Approved Bid Page.docx
DOCX document 16 KB Posted
- Attached to
- Supply & Installation of Fire Pump
- Solicitation number
- BPM042268
- Issued by
- Washington County, Maryland
About this file
This document is the Approved Bid Page for the Supply, Delivery, & Installation of Fire Pump & Control Panel contract opportunity for the Western Maryland Hospital Center. The contract requires the provision of a brand new 500 GPM fire pump and control panel that meets specific technical requirements outlined in the document, including a 208-volt, 20 HP electric motor and automatic transfer switch for emergency generator power supply. The installation of the pump and control panel is to be performed at the Western Maryland Hospital Center located in Hagerstown, Maryland. The contract includes a two-year warranty period covered by the vendor.
The bid price must be submitted on the provided Bid Form. No amendments or alterations to the Bid Form are permitted, and failure to adhere to the instructions may result in the bid being rejected as non-responsive. The contract does not mention any set-asides, incumbents, or funding sources, but it does state that all materials and installation must be in accordance with NFPA #13 and NFPA #20 requirements.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Attachment-N- Contract Affidavit.pdf | ||
| Approved Fire Pump Small Procurement Invitation for Bid.docx | DOCX document | |
| AttachmentH-Conflict-of-InterestAffidavit.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Attachment Western Maryland Hospital Center Supply, Delivery, & Installation of Fire Pum & Control Panel
BID FORM
The Bid shall contain all price information in the format specified on these pages. Complete the Bid Form only as provided in the Bid Pricing Instructions. Do not amend, alter or leave blank any items on the Bid Form. If option years are included, Bidders must submit Bids for each option year. Failure to adhere to any of these instructions may result in the bid being determined non-responsive and rejected by the Department.
1. General Requirement for the Fire Pum & Control Panel:
a. Brand New Fire Pump & Control Panel (No refurbish)
2. Product Specification:
Fire Pump
a. 500 GPM Flow Rating
b. 49 psi boost to existing side suction pressure
c. 8-inch inlet x 6-inch outlet
d. 20 HP electric motor as the prime mover
e. 208 Volt electrical supply
f. Motor cannot exceed 62 amperes as rated by the manufacturer at full load current.
Control Panel
a. The Control Panel must have Automatic transfer switch for emergency generator power supply.
b. Full controls as required by NFPA for fire pumps.
c. All electrical components must be sized to safely operate the new fire pump.
d. All materials and installation shall be in accordance with NFPA #13 and NFPA #20 requirements.
3. Warranty and Service:
a. First two (2) years warranty must be covered by the vendor.
4. Delivery & Installation:
a. Delivery shall be made to the Western Maryland Hospital Center located at 1500 Pennsylvania Avenue, Hagerstown Maryland 21742. The installation of the pump and the control panel shall be done within the pump house adjacent to the boiler room. should be restored to their original condition upon completion of the project.
Bid Price:____________________________________________
Submitted By:
Authorized Signature: _______________________________________ Date: ________________ Printed Name and Title: _______________________________________________________________________________ Bidder Name: _______________________________________________________________________________ Bidder Address: _______________________________________________________________________________
Location(s) from which services will be performed (City/State): Hagerstown, MD 21742
FEIN: __________________________________ eMMA # BPM042268 Bidder Contact Information: Telephone: (____) ____-- _____________ Fax: (____) ____--___________________ E-mail: _________________________________________________
This page must be filled-up and returned along with your bid.