR
SURFACE MOUNTED PANELS
ARC-FLASH HAZARD LABEL
OUTER LOCK
TWO INNER LOCKS IF INNER
DOOR IS OVER 36" HIGH
FLUSH LATCH AND LOCK
PIANO HINGE FOR
PANEL TRIM
CONCEALED HINGE (TYP)
OUTER LOCK
1/4-20-LARGE HEAD
SLOTTED SCREWS (TYP)
PNL
NAME
ARC-
FLASH
LIGHTING CONTROLS
SWITCH TYPES:
+ - SWITCH TYPE DESIGNATION (APPLIES TO ALL DEVICES)
NONE - SINGLE POLE
2 - DOUBLE POLE
3 - 3-WAY
4 - 4-WAY
D - LINE VOLTAGE DIMMER
K - KEY-OPERATED
OS# - OCCUPANCY/VACANCY SENSOR
L# - LOW VOLTAGE NON-NETWORKABLE
B# - LOW VOLTAGE NETWORKABLE
T - TIME SWITCH
P - PILOT LIGHT
# - INDICATES DEVICE INSTANCE REFER TO PLANS FOR
MORE INFORMATION
PC
ROOM CONTROLLER (NETWORKABLE, REFER TO SCHEDULES)
POWER PACK (NON-NETWORKABLE, REFER TO SCHEDULES)
PHOTOCELL
CEILING MOUNTED OCCUPANCY SENSOR (REFER TO SCHEDULES)
CORNER MOUNTED OCCUPANCY SENSOR (REFER TO SCHEDULES)
LIGHTING CONTROL PANELLCP
R01
C#
CL#
CONTACTOR
CURRENT LIMITING DEVICE
BTS
ALC
BRANCH CIRCUIT TRANSFER SWITCH
AUTOMATIC LOAD CONTROL RELAY
S+
LIGHTING CONTROLS
SWITCH TYPES:
+ - SWITCH TYPE DESIGNATION (APPLIES TO ALL DEVICES)
NONE - SINGLE POLE
2 - DOUBLE POLE
3 - 3-WAY
4 - 4-WAY
D - LINE VOLTAGE DIMMER
K - KEY-OPERATED
OS# - OCCUPANCY/VACANCY SENSOR
L# - LOW VOLTAGE NON-NETWORKABLE
B# - LOW VOLTAGE NETWORKABLE
T - TIME SWITCH
P - PILOT LIGHT
# - INDICATES DEVICE INSTANCE REFER TO PLANS FOR
MORE INFORMATION
PC
ROOM CONTROLLER (NETWORKABLE, REFER TO SCHEDULES)
POWER PACK (NON-NETWORKABLE, REFER TO SCHEDULES)
PHOTOCELL
CEILING MOUNTED OCCUPANCY SENSOR (REFER TO SCHEDULES)
CORNER MOUNTED OCCUPANCY SENSOR (REFER TO SCHEDULES)
LIGHTING CONTROL PANELLCP
R01
C#
CL#
CONTACTOR
CURRENT LIMITING DEVICE
BTS
ALC
BRANCH CIRCUIT TRANSFER SWITCH
AUTOMATIC LOAD CONTROL RELAY
S+
P#
SHEET NUMBER
PROJECT NAME of
325 BROADWAY BOULDER, COLORADO 80305-3328
NATIONAL INSTITUTE OF STANDARDS AND TECHNOLOGY
DATEDESIGN APPROVAL
ENGINEERING, MAINTENANCE and SUPPORT SERVICES
DATESUPV.BYDESCRIPTIONREVISION
3 DRAFTING
B2 - Room 1330 Walk-In Fume Hood
SJM
ELECTRICAL
Room 1330 Walk-In Fume Hood
BUILDING 2
01/30/2026
E-0SJM
SHEET NUMBER
PROJECT NAME of
325 BROADWAY BOULDER, COLORADO 80305-3328
NATIONAL INSTITUTE OF STANDARDS AND TECHNOLOGY
DATEDESIGN APPROVAL
ENGINEERING, MAINTENANCE and SUPPORT SERVICES
DATESUPV.BYDESCRIPTIONREVISION
3 DRAFTING
B2 - Room 1330 Walk-In Fume Hood
SJM
ELECTRICAL
Room 1330 Walk-In Fume Hood
E-1SJM
1. PRIOR TO SUBMITTING BID, VISIT THE JOB SITE AND BECOME FULLY ACQUAINTED
WITH THE EXISTING CONDITIONS. REVIEW OFPM/NIST PROJECT CRITERIA, GENERAL
NOTES, OTHER TRADE DRAWINGS AND OFPM/NIST SPECIFICATIONS FOR ADDITIONAL
REQUIREMENTS THAT MAY NOT BE CALLED OUT IN THIS PORTION OF THE
CONSTRUCTION DOCUMENTS. READ THE SPECIFICATIONS AND REVIEW DRAWINGS OF
ALL DIVISIONS OF WORK. COORDINATE THIS WORK WITH ALL OTHER DIVISIONS OF
WORK AND ALL SUBCONTRACTORS. PROVIDE ALL SUBCONTRACTORS WITH A
COMPLETE SET OF BID DOCUMENTS. NOTIFY ARCHITECT AND ENGINEER OF ANY
CONFLICTS OR DISCREPANCIES PRIOR TO SUBMITTING BID.
2. DRAWINGS ARE DIAGRAMMATIC ONLY AND REPRESENT THE GENERAL SCOPE OF
WORK. REVIEW THE GENERAL NOTES, SPECIFICATIONS, AND PLANS FOR ADDITIONAL
REQUIREMENTS THAT MAY NOT BE SPECIFICALLY NOTED IN THIS PORTION OF THE
CONSTRUCTION DOCUMENTS. IT IS NOT WITHIN THE SCOPE OF THE ELECTRICAL
DRAWINGS TO SHOW ALL NECESSARY RACEWAY ROUTING, BENDS, OFFSETS, PULL
BOXES AND OBSTRUCTIONS. THE DRAWINGS REPRESENT THE BEST INFORMATION
AVAILABLE TO THE ENGINEER. ALL DIMENSIONS AND SIZES SHALL BE FIELD VERIFIED.
DO NOT SCALE FROM THE DRAWINGS. SMALL DEVIATIONS SHALL BE RECONCILED
DURING THE PERFORMANCE OF THE WORK. NOTIFY THE ARCHITECT OF ANY
CONFLICTS OR DISCREPANCIES PRIOR TO SUBMISSION OF BID.
3. ALL WORK SHALL CONFORM TO OFPM/NIST STANDARDS, ALL NATIONAL CODES AS
WELL AS APPLICABLE INDUSTRY STANDARDS. ALL EQUIPMENT SHALL BEAR LABELS FOR
THE USE INTENDED BY AN ACCEPTED NATIONALLY RECOGNIZED TESTING
LABORATORY(NRTL), SUCH AS UL OR ETL. THE FINAL ELECTRICAL INSTALLATION OF THE
FACILITY SHALL BE FREE FROM ELECTRICAL DEFECTS TO THE SATISFACTION OF
OFPM/NIST PERSONNEL.
4. COORDINATE FINAL LOCATION AND INSTALLATION REQUIREMENTS OF ALL WORK:
LIGHT FIXTURES, ELECTRICAL EQUIPMENT AND ELECTRICAL DEVICES, ETC. WITH
ARCHITECTURAL DRAWINGS, EXISTING CONDITIONS AND OTHER TRADES AND
CONTRACTORS PRIOR TO ROUGH-IN. PROVIDE ALL NECESSARY DEVICES, CORDS,
PLUGS, DISCONNECTS AND FINAL CONNECTIONS TO ELECTRICAL EQUIPMENT FOR
PROPER OPERATION IN ACCORDANCE WITH CODE, OWNER AND MANUFACTURER
REQUIREMENTS
5. REFER TO OFPM/NIST STANDARDS DOCUMENTS: CONDUIT AND LABEL COLOR CHART
FOR COLOR CODING CONDUITS AND LABELING OF SYSTEMS BY SYSTEM TYPE.
ELECTRICAL STANDARDS FOR SYSTEM PERFORMANCE CRITERIA. EQUIPMENT LIST AND
IDS FOR EQUIPMENT LABEL IDENTIFICATION.
6. DRAWINGS AND SPECIFICATIONS GOVERN, WHERE THEY EXCEED CODE
REQUIREMENTS. SYSTEM INSTALLATION SHALL COMPLY WITH LEGALLY CONSTITUTED
CODES AND THE REQUIREMENTS OF NIST/OFPM.
7. FIELD VERIFY EXACT LOCATIONS AND ELECTRICAL REQUIREMENTS OF ALL HVAC AND
PLUMBING EQUIPMENT WITH OTHER TRADE CONTRACTORS PRIOR TO ORDERING
RELATED ELECTRICAL EQUIPMENT.
8. ROOM NAMES/NUMBERS SHOWN IN PANELBOARD SCHEDULES ARE PER
ARCHITECTURAL FLOOR PLANS. CONTRACTOR SHALL PROVIDE FINALIZED PANELBOARD
SCHEDULES AT COMPLETION OF PROJECT WITH NIST PROVIDED ROOM
NAMES/NUMBERS. SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION. PROVIDE
UPDATED TYPED PANEL DIRECTORIES TO REFLECT WORK PERFORMED UNDER THIS
CONTRACT.
9. PROVIDE A CONSTRUCTION RECORD SET OF "AS-BUILT" DOCUMENTS REFLECTING ANY
VARIANCES OF INSTALLED PIPING, EQUIPMENT DEVICES, ETC LOCATIONS THAT ARE
CONTRARY TO THE CONSTRUCTION DOCUMENTS. REFER TO SPECIFICATIONS FOR
ADDITIONAL INFORMATION.
10. WHERE DEVICES ARE MOUNTED RECESSED IN CMU WALLS, ROUTE CONDUIT
CONCEALED WITHIN INTERIOR OPENINGS WITHIN CMU WALL. COORDINATE WITH
GENERAL CONTRACTOR PRIOR TO ROUGH-IN.
11. ALL DEVICES SHOWN DIRECTLY ADJACENT TO EACH OTHER SHALL BE INSTALLED
DIRECTLY ADJACENT TO EACH OTHER, U.N.O. ADJACENT DEVICES OF SIMILAR TYPE
SHALL BE PROVIDED WITH SINGLE FACEPLATE WHERE FEASIBLE.
12. ALL APPLICABLE SWITCHES, RECEPTACLES, OUTLETS, AND CONTROLS SHALL BE PLACED
AT HEIGHTS THAT ARE IN ACCORDANCE WITH ADA ACCESSIBILITY GUIDELINES.
13. ALL JUNCTION BOXES SHALL BE RIGIDLY ATTACHED TO STRUCTURE OR MILLWORK.
14. ALL WP OUTLET BOX HOODS SHALL BE “EXTRA-DUTY” AND “WHILE-IN-USE COVER”
TYPE. OUTLET BOX HOODS SHALL BE LOW PROFILE WHEREVER PRACTICABLE, UNLESS
NOTED OTHERWISE. THE USE OF LARGE BUBBLE COVERS SHALL BE AVOIDED ON THE
EXTERIOR OF THE BUILDING OR BEHIND EQUIPMENT IN ORDER TO PREVENT DAMAGE
TO THE COVER AND TO ALLOW THE EQUIPMENT TO BE LOCATED CLOSE TO THE WALL.
15. REFER TO ARCHITECTURAL PLANS AND DETAILS FOR EXACT LOCATIONS, ALIGNMENT,
AND MOUNTING OF ALL CEILING, WALL, AND FLOOR MOUNTED DEVICES.
16. CONDUIT AND BOX ROUGH-IN FOR ADJACENT FIRE ALARM, TEMPERATURE CONTROLS,
RECEPTACLES, LIGHTING CONTROL DEVICES, ETC, ON THE SAME WALL, SHALL BE
PROVIDED IN A MANNER TO WHICH DEVICES ALIGN VERTICALLY ON SAME WALL.
COORDINATE WITH OTHER TRADES.
17. REFER TO TELECOM DRAWINGS FOR BOXES, FLOOR BOXES, RACEWAYS, PATHWAYS,
AND CABLE TRAY TO BE BID AS PART OF THE MEP/FP PACKAGE. REFER TO
SPECIFICATION 260510 FOR ADDITIONAL INFORMATION.
18. COORDINATE CONDUIT PENETRATIONS THROUGH SLABS WITH STRUCTURAL
DOCUMENTS. CONDUITS ARE NOT TO BE ROUTED WITHIN A COMPOSITE SLAB. X-RAY
CONCRETE PRIOR TO CORE DRILLING AND/OR SAW CUTTING
19. WHERE SPARE CONDUIT(S) ARE INDICATED FOR FUTURE USE, PROVIDE PULL STRINGS
IN CONDUIT(S) AND PROTECTIVE BUSHINGS AT OPENINGS. CAP CONDUITS WHERE
LOCATED BELOW GRADE OR EXPOSED TO THE ELEMENTS.
20. REFER TO MECHANICAL EQUIPMENT SCHEDULES FOR ELECTRICAL SCOPE OF WORK, IN
ADDITION TO WORK SHOWN ON ELECTRICAL DRAWINGS.
21. PROVIDE RECESSED CONDUIT AND OUTLET BOXES FOR ALL HVAC CONTROL
LOCATIONS. PROVIDE CONDUIT FOR ALL CONTROLS WIRING LOCATED IN SPACES WITH
EXPOSED CEILINGS. REFER TO MECHANICAL DOCUMENTS AND SCHEDULES FOR ALL
DEVICE LOCATIONS. COORDINATE WORK WITH MECHANICAL CONTRACTOR.
22. PROVIDE ALL MISCELLANEOUS STEEL REQUIRED FOR THE PROPER INSTALLATION OF
ELECTRICAL EQUIPMENT AND SYSTEMS.
23. FOR NEW WORK IN EXISTING BUILDINGS POWER AND TELECOM OUTLETS TO BE
PROVIDED IN SURFACE MOUNT RACEWAYS, WIREMOLD 3000 SERIES.
24. REFER TO SPECIFICATIONS AND DETAILS FOR APPROVED CABLE AND RACEWAY
INSTALLATION. NON-COMPLIANT INSTALLATIONS OF CABLE AND RACEWAY WILL NOT
BE ACCEPTED AND WILL BE REQUIRED TO BE BROUGHT TO COMPLIANCE AT NO COST
TO THE OWNER, PRIOR TO COMPLETION OF WORK.
25. ALL NEW AND EXISTING ELECTRICAL EQUIPMENT ALTERED UNDER THIS PROJECT SHALL
BE VACUUM CLEANED OF ANY DEBRIS. ALL OPENINGS REMAINING SHALL BE SEALED
WITH THE PROPER DEVICE (IE. KNOCKOUT BLANKS, BREAKER BLANKS, ETC) LISTED AND
APPROVED FOR USE.
26. NO WORK SHALL BE PERFORMED PRIOR TO REVIEW AND APPROVAL OF ALL REQUIRED
SHOP DRAWINGS, PRODUCT MATERIALS, AND EQUIPMENT SUBMITTALS. ANY WORK
INSTALLED PRIOR TO MEETING THESE REQUIREMENTS SHALL BE DONE SO AT THE SOLE
RISK OF THIS CONTRACTOR.
27. PROVIDE PROPER FIRE PROOFING AND SEALANT FOR PENETRATIONS THROUGH FIRE
RATED ASSEMBLIES. THE FIRE STOPPING METHOD, MATERIAL AND ITS APPLICATION
SHALL BE NRTL LISTED, CODE COMPLIANT AND APPROVED BY OFPM/OSHE/NIST.
1. THE ELECTRICAL DRAWINGS INDICATE EXISTING ELECTRICAL ITEMS TO BE REMOVED.
THE DRAWINGS ARE INTENDED TO INDICATE THE SCOPE OF WORK REQUIRED AND DO
NOT INDICATED EVERY BOX, CONDUIT, OR WIRE THAT MUST BE REMOVED.
CONTRACTOR SHALL INSPECT THE SITE PRIOR TO THE SUBMISSION OF A BID.
CONTRACTOR SHALL INFORM THEMSELVES OF THE CONDITIONS UNDER WHICH THE
WORK IS TO BE PERFORMED CONCERNING THE SITE OF THE WORK, THE OBSTACLES
WHICH MAY BE ENCOUNTERED, THE DEMOLITION, AND TEMPORARY REMOVAL AND
REINSTALLATION REQUIRED TO PROVIDE ACCESS TO THE WORK, AND ALL OTHER
RELEVANT MATTERS CONCERNING THE WORK TO BE PERFORMED.
2. CONTRACTOR SHALL REPAIR ALL DAMAGE TO EXISTING BUILDING, FIXTURES, AND
FINISHED CAUSED BY CONTRACTOR DURING THE PERFORMANCE OF THE WORK.
REPAIRS SHALL BE PERFORMED BY A QUALIFIED TRADESMEN AND SHALL BE
COMPLETED IN A MANNER ACCEPTABLE TO THE OWNER.
3. REMOVAL OF CONDUITS SHALL INCLUDE REMOVAL OF HANGERS, SUPPORTS, AND
ASSOCIATED MISCELLANEOUS MATERIALS.
4. ALL PIPING, TUBING, CONDUITS, ETC. MADE OBSOLETE, BY WORK UNDER THIS
CONTRACT, EXPOSED OR IN CONFLICT WITH NEW WORK, ARE TO BE REMOVED. REPAIR
ALL HOLES IN WALLS, FLOORS, AND CEILING TO MATCH EXISTING CONDITIONS AND
MAINTAIN FIRE/SMOKE RATINGS.
5. IT SHALL BE THE RESPONSIBILITY OF THIS CONTRACTOR TO PERFORM ALL SELECTIVE
DEMOLITION NECESSARY TO PERFORM THE WORK SHOWN ON THE DRAWINGS EXCEPT
WHERE SAID DEMOLITION IS SHOWN ON THE ARCHITECTURAL DRAWINGS TO BE
PERFORMED BY THE GENERAL CONTRACTOR.
6. SHOULD ACTUAL CONDITIONS DEVIATE SUBSTANTIALLY FROM THOSE INDICATED ON
THE DRAWING, CONTRACTOR SHALL NOTIFY ENGINEER AND REQUEST INSTRUCTIONS.
7. NIST SHALL HAVE THE RIGHT TO SALVAGE ANY AND ALL MATERIALS AND EQUIPMENT
OR PORTION THEREOF. ALL REMOVED EQUIPMENT MATERIALS NOT RETAINED BY NIST
SHALL BE PROMPTLY REMOVED FROM NIST FACILITIES AND LEGALLY DISPOSED OF.
GENERAL DEMOLITION NOTES
1. CONNECTIONS TO FIRE ALARM SYSTEM TO BE DESIGN BUILD BY QUALIFIED
LICENSED FIRE ALARM CONTRACTOR. FIRE ALARM CONTRACTOR TO SUBMIT
SIGNED AND STAMPED DRAWINGS OF FIRE ALARM SYSTEM AS A SUBMITTAL TO
NIST LIFE SAFETY OFFICE PRIOR TO BEGINNING ANY WORK.
2. PROVIDE UL RATED FIRE STOPPING ASSEMBLIES AT ALL PENETRATIONS OF FIRE
RATED CONSTRUCTION. SEAL ALL PENETRATIONS OF SMOKE WALLS SMOKE TIGHT.
3. FIRE ALARM CONTRACTOR SHALL PROVIDE ALL WORK (HARDWARE, SOFTWARE,
PROGRAMMING, WIRE, CONDUIT, ETC.) NECESSARY TO PROVIDE A COMPLETE
AND CODE COMPLIANT SYSTEM.
4. REMOVE ALL FIRE ALARM COMPONENTS, INCLUDING WIRE AND CONDUIT MADE
OBSOLETE BY WORK PERFORMED UNDER THIS CONTRACT. PROVIDE NECESSARY
SOFTWARE AND PROGRAMMING REVISIONS.
5. ALL FIRE DETECTION SYSTEM WIRE TO BE UL PLENUM RATED PER NIST
STANDARDS. WIRE TO BE INSTALLED IN RACEWAYS PER NIST STANDARDS .
6. LABEL ALL FIRE DETECTION SYSTEM WIRE AND RACEWAY PER THE SPECIFICATIONS
AND TO MATCH EXISTING FACILITY IDENTIFICATION SYSTEM.
GENERAL FIRE ALARM NOTES
1. ALL CIRCUITY SHALL BE #12 AWG IN 1/2" CONDUIT, MINIMUM, UNLESS
OTHERWISE NOTED.
2. PROVIDE A SEPARATE CODE SIZED GREEN EQUIPMENT GROUNDING CONDUCTOR
IN ALL CONDUITS AND RACEWAYS CONTAINING LINE VOLTAGE CIRCUITS. FOR ALL
20A CIRCUITS, EQUIPMENT GROUNDING CONDUCTOR SHALL MATCH PHASE
CONDUCTOR SIZE. FOR CIRCUITS UPSIZED DUE TO VOLTAGE DROP, INCREASE
EQUIPMENT GROUNDING CONDUCTOR SIZE PER NEC 2017 250.122.B.
3. PROVIDE A MINIMUM OF FOUR (4) SPARE 1" CONDUITS FROM RECESSED
PANELBOARDS, UP TO ACCESSIBLE CEILING SPACE.
4. PROVIDE A NEUTRAL CONDUCTOR TO THREE-PHASE EQUIPMENT WHEREVER
REQUIRED BY THE EQUIPMENT MANUFACTURER.
5. ALL SINGLE PHASE 120V, 208V OR 240V RECEPTACLES 50A OR LESS, AND THREE
PHASE 208V AND 240V RECEPTACLES 100A OR LESS, SHALL BE GFCI PROTECTED IN
LOCATIONS REQUIRED BY CODE; THIS INCLUDES BATHROOMS, KITCHENS/FOOD
PREP AREAS, DRINK PREP AREAS, EXTERIOR LOCATIONS AND RECEPTACLES WITHIN
6 FEET OF A SINK. GFCI RECEPTACLES SHALL BE READILY ACCESSIBLE AND SHALL
NOT BE LOCATED BEHIND STATIONARY EQUIPMENT. GFCI PROTECTION MAY BE
VIA A GFCI CIRCUIT BREAKER OR GFCI RECEPTACLE, UNLESS NOTED OTHERWISE.
WHERE NECESSARY, GFCI PROTECTION MAY BE ACHIEVED VIA A BLANK FACE GFCI
DEVICE LOCATED IN A READILY ACCESSIBLE LOCATION NEAR RECEPTACLE BEING
PROTECTED. FOR DOWNSTREAM WIRING DEVICES LOCATED ON THE SAME
BRANCH CIRCUIT, THE GFCI PROTECTION MAY BE PROVIDED FOR BY A SINGLE
UPSTREAM DEVICE IF ALL PROTECTED DEVICES ARE LABELED PER CODE.
6. GROUND AND NEUTRAL CONDUCTORS SHALL NOT BE SHARED UNLESS
SPECIFICALLY NOTED ON PLANS.
7. ALL GFCI PROTECTED CIRCUITS SHALL HAVE INDIVIDUAL AND DEDICATED
NEUTRALS
8. VERIFY REQUIREMENTS OF ALL MECHANICAL EQUIPMENT WITH SHOP DRAWING
SUBMITTALS. NOTIFY ENGINEER OF ANY CONFLICTS BETWEEN SUBMITTALS AND
ELECTRICAL DRAWINGS.
9. RACEWAYS INSTALLED ON ROOFTOPS OR EXPOSED TO DIRECT SUNLIGHT
CORRECTIONS NEED TO BE PROVIDED FOR CONDUCTOR AMPACITY AND OR SIZING
BASED ON AMBIENT TEMPERATURE CORRECTION FACTORS. TEMPERATURE
CORRECTION FACTORS SHOWN IN NEC TABLE 310.15(B)(3)(C) SHALL BE ADDED TO
THE OUTDOOR TEMPERATURE TO DETERMINE THE APPLICABLE AMBIENT
TEMPERATURE FOR APPLICATION OF THE CORRECTION FACTORS IN TABLE
310.15(B)(2)(A) OR TABLE 310.15(B)(2)(B).
10. AN INDIVIDUAL DISCONNECTING MEANS SHALL BE PROVIDED LOCATED IN SIGHT
FROM EACH MOTOR OR DRIVEN MACHINERY IN ACCORDANCE WITH NEC ARTICLE
430.
10. MAINTAIN DEDICATED EQUIPMENT AND WORKING SPACE IN FRONT AND ABOVE
ALL ELECTRICAL EQUIPMENT REQUIRING SERVICING WHILE ENERGIZED PER NEC
110.26. THIS INCLUDES CONTROL PANELS AND ELECTRICAL DISCONNECTS FOR
HVAC EQUIPMENT ON LOCATED ON ROOFTOPS AND ABOVE/BELOW CEILING.
PENETRATIONS SUCH AS ROOF JACKS FOR ELECTRICAL POWER, LOW VOLTAGE
CONTROL POWER, REFRIGERANT LINES, VENT PIPES, ETC., AND INCLUDING GAS
LINES, DUCTWORK, ROOF DRAINS, SCREENING WALLS AND OTHER EQUIPMENT OF
ANY TYPE, ARE NOT TO INTRUDE INTO DEDICATED ELECTRICAL EQUIPMENT SPACE.
1. ALL TELECOM AND NETWORK CABLING AND EQUIPMENT SHALL CONFORM WITH AND BE
INSTALLED ACCORDING TO OISM/CURRENT NIST NETWORK INFRASTRUCTURE STANDARDS
AND ARE SUBJECT TO BUY AMERICAN COMPLIANCE ACT.
2. MINIMUM TELECOM CONDUIT SIZE IS 1" ALL CONDUITS TO BE ROUTED TO ACCESSIBLE
SPACE AND PROVIDED WITH PLASTIC BUSHING AND PULL STRING.
3. TELECOM JACK REQUIREMENTS:
· TELECOM OUTLETS SHALL HAVE ONE VOICE CABLE/JACK AND THREE DATA
CABLES/JACKS PER USER STATION.
· BLUE KEYSTONE JACKS SHALL BE USED FOR DATA JACKS.
· WHITE KEYSTONE JACKS SHALL BE USED FOR TELEPHONE JACKS.
· ALL CABLES SHALL BE COMSCOPE CERTIFIED PRIOR TO PROJECT CLOSEOUT.
· NO NIST SYSTEMS SHALL BE CONNECTED TO NEW CABLE INSTALLATIONS WITHOUT
COMMSCOPE CERTIFICATION AND 25 YEAR WARRANTY.
3. CABLE REQUIREMENTS:
· DATA CABLES SHALL BE BLUE.
· PHONE CABLES SHALL BE WHITE.
4. CABLE AND JACK LABELLING:
· ALL PATCH PANEL AND WALL JACKS SHALL BE LABELED PER NIST SITE
STANDARD. COORDINATE WITH NIST ON LABELING NOMENCLATURE.
· PATCH PANELS AND WALL JACKS SHALL BE LABELED SEQUENTIALLY BASED ON
ROOM NUMBER/STATION NUMBER/JACK LETTER.
· JACKS STATION NUMBERS SHALL BE LABELED AND INCREMENTED IN A
COUNTERCLOCKWISE FASHION FROM ROOM ENTRY STARTING FROM THE LEFT.
· LABELS SHALL BE SNAP-IN, CLEAR-LABEL COVERS AND MACHINE-PRINTED
PAPER INSERTS.
5. CONTRACTOR REQUIREMENTS AND RESPONSIBILITIES:
i. COMMSCOPE CERTIFICATION
· THE CONTRACTOR PROVIDING THE CERTIFICATION SHALL BE A COMMSCOPE
CERTIFIED COMPANY WHO IS AUTHORIZED BY THE REGIONAL COMMSCOPE
AUTHORITY AND SHALL BE AUTHORIZED IN BOULDER OR GAITHERSBURG
REGIONAL AREAS.
ii. KEY PERSONNEL TECHNICAL QUALIFICATIONS
a. PROJECT MANAGER(S):
· SHALL HAVE AT LEAST 3 YEARS' EXPERIENCE ESTIMATING AND INSTALLING
COMMSCOPE SYSTIMAX FIBER AND COPPER CABLING PRODUCTS ON JOBS
WHERE COMMSCOPE CERTIFICATION IS REQUIRED.
· SHALL HAVE PROJECT MANAGEMENT PROFESSIONAL (PMP) CERTIFICATION.
· SHALL HAVE REGISTERED COMMUNICATIONS DISTRIBUTION DESIGNER (RCDD)
CERTIFICATION.
· SHALL BE CERTIFIED IN COMMSCOPE DESIGN AND ENGINEERING COURSE
(SP3321)
b. FIBER TECHNICIANS:
· SHALL HAVE AT LEAST 3 YEARS' EXPERIENCE INSTALLING COMMSCOPE
SYSTIMAX FIBER CABLING PRODUCTS ON JOBS WHERE COMMSCOPE
CERTIFICATION IS REQUIRED.
· SHALL BE CERTIFIED IN COMMSCOPE FIBER OPTICS SP4400 AND SP4410
COURSES.
· SHALL BE BICSI CERTIFIED.
c. CAT6/CAT6A TECHNICIANS:
· SHALL HAVE AT LEAST 2 YEARS' EXPERIENCE INSTALLING COMMSCOPE
SYSTIMAX CAT6 CABLING PRODUCTS ON JOBS WHERE COMMSCOPE
CERTIFICATION IS REQUIRED.
· SHALL BE CERTIFIED IN COMMSCOPE INSTALLATION AND MAINTENANCE
ND3361 OR FC3361 COURSES.
· SHALL BE BICSI CERTIFIED.
· RESUMES OF CONTRACTOR KEY PERSONNEL SHALL BE PROVIDED IN PROPOSAL.
6. COPPER INSTALLATION
· TERMINATION AND TESTING OF CAT6/6A SHALL BE DONE BY COMMSCOPE
CERTIFIED CAT6/6A INSTALLERS.
· ALL CAT6/6A CABLE SHALL BE PLENUM RATED UNSHIELDED COMMSCOPE
SYSTIMAX CABLE UNLESS ANOTHER CABLE STANDARD IS REQUESTED BY USERS.
· ALL DATA CABLES ARE TO BE BLUE CATEGORY 6/6A.
· PATCH PANELS AND CABLES SHALL BE CLEARLY LABELED WITH A MACHINE
PRINTED LABEL ACCORDING TO THE LABELING SPECIFICATION GIVEN ON THE
CUTSHEET PROVIDED BY THE COR.
· ELECTRONIC COPY OF END-TO-END POWER METER TRACES AS REQUIRED BY
COMMSCOPE FOR SUBMISSION FOR WARRANTY. PROVIDE COR AND NETWORK
OPERATIONS TEAM WITH PDF FORMAT.
· WHERE ANY COPPER CABLE DOES NOT MEET COMMSCOPE SPECIFICATIONS
FOR WARRANTY THE CABLE SHALL BE RE-TERMINATED AND RE-TESTED AT NO
ADDITIONAL COST TO NIST.
· USE CABLE SUPPORT BARS TO ELIMINATE SLACK AT CABLE RACK. CABLE
SHOULD NOT HANG BELOW THE RACK UNIT IN WHICH IT IS INSTALLED. CABLE
SLACK CANNOT IMPEDE EQUIPMENT PLACEMENT.
· FIVE FEET OF CABLE SLACK FOR STATION CABLE SHALL BE PLACED NEAR END
USER STATION.
· CUSTOMER REQUIREMENTS WILL GENERATE ACTUAL CABLE DENSITY
REQUIREMENTS.
· DURING RENOVATIONS OLD COPPER CABLING SHALL BE REMOVED FROM
STATION TO MDF/IDF.
7. PROJECT SEQUENCING
· ALL COMMUNICATION LINES SHALL BE TESTED AND CERTIFIED PRIOR TO
ACCEPTANCE BY THE NETWORK OPERATIONS TEAM
· NO NETWORK EQUIPMENT OR ENDPOINTS SHALL BE CONNECTED UNTIL THE
COMMSCOPE 25-WARRANTY CERTIFICATION RECEIVED.
· PROJECT MILESTONES SHOULD BE ESTABLISHED TO CONSULT WITH NETWORK
TEAM TO INSPECT WORK
GENERAL NOTESGENERAL POWER NOTESGENERAL TELECOM NOTES
GAS STORAGE
VISCOMETERS
THERMAL
CONDUCTIVITY
LAB
HALL
W M
J
J
WM
(E)WIREMOLD(D),XP
(E)GROUND BAR
GF
GF
EPO
S
D FE
(E)FIRE ALARM JBOX
(E)CABLE TRAY
F (D)7
D E
SHEET NUMBER
PROJECT NAME of
325 BROADWAY BOULDER, COLORADO 80305-3328
NATIONAL INSTITUTE OF STANDARDS AND TECHNOLOGY
DATEDESIGN APPROVAL
ENGINEERING, MAINTENANCE and SUPPORT SERVICES
DATESUPV.BYDESCRIPTIONREVISION
3 DRAFTING
B2 - Room 1330 Walk-In Fume Hood
SJM
ELECTRICAL
Room 1330 Walk-In Fume Hood
E-2SJM
SCALE: 1/4" = 1'
FIRST FLOOR DEMOLITION PLAN
PROJECT
0 4' 8' 16'
SCALE: 1/8"=1'-0" (IN FEET)
AREA
GENERAL NOTES :
1. PLAN SHOWN IS DIAGRAMMATIC IN NATURE AND IS
INTENDED FOR ILLUSTRATING SCOPE OF WORK. CONTRACTOR
TO FIELD COORDINATE EXISTING
2. ROOM CONTAINS MANY LEGACY EXPLOSION PROOF DEVICES
FROM PREVIOUS USERS. NEW DEVICES IN THIS ROOM WILL
NOT BE REQUIRED TO HAVE EXPLOSION PROOF RATINGS.
PLAN NOTES:
1. CONTRACTOR TO SHORTEN EXISTING GROUND BAR TO MAKE
ROOM FOR NEW FUME HOOD. FIELD COORDINATE THE
LENGTH OF GROUND BAR TO BE REMOVED. PROVIDE
ADDITIONAL STANDOFF/WALL SUPPORTS AS NEEDED.
2. CONTRACTOR TO DEMO EXPLOSION PROOF RECEPTACLE AND
ASSOCIATED CONDUIT AND CONDUCTORS BACK TO THE
NEAREST DEVICE.
3. CONTRACTOR TO DEMO POWER CONNECTIONS TO EXISTING
FUME HOOD AND EXISTING EXPLOSION PROOF SWITCH.
REWORK EXISTING CONDUIT AND JUNCTION BOXES AS
NEEDED TO REUSE EXISTING HOOD CIRCUIT(S) FOR NEW
FUME HOOD.
4. CONTRACTOR TO DEMO EXISTING FUME HOOD PANIC
BUTTON, CONDUIT AND CONDUCTORS BACK TO NEAREST
JUNCTION BOX.
5. CONTRACTOR TO REMOVE EXISTING WIREMOLD ABOVE
COUNTER. WIREMOLD AND EXISTING CIRCUITS TO BE
SHORTEN AND REUSED ABOVE NEW COUNTERTOP.
6. CONTRACTOR TO REMOVE CONDUCTORS FROM EXISTING
SEVERED CONDUIT BACK TO SOURCE AND CUT CONDUIT
BACK FLUSH WITH THE FLOOR AND FILL.
7.…