JBSA Asbestos Inventory Print Report
Facility Type:
Facility Site: JBSA Randolph
Aircraft Maintenance
Square Footage: 85477Number of Floors: 1
B75.tifDrawing File Name:
Facility Status: Manned
75.jpgPhoto File Name
Date Constructed: 1931
Facility Number: Facility Name:75 HG MAINT
Facility Owner: 902/CES
Facility Address: 650 NEW Street West Asbestos:
Facility Summary Report:
Major renovation abatement, took place on this facility from 03/30/2011 - 05/30/201
05/17/2013 - Workorder 11279 - Install sound supression material throughout hangar - Since all of the surfaces are constructed of Concrete, there are no concerns for Asbestos Containing Materials. The interior of the hangar and all rooms within have been abated of all Asbestos Containing Materials. This does not include any attic areas that may still contain asbestos pipe insulation, HDUCT Mastic, and beams sprayed with an asbestos texture.
04/25/2011 - Floor Felt Found During Abatement - All floor Felt material is NAD (No Asbestos Detected)
03/31/2011 - Contractor SW Environmental Request sampling of suspect materials for asbestos. Material sampled from HDUCT is NAD (No Asbestos Detected)
11 Jun 10, Work Order L3119 - LSI Transition Project, The following areas contain asbestos containing materials (ACM). 1).
Egress and Egress Office Area -Floor Tiles, 2). Tool Crib Breezeway - Floor Tiles and Mastic. 3). Tool Crib, Floor Tiles and Mastic. 4). Admin Office, Floor Tile and Mastic. 5.) Ceiling above lay in Ceiling tiles - Throughout facility - All Ceiling Joint Compound. 6).Superintendents Office - Mastic under Carpet Tiles. Non Asbestos Materials are Pipe Insulation, HDUCT Mastic, Wall-Sheetrock, Ceiling Tiles, Wall Boards above suspended ceiling, Sheet Rock-Wall - Joint Compound. Wall Plaster, Wall Mastic above suspended ceiling, Ceiling Sheetrock except for the joint compound, and all Window Glazing throughout.
12 May 10, 2GWLAN ProjectArea of penetration is NAD for Asbestos
25 Mar 10, All 12" X 12" floor tile in Egress shop is asbestos containing at 2% Chrysotile
13 Mar 10, K7995, Reseal Roof. All roof areas were NAD for Asbestos Containing Materials.