Atch 1 - Project 16008_ UPS Specification.pdf
PDF 274 KB Posted
- Attached to
- Project 16008: Uninterruptible Power Supply Federal contract opportunity
- Solicitation number
- FA9101-23-Q-B019
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| FA9101-23-Q-B019 - Questions and Answers - 2 - Project 16008 Uninterpretable Power Supply-Combined Synopsis Solicitation-Final.pdf | ||
| FA9101-23-Q-B019 - Questions and Answers - Project 16008 Uninterpretable Power Supply-Combined Synopsis Solicitation-Final.pdf | ||
| FA9101-23-Q-B019 - Model Contract.pdf | ||
| FA9101-23-Q-B019 - Project 16008 Uninterpretable Power Supply-Combined Synopsis Solicitation-Final.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Specifications – Project 16008: UPS
Item 0001 - Quantity: 1 / Description: 20kVA Uninterruptible Power Supply (UPS) System
• UPS Type: Online Double Conversion, with static bypass
• UPS/Load Protection: Constantly monitors operation and transfers power to bypass source on problem; reverts to normal operation automatically if problem is corrected
• Battery (if installed in UPS cabinet): Sealed, valve regulated, reduced maintenance, lead acid cells
(VRLA), flame retardant suitable for installation in a computer room per requirements of UL
Standard 1778
• Battery charger overvoltage protection
• Battery charger, overcurrent protection
• VA rating: 20,000 minimum
• Wattage rating: 18,000 minimum
• Input: Hardwired, 3-Phase, 4-Wire, 208Y/120VAC
• Output: Hardwired, 3-Phase, 4-Wire, 208Y/120VAC
• Maintenance Bypass: Discrete wall-mount maintenance bypass panel providing wrap-around bypass for complete UPS isolation from the load, with mechanical interlocks
• Operating Environment: (0 – 40) Deg. C
• Communication: Relay output contacts to indicate utility power failure, low battery, UPS alarm/
OK, and in bypass mode; Input for remote power-off
• Communication: LCD Display that provides load status, alarms, events, measurements, and settings
• Battery runtime: Minimum 15 minutes @ full load
• Warranty: 1 year minimum
• Training: Basic operator training conducted as part of system start-up
• Audible noise: Less than 65 dB @ 1 meter
• Certifications: Built to UL1778 / NEC, UL Listed or Recognized
• Construction: Metal chassis, preferably painted steel (power coat)
• Cabinets: Batteries may be in separate cabinet to meet capacity for minimum run time requirement
• Site Testing/Inspection: Manufacturers field service personnel shall provide system start-up testing, and initial operation pre-inspection o Verify proper installation to meet warranty requirements o UPS system operational test as part of start-up procedure o Partial battery discharge test as part of start-up procedure o Test/inspection shall be documented, signed, and dated
Item 0002 - Quantity: 1 / Description: 20kVA Uninterruptible Power Supply (UPS) System extended battery module (as required to meet minimum UPS battery minimum run time)
• Compatible with Item 0001 20,000 VA UPS System
• Warranty: 1 year minimum
• Battery: Sealed, valve regulated, reduced maintenance, lead acid cells (VRLA), flame retardant suitable for installation in a computer room per requirements of UL Standard 1778
• Main Circuit Breaker rated for battery overload protection and isolation from UPS for battery maintenance or replacement
• Certifications: Built to UL1778 / NEC, UL Listed or Recognized
• Construction: Metal chassis, preferably painted steel (power coat)
** ALL QUOTED ITEMS SHALL BE NEW AND NOT REFURBISHED**