The file is a comprehensive set of architectural, mechanical, plumbing, and electrical design drawings for a restroom remodel and door hinge project at Jewel Cave National Monument in Custer, South Dakota. The 31-page drawing set provides detailed plans for a first-floor renovation, including demolition and new construction of restroom facilities. Key elements include replacing existing plumbing fixtures with new wall-mounted water closets, urinals, and lavatories, installing new electrical systems and lighting, updating mechanical ventilation, and reconfiguring the interior layout to improve accessibility and functionality. The drawings specify ADA-compliant design elements, such as grab bars, accessible height fixtures, and appropriate clearances, and show plans for updating electrical panels, lighting, and power systems to support the renovated space.
View the file
Other files
Show all 17
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
LOCATION OF WORK
LOCATION OF WORK
CONTRACTOR
LAYDOWN AREA
3-STALL
ACCESSIBLE
TEMPORARY
RESTROOM
TRAILER
6-STALL
STANDARD
TEMPORARY
RESTROOM
TRAILER
TEMPORARY
CONSTRUCTION
FENCE: MUST
BE ABLE TO BE
REMOVED IN
LESS THAN 5
MINUTES FOR
PASSAGE OF
EMERGENCY
TRAFFIC.
1300 w 57th Street | Suite 2 Sioux Falls, SD 57108
(605) 332-7850 www.schemmer.com
REVISED TITLE OF SHEET DRAWING NO.
SHEET
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATE
238608 / 80005
80005
C :\U se rs
\e lin eh an
\D oc um en ts \R ev it_ te m p\
-A
R C
H _R
_e lin eh an
BC
9A F.
rv t
RJM
EML
RTG
01/10/2025
009258.004
COVER SHEET
009258004- 0- 0 COVER SHEET
RESTROOM REMODEL & DOOR HINGE
JEWEL CAVE NATIONAL MONUMENT
CUSTER, SD
ARCHITECTURAL
A 00 ARCHITECTURAL INFO SHEET
A 01 ARCHITECTURAL SPECIFICATIONS
A 02 ARCHITECTURAL SPECIFICATIONS
A 03 ARCHITECTURAL SPECIFICATIONS
A 04 ARCHITECTURAL SPECIFICATIONS
A 05 ARCHITECTURAL SPECIFICATIONS
A001 DEMOLITION FLOOR PLANS &
PHOTOS
A101 FLOOR PLAN & REFLECTED
CEILING PLAN
A301 SCHEDULES, DOOR AND WINDOW
DETAILS
A501 MOUNTING HEIGHTS AND INTERIOR
ELEVATIONS
A801 FINISH FLOOR PLAN AND
SCHEDULE
GENERAL
0 COVER SHEET
ACC01 ARCHITECTURAL CODE
COMPLIANCE
PLUMBING
P 00 PLUMBING INFO SHEET
P 01 SHEET SPECIFICATIONS - PLUMBING
P 02 SHEET SPECIFICATIONS - PLUMBING
P 03 SHEET SPECIFICATIONS - PLUMBING
P101 FLOOR PLAN - PLUMBING
P401 SCHEDULES, DETAILS, & RISERS -
PLUMBING
MECHANICAL
M 00 MECHANICAL INFO SHEET
M 01 SHEET SPECIFICATIONS -
MECHANICAL
M101 FLOOR PLAN - MECHANICAL
ELECTRICAL
E 00 ELECTRICAL INFO SHEET
E 01 ELECTRICAL SPECIFICATIONS
E 02 ELECTRICAL SPECIFICATIONS
E 03 ELECTRICAL SPECIFICATIONS
E001 FLOOR PLAN - DEMOLITION
E101 FLOOR PLAN - LIGHTING, POWER, & AUXILIARY
E401 ELECTRICAL DETAILS
E402 ELECTRICAL DETAILS
E601 LUMINAIRE, EQUIPMENT, & PANEL SCHEDULES
DRAWING INDEX
NOT TO SCALE
Region Map
NOT TO SCALE
Site Map
TRUE
NORTH
TRUE
NORTH
NOT TO SCALE
SITE MAP - TEMPORARY FACILITIES
TRUE
NORTH
DATE INITIAL
JEWEL CAVE NATIONAL MONUMENT
11149 US-16 B-12
CUSTER, SD 57730
NPS RESTROOM REMODEL
AND DOOR HINGE
1/10/25
FE
B
FEC
OCCUPANCY CLASSIFICATION
ASSEMBLY (A-3)
BUSINESS (B)
MERCANTILE (M)
SECRETARY
STORAGE
OFFICE
OFFICE
OFFICE
OFFICE
EXHIBIT ROOM
LOBBY
CORRIDOR
117G
ELEVATOR
LOBBY
CORRIDOR
LOBBY EXHIBIT
PARK STORE
HALL
COURTYARD
117H
CORRIDOR
117A
CORRIDOR
VESTIBULE
STAIR
GUIDES
ELEVATOR
HOISTWAY
LOBBY
MEN
WOMEN
FAMILY
UTILITY
2 2
PROJECT SCOPE,
INTERIOR ONLY
2-HR SEPARATION UNCONFIRMED
MECH CHASE
AREA A
AREA B
1300 w 57th Street | Suite 2 Sioux Falls, SD 57108
(605) 332-7850 www.schemmer.com
REVISED TITLE OF SHEET DRAWING NO.
SHEET
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATE
238608 / 80005
80005
C :\U se rs
\e lin eh an
\D oc um en ts \R ev it_ te m p\
-A
R C
H _R
_e lin eh an
BC
9A F.
rv t
RJM
EML
RTG
01/10/2025
009258.004
ACC01
ARCHITECTURAL CODE
COMPLIANCE
009258004- 0- ACC01 ARCHITECTURAL CODE COMPLIANCE
RESTROOM REMODEL & DOOR HINGE
JEWEL CAVE NATIONAL MONUMENT
CUSTER, SD
SCALE: 1/8" = 1'-0"
FIRST FLOOR - CODE REVIEW PLAN
XX BUILDING SEPARATION
(X HOURS)
CODE COMPLIANCE
LEGEND
NOTES:
CONTRACTOR SHALL PROVIDE PERMANENT
SIGNAGE OR STENCILING WITHIN CEILING
PLENUM AT ALL FIRE RATED WALLS, SMOKE
BARRIERS & SMOKE PARTITIONS. LETTERING
SHALL BE AT LEAST 3" IN HEIGHT WITH THE
WORDING: "FIRE AND/OR SMOKE BARRIER -
PROTECT ALL OPENINGS:. REPEAT AT
INTERVALS NOT EXCEEDING 30'-0" MEASURED
HORIZONTALLY ALONG THE PARTITION WALL.
SEAL PENETRATIONS IN FIRE RATED SMOKE
BARRIERS, FIRE RATED BARRIERS & SMOKE
BARRIERS.
CODE SUMMARY
APPLICABLE CODES
BUILDING :
ACCESSIBILITY :
LIFE SAFETY :
ENERGY :
MECHANICAL :
PLUMBING :
ELECTRICAL :
OCCUPANCY GROUP :
TYPE OF CONSTRUCTION :
MAXIMUM ALLOWED HEIGHT
MAXIMUM ALLOWED AREA
MIXED USE SEPARATIONS :
HEIGHT AND AREA LIMITS
EXTERIOR WALL OPENING LIMITS :
DRAFTSTOPS :
FIRE PROTECTIVE SYSTEMS
FIRE SEPARATION ASSEMBLIES
EXITS
SHAFTS / HOISTWAYS
DWELLING UNIT SEPARATIONS
INTERIOR LOAD BEARING
WALLS, COLUMNS, FRAMING
ROOF CONSTRUCTION
FLOOR CONSTRUCTION
FIRE WALLS
FIRE RESISTANCE OF STRUCTURAL
ELEMENTS
RATING
(HOURS)
DESIGN
NUMBER
EXTERIOR WALLS
LOAD BEARING WALLS
NON-LOAD BEARING WALLS
CALCULATIONS
DOOR
STAIR
B
VB
65'
30,000 SF
NA
2004 ABAAS
NA
2024 NFPA 101
2024 IECC
2024 IMC
2024 UPC
2023 NEC
2024 IBC
NA
UL
UL
UL
UL
UL
UL
UL
UL
0.2" / OCC
0.3" / OCC
PLUMBING FIXTURE
REQUIREMENTS
MEN - REQUIRED
WOMEN - REQUIRED
MEN - PROVIDED
WOMEN - PROVIDED
NUMBER OF OCCUPANTS
MEN
WOMEN
WC LAV URINALS TUB/
SHOWER
DRINKING FOUNTAINS
REQUIRED
PROVIDED
OCC TYPE
125/65 1 PER 200 - - - -
1 PER 500
1 1 0 0
2 3 2 0
1 1 0
4 3 0
FIRST FLOOR
SECOND FLOOR
TOTAL
AREA (GROSS SQUARE FOOTAGE) :
BUILDING STATISTICS
NUMBER OF STORIES :
THIRD FLOOR
SUBGRADE
11999 SF
1218 SF
7415 SF
1218 SF
1148 SF
CODE_ROOM SCHEDULE
ROOM NO ROOM NAME FUNCTION OF SPACE CALC (SQF/OCC) OCCUPANT LOAD
AREA / OCC
SUB GRADE
ASSEMBLY (A-3)
001 ENTRY 165 SF 0 SF
002 RESTROOM 45 SF 0 SF
003 OFFICE BUSINESS AREAS 102 SF / 150 SF 1
004 STORAGE STORAGE AREAS 35 SF / 300 SF 0
005 MECH MECHANICAL
EQUIPMENT ROOM
330 SF / 300 SF 1
006 ELEV 78 SF 0 SF
007 ELEV 78 SF 0 SF
FIRST FLOOR
155 MECH CHASE (none) 19 SF 0 SF
ASSEMBLY (A-3)
115 EXHIBIT ROOM ASSEMBLY EXHIBIT
GALLERY & MUSEUM
641 SF / 30 NET SF 21
116 CORRIDOR 276 SF 0 SF
117 LOBBY 788 SF 0 SF
117H COURTYARD ASSEMBLY EXHIBIT
GALLERY & MUSEUM
728 SF / 30 NET SF 24
118 VESTIBULE 139 SF 0 SF
119 HALL 201 SF 0 SF
121 LOBBY EXHIBIT ASSEMBLY EXHIBIT
GALLERY & MUSEUM
936 SF / 30 NET SF 31
122 ELEVATOR LOBBY 376 SF 0 SF
123 CORRIDOR 465 SF 0 SF
125 HOISTWAY 78 SF 0 SF
126 ELEVATOR 78 SF 0 SF
127 GUIDES BUSINESS AREAS 141 SF / 150 SF 1
128 STAIR 71 SF 0 SF
BUSINESS (B)
104 SECRETARY BUSINESS AREAS 89 SF / 150 SF 1
105 STORAGE STORAGE AREAS 72 SF / 300 SF 0
106 OFFICE BUSINESS AREAS 104 SF / 150 SF 1
107 OFFICE BUSINESS AREAS 103 SF / 150 SF 1
108 OFFICE BUSINESS AREAS 143 SF / 150 SF 1
109 OFFICE BUSINESS AREAS 108 SF / 150 SF 1
117A CORRIDOR 53 SF 0 SF
117G CORRIDOR 193 SF 0 SF
150 LOBBY 311 SF 0 SF
151 MEN 0 SF
152 WOMEN 212 SF 0 SF
153 FAMILY 86 SF 0 SF
154 UTILITY 19 SF 0 SF
MERCANTILE (M)
120 PARK STORE MERCANTILE 517 SF / 60 SF 9
SECOND FLOOR
ASSEMBLY (A-3)
202 FAN ROOM MECHANICAL
EQUIPMENT ROOM
511 SF / 300 SF 2
203 STORAGE STORAGE AREAS 395 SF / 300 SF 1
TOTALS:: 37 95
N.S.
OCCUPANTS: 95
IM
PA
C
TE
D S
C O
PE
DATE INITIAL
1044 North 115th Street | Suite 300 Omaha, NE 68154
(402) 493-4800 www.schemmer.com
REVISED TITLE OF SHEET DRAWING NO.
SHEET
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATE
238608 / 80005
80005
C :\U se rs
\e lin eh an
\D oc um en ts \R ev it_ te m p\
-A
R C
H _R
_e lin eh an
BC
9A F.
rv t
RJM
EML
RTG
01/10/2025
009258.004
A 00
ARCHITECTURAL INFO
SHEET
009258004- 2- A 00 ARCHITECTURAL INFO SHEET
RESTROOM REMODEL & DOOR HINGE
JEWEL CAVE NATIONAL MONUMENT
CUSTER, SD
XXXX
DX
XREFERENCE
NOTE
REFERENCE
DEMOLITION
NOTE
EQUIPMENT
NUMBER
ROOM NAME
150 SF
ROOM
NUMBER
REFERENCE
DESIGNATION
DEMOLITION
DESIGNATION
EQUIPMENT
NUMBER
ROOM NAME
DESIGNATION
ROOM NUMBER
DESIGNATION
ROOM AREA
DESIGNATION
SYMBOL LEGEND
ROOM /
FRAMING
ELEVATION
EXTERIOR
ELEVATION
XX-XX
XX-XX
ELEVATION LETTER
DIRECTION OF VIEW
SHEET NUMBER
ELEVATION LETTER
DIRECTION OF VIEW
SHEET NUMBER
DOOR
NUMBER DOOR NUMBER10
WINDOW
DESIGNATION WINDOW DESIGNATION000
TA-XTOILET
ACCESSORY TOILET ACCESSORY
NUMBER
WALL
TYPE
LETTER
INDICATES
PARTITION OR
WALL TYPE
X
ABBREVIATIONS
REFERENCE LEGEND
PLAN VIEW
SECTION / ELEVATION VIEW
SHEAR WALL
MASONRY-CMU
MASONRY-VENEER
STUD WALL
CONCRETE
GRAVEL
EARTH / COMPACTED
EARTH /
NONCOMPACTED
RIGID INSULATION
JOINT FILLER
STEEL
GYPSUM
FLEXIBLE INSULATION
GROUT
PLYWOOD
WOOD (FINISH)
MASONRY-CMU FACE
MASONRY-CMU
MASONRY-VENEER
S SOUTH
SA SUPPLY AIR
SAN SANITARY
SB SECURITY BARS
SB SPLASH BLOCK
SCH SCHEDULE
SCHED SCHEDULE
SCR SCREW
SCT STRUCTURAL CLAY TILE
SCUT SCUTTLE
SCW SOFT COLD WATER
SD STORM DRAIN
SD SUBDRAIN
SDI STEEL DECK INSTITUTE
SECT SECTION
SECY SECRETARY
SEQ SEQUENCE
SF SQUARE FOOT (FEET)
SFU STRUCTURAL FACING
UNIT
SHLD SHOULDER
SHT SHEET
SHTG SHEATHING
SHW SOFT HOT WATER
SIM SIMILAR
SJI STEEL JOIST INSTITUTE
SL SNOW LOAD
SLBB SHORT LEG BACK TO
BACK
SM SPRINKLER MAIN
SOV SHUT OFF VALVE
SPA SPACE(ING)
SPEC SPECIFICATIONS
SPF SOUNDPROOF
SPH SPACE HEATER
SPKR SPEAKER
SPL SPECIAL
SQ SQUARE
SS SANITARY SEWER
SS STAINLESS STEEL
SSMR STANDING SEAM METAL
ROOFING
STA STATION
STAIR STAIRWAY
STC SOUND TRANSMISSION
COEFFICIENT
STD STANDARD
STGR STRINGER
STIFF STIFFENER
STIRR STIRRUPS
STL STEEL
STN STONE
STOR STORAGE
STR STRUCTURAL
SUB FL SUB FLOOR
SUCT SUCTION
SUSP SUSPENDED
SVF SHEET VINYL FLOORING
SW SWITCH
SWBD SWITCH BOARD
SYM SYMMETRICAL
T TREAD
T or TLT TOILET
TAN TANGENT
TBD TACK BOARD
TE TOP ELEVATION
TEL TELEPHONE
TEMP TEMPERATURE
TER TERRAZZO
TERM TERMINAL
TGL TOGGLE
TH THRESHOLD
THK THICK
THRD THREAD
TO TOP OF
TOB TOP OF BEAM
TOC TOP OF CONCRETE
TOF TOP OF FOOTING
TOJ TOP OF JOIST
TOPO TOPOGRAPHIC
TOS TOP OF STEEL
TOW TOP OF WALL
TRANS TRANSVERSE
TSTAT THERMOSTAT
TV TELEVISION
TW TEMPERED WATER
TWR TEMPERED WATER
RETURN
TYP TYPICAL
UC UNIT COOLER
UG UNDERGROUND
UH UNIT HEATER
UL UNDERWRITERS
LABORATORIES
UNEX UNEXCAVATED
UNFIN UNFINISHED
UNO UNLESS NOTED
OTHERWISE
UPS UNINTERRUPTIBLE
POWER SYSTEM
UR URINAL
UT UTILITY
UV UNIT VENTILATOR
V VOLT
VAC VACUUM
VAV VARIABLE AIR VOLUME
VCP VITRIFIED CLAY PIPE
VCT VINYL COMPOSITION TILE
VD VAULT DOOR
VEL VELOCITY
VENT VENTILATOR(ION)
VERT VERTICAL
VEST VESTIBULE
VFD VARIABLE FREQUENCY
DRIVE
VOL VOLUME
VPC VERTICAL POINT OF
CURVATURE
VPI VERTICAL POINT OF
INTERSECTION
VPT VERTICAL POINT OF
TANGENCY
VS VENT STACK
VT VINYL-TILE
VTR VENT THRU ROOF
VWC VINYL WALL COVERING
W WEST
W WIDE (WIDTH)
W WIRE
W/ WITH
W/O WITHOUT
WB WET BULB
WC WATER CLOSET
WC WATER COLUMN
WD WASTE DRAIN
WD WOOD
WD BLKG WOOD BLOCKING
WD DR WOOD DOOR
WDW WINDOW
WF WIDE FLANGE
WG WIRE GLASS
WH WALL HYDRANT
WHT WHITE
WI WROUGHT IRON
WKSH WORK SHOP
WL WIND LOAD
WNSCT WAINSCOT
WP WEATHER PROOF
WP WORK POINT
WPF WATER PROOF
WPFG WATER PROOFING
WRB WARDROBE
WS WASTE STACK
WT WEIGHT
WWF WELDED WIRE FABRIC
WWM WOVEN WIRE MESH
XFMR TRANSFORMER
YD YARD or YARD DRAIN
P PAINT
PA PUBLIC ADDRESS
PBS PUSH BUTTON STATION
PC PIECE
PC POINT OF CURVATURE
PC PRECAST
PCC PORTLAND CEMENT
CONCRETE
PCT PORCELAIN CERAMIC TILE
PD PRESSURE DROP
PE POLYETHYLENE
PEN PENETRATION
PERF PERFORATED
PH PHASE
PHAR PHARMACY
PI POINT OF INTERSECTION
PIV POST INDICATING VALVE
PL or P PLATE
PLAM PLASTIC LAMINATE
PLAS PLASTER
PLATF PLATFORM
PLBG PLUMBING
PLG PILING
PLWD PLYWOOD
PNL PANEL
POL POLISH(ED)
PORC PORCELAIN
PPM PARTS PER MILLION
PR PAIR
PREFAB PREFABRICATED
PREFIN PREFINISHED
PRESS PRESSURE
PROJ PROJECT
PRV PRESSURE REGULATING
VALVE
PS PRESSED STEEL
PSFT POUNDS PER SQUARE
FOOT
PSI POUNDS PER SQUARE
INCH
PT POINT
PT POINT OF TANGENCY
PTD PAINTED
PTN PARTITION
PVC POLYVINYL-CHLORIDE
PVMT PAVEMENT
PW PASS WINDOW
1/4 RD QUARTER ROUND
QT QUARRY TILE
QT QUART
QTRS QUARTERS
QTY QUANTITY
QTZ QUARTZ
R REGISTER
R RISER
RA RETURN AIR
RAD OR
R
RADIUS
RB RESILIENT BASE
RC REMOTE CONTROL
RCP REINFORCED CONCRETE
PIPE
RD ROOF DRAIN
RE RIGHT END
REC RECEIVER
RECP RECEPTACLE
RECR RECREATION
RECT RECTIFIER
REF REFERENCE
REFR REFRIGERANT
REFR REFRIGERATOR
REG REGISTER
REINF REINFORCEMENT
REM REMOVE(ABLE)
REQD REQUIRED
RESIL RESILIENT
REV REVISIONS
RFG ROOFING
RH RELATIVE HUMIDITY
RL REFRIGERANT LIQUID
RM ROOM
RND ROUND
RO ROUGH OPENING
RPM REVOLUTIONS PER
MINUTE
RT RUBBER TILE
RTU ROOF TOP UNIT
RUB RUBBER
DIAG DIAGONAL
DIM DIMENSION
DIP DUCTILE IRON PIPE
DISC DISCONNECT
DIST DISTRIBUTION
DL DEAD LOAD
DMPR DAMPER
DN DOWN
DP DAMP PROOFING
DPT DEW POINT
DR DOOR
DRN DRAIN
DS DOWN SPOUT
DV DENTAL VACUUM
DWG DRAWING
DWLS DOWELS
DX DIRECT EXPANSION
E EAST
EA EACH
EA EXHAUST AIR
EDH ELECTRIC DUCT HEATER
EER ENERGY EFFICIENCY
RATIO
EJ EXPANSION JOINT
EL OR
ELEV
ELEVATION - GRADE OR
BUILDING
ELEC ELECTRIC OR ELECTRICAL
ELEV ELEVATOR
ENCL ENCLOSURE
ENT ENTERING
ENT ENTRANCE
EQ EQUAL
EQUIP EQUIPMENT
ES EACH SIDE
EST ESTIMATE
EVAP EVAPORATOR
EW EACH WAY
EWC ELECTRIC WATER
COOLER
EXC EXCAVATE
EXD EXIT DEVICE
EXH EXHAUST
EXIST EXISTING
EXP EXPOSED
EXPL EXPLOSION
EXPN EXPANSION
EXT EXTERIOR
F FAHRENHEIT
F
FIRE
FA FRESH AIR
FCG FACING
FD FLOOR DRAIN
FDN FOUNDATION
FE FIRE EXTINGUISHER
FEB FIRE EXTINGUISHER
BRACKET
FEC FIRE EXTINGUISHER
CABINET
FH FIRE HYDRANT
FHC FIRE HOSE CABINET
FIG FIGURE
FIN FINISH
FIX FIXTURE
FL or FLR FLOOR
FLASH FLASHING
FLEX FLEXIBLE
FLG FLANGE
FLG FLOORING
FLUOR FLUORESCENT
FP FIRE PROTECTION
FPM FEET PER MINUTE
FPRF FIRE PROOF
FR FRAME
FRG FURRING
FS FAR SIDE
FS FLOOR SINK
FS FULL SIZE
FT FEET (FOOT)
FTG FOOTING
FV FIELD VERIFY
FWC FABRIC WALL COVERING
G GRILLE
G NATURAL GAS
GA GAGE OR GAUGE
GAL GALLON
GALV GALVANIZED
GEN GENERAL
GFE GOVERNMENT FURNISHED
EQUIPMENT
GFE/CI GOVERNMENT FURNISHED
EQUIPMENT/CONTRACTOR
INSTALLED
GFI GROUND FAULT
INTERRUPTER
GI GALVANIZED IRON
GL GLASS
GND GROUND
GOVT GOVERNMENT
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GR GRADE
GRS GALVANIZED RIGID STEEL
CONDUIT
GRTG GRATING
GSU GLAZED STRUCTURAL
UNITS
GWB GYPSUM WALLBOARD
GWT GLAZED WALL TILE
GYP GYPSUM
H or HT HEIGHT (HIGH)
HB HOSE BIBB
HBD HARDBOARD
HC HANDICAPPED
HD HEAD
HDPE HIGH DENSITY
POLYETHYLENE
HDR HEADER
HDW HARDWARE
HIP HIGH PRESSURE
HM HOLLOW METAL
HORIZ HORIZONTAL(LY)
HP HORSE POWER
HPS HIGH PRESURE STEAM
HPT HIGH POINT
HR HOUR
HS HIGH STRENGTH
HSGYP HIGH STRENGTH GYPSUM
PLASTER
HTG HEATING
HTR HEATER
HW HEAD WALL
HW HOT WATER
HWH HOT WATER HEATER
HWR HOT WATER RETURN
(HEATING)
HWS HOT WATER SUPPLY
(HEATING)
HYD HYDRAULIC
I or FE IRON
IC INTERCOM
ID INSIDE DIAMETER
IE INVERT ELEVATION
IES ILLUMINATING
ENGINEERING SOCIETY
IN INCH
INSUL INSULATION
INT INTERIOR
INV INVERT OR INVERTER
IP IRON PIPE
ISF INSIDE FACE
JB JUNCTION BOX
JBOX JUNCTION BOX
JC JANITOR CLOSET
JCT JUNCTION
JST JOIST
JT JOINT
K KEY
KCP KEENE'S CEMENT
PLASTER
KIP or K KILOPOUND (1000 LBS)
KIT KITCHEN
KL KEY LOCK
KP KICK PLATE
KV KILOVOLTS
KVA KILOVOLT AMPERES
KW KILOWATT
LAB LABORATORY
LAU LAUNDRY
LAV LAVATORY
LBR LUMBER
A COMPRESSED AIR
A/C AIR CONDITIONING
AB ANCHOR BOLT
ABS ACRYLONITRILE BUTAD
STYRENE
AC ALTERNATING CURRENT
ACI AMERICAN CONCRETE
INSTITUTE
ACSR ALUMINUM CONDUCTOR
STEEL REINFORCED
ACST ACOUSTIC
AD ACCESS DOOR
AD AREA DRAIN
ADMIN ADMIN ADMINISTRATION
(IVE)
AFF ABOVE FINISH FLOOR
AFFF AQUEOUS FILM FORMING
FOAM
AGG AGGREGATE
AHU AIR HANDLING UNIT
AI AREA INLET
AIC AMPS INTERRUPTING
CAPACITY (SYM RMS)
AISC AMERICAN INSTITUTE OF
STEEL CONSTRUCTION
AL ACTIVE LEAF
AL ALUMINUM
ALT ALTERNATE
AMP AMPERE
ANSI AMERICAN NATIONAL
STANDARDS INSTITUTE
AP ACCESS PANEL
APD AIR PRESSURE DROP
APPD APPROVED
APPROX APPROXIMATE
ARCH ARCHITECTURAL OR
ARCHITECT
ARI AMERICAN
REFRIGERATION
INSTITUTE
ASB ASBESTOS
ASPH ASPHALT
APC ACOUSTICAL PANEL
CEILING
AUTO AUTOMATIC
AV ACID VENT
AVG AVERAGE
AW ACID WASTE
AWC ACOUSTICAL WALL
COVERING
AWG AMERICAN WIRE GAUGE
L ANGLE
BATT BATT INSULATION
BB BULLETIN BOARD
BBO BOILER BLOW OFF
BC BOOKCASE
BD BOARD
BDY BOUNDARY
BEJ BRICK EXPANSION JOINT
BIT BITUMINOUS
BKR BREAKER
BL BUILDING LINE
BLDG BUILDING
BLK BLOCK
BLKG BLOCKING
BM BEAM
BM BENCH MARK
BO BOTTOM OF
BOT BOTTOM
BRCG BRACING
BRDG BRIDGING
BRG BEARING
BRK BRICK
BRKT BRACKET
BS BOTH SIDES
BTU BRITISH THERMAL UNIT
BTUH BTU PER HOUR
BUR BUILT-UP ROOFING
BW BOTH WAYS
C CENTER
C OR
CND
CONDUIT (ELECTRICAL
SHEETS)
C TO C CENTER TO CENTER
CAP CAPACITY
CB CATCH BASIN (OR CIRCUIT
BREAKER)
CC CENTER TO CENTER
CCT CIRCUIT
CD CONDENSATE DRAIN
CE COVER ELEVATION
CEM CEMENT
CF CUBIC FEET
CFH CUBIC FEET PER HOUR
CFM CUBIC FEET PER MINUTE
CHIM CHIMNEY
CI CAST IRON
CI CURB INLET
CIP CAST IN PLACE
CIR CIRCULAR
CJ CONTROL JOINT
CKT CIRCUIT
CL CENTER LINE
CL WG CLEAR WIRE GLASS
CLG CEILING
CLKG CAULKING
CMP CORRUGATED METAL PIPE
CMU CONCRETE MASONRY
UNIT
CNTR COUNTER
CO CLEAN OUT
CO2 CARBON DIOXIDE
COL COLUMN
COM COMMON
COMB COMBINATION
COMB COMBUSTION
COMP COMPRESSIBLE
COMPR COMPRESSOR
CONC CONCRETE
CONF CONFERENCE
CONN CONNECTION
CONSTR CONSTRUCTION
CONSTR
JT
CONSTRUCTION JOINT
CONT CONTINUOUS
(CONTINUATION)
CONTR CONTRACTOR
COR CORNER
CORR
COVEREDCOV
CORRIDOR
CPL CEMENT PLASTER
CPS CYCLES PER SECOND
(HERTZ)
CPT CARPET
CR CONDENSER WATER
RETURN
CRES CORROSIVE RESISTANT
STEEL
CRG CARRIAGE
CRSE COURSE
CS CONDENSER WATER
SUPPLY
CS COUNTER SINK
CSMT CASEMENT
CT CERAMIC TILE
CT CURRENT TRANSFORMER
CTL CARPET TILE
CU CONDENSING UNIT
CU YD CUBIC YARDS
CUH CABINET UNIT HEATER
CV CEILING VENT
CW COLD WATER
CWR CHILLED WATER RETURN
CWS CHILLED WATER SUPPLY
CYL CYLINDER
D DEPTH (DEEP)
D DIFFUSER
d PENNY (as in nail - 10d)
D&M DRESSED AND MATCHED
DA DOUBLE ACTING
DB DRY BULB
dB DECIBEL
DBL DOUBLE
DC DIRECT CURRENT
DCJ DOWELED CONTROL
JOINT
DCJT DUMMY CONTROL JOINT
DCL DOOR CLOSER
DCW DOMESTIC COLD WATER
DEG DEGREE
DEMO DEMOLITION
DEPR DEPRESSION
DEPT DEPARTMENT
DET DETAIL
DF DRINKING FOUNTAIN
DH DOUBLE HUNG
DHW DOMESTIC HOT WATER
DI DEIONIZED WATER
DIA DIAMETER
CLO CLOSET
FR FIRE RATED
U/C UNDER CABINET
CBU CEMENTITIOUS BACKER
UNIT
F FLUSH or FRAME
FG FULL GLASS
G GLASS or GLASS TYPE
HG HALF GLASS
V VISION
SL SLIDING
BF(2) BIFOLD (DOUBLE)
IG INSULATED GLASS
SS SOLID SURFACE
WIDTH DEPTH
HEIGHT
CABINET DESIGN
SERIES MODELCASEWORK
TAG
DWR DRAWER
CAB CABINET
SHV SHELF OR SHELVES
SNGL SINGLE
GENERAL NOTES
LBS POUNDS
LD LOAD
LDG LOADING
LE LEFT END
LG LENGTH (LONG)
LIN LINEAR
LIS LAWN IRRIGATION
SYSTEM
LL LIVE LOAD
LLBB LONG LEG BACK TO BACK
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LNTL LINTEL
LP LOW POINT
LPG LIQUIFIED PETROLEUM
GAS
LPS LOW PRESSURE STEAM
LR LIVING ROOM
LS LAWN SPRINKLER
LT LIGHT
LT WT LIGHT WEIGHT
LTG LIGHTING
LVT LUXURY VINYL TILE
M MIDDLE
M THOUSAND
M & B MATCHED AND BEADED
MA MAKE-UP AIR
MACH MACHINE
MAS MASONRY
MAT or
MATL
MATERIAL
MAX MAXIMUM
MB MACHINE BOLT
MBH 1000 BTUH
MC MEDICINE CABINET
MC MISCELLANEOUS
CHANNELS
MECH MECHANICAL
MER MECHANICAL EQUIPMENT
ROOM
MET METAL
MFG MANUFACTURING
MFR MANUFACTURER
MH MANHOLE
MIN MINIMUM
MISC MISCELLANEOUS
ML METAL LATH
MLDG MOULDING
MO MASONRY OPENING
MONO MONOLITHIC
MT METAL THRESHOLD
MTD MOUNTED
N NORTH
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL
CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURERS
ASSOCIATION
NFPA NATIONAL FIRE
PROTECTION
ASSOCIATION
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NO NUMBER
NR NOT REQUIRED
NS NEAR SIDE
NTS NOT TO SCALE
OA OUTSIDE AIR
OB WG OBSCURE WIRE GLASS
OBGL OBSCURE GLASS
OBSC OBSCURE
OC ON CENTER(S)
OCEW ON CENTER EACH WAY
OD OUTSIDE DIAMETER
OFF OFFICE
OH OVERHEAD
OPNG OPENING
OPP OPPOSITE
OPS OPERATIONS
OS & Y OUTSIDE SCREW & YOKE
OSF OUTSIDE FACE
OV OVERFLOW VALVE
OX OXYGEN
OZ OUNCE
NV NARROW VISION
MICRO MICROWAVE
NORTH
ARROW
NAME
ELEVATIONLEVEL
MATCHLINE
AREA A
AREA B
TITLE
MARKER 1
VIEW NAME
SCALE: 1/8" = 1'-0"
EXISTING
COLUMN
NEW
COLUMN
X
X
X
XX-XX
SIM
X
XX-XX
SECTION/
DETAIL
PLAN
DETAIL
LETTER INDICATES
NEW COLUMN LINE
LETTER INDICATES
EXISTING COLUMN LINE
SECTION/DETAIL
NUMBER
SHEET NUMBER
INDICATES DIRECTION
OF VIEW
DETAIL NUMBER
SHEET NUMBER
DETAIL NUMBER
LEVEL CALLOUT
DESIGNATION
ELEVATION
DESIGNATION
GRAPHIC AREA FOR
DRAWING
TITLE
SCALE OF THE
DRAWING
NORTH PLAN
NORTH
TRUE
NORTH
GENERAL DEMO NOTES
ARCHITECTURAL SHEET LIST
REF. DEMO NOTES ( )
PROJECT ARCHITECTURAL REFERENCED DEMOLITION NOTES
DX
X
PROJECT ARCHITECTURAL REFERENCED NOTES
REF. NOTES ( )
0 COVER SHEET
ACC01 ARCHITECTURAL CODE COMPLIANCE
A 00 ARCHITECTURAL INFO SHEET
A 01 ARCHITECTURAL SPECIFICATIONS
A 02 ARCHITECTURAL SPECIFICATIONS
A 03 ARCHITECTURAL SPECIFICATIONS
A 04 ARCHITECTURAL SPECIFICATIONS
A 05 ARCHITECTURAL SPECIFICATIONS
A001 DEMOLITION FLOOR PLANS & PHOTOS
A101 FLOOR PLAN & REFLECTED CEILING PLAN
A301 SCHEDULES, DOOR AND WINDOW DETAILS
A501 MOUNTING HEIGHTS AND INTERIOR ELEVATIONS
A801 FINISH FLOOR PLAN AND SCHEDULE
A.
B.
C.
D.
E.
F.
G.
H.
1.
I.
J.
PRIOR TO COMMENCEMENT OF DEMOLITION, CONFIRM APPROVAL OF EXIT CONDITIONS FOR ALL
OFFICES 106, 127, 108, AND 109 WITH THE AHJ AND PROVIDE TEMPORARY TOILET FACILITIES AS
INDICATED.
THE DEMOLITION PLANS WERE PRODUCED BY DUPLICATING THE ORIGINAL DRAWINGS PROVIDED BY
THE OWNER AND LIMITED FIELD VERIFICATION. DIMENSIONS AND EXISTING CONDITIONS ARE
APPROXIMATE. CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITIONS. ITEMS WHICH ARE
INTENDED TO BE REMOVED, RELOCATED, OR SALVAGED ARE SHOWN AS FULL-TONE DASHED LINES AND ARE LISTED IN THE REFERENCED DEMOLITION NOTES. ALL OTHER ITEMS ARE INTENDED TO
REMAIN IN PLACE AND ARE SHOWN HALF-TONE.
DEMOLITION SHALL INCLUDE, BUT IS NOT LIMITED TO, THE ITEMS BELOW OR HERE-IN. THE
CONTRACTOR SHALL COORDINATE ALL REQUIRED RENOVATION AND NEW CONSTRUCTION WITH THE EXISTING BUILDING TO IDENTIFY THE TOTAL EXTENT OF THE DEMOLITION REQUIRED AND AS LISTED
BELOW.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE DEMOLITION AND REMOVAL OF ALL EXISTING BUILDING COMPONENTS, MATERIALS, EQUIPMENT, AND APPURTENANCES AS REQUIRED TO BUILD, ERECT, INSTALL, OR ACCOMMODATE ALL NEW CONSTRUCTION WITH THE OWNER HAVING FIRST RIGHT
OF REFUSAL ON ALL ITEMS.
ITEMS NOTED TO BE REMOVED AND SALVAGED OR REINSTALLED SHALL BE CAREFULLY REMOVED BY
THE CONTRACTOR WITHOUT DAMAGE AND STORED OR REINSTALLED ON THE SITE AS DIRECTED.
REMOVED AND SALVAGED ITEMS SHALL REMAIN THE PROPERTY OF THE OWNER.
IN THE EVENT THE CONTRACTOR ENCOUNTERS, MATERIAL REASONABLY BELIEVED TO BE ASBESTOS, LEAD-BASED PAINT, OR ANY OTHER HAZARDOUS MATERIAL WHICH HAS NOT BEEN RENDERED
HARMLESS, THE CONTRACTOR SHALL IMMEDIATELY STOP WORK IN THE AREA AFFECTED AND REPORT THE CONDITION TO THE OWNER AND ARCHITECT IN WRITING. THE WORK IN THE AFFECTED AREA
SHALL NOT THEREAFTER BE RESUMED EXCEPT BY WRITTEN AGREEMENT OF THE OWNER AND
CONTRACTOR.
THE CONTRACTOR IS RESPONSIBLE FOR THE ERECTION, MAINTENANCE, AND REMOVAL OF ALL
CONSTRUCTION BARRIERS.
REMOVE EXISTING ELEMENTS/FINISHES NOT REQUIRED IN THE COMPLETED PROJECT, BUT
CONFLICTING WITH NEW FINISHES. THESE ELEMENTS/FINISHES SHALL INCLUDE, BUT ARE NOT LIMITED
TO THE ITEMS LISTED BELOW:
REMOVE EXISTING CEILING SUSPENSION SYSTEMS ANYWHERE NEW CEILINGS ARE INDICATED PER
THE REFLECTED CEILING PLAN AND ROOM FINISH SCHEDULE
ALL EXISTING WALLS, DOORS, FRAMES, AND WINDOWS SHOWN ON THE PLAN AS A FULL-TONE DASHED
LINE ARE TO BE REMOVED.
REFER TO MECHANICAL DEMOLITION PLANS FOR ADDITIONAL DEMOLITION REQUIRED TO
ACCOMMODATE NEW MECHANICAL PIPING AND ASSOCIATED EQUIPMENT.
A.
B.
C.
D.
E.
F.
G.
EXISTING CONDITIONS ARE BASED ON DRAWINGS PROVIDED BY THE OWNER AND LIMITED FIELD VERIFICATION. THE CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS AND NOTIFY THE ARCHITECT/ENGINEER OF ANY DISCREPANCIES OR VARIATIONS FROM THOSE SHOWN
ON THE DRAWINGS. THE CONTRACTOR SHALL ADJUST TO ACTUAL FIELD CONDITIONS AT NO
ADDITIONAL EXPENSE TO THE OWNER.
ALL CONTRACTORS ARE RESPONSIBLE FOR REVIEWING ENTIRE SET OF DOCUMENTS TO DETERMINE THEIR FULL SCOPE OF WORK. CONTRACTOR SHALL NOT BE ALLOWED EXTRA COSTS DUE TO FAILURE
TO REVIEW ENTIRE SET OF DOCUMENTS.
CONTRACTOR SHALL TAKE ALL MEASUREMENTS FOR WORK AND BE RESPONSIBLE FOR SAME.
CONTRACTOR SHALL ADJUST FOR ACTUAL FIELD CONDITIONS AT NO ADDITIONAL EXPENSE TO OWNER.
COORDINATE THE WORK AND SHOP DRAWINGS WITH ALL OTHER TRADES AFFECTED. PRIOR TO
MAKING FIELD ADJUSTMENTS VERIFY ADA CLEARANCE.
SCREENED HALF-TONE LINES INDICATE EXISTING CONSTRUCTION TO REMAIN. FULL-TONE LINES
INDICATE NEW OR RELOCATED CONSTRUCTION.
DIMENSIONS ARE TO FACE OF STUD UNLESS NOTED OTHERWISE.
ALL ANGLES ON THE FLOOR PLANS ARE 45 OR 90 DEGREES UNLESS OTHERWISE INDICATED.
PATCH EXISTING WALLS, FLOORS, AND CEILING SURFACES DEMOLISHED, CUT, CORED, OR ALTERED IN
ANY WAY TO ACCOMMODATE NEW CONSTRUCTION OR TO RECEIVE NEW FINISHES. PREP ALL
EXISTING FLOORS TO RECEIVE NEW FINISHES PER ROOM FINISH SCHEDULE.
2 WALL-MOUNTED WATER CLOSET WITH FLUSH VALVE. REFER TO PLUMBING.
3 WALL-MOUNTED WATER CLOSET WITH FLUSH VALVE, ACCESSIBLE HEIGHT. REFER TO PLUMBING.
4 URINAL & FLUSH VALVE. REFER TO PLUMBING.
5 SINK. REFER TO PLUMBING.
6 HAND DRYER AND SOAP DISPENSER INTEGRATED INTO WASH BAR. REFER TO ELECTRICAL AND
PLUMBING.
8 ADULT CHANGING TABLE.
9 DUAL HEIGHT ELECTRIC WATER COOLER.
10 URINAL SCREEN WITH CONTINUOUS MOUNTING BRACKET.
11 TOILET PARTITION PANEL AND DOOR - CEILING HUNG.
13 FLOOR DRAIN. REFER TO PLUMBING.
15 ACCESSIBLE DRINKING FOUNTAIN WITH BOTTLE FILLER.
17 EPOXY TO CONCRETE ALUMINUM TRANSITION TRIM.
18 FULL WIDTH (APPROX 7'-3") X 3'-6" TALL MIRROR. SPAN WALL TO WALL.
19 CEILING ACCESS HATCH 2'-3" X 2'-3".
20 GYPSUM WALL BOARD, VAPOR BARRIER AND INSULATION TO INTERIOR SIDE OF PERIMETER WALLS.
21 LIGHT BAR. REFER TO ELECTRICAL.
22 FIRE EXTINGUISHER AND CABINET.
23 EPOXY WALL BASE.
24 SLAB JOINT.
25 30" X 22" CEILING ACCESS PANEL. FIELD VERIFY LOCATION BETWEEN STRUCTURAL MEMBERS.
26 HEATER. REFER TO MECHANICAL. REFERENCED PLAN NOTES
27 ADA PUSH BUTTON DOOR OPENER, SEE ELECTRICAL.
A PROVIDE & MAINTAIN 2 ADA ACCESSIBLE AND 6 STANDARD PORTABLE TOILETS WITH HAND
SANITATION DURING CONSTRUCTION ONLY. CONFIRM LOCATION WITH OWNER. SEE COVER SHEET
FOR LOCATIONS AND SPECIFICATIONS FOR DETAILS AND REQUIREMENTS.
D1 REMOVE EXISTING GYPSUM CEILING, GWB BACKING AND
ATTIC INSULATION, AND DEVICES ATTACHED OR INSTALLED
WITH IT.
D2 REMOVE EXISTING TONGUE & GROOVE CEILING, FRAMING AND
ATTIC INSULATION AND DEVICES ATTACHED OR INSTALLED
WITH IT.
D3 REMOVE EXISTING WOOD STUD WALL.
D4 REMOVE EXISTING WOOD STUD & BRICK WALL.
D5 REMOVE ALL EXISTING PLUMBING FIXTURES. REFER TO
MECHANICAL.
D6 REMOVE ALL EXISTING SOAP DISPENSERS.
D7 REMOVE ALL EXISTING HAND DRYERS & SALVAGE TO OWNER.
D8 REMOVE ALL EXISTING TOILET PAPER DISPENSERS.
D9 REMOVE ALL EXISTING SANITARY DISPOSALS.
D10 REMOVE ALL EXISTING FLOOR DRAINS. REFER TO
MECHANICAL.
D11 REMOVE ALL EXISTING TOILET PARTITIONS AND URINAL
SCREENS IN THEIR ENTIRETY.
D12 REMOVE EXISTING CERAMIC TILE FLOOR.
D13 REMOVE EXISTING HOLLOW METAL DOOR, FRAME, &
ASSOCIATED HARDWARE. SALVAGE AUTOMATIC OPENER
HARDWARE AND REUSE.
D14 REMOVE EXISTING TONGUE & GROOVE DOOR & HARDWARE.
D15 REMOVE EXISTING ALUMINUM STOREFRONT DOOR FRAME,
GLAZING & ASSOCIATED HARDWARE. SALVAGE HARDWARE.
D16 REMOVE EXISTING VCT FLOORING & ADHESIVE.
D17 REMOVE EXISTING MIRRORS.
D18 REMOVE EXISTING MOP SINK. REFER TO MECHANICAL.
D19 REMOVE EXISTING WATER HEATER. REFER TO MECHANICAL.
D20 REMOVE EXISTING CARPET TILE & ADHESIVE.
D23 REMOVE WOOD PANELING.
D24 REMOVE EXISTING CHANGING STATION.
D25 REMOVE EXISTING GRAB BARS.
D26 REMOVE EXISTING BASE CABINETS, COUNTERTOP, & UPPER
CABINETS. SALVAGE FOR OWNER.
D27 REMOVE EXISTING CASED OPENING.
D28 REMOVE EXISTING HOLLOW METAL DOOR, FRAME, &
HARDWARE (KEYPAD). SALVAGE FOR REUSE.
D29 REMOVE ALL EXISTING DRYWALL, MOISTURE BARRIER AND
INSULATION FROM INTERIOR PERIMETER WALLS.
D30 REMOVE EXISTING CONCRETE SLAB THROUGHOUT.
D31 EXISTING WINDOW TO REMAIN.
D32 REMOVE GLAZING, THIS WINDOW ONLY.
DATE INITIAL
THE INTENT OF DEMOLITON NOTES IS TO EXPRESS THE GENERAL
SCOPE REQUIRED TO ACHIEVE A COMPLETE INTERIOR DEMOLITION
WHILE RETAINING THE ROOF & EXTERIOR SYSTEMS
1300 w 57th Street | Suite 2 Sioux Falls, SD 57108
(605) 332-7850 www.schemmer.com
REVISED TITLE OF SHEET DRAWING NO.
SHEET
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATE
238608 / 80005
80005
C :\U se rs
\e lin eh an
\D oc um en ts \R ev it_ te m p\
-A
R C
H _R
_e lin eh an
BC
9A F.
rv t
RJM
EML
RTG
01/10/2025
009258.004
A 01
ARCHITECTURAL
SPECIFICATIONS
009258004- 2- A 01 ARCHITECTURAL SPECIFICATIONS
RESTROOM REMODEL & DOOR HINGE
JEWEL CAVE NATIONAL MONUMENT
CUSTER, SD
DATE INITIAL
DIVISION 02 - EXISTING CONDITIONS
SECTION 02-4100 - DEMOLITION
PART 1 GENERAL
1.01 SECTION INCLUDES
A. Selective demolition of building elements for alteration purposes.
PART 2 PRODUCTS -- NOT USED
PART 3 EXECUTION
3.01 GENERAL PROCEDURES AND PROJECT CONDITIONS
A. Comply with applicable codes and regulations for demolition operations and safety of adjacent structures and the public.
1. Obtain required permits.
2. Take precautions to prevent catastrophic or uncontrolled collapse of structures; do not allow worker or public access within range of potential collapse of unstable structures.
3. Provide, erect, and maintain temporary barriers and security devices.
4. Use physical barriers to prevent access to areas that could be hazardous to workers or the public.
5. Conduct operations to minimize effects on and interference with adjacent structures and occupants.
6. Do not close or obstruct roadways or sidewalks without permits from authority having jurisdiction.
7. Conduct operations to minimize obstruction of public and private entrances and exits. Do not obstruct required exits at any time. Protect persons using entrances and exits from removal operations.
B. Do not begin removal until receipt of notification to proceed from Owner.
C. Do not begin removal until built elements to be salvaged or relocated have been removed.
D. Protect existing structures and other elements to remain in place and not removed.
E. Minimize production of dust due to demolition operations. Do not use water if that will result in ice, flooding, sedimentation of public waterways or storm sewers, or other pollution.
3.02 EXISTING UTILITIES
A. Coordinate work with utility companies. Notify utilities before starting work, comply with their requirements, and obtain required permits.
B. Protect existing utilities to remain from damage.
C. Do not disrupt public utilities without permit from authority having jurisdiction.
D. Do not close, shut off, or disrupt existing life safety systems that are in use without at least 7 days prior written notification to Owner.
E. Do not close, shut off, or disrupt existing utility branches or take-offs that are in use without at least 3 days prior written notification to Owner.
F. Locate and mark utilities to remain; mark using highly visible tags or flags, with identification of utility type; protect from damage due to subsequent construction, using substantial barricades if necessary.
3.03 SELECTIVE DEMOLITION FOR ALTERATIONS
A. Existing construction and utilities indicated on drawings are based on casual field observation and existing record documents only.
1. Verify construction and utility arrangements are as indicated.
2. Report discrepancies to Architect before disturbing existing installation.
3. Beginning of demolition work constitutes acceptance of existing conditions that would be apparent upon examination prior to starting demolition.
B. Separate areas in which demolition is being conducted from areas that remain occupied.
1. Provide, erect, and maintain temporary dustproof partitions of construction in locations indicated on drawings.
C. Maintain weatherproof exterior building enclosure, except for interruptions required for replacement or modifications; prevent water and humidity damage.
D. Remove existing work as indicated and required to accomplish new work.
1. Remove items indicated on drawings.
E. Services including, but not limited to, HVAC, Plumbing, and Electrical: Remove existing systems and equipment as indicated.
1. Maintain existing active systems to remain in operation, and maintain access to equipment and operational components.
2. Where existing active systems serve occupied facilities but are to be replaced with new services, maintain existing systems in service until new systems are complete and ready for service.
3. Verify that abandoned services serve only abandoned facilities before removal.
4. Remove abandoned pipe, ducts, conduits, and equipmentincluding those above ceilings. Remove back to source of supply where possible, otherwise cap stub and tag with identification.
F. Protect existing work to remain.
1. Prevent movement of structure. Provide shoring and bracing as required.
2. Perform cutting to accomplish removal work neatly and as specified for cutting new work.
3. Repair adjacent construction and finishes damaged during removal work.
4. Patch to match new work.
3.04 DEBRIS AND WASTE REMOVAL
A. Remove debris, junk, and trash from site.
B. Leave site in clean condition, ready for subsequent work.
C. Clean up spillage and wind-blown debris daily from public and private lands.
END OF SECTION
DIVISION 03 - CONCRETE
SECTION 03-0516 - UNDERSLAB VAPOR BARRIER
PART 1 GENERAL
1.01 SECTION INCLUDES
A. Sheet vapor barrier under concrete slabs on grade.
1.02 SUBMITTALS
A. Product Data: Submit manufacturers' data on manufactured products.
B. Manufacturer’s installation instructions for placement, seaming, penetration prevention and repair, and perimeter seal per ASTM E1643.
C. Provide third party documentation that all testing was performed on a single production roll per ASTM E1745 Section 8.1.
D. Provide letter from manufacturer to document installation review (in a manner described below under Quality Assurance) and consistency with the governing installation standard, ASTM E1643.
1.03 QUALITY ASSURANCE
A. Inspection by Manufacturer: Provide manufacturers review of the barrier membrane installation (digitally or in-person, when possible) prior to concrete placement to help ensure compliance with governing installation standard, ASTM E1643, and Contract Documents. Provide report within three days of activity and prior to placement of concrete.
PART 2 PRODUCTS
2.01 MATERIALS
A. Underslab Vapor Barrier:
1. Water Vapor Permeance: Not more than 0.010 perms, maximum.
2. Complying with ASTM E1745 Class A.
a. Strength: ASTM E1745 Class A.
b. Thickness: 15 mils minimum.
3. Provide third party documentation that all testing was performed on a single production roll per ASTM E1745 Section 8.1.
4. Product:
a. Stego Industries LLC; Stego Wrap Vapor Barrier (15-mil): www.stegoindustries.com/#sle.
5. Other Acceptable Manufacturers ( Equivalent products subject to submittal approval ):
a. Henry Company; Moistop Ultra 15: www.henry.com/#sle.
b. Inteplast Group; Barrier-Bac VB-350: www.barrierbac.com/#sle.
c. ISI Building Products; Viper VaporCheck II 15-mil (Class A): www.isibp.com/#sle.
d. Tex-Trude, LP; Xtreme Vapor Barrier (15-mil): www.tex-trude.com/#sle.
6. Substitutions: Not permitted.
B. Accessory Products: Vapor barrier manufacturer's recommended tape, adhesive, mastic, etc., for sealing seams and penetrations in vapor barrier.
1. All accessories must be from the same manufacturer of the vapor barrier material used, or must be approved by the vapor barrier manufacturer.
a. Seams
1) Approved tape.
b. Sealing Permanent penetrations of Vapor barrier
1) Approved vaporproofing mastic.
2) Approved tape.
c. Perimeter edge/seal
1) Approved tape with a textured surface that creates a mechanical seal to freshly-placed concrete.
2) Approved termination bar.
3) Approved double-sided sealant tape.
d. Penetration prevention forming system
1) Approved peel-and-stick base/foot and blunt-end stake.
e. Vapor Barrier-Safe Screed System
1) Approved vapor barrier-safe, fixed elevation, point-to-point guide screed system.
PART 3 EXECUTION
3.01 EXAMINATION
A. Verify that surface over which vapor barrier is to be installed is complete and ready before proceeding with installation of vapor barrier.
3.02 INSTALLATION
A. Install vapor barrier in accordance with manufacturer's instructions and ASTM E1643.
B. Unroll vapor barrier with the longest dimension parallel with the direction of the concrete placement and face laps away from the expected direction of the placement whenever possible.
C. Install vapor barrier under interior slabs on grade; lap sheet over footings and seal to foundation walls.
D. Extend vapor barrier to the perimeter of the slab. If practicable, terminate it at the top of the slab, otherwise where obstructed by impediments, such as dowels, waterstops, or any other site condition requiring early termination of the vapor barrier. At the point of termination, seal vapor barrier to the foundation wall, grade beam or slab itself.
1. Seal vapor barrier to the entire slab perimeter using textured tape, per manufacturer's instructions.
E. Lap joints minimum 6 inches.
F. Apply seam tape/textured tape/double-sided tape to a clean and dry vapor barrier.
G. Seal joints, seams and penetrations (including pipes) watertight with manufacturer's recommended products and follow manufacturer's written instructions.
H. No penetration of vapor barrier is allowed except for reinforcing steel and permanent utilities.
I. Avoid the use of stakes driven through vapor barrier by utilizing vapor barrier-safe, peel-and-stick screed and forming penetration prevention systems. Ensure peel-and-stick adhesive base is fully adhered to the vapor barrier.
1. If non-permanent stakes must be driven through vapor barrier, repair as recommended by vapor barrier manufacturer.
2. Use reinforcing bar supports with base sections that eliminate or minimize the potential for puncture of the vapor barrier.
J. Repair damaged vapor retarder with vapor barrier material of similar (or better) permeance, puncture and tensile strength, before covering with other materials.
K. For vapor barrier-safe concrete screeding applications, install vapor barrier-safe, fixed elevation, point-to-point guide screed system prior to placing concrete.
L. Provide quality assurance letter report.
END OF SECTION
SECTION 03-3000 - CAST-IN-PLACE CONCRETE
PART 1 GENERAL
1.01 SECTION INCLUDES
A. Floors and slabs on grade.
B. Concrete reinforcement.
C. Joint devices associated with concrete work.
D. Concrete curing.
1.02 SUBMITTALS
A. Product Data: Submit manufacturers' data on manufactured products showing compliance with specified requirements and installation instructions.
1. See 03-0516 for underslab vapor barrier.
B. Mix Design: Submit proposed concrete mix design.
1. Indicate proposed mix design complies with requirements of ACI SPEC-301, Section 4 - Concrete Mixtures.
2. For each concrete mixture, include the following:
a. Mixture identification.
b. Minimum 28-day compressive strength.
c. Durability exposure class.
d. Maximum w/cm.
e. Slump limit.
f. Air content.
g. Nominal maximum aggregate size.
h. Indicate amounts of mixing water to be withheld for later addition at Project site if permitted.
i. Intended placement method.
j. Submit alternate design mixtures when characteristics of materials, Project conditions, weather, test results, or other circumstances warrant adjustments.
C. Test Reports: Submit report for each test or series of tests specified.
1.03 QUALITY ASSURANCE
A. Perform work of this section in accordance with ACI SPEC-301 and ACI CODE-318.
B. Follow recommendations of ACI PRC-306 when concreting during cold weather.
1.04 FIELD CONDITIONS
A. Cold-Weather Placement: Comply with ACI 301 (ACI 301M) and ACI 306.1 and as follows.
1. Protect concrete work from physical damage or reduced strength that could be caused by frost, freezing actions, or low temperatures.
2. When average high and low temperature is expected to fall below 40 deg F (4.4 deg C) for three successive days, maintain delivered concrete mixture temperature within the temperature range required by ACI 301 (ACI 301M).
B. Do not use frozen materials or materials containing ice or snow.
C. Do not place concrete in contact with surfaces less than 35 deg F (1.7 deg C), other than reinforcing steel.
1. Do not use calcium chloride, salt, or other materials containing antifreeze agents or chemical accelerators unless otherwise specified and approved in mixture designs.
D. Hot-Weather Placement: Comply with ACI 301 (ACI 301M) and ACI 305.1 (ACI 305.1M), and as follows:
E. Maintain concrete temperature at time of discharge to not exceed 95 deg F (35 deg C).
F. Fog-spray forms, steel reinforcement, and subgrade just before placing concrete. Keep subgrade uniformly moist without standing water, soft spots, or dry areas.
PART 2 PRODUCTS
2.01 REINFORCEMENT MATERIALS
A. Reinforcing Steel: ASTM A615/A615M, Grade 60 (60,000 psi).
1. Finish: Unfinished, unless otherwise indicated.
B. Steel Welded Wire Reinforcement (WWR): Galvanized, plain type, ASTM A1064/A1064M.
1. Form: Flat Sheets.
C. Reinforcement Accessories:
1. Chairs, Bolsters, Bar Supports, Spacers: Sized and shaped for adequate support of reinforcement during concrete placement.
2.02 CONCRETE MATERIALS
A. Blended, Hydraulic Cement: ASTM C595, Type IL - Portland-Limestone Cement.
B. Fine and Coarse Aggregates: ASTM C33/C33M.
1. Acquire aggregates for entire project from same source.
C. Fly Ash: ASTM C618, Class C or F.
D. Water: ASTM C1602/C1602M; clean, potable, and not detrimental to concrete.
2.03 ADMIXTURES
A. Do not use chemicals that will result in soluble chloride ions in excess of 0.1 percent by weight of cement.
B. Air Entrainment Admixture: ASTM C260/C260M.
C. High Range Water Reducing and Retarding Admixture: ASTM C494/C494M Type G.
D. High Range Water Reducing Admixture: ASTM C494/C494M Type F.
E. Water Reducing and Retarding Admixture: ASTM C494/C494M Type D.
F. Accelerating Admixture: ASTM C494/C494M Type C.
G. Retarding Admixture: ASTM C494/C494M Type B.
H. Water Reducing Admixture: ASTM C494/C494M Type A.
I. Waterproofing Admixture: Admixture formulated to reduce permeability to liquid water, with no adverse effect on concrete properties.
1. Admixture Composition: Hydrophobic polymer waterproofing and corrosion inhibitor, functioning by closing concrete pores and chemical bonding.
2.04 ACCESSORY MATERIALS
A. Non-Shrink Cementitious Grout: Premixed compound consisting of nonmetallic aggregate, cement, water reducing and plasticizing agents.
1. Grout: Comply with ASTM C1107/C1107M.
2. Minimum Compressive Strength at 48 Hours: 2,000 pounds per square inch.
3. Minimum Compressive Strength at 28 Days: 7,000 pounds per square inch.
2.05 BONDING AND JOINTING PRODUCTS
A. Latex Bonding Agent: Non-redispersable acrylic latex, complying with ASTM C1059/C1059M, Type II.
B. Epoxy Bonding System:
1. Complying with ASTM C881/C881M and of Type required for specific application.
C. Slab Isolation Joint Filler: 1/2-inch thick, height equal to slab thickness, with removable top section forming 1/2-inch deep sealant pocket after removal.
1. Material: ASTM D1751, cellulose fiber.
2.06 CURING MATERIALS
A. Curing Compound, Naturally Dissipating: Clear, water-based, liquid membrane-forming compound; complying with ASTM C309, Type I, Class B.
B. Moisture-Retaining Sheet: ASTM C171.
C. Water: Potable, not detrimental to concrete.
2.07 CONCRETE MIX DESIGN
A. Concrete Strength: Establish required average strength for each type of concrete on the basis of field experience or trial mixtures, as specified in ACI SPEC-301.
1. For trial mixtures method, employ independent testing agency acceptable to Architect for preparing and reporting proposed mix designs.
B. Admixtures: Add acceptable admixtures as recommended in ACI PRC-211.1 and at rates recommended or required by manufacturer.
C. Class C: Normal-weight concrete used for interior slabs-on-ground.
1. Compressive Strength, when tested in accordance with ASTM C39/C39M at 28 days: 4,000 pounds per square inch.
2. Water-Cement Ratio: Maximum 45 percent by weight.
3. Maximum dry unit weight: 470 pounds per cubic foot.
4. Slump Limit: 4 inches (100 mm), plus or minus 1 inch (25 mm).
5. Air Content:
a. Do not use an air-entraining admixture or allow total air content to exceed 3 percent for concrete used in trowel-finished floors.
D. Class G: Normal-weight concrete used for building walls.
2.08 MIXING
A. Adding Water: If concrete arrives on-site with slump less than suitable for placement, do not add water that exceeds the maximum water-cement ratio or exceeds the maximum permissible slump.
PART 3 EXECUTION
3.01 EXAMINATION
A. Verify lines, levels, and dimensions before proceeding with work of this section.
B. Verify that surface over which vapor barrier is to be installed is complete and ready before proceeding with installation of vapor barrier.
3.02 PREPARATION
A. Where new concrete is to be bonded to previously placed concrete, prepare existing surface by cleaning and applying bonding agent in according to bonding agent manufacturer's instructions.
1. Use epoxy bonding system for bonding to damp surfaces, for structural load-bearing applications, and where curing under humid conditions is required.
2. Use latex bonding agent only for non-load-bearing applications.
3.03 INSTALLING VAPOR BARRIER/RETARDER
A. Interior Slabs on Grade: Confirm vapor barrier/retarder under interior slabs on grade are properly installed per section 03-0516.
3.04 INSTALLING REINFORCEMENT AND OTHER EMBEDDED ITEMS
A. Comply with requirements of ACI SPEC-301. Clean reinforcement of loose rust and mill scale, and accurately position, support, and secure in place to achieve not less than minimum concrete coverage required for protection.
B. Install welded wire reinforcement in maximum possible lengths, and offset end laps in both directions. Splice laps with tie wire.
C. Verify that anchors, seats, plates, reinforcement and other items to be cast into concrete are accurately placed, positioned securely, and will not interfere with concrete placement.
3.05 PLACING CONCRETE
A. Place concrete in accordance with ACI PRC-304.
B. Ensure reinforcement, inserts, waterstops, embedded parts, and formed construction joint devices will not be disturbed during concrete placement.
3.06 SLAB JOINTING
A. Locate joints as indicated on drawings.
B. Anchor joint fillers and devices to prevent movement during concrete placement.
C. Isolation Joints: Use preformed joint filler with removable top section for joint sealant, total height equal to thickness of slab, set flush with top of slab.
D. Saw Cut Contraction Joints: Saw cut joints before concrete begins to cool, within 4 to 12 hours after placing; use 1/8 inch thick blade and cut at least 1 inch deep but not less than one quarter (1/4) the depth of the slab.
3.07 FLOOR FLATNESS AND LEVELNESS TOLERANCES
A. Minimum F(F) Floor Flatness and F(L) Floor Levelness Values:
1. Exposed to View and Foot Traffic: F(F) of 20; F(L) of 15, on-grade only. Where shown, provide slopes from perimeter wall to drain.
B. Measure F(F) Floor Flatness and F(L) Floor Levelness in accordance with ASTM E1155, within 48 hours after slab installation; report both composite overall values and local values for each measured section.
C. Correct the slab surface if composite overall value is less than specified and if local value is less than two-thirds of specified value or less than F(F) 13/F(L) 10.
D. Correct defects by grinding or by removal and replacement of the defective work. Areas requiring corrective work will be identified. Re-measure corrected areas by the same process.
3.08 CONCRETE FINISHING
A. Concrete Slabs: Finish to requirements of ACI PRC-302.1 and as follows:
1. Surfaces to Receive Thin Floor Coverings: "Steel trowel" as described in ACI PRC-302.1; thin floor coverings include carpeting, resilient flooring, seamless flooring, resinous matrix terrazzo, thin set quarry tile, and thin set ceramic tile.
3.09 CURING AND PROTECTION
A. Comply with requirements of ACI PRC-308. Immediately after placement, protect concrete from premature drying, excessively hot or cold temperatures, and mechanical injury.
B. Maintain concrete with minimal moisture loss at relatively constant temperature for period necessary for hydration of cement and hardening of concrete.
C. Surfaces Not in Contact with Forms:
1. Initial Curing: Start as soon as free water has disappeared and before surface is dry. Keep continuously moist for not less than three days by water ponding, water-saturated sand, water-fog spray, or saturated burlap.
2. Final Curing: Begin after initial curing but before surface is dry.
3.10 FIELD QUALITY CONTROL
A. An independent testing agency will perform field quality control tests provided by the General Contractor at their own expense.
B. Provide free access to concrete operations at project site and cooperate with appointed firm.
C. Submit proposed mix design of each class of concrete to inspection and testing firm for review prior to commencement of concrete operations.
D. Compressive Strength Tests: ASTM C39/C39M, for each test, mold and cure three concrete test cylinders. Obtain test samples for every 100 cubic yards or less of each class of concrete placed.
E. Take one additional test cylinder during cold weather concreting, cured on job site under same conditions as concrete it represents.
F. Perform one slump test for each set of test cylinders taken, following procedures of ASTM C143/C143M.
3.11 DEFECTIVE CONCRETE
3.12 PROTECTION
A. Do not permit traffic over unprotected concrete floor surface until fully cured.
END OF SECTION
DIVISION 06 - WOOD, PLASTICS, AND COMPOSITES
SECTION 06-8316 - FIBERGLASS REINFORCED PANELING
PART 1 GENERAL
1.01 SECTION INCLUDES
A. Fiberglass reinforced plastic panels.
B. Trim.
1.02 DELIVERY, STORAGE, AND HANDLING
A. Store panels flat, indoors, on a clean, dry surface. Remove packaging and allow panels to acclimate to room temperature for 48 hours prior to installation.
PART 2 PRODUCTS
2.01 MANUFACTURERS
A. Fiberglass Reinforced Plastic Panels:
1. Crane Composites, Inc: www.cranecomposites.com
2. Specialized Building Systems, Inc; : www.sbs-frp.com.
3. Nudo Products, Inc: www.nudo.com
4. Panolam Industries International, Inc: www.panolam.com
5. Substitutions: Approved Equal.
2.02 PANEL SYSTEMS
A. Wall Panels:
1. Panel Size: 4 by 8 feet.
2. Panel Thickness: 0.10 inch.
3. Surface Design: Embossed.
4. Color: White.
5. Attachment Method: Adhesive only, with trim and sealant in joints.
2.03 MATERIALS
A. Panels: Fiberglass reinforced plastic (FRP), complying with ASTM D5319.
1. Surface Burning Characteristics: Maximum flame spread index of 25 and smoke developed index of 450; when system tested in accordance with ASTM E84.
2. Sanitation and Cleanability: Comply with 9 CFR 416.2.
3. Chemical Cleanability: Excellent chemical resistance to common cleaners and detergents when tested in accordance with ISO 2812-1.
B. Trim: Vinyl; color coordinating with panel.
C. Adhesive: Type recommended by panel manufacturer.
D. Sealant: Type recommended by panel manufacturer; color matching panel.
PART 3 EXECUTION
3.01 EXAMINATION
A. Verify existing conditions and substrate flatness before starting work.
B. Verify that substrate conditions are ready to receive the work of this section.
3.02 INSTALLATION - WALLS
A. Install panels in accordance with manufacturer's instructions.
B. Cut panels with carbide tipped saw blades or snips.
C. Apply adhesive to the back side of the panel using trowel as recommended by adhesive manufacturer.
D. Apply panels to wall with seams plumb and pattern aligned with adjoining panels.
E. Install panels with manufacturer's recommended gap for panel field and corner joints.
F. Place trim on panel before fastening edges, as required.
G. Fill channels in trim with sealant before attaching to panel.
H. Install trim with adhesive as required.
I. Seal gaps at floor, mop basin, and between panels with applicable sealant to prevent moisture intrusion.
J. Remove excess sealant after paneling is installed and prior to curing.
END OF SECTION
DIVISION 07 - THERMAL AND MOISTURE PROTECTION
SECTION 07-2100 - THERMAL INSULATION
PART 1 GENERAL
1.01 SECTION INCLUDES
A. Board insulation at underside of floor slabs.
B. Batt insulation for filling perimeter window space.
PART 2 PRODUCTS
2.01 APPLICATIONS
A. Insulation Under Concrete Slabs: Extruded polystyrene (XPS) board.
B. Insulation for filling perimeter window. One location as shown: Batt insulation with vapor retarder.
2.02 FOAM BOARD INSULATION MATERIALS
A. Extruded Polystyrene (XPS) Board Insulation: Comply with ASTM C578 with either natural skin or cut cell surfaces.
1. Type and Compressive Resistance: Type IV, 25 psi (173 kPa), minimum.
2. Type and Thermal Resistance, R-value: Type IV, 5.0 (0.88), minimum, per 1 inch thickness at 75 degrees F mean temperature.
3. Board Edges: Square.
4. Type and Water Absorption: Type XII, 0.3 percent by volume, maximum, by total immersion.
5. Products:
a. DuPont de Nemours, Inc: building.dupont.com/#sle.
b. Owens Corning Corporation; FOAMULAR Extruded Polystyrene (XPS)…