APS_Streetlight_Specifications.pdf
PDF 1 MB Posted
- Attached to
- Streetlight Maintenance Services
- Solicitation number
- RFP GGS-26-0220
- Issued by
- Maricopa County, Phoenix City, Arizona
About this file
This is a streetlight specifications document for the City of Phoenix, Arizona, detailing technical and operational requirements for streetlight maintenance services. The City of Phoenix is soliciting sealed offers for comprehensive streetlight maintenance services through its Procurement Portal, with an effective date upon final signature and recording by the City Clerk's department. The agreement commencement date is December 1, 2026, or the effective date, whichever occurs later. The initial contract term spans five years from the commencement date, with two optional one-year extensions available at the City's sole discretion. Interested offerors should direct technical support inquiries regarding the Procurement Portal to the support bubble feature or procurement-support@opengov.com, while other solicitation-related questions should be directed to the listed procurement officer. The agreement will terminate upon the earliest of: completion of the full term including any exercised extensions, or termination in accordance with the agreement's provisions.
The file does not contain detailed pricing terms, set-asides, incumbent information, or specific funding sources and amounts. These critical financial and administrative details would typically be included in the complete solicitation documents, such as the scope of work, cost schedules, or supporting exhibits that accompany this specifications document.
View the file
Other files
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
LIGHTS
ACORN POST TOP ON
CONCRETE OR FIBERGLASS POLE
B. McMinn S. Sierra 12/10/04 3KLS
BY LDR. MGR. DATE REV.
ARIZONA PUBLIC SERVICE COMPANY
T&D CONSTRUCTION STANDARDS
SH 1 OF 1
A3
8005. S _ _ _ _
IF APPLICABLE:
D = DUSK-TO-DAWN
LIGHT CODE
1 = 120 VOLT
2 = 208 VOLT
4 = 240 VOLT
7 = 277 VOLT
S = SINGLE
LIGHT
CODE APN WATTS TYPE VOLTS INITIAL
LUMENS
LAMP
HEIGHT
ED 00053005 100 HPS 120/208/240/277 9,500 12'-0"
EF 00059015 150 HPS 120/208/240/277 16,000 12'-0"
CONSTRUCTION NOTES:
1. ADJUST PHOTO EYE TO FACE NORTH.
2. A GROUND ROD IS PROVIDED WITH THE JUNCTION BOX.
WHERE A GROUND ROD CANNOT BE DRIVEN ALTERNATE
GROUND SHALL BE USED. SEE 2449 THRU 2460 FOR
APPROVED ALTERNATES.
3. SIGN, "NOTICE THIS POLE IS OWNED AND MAINTAINED BY
APS. DISCONNECT INSIDE", IS REQUIRED ON ALL DUSK-
TO-DAWN AND AREA LIGHTING APPLICATIONS.
4. A 2-INCH COUPLING AND FLEX CONDUIT IS PROVIDED TO
RUN FROM THE STUB OUT AT THE FOUNDATION TO THE J-
BOX. RIGID MAY BE USED IF PREFERRED.
5. IF LUMINAIRE GLOBE BECOMES CRACKED OR DAMAGED
REPLACEMENT GLOBES ARE AVAILABLE, APN 00079294.
REPLACEMENT GLOBES WILL ACCOMIDATE 100W AND
150W LUMINAIRES.
ENGINEERING NOTES:
A. SEE SPEC 8130 FOR IN-LINE FUSE FOR UNDERGROUND
FEEDS.
B. BASE MOUNTED POLES ARE DESIGNED FOR
UNDERGROUND FEED ONLY.
COMPLETE REVISION
CO
DE
.S
ED
.S
EF
MATERIAL LIST
ITEM QTY QTY DESCRIPTION APN
1 7 7 CONDUIT PLAST FLEX 2" 32900862
2 1 1 CONTROL PHOTO MULTI BLACK 00063965
3 1 1 COUPLING 2" PVC 32900990
4 1 - LAMP HPS 100W CLR MOG BSE 72104419
5 - 1 LAMP HPS 150W CLR MOG BSE 72104420
6 1 - LUMINAIRE 100W HPS ACORN 00053005
7 - 1 LUMINAIRE 150W HPS ACORN 00059015
8 10 10 WIRE BARE #6 SOLID CU 33007580
CO
D
E
.S
CB
.S
FE
.S
TD
ITEM QTY QTY QTY DESCRIPTION APN
1 1 1 - BRACKET POST TOP REDUCER 00079699
2 7 7 7 CONDUIT PLAST FLEX 2" 32900862
3 1 1 1 CONTROL PHOTO MULTI BLACK 00063965
4 1 1 1 COUPLING 2" PVC 32900990
5 1 1 1 LAMP HPS 100W CLR MOG COL BSE 72104419
6 1 - - LUMINAIRE 100W HPS COL BK 33806668
7 - 1 - LUMINAIRE 100W HPS FT ERIE 00097717
8 - - 1 LUMINAIRE 100WHPS TRANSIT P 00074023
9 1 1 1 SIGN POLE OWNED BY APS 00050092
10 10 10 10 WIRE BARE #6 SOLID CU 33007580
MATERIAL LIST
LIGHT INITIAL MOUNTING
CODE LUMENS HEIGHT
CB 33806668 100 120 9500 17'-2-1/2"
FE 00097717 100 HPS 120/208/240/277 9500 18'-2"
TD 00074023 100 HPS 120/208/240/277 9500 17'-8"
APN WATTS TYPE VOLTS
COLONIAL POST TOP FOR THE 23’-6”
GALVANIZED STEEL OR
BLACK PAINTED STEEL POLEB. McMinn S. Sierra 12/10/04 7KLS
BY LDR. MGR. DATE REV.
ARIZONA PUBLIC SERVICE COMPANY
T&D CONSTRUCTION STANDARDS
SH 1 OF 1
A3
LIGHT
CODE APN WATTS TYPE VOLTS INITIAL
LUMENS
MOUNTING
HEIGHT
CB 33806668 100
HPS
120 9500 20'-4"
CG 33806667 100 120 9500 20'-4"
IG 00064402 100 IND 120 8000 20'-4"
CONSTRUCTION NOTES:
1. ADJUST PHOTO EYE TO FACE NORTH
2. A GROUND ROD IS PROVIDED WITH THE JUNCTION BOX. WHERE A
GROUND ROD CANNOT BE DRIVEN ALTERNATE GROUND SHALL BE
USED. SEE 2449 THRU 2460 FOR APPROVED ALTERNATES.
3. SIGN, "NOTICE THIS POLE IS OWNED AND MAINTAINED BY APS.
DISCONNECT INSIDE", IS REQUIRED ON ALL DUSK-TO-DAWN AND
AREA LIGHTING APPLICATIONS.
ENGINEERING NOTES:
A. SEE SPEC 8130 FOR IN-LINE FUSE FOR UNDERGROUND FEEDS.
8010. S _ _ 1 _
IF APPLICABLE:
D = DUSK-TO-DAWN
LIGHT CODE
S = SINGLE
COMPLETE REVISION
CO
D
E
SC
B
SC
G
SI
G
MATERIAL LIST
ITEM QTY QTY QTY DESCRIPTION APN
1 1 1 1 CONTROL PHOTO MULTI BLACK 00063965
2 1 1 - LAMP HPS 100W CLR MOG BSE 72104419
3 1 - - LUMINAIRE 100W HPS COL BK 33806668
4 - 1 - LUMINAIRE 100W HPS COL GR 33806667
5 - - 1 LUMINAIRE 100W IND COL GR 00064402
6 1 1 1 SIGN POLE OWNED BY APS 00050092
7 14 14 14 WIRE BARE #6 SOLID CU 33007580
ONLINE ONLY - PRINTING REQUIRED
8012. S _ _ _ _
IF APPLICABLE:
D = DUSK-TO-DAWN
LIGHT CODE
1 = 120 VOLT
2 = 208 VOLT
4 = 240 VOLT
7 = 277 VOLT
S = SINGLE
LIGHT
CODE APN WATTS TYPE VOLTS INITIAL
LUMENS
SH 00051564 250
HPS
120/208/240/277 30000
SJ 00051565 400 120/208/240/277 50000
SM 00051566 250
MH
120/208/240/277 21000
SN 00051567 400 120/208/240/277 36000
POLE
CODE
POLE
LENGTH
BURY
DEPTH
ABOVE GROUND
LUMINARE
MOUNTING HEIGHT
1940.20 20’-0” 5 16’-6”
1940.30 30’-6” 5 26’-6”
1940.38 38’-0” 6.6 33’-0”
POLE CODE
ABOVE GROUND LUMINAIRE MOUNTING HEIGHTS
FLUSH PEDESTAL
1946S13 14’-6” 16’-6” 1946S15 16’-6” 18’-6” 1946S23 24’-6” 26’-6” 1946S25 26’-6” 28’-6” 1946S28 29’-6” 31’-6” 1946S32 33’-6” 35’-6”
CONSTRUCTION NOTES:
1. ADJUST PHOTO EYE TO FACE NORTH
2. A GROUND ROD IS PROVIDED WITH THE JUNCTION BOX. WHERE A GROUND
ROD CANNOT BE DRIVEN ALTERNATE GROUND SHALL BE USED. SEE 2449 THR
2460 FOR APPROVED ALTERNATES.
3. SIGN, "NOTICE THIS POLE IS OWNED AND MAINTAINED BY APS. DISCONNECT
INSIDE", IS REQUIRED ON ALL DUSK-TO-DAWN AND AREA LIGHTING
APPLICATIONS.
ENGINEERING NOTES:
A. SEE SPEC 8130 FOR IN-LINE FUSE FOR UNDERGROUND FEEDS.
B. LUMINAIRE AND BRACKET FOR THE DECORATIVE SPIDER FIXTURE MUST BE
ORDERED ON PROJECT BASIS. STOCK IS KEPT AT ZERO, UNTIL USAGE
WARRANTS WAREHOUSE INVENTORY, 6 WEEKS LEADTIME IS REQUIRED
CO
DE
.S
MATERIAL LIST
ITEM QTY DESCRIPTION APN
1 1 BRACKET POST TOP SPIDER 00051654
2 10 CONDUIT 1" PVC FLEX CORR 32900891
3 1 CONTROL PHOTO MULTI BLACK 00063965
4 1 LAMP - SEE 8164 - 8171
5 1 LUMINAIRE - SEE CHART
6 1 SIGN POLE OWNED BY APS 00050092
7 14 WIRE BARE #6 SOLID CU 33007580
LIGHTS
DECORATIVE, SPIDER POST FOR THE 38’-0” SQUARE
BROWN PAINTED STEEL POLE
B. McMinn S. Sierra 9/2006 5KLS
BY LDR. MGR. DATE REV.
ARIZONA PUBLIC SERVICE COMPANY
T&D CONSTRUCTION STANDARDS
SH 1 OF 1
A3
8027. _ S 2 _ _ _ _
IF APPLICABLE:
D = DUSK-TO-DAWN
LIGHT CODE
1 = 120 VOLT
2 = 208 VOLT
4 = 240 VOLT
7 = 277 VOLT
S = STREET LIGHT
ARM CODE
P = PEDESTRIAN LIGHT
CONSTRUCTION NOTES:
1. ADJUST PHOTO EYE TO FACE NORTH
2. A GROUND ROD IS PROVIDED WITH THE JUNCTION BOX. WHERE A
GROUND ROD CANNOT BE DRIVEN, ALTERNATE GROUND SHALL BE USED.
SEE 2449 THRU 2460 FOR APPROVED ALTERNATES.
3. SIGN, "NOTICE THIS POLE IS OWNED AND MAINTAINED BY APS.
DISCONNECT INSIDE", IS REQUIRED ON ALL DUSK-TO-DAWN AND AREA
LIGHTING APPLICATIONS.
4. DRILL ONE HOLE 9-1/2” UP FROM CAP SCREW FOR PEDESTRIAN LIGHT
WIRE ENTRANCE. CAP SCREW SHOULD BE INSTALLED AT 22’-0” FROM
THE BUTT OR 14’-4” FROM CENTER OF HANDHOLE, BY MANUFACTURER.
5. POLES THAT HAVE MORE THAN ONE LUMINAIRE REQUIRE A SEPARATE
CIRCUIT WITH FUSING FROM THE J-BOX TO EACH LUMINAIRE.
ENGINEERING NOTES:
A. THE LUMINAIRE SHOWN IS RECOMMENDED FOR THIS MOUNTING HEIGHT.
SEE 8153 FOR ADDITIONAL BROWN ARCHITECTURAL LUMINAIRES.
B. TO ACCOMODATE LESS THAN THE SPECIFIED LUMINAIRE MOUNTING
HEIGHT, A SHOP ORDER IS REQUIRED TO HAVE A PORTION FROM THE TOP
OF THE POLE CUT OFF. THE TENON ARM BRACKET SLIDES OVER AND
COVERS THE CUT PORTION OF THE POLE.
C. PEDESTRIAN ONLY APPLICATIONS SEE 8030.
CO
DE
.S
.P
MATERIAL LIST
ITEM QTY QTY DESCRIPTION APN
1 10 - CONDUIT 1" PVC FLEX CORR 32900891
2 1 1 CONTROL PHOTO MULTI BLACK 00063965
3 1 1 LAMP - SEE 8164 - 8171
4 1 1 LUMINAIRE - SEE CHART
5 1 1 MAST ARM STLT 3"SQX2' SGL 33701116
6 1 - SIGN POLE OWNED BY APS 00050092
7 10 - WIRE BARE #6 SOLID CU 33007580
LIGHT
CODE APN WATTS TYPE VOLTS INITIAL
LUMENS
MOUNTING
HEIGHT
AD 00050216 100
HPS
120/208/240/277 9500
31'-6"
AF 33806679 150 120/208/240/277 16000
AH 33806726 250 120/208/240/277 30000
AJ 33806737 400 120/208/240/277 50000
AL 00050103 175
MH
120/208/240/277 14000
AM 00050104 250 120/208/240/277 21000
AN 00050166 400 120/208/240/277 36000
AQ 33806772 55
LPS
120/240 8000
AS 33806774 90 120/240 13500
AU 33806776 135 120/240 22500
AW 33806778 180 120/240 33000
LIGHTS
ARCHITECTURAL ON
38’-0” SQUARE BROWN PAINTED STEEL POLE
WITH THE 2’-0” ARM WITH PEDESTRIANB. McMinn S. Sierra 1/2007 5KLS
BY LDR. MGR. DATE REV.
ARIZONA PUBLIC SERVICE COMPANY
T&D CONSTRUCTION STANDARDS
SH 1 OF 1
A2
8030. _ _ _ _ _ _
D = DUSK-TO-DAWN
LIGHT CODE
1 = 120 VOLT
2 = 208 VOLT
4 = 240 VOLT
7 = 277 VOLT
S0 = SINGLE 6” ARM
S2 = SINGLE 2’ ARM
S4 = SINGLE 4’ ARM
S8 = SINGLE 8’ HI-RISE ARM
D4 = DOUBLE 4’ ARM
D8 = DOUBLE 8’ HI-RISE ARM
D2 = DOUBLE 2’ ARM
Q2 = QUAD 2’ ARM
T2 = TRIPLE 2’ ARM
LIGHT
CODE
APN WATTS TYPE VOLTS INITIAL
LUMENS
AD 00050216 100
HPS
120/208/240/277 9500
AF 33806679 150 120/208/240/277 16000
AH 33806726 250 120/208/240/277 30000
AJ 33806737 400 120/208/240/277 50000
AL 00050103 175
MH
120/208/240/277 14000
AM 00050104 250 120/208/240/277 21000
AN 00050166 400 120/208/240/277 36000
AQ 33806772 55
LPS
120/240 8000
AS 33806774 90 120/240 13500
AU 33806776 135 120/240 22500
AW 33806778 180 120/240 33000
LIGHTS
ARCHITECTURAL ON
5” SQUARE BROWN PAINTED STEEL POLE
DIRECT BURYB. McMinn S. Sierra 1/2007 8KLS
BY LDR. MGR. DATE REV.
ARIZONA PUBLIC SERVICE COMPANY
T&D CONSTRUCTION STANDARDS
SH 1 OF 2
ARCHITECTURAL ON
5” SQUARE BROWN PAINTED STEEL POLE
DIRECT BURYB. McMinn S. Sierra 1/2007 8KLS
BY LDR. MGR. DATE REV.
ARIZONA PUBLIC SERVICE COMPANY
T&D CONSTRUCTION STANDARDS
SH 2 OF 2
CONSTRUCTION NOTES:
1. ADJUST PHOTO EYE TO FACE NORTH
2. A GROUND ROD IS PROVIDED WITH THE JUNCTION BOX.
WHERE A GROUND ROD CANNOT BE DRIVEN, ALTERNATE
GROUND SHALL BE USED. SEE 2449 THRU 2460 FOR
APPROVED ALTERNATES.
3. SIGN, "NOTICE THIS POLE IS OWNED AND MAINTAINED BY APS.
DISCONNECT INSIDE", IS REQUIRED ON ALL DUSK-TO-DAWN
AND AREA LIGHTING APPLICATIONS.
4. POLES THAT HAVE MORE THAN ONE LUMINAIRE REQUIRE A
SEPARATE CIRCUIT WITH FUSING FROM THE J-BOX TO EACH
LUMINAIRE.
5. USING THE 20'-0" POLE, TO MATCH THE 16'-0" PEDESTRIAN
LIGHT MOUNTING HEIGHT, REDUCE POLE BURY DEPTH TO 4'-0".
6. ON 277 VOLT STREET LIGHT CIRCUITS, INSTALL A “277 VOLT”
MICARTA TAG ON CABLE IN J-BOX. TAG PROVIDED BY SPEC
8129.
ENGINEERING NOTES:
A. THE LUMINAIRE SHOWN IS RECOMMENDED FOR THIS
MOUNTING HEIGHT. SEE 8153 FOR ADDITIONAL BROWN
ARCHITECTURAL LUMINAIRES.
B. THE TWO ARMED TENON BRACKET POSITIONS THE DOUBLE
ARM 180 DEGREES APART.
C. TO ACCOMODATE LESS THAN THE SPECIFIED LUMINAIRE
MOUNTING HEIGHT, A SHOP ORDER IS REQUIRED TO HAVE A
PORTION FROM THE TOP OF THE POLE CUT OFF. THE TENON
ARM BRACKET SLIDES OVER AND COVERS THE CUT PORTION
OF THE POLE.
D. THE LIGHT CODE PROVIDES TWO SAME WATTAGE LUMINAIRES
WHEN DOUBLE ARMS ARE SPECIFIED..
POLE
CODE
POLE
LENGTH
BURY
DEPTH
POLE
ABOVE
GROUND
LUMINAIRE
HEIGHT ABOVE GROUND
6 IN
ARM
2 FT
ARM
4 FT
ARM 8 FT ARM
1940.20 20'-0" 5'-0" * 15'-0" 15'-0" 15'-0" 15'-0" ---
1940.30 30'-6" 5'-0" 25'-0" 25'-0" 25'-0" 25'-0" 33"-0"
1940.34 34'-0" 6'-0" 28'-0" 28'-0" 28'-0" 28'-0" 39'-6"
1940.38 38'-0" 6'-6" 31'-6" 31'-6" 31'-6" 31'-6" 39'-6"
* SEE NOTE 5
CODE
ITEM 80
.S
.S
.S
.S
.D
.D
.T
.Q
MATERIAL LIST
QTY QTY QTY QTY QTY QTY QTY QTY DESCRIPTION APN
1 - - - - - 1 - - BRACKET ARCH SLIP BOLTED 00092251
2 10 10 10 10 10 10 10 10 CONDUIT 1" PVC FLEX CORR 32900891
3 1 1 1 1 2 2 3 4 CONTROL PHOTO MULTI BLACK 00063965
4 1 1 1 1 2 2 3 4 LAMP - SEE 8164 - 8171
5 1 1 1 1 2 2 3 4 LUMINAIRE - SEE CHART
6 - - - - 1 - - - MAST ARM STLT 3"SQ X2' DBL 33701117
7 - - - - - - - 1 MAST ARM STLT 3"SQ X2' QUAD 00052665
8 - 1 - - - - - - MAST ARM STLT 3"SQ X2' SGL 33701116
9 - - - - - - 1 - MAST ARM STLT 3"SQ X2' TPL 00052664
10 - - 1 - - - - - MAST ARM STLT 3"SQ X4' SGL 00061738
11 - - - 1 - - - - MAST ARM STLT 3"SQ X8' SGL 33701120
12 - - - - - 2 - - MAST ARM STLT 8' BOLT-ON 00092252
13 1 - - - - - - - MAST ARM STLT SQ X6" SGL 00088370
14 1 1 1 1 1 1 1 1 SIGN POLE OWNED BY APS 00050092
15 10 10 10 10 10 10 10 10 WIRE BARE #6 SOLID CU 33007580
ROADWAY LUMINAIRE ON
20"X6', 3'X8' OR 8'X8' MAST ARMS ON
19'-0", 30’-0”, 38'-0" OR 40'-6" STEEL POLESB. McMinn S. Sierra 1/2007 9KLS
BY LDR. MGR. DATE REV.
ARIZONA PUBLIC SERVICE COMPANY
T&D CONSTRUCTION STANDARDS
SH 1 OF 2
CODE APN WATTS TYPE VOLTS INITIAL
LUMENS
MOUNTING
HEIGHT
RD 33806640 100
HPS
120 9500
RE 33806642 100 120/208/240/277 9500
RJ 00050098 150 120/208/240/277 16000
RN 00047119 250 120/208/240/277 30000
RR 00050099 400 120/208/240/277 50000
RV 00050100 175
MH
120/208/240/277 14000 SEE
RW 00050101 250 120/208/240/277 21000 CHART
RX 00050102 400 120/208/240/277 36000
RT 00070898 100 IND 120/208/240/277 12000
AQ 33806772 55
LPS
120/240 8000
AS 33806774 90 120/240 13500
AU 33806776 135 120/240 22500
AW 33806778 180 120/240 33000
8040. _ _ _ _ _ _
IF APPLICABLE:
D = DUSK-TO-DAWN
LIGHT CODE
1 = 120 VOLT
2 = 208 VOLT
4 = 240 VOLT
7 = 277 VOLT
S2 = SINGLE 2’ ARM
SH = SINGLE 8’ HI-RISE ARM
D6 = DOUBLE 6’ ARM
D8 = DOUBLE 8’ ARM
S6 = SINGLE 6’ ARM
S8 = SINGLE 8’ ARM
DH = DOUBLE 8’ HI-RISE ARM
ROADWAY LUMINAIRE ON
20"X6', 3'X8' OR 8'X8' MAST ARMS ON
19'-0", 30’-0”, 38'-0" OR 40'-6" STEEL POLESB. McMinn S. Sierra 1/2007 9KLS
BY LDR. MGR. DATE REV.
ARIZONA PUBLIC SERVICE COMPANY
T&D CONSTRUCTION STANDARDS
SH 2 OF 2
A3
CONSTRUCTION NOTES:
1. ADJUST PHOTO EYE TO FACE NORTH.
2. A GROUND ROD IS PROVIDED WITH THE JUNCTION BOX. WHERE A GROUND
ROD CANNOT BE DRIVEN ALTERNATE GROUND SHALL BE USED. SEE 2449
THRU 2460 FOR APPROVED ALTERNATES.
3. THE 40'-6" SELF-SUPPORTING STEEL POLE AND ONE OF THE 38'-6", HAVE
TWO, MANUFACTURER INSTALLED SIMPLEX FITTINGS 180° APART FOR
DOUBLE ARMS, SEE CHART.
4. APN 33701054 IS A POLE BAND ADAPTOR WITH A SIMPLEX FITTING.
ADAPTOR IS REQUIRED FOR THE SECOND ARM IN DOUBLE ARM
APPLICATIONS ON EXISTING POLES IN THE FIELD WITHOUT TWO SIMPLEX
FITTINGS. SEE 8198 FOR AVAILABLE SIZES.
5. SIGN, "NOTICE THIS POLE IS OWNED AND MAINTAINED BY APS. DISCONNECT
INSIDE," IS REQUIRED ON ALL DUSK-TO-DAWN AND AREA LIGHTING
APPLICATIONS.
6. POLES THAT HAVE MORE THAN ONE LUMINAIRE REQUIRE A SEPARATE
CIRCUIT WITH FUSING FROM THE J-BOX TO EACH LUMINAIRE
ENGINEERING NOTES:
A. THE LIGHT CODE PROVIDES TWO SAME WATTAGE LUMINAIRES WHEN
DOUBLE ARMS ARE SPECIFIED.
B. SEE SPEC 8130 - 8140 FOR IN-LINE FUSE FOR UNDERGROUND FEEDS.
C. SEE 8100 THRU 8107 FOR OVERHEAD ATTACHMENTS.
POLE
CODE
POLE
LENGTH
BURY
DEPTH
POLE
ABOVE
GROUND
LUMINAIRE HEIGHT ABOVE
GROUND ON ARM
20" X 6' 3' X 8' 8' X 8'
1944.19 19'-0" 5'-0" 14'-0" 14'-11" 16'-3" ---
1944.30 30'-6" 5'-6" 25'-0" 25'-11" 27'-3" ---
1944.38 38'-6" 6'-6" 32'-0" 32'-11" 34'-3" 39'-3" 1944.38X 38'-6" 6'-6" 32'-0" 32'-11" 34'-3" 39'-3" 1944.40X 40'-6" 8'-6" 32'-0" 32'-11" 34'-3" 39'-3"
CO
D
E
.S
.S
.S H
.D
.D
.D H
MATERIAL LIST
ITEM QTY QTY QTY QTY QTY QTY DESCRIPTION APN
1 - - - 1 1 1 ADAPTER BAND W/SIMPLEX 3" 33701054
2 10 10 10 10 10 10 CONDUIT 1" PVC FLEX CORR 32900891
3 1 1 1 2 2 2 CONTROL PHOTO MULTI BLACK 00063965
4 1 1 1 2 2 2 LAMP - SEE 8164 - 8171
5 1 1 1 2 2 2 LUMINAIRE - SEE CHART
6 1 - - 2 - - MAST ARM ST LT 2"X20"X6' 33701112
7 - 1 - - 2 - MAST ARM ST LT 2"X3"X8' 33701124
8 - - 1 - - 2 MAST ARM ST LT 2"X8"X8' 33701123
9 1 1 1 1 1 1 SIGN POLE OWNED BY APS 00050092
10 10 10 10 10 10 10 WIRE BARE #6 SOLID CU 33007580
8048._ _ _ _ _ _ _
D = DUSK-TO-DAWN
LIGHT CODE
1 = 120 VOLT
2 = 208 VOLT
4 = 240 VOLT
7 = 277 VOLT
P = PEDESTRIAN 4” POLE
R = PEDESTRIAN 6” POLE
S = STREET LIGHT 6” POLE
ARM CODE
S2 = SINGLE 2’ ARM
D2 = DOUBLE 2’ ARM
LIGHT
CODE
POLE
DIA APN WATTS TYPE VOLTS INITIAL
LUMENS
MOUNTING
HEIGHT
TD 4" 00074024 100
HPS
120/208/240/277 9500 13'-9"
TE 6" 00074497 100 120/208/240/277 9500 13'-9"
TG 6" 00085973 150 120/208/240/277 16000 27'-9"
TH 6" 00074025 250 120/208/240/277 30000 27'-9"
LIGHTS
DECORATIVE LUMINAIRE ON
16’-0” AND 30’-0” ALUMINUM POLES WITH 2’-0” ARM
WITH PEDESTRIAN OPTIONB. McMinn S. Sierra 1/2007 5KLS
BY LDR. MGR. DATE REV.
ARIZONA PUBLIC SERVICE COMPANY
T&D CONSTRUCTION STANDARDS
SH 1 OF 2
CONSTRUCTION NOTES:
1. ADJUST PHOTO EYE TO FACE NORTH
2. A GROUND ROD IS PROVIDED WITH THE JUNCTION BOX.
WHERE A GROUND ROD CANNOT BE DRIVEN ALTERNATE
GROUND SHALL BE USED. SEE 2449 THRU 2460 FOR
APPROVED ALTERNATES.
3. SIGN, "NOTICE THIS POLE IS OWNED AND MAINTAINED BY
APS. DISCONNECT INSIDE", IS REQUIRED ON ALL DUSK-
TO-DAWN AND AREA LIGHTING APPLICATIONS.
4. POLES THAT HAVE MORE THAN ONE LUMINAIRE REQUIRE
A SEPARATE CIRCUIT WITH FUSING FROM THE J-BOX TO
EACH LUMINAIRE.
ENGINEERING NOTES:
A. THE LIGHT CODE PROVIDES TWO SAME WATTAGE
LUMINAIRES WHEN DOUBLE ARM IS SPECIFIED.
B. SEE SPEC 8130 - 8140 IS FOR IN-LINE FUSE FOR
UNDERGROUND FEEDS.
C. BASE MOUNTED POLES ARE DESIGNED FOR
UNDERGROUND FEED ONLY
CO
DE
.P S2
TD
.P S2
TD
_D
.R S2
TE
.S S2
TG
.S S2
TH
.S D2
TH
MATERIAL LIST
ITEM QTY QTY QTY QTY QTY QTY DESCRIPTION APN
1 5 5 5 5 5 5 CONDUIT PLAST FLEX 2" 32900862
2 1 1 1 1 1 2 CONTROL PHOTO MULTI BLACK 00063965
3 1 1 1 1 1 1 COUPLING 2" PVC 32900990
4 1 1 1 1 1 2 LAMP - SEE 8164 - 8171
5 1 1 - - - - LUMINAIRE 100WHPS TRANSIT P 00074024
6 - - 1 - - - LUMINAIRE 100WHPS TRANSIT R 00074497
7 - - - 1 - - LUMINAIRE 150WHPS TRANSIT S 00085973
8 - - - - 1 2 LUMINAIRE 250WHPS TRANSIT S 00074025
9 1 1 - - - - MAST ARM STLT 2'TRANSIT 4"P 00074026
10 - - - 1 1 2 MAST ARM STLT 2'TRANSIT 6"S 00074496
11 - 1 - - - - SIGN POLE OWNED BY APS 00050092
12 10 10 10 10 10 10 WIRE BARE #6 SOLID CU 33007580
LIGHTS
DECORATIVE LUMINAIRE ON
16’-0” AND 30’-0” ALUMINUM POLES WITH 2’-0” ARM
WITH PEDESTRIAN OPTIONB. McMinn S. Sierra 1/2007 5KLS
BY LDR. MGR. DATE REV.
ARIZONA PUBLIC SERVICE COMPANY
T&D CONSTRUCTION STANDARDS
SH 2 OF 2
1. ADJUST PHOTO EYE TO FACE NORTH.
2. A GROUND ROD IS PROVIDED WITH THE JUNCTION BOX. WHERE A GROUND
ROD CANNOT BE DRIVEN, ALTERNATE GROUNDING SHALL BE USED. SEE 2449
THRU 2460 FOR APPROVED ALTERNATES.
3. ALL THREE-BOLT SIMPLEX ARMS HAVE AN 8' RISE AND ARE AVAILABLE IN
12'-0", 14'-0" AND 16'-0" LENGTHS.
4. SIGN, "NOTICE THIS POLE IS OWNED AND MAINTAINED BY APS. DISCONNECT
INSIDE", IS REQUIRED ON ALL DUSK-TO-DAWN AND AREA LIGHTING
APPLICATIONS.
5. THREE-BOLT SIMPLEX POLES SHALL ONLY BE FED FROM AN UNDERGROUND
SOURCE.
ENGINEERING NOTES:
A. BASE MOUNTED POLES ARE DESIGNED FOR UNDERGROUND FEED ONLY.
1 = 120 VOLT
2 = 208 VOLT
4 = 240 VOLT
7 = 277 VOLT
S12 = SINGLE 12’ ARM
S14 = SINGLE 14’ ARM
S16 = SINGLE 16’ ARM
8050. G _ _ _ _ _ _
ARM CODE
LIGHT CODE
LIGHT
CODE APN WATTS TYPE VOLTS INITIAL
LUMENS
RD 33806640 100
HPS
120 9500
RE 33806642 100 120/208/240/277 9500
RJ 00050098 150 120/208/240/277 16000
RN 00047119 250 120/208/240/277 30000
RR 00050099 400 120/208/240/277 50000
RV 00050100 175
MH
120/208/240/277 14000
RW 00050101 250 120/208/240/277 21000
RX 00050102 400 120/208/240/277 36000
AQ 33806772 55
LPS
120/240 8000
AS 33806774 90 120/240 13500
AU 33806776 135 120/240 22500
AW 33806778 180 120/240 33000
CO
DE
.G S1
.G S1
.G S1
MATERIAL LIST
ITEM QTY QTY QTY DESCRIPTION APN
1 5 5 5 CONDUIT PLAST FLEX 2" 32900862
2 1 1 1 CONTROL PHOTO MULTI BLACK 00063965
3 1 1 1 COUPLING 2" PVC 32900990
4 1 1 1 LAMP - SEE 8164 - 8171
5 1 1 1 LUMINAIRE - SEE CHART
6 1 - - MAST ARM ST LT 2"X8'X12' 00060387
7 - 1 - MAST ARM ST LT 2"X8'X14' 00060385
8 - - 1 MAST ARM ST LT 2"X8'X16' 00060386
9 1 1 1 SIGN POLE OWNED BY APS 00050092
10 10 10 10 WIRE BARE #6 SOLID CU 33007580
LIGHTS
ROADWAY LUMINAIRE WITH
8'X12', 8'X14' OR 8'X16' MAST ARMS ON
32'-0" STEEL POLES BASE MOUNTEDB. McMinn S. Sierra 9/2006 5KLS
8050G
BY LDR. MGR. DATE REV.
ARIZONA PUBLIC SERVICE COMPANY
T&D CONSTRUCTION STANDARDS
SH 1 OF 1
G
ROADWAY LUMINAIRE WITH 20"X6',
3'X8' OR 8'X8' MAST ARMS ON 12'-0", 22'-0",
25'-0", 30'-0" OR 32'-0" BASE MOUNTED STEEL POLEB. McMinn S. Sierra 12/10/04 3KLS
8050R
BY LDR. MGR. DATE REV.
ARIZONA PUBLIC SERVICE COMPANY
T&D CONSTRUCTION STANDARDS
SH 1 OF 2
RA
IF APPLICABLE:
D = DUSK-TO-DAWN
LIGHT CODE
1 = 120 VOLT
2 = 208 VOLT
4 = 240 VOLT
7 = 277 VOLT
S6 = SINGLE 6’ ARM
S8 = SINGLE 8’ ARM
D8 = DOUBLE 8’ ARM
DH = DOUBLE HI-RISE ARM
SH = SINGLE HI-RISE ARM
D6 = DOUBLE 6’ ARM
8050. R _ _ _ _ _ _
R = ROUND
LIGHT
CODE APN WATTS TYPE VOLTS INITIAL
LUMENS
RD 33806640 100
HPS
120 9500
RE 33806642 100 120/208/240/277 9500
RJ 00050098 150 120/208/240/277 16000
RN 00047119 250 120/208/240/277 30000
RR 00050099 400 120/208/240/277 50000
RT 00070898 100 IND 120 12000
RV 00050100 175
MH
120/208/240/277 14000
RW 00050101 250 120/208/240/277 21000
RX 00050102 400 120/208/240/277 36000
AQ 33806772 55
LPS
120/240 8000
AS 33806774 90 120/240 13500
AU 33806776 135 120/240 22500
AW 33806778 180 120/240 33000
COMPLETE REVISION
ROADWAY LUMINAIRE WITH 20"X6',
3'X8' OR 8'X8' MAST ARMS ON 12'-0", 22'-0",
25'-0", 30'-0" OR 32'-0" BASE MOUNTED STEEL POLESB. McMinn S. Sierra 12/10/04 3KLS
8050R
BY LDR. MGR. DATE REV.
ARIZONA PUBLIC SERVICE COMPANY
T&D CONSTRUCTION STANDARDS
SH 2 OF 2
ABOVE GROUND MOUNTING HEIGHTS (HT) 8' X 8' HI-RISE ARM
POLE CODE POLE CODE
FLUSH
2'-0"
1 SIMPLEX 2 SIMPLEX PEDSTAL
1946R12 1946D12 20'-0" 22'-0" 1946R22 1946D22 30'-0" 32'-0" 1946R25 1946D25 33'-0" 35'-0" 1946R30 1946D30 38'-0" 40'-0" 1946R32 1946D32 40'-0" 42'-0"
ABOVE GROUND MOUNTING HEIGHTS (HT) 8' X 3' ARM
POLE CODE POLE CODE
FLUSH
2'-0"
1 SIMPLEX 2 SIMPLEX PEDSTAL
1946R12 1946D12 15'-0" 17'-0" 1946R22 1946D22 25'-0" 27'-0" 1946R25 1946D25 28'-0" 30'-0" 1946R30 1946D30 33'-0" 35'-0" 1946R32 1946D32 35'-0" 37'-0"
ABOVE GROUND MOUNTING HEIGHTS (HT) 6' X 20" ARM
POLE CODE POLE CODE
FLUSH
2'-0"
1 SIMPLEX 2 SIMPLEX PEDSTAL
1946R12 1946D12 13'-8" 15'-8" 1946R22 1946D22 23'-8" 25'-8" 1946R25 1946D25 26'-8" 28'-8" 1946R30 1946D30 31'-8" 33'-8" 1946R32 1946D32 33'-8" 35'-8"
CO
DE
RS
RS
RS
H
RD
RD
RD
H
MATERIAL LIST
ITEM QTY QTY QTY QTY QTY QTY DESCRIPTION APN
1 5 5 5 5 5 5 CONDUIT PLAST FLEX 2" 32900862
2 1 1 1 2 2 2 CONTROL PHOTO MULTI BLACK 00063965
3 1 1 1 1 1 1 COUPLING 2" PVC 32900990
4 1 1 1 2 2 2 LAMP - SEE 8164 - 8171
5 1 1 1 2 2 2 LUMINAIRE - SEE CHART
6 1 - - 2 - - MAST ARM ST LT 2"X20"X6' 33701112
7 - 1 - - 2 - MAST ARM ST LT 2"X3'X8' 33701124
8 - - 1 - - 2 MAST ARM STLT 2"X8'X8 33701123
9 1 1 1 1 1 1 SIGN POLE OWNED BY APS 00050092
10 10 10 10 10 10 10 WIRE BARE #6 SOLID CU 33007580
CONSTRUCTION NOTES:
1. ADJUST PHOTO EYE TO FACE NORTH.
2. A GROUND ROD IS PROVIDED WITH THE
JUNCTION BOX. WHERE A GROUND ROD
CANNOT BE DRIVEN ALTERNATE GROUND
SHALL BE USED. SEE 2449 THRU 2460 FOR
APPROVED ALTERNATES.
3. SIGN, "NOTICE THIS POLE IS OWNED AND
MAINTAINED BY APS. DISCONNECT INSIDE", IS
REQUIRED ON ALL DUSK-TO-DAWN AND AREA
LIGHTING APPLICATIONS.
4. POLES THAT HAVE MORE THAN ONE LUMINAIRE
REQUIRE A SEPARATE CIRCUIT WITH FUSING
FROM THE J-BOX TO EACH LUMINAIRE.
ENGINEERING NOTES:
A. THE LIGHT CODE PROVIDES TWO SAME
WATTAGE LUMINAIRES WHEN DOUBLE ARM ARE
SPECIFIED.
B. SEE SPEC 8130-8031 FOR IN-LINE FUSE FOR
UNDERGROUND FEEDS.
C. BASE MOUNTED POLES ARE DESIGNED FOR
UNDERGROUND FEED ONLY.
8050._ _ _ _ _ _ _
D = DUSK-TO-DAWN
LIGHT CODE
1 = 120 VOLT
2 = 208 VOLT
4 = 240 VOLT
7 = 277 VOLT
S2 = SINGLE 2’ ARM
S4 = SINGLE 4’ ARM
S8 = SINGLE 8’ ARM
S = SQUARE STREET LIGHT
Q2 = QUAD 2’ ARM
T2 = TRIPLE 2’ ARM
D8 = DOUBLE 8’ ARM
D2 = DOUBLE 2’ ARM
ARM CODE
P = SQUARE PEDESTRAIN
S0 = SINGLE 6”ARM
APN WATTS TYPE VOLTS INITIAL
LUMENS
MOUNTING
HEIGHTCODE
AD 00050216 100 HPS 120/208/240/277 9500
SEE
CHART
AF 33806679 150 120/208/240/277 16000
AH 33806726 250 120/208/240/277 30000
AJ 33806737 400 120/208/240/277 50000
AL 00050103 175
MH
120/208/240/277 14000
AM 00050104 250 120/208/240/277 21000
AN 00050166 400 120/208/240/277 36000
AQ 33806772 55
LPS
120/240 8000
AS 33806774 90 120/240 13500
AU 33806776 135 120/240 22500
AW 33806778 180 120/240 33000
LIGHTS
ARCHITECTURAL LUMINAIRES WITH
2’-0”, 4’-0” AND 8’-0” ARMS ON
SQUARE 5” BASE MOUNTED STEEL POLEB. McMinn S. Sierra 1/2007 6KLS
8050S
BY LDR. MGR. DATE REV.
ARIZONA PUBLIC SERVICE COMPANY
T&D CONSTRUCTION STANDARDS
SH 1 OF 2
SA
1. ADJUST PHOTO EYE TO FACE NORTH.
2. A GROUND ROD IS PROVIDED WITH THE JUNCTION BOX. WHERE
A GROUND ROD CANNOT BE DRIVEN ALTERNATE GROUND SHALL
BE USED. SEE 2449 THRU 2460 FOR APPROVED ALTERNATES.
3. SIGN, "NOTICE THIS POLE IS OWNED AND MAINTAINED BY APS.
DISCONNECT INSIDE", IS REQUIRED ON ALL DUSK-TO-DAWN AND
AREA LIGHTING APPLICATIONS.
4. POLES, THAT HAVE MORE THAN ONE LUMINAIRE, REQUIRE A
SEPARATE CIRCUIT WITH FUSING FROM THE J-BOX TO EACH
LUMINAIRE.
5. USING THE 20'-0" POLE, TO MATCH THE 16'-0" PEDESTRIAN LIGHT
MOUNTING HEIGHT, CUT THE TOP 4'-0" OF THE POLE OFF.
ENGINEERING NOTES:
A. THE LUMINAIRES SHOWN ARE RECOMMENDED FOR THIS
MOUNTING HEIGHT. SEE 8153 FOR ADDITIONAL BROWN
ARCHITECTURAL LUMINAIRES.
B. THE TWO ARMED TENON BRACKET POSITIONS THE DOUBLE ARM
180 DEGREES APART.
C. TO ACCOMMODATE LESS THAN THE SPECIFIED LUMINAIRE
MOUNTING HEIGHT, A SHOP ORDER IS REQUIRED TO HAVE A
PORTION FROM THE TOP OF THE POLE CUT OFF. THE TENON ARM
BRACKET SLIDES OVER AND COVERS THE CUT PORTION OF THE
POLE.
D. THE LIGHT CODE PROVIDES TWO SAME WATTAGE LUMINAIRES
WHEN DOUBLE ARM IS SPECIFIED.
E. IN-LINE FUSE FOR UNDERGROUND FEEDS, SEE 8130-8131.
ABOVE GROUND MOUNTING HEIGHTS (HT) 2'-0" OR 4'-0" ARM
POLE CODE FLUSH 2'-0" PEDESTAL
1946S13 13'-0" 15'-0" 1946S15 15'-0" 17'-0" 1946S23 23'-0" 25'-0" 1946S25 25'-0" 27'-0" 1946S28 28'-0" 30'-0" 1946S32 32'-0" 34'-0"
ABOVE GROUND MOUNTING HEIGHTS (HT) 8'-0" HI-RISE
POLE CODE FLUSH 2'-0" PEDESTAL
1946S13 21'-0" 23'-0" 1946S15 23'-0" 25'-0" 1946S23 31'-0" 33'-0" 1946S25 33'-0" 35'-0" 1946S28 36'-0" 38'-0" 1946S32 40'-0" 42'-0"
LIGHTS
ARCHITECTURAL LUMINAIRES WITH
2’-0”, 4’-0” AND 8’-0” ARMS ON
SQUARE 5” BASE MOUNTED STEEL POLEB. McMinn S. Sierra 1/2007 6KLS
8050S
BY LDR. MGR. DATE REV.
ARIZONA PUBLIC SERVICE COMPANY
T&D CONSTRUCTION STANDARDS
SH 2 OF 2
SA
CO
DE
.S
.S
.S
.D
.D
.T
.Q
MATERIAL LIST
ITEM QTY QTY QTY QTY QTY QTY QTY DESCRIPTION APN
1 - - - - 1 - - BRACKET ARCH SLIP BOLTED 00092251
2 5 5 5 5 5 5 5 CONDUIT PLAST FLEX 2" 32900862
3 1 1 1 2 2 3 4 CONTROL PHOTO MULTI BLACK 00063965
4 1 1 1 1 1 1 1 COUPLING 2" PVC 32900990
5 1 1 1 2 2 3 4 LAMP - SEE 8164 - 8171
6 1 1 1 2 2 3 4 LUMINAIRE - SEE CHART
7 - - - 1 - - - MAST ARM STLT 3"SQX2' DBL 33701117
8 1 - - - - - - MAST ARM STLT 3"SQX2' SGL 33701116
9 - - - - - 1 - MAST ARM STLT 3"SQX2' TPL 00052664
10 - - - - - - 1 MAST ARM STLT 3"SQX2'QUAD 00052665
11 - 1 - - - - - MAST ARM STLT 3"SQX4' SGL 00061738
12 - - 1 - - - - MAST ARM STLT 3"SQX8' SGL 33701120
13 - - - - 2 - - MAST ARM STLT 8' BOLT-ON 00092252
14 1 1 1 1 1 1 1 SIGN POLE OWNED BY APS 00050092
15 10 10 10 10 10 10 10 WIRE BARE #6 SOLID CU 33007580
8054. _ _ _ _ _ _ _
D = DUSK-TO-DAWN
LIGHT CODE
S = STEEL
W = WOOD
4 = 240 VOLT
7 = 277 VOLT
POLE TYPE CODE
1 = 120 VOLT
2 = 208 VOLT
VOLTAGE CODE
S6 = SINGLE 6’ ARM
S8 = SINGLE 8’ ARM
SH = SINGLE HI-RISE 8’ ARM
ARM CODE
S2 = SINGLE 2’ ARM
LIGHT
CODE APN WATTS TYPE VOLTS INITIAL
LUMENS
MOUNTING
HEIGHT
MIN. MAX.
RD 33806640 100
HPS
120 9500 25' 30'
RE 33806642 100 120/208/240/277 9500 25' 30'
RJ 00050098 150 120/208/240/277 16000 30' 35'
RN 00047119 250 120/208/240/277 30000 35' 40'
RR 00050099 400 120/208/240/277 50000 35' 40'
RV 00050100 175
MH
120/208/240/277 14000 30' 35'
RW 00050101 250 120/208/240/277 21000 35' 40'
RX 00050102 400 120/208/240/277 36000 35' 40'
RT 00070898 100 IND 120/208/240/277 12000 25' 30'
AQ 33806772 55
LPS
120/240 8000 25' 30'
AS 33806774 90 120/240 13500 25' 30'
AU 33806776 135 120/240 22500 30' 35'
AW 33806778 180 120/240 33000 35' 40'
LIGHTS
ROADWAY LUMINAIRE WITH
20”X6’, 3’X8’, 8’X8’ MAST ARMS
B. McMinn S. Sierra 1/2007 7KLS
BY LDR. MGR. DATE REV.
ARIZONA PUBLIC SERVICE COMPANY
T&D CONSTRUCTION STANDARDS
SH 1 OF 2
CO
DE
.S S6
.S S8
.S
SH
.W S6
.W S8
.W
SH
MATERIAL LIST
ITEM QTY QTY QTY QTY QTY QTY DESCRIPTION APN
1 1 1 1 1 1 1 ADAPTER GALV STEEL W/SIMP 33701050
2 2 2 2 - - - BOLT GALV MACH 5/8" X 12" 33001550
3 - - - 2 2 2 BOLT GALV MACH 5/8" X 14" 33001551
4 1 1 1 1 1 1 CONNECTOR ALUM COMP ST LT 33003095
5 1 1 1 1 1 1 CONTROL PHOTO MULTI BLACK 00063965
6 - - - 1 1 1 HOLDER AL 4-1/4" X 7-1/4" 00052747
7 1 1 1 1 1 1 LAMP - SEE 8164 - 8171
8 1 1 1 1 1 1 LUMINAIRE - SEE CHART
9 - - - - - - MAST ARM ST LT 2" X 2' 00061225
10 1 - - 1 - - MAST ARM ST LT 2" X 20" X 6' 33701112
11 - 1 - - 1 - MAST ARM ST LT 2" X 3' X 8' 33701124
12 - - 1 - - 1 MAST ARM, STLT 2" X 8' X 8' 33701123
13 - - - 4 4 4 NAIL GROUND WIRE CLIP 71406270
14 1 1 1 1 1 1 SIGN POLE OWNED BY APS 00050092
15 2 2 2 2 2 2 WASHER GALV CUR 3X3X1/4" 33007126
16 2 2 2 2 2 2 WASHER GALV DBL COIL 5/8" 33007154
17 3 3 3 3 3 3 WIRE #6 SOLID SD CU BARE 33007580
CONSTRUCTION NOTES:
1. ADJUST PHOTO EYE TO FACE NORTH.
2. COVER THE #14 STREET LIGHT CONDUCTOR WITH 1-INCH
MOLDING, APN 58285, IF MORE THAN 12 INCHES FROM THE
SUPPLY CONDUCTOR.
3. “X” DIMENSION IS A 30-INCH MINIMUM VERTICAL CLEARANCE
FROM THE PRIMARY CONDUCTOR.
4. SIGN, "NOTICE THIS POLE IS OWNED AND MAINTAINED BY APS.
DISCONNECT INSIDE”, IS REQUIRED ON ALL DUSK-TO-DAWN
AND AREA LIGHTING APPLICATIONS.
ENGINEERING NOTES:
A. THE WORK ORDER PREPARER SHALL SPECIFY DRILLING/
MOUNTING DIMENSIONS REQUIRED TO ACHIEVE THE PROPER
LUMINAIRE MOUNTING HEIGHT.
B. LUMINAIRE MOUNTING HEIGHTS ARE MEASURED VERTICALLY
FROM THE CENTER OF THE LIGHT SOURCE TO THE ROADWAY.
MOUNTING HEIGHTS OF THE LUMINAIRE SHALL BE KEPT AS
UNIFORM AS POSSIBLE.
C. FOR UNDERGROUND FEED, SEE 8130-8140 FOR FUSING AND
5060 FOR TRANSITION.
D. SEE 8108 THRU 8119 FOR OVERHEAD ATTACHMENTS.
LIGHTS
ROADWAY LUMINAIRE WITH
20”X6’, 3’X8’, 8’X8’ MAST ARMS
B. McMinn S. Sierra 1/2007 7KLS
BY LDR. MGR. DATE REV.
ARIZONA PUBLIC SERVICE COMPANY
T&D CONSTRUCTION STANDARDS
SH 2 OF 2
ONLINE ONLY - PRINTING REQUIRED
8185. _ _
IF APPLICABLE
S = 6” MOUNTED ON 30’ POLE
P = 4” MOUNTED ON 16’ POLE
D = DUSK - TO - DAWN
ARM CODE
CO
DE
.P
.S
MATERIAL LIST
ITEM QTY QTY DESCRIPTION APN
1 1 - MAST ARM STLT 2'TRNST 4"P 00074026
2 - 1 MAST ARM STLT 2'TRNST 6"S 00074496
LIGHTS
TRANSIT 2’ MAST ARM
4” OR 6” POLE ADAPTOR
B. McMinn S. Sierra 1/2007 3KLS
BY LDR. MGR. DATE REV.
ARIZONA PUBLIC SERVICE COMPANY
T&D CONSTRUCTION STANDARDS
SH 1 OF 1