Applegate FS4_ECSO_PCD_1-25-23.pdf
PDF 10 MB Posted
- Attached to
- ITB - Ashland Acres, Smith/Winningham, Fire District #4 New Communications Site Construction
- Solicitation number
- S-X15022-00005576
- Issued by
- Jackson County, Oregon
About this file
The document "Applegate FS4_ECSO_PCD_1-25-23.pdf" appears to be related to an Invitation to Bid (ITB) for the Ashland Acres, Smith/Winningham, Fire District #4 New Communications Site Construction project located in Josephine County, Oregon. The ITB outlines the scope of work for the construction of a new communications site, including the submission of clarifications, changes, questions, and substitution requests by February 13, 2023.
The document does not provide additional details about the pricing terms, set asides, incumbents, funding requirements, or other salient information related to the contract opportunity.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1. EMERGENCY COMMUNICATIONS OF SOUTHERN OREGON (ECSO
911) PROPOSES COMMUNICATION MODIFICATIONS TO THE
EXISTING PUBLIC SAFETY FACILITY (FIRE STATION #4).
2. PROPOSED NEW 100' TOWER WITH THE FOLLOWING EQUIPMENT:
* ANTENNAS W/ ASSOCIATED ANCILLARY EQUIPMENT
3. PROPOSED INSTALLATION OF THE FOLLOWING EQUIPMENT
WITHIN OR NEAR EXISTING BUILDING:
* SIX (6) EQUIPMENT RACKS
* OVERHEAD CANOPY
* 500 GAL. PROPANE TANK
* PROPANE GENERATOR
SHEET INDEX
SCALE: NTS
FROM ECSO 911 BUILDING
1. TAKE CIRRUS DR TO BIDDLE RD
1 MIN (0.4 MI)
2. HEAD EAST ON PECH RD TOWARD CIRRUS DR
0.1 MI
3. TURN RIGHT ONTO CIRRUS DR
0.3 MI
4. DRIVE TO OR-238 W IN JOSEPHINE COUNTY
42 MIN (29.2 MI)
5. TURN LEFT ONTO BIDDLE RD
0.4 MI
6. TURN RIGHT ONTO AIRPORT RD
0.3 MI
7. TURN LEFT ONTO TABLE ROCK RD
1.6 MI
8. CONTINUE ONTO N CENTRAL AVE
0.1 MI
9. KEEP RIGHT TO STAY ON N CENTRAL AVE
0.2 MI
10. TURN RIGHT ONTO OR-238 W/ROSSANLEY DR
2.2 MI
11. TURN LEFT ONTO OR-238 W
2.8 MI
12. TURN RIGHT ONTO OR-238 W/E CALIFORNIA ST
CONTINUE TO FOLLOW OR-238 W
13. DESTINATION WILL BE ON THE RIGHT
EST. TIME: 44 MINS.
EST. MILEAGE: 29.6 MI
COVER
SHEET
SHEET NUMBER:
SHEET TITLE:
PROJECT INFORMATION PROJECT INFORMATION CONTINUED DRIVING DIRECTIONS
VICINITY MAP
PROPERTY OWNER:
APPLEGATE VALLEY RFPD #9
12188 WILLIAMS HWY
GRANTS PASS, OR 97527
MAILING ADDRESS:
1095 UPPER APPLEGATE RD
JACKSONVILLE, OR 97530
CONTACT:
CHRIS WOLFORD
541-890-0403
JURISDICTION:
JOSEPHINE COUNTY
COUNTY:
JOSEPHINE
ZONING:
EF: EXCLUSIVE FARM 80 ACRE MIN
PARCEL NUMBER(S) & AREA:
TAX LOT#: 0906
ACCOUNT ID#: R334938
45,302.4 SQ FEET±
1.04 ACRES±
PROJECT LOCATION:
LAT: N 42°18'11.00" (42.3030556°)
LONG: W 123°15'35.33" (-123.2598138°)
UTILITY PROVIDERS:
TELCO PROVIDER: TBD
POWER PROVIDER: PACIFIC POWER (PACIFICORP)
GENERAL INFORMATION:
1. TRAFFIC IS UNAFFECTED
2. SIGNAGE AT SITE IS PROPOSED
3. SITE IS UNMANNED AND HANDICAP ACCESS IS NOT REQUIRED
CODE INFORMATION:
1. IBC-2018 INTERNATIONAL BUILDING CODE
2. 2019 OREGON FIRE CODE
3. NEC-2017 NATIONAL ELECTRIC CODE
4. 2019 OREGON STRUCTURAL SPECIALITY CODE
5. 2017 NFPA 58 CODE
6. OCCUPANCY GROUP: U
7. CONSTRUCTION TYPE: II-B
SITE NAME:
APPLEGATE FIRE STATION 4 NSB
T-1
PROJECT AREA:
TOTAL COMPOUND AREA - TBD SQ FEET
ACCESS DRIVE AND PARKING - 28,232 SQ FEET ±
TOTAL - 28,232 SQ FEET ±
SCALE: NTS
LOCATOR MAP
LICENSURE:
DRAWING INFORMATION:
THIS DRAWING IS COPYRIGHTED AND IS THE SOLE
PROPERTY OF THE OWNER. IT IS PRODUCED SOLELY
FOR USE BY THE OWNER AND ITS AFFILIATES.
REPRODUCTION OR USE OF THIS DRAWING AND/OR
THE INFORMATION CONTAINED IN IT IS FORBIDDEN
WITHOUT THE WRITTEN PERMISSION OF THE OWNER.
PLANS PREPARED BY:
DATE RELEASE
10-14-21 SITE SKETCH
11-02-21 PRELIM ZONING DRAWINGS
04-06-22
CLIENT COMMENT / SURVEY UPDATE
07-06-22 FINAL ZONING DRAWINGS
1-25-23 BID DRAWINGS
PROJECT INFORMATION:
ECSO 9-1-1
APPLEGATE
FIRE STATION 4 NSB
12188 WILLIAMS HWY
GRANTS PASS, OR 97527
12725 SW MILLIKAN WAY, SUITE 300
BEAVERTON, OR 97005
503-387-5331 www.cushing-engr.com
Cushing
Civil Engineers
Civil Engineers
N
O
T
F
R
C
O
N
S
T
R
U
C
T
I
O
N
LOCATION:
12188 WILLIAMS HWY, GRANTS PASS, OR 97527
PROJECT DESCRIPTION:
APPLICANT:
ECSO 911 (EMERGENCY COMMUNICATIONS OF SOUTHERN OREGON)
400 PECH ROAD
CENTRAL POINT, OR 97502
CONTACT:
JODY HATHAWAY
541-774-5062
PROJECT MANAGER:
FEDERAL ENGINEERING, INC
10560 ARROWHEAD DRIVE,
SUITE 100, FAIRFAX, VA 22030
DAVID TERMORSHUIZEN
703-359-8200
CONSTRUCTION
MANAGER:
TBD
SURVEYEOR
ORION GEOMATICS
1724 23RD AVE
FOREST GROVE, OR 97116
JOHN PUTNAM
503-359-1688
CONSTRUCTION SUBMITTAL:
T-1 COVER SHEET
V-1 EXISTING CONDITIONS (SURVEY)
G-1 GENERAL NOTES
ER-1 GRADING & EROSION CONTROL PLAN
ER-2 GRADING & EROSION CONTROL DETAILS
C-1 OVERALL SITE PLAN
C-2 PROPOSED ENLARGED SITE PLAN
C-3 ELEVATIONS
C-4 CONSTRUCTION DETAILS I
C-5 GENERATOR & PROPANE TANK DETAILS
E-1 SITE GROUNDING PLAN
E-2 GROUNDING DETAILS I
E-3 GROUNDING DETAILS II
E-4 GROUNDING DETAILS III
RF-1 RF TOWER APPURTENANCES
RF-1.1 MICROWAVE ICE-SHIELD DETAIL
RF-2 RF TOWER APPURTENANCES
TOWER DRAWINGS BY WESTERN UTILITY
ZONING CONTACT:
CUSHING CIVIL ENGINEERS
12725 SW MILLIKAN WAY,
SUITE 300
BEAVERTON, OR 97005
KENNY MCMANAWAY
503-387-5331
ENGINEER OF RECORD:
CUSHING CIVIL ENGINEERS
12725 SW MILLIKAN WAY, SUITE 300
BEAVERTON, OR 97005
KENNY MCMANAWAY
503-387-5331
NOTE TO BIDDERS: RF
SHEETS ARE FOR
INFORMATIONAL
PURPOSES ONLY, ALL
ANTENNAS, MOUNTS,
FEED LINES ARE NOT
PART OF THIS BID SCOPE
CENTER LINE
PROPERTY LINE
NUMBER
OTHERWISE
WATERPROOF
VERIFY IN FIELD
WITHOUT
WINDOW
VINYL TILE
VERTICAL
UNLESS NOTED
TOP OF MASONRY
TOP OF CONCRETE
SHEET VINYL
TYPICAL
THROUGH
SUSPENDED
STRUCTURAL
STAINLESS STEEL
SPECIFICATION
ROUGH OPENING
SQUARE
SIMILAR
REQUIRED
W/O
GA
GC
GALV
FT
FLR
FLUOR
FIN
EXT
EX
GAUGE
GENERAL CONTRACTOR
GALVANIZE(D)
FLUORESCENT
FOOT
FLOOR
FINISH
EXTERIOR
EXISTING
PRESSURE TREATED
OUTSIDE DIAMETER
PAIRPR
PROP
PROJ
PT
PROPERTY
PROJECT
OPP
OC, o/c
OPG
OD
OPPOSITE
OPENING
ON CENTER
AT
WP
C P L L
AND
ANGLE
GROUNDGRND
AIR CONDITIONINGA/C
REQ'D
CONTINUOUSCONT
DWG
EL, ELEV
E.W.
EQUIP
EQ
ELECT
EA
E
DIAG
DIM
DN
DTL, DETL
DIA, Ø
DBL
DRAWING
ELEVATION
EACH WAY
EQUIPMENT
EQUAL
ELECTRICAL
EACH
EAST
DIAGONAL
DETAIL
DOWN
DIMENSION
DIAMETER
DOUBLE
CONST
CONC
CLR
CLG
BLK
B/S
BMR
BLDG
AWG
ASTM
APPROX
AFF
ADJ
CONSTRUCTION
BUILDING STANDARD
BASE MOBILE RADIO
CONCRETE
CLEAR
CEILING
BLOCK
AMERICAN WIRE GAUGE
TESTING & MATERIALS
AMERICAN SOCIETY FOR
APPROXIMATELY
ABOVE FINISH FLOOR
BUILDING
ADJUSTABLE
T.O.C.
NOT IN CONTRACT
NOT APPLICABLE
MINIMUMMIN
N
NTS
NIC
NA
MISC
NORTH
NOT TO SCALE
MISCELLANEOUS
MET, MTL
MECH
MGR
MFR
LB(S)
MAX
MANAGER
MANUFACTURER
MECHANICAL
METAL
MAXIMUM
POUND(S)
VERT
WIN
W/ W
VT
VIF
WEST
WITH
U.N.O.
T.O.M.
TYP
GYPSUM WALL BOARD
HVAC
IN
INSUL
INT
INFO
I.D.
INCH
INTERIOR
INSULATION
INFORMATION
INSIDE DIA.
HORIZ
HARD'WD
HT
HR
GYP BD
GWB
HORIZONTAL
HARDWOOD
HEIGHT
HOUR
GYPSUM BOARD
SQ
TNND
THRU
SUSP
STRUCT
S.V.
SS
STL
TINNED
STEEL
SPEC
S
SHT
SIM
RM
R.O.
SOUTH
SHEET
ROOM
ANTENNA AMPLIFIERLNA
OVERHEAD POWEROHP
UNDRGRND POWERUGP
OVERHEAD TELCOOHT
UNDRGRND TELCOUGT
HEATING, VENTING AND
AIR CONDITIONING
1. DRAWINGS ARE NOT TO BE SCALED, WRITTEN DIMENSIONS TAKE PRECEDENCE, THIS SET OF
DOCUMENTS IS INTENDED TO BE USED FOR DIAGRAMMATIC PURPOSED ONLY, UNLESS
NOTED OTHERWISE. THE GENERAL CONTRACTOR'S SCOPE OF WORK SHALL INCLUDE
FURNISHING ALL MATERIALS, EQUIPMENT, LABOR AND ANY REQUIREMENTS DEEMED
NECESSARY TO COMPLETE INSTALLATION AS DESCRIBED IN THE DRAWINGS AND OWNER'S
PROJECT MANUAL.
2. THE CONTRACTOR IS RESPONSIBLE FOR ALL DIMENSIONS AND STANDARDIZED DETAILS THAT
REQUIRE MODIFICATIONS DUE TO ACTUAL FIELD CONDITIONS AND REQUIREMENTS MUST BE
SUBMITTED TO AND APPROVED BY OWNERS REPRESENTATIVE PRIOR TO START OF WORK.
3. PRIOR TO THE SUBMISSION OF BIDS, CONTRACTORS INVOLVED SHALL VISIT THE JOB SITE TO
FAMILIARIZE THEMSELVES WITH ALL CONDITIONS AFFECTING THE PROPOSED PROJECT.
CONTRACTORS SHALL VISIT THE CONSTRUCTION SITE WITH THE CONSTRUCTION/CONTRACT
DOCUMENTS TO VERIFY FIELD CONDITIONS AND CONFIRM THAT THE PROJECT WILL BE
ACCOMPLISHED AS SHOWN. PRIOR TO PROCEEDING WITH CONSTRUCTION, ANY ERRORS,
OMISSIONS, OR DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE
ARCHITECT/ENGINEER VERBALLY AND IN WRITING.
4. THE GENERAL CONTRACTOR SHALL RECEIVE WRITTEN AUTHORIZATION TO PROCEED WITH
CONSTRUCTION PRIOR TO STARTING WORK ON ANY ITEM NOT CLEARLY DEFINED BY THE
CONSTRUCTION DRAWINGS/CONTRACT DOCUMENTS.
5. THE CONTRACTOR SHALL SUPERVISE AND DIRECT THE PROJECT DESCRIBED IN THE
CONTRACT DOCUMENTS. THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR ALL
CONSTRUCTION MEANS, METHODS, TECHNIQUES, SEQUENCES, SAFETY, AND PROCEDURES
FOR COORDINATING ALL PORTIONS OF THE WORK UNDER THE CONTRACT.
6. THE CONTRACTOR SHALL INSTALL ALL EQUIPMENT AND MATERIALS ACCORDING TO
MANUFACTURER'S/VENDOR'S SPECIFICATIONS UNLESS NOTED OTHERWISE OR WHERE
LOCAL CODES OR ORDINANCES TAKE PRECEDENCE.
7. ALL WORK PERFORMED ON THE PROJECT AND MATERIALS INSTALLED SHALL BE IN STRICT
ACCORDANCE WITH ALL APPLICABLE CODES, REGULATIONS, AND ORDINANCES.
CONTRACTOR SHALL GIVE ALL NOTICES AND COMPLY WITH ALL LAWS, ORDINANCES, RULES,
REGULATIONS AND LAWFUL ORDERS OF ANY PUBLIC AUTHORITY, MUNICIPAL AND UTILITY
COMPANY SPECIFICATIONS, AND LOCAL AND STATE JURISDICTIONAL CODES BEARING ON THE
PERFORMANCE OF THE WORK.
8. THE CONTRACTOR SHALL PROVIDE, AT THE PROJECT SITE, A FULL SET OF CONSTRUCTION
DOCUMENTS UPDATED WITH THE LATEST REVISIONS INVOLVED WITH THE PROJECT. THIS
SET IS A VALID CONTRACT DOCUMENT ONLY IF THE TITLE SHEET IS STAMPED IN RED INK "FOR
CONSTRUCTION" AND EACH SUCCESSIVE SHEET BEARS THE ARCHITECT'S/ENGINEER'S
SIGNED WET STAMP.
9. THE CONTRACTOR IS RESPONSIBLE FOR ADEQUATELY BRACING AND PROTECTING ALL WORK
DURING CONSTRUCTION AGAINST DAMAGE, BREAKAGE, COLLAPSE, ETC. ACCORDING TO
APPLICABLE CODES, STANDARDS, AND GOOD CONSTRUCTION PRACTICES. THE
STRUCTURAL COMPONENTS OF ADJACENT CONSTRUCTION OR FACILITIES ARE NOT TO BE
ALTERED BY THE CONSTRUCTION PROJECT UNLESS NOTED OTHERWISE.
10. THE CONTRACTOR SHALL MEET ALL OSHA REQUIREMENTS FOR ALL INSTALLATIONS.
11. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL DAMAGES TO THE EXISTING
CONSTRUCTION AND REPAIR ALL DAMAGES TO EQUAL OR BETTER NEW CONSTRUCTION. THE
CONTRACTOR SHALL NOTIFY THE PROJECT MANAGER OF ANY DAMAGE TO THE BUILDING
SITE OR ANY ADJACENT STRUCTURES AROUND THE PROJECT. THE OWNERS
REPRESENTATIVE SHALL BE SOLE AND FINAL JUDGE AS TO THE QUALITY OF THE REPAIRED
CONSTRUCTION. ANY ADDITIONAL MODIFICATIONS WHICH MUST BE MADE SHALL BE MADE AT
THE CONTRACTOR'S EXPENSE.
12. WHERE NEW PAVING, CONCRETE SIDEWALKS OR PATHS MEET EXISTING CONSTRUCTION, THE
CONTRACTOR SHALL MATCH THE EXISTING PITCH, GRADE, AND ELEVATION SO THE ENTIRE
STRUCTURE SHALL HAVE A SMOOTH TRANSITION.
13. THE CONTRACTOR SHALL MODIFY THE EXISTING FLOORS, WALL, CEILING, OR OTHER
CONSTRUCTION AS REQUIRED TO GAIN ACCESS TO AREAS FOR ALL MECHANICAL, PLUMBING,
ELECTRICAL, OR STRUCTURAL MODIFICATIONS. WHERE THE EXISTING CONSTRUCTION
DOORS, PARTITIONS, CEILING, ETC., ARE TO BE REMOVED, MODIFIED, OR REARRANGED OR
WHERE THE EXPOSED OR HIDDEN MECHANICAL, ELECTRICAL, SYSTEMS ARE ADDED OR
MODIFIED, THE GENERAL CONTRACTOR SHALL REPAIR, PATCH AND MATCH ALL EXISTING
CONSTRUCTION AND FINISHES OF ALL FLOORS WALLS AND CEILINGS. WHERE CONCRETE
MASONRY CONSTRUCTION IS MODIFIED, THE CONTRACTOR SHALL TOOTH IN ALL NEW
CONSTRUCTION TO MATCH THE EXISTING BOND. WHERE CONCRETE CONSTRUCTION IS
MODIFIED, THE CONTRACTOR SHALL VERIFY THE EXACT DETAILS TO BE USED FOR
CONSTRUCTION. ALL WORK SHALL BE COVERED UNDER THE GENERAL CONTRACT.
14. IF CONTRACTOR OR SUBCONTRACTOR FIND IT NECESSARY TO DEVIATE FROM ORIGINAL
APPROVED PLANS, THEN IT IS THE CONTRACTOR'S AND THE SUBCONTRACTOR'S
RESPONSIBILITY TO PROVIDE THE PROJECT MANAGER WITH 4 COPIES OF THE PROPOSED
CHANGES FOR HIS APPROVAL BEFORE PROCEEDING WITH THE WORK. IN ADDITION THE
CONTRACTOR AND SUBCONTRACTORS SHALL BE RESPONSIBLE FOR PROCURING ALL
NECESSARY APPROVALS FROM THE BUILDING AUTHORITIES FOR THE PROPOSED CHANGES
BEFORE PROCEEDING WITH THE WORK. THE CONTRACTOR AND SUBCONTRACTORS SHALL
BE RESPONSIBLE FOR PROCURING ALL NECESSARY INSPECTIONS AND APPROVALS FROM
BUILDING AUTHORITIES DURING THE EXECUTION OF THE WORK.
15. CONTRACTOR TO PROVIDE A PORTABLE FIRE EXTINGUISHER WITH A RATING OF NOT LESS
THAN 2-A OR 2-A10BC WITHIN 75 FEET TRAVEL DISTANCE TO ALL PORTIONS OF PROJECT
AREA DURING CONSTRUCTION.
16. THIS IS AN ESSENTIAL FACILITY THEREFORE SHALL STRICTLY MEET ALL APPLICABLE CODE
AND JURISDICTIONAL REQUIREMENTS.
1. RUBBISH, STUMPS, DEBRIS, STICKS, STONES AND OTHER REFUSE SHALL BE REMOVED
FROM THE SITE AND DISPOSED OF LEGALLY UNLESS OTHERWISE REQUIRED TO BE LEFT AS
DEFINED BY LAND/PROPERTY OWNER.
2. THE SITE SHALL BE GRADED TO CAUSE SURFACE WATER TO FLOW AWAY FROM THE
EQUIPMENT, EQUIPMENT SHELTER, GENERATOR, FUEL TANK, TOWER AREAS, AND
ADJACENT BUILDINGS, ETC.
3. NO FILL OR EMBANKMENT MATERIAL SHALL BE PLACED ON FROZEN GROUND. FROZEN
MATERIALS, SNOW OR ICE SHALL NOT BE PLACED IN ANY FILL OR EMBANKMENT.
4. THE SUBGRADE SHALL BE COMPACTED AND BROUGHT TO A SMOOTH UNIFORM GRADE
PRIOR TO THE CRUSHED STONE APPLICATION. FABRIC USE AS REQUIRED.
5. ALL APPLICABLE LOCATES SHALL BE PERFORMED PRIOR TO TO ANY EXCAVATION OR SITE
GRADING. ALL EXISTING ACTIVE SEWER, WATER, GAS, ELECTRIC, AND OTHER UTILITIES
WHERE ENCOUNTERED IN THE WORK, SHALL BE PROTECTED AT ALL TIMES, AND WHERE
REQUIRED FOR THE PROPER EXECUTION OF THE WORK, SHALL BE RELOCATED AS
DIRECTED BY ENGINEERS. EXTREME CAUTION SHOULD BE USED BY THE CONTRACTOR
WHEN EXCAVATING OR PIER DRILLING AROUND OR NEAR UTILITIES. CONTRACTOR SHALL
PROVIDE SAFETY TRAINING FOR THE WORKING CREW.
6. ALL EXISTING INACTIVE SEWER, WATER, GAS, ELECTRIC AND OTHER UTILITIES, WHICH
INTERFERE WITH THE EXECUTION OF THE WORK, SHALL BE REMOVED AND SHALL BE
CAPPED, PLUGGED OR OTHERWISE DISCONTINUED AT POINTS WHICH WILL NOT INTERFERE
WITH THE EXECUTION OF THE WORK, SUBJECT TO THE APPROVAL OF ENGINEERING.
7. THE AREAS OF THE PROPERTY DISTURBED BY THE WORK AND NOT COVERED BY THE
BUILDING, DRIVEWAY OR CRUSHED STONE, SHALL BE GRADED TO A UNIFORM SLOPE,
FERTILIZED, SEEDED, AND COVERED WITH MULCH AS SPECIFIED IN THE SPECIFICATION
LANDSCAPE WORK..
8. BEDDING MATERIAL FOR UTILITY LINES, CULVERTS AND PIPING: CLEAN SAND, MEDIUM TP
COARSE, SUB ROUNDED NATURAL RIVER OR BANK SAND, WASHED, FREE OF SILT OR CLAY,
LOAM, FRIABLE OR SOLUBLE MATERIALS, AND ORGANIC MATTER; GRADED IN
ACCORDANCE WITH THE FOLLOWING GRAIN SIZE DISTRIBUTION:
9. BMP'S FOR TEMPORARY EROSION/SEDIMENTATION CONTROL SHALL BE IMPLEMENTED PER
LOCAL, CITY OR COUNTY GUIDELINES AND PER PLAN IF APPLICABLE.
1. ALL CONCRETE WORK SHALL BE IN ACCORDANCE WITH THE ACI 301, ACI 318 AND THE
SPECIFICATION CAST-IN-PLACE CONCRETE.
2. ALL CONCRETE SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI AT 28 DAYS
(UNO).
3. REINFORCING STEEL SHALL CONFORM TO ASTM A 615, GRADE 60, DEFORMED UNLESS NOTED
OTHERWISE. WELDED WIRE FABRIC SHALL CONFORM TO ASTM A 185 WELDED STEEL WIRE
FABRIC UNLESS NOTED OTHERWISE. SPLICES CLASS "B" AND ALL HOOKS SHALL BE
STANDARD (UNO).
4. THE FOLLOWING MINIMUM CONCRETE COVER SHALL BE PROVIDED FOR REINFORCING STEEL
UNLESS SHOWN OTHERWISE ON DRAWINGS: CONCRETE CAST AGAINST EARTH - 3 IN.
CONCRETE EXPOSED TO EARTH OR WEATHER:
#6 AND LARGER ..........................2 IN.
#5 AND SMALLER & WWF ...........1-1/2 IN.
5. A 1/2" TROWELED RADIUS SHALL BE PROVIDED AT ALL EXPOSED EDGES OF CONCRETE (UNO).
HOLES TO RECEIVE EXPANSION/WEDGE ANCHORS SHALL BE 1/8" LARGER IN DIAMETER THAN
THE ANCHOR BOLT, DOWEL OR ROD AND SHALL CONFORM TO MFR RECOMMENDATION FOR
EMBEDMENT DEPTH OR AS SHOWN ON THE DRAWINGS. AVOID CUTTING EXISTING REBAR
WHEN DRILLING HOLES IN THE ELEVATED SLAB.
6. INSTALLATION OF CONCRETE EXPANSION AND WEDGE ANCHOR, SHALL BE PER
MANUFACTURER'S WRITTEN RECOMMENDED PROCEDURES.
7. FLOAT SURFACE SHALL BE A SMOOTH FINISH. SURFACE SHALL BE FREE OF ALL OBVIOUS
DEPRESSIONS. SURFACE SHALL BE SLOPED AT 2% TO PROMOTE DRAINAGE AWAY FROM
EQUIPMENT.
17. THE CONTRACTOR SHALL PERFORM WORK DURING SITE/PROPERTY OWNER'S PREFERRED
HOURS TO AVOID DISTURBING NORMAL BUSINESS.
18. SEAL ALL PENETRATIONS THROUGH FIRE-RATED AREAS WITH U.L. LISTED OR FIRE MARSHAL
APPROVED MATERIALS AS APPLICABLE TO THIS FACILITY AND OR PROJECT SITE.
19. CONTRACTOR SHALL BE RESPONSIBLE FOR UTILITY LOCATES, SCHEDULING, COORDINATING
SPECIAL AND BUILDING DEPARTMENT INSPECTIONS.
21. ROUTING OF ALL CONDUITS, CABLES, CABLE TRAYS ETC ARE INDICATED AS PROPOSED
LOCATION ONLY. CONFIRM THE EXACT LOCATION AND ROUTING WITH THE ON SITE PROJECT
MANAGER PRIOR TO STARTING WORK.
AGL ABOVE GRADE LEVEL
GENERAL NOTES CONTINUED:
CONCRETE NOTES:
GENERAL NOTES:
SITE WORK NOTES:
60-90
0-45 0-25 0-2
0-2NO. 200 MESH
NO. 100 MESH
NO. 16 MESH
NO. 8 MESH
NO. 4 MESH
PERCENT PASSINGSIEVE SIZE
SYMBOLS LEGEND
WATER
CENTERLINE
COAX
POWER/TELCO
TELCO
EASEMENT
PROPERTY LINE
GAS
UNDERGROUND POWER
CEDAR FENCE
CHAINLINK FENCE
ABBREVIATIONS LEGEND
GENERAL
NOTES
G-1
SHEET NUMBER:
SHEET TITLE:
C-5
REVISION
KEY NOTE DETAIL
REFERENCE ELEVATION
SECTION REFERENCE
ELEVATION DATUM POINT
A C-3
GA
GC
GALV
FT
FLR
FIN
EXT
DWG
E.W.
EQ
EA
E
DIAG
DIM
DN
DBL
CLR
CLG
BLK
B/S
BMR
BLDG
AWG
LB(S)
MAX
IN
INT
INFO
I.D.
HT
HR
GWB
LNA
SYMBOLS LEGEND
DESIGN LOADS:
W W
OVERHEAD POWER
G G G G G G
10. ALL SITE DESIGN AND CONSTRUCTION MUST COMPLY WITH INDUSTRY STANDARDS AND BE
ALIGNED WITH BMP GUIDELINES AS TECHNICALLY APPLICABLE. EACH SITE MUST BE PM
APPROVED BEFORE IT SHALL BE CONSIDERED COMPLETE AND ACCEPTED.
11. IF INADVERTENT DISCOVERIES OF NATIVE AMERICAN CULTURAL MATERIALS OR HUMAN
REMAINS ARE MADE DURING CONSTRUCTION, ALL WORK SHOULD CEASE AND POTENTIALLY
AFFECTED TRIBES, AS WELL AS THE STATE HISTORIC PRESERVATION OFFICE, SHOULD BE
NOTIFIED IMMEDIATELY.
1. ALL ANTENNAS, LINES AND RELATED INSTALLATION HARDWARE TO BE PROVIDED BY THE
LAND MOBILE COMMUNICATIONS PROVIDER.
2. ALL HARDWARE (NUTS AND BOLTS) BE TIGHTENED AND TORQUED IN ACCORDANCE WITH
THE TOWER MANUFACTURER'S AND STRUCTURAL ENGINEER'S SPECIFICATIONS.
3. VERIFICATION THAT THE TOWER/POLE CAN SUPPORT THE PROPOSED ANTENNA LOADING
IS TO BE DONE BY OTHERS.
4. PROVIDE SUPPORTS FOR THE ANTENNA COAX CABLES TO THE ELEVATION OF ALL INITIAL
AND FUTURE ANTENNAS. ANTENNA COAX CABLES ARE TO BE SUPPORTED AND
RESTRAINED AT THE CENTERS SUITABLE TO THE MANUFACTURER'S REQUIREMENTS.
SITE WORK NOTES CONTINUED:
TOWER/POLE NOTES:
CALL 1-800-332-2344 48 HOURS BEFORE YOU DIG. OREGON LAW REQUIRES YOU TO FOLLOW
OAR 952-001-0010 THRU 952-001-0090. COPIES ARE AVAILABLE AT THE OREGON UTILITY
NOTIFICATION CENTER 503-232-1987
ATTENTION (OREGON SITES ONLY):
ROOF SNOW LOAD DATA - GROUND SNOW LOAD: 27 PSF
FLAT-ROOF SNOW LOAD: 25 PSF
SNOW EXPOSURE FACTOR: 1.0
SNOW LOAD IMPORTANCE FACTOR: 1.2
THERMAL FACTOR: 1.0
WIND DESIGN DATA - ULTIMATE DESIGN WIND SPEED: 105 MPH
RISK CATEGORY: IV
WIND EXPOSURE: C
INTERNAL PRESSURE COEFFICIENT: 0.18±
DESIGN WIND PRESSURES;
WIND LOAD HORIZONTAL (MWFRS):22.5 PSF
WIND LOAD (UPLIFT) (MWFRS): 25.3 PSF
EARTHQUAKE DESIGN DATA - RISK CATEGORY: IV
SEISMIC IMPORTANCE FACTOR: 1.5
MAPPED SPECTRAL RESPONSE ACCEL-
ERATION PARAMETERS;
SS 0.839
S1 0.465
SITE CLASS: D
DESIGN SPECTRAL RESPONSE ACCEL-
ERATION PARAMETERS;
SDS 0.651
SD1 N/A
SEISMIC DESIGN CATEGORY: D
BASIC SEISMIC FORCE-RESISTING
SYSTEM: BEARING WALL
DESIGN BASE SHEAR: 0.15W
SEISMIC RESPONSE COEFFICIENT: 0.15
RESPONSE MODIFICATION COEFFICIENT: 6.5
ANALYSIS PROCEDURE USED: EQUIVALENT LATERAL
FORCE PROCEDURE
GEOTECHNICAL INFORMATION - ALLOWABLE BEARING CAPACITY: PER SOILS REPORT
LICENSURE:
DRAWING INFORMATION:
THIS DRAWING IS COPYRIGHTED AND IS THE SOLE
PROPERTY OF THE OWNER. IT IS PRODUCED SOLELY
FOR USE BY THE OWNER AND ITS AFFILIATES.
REPRODUCTION OR USE OF THIS DRAWING AND/OR
THE INFORMATION CONTAINED IN IT IS FORBIDDEN
WITHOUT THE WRITTEN PERMISSION OF THE OWNER.
PLANS PREPARED BY:
DATE RELEASE
10-14-21 SITE SKETCH
11-02-21 PRELIM ZONING DRAWINGS
04-06-22
CLIENT COMMENT / SURVEY UPDATE
07-06-22 FINAL ZONING DRAWINGS
1-25-23 BID DRAWINGS
PROJECT INFORMATION:
ECSO 9-1-1
APPLEGATE
FIRE STATION 4 NSB
12188 WILLIAMS HWY
GRANTS PASS, OR 97527
12725 SW MILLIKAN WAY, SUITE 300
BEAVERTON, OR 97005
503-387-5331 www.cushing-engr.com
Cushing
Civil Engineers
Civil Engineers
N
R
C
O
N
S
T
R
U
C
T
I
O
N
P PROPOSED
OHP OHP OHP OHP OHP
LPG LPG LPG LPG
PROPANE
DOOR
WHIP ANTENNA TOP
1197.5
DOOR
CEDAR
RIM: 1155.56
RIM: 1155.48
TB
CEDAR TOP
1196.2
PINE
PINE
PINE
PINE
PINE
PINE
PINE
PINE
P
S 89° 13' 01" E
301.66'
N
W
P P
P
P P
P
L
P
G
L
P
G
L
P
G
L
P
G
L
P
G
L
P
G
L
P
G
L
P
G
L
P
G
L
P
G
L
P
G
L
P
G
P
GRADING &
EROSION
CONTROL PLAN
ER-1
SHEET NUMBER:
SHEET TITLE:
11X17 SCALE: 1" = 20' 22X34 SCALE: 1" = 10' ENLARGED SITE PLAN 1
EROSION CONTROL NOTES:
1. OWNER OR DESIGNATED PERSON SHALL BE RESPONSIBLE FOR PROPER INSTALLATION AND MAINTENANCE OF ALL EROSION AND SEDIMENT CONTROL MEASURES, IN ACCORDANCE WITH LOCAL, STATE, AND FEDERAL REGULATIONS.
2. THE IMPLEMENTATION OF THESE ESC PLANS AND CONSTRUCTION, MAINTENANCE, REPLACEMENT, AND UPGRADING OF THESE ESC FACILITIES IS THE RESPONSIBILITY OF THE CONTRACTOR UNTIL ALL CONSTRUCTION IS COMPLETED AND APPROVED BY THE LOCAL JURISDICTION, AND VEGETATION/LANDSCAPING IS ESTABLISHED. THE DEVELOPER SHALL BE RESPONSIBLE FOR MAINTENANCE AFTER THE PROJECT IS APPROVED UNTIL THE LOTS ARE SOLD.
3. THE BOUNDARIES OF THE CLEARING LIMITS SHOWN ON THIS PLAN SHALL BE CLEARLY MARKED IN THE FIELD PRIOR TO CONSTRUCTION. DURING THE CONSTRUCTION PERIOD, NO DISTURBANCE BEYOND THE CLEARING LIMITS SHALL BE PERMITTED. THE MARKINGS SHALL BE MAINTAINED BY THE APPLICANT/CONTRACTOR FOR THE DURATION OF
CONSTRUCTION.
4. THE ESC FACILITIES SHOWN ON THIS PLAN MUST BE CONSTRUCTED IN CONJUNCTION WITH ALL CLEARING AND GRADING ACTIVITIES, AND IN SUCH A MANNER AS TO INSURE THAT SEDIMENT AND SEDIMENT LADEN WATER DOES
NOT ENTER THE DRAINAGE SYSTEM, ROADWAYS, OR VIOLATE APPLICABLE WATER STANDARDS.
5. THE ESC FACILITIES SHOWN ON THIS PLAN ARE MINIMUM REQUIREMENTS FOR ANTICIPATED SITE CONDITIONS.
DURING CONSTRUCTION PERIODS, THESE ESC FACILITIES SHALL BE UPGRADED AS NEEDED FOR UNEXPECTED STORM EVENTS AND TO ENSURE THAT SEDIMENT AND SEDIMENT LADEN WATER DOES NOT LEAVE THE SITE.
6. THE ESC FACILITIES SHALL BE INSPECTED DAILY BY THE APPLICANT/CONTRACTOR AND MAINTAINED AS NECESSARY
TO ENSURE THEIR CONTINUED FUNCTIONING.
7. AT NO TIME SHALL SEDIMENT BE ALLOWED TO ACCUMULATE MORE THAN 1/3 THE BARRIER HEIGHT. ALL CATCH BASINS AND CONVEYANCE LINES SHALL BE CLEANED PRIOR TO PAVING. THE CLEANING OPERATIONS SHALL NOT
FLUSH SEDIMENT-LADEN WATER INTO THE DOWNSTREAM SYSTEM.
8. STABILIZED GRAVEL ENTRANCES SHALL BE INSTALLED AT THE BEGINNING OF CONSTRUCTION AND MAINTAINED FOR THE DURATION OF THE PROJECT. ADDITIONAL MEASURES MAY BE REQUIRED TO INSURE THAT ALL PAVED AREAS
ARE KEPT CLEAN FOR THE DURATION OF THE PROJECT.
9. STORM DRAIN INLETS, BASINS, AND AREA DRAINS SHALL BE PROTECTED UNTIL PAVEMENT SURFACES ARE
COMPLETED AND/OR VEGETATION IS RE-ESTABLISHED.
10. PAVEMENT SURFACES AND VEGETATION ARE TO BE PLACED AS RAPIDLY AS POSSIBLE.
11. SEEDING SHALL BE PERFORMED NO LATER THAN SEPTEMBER 1 FOR EACH PHASE OF CONSTRUCTION.
12. IF THERE ARE EXPOSED SOILS OR SOILS NOT FULLY ESTABLISHED FROM OCTOBER 1ST THROUGH APRIL 30TH, THE
WET WEATHER EROSION PREVENTION MEASURES WILL BE IN EFFECT. SEE THE EROSION PREVENTION AND
SEDIMENT CONTROL PLANNING AND DESIGN MANUAL (CHAPTER 4) FOR REQUIREMENTS.
13. NO EXPOSED, BARE SOILS SHALL REMAIN UNSTABILIZED FOR MORE THAN TWO DAYS DURING THE PERIOD OCTOBER 1 THROUGH APRIL 30 OR FOR MORE THAN SEVEN DAYS DURING THE PERIOD OF MAY 1 THROUGH SEPTEMBER 30.
ALL DISTURBED SOIL SURFACES SHALL BE STABILIZED BY A SUITABLE APPLICATION OF "BEST MANAGEMENT
PRACTICES".
14. WHERE FEASIBLE, NO MORE THAN 500 FEET OF TRENCH SHALL BE OPEN AT ONE TIME. EXCAVATED MATERIAL SHALL BE PLACED ON THE UPHIL SIDE OF TRENCHES PROVIDED IT DOES NOT CONFLICT WITH SAFETY
REQUIREMENTS.
15. THE DEVELOPER SHALL REMOVE ESC MEASURES WHEN VEGETATION IS FULLY ESTABLISHED.
4 GENERAL NOTES SCALE: NTS
2SCALE: NTS
3SCALE: NTS CUT/ FILL QUANTITIES
UNADJUSTED CUT/ FILL QUANTITIES
STRIPPING ORGANICS FOR COMPOUND;
CUT = 0 CU. YD.
STRIPPING FOR ACCESS ROAD AND PARKING;
CUT = 0 CU. YD.
PROPOSED COMPOUND AREA;
CUT = 0 CU. YD.
FILL = 0 CU. YD.
PROPOSED ACCESS ROAD AND PARKING;
CUT = 0 CU. YD.
FILL = 0 CU. YD.
PROPOSED TOWER FOUNDATION, (3) PIERS;
EXCAVATION = 0 CU. YD.
APPROX. TOTAL AREA OF DISTURBANCE OF PROPOSED GRADING = XXXXX SQ. FT.
REFER TO GEO-TECHNICAL ENGINEERING EVALUATION BY BLACK MOUNTAIN DATED X/X/2022
IMPERVIOUS AREAS
TOTAL PARCEL AREA = 45,302.4 SQ. FT.
PRE-DEVELOPMENT AREA; EXISTING IMPERVIOUS:
EXISTING COMPOUND = 0 SQ. FT.
EXISTING ACCESS & PARKING = 28,232 SQ. FT.
TOTAL = 28,232 SQ. FT.
POST-DEVELOPMENT AREA; NEW IMPERVIOUS:
NEW COMPOUND = 0 SQ. FT.
NEW ACCESS & PARKING = 0 SQ. FT.
TOTAL = 0 SQ. FT.
PERVIOUS = 0 SQ. FT
LICENSURE:
DRAWING INFORMATION:
THIS DRAWING IS COPYRIGHTED AND IS THE SOLE
PROPERTY OF THE OWNER. IT IS PRODUCED SOLELY
FOR USE BY THE OWNER AND ITS AFFILIATES.
REPRODUCTION OR USE OF THIS DRAWING AND/OR
THE INFORMATION CONTAINED IN IT IS FORBIDDEN
WITHOUT THE WRITTEN PERMISSION OF THE OWNER.
PLANS PREPARED BY:
DATE RELEASE
10-14-21 SITE SKETCH
11-02-21 PRELIM ZONING DRAWINGS
04-06-22
CLIENT COMMENT / SURVEY UPDATE
07-06-22 FINAL ZONING DRAWINGS
1-25-23 BID DRAWINGS
PROJECT INFORMATION:
ECSO 9-1-1
APPLEGATE
FIRE STATION 4 NSB
12188 WILLIAMS HWY
GRANTS PASS, OR 97527
12725 SW MILLIKAN WAY, SUITE 300
BEAVERTON, OR 97005
503-387-5331 www.cushing-engr.com
Cushing
Civil Engineers
Civil Engineers
N
R
C
O
N
S
T
R
U
C
T
I
O
N
EXISTING GRADE
PROPOSED GRADE
TEMPORARY SILT FENCE
CONSTRUCTION ENTRANCE
FLOW DIRECTION
GROUND ELEVATION
LEGEND
FLOW DIRECTION, TYP
45 LF OF (P) SILT FENCE
SEE DETAIL ON ER-2
(P) 100' SELF-SUPPORT
TOWER
(P) GENERATOR
(P) 500 GALLON
PROPANE TANK
1155'
1154'
(P) TYPE 3 SEDIMENT BARRIER
OR APPROVED EQUAL TO
REDUCE SEDIMENT POLLUTION
DURING CONSTRUCTION
PROTECT (EX) TREE
DURING ALL TIMES OF
CONSTRUCTION
(EX) LANDSCAPE AREA
(EX) ASPHALT AREA
(EX) CONC. AREA
(EX) CONC. AREA
(EX) BLDG.
(P) TYPE 3 SEDIMENT BARRIER
OR APPROVED EQUAL TO
REDUCE SEDIMENT POLLUTION
DURING CONSTRUCTION
AutoCAD SHX Text
AutoCAD SHX Text
SCALE: 1" = '
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
GRADING AND
EROSION CONTROL
DETAILS
SHEET NUMBER:
SHEET TITLE:
LICENSURE:
DRAWING INFORMATION:
THIS DRAWING IS COPYRIGHTED AND IS THE SOLE
PROPERTY OF THE OWNER. IT IS PRODUCED SOLELY
FOR USE BY THE OWNER AND ITS AFFILIATES.
REPRODUCTION OR USE OF THIS DRAWING AND/OR
THE INFORMATION CONTAINED IN IT IS FORBIDDEN
WITHOUT THE WRITTEN PERMISSION OF THE OWNER.
PLANS PREPARED BY:
DATE RELEASE
10-14-21 SITE SKETCH
11-02-21 PRELIM ZONING DRAWINGS
04-06-22
CLIENT COMMENT / SURVEY UPDATE
07-06-22 FINAL ZONING DRAWINGS
1-25-23 BID DRAWINGS
PROJECT INFORMATION:
ECSO 9-1-1
APPLEGATE
FIRE STATION 4 NSB
12188 WILLIAMS HWY
GRANTS PASS, OR 97527
12725 SW MILLIKAN WAY, SUITE 300
BEAVERTON, OR 97005
503-387-5331 www.cushing-engr.com
Cushing
Civil Engineers
Civil Engineers
N
R
C
O
N
S
T
R
U
C
T
I
O
N
SEDIMENT FENCE NOTES:
1. THE FILTER FABRIC FENCE SHALL BE INSTALLED TO FOLLOW THE CONTOURS WHERE FEASIBLE. THE FENCE POSTS
SHALL BE SPACED A MAXIMUM OF 6' APART AND DRIVEN SECURELY INTO THE GROUND A MINIMUM OF 24”.
2. THE FILTER FABRIC SHALL BE PURCHASED IN A CONTINUOUS ROLL CUT TO THE LENGTH OF THE BARRIER TO AVOID USE OF JOINTS. WHEN JOINTS ARE NECESSARY, FILTER CLOTH SHALL BE SPLICED TOGETHER ONLY AT A SUPPORT POST, WITH A MINIMUM 6” OVERLAP, AND BOTH ENDS SECURELY FASTENED TO THE POST, OR OVERLAP 2” X 2” POSTS
AND ATTACH AS SHOWN ON DETAIL SHEET 4-3A OF THE EROSION CONTROL MANUAL.
3. THE FILTER FABRIC SHALL HAVE A MINIMUM VERTICAL BURIAL OF 6”. ALL EXCAVATED MATERIAL FROM FILTER FABRIC
INSTALLATION SHALL BE BACKFILLED AND COMPACTED ALONG THE ENTIRE DISTURBED AREA.
4. STANDARD OR HEAVY-DUTY FILTER FABRIC FENCES SHALL HAVE MANUFACTURED STITCHED LOOPS FOR 2” X 2” POST INSTALLATION. STITCHED LOOPS SHALL BE INSTALLED ON THE UP HILLSIDE OF THE SLOPED AREA.
5. FILTER FABRIC FENCES SHALL BE REMOVED WHEN THEY HAVE SERVED THEIR USEFUL PURPOSE, BUT NOT BEFORE
THE UPSLOPE AREA HAS BEEN PERMANENTLY PROTECTED AND STABILIZED.
6. FILTER FABRIC FENCES SHALL BE INSPECTED BY APPLICANT/CONTRACTOR IMMEDIATELY AFTER EACH RAINFALL AND AT LEAST DAILY DURING PROLONGED RAINFALL. ANY REQUIRED REPAIRS SHALL BE MADE IMMEDIATELY.
SETBACKS AND DRAINAGE DIMENSIONS
TEMPORARY SEDIMENT FENCE
GRAVEL CONSTRUCTION ENTRANCEPLASTIC SHEETING 1SCALE: NTS 2SCALE: NTS
3SCALE: NTS
4SCALE: NTS
ER-2
TOE OF
SLOPE
P
L
P
L
H/5 BUT 2' MINIMUM
AND NEED NOT EXCEED
20' MAXIMUM
TOE OF
SLOPE
H/5 BUT 2' MINIMUM
AND NEED NOT
EXCEED 10' MAXIMUM
NATURAL OR
FINISH GRADE
INTERCEPTOR
DRAIN (IF
REQUIRED)
H
NATURAL OR
FINISH GRADE
CUT OR
FILL
SLOPE
NOT USED 4SCALE: NTS
© 2022 Microsoft Corporation © 2022 Maxar ©CNES (2022) Distribution Airbus DS
C
CEDAR
TB
CEDAR TOP
1196.2
PINE
PINE
PINE
PINE
PINE
PINE
PINE
PINE
PINE
PINE
PINE
PINE
PINE
PINE
PINE
PINE
PINE
PINE
PINE
PINE
PINE
PINE
G
A T
E
C
C
C
C
C
C
C
C
C
C
C
C
C
C
P
P
P
P
P
P
P
S 89° 13' 01" E
301.66'
S
W
W
G
A
E
W
PINE
PINE
N 11°02'48" W
51.27'
N 00°51'26" E
50.00'
N 89° 17' 13" W
30.76'
P
P
L
P
G
L
P
G
L
P
G
L
P
G
L
P
G
L
P
G
22X34 SCALE: 1" = 20' OVERALL SITE PLAN 1
OVERALL
SITE PLAN
C-1
SHEET NUMBER:
SHEET TITLE:
LICENSURE:
DRAWING INFORMATION:
THIS DRAWING IS COPYRIGHTED AND IS THE SOLE
PROPERTY OF THE OWNER. IT IS PRODUCED SOLELY
FOR USE BY THE OWNER AND ITS AFFILIATES.
REPRODUCTION OR USE OF THIS DRAWING AND/OR
THE INFORMATION CONTAINED IN IT IS FORBIDDEN
WITHOUT THE WRITTEN PERMISSION OF THE OWNER.
PLANS PREPARED BY:
DATE RELEASE
10-14-21 SITE SKETCH
11-02-21 PRELIM ZONING DRAWINGS
04-06-22
CLIENT COMMENT / SURVEY UPDATE
07-06-22 FINAL ZONING DRAWINGS
1-25-23 BID DRAWINGS
PROJECT INFORMATION:
ECSO 9-1-1
APPLEGATE
FIRE STATION 4 NSB
12188 WILLIAMS HWY
GRANTS PASS, OR 97527
12725 SW MILLIKAN WAY, SUITE 300
BEAVERTON, OR 97005
503-387-5331 www.cushing-engr.com
Cushing
Civil Engineers
Civil Engineers
N
R
C
O
N
S
T
R
U
C
T
I
O
N
NOTE:
THIS IS NOT A SURVEY ALL
EXISTING INFORMATION IS
PROVIDED BY GIS.
11X17 SCALE: 1" = 40'
ZONING
EF: (EXCLUSIVE FARM 80 ACRE MIN)
ACCOUNT: R334938
W
ILL
IA
MS
H W
Y (2
PROPOSED PROJECT AREA
SEE SHEET C-2 FOR DETAILS
(EX) SUBJECT
PROPERTY LINE
ZONING
EF: (EXCLUSIVE FARM 80 ACRE MIN)
ACCOUNT: R323833
ZONING
EF: (EXCLUSIVE FARM 80 ACRE MIN)
ACCOUNT: R323834
ACCOUNT: R323840
ZONING
RI: (RURAL INDUSTRIAL)
ACCOUNT: R326213
ZONING
RI: (RURAL INDUSTRIAL)
ZONING
RI: (RURAL INDUSTRIAL)
ACCOUNT: R326219
W
AT
E
GA
P
RD
WILLIAMS HWY (238)
(EX) WATER TANK
(EX) FENCE
(EX) BUILDING
(EX) TREE, TYP
(EX) SLIDING
SECURITY GATE
E
X
D
R
A
I
E
L
D
(EX) UTILITY
POLE
(EX) FENCE, TYP
(EX) GATE, TYP
(EX) UTILITY
EASEMENT PER
SURVEY
(EX) ACCESS
EASEMENT
AutoCAD SHX Text
AutoCAD SHX Text
SCALE: 1" = '
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
B
70.2'
70.2'
G A
E
C
C
C
C
C
C
C
C
C
C
C
P
P
P
P
P
P
S
E
S
W
W
N 82° 2 3' 50" W
170.95'
N 11°02'48" W
N 00°51'26" E
50.00'
P P
P
P P P
LPGLPGLPGLPGLPGLPGLPGLPG
L
P
G
L
P
G
L
P
G
L
P
G
P
11X17 SCALE: 1" = 20' 22X34 SCALE: 1" = 10' ENLARGED SITE PLAN 1
ENLARGED
SITE PLAN
C-2
SHEET NUMBER:
SHEET TITLE:
LICENSURE:
DRAWING INFORMATION:
THIS DRAWING IS COPYRIGHTED AND IS THE SOLE
PROPERTY OF THE OWNER. IT IS PRODUCED SOLELY
FOR USE BY THE OWNER AND ITS AFFILIATES.
REPRODUCTION OR USE OF THIS DRAWING AND/OR
THE INFORMATION CONTAINED IN IT IS FORBIDDEN
WITHOUT THE WRITTEN PERMISSION OF THE OWNER.
PLANS PREPARED BY:
DATE RELEASE
10-14-21 SITE SKETCH
11-02-21 PRELIM ZONING DRAWINGS
04-06-22
CLIENT COMMENT / SURVEY UPDATE
07-06-22 FINAL ZONING DRAWINGS
1-25-23 BID DRAWINGS
PROJECT INFORMATION:
ECSO 9-1-1
APPLEGATE
FIRE STATION 4 NSB
12188 WILLIAMS HWY
GRANTS PASS, OR 97527
12725 SW MILLIKAN WAY, SUITE 300
BEAVERTON, OR 97005
503-387-5331 www.cushing-engr.com
Cushing
Civil Engineers
Civil Engineers
N
R
C
O
N
S
T
R
U
C
T
I
O
N
NOTES:
1. TOWER INFO SHOWN FOR CONCEPTUAL USE ONLY.
SEE TOWER STRUCTURAL DESIGN BY WESTERN
UTILITY DATED 11-7-22.
(P) 100' SELF-SUPPORT
TOWER;
SEE DRAWINGS BY
TOWER WESTERN UTILITY
(EX) FUEL TANK
(EX) WATER TANK
(EX) FENCE (EX) PAVEMENT
(EX) BUILDING
(EX) METER
4'
(EX) SLIDING
SECURITY
GATE ; INSTALL
SIGANGE PER
SHEET C-5
(EX) CONCRETE
(EX) CONCRETE
12'
10'
E
X
D
R
A
E
L
D
(EX) UNDERGROUND
SEPTIC TANK
APPROX. LOCATION
OF (EX) SUBJECT
PROPERTY LINE
(P) OVERHEAD CABLE TRAY
C-3
C-3
(EX) TREE,
TYP
(EX) FENCE
(EX) EDGE OF
PAVEMENT
(EX) LIGHT
E
X
A
C C
E S
S
E
A S
E M
E N
T
1155'
1154'
1156'
(P) ICE-BRIDGE (9'±)
SEE C-4 FOR DETAIL
(P) ANTENNAS ATTACHED TO
(P) TOWER (NOT SHOWN FOR
CLARITY); SEE SHEET C-3
(P) EQUIPMENT RACKS TO BE INSTALLED WITHIN (EX)
BUILDING ; INSTALL SIX (3) 7.5’ TALL RACKS INCLUDING –
ONE (1) P-25 ESS RACK, ONE (1) VHF CAVITY FILTER RACK,
ONE (1) MICROWAVE / MPLS RACK
(P) 200A METER W/
DISCONNECT
(P) 500 GAL. PROPANE TANK;
SEE C-5 FOR DETAILS
(P) GENERATOR ON 9'-6"X4'
CONCRETE PAD
SEE SHEET C-5
(P) GAS AND TELCO LINE TO
NEW PROPANE TANK (75'±) AND
REPLACE PAVEMENT SAWCUTS;
SEE SHEET C-5
(P) BOLLARD, TYP OF (4)
(EX) CONTOUR PER SURVEY;
SEE SHEETS V-1
(P) BOLLARD, TYP OF (8)
SEE SHEET C4
(EX) ACCESS
DOOR, TYP
SAWCUT (E) CONCRETE 14'X14'
AND CONCRETE TO BE REPLACED
WITH CRUSHED GRAVEL
9'-11"
(P) PATCH EXISTING ASPHALT
PAVEMENT WITH 6" AC (IN TWO
LIFTS) ON 3" CRUSHED GRAVEL
3/4-0
NOTE TO BIDDERS: INTERIOR
EQUIPMENT INSTALLATION IS
NOT PART OF THE SCOPE FOR
BIDDERS
AutoCAD SHX Text
AutoCAD SHX Text
SCALE: 1" = '
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
DIESEL
NOTES:
· CONCEPTUAL USE ONLY
· EXISTING TREES NOT SHOWN
FOR CLARITY
· PROPOSED ANTS. TO BE LIGHT
GRAY OR LIGHT BLUE IN COLOR
LICENSURE:
DRAWING INFORMATION:
THIS DRAWING IS COPYRIGHTED AND IS THE SOLE
PROPERTY OF THE OWNER. IT IS PRODUCED SOLELY
FOR USE BY THE OWNER AND ITS AFFILIATES.
REPRODUCTION OR USE OF THIS DRAWING AND/OR
THE INFORMATION CONTAINED IN IT IS FORBIDDEN
WITHOUT THE WRITTEN PERMISSION OF THE OWNER.
PLANS PREPARED BY:
DATE RELEASE
10-14-21 SITE SKETCH
11-02-21 PRELIM ZONING DRAWINGS
04-06-22
CLIENT COMMENT / SURVEY UPDATE
07-06-22 FINAL ZONING DRAWINGS
1-25-23 BID DRAWINGS
PROJECT INFORMATION:
ECSO 9-1-1
APPLEGATE
FIRE STATION 4 NSB
12188 WILLIAMS HWY
GRANTS PASS, OR 97527
12725 SW MILLIKAN WAY, SUITE 300
BEAVERTON, OR 97005
503-387-5331 www.cushing-engr.com
Cushing
Civil Engineers
Civil Engineers
N
R
C
O
N
S
T
R
U
C
T
I
O
N
11X17 SCALE: 1" = 5' 22X34 SCALE: 1" = 2.5'PROPOSED SOUTH ELEVATION 1 11X17 SCALE: 1" = 20'PROPOSED WEST ELEVATION 222X34 SCALE: 1" = 10'
ELEVATIONS
C-3
SHEET NUMBER:
SHEET TITLE:
GROUND LEVEL (GL)
(P) ANTENNA TOP (TBD)
(P) EQUIPMENT RACK TO BE
INSTALLED WITHIN (EX) BUILDING
MEZZANINE, TYP OF (6)
(P) 100' SELF-SUPPORT TOWER
(EX) BUILDING
(P) GENERATOR
(BEYOND)
(EX) METER
(P) ANTENNA;
RFI EA80-41-DIN
4 BAY EXPOSED DIPOLE
(EX) ANTENNA TO BE RELOCATED
TO NEW TOWER
(P) TOWER TOP 100.0' AGL
(P) ANTENNA BASE 90.0' AGL
(P) CABLE LADDER &
COAX CABLES
(P) ANTENNA CL 70.0' AGL
(P) ANTENNA BASE 50.0' AGL
(EX) BUILDING TOP ±17.0' AGL
GROUND LEVEL (GL)
(P) ANTENNA TOP (TBD)
(P) EQUIPMENT RACK TO BE
INSTALLED WITHIN (EX) BUILDING
MEZZANINE, TYP OF (6)
(EX) BUILDING
(P) GENERATOR
(BEYOND)
(EX) METER
APPROX. OF (P)
PROPANE TANK;
LOCATION TO TBD
FOR PROPER
CLEARANCES
(EX) ANTENNA
(P) TOWER TOP 100.0' AGL
(P) ANTENNA BASE 90.0' AGL
(P) ANTENNA CL 70.0' AGL
(P) ANTENNA BASE 50.0' AGL
(EX) BUILDING TOP ±17.0' AGL
(EX) LIGHT POLE
(EX) FUEL TANK
(EX) FUEL
TANK
(P) 6'Ø MICROWAVE ANTENNA;
LINK TO TALLOWBOX
PAD 6-59BC
AZIMUTH: 142.98°
(P) 100' SELF-SUPPORT TOWER
(P) CABLE LADDER &
COAX CABLES
(P) 6'Ø MICROWAVE ANTENNA;
PAD 6-59C
AZIMUTH: 142.98°
(P) ANTENNA;
RFI BA40-41-DIN
2 BAY EXPOSED DIPOLE
(P) ANTENNA;
RFI BA40-41-DIN
2 BAY EXPOSED DIPOLE
(P) ANTENNA;
RFI EA80-41-DIN
4 BAY EXPOSED DIPOLE
(P) CABLE BRIDGE
(P) 500 GALLON
PROPANE TANK
(P) MICROWAVE ICE-SHIELD, TYP
(P) MICROWAVE ICE-SHIELD, TYP
NOTES:
1. TOWER INFO SHOWN FOR CONCEPTUAL USE ONLY. SEE
TOWER STRUCTURAL DESIGN BY OTHERS.
2. REFER TO TOWER AND FOUNDATION STRUCTURAL
ANALYSIS BY WESTERN UTILITY DATED 11-7-22.
3. REFER TO RF TOWER APPURTENANCES SHEETS
FOR MORE INFORMATION.
CONSTRUCTION
DETAILS I
SHEET NUMBER:
SHEET TITLE:
LICENSURE:
DRAWING INFORMATION:
THIS DRAWING IS COPYRIGHTED AND IS THE SOLE
PROPERTY OF THE OWNER. IT IS PRODUCED SOLELY
FOR USE BY THE OWNER AND ITS AFFILIATES.
REPRODUCTION OR USE OF THIS DRAWING AND/OR
THE INFORMATION CONTAINED IN IT IS FORBIDDEN
WITHOUT THE WRITTEN PERMISSION OF THE OWNER.
PLANS PREPARED BY:
DATE RELEASE
10-14-21 SITE SKETCH
11-02-21
PRELIM ZONING DRAWINGS
04-06-22 CLIENT COMMENT / SURVEY UPDATE
07-06-22 FINAL ZONING DRAWINGS
1-25-23
BID DRAWINGS
PROJECT INFORMATION:
ECSO 9-1-1
APPLEGATE
FIRE STATION 4 NSB
12188 WILLIAMS HWY
GRANTS PASS, OR 97527
12725 SW MILLIKAN WAY, SUITE 300
BEAVERTON, OR 97005
503-387-5331 www.cushing-engr.com
Cushing
Civil Engineers
Civil Engineers
N
R
C
O
N
S
T
R
U
C
T
I
O
N
SIGN NOTES:
1. SIGN MATERIAL: 18GA
ALUMINUM
2. LETTERING COLOR =
BLACK / WHITE
3. BACKGROUND COLOR =
WHITE / BLUE
7"
SIGN NOTES:
1. SIGN MATERIAL: 18GA
ALUMINUM
2. LETTERING COLOR =
BLACK
3. BACKGROUND COLOR =
WHITE / RED
12"
SIGN NOTES:
1. SIGN MATERIAL: 18GA
ALUMINUM
2. LETTERING COLOR =
BLACK
3. BACKGROUND COLOR =
YELLOW
7"
36" OC MAX
10'-0" OC MAX
FIELD VERIFY
12"
2"CLR.
2'-0"
CLR MIN.
COAX BRIDGE: 14 GA.
GALV. GRIPSTRUT 24"
WIDTH, 2" PLANK 14 GA.
SUPPORT COLUMN: 4"Ø
O.D. GALV. SCHED. 40
POST @ 10'-0" O.C. MAX
CROWN TO DRAIN; TYP.
FOOTING
MUST BE 6"
BELOW
FROST LINE,
TYP.
SIDE ELEVATIONFRONT ELEVATION
NOTE: GROUND COAX BRIDGE PER THE REQUIREMENTS
OF THE NEC STANDARDS - SEE DETAIL 1/E-2
COAX SUPPORT BLOCKS
AT 3'-0" MAX O.C.
EDGE OF
SHELTER
20" UNISTRUT W/ NUT
AND WASHER EACH
SIDE/ EACH LEVEL AS
REQUIRED
12"Ø X 48" DEEP CONC.
FOOTING; TYPICAL
COAX BRIDGE-(2) 24" WIDE
SAFETY GRATED WAVE
GUIDE BRIDGE CHANNEL,
OR APPROVED EQUAL
DUAL POST 24" ICE
BRIDGE KIT SITE PRO1
PART# 4B24D OR
APPROVED EQUAL
C-4
8"
2-1/2"
1-1/2"
8" x 8" x 1/2" PLATE
SUPPORT PIPE
1/2"Ø HILTI-KWIK-BOLT-TZ
SS EXPANSION ANCHOR
MIN 2" EMBED (TYP. OF 4)
5/16 TYP
8" x 8" x 1/2" PLATE
CONC. SLAB (IF
REQUIRED)
B
ICE-BRIDGE
SUPPORT POST
SECTION B
BASE PLATE -
OPTIONAL PIPE TO
CONC ATTACHMENT
POWER LINE TRENCH
4SCALE: NTS BOLLARD DETAIL SIGN DETAILS 5SCALE: NTS
3SCALE: NTS2 COMPOUND ROCK SECTION DETAILSCALE: NTS1SCALE: NTS NOT USED
6SCALE: NTS NOT USED
" E
LE
CT
RI
CA
L P
RI
MA
RY
" E
LE
CT
RI
CA
L S
EC
ON
DA
RY
2'- 6"
T O
3'- 6"
4" 4"
12" MIN
CLEAR
24"±
WARNING TAPE
FINISH GRADE
UNEXCAVATED EARTH
COMPACTED FILL
(85% IN LANDSCAPED AREAS,
95% IN PAVED AREAS)
ELECTRICAL CONDUIT(S); 3"Ø
MIN, SCHEDULE 40 PVC, OR
AS SHOWN ON PLAN
COMPACTED SANDNOTES:
1. EXCAVATE TO REQUIRED DEPTH.
2. VERIFY ALL TRENCHING REQUIREMENTS PER LOCAL UTILITIES.
3. CONTRACTOR TO PROVIDE (1) 300 POUND NYLON PULL CORD
AND CONDUCTORS AS REQUIRED PER CONDUIT.
CONTRACTOR TO VERIFY
WITH WCCCA PM IF SPARE
CONDUIT TO BE PLACED IN
TRENCH FOR FUTURE
ICE BRIDGE DETAIL 7SCALE: NTS
(E) GRADE
4"Ø (MIN) 11 GAUGE METAL FILLED WITH
2,500 PSI CONC. ROUND CONCRETE AT
TOP TO PREVENT WATER COLLECTION.
PAINT W/ (3) COATS EPOXY ENAMEL
(YELLOW)
THE BOLLARDS SHALL MEET THE
FOLLOWING CRITERIA:
1. THEY SHALL BE CONSTRUCTED OF
STEEL NOT LESS THAN 4" IN
DIAMETER AND CONCRETE FILLED.
2. SPACED NOT MORE THAN 5 FEET
BETWEEN POSTS ON CENTER.
3. THEY SHALL BE SET NOT LESS
THAN 3 FEET DEEP IN A CONCRETE
FOOTING OF NOT LESS THAN 15"
DIAMETER.
4. THEY SHALL BE SET WITH THE TOP
OF THE POSTS NOT LESS THAN 3'
ABOVE GROUND.
CROWN FOOTING TO
DRAIN
UNDISTURBED
EARTH, TYP
4" OF 3/4" CHIP ROCK;
NO FINES
GEOTEXTILE FABRIC,
TYPAR-3401
OR EQUIVALENT
4" OF 3/4"-MINUS
CRUSHED ROCK
COMPACTED 95%
SUBSOIL COMPACTED TO 92% OF
MAXIMUM DRY DENSITY MIN. PER
ASTM-D1557
NOTE: STRIP ALL ORGANICS
ECSO 911
AutoCAD SHX Text 541-xxx-xxxx
AutoCAD SHX Text
IN CASE OF AN EMERGENCY
AutoCAD SHX Text
CALL
AutoCAD SHX Text
APPLEGATE FS 4
AutoCAD SHX Text Site Name:
AutoCAD SHX Text
GENERAL INFORMATION FOR WORKING IN THE AREA OF ANTENNAS
AutoCAD SHX Text
* All personnel entering this site All personnel entering this site must be authorized. * Obey all posted signs. Obey all posted signs. * Assume all antennas are active. Assume all antennas are active. * Maintain minimum distance of 3 Maintain minimum distance of 3 feet clearance from antennas.
Call 1-888-xxx-xxxx for information or assistance.
GENERATOR &
PROPANE TANK
DETAILS
C-5
SHEET NUMBER:
SHEET TITLE:
LICENSURE:
DRAWING INFORMATION:
THIS DRAWING IS COPYRIGHTED AND IS THE SOLE
PROPERTY OF THE OWNER. IT IS PRODUCED SOLELY
FOR USE BY THE OWNER AND ITS AFFILIATES.
REPRODUCTION OR USE OF THIS DRAWING AND/OR
THE INFORMATION CONTAINED IN IT IS FORBIDDEN
WITHOUT THE WRITTEN PERMISSION OF THE OWNER.
PLANS PREPARED BY:
DATE RELEASE
10-14-21 SITE SKETCH
11-02-21
PRELIM ZONING DRAWINGS
04-06-22 CLIENT COMMENT / SURVEY UPDATE
07-06-22 FINAL ZONING DRAWINGS
1-25-23
BID DRAWINGS
PROJECT INFORMATION:
ECSO 9-1-1
APPLEGATE
FIRE STATION 4 NSB
12188 WILLIAMS HWY
GRANTS PASS, OR 97527
12725 SW MILLIKAN WAY, SUITE 300
BEAVERTON, OR 97005
503-387-5331 www.cushing-engr.com
Cushing
Civil Engineers
Civil Engineers
N
R
C
O
N
S
T
R
U
C
T
I
O
N
35 KW 60 HZ 44KVA AC
BACKUP GENERATOR
MANUFACTURER TBD
GENERATOR TO BE
PROVIDED BY ECSO
G A
S G
A S
G A
S G
A S
10'-0" REQUIRED PROPANE
TANK SETBACK BUFFER;
NO IGNITION SOURCES
WITHIN SETBACK
NOTE:
ALL CONDUIT INSIDE THE BUILDING MUST BE METAL AND BE GROUNDED PER R-56 STANDARDS.
INTERIOR SHELTER LAYOUT IS FOR REFERENCE ONLY.
THIS GENERATOR & PROPANE LAYOUT IS FOR INFORMATION ONLY AND IS PRESENTED AS A GUIDELINE. VERIFY SITE CONDITIONS AND LAYOUT PRIOR TO INSTALLATION OF ALL EQUIPMENT. INSTALL ALL EQUIPMENT PER MANUFACTURER'S
INSTRUCTIONS.
FUEL LINE SIZE PER MANUFACTURERS
RECOMMENDATION
1-CAT-5 FOR HALL EFFECT FUEL
SENSOR WIRE SUPPLIED BY
OTHERS IN 3/4" RIGID PVC
CONDUIT FROM GENERATOR TO
PROPANE TANK
3-#2 THHN PLUS #8
GROUND IN 2" RIGID
PVC CONDUIT FROM
GENERATOR TO
TRANSFER SWITCH
EQUIPMENT SHELTER
10'
TRINITY LIQUID PROPANE
FUEL TANK OR EQUAL ON
CONCRETE PAD
2-CAT-5 CONTROL WIRING IN 3/4"
RIGID PVC CONDUIT
AUTOMATIC TRANSFER SWITCH
CIRCUIT BREAKER PANEL
POWER CONDUIT TO STUB UP AT
METER
BORE AND WEATHERPROOF NEW PENETRATIONS
INTO SHELTER FOR NEW CONDUIT ROUTING, TYP.
LIQUID WITHDRAWL
DOME
RELIEF VALVE
2-#12 THHN PLUS #12 GROUND IN
1" RIGID METAL CONDUIT FROM
GENERATOR TO DEDICATED
CIRCUIT BREAKER @ BREAKER
PANEL, RATING 20A
MANUAL TRANSFER SWITCH
35 KW 60 HZ 44KVA AC
BACKUP GENERATOR
MANUFACTURER TBD
GENERATOR TO BE
PROVIDED BY ECSO
GENERATOR SEE DETAIL 5
SHUT-OFF VALVE
LEGEND
UNION
PRESSURE REGULATOR
SOLENOID VALVE
FLEXIBLE CONNECTION
3/4" DIA. CONDUIT W/ 1-4/18 AWG
1/4" FLEX FUEL LINE FROM PROP
TANK TO REG
SOLENOID VALVE AND
REGULATOR TO COME
WITH GENSET
TO CARBURETOR
NOTES:
1. GROUND SYSTEM SHOULD COMPLY WITH INDUSTRY STANDARDS
2. CONFIRM CONNECTIONS PROVIDED WITH FUEL TANK
3. USE GASEOUS LP VAPOR WITHDRAWAL SYSTEM
4. TO CODE OFFICIAL, PAD IS FOR EQUIPMENT ONLY (NO BUILDINGS)
5. CONTRACTOR IS TO VERIFY THAT ALL PROPOSED ANCHORS WILL PROVIDE ADEQUATE FIT
PRIOR TO POURING CONCRETE PADS, NOTIFY DON CUSHING ASSOCIATES IF ANY
DISCREPANCIES EXIST
C-9
NOTES:
1. PROPANE TANK REGISTERED WITH
NATIONAL BOARD AND COMPLIES
AND INSTALLED PER NFPA 58 CODE
2. PROPANE TANK INSTALLED AT LEAST
10 FT FROM EXTERNAL SOURCE OF
IGNITION
TRINITY LIQUID
PROPANE FUEL
TANK OR EQUAL
SEE PROPANE TANK SPEC SHEET
FOR DIMENSIONS AND WEIGHTS
# 4 X 25"X12" @
12" O.C. TYP.
8" 4"
12"
1ST STAGE REG; LV4403TR96 14" IN
AND 3/4 " OUT
2ND STAGE REG LV5503B8;
4" IN AND 1" OUT
SNAP2IT NON-METALLIC CONN 34"
NM LIQUID TIGHT CONN CAT 5
GALV. 1 12" Ø STAND PIPE POST
(1.9" OD) W/ CAP
SHUT-OFF VALVE W/ DRIP LEG
HOR. UNI-STR W/ NON
CORR PIPE CLAMP
SERVI-SERT TOP-CON RISER
5'-0" X 16'-0" X 8" CONCRETE
PAD W/ #4 @ 12" O.C. EA WAY
GROUND PROPANE TANK
PER NEC REQUIREMENTS
DOME
PLUG
RELIEF VALVE
VAPOR WITHDRAWAL
# 4 CONT. IN
TURNED-DOWN EDGE
FOOTING
FINISHED GRADE
6" MIN. COMPACTED GRAVEL
BASE UNDER PERIMETER
FOOTING AND SLAB
FUEL GAUGE, R3D
3/4" ULTRATITE LIQUIDTIGHT FLEX
NON-MET PVC COND FOR 1-4/18 AWG
FOR HALL EFFECT FUEL SENSOR,
DS_1318
CUSTOM PROPANE TANK
CANOPY GENERATOR CANOPY NOT
SHOWN FOR CLARITY
UFER GROUND
5/8" X 5" SS TITEN HD
ANCHORAGE, TYP
18"
6" MIN. COMPACTED GRAVEL
BASE UNDER PERIMETER
FOOTING AND SLAB
12"
# 4 CONT. IN
TURNED-DOWN EDGE
FOOTING
UFER GROUND
4'-0" X 9'-6" X 8"
CONCRETE PAD W/ #4
@ 12" O.C. EA WAY
SCALE: NTS 1
SCALE: NTS
SCALE: NTS
SCALE: NTSSCALE: NTS
2-CAT-5 CONTROL WIRING
IN 3/4" RIGID PVC
CONDUIT
3-#2 THHN PLUS #8
GROUND IN 2" RIGID PVC
CONDUIT
1-CAT-5 HALL EFFECT
FUEL SENSOR WIRING IN
3/4" RIGID PVC CONDUIT
GENERATOR PLAN
GENERATOR FUEL SYSTEM ELEVATION
2-#12 THHN PLUS #12
GROUND IN 3/4" RIGID PVC
CONDUIT (BLOCK HEATER
AND BATTERY CHARGER)
FUEL LINE CONNECTION PER
MANUFACTURER RECOMMENDATION
FRONT
SIDE
FRONT
SIDE
35 KW 60 HZ 44KVA AC
BACKUP GENERATOR
MANUFACTURER TBD
GENERATOR TO BE
PROVIDED BY ECSO
TRENCH SECTION NOT USED
2SCALE: NTS GENERATOR ELEVATION NOT USED
TYPICAL GENERATOR LAYOUT
NOTE: DOCUMENTATION FOR THE GENERATOR IS TO BE PROVIDED BY THE SUPPLIER CERTIFYING THAT ALL HAZARDOUS CONTENTS WILL REMAIN CONTAINED FOLLOWING THE DESIGN EARTHQUAKE FOR THIS SITE. CERTIFICATION OF CONTAINMENT IS TO BE PROVIDED BY 1) ANALYSIS, 2) APPROVED SHAKE TABLE TESTING IN ACCORDANCE WITH SECTION 13.2.5 OF ASCE 7, OR 3) EXPERIENCE DATA IN ACCORDANCE WITH ASCE 7 SECTION 13.2.6. EVIDENCE DEMONSTRATING COMPLIANCE OF THIS REQUIREMENT SHALL BE SUBMITTED TO THE LOCAL JURISDICTION AFTER REVIEW AND APPROVAL BY THE ENGINEER OF RECORD.
SEE GENERATOR SPEC SHEET FOR DIMENSIONS
AND WEIGHTS
(4) 1/2"Ø X 5" EMBED.
TITEN HD ANCHORS,
SEE DETAIL #3 THIS
SHEET
(4) 3/4"Ø X 5" EMBED.
TITEN HD SS
ANCHORS
35 KW 60 HZ 44KVA AC
BACKUP GENERATOR
MANUFACTURER TBD
GENERATOR TO BE
PROVIDED BY ECSO
FUEL LINE CONNECTION
PER MANUFACTURER
RECOMMENDATION
SCALE: NTS 4 GENERAL NOTES
SCALE: NTS 6
1. CONTRACTOR TO VERIFY AND CONFIRM ALL DIMENSIONS
AND CONDITIONS AND NOTIFY ENGINEER OF RECORD OF
ANY DISCREPANCIES PRIOR TO START OF WORK.
2. THE CONTRACTOR SHALL BE RESPONSIBLE FOR
STRUCTURAL STABILITY DURING CONSTRUCTION. THE
STRUCTURE SHOWN ON THE DRAWINGS HAS BEEN
DESIGNED FOR STABILITY UNDER THE FINAL
CONFIGURATION ONLY.
3. CODE: 2019 OREGON STRUCTURAL SPECIALTY CODE
(OSSC).
4. THE FOOTINGS HAVE BEEN DESIGNED FOR AN ALLOWABLE
SOIL BEARING PRESSURE OF 1,500 PSF.
5. CONCRETE: FOOTINGS, F'C = 3,000 PSI MINIMUM
COMPRESSIVE STRENGTH AT 28 DAYS.
6. REINFORCING STEEL: FY = 60,000 PSI
7. STRUCTURAL AND MISCELLANEOUS STEEL SHALL BE IN
ACCORDANCE WITH AISC SPECIFICATION FOR THE DESIGN,
FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR
BUILDINGS AND SHALL BE ASTM A-36 U.O.N. ALL BOLTS
HOLES SHALL BE PUNCHED OR DRILLED; BURNING OF
HOLES SHALL NOT BE PERMITTED. ALL STRUCTURAL STEEL
SHALL HAVE ONE SHOP COAT OF PAINT.
ALL MATERIALS SHALL CONFORM TO THE FOLLOWING
STANDARDS:
PIPE: A53 GR. B (MIN. FY = 35 KSI)
SHAPES: ASTM A36/ ASTM A572 GR. 50
WIDE FLANGE: ASTM A992
TUBES: A500 GR. B, FY = 46 KSI
PLATES: A36
WELDS: E70XX ELECTRODES
STRUCTURAL BOLTS: ASTM A325N
NON-STRUCTURAL BOLTS: SAE J429 GR. 5 / F1554-36
U-BOLTS: ASTM A36
THREADED ROD: ASTM A307
SPECIAL INSPECTION BY OWNERS TESTING AGENCY
SPECIAL INSPECTIONS AND TESTING SHALL BE PERFORMED BY
AN APPROVED AGENCY IN ACCORDANCE WITH OREGON
STRUCTURAL SPECIALTY CODE (OSSC) SECTIONS 1703 AND 1704,
AND WITH THE STATEMENT OF SPECIAL INSPECTIONS AS
REQUIRED BY OSSC SECTIONS 1704.1.1 AND 1705 FOR BUILDING
STRUCTURAL ELEMENTS SUMMARIZED AS FOLLOWS;
1. STRUCTURAL STEEL CONSTRUCTION PER OSSC SECTIONS
1704.3 AND TABLE 1704.3 INCLUDING MATERIAL
IDENTIFICATION, AND SHOP WELDING.
1'-4"1'
SCALE: NTS 7
4"
NONVEHICULAR AREAS:
BACKFILL WITH CLEAN NATIVE
BACKFILL AND COMPACT TO
90% MAX. DRY DENSITY.
VEHICULAR AREAS: BACKFILL
WITH GRANULAR 'A' AND
COMPACT TO 95% MDD
2'
WARNING TAPE
CONDUIT, TYPICAL
BRICK SAND
FUEL LINE SIZE AND TRACE
WIRE PER MANUFACTURERS
RECOMMENDATION
NOT USED
CONCRETE PAD
SEE DETAIL 5
BACKUP GENERATOR
MANUFACTURER TBD
AutoCAD SHX Text
P P
P P
P P P P P P
LPGLPG
LPG
LPG
LPG
LPG
LPG
LPG
LPG
LPG
LPG
LPG
LPG
LPG
LPG
LPG
L
P
G
L
P
G
L
P
G
L
P
G
L
P
G
L
P
G
L
P
G
L
P
G
L
P
G
P P
P
11X17 SCALE: 1" = 10' 22X34 SCALE: 1" = 5' SITE COMPOUND GROUNDING PLAN 1
SITE GROUNDING
PLAN & DETAILS
E-1
SHEET NUMBER:
SHEET TITLE:
SCALE: NTS 3 SCALE: NTS 2 TERRADYNE ELECTROLYTIC GROUND ELECTRODE
LICENSURE:
DRAWING INFORMATION:
THIS DRAWING IS COPYRIGHTED AND IS THE SOLE
PROPERTY OF THE OWNER. IT IS PRODUCED SOLELY
FOR USE BY THE OWNER AND ITS AFFILIATES.
REPRODUCTION OR USE OF THIS DRAWING AND/OR
THE INFORMATION CONTAINED IN IT IS FORBIDDEN
WITHOUT THE WRITTEN PERMISSION OF THE OWNER.
PLANS PREPARED BY:
DATE RELEASE
10-14-21 SITE SKETCH
11-02-21
PRELIM ZONING DRAWINGS
04-06-22 CLIENT COMMENT / SURVEY UPDATE
07-06-22 FINAL ZONING DRAWINGS
1-25-23
BID DRAWINGS
PROJECT INFORMATION:
ECSO 9-1-1
APPLEGATE
FIRE STATION 4 NSB
12188 WILLIAMS HWY
GRANTS PASS, OR 97527
12725 SW MILLIKAN WAY, SUITE 300
BEAVERTON, OR 97005
503-387-5331 www.cushing-engr.com
Cushing
Civil Engineers
Civil Engineers
N
R
C
O
N
S
T
R
U
C
T
I
O
N
GENERAL NOTES:
1. ALL INSTALLATIONS ARE TO BE FIELD VERIFIED.
2. GROUND CONDUCTORS ARE TO BE BURIED AT A MINIMUM 30" BELOW GRADE
OR 6" BELOW FREEZE LINE, WHICHEVER IS GREATER.
3. ALL BELOW GRADE GROUNDING CONDUCTORS ARE TO BE ENCOMPASSED IN
A 2" X 4" BED OF SOIL ENHANCEMENT MATERIAL.
4. BONDS TO FENCE POSTS ARE TO BE MADE AT 12" ABOVE GRADE WHERE
APPLICABLE.
5. NO CONDUCTOR SHALL HAVE A BEND IN RADIUS OF LESS THAN 12" AND
SHALL NOT EXCEED 90 DEGREES.
6. TERRADYNE ELECTROLYTIC GROUND ELECTRODES ARE NOT TO SHARE THE
SAME TRENCH AS GROUNDING CONDUCTOR, NOR RUN IN A PARALLEL PATH
TO THE CONDUCTOR.
7. ALL GROUND SYSTEMS ARE TO BE MADE COMMON.
8. ALL BONDS ARE TO BE COATED WITH ANTI-OXIDATION COMPOUND.
9. WHERE STANDARD GROUND ELECTRODES ARE UNABLE TO BE DRIVEN, 12" X
12" X 1/8" COPPER GROUND PLATES SHALL BE INSTALLED 30" BELOW
FINISHED GRADE & ENCOMPASSED IN 50LBS OF TERRAFILL SOIL
ENHANCEMENT MATERIAL.
LEGEND:
TERRADYNE TG-100L-H36-2T-36-4F-P SERIES
ELECTRODE W/ INSPECTION WELL
EXOTHERMIC WELD
MECHANICAL CONNECTION
5/8" X 10' COPPER CLAD GROUND ELECTRODE
5/8" X 10' COPPER CLAD GROUND ELECTRODE
WITH INSPECTION SLEEVE
#2 TINNED SOLID COPPER CONDUCTOR
SOIL ENHANCEMENT DETAIL
POLYMER TEST WELL
4"
2"
" M
IN
5"
#2 TINNED BARE
COPPER
CONDUCTOR
TERRAFILL SOIL
ENHANCEMENT
MATERIAL
TERRAFILL SOIL
ENHANCEMENT MATERIAL
(DISTRIBUTED EQUALLY)
EXOTHERMIC WELD (AT FACTORY)
#2 TINNED BARE COPPER
CONDUCTOR (AT FACTORY)
36" VERTICAL RISER
EXOTHERMIC WELD TO GROUND RING
20' HORIZONTAL ELECTRODE SHFT
VENTILATION PORT
(NOTE: PORT SHALL NOT BE
COVERED IN EARTH)
TGB
(P) BOND TO WAVEGUIDE
BRIDGE SUPPORT - PER
MANUF'S REQUIREMENTS AND
NEC STANDARDS
(P) PROPOSED BOND TO ANTENNA AND
TOWER EQUIPMENT PER MANUF'S
REQUIREMENTS AND INDUSTRY
STANDARDS
(P) BOND TO TO WAVE
GUIDE LADDER ON TOWER
AS REQUIRED
(P) BOND TO FUEL TANK SUPPORT VIA
MECHANICAL CONNECTION - PER
MANUF'S REQUIREMENTS AND NEC
STANDARDS
EGB
(P) BOND TO EQUIPMENT (HVAC, ELECTRIC
SERVICE) TYP - PER MANUF'S REQUIREMENTS
AND NEC STANDARDS
(P) 5/8" X 10' COPPER CLAD
GROUND ELECTRODE WITH
INSPECTION SLEEVE TYP
(P) BOND TO EACH TOWER LEG
IN 2 PLACES AT 90° TYP - PER
MANUF'S REQUIREMENTS AND
NEC STANDARDS
(P) 5/8" X 10' COPPER CLAD
GROUND ELECTRODE TYP - 20'
MAX SPACING
(P) TOWER
(P) TOWER GROUND RING;
INSTALL DURING TOWER
PIER CONSTRICTION
(P) GENERATOR
ON CONC. PAD
BOND TOWER RING TO (EX) BUILDING GROUND
PER NEC STANDARDS, TYP OF (2)
(P) EQUIPMENT
ROOM
MGB
(P) BOND TO GENERATOR VIA MECHANICAL
CONNECTION, ADD UFER GROUND TO CABINET
FOUNDATION - PER MANUF'S REQUIREMENTS
AND NEC STANDARDS
(P) 5/8" X 10' COPPER CLAD
GROUND ELECTRODE TYP - 20'
MAX SPACING
AutoCAD SHX Text
AutoCAD SHX Text
SCALE: 1" = '
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
NOTE: NOT GC
GENERAL NOTES
ALL ANTENNAS, LINES AND RELATED
INSTALLATION HARDWARE TO BE
PROVIDED BY THE LAND MOBILE
COMMUNICATIONS PROVIDER.
25MM SQ. CSA (#4 AWG) OR
COARSER BARE COPPER
CONDUCTOR OR STEEL
REINFORCING BAR OR ROD,
NOT LESS THAN 0.5" Ø AND AT
LEAST 20' LONG
GROUNDING
ELECTRODE
CONDUCTOR
CONNECTION
LISTED FOR
THE PURPOSE
FOUNDATION
IN DIRECT
CONTACT
WITH EARTH
2" MIN.
NOTE: FOR REFERENCE ONLY
NONMETALLIC
PROTECTIVE
SLEEVE
NEW
GROUND
RING
BOND
EQUIPMENT
TO NEW
GROUND RING
AND UFER
FOR ALL NEW
CONCRETE
PADS
COAX CABLE GROUNDING
KITS
ANTENNA MOUNT GROUND
NOTE:
1. DO NOT BOND AIR TERMINAL OR
LIGHTNING ROD TO AGB
2. AGB GROUND BAR TO BE PLATED.
AGB TO BE BONDED DIRECTLY TO
TOWER.
HARGER 1/4"X4"X20" TIN PLATED
GROUNDING BAR #TGBIA14412M OR
SIMILAR PER NEC AGB GROUNDING
LICENSURE:
DRAWING INFORMATION:
THIS DRAWING IS COPYRIGHTED AND IS THE SOLE
PROPERTY OF THE OWNER. IT IS PRODUCED SOLELY
FOR USE BY THE OWNER AND ITS AFFILIATES.
REPRODUCTION OR USE OF THIS DRAWING AND/OR
THE INFORMATION CONTAINED IN IT IS FORBIDDEN
WITHOUT THE WRITTEN PERMISSION OF THE OWNER.
PLANS PREPARED BY:
DATE RELEASE
10-14-21 SITE SKETCH
11-02-21
PRELIM ZONING DRAWINGS
04-06-22 CLIENT COMMENT / SURVEY UPDATE
07-06-22 FINAL ZONING DRAWINGS
1-25-23
BID DRAWINGS
PROJECT INFORMATION:
ECSO 9-1-1
APPLEGATE
FIRE STATION 4 NSB
12188 WILLIAMS HWY
GRANTS PASS, OR 97527
12725 SW MILLIKAN WAY, SUITE 300
BEAVERTON, OR 97005
503-387-5331 www.cushing-engr.com
Cushing
Civil Engineers
Civil Engineers
N
R
C
O
N
S
T
R
U
C
T
I
O
N
GROUNDING
DETAILS I
E-2
SHEET NUMBER:
SHEET TITLE:
7SCALE: NTS GROUND BAR DETAILS ICE BRIDGE GROUNDING DETAIL FOR ONE 24" SECTION
3SCALE: NTS
FEED LINE CABLE GROUNDING
NOTES
1. TYP. FOR ALL GROUND WIRES FOR
ELECT. AND OTHER EQUIPMENT.
2. THE ENTIRE LUG AND AREA TO BE
SPRAYED WITH CLEAR LACQUER OR
COLD GALVANIZING SPRAY.
3. GROUND LEADS TO BE EXOTHERMIC
WELDED TO…
This is the start of the file's text. The full file is on GovTribe.