This document is an Addendum (No. 5) for the NPS Restroom Remodel and Door Hinge project by The Schemmer Associates, dated August 19, 2025. The addendum modifies two key drawing sheets: A101 (Partition Framing and Ceiling Details) and E101 (Luminaire coordination with toilet partitions). NPS has additionally requested the inclusion of drawing sheets from previous Addendums 2-4. The architectural modifications involve partition framing adjustments, while the electrical changes focus on coordinating lighting placement with toilet partition layouts. The project is located at Jewel Cave National Monument in Custer, South Dakota, and involves comprehensive restroom renovations including electrical, architectural, and accessibility improvements.
The project documents include detailed floor plans, lighting and power system layouts, interior finish schedules, and accessibility considerations. Specific design elements include ADA-compliant restroom features, such as accessible water closets, urinal screens, grab bar backing, push-button door openers, and a family/changing station restroom. The electrical plans indicate connecting new lighting to existing circuits, relocating fixtures, and maintaining existing electrical infrastructure where possible. The architectural drawings show a complex restroom layout with separate men's, women's, family, and utility spaces, incorporating epoxy flooring, gypsum wall boards, and comprehensive accessibility design.
View the file
Other files
Show all 17
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
August 19, 2025 Addendum No. 5 - 1 Project #09258.004
DATE: August 19, 2025
FROM: The Schemmer Associates
1044 North 115th Street, Suite 300 Omaha, Nebraska 68154 Phone: (402) 493-4800
TO: Prospective Bidders and Plan Holders
RE: Addendum No. 5 to the Bidding Documents for:
NPS Restroom Remodel and Door Hinge Schemmer Project No. 09258.004
This addendum is issued by the Architect to the Contractor. This Addendum shall be made as a part of the Contract Documents. Acknowledge receipt of this Addendum shall be provided on the Bid Form.
Failure to do so may subject Bidder to disqualification.
This addendum consists of one (1) page of written addendum items and one (1) pages of supplemental drawings for Addendum 5. NPS has requested adding all drawing sheets from Addendums 2-4 as well.
THE SCHEMMER ASSOCIATES INC.
DRAWINGS
ARCHITECTURAL
Item No. SA-1 A101 – Partition Framing and Ceiling Details modified.
ELECTRICAL
Item No. SE-1 E101 – Coordination of luminaires with the toilet partitions.
END OF ADDENDUM NO. 5
1300 w 57th Street | Suite 2 Sioux Falls, SD 57108
(605) 332-7850 www.schemmer.com
REVISED TITLE OF SHEET DRAWING NO.
SHEET
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATE
238608 / 80005
80005
C :\U se rs
\e lin eh an
\D oc um en ts \R ev it_ te m p\
-A
R C
H _R
_e lin eh an
BC
9A F.
rv t
RJM
EML
RTG
01/10/2025
009258.004
A 05
ARCHITECTURAL
SPECIFICATIONS
009258004- 2- A 05 ARCHITECTURAL SPECIFICATIONS
RESTROOM REMODEL & DOOR HINGE
JEWEL CAVE NATIONAL MONUMENT
CUSTER, SD
DATE INITIAL
08/18/2025 EML
1.03 SUBMITTALS
A. Product Data: Provide data on panel construction, hardware, and accessories.
B. Shop Drawings: Indicate partition plan, elevation views, dimensions, details of wall and ceiling supports, door swings.
PART 2 PRODUCTS
2.01 MANUFACTURERS
A. Solid Plastic Toilet Compartments:
1. All American Metal Corp - AAMCO: www.allamericanmetal.com
2. Metpar Corp: www.metpar.com
3. Partition Systems International of South Carolina: www.psisc.com
4. Scranton Products; Hiny Hider Partitions: www.scrantonproducts.com.
5. Substitutions: Approved Equal.
2.02 PLASTIC TOILET COMPARTMENTS
A. Solid Plastic Toilet Compartments: Factory fabricated doors, pilasters, and divider panels made of solid molded high density polyethylene (HDPE); ceiling-hung.
1. Color: To be selected from manufactuer's full range of colors and textures.
B. Doors:
1. Thickness: 1 inch.
2. Width: 28" inch.
3. Width for Handicapped Use: 36 inch, out-swinging.
4. Height: 55 inch.
C. Panels:
1. Thickness: 1 inch.
2. Height: 55 inch.
3. Depth: As indicated on drawings.
D. Pilasters:
1. Thickness: 1 inch.
2. Width: As required to fit space; minimum 3 inch.
E. Screens: Without doors; to match compartments; mounted to wall with two panel brackets.
2.03 ACCESSORIES
A. Pilaster Shoes: Stainless steel, satin finish, 3 inches high; concealing ceiling fastenings.
1. Provide ceiling attachment using two adjustable hanging studs, attached to above-ceiling framing.
B. Wall and Pilaster Brackets: Stainless steel; manufacturer's standard type for conditions indicated on drawings.
C. Attachments, Screws, and Bolts: Stainless steel , tamper proof type.
D. Hinges: Stainless steel, manufacturer's standard finish.
1. Pivot hinges, gravity type, adjustable for door close positioning; two per door.
E. Door Hardware: Stainless steel, manufacturer's standard finish.
1. Door Latch: Slide type with exterior emergency access feature.
2. Door Strike and Keeper with Rubber Bumper: Mount on pilaster in alignment with door latch.
3. Provide door pull for outswinging doors.
F. Coat Hook: One per compartment, mounted on door.
PART 3 EXECUTION
3.01 EXAMINATION
A. Verify that field measurements are as indicated.
B. Verify correct spacing of and between plumbing fixtures.
C. Verify correct location of built-in framing, anchorage, and bracing.
3.02 INSTALLATION
A. Install partitions secure, rigid, plumb, and level in accordance with manufacturer's instructions.
B. Maintain 3/8 inch to 1/2 inch space between wall and panels and between wall and end pilasters.
C. Attach panel brackets securely to walls using anchor devices.
D. Attach panels and pilasters to brackets. Locate head rail joints at pilaster center lines.
E. Field touch-up of scratches or damaged finish will not be permitted. Replace damaged or scratched materials with new materials.
3.03 TOLERANCES
A. Maximum Variation From True Position: 1/4 inch.
B. Maximum Variation From Plumb: 1/8 inch.
3.04 ADJUSTING
A. Adjust and align hardware to uniform clearance at vertical edge of doors, not exceeding 3/16 inch.
B. Adjust hinges to position doors in partial opening position when unlatched. Return out-swinging doors to closed position.
C. Adjust adjacent components for consistency of line or plane.
END OF SECTION
SECTION 10-2800 - TOILET, BATH, AND LAUNDRY ACCESSORIES
PART 1 GENERAL
1.01 SECTION INCLUDES
A. Commercial toilet accessories.
B. Diaper changing stations.
C. Adult changing stations.
D. Utility room accessories.
1.02 ADMINISTRATIVE REQUIREMENTS
A. Coordinate the work with the placement of internal wall reinforcement, concealed ceiling supports, and reinforcement of toilet partitions to receive anchor attachments.
1.03 SUBMITTALS
A. Product Data: Submit data on accessories describing size, finish, details of function, and attachment methods.
PART 2 PRODUCTS
2.01 MANUFACTURERS
A. Commercial Toilet, Shower, and Bath Accessories:
1. American Specialties, Inc: www.americanspecialties.com
2. Bradley Corporation: www.bradleycorp.com
3. Georgia-Pacific Professional: www.blue-connect.com
4. Substitutions: Approved Equal
B. Diaper Changing Stations:
1. American Specialties, Inc: www.americanspecialties.com
2. Bradley Corporation: www.bradleycorp.com
3. Diaper Deck & Company: www.diaperdeck.com
4. Koala Kare Products: www.koalabear.com
5. Safe-Strap Company, Inc: www.diaperdepot.com
6. Substitutions: Approved Equal.
C. Adult Changing Stations:
1. Diaper Changing Stations:American Specialties, Inc: www.americanspecialties.comBradley Corporation: www.bradleycorp.comDiaper Deck & Company:
www.diaperdeck.com Koala Kare Products: www.koalabear.comSafe-Strap Company, Inc: www.diaperdepot.com.Substitutions: Approved Equal.
2. Bradley Corporation: www.bradleycorp.com
3. Diaper Deck & Company: www.diaperdeck.com
4. Koala Kare Products: www.koalabear.com
5. Safe-Strap Company, Inc: www.diaperdepot.com.
6. Substitutions: Approved Equal.
2.02 MATERIALS
A. Accessories - General: Shop assembled, free of dents and scratches and packaged complete with anchors and fittings, steel anchor plates, adapters, and anchor components for installation.
1. Grind welded joints smooth.
B. Stainless Steel Sheet: ASTM A666, Type 304.
C. Stainless Steel Tubing: ASTM A269/A269M, Grade TP304 or TP316.
D. Fasteners, Screws, and Bolts: Hot dip galvanized; tamper-proof; security type.
2.03 FINISHES
A. Stainless Steel: Satin finish, unless otherwise noted.
2.04 Commercial Toilet Accessories
A. Toilet Paper Dispenser: Hillyard PAP22315 (Black) Jumbo Roll (9") Tissue Dispenser B. Grab Bars: Stainless steel, textured surface.
1. Standard Duty Grab Bars:
a. Push/Pull Point Load: 250 pound-force, minimum.
b. Dimensions: 1-1/2 inch outside diameter, minimum 0.05 inch wall thickness, exposed flange mounting, 1-1/2 inch clearance between wall and inside of grab bar.
c. Finish: Satin.
d. Length and Configuration: As indicated on drawings.
C. Sanitary Napkin Disposal Unit: Stainless steel, surface-mounted, self-closing door, locking bottom panel with full-length stainless steel piano-type hinge, removable receptacle.
1. Products:
a. American Specialties, Inc: www.americanspecialties.com/#sle.
b. Substitutions: Approved Equal.
2.06 DIAPER CHANGING STATIONS
A. Diaper Changing Station: Wall-mounted folding diaper changing station for use in commercial toilet facilities, meeting or exceeding ASTM F2285.
1. Material: Polyethylene.
2. Mounting: Surface.
3. Color: As selected.
4. Minimum Rated Load: 250 pounds.
B. Adult Changing Station: Wall-mounted folding diaper changing station for us in commerical toilet facilities, meeting or exceeding ASTM F2285.
1. Material: Polyethylene.
2. Color: As selected.
3. Minimum Rated Load: 300 pounds.
2.07 UTILITY ROOM ACCESSORIES
A. Combination Utility Shelf/Mop and Broom Holder: 0.05 inch thick stainless steel, Type 304, with 1/2 inch returned edges, 0.06 inch steel wall brackets.
1. Mop/broom holders: Four spring-loaded rubber cam holders at shelf front.
2. Length: Manufacturer's standard length for number of holders/hooks.
3. Products:
a. American Specialties, Inc: www.americanspecialties.com/#sle.
b. Substitutions: Approved Equal.
PART 3 EXECUTION
3.01 EXAMINATION
A. Verify existing conditions before starting work.
B. Verify exact location of accessories for installation.
C. Verify that field measurements are as indicated on drawings.
3.02 PREPARATION
A. Deliver inserts and rough-in frames to site for timely installation.
B. Provide templates and rough-in measurements as required.
3.03 INSTALLATION
A. Install accessories in accordance with manufacturers' instructions in locations indicated on drawings.
B. Install plumb and level, securely and rigidly anchored to substrate.
C. Mounting Heights: As required by accessibility regulations, unless otherwise indicated.
1. Other Accessories: As indicated on drawings.
3.04 PROTECTION
A. Protect installed accessories from damage due to subsequent construction operations.
END OF SECTION
SECTION 10-4400 - FIRE PROTECTION SPECIALTIES
PART 1 GENERAL
1.01 SECTION INCLUDES
A. Fire extinguishers.
B. Fire extinguisher cabinets.
C. Accessories.
1.02 FIELD CONDITIONS
A. Do not install extinguishers when ambient temperature may cause freezing of extinguisher ingredients.
PART 2 PRODUCTS
2.01 MANUFACTURERS
A. Fire Extinguishers:
1. Activar Construction Products Group, Inc. - JL Industries; Cosmic Extinguisher - Multipurpose Chemical: www.activarcpg.com
2. Substitutions: Approved Equal.
B. Fire Extinguisher Cabinets and Accessories:
1. Activar Construction Products Group, Inc. - JL Industries; Academy Series: www.activarcpg.com
2. Larsen's Manufacturing Co: www.larsensmfg.com
3. Substitutions: Approved Equal.
2.02 FIRE EXTINGUISHERS
A. Fire Extinguishers - General: Comply with product requirements of NFPA 10 and applicable codes, whichever is more stringent.
1. Provide extinguishers labeled by UL (DIR) or FM (AG) for purpose specified and as indicated.
B. Multipurpose Dry Chemical Type Fire Extinguishers: Carbon steel tank, with pressure gauge.
1. Stored Pressure Operated: Deep Drawn.
2. Class: A:B:C type.
3. Size: 10 pound.
4. Finish: Baked polyester powder coat red color.
5. Temperature range: Minus 40 degrees F to 120 degrees F.
2.03 FIRE EXTINGUISHER CABINETS
A. Cabinet Configuration: Semi-recessed type.
1. Sized to accomodate the extinguisher.
2. Trim: Semi-recessed from wall with 3" wide face.
3. Provide cabinet enclosure with right angle inside corners and seams, and with formed perimeter trim and door stiles.
B. Door: 0.036 inch metal thickness, reinforced for flatness and rigidity with lock and breakable window access. Hinge doors for 180 degree opening with continuous piano hinge.
C. Door Glazing: Tempered glass, clear, 1/8 inch thick, and set in resilient channel glazing gasket.
D. Cabinet Mounting Hardware: Appropriate to cabinet, with pre-drilled holes for placement of anchors.
E. Finish of Cabinet Exterior Trim and Door: No. 180 clear anodized aluminum..
F. Finish of Cabinet Interior: White colored enamel.
2.04 ACCESSORIES
A. Extinguisher Brackets: Formed steel, chrome-plated.
B. Lettering:{ }“FIRE EXTINGUISHER” decal, or vinyl self-adhering, pre-spaced red lettering in accordance with authorities having jurisdiction (AHJ).
PART 3 EXECUTION
3.01 EXAMINATION
A. Verify existing conditions before starting work.
B. Verify rough openings for cabinet are correctly sized and located.
3.02 INSTALLATION
A. Install in accordance with manufacturer's instructions.
B. Install cabinets plumb and level in wall openings.
C. Secure rigidly in place.
D. Hang extinguishers in cabinets.
END OF SECTION
�150-C
�1
-A
�153 15
�1
-B
FEC
OS
OS OS
OS
OS
OS
�150-C
�1
-A
�153 15
�1
-B
SL
O
PE
1"
SLOPE
1"
SLOPE
1"
SL
O
PE
1"
SL
O
PE
1"
SLOPE
1"
SLOPE
1"
SL
O
PE
1"
SLO
PE
1"
SLOPE
1"
SLOPE
1"
SLOPE1"
SL
O
PE
1"
SL
O
PE
1"
SLOPE
1"
SL
O
PE
1"
SLOPE
1"
SL
O
PE
1"
SL
O
PE
1"
SLOPE
1"
SL
O
PE
1"
SLOPE
1"
SL
O
PE
1"
SLOPE
1"
SLOPE
1"
SL
O
PE
1"
SLOPE
1"
SL
O
PE
1"
SLOPE
1"
SLOPE
1"
SL
O
PE
1" SLOPE
1"
�150-C
�1
-A
�153 15
�1
-B
LIGHT FIXTURES
(SEE ELECTRICAL)
GRILLES AND DIFFUSERS
(SEE MECHANICAL)
GYPSUM BOARD CEILING
LEGEND:
FOR CEILING HEIGHTS, SEE ROOM FINISH SCHEDULE
FIRE ALARM STROBE, SEE ELEC
FIRE ALARM SPEAKER, SEE ELEC
FIRE ALARM SPEAKER STROBE,
SEE ELEC
OCCUPANCY SENSOR, SEE ELEC
EXIT SIGN, SEE ELEC
FIRE ALARM HORN, SEE ELEC
FIRE ALARM HORN STROBE,
SEE ELEC
SMOKE DETECTOR, SEE ELEC
SPEAKER, SEE ELEC
F
F S
F S
OS
F
F
S
S
A501 79
A501 111
A50115
FAMILY
WOMEN
LOBBY
MEN
A5015 3
C
A
C
A
C
B
B
C
C
'-4
/2
7'
-8
3' -5
'-9
/4
3'
-1
/8
3'-6"
3'-0" 7'-0"
2'-2 1/4" 2'-9 3/4" 1'-11" 5'-4" 4'-9"
8 1/2"
7'-7 1/2"AL F1
UTILITY
154B
3 3
MECH CHASE
7' -6
/8
A301
A
A301
A
C
8 1/2"
A501
20 TA-7
ADD BACKING FOR
GRAB BAR
ADD BACKING FOR
GRAB BAR
ADD BACKING FOR
WATER HEATER
A.F.F.
5/8" GWB on Wood Stud
8' - 6"
A.F.F.
5/8" GWB on Wood Stud
8' - 6"
A.F.F.
5/8" GWB on Wood Stud
8' - 6"
WOMEN
MEN
FAMILY
LOBBY
A.F.F.
5/8" GWB on Wood Stud
8' - 6"
A.F.F.
5/8" GWB on Wood Stud
8' - 6"
A B C
CEILING
8'-6" A.F.F.
7 1/4" 4 1/4" 4 7/8"
5'- 7"
Ø
10"
ALLOWABLE OVERLAP
ADA CLEARANCES ARE CRITICAL. ONCE
MARKED ON THE FLOOR AND PRIOR TO
FRAMING, CONFIRM THAT CRITICAL
DIMENSIONS ARE ACHIEVED.
FAMILY
WOMEN
LOBBY
MEN
UTILITY
MECH CHASE
FLAT
FLAT
EXISTING STRUCTURE ABOVE
WITH NEW R-42 BLOWN-IN INSULATION
VAPOR BARRIER
GYPSUM BOARD CEILING
WOOD STUDS
16" O.C.
CEILING
8'-6" A.F.F.
2X NEEDED AT BOTH SIDES OF THE CORNERS
TRUSS CHORD BOTTOM
HSS 3 x 1-1/2 x 1/4 CONT.
TYP.
1/4"
L2-1/2 x 1-11/2 x 1/4 x 2"-LONG W/ (2) NO. 10
WOOD SCREWS EACH SIDE OF HSS AT EACH
TRUSS. COORDINATE STRUCTURAL SUPPORT
LOCATIONS WITH PARTITION MANUFACTURER.
CEILING-HUNG PARTITION
ALIGN CONTINUOUS
STRUCTURAL STEEL WITH
PARTITION SUPPORTS.
COORDINATE STRUCTURAL
SUPPORT LOCATIONS WITH
PARTITION MANUFACTURER.
ALIGN CONTINUOUS
STRUCTURAL STEEL WITH
PARTITION SUPPORTS.
COORDINATE STRUCTURAL
SUPPORT LOCATIONS WITH
PARTITION MANUFACTURER.
EXISTING TRUSSES
1300 w 57th Street | Suite 2 Sioux Falls, SD 57108
(605) 332-7850 www.schemmer.com
REVISED TITLE OF SHEET DRAWING NO.
SHEET
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATE
238608 / 80005
80005
C :\U se rs
\e lin eh an
\D oc um en ts \R ev it_ te m p\
-A
R C
H _R
_e lin eh an
BC
9A F.
rv t
RJM
EML
RTG
01/10/2025
009258.004
A101
FLOOR PLAN & REFLECTED
CEILING PLAN
009258004- 2- A101 FLOOR PLAN & REFLECTED CEILING PLAN
RESTROOM REMODEL & DOOR HINGE
JEWEL CAVE NATIONAL MONUMENT
CUSTER, SD
2 WALL-MOUNTED WATER CLOSET WITH FLUSH VALVE. REFER TO
PLUMBING.
3 WALL-MOUNTED WATER CLOSET WITH FLUSH VALVE, ACCESSIBLE
HEIGHT. REFER TO PLUMBING.
4 URINAL & FLUSH VALVE. REFER TO PLUMBING.
5 SINK. REFER TO PLUMBING.
6 HAND DRYER AND SOAP DISPENSER INTEGRATED INTO WASH BAR.
REFER TO ELECTRICAL AND PLUMBING.
8 ADULT CHANGING TABLE.
10 URINAL SCREEN WITH CONTINUOUS MOUNTING BRACKET.
11 TOILET PARTITION PANEL AND DOOR - CEILING HUNG.
13 FLOOR DRAIN. REFER TO PLUMBING.
19 CEILING ACCESS HATCH 2'-3" X 2'-3".
20 GYPSUM WALL BOARD, VAPOR BARRIER AND INSULATION TO INTERIOR
SIDE OF PERIMETER WALLS.
22 FIRE EXTINGUISHER AND CABINET.
24 SLAB JOINT.
25 30" X 22" CEILING ACCESS PANEL. FIELD VERIFY LOCATION BETWEEN
STRUCTURAL MEMBERS.
26 HEATER. REFER TO MECHANICAL. REFERENCED PLAN NOTES
27 ADA PUSH BUTTON DOOR OPENER, SEE ELECTRICAL.
A PROVIDE & MAINTAIN 2 ADA ACCESSIBLE AND 6 STANDARD PORTABLE
TOILETS WITH HAND SANITATION DURING CONSTRUCTION ONLY.
CONFIRM LOCATION WITH OWNER. SEE COVER SHEET FOR LOCATIONS
AND SPECIFICATIONS FOR DETAILS AND REQUIREMENTS.
REF. NOTES ( ):X
KEY PLAN NORTH
A
SCALE: 1/4" = 1'-0"
FIRST FLOOR AREA 'A'
SCALE: 1/4" = 1'-0"
FIRST FLOOR AREA 'A' - REFLECTED CEILING
TYPE WIDTH
A 0' - 7 1/4" 6" MET FRAME GWB BOTH SIDES
B 0' - 4 1/4" MET FRAME GWB ONE SIDE
C 0' - 4 3/4"
C 0' - 4 7/8" MET FRAME GWB BOTH SIDES
SCALE: 1/4" = 1'-0"
PARTITION TYPES
SCALE: 1/4" = 1'-0"
ADA TURNING RADIUS KEY
NOT TO SCALE
FIRST FLOOR AREA 'A' SLAB LAYOUT
DATE INITIAL
07/25/2025 EML
08/18/2025 EML
NOT TO SCALE
CEILING DETAIL
SCALE: 1/4" = 1'-0"
FIRST FLOOR AREA 'A' PARTITION FRAMING
�150-C
�1
-A
�153 15
�1
-B
FEC
MEN
WOMEN
LOBBY
FAMILY
UTILITY
A801
SOME BUILDING ELEMENTS NOT SHOWN FOR CLARITY. ONLY USE THIS PLAN FOR
FLOOR FINISHES, SEE AREA PLANS FOR DETAILED INFO.
EPX-1: FLUID APPLIED EPOXY
FLOORING
METAL CAP STRIP
INTEGRAL EPOXY
QUARTZ WALL BASE
COVE CANT STRIP
METAL DIVIDER STRIP
EPOXY QUARTZ FLOORING
4"
EPOXY
FLOORING
ALUMINUM TRANSITION STRIPAREA OF
REFUGE
" M
IN
" M
AX
18" CLEAR @ SIGN
DOOR SIGNAGE
DOORS
1300 w 57th Street | Suite 2 Sioux Falls, SD 57108
(605) 332-7850 www.schemmer.com
REVISED TITLE OF SHEET DRAWING NO.
SHEET
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATE
238608 / 80005
80005
C :\U se rs
\e lin eh an
\D oc um en ts \R ev it_ te m p\
-A
R C
H _R
_e lin eh an
BC
9A F.
rv t
RJM
EML
RTG
01/10/2025
009258.004
A801
FINISH FLOOR PLAN AND
SCHEDULE
009258004- 2- A801 FINISH FLOOR PLAN AND SCHEDULE
RESTROOM REMODEL & DOOR HINGE
JEWEL CAVE NATIONAL MONUMENT
CUSTER, SD
SCALE: 1/4" = 1'-0"
FIRST FLOOR FINISH PLAN AREA 'A'
17 EPOXY TO CONCRETE ALUMINUM TRANSITION TRIM.
REF. NOTES ( ):X
ROOM SCHEDULE
ROOM NO ROOM NAME
FLOOR
MATL
FLOOR
FINISH
BASE
MATL
PLAN NORTH WALL PLAN EAST WALL PLAN SOUTH WALL PLAN WEST WALL
REMARKSMATL FINISH MATL FINISH MATL FINISH MATL FINISH
150 LOBBY CONC. EPX-1 EPX-1 GYP PNT-2 GYP PNT-2 GYP PNT-2 GYP PNT-2
151 MEN CONC. EPX-1 EPX-1 GYP PNT-2 GYP PNT-2 GYP PNT-2 GYP PNT-2
152 WOMEN CONC. EPX-1 EPX-1 GYP PNT-2 GYP PNT-2 GYP PNT-2 GYP PNT-2
153 FAMILY CONC. EPX-1 EPX-1 GYP PNT-2 GYP PNT-2 GYP PNT-2 GYP PNT-2
154 UTILITY CONC. EPX-1 EPX-1 FRP FRP FRP FRP FRP FRP FRP FRP
155 MECH CHASE CONC. NONE NONE NA NA NA NA NA NA NA NA
INTERIOR FINISH MATERIAL SCHEDULE
SECTION DESCRIPTION LOCATION MANUFACTURER STYLE STYLE NO. PATTERN SIZE COLOR COLOR NO. REMARKS
EPX-1 09-6700 FLUID APPLIED FLOORING KEY RESIN COMPANY POLAR
PNT-1 09-9123 PAINT HOLLOW METAL FRAMES SHERWIN WILLIAMS DIRECT TO METAL PAINT - SATIN FINISH SW7068 GRIZZLE GRAY
PNT-3 09-9123 PAINT CEILING SHERWIN WILLIAMS SW7757 HIGH REFLECTIVE WHITE
PNT-4 09-9123 PAINT HOLLOW METAL DOORS SHERWIN WILLIAMS SW9163 TIN LIZZIE
PNT-2 09-9656 HIGH PERFORMANCE COATING WALL SHERWIN WILLIAMS SW7650 ELLIE GRAY
TP-1 10-2113.19 PLASTIC TOILET COMPARTMENTS RESTROOM TOILETS SCRANTON HINY HIDERS PARTITIONS GRIP EX BLACK
SS-1 22-4216.03 COMMERCIAL LAVATORIES AND
FAUCETS
VANITY TERREON SOLID SURFACE MOONSTONE
FLOORING TYPES
KEY PLAN NORTH
A
SCALE: 6" = 1'-0"
2 EPOXY WALL BASE
SCALE: 6" = 1'-0"
3 EPOXY TO CARPET
NOT TO SCALE
RESTROOM SIGNAGE
NOT TO SCALE
SIGNAGE DETAILS
DATE INITIAL
08/13/2025 EML
OS
OS OS
OS
OS
OS
J J
J J
J J
J
J
J
J
J
J
J J
CORRIDOR
117A LOBBY
MEN
WOMEN
FAMILY
UTILITY
PANEL 'L-RR'
A1E
A1
C05
C05 C05
C05
C05
I4
A1EA1
A1E
A1A1
A1E
(+9' AFF)
C05
E401
(TYP.)
E401
(TYP.)
W1 W1
W1W1
+7' - 0" AFF
X1
CORRIDOR
117A
LOBBY
MEN
WOMEN
FAMILY
AC, G AC, G
AC, G
L-RR - 4
EWC-1
A - 10
EF-1
G G
GG
G G
(+22" AFF - TYP. OF 6)
G
(+22" AFF)
PANEL 'L-RR'
WP, G
(ON ROOF)
(ON ROOF)
1 1
7 10
11 1
UTILITY
E402
(TYP.)
G +48"
L-RR - 1
TP-1
L-RR - 13,15
EWH-1
(+96" AFF)
L-RR - 1
DWCP-1
L-RR - 6
EUH-1
L-RR - 2
FLUSH VALVE
PANEL 'A' 21
L-RR - 17
DOOR OPERATOR
1300 w 57th Street | Suite 2
Sioux Falls, SD 57108
(605) 332-7850 www.schemmer.com
REVISED TITLE OF SHEET DRAWING NO.
SHEET
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATE
238608 / 80005
80005
C U s e rs \j b in g e \D o c u m e n ts \R e v it te m p
\0
-E L
E C
R jb in g e .r v t
DES
DRW
CHK
01/10/2025
009258.004
E101
FLOOR PLAN - LIGHTING,
POWER, & AUXILIARY
009258004- 7- E101 FLOOR PLAN - LIGHTING, POWER, & AUXILIARY
RESTROOM REMODEL & DOOR HINGE
JEWEL CAVE NATIONAL MONUMENT
CUSTER, SD
REF. NOTES ( ):X
1 CONNECT NEW LIGHTING TO EXISTING CIRCUIT IN PANEL 'A' PREVIOUSLY
SERVING LIGHTING IN THIS AREA.
2 FIXTURE AND SWITCH ARE EXISTING AND RELOCATED. SEE E001 FOR
ORIGINAL LOCATIONS. CONNECT TO CIRCUITS PREVIOUSLY SERVING
DEVICES. USE EXISTING CONDUIT AND CONDUCTORS TO EXTENT
POSSIBLE. DO NOT SPLICE CONDUCTORS.
21 CONNECT NEW PANEL TO EXISTING SERVING FEEDER AND RECONNECT
EXISTING BRANCH CIRCUITS.
22 CONNECT TO 20/1 CIRCUIT BREAKER IN PANEL 'A' PREVIOUSLY SERVING
RESTROOM EXHAUST FANS,
KEY PLAN NORTH
A
SCALE: 1/4" = 1'-0"
FIRST FLOOR PLAN - LIGHTING
SCALE: 1/4" = 1'-0"
FIRST FLOOR PLAN - POWER & AUXILIARY SYSTEMS
DATE INITIAL
08/15/2025 JCB
08/15/2025