This pre-solicitation notice provides details for an upcoming federal contract opportunity to upgrade communication facilities and infrastructure at Aviano Air Base in Italy. The scope of work includes civil, architectural, structural, mechanical, electrical, and communications upgrades and additions at three buildings. The contract value is estimated between $1 million and $5 million. Interested vendors must have an active System for Award Management registration and certification in Operational Group 11 construction categories. A site visit is scheduled. The solicitation is expected to be issued in February 2023. Responses are due in accordance with the forthcoming solicitation. The work will be performed under Italian law.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| AVIANO MASTERSPECS 2020.pdf | ||
| ASHE 21-2001 PSC.pdf | ||
| ASHE 21-2001 CCEB.xls | XLS spreadsheet | |
| ASHE 21-2001_Dwgs 73-135.pdf | ||
| ASHE 21-2001_Dwgs 1-72.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Prepared and Submitted by:
Architecture, Engineering and Consulting Services Via di Sacco Pastore n. 4 - Rome, Italy
Tel. +39.06.97848041 fax +39.06.97848175 E-mail: design@soinci.it
31st FIGHTER WING 31st CIVIL ENGINEERING SQUADRON
31st CES/CENM PROJECT MANAGEMENT ELEMENT
PROJECT ASHE 21-2001
UPGRADE COMM FACILITIES
AND INFRASTRUCTURE
AVIANO AB, ITALY
TECHNICAL SPECIFICATIONS
FINAL SUBMITTAL (100%)
Date: Jan 2023
Prepared and Submitted by:
Architecture, Engineering and Consulting Services Via di Sacco Pastore n. 4 - Rome, Italy
Tel. +39.06.97848041 fax +39.06.97848175 E-mail: design@soinci.it
31st FIGHTER WING 31st CIVIL ENGINEERING SQUADRON
31st CES/CENM PROJECT MANAGEMENT ELEMENT
PROJECT ASHE 21-2001
UPGRADE COMM FACILITIES
AND INFRASTRUCTURE
AVIANO AB, ITALY
HAVING REVIEWED THE DEFINITIVE AND DETAILED PROJECT, I DECLARE THAT I HAVE ASCERTAINED THAT
THE STRUCTURES AND THE TECHNOLOGICAL SYSTEMS INCLUDED THEREIN COMPLY WITH THE APPLICABLE
ITALIAN NORMS.
Date: Jan 2023
Architectural, Civil and Structural
Arch. M. Cantagallo
Ordine degli Architetti della Provincia di Frosinone
No.338
Mechanical Systems:
Ing. Pierluigi Chiarello Ordine degli Ingegneri della Provincia di Roma
No.24166, sez. A
Electrical Systems:
Ing. M. Ferrigno
Ordine degli Ingegneri della Provincia di Roma
No.36957, sez. A
INDEX
SECTION PAGE No.
AC1 - SCOPE OF PROJECT AND APPLICABLE CONDITIONS 1-22
AF FORM 66 - SCHEDULE OF MATERIAL SUBMITTALS 23
− Building 1442 24-30
− Building 11341 31-36
− Building 1304 (Ss F04) 37-39
REVISED MASTER SPECIFICATIONS 40-51
ADDITIONAL SPECIFICATIONS 52-63
SCHEDULE OF WORK ITEMS 64
− Building 1442 65-110
− Building 11341 111-144
− Building 1304 (Ss F04) 145-166
ASHE 21-2001 – Upgrade Comm Facilities 2
SECTION AC1
SCOPE OF PROJECT AND APPLICABLE CONDITIONS
AC1-01 SCOPE OF PROJECT: The Scope of this project number ASHE 21-2001 is
“UPGRADE COMM FACILITIES AND INFRASTRUCTURE” of Aviano Air Base to achieve
Rating-3 standard as per TIA942 and DoD standards.
This project involves three buildings:
Building 1442 – ICC Building
Building 11341 – Alternate Comm facility
Building 1304 – Electrical Substation F04
Project works for each facility are described below:
a. CIVIL / ARCHITECTURAL
Building 1442
As was already noted in the February 2018 Gap Analysis it will not be economically feasible for Building #1442 to be upgraded to meet all the A2 or A3 standards of TIA-942, it was recommended to accept the data centers in their current condition.
All general construction modifications required would be in support of new infrastructure equipment being installed and improving seismic safety conditions of existing equipment.
Works to be provided are as follows:
− Construction of a new generator room to be built adjacent to the existing outdoor technical space, including:
Demolition Works:
− Excavations on bituminous concrete pavement.
− Excavations on earth.
− Concrete pavement demolition.
Structural works:
− Furnishing and placing of C16/20 lean concrete
− Furnishing and placing of C28/35 concrete foundation and walls
− Furnishing and placing of predalle type floor and roof slabs.
− Furnishing on installation of B450C steel reinforcement.
− Furnishing and installation of root resistant bituminous membrane
− Testing of the structure
Civil works:
− Construction of reinforced concrete pavement
− Furnishing and placing of prefabricated concrete road curbs
− Construction/Repair of bituminous concrete pavement
− Upgrading of existing underground utilities including existing underground utilities re-routing
Architectural works:
ASHE 21-2001 – Upgrade Comm Facilities 3
− Furnishing and placing of 10cm thick industrial type floor pavement.
− Furnishing and installation of roofing system, including flashings, downspouts and fall protection system.
− Furnishing and placing of exterior plaster
− Painting of interior/exterior surfaces
− Furnishing and installation of marble sills, thresholds, and baseboard
− Furnishing and installation of ventilation steel louvers
− Furnishing and installation of steel doors.
− Furnishing and installation of additional seismic bracings to all life safety systems, UPS and batteries. Cabinets within the critical rooms shall be bolted to the floor to reduce the possibility of tipping.
Building 11341
The building is a single room stand-alone building, with no immediate adjacencies that could pose security issues, provided with 25 cm thick walls are robust and should provide adequate protection of the equipment inside.
Due the space limitations a new addition will be provided to house electrical equipment while comm equipment shall remain in the existing building.
Works to be provided are as follows:
Demolition Works:
− Excavations on bituminous concrete pavement.
− Excavations on earth.
− Partial demolition of existing concrete sidewalk.
− Partial demolition of concrete wall to provide existing door enlargement and new passageway to the addition.
− Metal door removal
− Removal of existing downspouts, including concrete splash blocks.
Structural works:
− Furnishing and placing of C16/20 lean concrete
− Furnishing and placing of C28/35 concrete foundation and walls
− Furnishing and installation of B450C steel reinforcement
− Furnishing and placing of predalle type roof slab
− Furnishing and installation of root resistant bituminous membrane
− Furnishing and installation of structural joints
− Testing of the structure
Civil works:
− Construction of reinforced concrete sidewalk
− Construction/Repair of bituminous concrete pavement
− Construction of equipment yard including concrete pads and metal fencing for new infrastructure equipment
− Upgrading of existing underground utilities including existing underground utilities re-routing, where needed
− Miscellaneous site work.
Architectural works:
− Furnishing and placing of 30cm thick gravel material subbase
ASHE 21-2001 – Upgrade Comm Facilities 4
− Furnishing and placing of 15cm thick industrial type floor pavement.
− Furnishing and installation of roofing system including flashings, downspouts, metal joints cover and fall protection system.
− Furnishing and placing of exterior plaster
− Painting of interior/exterior surfaces including plaster repair where needed
− Furnishing and installation of marble sills, thresholds, and baseboard
− Furnishing and installation of ventilation steel louvers
− Securing of equipment for seismic activity
− Furnishing and installation of steel doors, including upgrade entry door to building for security purposes
− Installation of vinyl antistatic coating to existing and new concrete pavement
Building 1304 - Substation F04
All general construction modifications required would be in support of new infrastructure equipment being installed.
Architectural and civil works are summarized as follows:
− Painting of exterior wall surfaces
− Painting of interior wall surfaces
− Painting of exterior/interiors metal surface as doors, screens, flashings, and downspouts
− Supply and installation of new mouse screen, incl, frame
− Supply and installation on existing doors of panic bar
b. MECHANICAL
To conforms to the TIA, RMF, and DCRA requirements for the Data Center Design the Mechanical Systems shall be Rated-3.
General requirements
The general requirements for mechanical systems (valid both for Bldg. 1442 and 11341) as identified in the “BT Federal Report – 221093” can be summarized as follows:
HVAC
− The systems shall allow concurrent maintenance. It shall be possible to handle maintenance on any part of distribution path or any single piece of equipment without causing interruption to the data center operations.
− N+1 redundancy for mechanical equipment.
− Temporary loss of electrical power or interruption of water shall not cause loss of cooling.
− All new CRAC units shall be provided with an onboard electric humidifier.
− Piping systems shall allow for concurrent maintainability.
ASHE 21-2001 – Upgrade Comm Facilities 5
− All systems shall be provided with a monitoring system able to alarm if loss of cooling or a change of state occur. Remote temperature and humidity sensors shall be installed in all data center, UPS and battery areas.
− A leak detection system shall be installed to protect from chilled water or condensate leakages in each of the technical rooms.
− A positive pressure shall be maintained within the data center as related to outdoors and non-data center spaces, supply fan shall supply fresh air and maintain room pressurization.
− A failure of the building automation system BAS should not prevent cooling to the critical areas. All CEDC equipment shall have local controllers (standalone controllers) that run independent of the BAS in case of BAS failure. In case of BMS failure or signal loss the local controller shall sustain cooling operation in either full on or last control position until BMS control is re-established
Fire Suppression
− A gas suppression system shall be installed.
− The system shall be a chemical gas using a “clean agent” as extinguishing agent as Novec 1230 or other technically equivalent.
− No inert gas system shall be installed.
− The system shall be activated automatically by a detection system
(conventional or VESDA type) according to standard procedures for this type of system (count-down, quick release, abort functions, proper labelling, etc.). A second shot reserve gas supply should be available during re-charge operation.
BUILDING 1442
The duplication of the CRACU air conditioners in rooms 224 and 225 hypothesized by BT Federal report is not feasible due to the lack of space and not necessary.
The solution we propose consists in the installation of an alternative line of chilled water produced by a new chiller and, for both room 224 and 225, in the connection of one of the two air conditioners (CRACU) to this new line.
In rooms where the CRACUs cooling capability is not enough to neutralize the thermal loads, additional air conditioners, additional direct expansion
(“DX”) type shall be installed.
Both CRACUs and DX air conditioners shall be No.2 and of the same cooling capacity. A CRACU and a DX air conditioner shall be supplied by a dedicated electrical panel, which shall be connected to an electrical line (for example the ordinary line). The other CRACU and DX air conditioner shall be supplied by another dedicated panel, which shall be supplied by a different electrical line. In this way, if a failure occurs in any equipment or distribution path, the system can supply the necessary cooling power to the room in order to maintain the correct room temperature.
On the basis of the above considerations, the main necessary works are described below:
− Installation of a new chiller (CH-3), cooling capacity of about 120kW, with desuperheater and free-cooling option, and the relevant new chilled and hot water distribution lines to alternatively feed the
CRACU in rooms #224 and #225.
ASHE 21-2001 – Upgrade Comm Facilities 6
− Room #128: existing CRAC units comply to Rated-3 requirements in terms of cooling capacity and redundancy/concurrent maintainability. No additional CRAC unit is needed.
Existing CRACU #1, #2 and #2bis shall be equipped with a MODbus card provided by the own manufacturer of each unit
− Room #224: the following works are considered:
− Removal of the existing portable conditioner PDXU-2
− connection of one of the two existing CRACUs to the new chilled water line
− installation of an additional DX air-conditioner “in row” type with cooling capacity of about 24kW
− Existing CRACU #5, #6 and PDXU-1 shall be equipped with a MODbus card provided by the own manufacturer of each unit.
− Room #225: the following works are considered.
− connection of one of the two existing CRACUs to the new chilled water line
− installation of an additional DX air-conditioner “in row” type with cooling capacity of about 24kW
− Existing CRACU #3, #4 and PDXU-3 shall be equipped with a MODbus card provided by the own manufacturer of each unit.
− Room #174: No.2 additional DX fan-coils, about 30kW cooling capacity each, shall be installed.
− Installation of an overpressure monitoring system in each of the Rooms
#128, #224, #225
− Installation of a temperature/humidity monitoring system in each of the
Rooms #128, #224, #225, #174
− Installation of a leak detection system in each of the Rooms #128, #224, #225, #174
− Installation of a dedicated controls and monitoring system connecting the room pressurization, leakage and temp/hum monitoring systems by a
MODbus on RS485.
− The air conditioners of each room will be grouped into two groups of equal power and powered by different electrical panels. The No. 2 electrical panels must be powered by different power lines (see electrical design description).
− NOVEC 1230 fire suppression systems to be installed in the involved
CEDC Rooms: #128 and #B01, #130, #224, #225 and #174, including cylinder storage, piping, controls and accessories. Systems shall be connected and interfaced to/from the fire alarm system of the building
(see electrical design documents).
− Diesel pipeline (supply and return line) for the connection of the new electrical generator to the new fuel tank. Line in Copper pipes or equivalent approved for fuel transportation, underground pipes, leak detection system, valves, inline devices, in accordance to in force laws and codes.
− Ventilation louvers and exhaust fans and electric heater unit in the generator room including actuators, controls, wirings, and monitoring system
− Monitoring system for the existing room ventilation system in UPS Room
#174.
BUILDING 11341
Bldg.11341 will be added by a technical room for UPSs and electrical panel.
In the Rack Room the original equipment will be added by new ones. The
ASHE 21-2001 – Upgrade Comm Facilities 7 existing HVAC system is completely inadequate and shall be remove and replaced by a new one.
The main working items are the following:
− Removal of the No.2 existing ari conditioner in the building
− In the Rack room, No.4 DX mono-split air conditioners (ceiling mounted fan coils and external condensing unit) shall be installed.
− In the new UPS room, No.2 DX systems (ceiling mounted fan coils and external condensing unit) shall be installed.
− Installation of a new ventilation system in order to guarantee the pressurization of the above mentioned rooms.
− Installation of an overpressure monitoring system in each of the Rack and UPS Room
− Installation of a temperature/humidity monitoring system in each of the
Rack and UPS Room
− Installation of a leak detection system in each of the Rack and UPS
Room
− Installation of a dedicated controls and monitoring system connecting the room pressurization, leakage and temp/hum monitoring systems by a
MODbus on RS485.
− The air conditioners of each room will be grouped into two groups of equal power and powered by different electrical panels. The No. 2 electrical panels must be powered by different power lines (see electrical design description).
− NOVEC 1230 fire suppression systems to be installed in the involved
CEDC Rooms: each of the Rack Room, UPS Room and Basement Room, including cylinder storage, piping, controls and accessories. Systems shall be connected and interfaced to/from the fire alarm system of the building
(see electrical design documents).
BUILDING 1304
Bldg.1304 will be equipped with a technical ventilation system sized in order to limit the internal temperature of the building due to the heat load of electrical equipment hosted.
The main working items are the following:
− Installation of a ventilation system composed by No.2 wall electrical fans in service backup configuration and related controls and accessories.
At the end of the mechanical works, the entire systems shall be tested in accordance with applicable norms and the “Dichiarazione di Conformità” in accordance with the Law 37/08 shall be provided.
For existing systems that will remain after works, if without an existing”
Dichiarazione di Conformità”, the contractor shall provide a “Dichiarazione di Rispondenza” in accordance with the Law 37/08 if applicable.
c. ELECTRICAL
To conforms to the TIA, RMF, and DCRA requirements for the Data Center Design the Electrical System shall be rated 3 (E3).
Rated-3 Data Center: Concurrently Maintainable
ASHE 21-2001 – Upgrade Comm Facilities 8
A Concurrently Maintainable data center can handle planned maintenance on any part of the distribution path or any single piece of equipment or component without causing interruption to the data center operations.
Rated-3 data centers have, at a minimum, one active (N) and one standby (+1) path for distribution of power, cooling and telecommunications. There is no requirement for component/equipment redundancy within each distribution path.
Rated-3 data centers do not require, but should be compartmentalized for electrical, mechanical and telecommunication critical facilities.
Rated-3 data centers have improved physical security controls.
All works shall be done in Phases. Contractor, before starting the works shall submit for approval a Working phase schedule and GANT to avoid any power source interruptions to the activities at buildings 1442 and 11341.
To achieve Rated 3 Requirements the following works shall be provided:
BUILDING 1304 - SUBSTATION F04
− Remove of the existing HV and LV Switchgears;
− Remove of the existing Transformers;
− Remove miscellaneous electrical equipment to conforms and reflect the restored substation;
− Replace existing obsolete (19 years old) HV Switchgear, with new one
SF6 gas insulated;
− Replace two existing 1000 kVA cast resin transformer, 15 years old, not running in parallel, with two new cast resin transformers of adequate power running in parallel at 50% load each, and able to supply both
RAPCON and ICC loads at the same time (proposed 2x1250kVA Transformers);
− Replace existing two LV Switchgear (LVS1 and LVS2), obsolete (19 years old) with one new LV Switchgear circuit breakers equipped to provide the parallel of the two new cast resin transformers;
− Replace existing miscellaneous electrical devices, such us Power Factor
Correction Units, Substation Panels, Exhaust Fan System, etc., to reflect the new substation layout.
BUILDING 1442
− Provision of new emergency backup generator 800 kVA rated. New Backup generator should be housed in new generator. Architectural works shll be also provided in order to house new generator.
− New cable connections should be provided to reflect the new conditions;
− Replace existing obsolete UPS in UPS Room;
− New 2x300 kVA UPS, 30 min each minimum autonomy, with lithium type batteries;
− Provision of new Distribution Panels EP1 and MUPB;
− Provision of new Distribution Panels under Path “B” such as NIPR B1, NIPR B2, NIPR B3, SIPR B1, SIPR B2;
− New Emergency Power Off (EPO) underglass push buttoms;
− Rearrange interior distribution system for Computer loads in NIPR, SIPR and SWITCHING ROOM, including new electrical panels and wirings in so manner to have two paths (“A” and “B”) for the telecom equipment.
Telecomm equipment shall be dual cord supplied: one cord from path “A” and other cord from path “B” electrical panels.
In order to meet Rated-3 criteria, two power paths will be provided throughout the installation. Path “A” will operate in normal
ASHE 21-2001 – Upgrade Comm Facilities 9 conditions. Path “B” will operate only during the maintenance operations.
- New Static Transfer Switches (STS) shall be provided in all the existing telecom racks in order to meet the dual cord criteria.
− Upgrading of the existing Grounding and Lightning Systems;
− Miscellaneous security equipment such as new/implementation of TVCC outside the critical area;
− Upgrading of the existing Fire Alarm System;
− Telemonitoring System. The system should monitor the HV Switchgear
(Status and power), LV Switchgear (Status of the breakers and power), Transformers (Temperature levels), UPS (Status and temperature levels), Backup Generators (Status and temperature levels), the A/C Units
(Status and power). The Telemonitoring System should be connected to a
Control Room inside the Building with personnel that can manage the alarms in real time and at the same time can do start the maintenance technicians, in order to prevent any accidental power outage to the activities.
BUILDING 11341
The design is based on new telecom loads as provided during site visit performed on October 20 and 21:
− The existing normal power to B.11341 will be rewired, by two feeds from the nearest substations, Sub 13 and sub 14. Each feed will be from a new circuit breaker. Feeds will terminate in new, 380Y/220V, 3-Phase, 4-Wire Distribution Panels (Normal NPB and Emergency EPA) via new, 4-
Pole Automatic Transfer Switches. New Distribution Panels EPA and NPB will be located in new Technical Room. And they will serve all building loads.
− Standby power to B.11341 will be derived from two (2) new 125 kVA, 80 kW, 380Y/220V, 3-Phase, 4-Wire Diesel Generators GEN1 and GEN2.
Generators will be provided in weatherproof secure exterior enclosure with Automatic Paralleling and Transfer Switch.
− A new parallel-redundant 400V, 3-Phase, 3-Wire UPS system consisting of two (2) 60 kVA modules #1 and #2, a paralleling cabinet, with lithium type batteries, 60 min. minimum autonomy, and a maintenance bypass panel will be provided. The UPS power system will supply a new EPA
Panel and will serve as A-side source for critical / IT loads.
In order to meet Rated-3 criteria, two power paths will be provided throughout the installation. Path “B” will operate in normal conditions. Path “A” will operate only during the maintenance operations.
- New Static Transfer Switches (STS) shall be provided in all the existing telecom racks in order to meet the dual cord criteria.
− Upgrading of the existing Grounding and Lightning Systems;
− Upgrading of the existing Fire Alarm System;
− Miscellaneous security equipment such as new TVCC outside the critical area;
− Telemonitoring System. The system should monitor the LV Switchgear (Status of the breakers and power), UPS (Status and temperature levels), Backup Generators (Status and temperature levels), the A/C Units
(Status and power). The Telemonitoring System should be connected to a
Control Room inside/outside (to be defined) the Building with personnel that can manage the alarms in real time and at the same time can do start the maintenance technicians, in order to prevent any accidental power outage to the activities.
ASHE 21-2001 – Upgrade Comm Facilities 10
At the end of the electrical works, the upgraded systems shall be tested in accordance with the CEI 64/8 and the “Dichiarazione di Conformità” in accordance with the Decree No. 37/08 shall be provided.
AC1-02 TECHNICAL SPECIFICATION: The following Sections of the Master
Specifications for construction projects of the Air Base in Aviano (PN), Italy, dated March 2020 and applicable modifications, shall be applicable to the present project, together with the List of Work Items to be performed:
01100 GENERAL CONDITIONS
02220 SITE DEMOLITION
02315 EXCAVATION AND FILL
02630 STORM DRAINAGE
02722 GRADED CRUSHED AGGREGATE BASE COURSE FOR FLEXIBLE PAVEMENT
02724 AGGREGATE BASE COURSE AND SAND SUBBASE COURSE
02741 BITUMINOUS CONCRETE PAVEMENT
02821 CHAIN LINK FENCES AND GATES
02921 TURF
03401 HOLLOW SLAB SYSTEM
07214 BOARD INSULATION
07220 ROOF INSULATION
07230 ROOF WATERPROOFING MEMBRANES
07231 WALL INSULATION
07600 FLASHING AND SHEET METAL
07840 FIRE STOPPING
08110 STEEL DOORS AND STEEL FRAMES
09212 EXTERIOR STUCCO
09220 INTERIOR PLASTER
10201 METAL WALL AND DOOR LOUVERS
13855 ANALOG/ADDRESSABLE INTERIOR FIRE ALARM SYSTEM
15050 BASIC MECHANICAL MATERIALS AND METHODS
15070 MECHANICAL SOUND, VIBRATION AND SEISMIC CONTROL
15080 INSULATIONS FOR MECHANICAL EQUIPMENT
15181 CHILLED WATER AND HOT WATER PIPING
15601 CENTRAL REFRIGERATION EQUIPMENT FOR AIR CONDITIONING
15720 AIR HANDLING AND DISTRIBUTION EQUIPMENT
15810 DUCTWORK AND DUCTWORK ACCESSORIES
15950 HVAC TESTING/ADJUSTING/BALANCING
15960 DIRECT DIGITAL CONTROL SYSTEMS FOR HVAC
16303 UNDERGROUND TRANSMISSION AND DISTRIBUTION LINES
16316 SWITCHBOARDS
16360 SECONDARY SUBSTATION
16402 INTERIOR DISTRIBUTION SYSTEM
16510 INTERIOR LIGHTING
16670 LIGHTNING PROTECTION SYSTEM
See Paragraphs AC1-23 and AC1-24 for the applicable specifications.
AC1-03 SUBMITTAL OF MATERIALS: In accordance with Paragraph 2.5 of the technical specification No. 01100/R, entitled “GENERAL CONDITIONS” of the
Master Specifications, the materials listed in AF Form 66 shall be submitted as required by the time schedule indicated, for the approval by the
Contracting Officer’s Technical Representative.
The Contractor shall provide, for all the materials that will be furnished and installed, a written certification, completed with catalog data from which shall be clear the total absence of toxic-noxious materials.
The number of copies will be as required on AF Form 66.
ASHE 21-2001 – Upgrade Comm Facilities 11
AC1-04 CONSTRUCTION AREA SCREENING: All construction sites and material storage areas shall be securely fenced around the entire perimeter within an area defined by the Contracting Officer’s Technical Representative.
Bilingual signs, "VIETATO L'INGRESSO - LAVORI IN CORSO / WORK AREA - NO ENTRY" shall be placed at the work area entry and along each side of the fencing.
Fence type, height, and screening color should also be specified by the Base
Civil Engineering (BCE). Fencing shall be completely secured at top and bottom to prevent access. Fences shall be screened with opaque screening material to prevent visibility inside the fenced area. Fences and screens shall be adequately staked and/or anchored to prevent blowing over during high wind conditions. Contractor shall not start installation of area screening until approved, in writing, by BCE. Contractor shall submit photos or samples of the screening material for approval by BCE. The Contractor shall replace or repair in a timely manner, as determined by BCE, all fences and screening sections that have damage or develop unsightly rips or holes. At the end of the work or when exterior work requires it, temporary fencing shall be removed.
Night warning lights shall be installed to illuminate the work area, from sunset to dawn.
AC1-05 PROJECT SIGN: The Contractor shall furnish a project sign on site in accordance with Section 01101/R and Law 81/08. The sign shall be made of a durable material and maintained in good condition. Lettering is to be white gloss, exterior-type enamel. The sign and posts shall be given one prime coat and two finish coats of dark brown gloss exterior enamel paint.
The sign shall be erected at the designated location and shall be maintained in good condition by the Contractor until completion of the contract. The sign shall remain the property of the Contractor and shall be removed from the site upon final inspection and acceptance of the facility. Contractor identification and logo shall be allowed only on this sign and nowhere else on the exterior of the job site, with the exception of company vehicles.
There should be no signs for the purpose of advertising anywhere on the site.
Contractors shall submit sign proposal to CE for approval.
AC1-06 JOB SITE MOBILIZATION: The Contractor shall submit a proposal to
BCE diagramming their construction site and all material storage areas in locations separate from a construction site. The Contractor shall submit this plan 14 calendar days prior to the start of construction. Material mobilization and construction execution cannot begin until the plan has been approved by the base. Jobsite utility connections are the responsibility of the Contractor and shall be coordinated through BCE. Temporary overhead utility runs are prohibited. Contractor shall include a plan for supplying required utilities to their site in their proposal.
AC1-07 SAFETY: Reference regulations for construction works to applied are the following: “OSHA 29 CFR 1926 Construction Regulations”; “US Corps of
Engineers Manual EM385-1-1 Nov. 2014”; “AFMAN 91-203 Air Force Occupational
Safety, Fire, and Health Standards” and “Italian Legislative Decree 81/08”.
The contractor is responsible for ensuring overall compliance, in case of any difference, the more stringent applies.
At all times the Contractor will assure all personnel are wearing the correct safety equipment when performing their work, such as hard hats, steel toe boots, gloves, reflective gear and any other equipment deemed necessary to perform their work in the safest way. In this design service has been included by an appointed professional, R.A. Massimo Cantagallo, a site-specific Safety Plan (PSC - Piano di Sicurezza e Coordinamento), in accordance with Legislative Decree 81/08), PSC is considered equivalent to the Accident prevention plan required by Manual USACE EM385-1-1.
ASHE 21-2001 – Upgrade Comm Facilities 12
Contractor shall consider in advance interference hazard through a preliminary assessment plan. The “DUVRI -Documento Unico per la Valutazione
Rischi da Interferenze” shall be coordinated with 31°FW/CCPP Base employees safety representative (Phone 0434 30 5709), in accordance with Legislative
Decree 81/08.
Contractor shall develop the site-specific plan for operational safety (POS
- Piano Operativo di Sicurezza) in accordance with Legislative Decree 81/08, prior to starting planned work activities. Employee’s training certificates shall be attached to the POS.
Contractor's representatives shall receive a safety briefing during the pre-performance conference from Base 31FW/SEG Occupational Safety Office.
Electronic copy of POS will be provided to 31°FS/SEG (Phone 0434 30 8526).
In this contract the contractor to gain access inside the Substations will be escorted by the personnel of electric shop.
The Contractor shall provide barricades, traffic control signs and construction safety signs that meet installation standards and comply with all applicable laws. Actual location, size and final arrangement of these items shall be discussed and approved by the BCE prior to installation. Such approved items shall be of uniform size, design and color. All cones, barricades, warning lights, temporary signs and protective devices shall conform to the current host nation requirements and the U.S. Army Corps of
Engineers Safety and Health Requirements Manual EM 385-1-1.
Weapons safety: Facility 11341 is included in the “Quantity Distance Explosion
Arc”, the contractor shall provide the “Signed contractor risk acknowledgement” as directed by the contraction officer.
AC1-08 HAZMAT/HAZWASTE HOUSEKEEPING: Prior to bringing any hazardous material into the base, the Contractor must contact BCE to coordinate the storage and handling of all hazardous materials. Contractor is responsible for complying with all applicable environmental regulations and laws pertaining to the storage, handling, and transportation of hazardous materials and hazardous waste.
a. Hazardous materials: The Contractor shall identify all hazardous materials required for completion of the project.
b. Safety Data Sheets: The Contractor shall furnish English language versions of the Safety Data Sheets (SDS) of hazardous materials, chemical, toxic, and noxious, that will be used in the construction work, to 31st CES/CEIE for approval and coordination through SEG and
SGPB. The Contracting Officer will provide sample of the MSDS form to the Contractor.
c. Hazardous Waste Management Plan: The Contractor shall provide a hazardous waste management plan.
d. Chemicals Materials: The Contractor shall ensure that hazardous materials utilized during construction do not contain any chemicals listed as EPA 17 toxins. A list of the EPA 17 toxins con be obtained from the 31st CES/CEIE office.
e. Liquid, flammable or toxic substances: Any liquid, flammable, or any other toxic substances that are required for the execution of the works, shall be kept in properly labeled, special containers.
Relative data (quantity, characteristics and location) shall be transmitted to 31st CES/CEF or 31st CES/CEIE through the Director of
Works.
ASHE 21-2001 – Upgrade Comm Facilities 13
f. Asbestos Containing Materials: There is no evidence of Asbestos containing materials.
Contractor shall notify immediately the Contracting Officer if during demolition/excavation works asbestos containing materials will be encountered to coordinate its removal and disposal in the appropriate manner in compliance with all applicable Italian norms.
AC1-09 PRESERVATION OF EXISTING CONDITIONS: The Contractor shall preserve and protect all structures, equipment, and, where applicable, vegetation
(such as trees, shrubs, grass) on or adjacent to the work site, which are not to be removed and which do not unreasonably interfere with the work required under this contract. The Contractor shall only remove trees when specifically authorized by BCE to do so and shall avoid damaging vegetation that will remain in place. If any limbs or branches of trees are broken during contract performance, or by the careless operation of equipment, or by workmen, the Contractor shall trim those limbs or branches with a clean cut and paint the cut with a tree-pruning compound. The Contractor shall return all areas disturbed during construction to their original condition before final acceptance by the base.
AC1-10 WORK SITE CONDITIONS: The work areas shall be made available to the Contractor as follows:
a. Building interior area: Contractor is responsible for the moving and eventual demounting of all the furniture out of the rooms involved in works. All the computers, documents and personal items will be previously removed by the government. A dedicated space inside the building will be available for the temporary furniture stacking as directed by the contracting officer.
b. Building Location: building 1442, 11341 AND 1304 (F04) are located in area F. Building 1442 and 1304 and do not require special access procedures, any way the Contractor shall strictly comply with the
Contracting Officer’s instructions.
Building 11341 is located near the Alternate Command Post and requires special access procedures, the Contractor shall strictly comply with the Contracting Officer’s instructions
The government will not be held liable for unproductive time and other related costs due to delays for unannounced suspension of work due to military operations and/or exercises or safety reasons. The government will only negotiate an equitable extension of the performance period based on documented delays and unannounced suspensions of work.
c. Administrative Containers: Containers required on site for administrative reasons (office space, conference space, break room) must be in like new condition and painted a color which coordinates with the base architectural plan and is approved by BCE, unless it is hidden by the opaque fencing material. Administrative containers in need of painting and / or repairs or that are in an unsightly condition will not be allowed at the project site. A nameplate, no greater than 0.5 meters X 0.5 meters in size, shall be displayed on the exterior of all trailers which lists the name of the
Contractor’s company, 24-hour Contractor’s point(s) of contact
(POC) and telephone number where they can be reached.
d. Material Storage: Storage containers will be in like new condition and painted a color which coordinates with the base architectural plan and is approved by BCE, if it is not hidden by the opaque
ASHE 21-2001 – Upgrade Comm Facilities 14 fencing material. Contractor shall display a nameplate on the exterior of all storage units with the name of the Contractor’s company, the Contractor’s point(s) of contact (POC) and telephone number where they can be reached. Storage of materials at the work site is at the Contractor’s risk. The use of private security guards on a job site shall be coordinated with base Security Forces and approved by the installation commander. The Contractor shall not use any area(s) for material or equipment storage that has not been approved by BCE.
e. Loading and Unloading of Construction Materials and Equipment:
Unloading of materials will be allowed within the fenced work area.
Contractor's personnel, vehicles and equipment must not obstruct access roads to other buildings.
Temporary parking of vehicles, for loading or unloading materials and equipment is permitted in the proximity of the work area; unless such operations will obstruct traffic flow.
f. Housekeeping and Site Cleanup: At the end of each working day, the
Contractor shall be responsible for cleaning the area inside and surrounding the building involved in the work.
Since the adjacent buildings are used every day, the Contractor shall provide that the surrounding areas are kept constantly clean and accessible, completely safe, and that the facilities are not in any way aesthetically damaged, even temporarily.
Such functions include disposal of accumulated waste materials and rubbish and other operations necessary to present a neat appearance at all times. All rubbish and waste materials shall be placed in
Contractor furnished containers. Contractors shall ensure all lightweight debris at the construction site is properly secured in waste receptacles so that it does not blow to another area or onto the airfield.
AC1-11 AIRFIELD SAFETY TRAINING: Not Applicable
AC1-12 PARKING: Contractor or Contractor’s employees, including subcontractors, shall obey all traffic laws on installation.
The Contractor shall park all vehicles, including heavy equipment vehicles, only in unobtrusive locations within the fence line of the construction site or laydown areas. Every effort must be made to avoid parking vehicles or heavy equipment where it can be easily observed by the public.
The Contractor shall not park outside the construction zone unless approved through BCE.
The Contractor shall clearly identify their vehicles through the use of company logos or signs on their vehicles.
AC1-13 ACCESS ROUTES: The Contractor shall provide a haul route plan for approval by BCE.
For road detour/closures the Contractor shall submit a written request to the Contracting Officer or his authorized representative for approval four weeks prior to his scheduled starting of work.
AC1-14 TRUCKING AND ROADS: Trucks loaded with loose material that can create a dust, debris or falling hazard shall be secured and covered. Fasten suitable cover, such as tarpaulin, over the load before entering surrounding streets. The Contractor is solely responsible for spillage from their vehicles and such spillage shall be cleaned up immediately. All roads shall be maintained free of debris at all times. The Contractor is responsible for ensuring all haul routes and site access areas are maintained in a clean and
ASHE 21-2001 – Upgrade Comm Facilities orderly fashion, free from mud, debris and clutter at all times. Special consideration must be given to haul routes that cross active taxiways. No amount of debris at these locations shall be tolerated. The Contractor shall sweep these areas continuously as long as material deliveries are being made.
AC1-15 NOISE CONTROL: The Contractor shall comply with all applicable country, local, and installation laws, ordinances, and regulations relative to noise control, to include applicable base quiet hours.
AC1-16 EXCAVATIONS: Every trench/excavation shall be returned to its original condition within ten days of the original excavation; this may be extended to 30 days if approved by the BCE. Contractor shall phase trenching and excavation operations in order to comply. At minimum, Contractor shall
All soil stockpiles shall be
Prior approval by BCE is restore the site to pre-excavation conditions.
hidden from view to the maximum extent possible.
required if soil stockpiles are to remain exposed for long periods of time.
Dust control measures are the responsibility of the Contractor and shall be implemented as directed by BCE. All road cuts must be approved by BCE prior to execution.
AC1-17 LAWN MAINTENANCE: Grassy areas disturbed by any type of construction work including storage, equipment staging, and material delivery areas shall be sodded, or hydro-seeded, where required by BCE. Sodding, or seeding, damaged areas should be accomplished at the earliest planting season possible. Contractor shall be responsible for the successful growth and maintenance of all sodded, or seeded, areas under this contract for a period of thirty (30) days or three mowing after final acceptance of the work. All grass, shrubbery, and ornamental plants fenced by the construction site shall be maintained to base standards by the Contractor.
AC1-18 LAWN ESTABLISHMENT: Within seven (7) workdays of actual completion of work at contract site, the Contractor shall prepare all disturbed areas inside and outside of the fenced site for sodding, or hydro-seeding, as provided in contract specifications. Contractor shall restore the site to a condition and appearance equal to or better than existing before the work occurred. Such restoration work will not be considered complete, and the facility not accepted, until approved by BCE. Additionally, no seeding shall be authorized for lawn establishment, whether new, or for restoration purposes unless specifically authorized by BCE.
AC1-19 CONSTRUCTION SITE RESTORATION: All Contractor owned items such as, but not limited to, stakes, traffic/safety cones, barriers, warning tape, erosion control fences, that are erected during construction, shall be removed entirely after completion of project and within five (5) days of Government acceptance of the project site. The Contractor, at his own expense, shall return to the site to remove any items left at or near the project site after this time period. All trailers, equipment/storage units, residual construction materials shall be removed also within five (5) days of
Government acceptance of the project site.
AC1-20 PROCEDURES AND WORK PHASES: Prior to starting any work the
Contractor shall submit a Work Plan for approval by the Contracting Officer. In the Electrical demolitions and new work sections, it is extremely important to not only have the contractor's phasing plan, but for them to request any outages a minimum of six (6) weeks prior. 31CS must coordinate through the MAJCOM and DISA. During work execution Contractor shall be escorted all time by gvt personnel.
Contractor shall be allowed to work simultaneously in both B.11341 and B.1442.
Works in B.1442 may be executed simultaneously pending proper coordination with 31CS and a motivated technical reason supporting it.
Service Outage Coordination. The Contractor shall be responsible for preventing any unscheduled Contractor-caused interruptions of service. The Contractor shall coordinate planned outages, if the implementation necessitates disruption of service, (e.g., communications, electrical, or other utilities) IAW of an Authorized Service Interruption (ASI) request with the Aviano AB Network Operations Center. A minimum of six (6) weeks is required to schedule an ASI. The Contractor shall plan accordingly.
AC1-21 SALVAGEABLE MATERIALS: If applicable.
It shall be the responsibility of the Contractor to remove salvageable items with maximum care to avoid any damages; and to transport them to the storage areas as indicated by the Contracting Officer’s Technical Representative.
It shall be the responsibility of the Contractor to provide containers for material disposal and/or transportation of the salvageable items. All
ASHE 21-2001 – Upgrade Comm Facilities 16
AC1-21 SALVAGEABLE MATERIALS: If applicable.
It shall be the responsibility of the Contractor to remove salvageable items with maximum care to avoid any damages; and to transport them to the storage areas as indicated by the Contracting Officer’s Technical Representative. It shall be the responsibility of the Contractor to provide containers for material disposal and/or transportation of the salvageable items. Alldiscarded materials shall be transported to an authorized public dump site by the Regional and National Regulation according to the typology of the related material. Transportation of discarded materials shall be extended, to an authorized dump site, even if the dump site is located outside the authority limits of the Aviano
City Council Territory. Use of Base dumpsters is strictly prohibited for any type of waste.
The use of Aviano Air Base dumpsters is strictly prohibited for any type of waste.
AC1-22 CONSTRUCTION DRAWINGS: The following Construction Drawings complement this Technical Specification and are an integral part of the project documents:
GENERAL
1 of 125 T-1 PROJECT TITLE SHEET AND MAPS
2 of 125 T-2 LIST OF DRAWINGS & LEGENDS
3 of 125 T-3 LIST OF DRAWINGS & LEGENDS
BUILDING #1442 – ICC BUILDING
CIVIL
4 of 132 #1442/C-1 EXISTING CONDITION - TOPOGRAPHIC SURVEY
5 of 132 #1442/C-2 EXISTING CONDITION - DEMOLITION PLAN
6 of 132 #1442/C-3 NEW CONDITION - SITE AND UTILITIES PLAN
7 of 132 #1442/C-4 NEW CONDITION - DETAILS
ARCHITECTURAL
8 of 132 #1442/A-1 EXISTING CONDITION - FLOOR PLANS
9 of 132 #1442/A-2 EXISTING CONDITION - GROUND FLOOR PLAN, AREA A
10 of 132 #1442/A-3 EXISTING CONDITION - GROUND FLOOR PLAN, AREA B
11 of 132 #1442/A-4 EXISTING CONDITION - FIRST FLOOR PLAN
12 of 132 #1442/A-5 NEW CONDITION - GROUND FLOOR PLAN, AREA A
13 of 132 #1442/A-6 NEW CONDITION - GROUND FLOOR PLAN, AREA B
14 of 132 #1442/A-7 NEW CONDITION - ELEVATIONS
15 of 132 #1442/A-8 NEW CONDITION - NEW GENSET ROOM
16 of 132 #1442/A-9 NEW CONDITION - DETAILS
17 of 132 #1442/A-10 NEW CONDITION - DETAILS
STRUCTURAL
18 of 132 #1442/S-1 STRUCTURAL DESIGN DATA
19 of 132 #1442/S-2 NEW CONDITION - FRAMING PLANS AND DETAILS
20 of 132 #1442/S-2 NEW CONDITION – SECTIONS AND DETAILS
MECHANICAL
21 of 132 #1442/M-1 HVAC SYSTEM FUNCTIONAL DIAGRAM - ROOM #128
22 of 132 #1442/M-2 HVAC SYSTEM FUNCTIONAL DIAGRAM - ROOM #224
23 of 132 #1442/M-3 HVAC SYSTEM FUNCTIONAL DIAGRAM - ROOM #225
24 of 132 #1442/M-4 HVAC SYSTEM FUNCTIONAL DIAGRAM - ROOM #174
25 of 132 #1442/M-5 EXISTING CONDITION - DUCT PLAN ROOM #128
26 of 132 #1442/M-6 EXISTING CONDITION - DUCT PLAN ROOMS #224-225
27 of 132 #1442/M-7 EXISTING CONDITION - PIPING PLAN ROOM #128
28 of 132 #1442/M-8 EXISTING CONDITION - PIPING PLAN ROOMS #224-225
29 of 132 #1442/M-9 EXISTING CONDITION - PIPING PLAN ROOM #174
30 of 132 #1442/M-10 NEW CONDITION - PIPING PLAN ROOM #128
31 of 132 #1442/M-11 NEW CONDITION - PIPING PLAN ROOMS #224-225
32 of 132 #1442/M-12 NEW CONDITION - PIPING PLAN ROOM #174
33 of 132 #1442/M-13 HVAC SYSTEM - CHILLER DIAGRAM & EQPM SCHEDULES
34 of 132 #1442/M-14 NEW CONDITION - GENERATOR ROOM - MECH. SYSTEMS
35 of 132 #1442/M-15 NEW CONDITION - HVAC SYSTEM - DETAILS
FIRE SUPPRESSION
36 of 132 #1442/FP-1 NEW CONDITION – FIRE SUPPRESSION, LEGEND E DESIGN
DATA
ASHE 21-2001 – Upgrade Comm Facilities 17
37 of 132 #1442/FP-2 NEW CONDITION – FIRE SUPPRESSION, ROOM #128-130-174
38 of 132 #1442/FP-3 NEW CONDITION – FIRE SUPPRESSION, ROOM #224-225
39 of 132 #1442/FP-4 NEW CONDITION – FIRE SUPPRESSION DIAGRAMS
40 of 132 #1442/FP-5 NEW CONDITION – FIRE SUPPRESSION - DETAILS
ELECTRICAL
41 of 132 #1442/E-1 EXISTING CONDITION - GROUND & FIRST FLOOR PLANS
ELECTRICAL PANELS LOCATION
42 of 132 #1442/E-2 EXISTING CONDITION - RM 172, 173, 174 ENLARGED PLANS
43 of 132 #1442/E-3 EXISTING CONDITION - RM 128 ENLARGED PLANS
44 of 132 #1442/E-4 EXISTING CONDITION - RM 128 ENLARGED PLANS
45 of 132 #1442/E-5 EXISTING CONDITION - RM 224, 225 ENLARGED PLANS
46 of 132 #1442/E-6 EXISTING CONDITION - RM 224, 225 ENLARGED PLANS
47 of 132 #1442/E-7 EXISTING CONDITION - POWER SYSTEM DIAGRAM - "NORMAL"
SECTION
48 of 132 #1442/E-8 EXISTING CONDITION - POWER SYSTEM DIAGRAM -
"EMERGENCY" SECTION
49 of 132 #1442/E-9 EXISTING CONDITION - RL PANEL SCHEMATIC DIAGRAM
50 of 132 #1442/E-10 EXISTING CONDITION - BLA PANEL SCHEMATIC DIAGRAM
51 of 132 #1442/E-11 EXISTING CONDITION - BLB PANEL SCHEMATIC DIAGRAM
52 of 132 #1442/E-12 EXISTING CONDITION - NIPR PANEL SCHEMATIC DIAGRAM
53 of 132 #1442/E-13 EXISTING CONDITION - SIPR PANEL SCHEMATIC DIAGRAM
54 of 132 #1442/E-14 EXISTING CONDITION - TS PANEL SCHEMATIC DIAGRAM
55 of 132 #1442/E-15 EXISTING CONDITION - A/C UNIT PANEL SCHEMATIC DIAGRAM
56 of 132 #1442/E-16 NEW CONDITION - GROUND FLOOR PLAN - NEW CABLE TRAY
LAYOUT
57 of 132 #1442/E-17 NEW CONDITION - GROUND & FIRST FLOOR PLANS, AREA B -
NEW CABLE TRAY LAYOUT
58 of 132 #1442/E-18 NEW CONDITION - RM 172, 172A, 173, 174 ENLARGED PLANS
59 of 132 #1442/E-19 NEW CONDITION - RM 128 ENLARGED PLANS
60 of 132 #1442/E-20 NEW CONDITION - RM 224, 225 ENLARGED PLANS
61 of 132 #1442/E-21 NEW CONDITION - TVCC SYSTEM
62 of 132 #1442/E-22 NEW CONDITION - MECHANICAL EQUIPMENT FEEDING PLANS
63 of 132 #1442/E-23 NEW CONDITION - A/C UNITS FEEDERS BLOCK DIAGRAM
64 of 132 #1442/E-24 NEW COND. - POWER SYSTEM DIAGRAM - "NORMAL" SECTION
65 of 132 #1442/E-25 NEW COND. - POWER SYSTEM DIAGRAM - "EMERGENCY"
SECTION
66 of 132 #1442/E-26 NEW CONDITION - DUAL CORD TYPICAL BLOCK DIAGRAM
67 of 132 #1442/E-27 NEW CONDITION - EP1 AND MUP-B PANELS SCHEMATIC
DIAGRAMS
68 of 132 #1442/E-28 NEW CONDITION - NIPR-A1 PANEL (RENAMED) SCHEMATIC
DIAGRAM
69 of 132 #1442/E-29 NEW CONDITION - NIPR-A2 PANEL (RENAMED) SCHEMATIC
DIAGRAM
70 of 132 #1442/E-30 NEW CONDITION - NIPR-A3 PANEL (RENAMED) SCHEMATIC
DIAGRAM
71 of 132 #1442/E-31 NEW CONDITION - SIPR-A1 PANEL (RENAMED) SCHEMATIC
DIAGRAM
72 of 132 #1442/E-32 NEW CONDITION - SIPR-A2 PANEL (RENAMED) SCHEMATIC
DIAGRAM
73 of 132 #1442/E-33 NEW CONDITION - NEW NIPR-B1 PANEL SCHEMATIC DIAGRAM
74 of 132 #1442/E-34 NEW CONDITION - NEW NIPR-B2 PANEL SCHEMATIC DIAGRAM
75 of 132 #1442/E-35 NEW CONDITION - NEW NIPR-B3 PANEL SCHEMATIC DIAGRAM
76 of 132 #1442/E-36 NEW CONDITION - NEW SIPR-B1 PANEL SCHEMATIC DIAGRAM
77 of 132 #1442/E-37 NEW CONDITION - NEW SIPR-B2 PANEL SCHEMATIC DIAGRAM
78 of 132 #1442/E-38 NEW CONDITION - TS PANEL SCHEMATIC DIAGRAM
79 of 132 #1442/E-39 NEW CONDITION - A/C UNIT PANELS SCHEMATIC DIAGRAM
80 of 132 #1442/E-40 NEW CONDITION - PLANS - LIGHTINING AND GROUNDING
SYSTEMS
81 of 132 #1442/E-41 NEW CONDITION - GROUND & FIRST FLOOR PLANS -
GROUNDING SYSTEM
82 of 132 #1442/E-42 NEW CONDITION - MAIN GROUNDING SYSTEM SCHEMATIC BLOCK
DIAGRAM
ASHE 21-2001 – Upgrade Comm Facilities 18
83 of 132 #1442/E-43 NEW CONDITION - TELEMONITORING SCHEMATIC DIAGRAM
84 of 132 #1442/E-44 NEW CONDITION - FIRE ALARM SYSTEM SCHEMATIC DIAGRAM
85 of 132 #1442/E-45 NEW CONDITION - ELECTRICAL SYSTEM DETAILS