Appendix E Baseside List Feb2025.xlsx
XLSX spreadsheet 62 KB Posted
- Attached to
- Potable Water Backflow Prevention Survey Federal contract opportunity
- Solicitation number
- FA462625Q0017
About this file
This file is an appendix containing a comprehensive inventory list of backflow prevention devices and assemblies at Malmstrom Air Force Base as of February 2025. The spreadsheet details 698 total devices across various buildings and facilities, cataloging information such as building numbers, device IDs, equipment types, hazard rankings, manufacturers, models, sizes, and specific locations of each device. The inventory includes atmospheric vacuum breakers (AV), reduced pressure principle assemblies (RP), double check valve assemblies (DC), pressure vacuum breakers (PV), and other backflow prevention devices installed throughout the base.
The document appears to be supporting documentation for solicitation FA462625Q0017, which requires a contractor to perform a cross-connection control survey of the potable water system at Malmstrom AFB and 15 remote Missile Alert Facilities. Each entry provides detailed location information, such as "1/2" AV on water supply line to disposal unit located on north wall" or "3/4" RP on make-up water supply line to Low Temperature Heating System located in center of room," enabling precise identification and inspection of each device.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Appendix E Baseside List Updated March2025.xlsx | XLSX spreadsheet | |
| Combo Amendment 0002 - FA462625Q0017.pdf | ||
| Appendix Aa Base Map (2025).pdf | ||
| Solicitation Q and A for FA462625Q0017.pdf | ||
| Appendix Ab Base Map (2018).pdf | ||
| Appendix D AF Form 848.pdf | ||
| Solicitation Amendment FA462625Q00170001 SF 30.pdf | ||
| Appendix A Base Map 11x17.pdf | ||
| Appendix D AF Form 848.pdf | ||
| Appendix C Contractor Entry Authorization List.xlsx | XLSX spreadsheet | |
| Solicitation - FA462625Q0017.pdf | ||
| Appendix G AFMAN 32-1067.pdf | ||
| Appendix F Missile Zone BPDs Feb2025.xlsx | XLSX spreadsheet | |
| Appendix B MAF Map 34x22.pdf | ||
| Potable Water Backflow Survey SOW - Feb2025.pdf |
Show all 15
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
compbpds
| Building Number | BPD ID Full | RWP Equipment Type / Number | Hazard Rank | Manufacturer | Model | Size | Point of Use |
| 1010 | MA-1010-01-007-AV | 1000 / 0003 | Low | Chicago | b641 | 3/4 | Slop sink with AV located in janitor's closet north of old gymnasium |
| 1010 | MA-1010-01-008-AV | 1000 / 0595 | Low | Watts | NF 8 | 3/4" | Hose bibb in womens locker room, near jacuzzi |
| 1010 | MA-1010-01-009-AV | 1000 / 0596 | Low | Arrowhead | #58 ABP | 3/4" | Hose bibb in womens locker room |
| 1010 | MA-1010-OO-001-AV | 1000 / 0004 | Low | Watts | NF 8 | 3/4 | Hand hydrant with AV located northeast of building and southeast of running track |
| 1010 | MA-1010-OO-002-AV | 1000 / 0005 | Low | Watts | NF 8 | 3/4 | Hand hydrant with AV located east of running track |
| 1010 | MA-1010-OO-003-AV | 1000 / 0006 | Low | Watts | NF 8 | 3/4 | Hand hydrant with AV located northeast of running track |
| 1010 | MA-1010-01-004-AV | 1000 / 0007 | Low | Arrowhead | #58 ABP | 3/4 | Hose bibb with AV on main water supply located on east wall near entrance |
| 1010 | MA-1010-01-005-RP | 1000 / 0008 | High | Watts | 909 MOD QT | 1 | 1" RP on make-up water to steam boiler located in east end of room |
| 1010 | MA-1010-01-006-RP | 1000 / 0009 | High | Watts | 909 MOD QT | 3/4 | 3/4" RP on make-up water supply lines to steam boiler in west end of room, chiller, and both gymnasium Low Temperature Heating |
| 1012 | MA-1012-01-001-DC | 1000 / 0805 | Low | Watts | 709 | 4 | Used for main water supply, located in Mech Room |
| 1012 | MA-1012-01-002-DC | 1000 / 0806 | Low | Ames | 200 | 4 | Backflow used on the main fire suppression system, for the gym, located just inside the Mech Room on the left. |
| 102 | MA-102-OO-001-RP | 1000 / 0010 | High | Watts | 9 | 3 | 3" RP on water supply line to irrigation located in park, west of building in concrete block enclosure |
| 1062 | MA-1062-01-005-AV | 1000 / 0011 | Low | T&S | b969 | 3/4 | Slop sink with AV located in janitor's closet |
| 1062 | MA-1062-OO-001-AV | 1000 / 0012 | Low | Arrowhead | #58 ABP | 3/4 | Hose bibb with AV located on north wall outside north mechanical room door |
| 1062 | MA-1062-03-007-AV | 1000 / 0013 | Low | T&S | b969 | 3/4 | Slop sink with AV located in janitor's closet |
| Building Number | BPD ID Full | RWP Equipment Type / Number | Hazard Rank | Manufacturer | Model | Size | Point of Use |
| 1062 | MA-1062-02-006-AV | 1000 / 0014 | Low | T&S | B969 | 3/4 | Slop sink with AV located in janitor's closet |
| 1062 | MA-1062-01-002-DC | 1000 / 0015 | Low | Ames | 2000 SS | 3 | 3" DC on water supply line to fire suppression system located on west wall |
| 1062 | MA-1062-01-003-RP | 1000 / 0016 | High | Watts | 009 M2 QT | 1.5 | 1.5" RP on water supply line to irrigation located on east end of north wall (bottom assembly) |
| 1062 | MA-1062-01-004-RP | 1000 / 0017 | High | Wilkins Zurn | 975 XL | 3/4 | 3/4" RP on make-up water supply lines to both chiller and heating systems located on east end of north wall (top assembly) |
| 1075 | MA-1075-01-008-AV | 1000 / 0018 | Low | Watts | 288A | 1/2 | 1/2" AV on water supply line to dishwasher on top of machine (south device) located on east wall |
| 1075 | MA-1075-01-001-AV | 1000 / 0029 | Low | Watts | 288A | 1/2 | 1/2" AV on water supply line to disposal unit located on north wall |
| 1075 | MA-1075-01-016-AV | 1000 / 0020 | Low | Chicago | B641 | 3/4 | Sink faucet with AV located in southeast corner |
| 1075 | MA-1075-01-014-AV | 1000 / 0021 | Low | Chicago | b641 | 3/4 | Slop sink with AV on west wall in janitor's closet, south of east dining room |
| 1075 | MA-1075-01-011-AV | 1000 / 0022 | Low | Arrowhead | No. 58 abp | 3/4 | Hose bibb with AV located on south end of west wall adjacent to hand wash sink |
| 1075 | MA-1075-01-010-AV | 1000 / 0023 | Low | Arrowhead | No. 58 abp | 3/4 | Hose bibb with AV located south of triple basin sink on west wall |
| 1075 | MA-1075-01-009-AV | 1000 / 0024 | Low | Watts | 288A | 1/2 | 1/2" AV on water supply line to disposal unit located south of dishwashing machine |
| 1075 | MA-1075-01-007-AV | 1000 / 0025 | Low | Watts | 288A | 3/4 | 3/4" AV on water supply line to dishwasher on top of machine (north device) located on east wall |
| 1075 | MA-1075-01-006-AV | 1000 / 0026 | Low | Watts | 288A | 1/2 | 1/2" AV on water supply line to disposal unit located on west wall of dishwasher room |
| Building Number | BPD ID Full | RWP Equipment Type / Number | Hazard Rank | Manufacturer | Model | Size | Point of Use |
| 1075 | MA-1075-01-005-AV | 1000 / 0027 | Low | Watts | 288A | 1/2 | 1/2" AV on water supply line to disposal unit located on north wall |
| 1075 | MA-1075-01-004-AV | 1000 / 0030 | Low | T&S | B969 | 3/4 | Slop sink with AV in card board eater room |
| 1075 | MA-1075-01-002-AV | 1000 / 0019 | Low | Watts | 288A | 1/2 | 1/2" AV on water supply to kettle pot fill station located on east end (south device) |
| 1075 | MA-1075-01-003-AV | 1000 / 0028 | Low | Watts | 288A | 1/2 | 1/2" AV on water supply to kettle pot fill station located on east end (north device) |
| 1075 | MA-1075-01-012-DC | 1000 / 0031 | Low | Ames | 2000 SS | 6 | 6" DC on water supply line to fire suppression system located in northeast corner janitor's closet, south of east dining room |
| 1075 | MA-1075-01-013-RP | 1000 / 0032 | High | Watts | 009 M2 QT | 1.5 | 1.5" RP on water supply line to irrigation located on south wall in janitor's closet, south of east dining room |
| 1075 | MA-1075-01-017-RP | 1000 / 0033 | High | Watts | 909M1QT | 1.5" | 1 1/2" RP on make-up water to steam boiler located next to water softener approx. 5' high. |
| 1075 | MA-1075-02-015-RP | 1000 / 0034 | High | Watts | 009 M2 QT | 3/4 | 3/4" RP on water supply line to hose bibb with AV located adjacent to chemical feed/make-up water tank for chiller system and w |
| 1082 | MA-1082-OO-006-AV | 1000 / 0035 | Low | Watts | NF8 | 3/4 | Hand hydrant with AV located in grassy area east of building and adjacent to Goddard Drive |
| 1082 | MA-1082-OO-002-AV | 1000 / 0036 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located on west wall between mechanical room doors |
| 1082 | MA-1082-01-005-AV | 1000 / 0037 | Low | Chicago | B641 | 3/4 | Slop sink with AV located in janitor's closet |
| 1082 | MA-1082-OO-001-PV | 1000 / 0038 | High | Wilkins | 720 A | 1 | 1" PV on water supply line to irrigation located on southeast corner just outside mechanical room |
| 1082 | MA-1082-01-003-RP | 1000 / 0039 | High | Watts | 909 MOD QT | 3/4 | 3/4" RP on make-up water supply line to steam boiler located in southeast corner |
| Building Number | BPD ID Full | RWP Equipment Type / Number | Hazard Rank | Manufacturer | Model | Size | Point of Use |
| 1082 | MA-1082-01-004-RP | 1000 / 0040 | High | Watts | 909 MOD HW 210 | 3/4 | 3/4" RP on make-up water supply line Low Temperature Heating System located on west end near ceiling above package chiller |
| 1084 | MA-1084-01-001-AV | 1000 / 0041 | Low | Chicago | b641 | 3/4 | Slop sink with AV located in janitor's closet |
| 1145 | MA-1145-OO-002-AV | 1000 / 0043 | Low | Watts | NF8 | 3/4 | Hand hydrant with AV located east of north end of building in grassy area adjacent to Goddard Drive |
| 1145 | MA-1145-OO-003-AV | 1000 / 0044 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located on south wall adjacent to southwest mechanical room door |
| 1145 | MA-1145-OO-001-AV | 1000 / 0042 | Low | Watts | NF8 | 3/4 | Hand hydrant with AV located east of center of building in grassy area adjacent to Goddard Drive |
| 1145 | MA-1145-OO-005-AV | 1000 / 0045 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located on center of west wall |
| 1145 | MA-1145-01-006-DC | 1000 / 0644 | Low | Ames | Maxim 200 | 4 | 4" DC on fire suppression system located in mechanical room (southwest corner). |
| 1145 | MA-1145-01-004-RP | 1000 / 0046 | High | Watts | 909 MOD QT | 3/4 | 3/4" RP on make-up water supply line to Low Temperature Heating System located in center of room |
| 1150 | MA-1150-OO-009-AV | 1000 / 0049 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located on south end of east wall |
| 1150 | MA-1150-OO-006-AV | 1000 / 0056 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located on west end of south wall adjacent to AC cooling fans |
| 1150 | MA-1150-OO-010-AV | 1000 / 0047 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located south of main entrance on east wall |
| 1150 | MA-1150-00-012-DC | 1000 / 0645 | Low | Ames | Maxim 200 | 6" | 6" DC on fire suppression system located in rear mechanical room. |
| 1150 | MA-1150-OO-008-AV | 1000 / 0050 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located on south wall in corner |
| Building Number | BPD ID Full | RWP Equipment Type / Number | Hazard Rank | Manufacturer | Model | Size | Point of Use |
| 1150 | MA-1150-OO-007-AV | 1000 / 0051 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located on south end of west wall adjacent to break area and picnic table |
| 1150 | MA-1150-OO-003-AV | 1000 / 0053 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located on north end of west wall |
| 1150 | MA-1150-OO-002-AV | 1000 / 0054 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located east of shoppette entranceon center of north wall |
| 1150 | MA-1150-OO-001-AV | 1000 / 0055 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located on east end of north wall |
| 1150 | MA-1150-OO-004-AV | 1000 / 0052 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located on south end of west wall |
| 1150 | MA-1150-OO-011-AV | 1000 / 0048 | Low | Watts | NF8 | 3/4 | Hand hydrant with AV located east of main entrance in grassy area adjacent to Goddard Drive |
| 1150 | MA-1150-01-005-RP | 1000 / 0057 | High | Watts | 009 MOD CW | 1 | 1" RP on make-up water supply lines to chiller and Low Temperature Heating System located in northwest corner |
| 1150 | MA-1150-01-001-PV | 1000 / 0597 | High | Wilkens | 720A | 2" | Irrigation system in Grassy area along Goddard Ave. |
| 1152 | MA-1152-OO-001-AV | 1000 / 0058 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located on center of west wall |
| 1152 | MA-1152-OO-002-AV | 1000 / 0059 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located on south end of east wall near mechanical room door |
| 1152 | MA-1152-01-003-RP | 1000 / 0062 | High | Watts | 009 MQT | 2 | 2" RP on main water supply line to building located approximately 12' high on the south wall |
| 1152 | MA-1152-01-004-RP | 1000 / 0060 | High | Watts | 800 M4 | 1.5 | 1.5" RP on water supply line to irrigation approximately 12' high above entrance door and ventilation ductwork |
| 1152 | MA-1152-01-005-RP | 1000 / 0061 | High | Watts | 909 QT | 3/4 | 3/4" RP on make-up water supply line to Low Temperature Heating System located on north wall |
| Building Number | BPD ID Full | RWP Equipment Type / Number | Hazard Rank | Manufacturer | Model | Size | Point of Use |
| 1154 | MA-1154-OO-003-AV | 1000 / 0064 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located on west end of north wall |
| 1154 | MA-1154-OO-002-AV | 1000 / 0065 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located on east end of north wall |
| 1154 | MA-1154-01-004-DC | 1000 / 0066 | Low | Ames | 2000 SS | 3 | 3" DC on water supply line to fire suppression system located in northeast corner of building |
| 1154 | MA-1154-01-001-RP | 1000 / 0067 | High | Watts | 909 MOD CW | 3/4 | 3/4" RP on make-up water supply line to Low Temperature Heating System located on south wall |
| 1156 | MA-1156-01-003-AV | 1000 / 0068 | Low | T&S | b969 | 3/4 | Slop sink with AV located in janitor's closet |
| 1156 | MA-1156-01-004-AV | 1000 / 0069 | Low | T&S | b969 | 3/4 | Slop sink with AV in concession storage room |
| 1156 | MA-1156-01-005-DC | 1000 / 0070 | Low | Ames | HB-0892 | 4" | DC on Fire System in Mech room, south side wall |
| 1180 | MA-1180-01-001-DC | 1000/0822 | Low | Watts | 757 | 3" | DC on water supply line located in mechanical room along west wall. |
| MA-1180-01-002-DC | 1000/0823 | Low | Ames | 2000 SS | 6" | DC on Fire System in Mech room, south side wall | |
| MA-1180-01-003-RP | 1000/0824 | High | Watts | 009 | 1/2 inch | Located on boiler makeup line in center of mechanical room. | |
| 1191 | MA-1191-OO-003-AV | 1000 / 0072 | Low | Watts | NF8 | 3/4 | Hand hydrant with AV located northwest of building on west side of parking lot |
| 1191 | MA-1191-OO-004-AV | 1000 / 0073 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV on standpipe located southeast of building, east of sidewalk, and south of display rocket |
| 1191 | MA-1191-OO-002-PV | 1000 / 0074 | High | Wilkins | 720 A | 2 | 2" PV on water supply line to irrigation located on north side of building near mechanical room |
| 1191 | MA-1191-01-001-RP | 1000 / 0075 | High | Watts | 909 MOD CW | 1 | 1" RP on make-up water supply line to Low Temperature Heating System located west of center of room |
| 1192 | MA-1192-OO-003-AV | 1000 / 0076 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located on east end of south wall |
| Building Number | BPD ID Full | RWP Equipment Type / Number | Hazard Rank | Manufacturer | Model | Size | Point of Use |
| 1192 | MA-1192-01-001-RP | 1000 / 0078 | High | Watts | 909 MOD CW | 3/4 | 3/4" RP on make-up water supply line to chiller located approximately 8' high in southeast corner on south wall |
| 1192 | MA-1192-01-002-RP | 1000 / 0079 | High | Watts | 909 MOD CW | 3/4 | 3/4" RP on make-up water supply line to Low Temperature Heating System located in middle of room |
| 1199 | MA-1199-OO-001-AV | 1000 / 0080 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located on center of north wall |
| 1199 | MA-1199-OO-004-AV | 1000 / 0081 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located on north end of west wall |
| 1199 | MA-1199-BM-002-RP | 1000 / 0082 | High | Watts | 009 M2 QT | 2 | 2" RP on water supply line to irrigation located in northeast corner |
| 1199 | MA-1199-BM-003-RP | 1000 / 0083 | High | Watts | 909 MOD CW | 3/4 | 3/4" RP on make-up water supply line to chiller located in southwest corner of room behind pumps and heat exchanger |
| 120 | MA-120-01-001-RP | 1000 / 0598 | High | Watts | 909QT RPZ | 3/4 | 3/4" RP On water supply line to boiler make-up Located in Janitors closet along East wall. |
| 1199 | MA-1199-BM-005-RP | 1000 / 0084 | High | Wilkins Zurn | 975 XL | 3/4 | 3/4" RP on make-up water supply line to Low Temperature Heating System located on west wall behind air handler |
| 1203 | MA-1203-OO-002-AV | 1000 / 0085 | Low | Watts | NF8 | 3/4 | H.H. w/ AV located at N.E. corner of restroom facility 1201 at sun plaza park |
| 1203 | MA-1202-OO-001-PV | 1000 / 0086 | High | Wilkins | 720 A | 2 | 2" PV on water supply line to irrigation located southeast of gazebo 1202 |
| 1222 | MA-1222-01-005-AV | 1000 / 0087 | Low | Watts | 288A | 3/4 | 3/4" AV on water supply line to domestic hot water heater located in northwest corner |
| 1222 | MA-1222-01-004-AV | 1000 / 0088 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located on south wall, west of entrance and adjacent to fire suppression system water supply |
| 1222 | MA-1222-01-001-DC | 1000 / 0089 | Low | Ames | 2000 SS | 4 | 4" DC on water supply line to fire suppression system located on south wall |
| Building Number | BPD ID Full | RWP Equipment Type / Number | Hazard Rank | Manufacturer | Model | Size | Point of Use |
| 1222 | MA-1222-01-003-RP | 1000 / 0090 | High | Watts | 909 | 3/4 | 3/4" RP on make-up water supply line to boiler located near west wall approximately 15' high |
| 1222 | MA-1222-01-002-RP | 1000 / 0091 | High | Watts | 909 | 2 | 2" RP on main water supply line to building located in southwest corner approximately 15' high |
| 1240 | MA-1240-OO-003-AV | 1000 / 0092 | High | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located below grade in dirt immediately northeast of main entrance |
| 1240 | MA-1240-01-001-AV | 1000 / 0093 | High | Watts | 288A | 1 | 1" AV on water supply line to irrigation located in northwest corner |
| 1240 | MA-1240-01-004-AV | 1000 / 0094 | Low | T&S | b969 | 3/4 | Slop sink with AV located in janitor's closet in southeast corner of building |
| 1240 | MA-1240-01-005-AV | 1000 / 0095 | Low | T&S | b969 | 3/4 | Slop sink with AV in men's room |
| 1240 | MA-1240-01-002-RP | 1000 / 0096 | High | Watts | 909 MOD QT | 3/4 | 3/4" RP on make-up water supply line to boiler located in northeast corner adjacent to boiler |
| 1246 | MA-1246-01-003-AV | 1000 / 0097 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located on north end of west wall |
| 1246 | MA-1246-01-004-OT | 1000 / 0098 | High | Watts | 9D | 3/4 | 3/4" BPD with atmospheric vent located on water supply line to water heater for concrete bay floors |
| 1246 | MA-1246-OO-001-PV | 1000 / 0099 | High | Watts | 800 M4FR | 1 | 1" PV on water supply line to irrigation located on north end of east wall near mechanical room door |
| 1246 | MA-1246-01-002-RP | 1000 / 0100 | High | Watts | 009 M2 QT | 2 | 2" RP on main water supply line to building located in southwest corner |
| 1248 | MA-1248-01-007-AV | 1000 / 0101 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV on roof support pole located on west end of service bay |
| 1248 | MA-1248-OO-013-AV | 1000 / 0110 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located on west end of south wall |
| Building Number | BPD ID Full | RWP Equipment Type / Number | Hazard Rank | Manufacturer | Model | Size | Point of Use |
| 1248 | MA-1248-OO-012-AV | 1000 / 0102 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located on west end of north wall |
| 1248 | MA-1248-01-014 - PV | 1000 / 762 | High | Watts | 800M4 | 1.5" | 1 1/2" PVB for irrigation located on west side of building on the exterior side of kiln room emergency exit. |
| 1248 | MA-1248-OO-002-AV | 1000 / 0103 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located on north end of east wall |
| 1248 | MA-1248-OO-001-AV | 1000 / 0104 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located on south end of east wall |
| 1248 | MA-1248-01-008-AV | 1000 / 0105 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located on east wall in southeast corner |
| 1248 | MA-1248-01-006-AV | 1000 / 0106 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV on roof support pole located on west end of service bay |
| 1248 | MA-1248-01-005-AV | 1000 / 0107 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV on roof support pole located on east end of service bay |
| 1248 | MA-1248-01-004-AV | 1000 / 0108 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV on roof support pole located on east end of service bay |
| 1248 | MA-1248-01-003-AV | 1000 / 0109 | Low | Chicago | B641 | 3/4 | Slop sink with AV in janitor's closet |
| 1248 | MA-1248-01-009-DC | 1000 / 0111 | Low | Ames | 2000 SS | 4 | 4" DC on water supply line to fire suppression system located on west wall |
| 1248 | MA-1248-01-010-RP | 1000 / 0112 | High | Febco | 825 Y | 2 | 2" RP on main water supply line to building located on west wall |
| 1248 | MA-1248-01-011-RP | 1000 / 0113 | High | Febco | 825 Y | 3/4 | 3/4" RP on make-up water supply line to Low Temperature Heating System located approximately 12' high on the northwest end of r |
| 130 | MA-130-OO-004-AV | 1000 / 0114 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located on north wall west of mechanical room door |
| Building Number | BPD ID Full | RWP Equipment Type / Number | Hazard Rank | Manufacturer | Model | Size | Point of Use |
| 130 | MA-130-01-002-AV | 1000 / 0116 | Low | T&S | b969 | 3/4 | Slop sink with AV in janitor's closet |
| 130 | MA-130-01-003-RP | 1000 / 0117 | High | Watts | 009M2QT | 1.25 | 1.25" RP on water supply line to irrigation located on west wall |
| 1320 | MA-1320-OO-004-AV | 1000 / 0131 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located on east end of south wall |
| 1320 | MA-1320-OO-012-AV | 1000 / 0119 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located on north end of east wall |
| 1320 | MA-1320-OO-011-AV | 1000 / 0120 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located on east end of north wall |
| 1320 | MA-1320-OO-010-AV | 1000 / 0121 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located on west end of north wall |
| 1320 | MA-1320-OO-009-AV | 1000 / 0122 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located on north end of west wall, north of cardboard compactor |
| 1320 | MA-1320-01-026-DC | 1000 / 0646 | Low | Ames | Maxim 200 | 8 | 8" DC on fire suppression system located in rear of warehouse near loading docks. |
| 1320 | MA-1320-OO-008-AV | 1000 / 0123 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located on center of west wall, north of electrical mechanical room |
| 1320 | MA-1320-OO-007-AV | 1000 / 0124 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located on south end of west wall between loading dock bay doors |
| 1320 | MA-1320-OO-005-AV | 1000 / 0125 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located on west end of south wall |
| 1320 | MA-1320-OO-003-AV | 1000 / 0126 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located on south end of east wall |
| 1320 | MA-1320-OO-002-AV | 1000 / 0118 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located on center of east wall, south of building exit |
| Building Number | BPD ID Full | RWP Equipment Type / Number | Hazard Rank | Manufacturer | Model | Size | Point of Use |
| 1320 | MA-1320-OO-001-AV | 1000 / 0127 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located on center of east wall, north of building exit |
| 1320 | MA-1320-01-015-AV | 1000 / 0132 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located on south wall near steel sink |
| 1320 | MA-1320-01-014-AV | 1000 / 0140 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located on west wall of women's room |
| 1320 | MA-1320-01-024-AV | 1000 / 0128 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located on south wall in men's room near break room |
| 1320 | MA-1320-01-016-AV | 1000 / 0129 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located on north wall near steel sink |
| 1320 | MA-1320-01-017-AV | 1000 / 0134 | Low | Watts | 288A | 1/2 | 1/2" AV on water line located in southwest corner |
| 1320 | MA-1320-01-018-AV | 1000 / 0135 | Low | Nidel | 34 hd | 3/4 | Hose bibb with AV in restroom located between the meat and produce departments |
| 1320 | MA-1320-01-019-AV | 1000 / 0136 | Low | Nidel | 34 hd | 3/4 | Hose bibb with AV (hot and cold water) located north end of east wall |
| 1320 | MA-1320-01-021-AV | 1000 / 0138 | Low | Chicago | B641 | 3/4 | Slop sink with AV in janitor's closet located on northwest end of warehouse |
| 1320 | MA-1320-01-022-AV | 1000 / 0139 | Low | Chicago | B641 | 3/4 | Slop sink with AV in janitor's closet located east of warehouse |
| 1320 | MA-1320-01-023-AV | 1000 / 0133 | Low | Nidel | 34 hd | 3/4 | Hose bibb with AV located on north wall under sinks in women's room near break room |
| 1320 | MA-1320-01-020-AV | 1000 / 0137 | Low | Nidel | 34 hd | 3/4 | Hose bibb with AV attached to double basin steel sink |
| 1320 | MA-1320-01-013-AV | 1000 / 0130 | Low | Nidel | 34 hd | 3/4 | Hose bibb with AV located on north wall of men's room |
| Building Number | BPD ID Full | RWP Equipment Type / Number | Hazard Rank | Manufacturer | Model | Size | Point of Use |
| 1320 | MA-1320-OO-006-RP | 1000 / 0141 | High | Watts | 909 M1 QT | 2 | 2" RP on water supply line to irrigation located in grassy area southwest of building |
| 1439 | MA-1439-01-014-AV | 1000 / 0145 | Low | T&S | b969 | 3/4 | Slop sink with AV located in janitor's closet in southwest corner of building |
| 1439 | MA-1439-01-010-AV | 1000 / 0149 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located on center of north wall of southeast bay |
| 1439 | MA-1439-01-009-AV | 1000 / 0153 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located near eyewash station |
| 1439 | MA-1439-01-008-AV | 1000 / 0143 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located on south end of west wall |
| 1439 | MA-1439-01-007-AV | 1000 / 0144 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located on west wall near slop sink |
| 1439 | MA-1439-01-006-AV | 1000 / 0150 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located on south wall |
| 1439 | MA-1439-01-005-AV | 1000 / 0151 | Low | T&S | b969 | 3/4 | Slop sink with AV |
| 1439 | MA-1439-01-013-AV | 1000 / 0146 | Low | T&S | b969 | 3/4 | Hose bibb with AV located on south end of east wall |
| 1439 | MA-1439-01-004-AV | 1000 / 0152 | Low | T&S | b969 | 3/4 | Slop sink with AV |
| 1439 | MA-1439-01-011-AV | 1000 / 0148 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located on center of south wall of southeast bay |
| 1439 | MA-1439-01-012-AV | 1000 / 0147 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located on north end of east wall |
| 1439 | MA-1439-01-003-DC | 1000 / 0154 | Low | Hersey | No. 2 | 8 | 8" DC on water supply line to fire suppression system located on north end of west wall |
| Building Number | BPD ID Full | RWP Equipment Type / Number | Hazard Rank | Manufacturer | Model | Size | Point of Use |
| 1439 | MA-1439-01-002-PV | 1000 / 0155 | Low | Watts | 800M4 | 2 | 2" PV on water supply line to hot potable water system located in southeast corner |
| 1439 | MA-1439-01-001-RP | 1000 / 0156 | High | Watts | 909 MOD CW | 3/4 | 3/4" RP on make-up water supply line to Low Temperature Heating System located on center of east wall |
| 1440 | MA-1440-01-012-AV | 1000 / 0176 | Low | Watts | 388a | 2 | 2" AV on 2" potable cold hose bib located on center of east wall approximately 15' high |
| 1440 | MA-1440-01-026-AV | 1000 / 0157 | Low | T&S | b969 | 3/4 | Slop sink with AV located on west wall |
| 1440 | MA-1440-01-025-AV | 1000 / 0164 | Low | Nidel | 34 hd | 3/4 | Hose bibb with AV located on center of west wall |
| 1440 | MA-1440-01-024-AV | 1000 / 0166 | Low | Nidel | 34 hd | 3/4 | Hose bibb with AV located on north end of west wall |
| 1440 | MA-1440-01-023-AV | 1000 / 0162 | Low | Nidel | 34 hd | 3/4 | Hose bibb with AV located on north end of east wall |
| 1440 | MA-1440-01-022-AV | 1000 / 0161 | Low | Nidel | 34 hd | 3/4 | Hose bibb with AV located on center of east wall |
| 1440 | MA-1440-01-020-AV | 1000 / 0160 | Low | Nidel | 34 hd | 3/4 | Hose bibb with AV located near main water supply on south wall |
| 1440 | MA-1440-OO-001-AV | 1000 / 0159 | Low | Nidel | 34 hd | 3/4 | Hose bibb with AV located on north end of west wall |
| 1440 | MA-1440-OO-021-AV | 1000 / 0158 | Low | Nidel | 34 hd | 3/4 | Hose bibb with AV located on east wall |
| 1440 | MA-1440-01-013-AV | 1000 / 0163 | Low | Watts | 388a | 2 | 2" AV on 2" potable hot hose bib located on center of east wall approximately 15' high |
| 1440 | MA-1440-01-011-AV | 1000 / 0167 | Low | Watts | 388a | 2 | 2" AV on 2" potable hot hose bib located on north end of east wall approximately 15' high |
| Building Number | BPD ID Full | RWP Equipment Type / Number | Hazard Rank | Manufacturer | Model | Size | Point of Use |
| 1440 | MA-1440-01-010-AV | 1000 / 0165 | Low | Watts | 388a | 2 | 2" AV on 2" potable cold hose bib located on north end of east wall approximately 15' high |
| 1440 | MA-1440-01-009-AV | 1000 / 0169 | Low | Watts | 388a | 2 | 2" AV on 2" potable hot hose bib located on north of west wall approximately 15' high |
| 1440 | MA-1440-01-008-AV | 1000 / 0170 | Low | Watts | 388a | 2 | 2" AV on 2" potable cold hose bib located on north end of west wall approximately 15' high |
| 1440 | MA-1440-01-007-AV | 1000 / 0171 | Low | Watts | 388a | 2 | 2" AV on 2" potable hot hose bib located on center of west wall approximately 15' high |
| 1440 | MA-1440-01-006-AV | 1000 / 0172 | Low | Watts | 388a | 2 | 2" AV on 2" potable cold hose bib located on center of west wall approximately 15' high |
| 1440 | MA-1440-01-005-AV | 1000 / 0173 | Low | Nidel | 34 hd | 3/4 | Hose bibb with AV located on center of east wall |
| 1440 | MA-1440-01-003-AV | 1000 / 0174 | Low | Nidel | 34 hd | 3/4 | Hose bibb with AV located on west wall |
| 1440 | MA-1440-01-002-AV | 1000 / 0175 | Low | Nidel | 34 hd | 3/4 | Hose bibb with AV located on west end of south wall |
| 1440 | MA-1440-01-015-AV | 1000 / 0168 | Low | T&S | b969 | 3/4 | Slop sink with AV in janitor's closet located on east wall of west bay |
| 1440 | MA-1440-01-019-PV | 1000 / 0177 | Low | Watts | 800 M4 QT | 2 | 2" PV on potable hot water supply line located above water heater (heat exchanger) where potable hot exits |
| 1440 | MA-1440-02-014-RP | 1000 / 0178 | High | Watts | 909 MOD CW | 3/4 | 3/4" RP on make-up water supply line to Low Temperature Heating System located on second floor mezzanine mechanical area |
| 1440 | MA-1440-02-027-RP | 1000 / 0179 | High | Watts | 909 MOD | 3/4 | 3/4" RP on make-up water supply line to Low Temperature Heating System located on second floor mezzanine mechanical area |
| Building Number | BPD ID Full | RWP Equipment Type / Number | Hazard Rank | Manufacturer | Model | Size | Point of Use |
| 1440 | MA-1440-02-004-RP | 1000 / 0180 | High | Watts | 909 MOD CW | 3/4 | 3/4" RP on make-up water to Low Temperature Heating System located on east wall of second floor mezzanine mechanical area |
| 1440 | MA-1440-01-017-RP | 1000 / 0183 | High | Watts | 909 MOD QT | 2.5 | 2.5" RP on water supply line to potable hot water system located approximately 15' high in center of room |
| 1440 | MA-1440-01-016-RP | 1000 / 0182 | High | Watts | 909 MOD CW | 3/4 | 3/4" RP on make-up water supply line to Low Temperature Heating System located in southeast corner of room |
| 1440 | MA-1440-01-018-RP | 1000 / 0181 | High | Watts | 909 | 3/4 | 3/4" RP on make-up water supply line to Low Temperature Heating System located center of east end of room |
| 1441 | MA-1441-01-001-DC | 1000 / 0182 | Low | AMES | 2000SS | 6" | 6" AMES DC for Fire Suppression System |
| 1441 | MA-1441-01-002-DC | 1000 / 798 | Low | Watts | 007M | 3/4" | 3/4" DC on bypass line of Fire Suppression System |
| 1441 | MA-1441-01-003-DC | 1000 / 799 | Low | Watts | 709 | 2" | 2" DC located on main water feed to facility. |
| 1447 | MA-1447-OO-002-AV | 1000 / 0187 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located on north end of west wall |
| 1447 | MA-1447-OO-001-AV | 1000 / 0184 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located on south end of west wall |
| 1447 | MA-1447-01-003-AV | 1000 / 0185 | Low | Arrowhead | No.58 ABP | 3/4 | Slop sink with AV located in janitor's closet off break room |
| 1447 | MA-1447-01-004-AV | 1000 / 0186 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV under steel sink located on north wall |
| 1447 | MA-1447-01-005-DC | 1000 / 0188 | Low | Ames | 2000 SS | 6 | 6" DC on water supply line to fire suppression system located on east wall |
| 1447 | MA-1447-01-006-RP | 1000 / 0189 | High | Watts | 9 | 3/4 | 3/4" RP on make-up water supply line to Low Temperature Heating System located on east wall |
| 1447 | MA-1447-01-007-RP | 1000 / 0190 | High | Watts | 909 MOD CW | 1 | 1" RP on make-up water supply line to steam boiler located in west area of mechanical room |
| 1448 | MA-1448-01-001-AV | 1000 / 0191 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located on center of east wall |
| Building Number | BPD ID Full | RWP Equipment Type / Number | Hazard Rank | Manufacturer | Model | Size | Point of Use |
| 1448 | MA-1448-01-004-DC | 1000 / 0647 | Low | Ames | Maxim 200 | 6" | 6" DC on fire suppression system located next to north walk-in entrance. |
| 1448 | MA-1448-01-002-RP | 1000 / 0192 | High | Watts | 909 MOD QT | 3/4 | 3/4" RP on make-up water supply line to Low Temperature Heating System located in center of room adjacent to heat exchanger |
| 1448 | MA-1448-01-003-RP | 1000 / 0193 | High | Watts | 009 RP | 1 | 1" RP on main water supply line to washrack located approximately 12' high on center of south wall |
| 145 | MA-145-01-004-RP | 1000 / 763 | High | Watts | 009 RP | 3 | 3" RP Located in center of mechanical room on main water supply line for entire facility. |
| 145 | MA-145-01-003-RP | 1000 / 764 | High | Watts | 909M2QT | 2 | 2" RP for irrigation system. Located in center of mechanical room on Goddard side of building. |
| 145 | MA-145-01-002-AG | 1000 / 0194 | High | Potable water feed to chemical tank. | |||
| 145 | MA-145-01-001-RP | 1000 / 0195 | High | Watts | 909 | 3/4 | 3/4" RP on make up water supply line to Low Temperature Heating System |
| 1450 | MA-1450-01-011-AV | 1000 / 0198 | Low | Watts | 388a | 2 | 2" AV on 2" potable cold hose bib located on center of east wall approximately 15' high |
| 1450 | MA-1450-01-016-AV | 1000 / 0197 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV on main water supply located on east end of south wall |
| 1450 | MA-1450-01-012-AV | 1000 / 0204 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located on west wall |
| 1450 | MA-1450-01-010-AV | 1000 / 0196 | Low | Watts | 388a | 2 | 2" AV on 2" potable hot hose bib located on center of east wall approximately 15' high |
| 1450 | MA-1450-01-009-AV | 1000 / 0199 | Low | Watts | 388a | 2 | 2" AV on 2" potable cold hose bib located in southeast corner approximately 15' high |
| 1450 | MA-1450-01-002-AV | 1000 / 0206 | Low | Watts | 388a | 2 | 2" AV on 2" potable cold hose bib located on center of west wall approximately 15' high |
| 1450 | MA-1450-01-001-AV | 1000 / 0201 | Low | chicago | b641 | 3/4 | Slop sink with AV located in janitor's closet |
| 1450 | MA-1450-01-008-AV | 1000 / 0200 | Low | Watts | 388a | 2 | 2" AV on 2" potable hot hose bib located in southeast corner approximately 15' high |
| Building Number | BPD ID Full | RWP Equipment Type / Number | Hazard Rank | Manufacturer | Model | Size | Point of Use |
| 1450 | MA-1450-01-003-AV | 1000 / 0205 | Low | Watts | 388a | 2 | 2" AV on 2" potable hot hose bib located on center of west wall approximately 15' high |
| 1450 | MA-1450-01-004-AV | 1000 / 0203 | Low | Chicago | b641 | 3/4 | Slop sink with AV located on west side of main bay inside small building |
| 1450 | MA-1450-01-006-AV | 1000 / 0207 | Low | Watts | 388a | 2 | 2" AV on 2" potable cold hose bib located on southwest end approximately 15' high |
| 1450 | MA-1450-01-005-AV | 1000 / 0202 | Low | Watts | 388a | 2 | 2" AV on 2" potable hot hose bib located on southwest end approximately 15' high |
| 1450 | MA-1450-01-015-PV | 1000 / 0208 | Low | Watts | 800 M4 QT | 2 | 2" PV on water supply line to potable hot water heater located on west side of heater |
| 1450 | MA-1450-01-014-RP | 1000 / 0211 | High | Watts | MOD QT RPZ | 3/4 | 3/4" RP on make-up water supply line to GHS/GHR system located west end of north wall |
| 1450 | MA-1450-01-007-RP | 1000 / 0209 | High | Watts | 909 MOD QT | 3/4 | 3/4" RP on water supply line to aqueous parts washer located in southeast corner |
| 1450 | MA-1450-01-013-RP | 1000 / 0210 | High | Watts | 909 MOD CW | 1 | 1" RP on make-up water supply line to Low Temperature Heating System located on south end of east wall |
| 1459 | MA-1459-01-001-AV | 1000 / 0212 | Low | Nidel | 34 HD | 3/4 | Hose bibb with AV on main water supply located in northwest corner |
| 1459 | MA-1459-OO-002-RP | 1000 / 0214 | Low | Watts | 909 M1 | 10 | 10" RP on main water supply line to fire pump house located northwest of building. 1 of 2 devices in parallel, west device |
| 1459 | MA-1459-OO-003-RP | 1000 / 0213 | Low | Watts | 909 M1 | 10 | 10" RP on main water supply line to fire pump house located northwest of building. 1 of 2 devices in parallel, east device |
| 1460 | MA-1460-01-002-AV | 1000 / 0216 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located at end of hallway, west of center of main bay |
| 1460 | MA-1460-01-003-AV | 1000 / 0217 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located in middle of bay and east of center |
| Building Number | BPD ID Full | RWP Equipment Type / Number | Hazard Rank | Manufacturer | Model | Size | Point of Use |
| 1460 | MA-1460-01-004-AV | 1000 / 0218 | Low | T&S | b969 | 3/4 | Slop sink with AV in janitor's closet located east of center of bay |
| 1460 | MA-1460-01-006-AV | 1000 / 0219 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV on water supply line to domestic hot water heater located on south end of room |
| 1460 | MA-1460-01-001-AV | 1000 / 0215 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located on center of west wall near entrance |
| 1460 | MA-1460-01-008-DC | 1000 / 0220 | High | Hersey | No. 2 | 8 | 8" DC on water supply line to AFFF fire suppression system located on east wall |
| 1460 | MA-1460-01-009-OT | 1000 / 0599 | High | Watts | 9D | 3/4 | 3/4" BPD with atmospheric vent on make-up water supply line to Low Temperature Heating System located approximately 15' high in |
| 1460 | MA-1460-01-007-OT | 1000 / 0222 | Low | Watts | 9D | 3/4 | 3/4" BPD with atmospheric vent on water supply line to humidifier located near ceiling above south end of boiler |
| 1460 | MA-1460-01-010-OT | 1000 / 0221 | Low | Watts | 9D | 3/4 | 3/4" BPD with atmospheric vent on water supply line to humidifier located approximately 15' high in southwest corner |
| 1460 | MA-1460-01-005-RP | 1000 / 0224 | High | Watts | 909 MOD CW | 1 | 1" RP on make-up water supply line to steam boiler and condensate return located in center of room adjacent to boiler |
| 1463 | MA-1463-01-002-AV | 1000 / 0225 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located on center of west wall |
| 1463 | MA-1463-01-001-RP | 1000 / 0226 | High | Watts | 909 MOD | 3 | 3" RP on main water supply line to building located on south end of west wall |
| 1464 | MA-1464-01-001-AV | 1000 / 0227 | Low | nidel | 34 hd | 3/4 | Hose bibb with AV located in northwest corner |
| 1464 | MA-1464-01-002-AV | 1000 / 0228 | Low | chicago | b641 | 3/4 | Slop sink with AV in janitor's closet |
| 1464 | MA-1464-01-006-AV | 1000 / 0229 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located on west end of south wall |
| Building Number | BPD ID Full | RWP Equipment Type / Number | Hazard Rank | Manufacturer | Model | Size | Point of Use |
| 1464 | MA-1464-02-005-AV | 1000 / 0230 | Low | Watts | 344 a | 1.5 | 1.5" AV on water supply line to hot potable water heater located approximately 15' high on west wall |
| 1464 | MA-1464-02-003-RP | 1000 / 0231 | High | Watts | 909 | 3/4 | 3/4" RP on make-up water supply line to Low Temperature Heating System located on east wall (north RP) |
| 1464 | MA-1464-02-004-RP | 1000 / 0232 | High | Watts | Illegible | 3/4 | 3/4" RP on make-up water supply line to the GHS/GHR heating system located on east wall (south RP) |
| 1465 | MA-1465-OO-001-AV | 1000 / 0236 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located on west end of north wall |
| 1465 | MA-1465-OO-002-AV | 1000 / 0235 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located on east end of north wall |
| 1465 | MA-1465-OO-003-AV | 1000 / 0234 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located on center of south wall |
| 1465 | MA-1465-01-005-AV | 1000 / 0237 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located on center of east wall |
| 1465 | MA-1465-01-004-AV | 1000 / 0233 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located on east end of north wall |
| 1465 | MA-1465-01-006-AV | 1000 / 0238 | Low | chicago | B641 | 3/4 | Slop sink with AV in janitor's closet |
| 1465 | MA-1465-01-007-DC | 1000 / 0239 | Low | Ames | 2000 SS | 4 | 4" DC on water supply line to fire suppression system located on south wall |
| 1466 | MA-1466-OO-001-AV | 1000 / 0240 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located on east end of north wall |
| 1466 | MA-1466-OO-002-AV | 1000 / 0243 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located on center of east wall |
| 1466 | MA-1466-01-003-AV | 1000 / 0241 | Low | chicago | B641 | 3/4 | Slop sink with AV located in southeast corner |
| Building Number | BPD ID Full | RWP Equipment Type / Number | Hazard Rank | Manufacturer | Model | Size | Point of Use |
| 1466 | MA-1466-OO-007-AV | 1000 / 0242 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located on west end of south wall |
| 1466 | MA-1466-01-004-DC | 1000 / 0244 | Low | Ames | 2000 SS | 4 | 4" DC on water supply line to fire suppression system located in southwest corner |
| 1466 | MA-1466-01-005-PV | 1000 / 0245 | High | Watts | 800M4 | 1.5 | 1.5" PV on water supply line to irrigation located approximately 15' high on east wall above domestic hot water heater |
| 1466 | MA-1466-01-006-RP | 1000 / 0246 | High | Watts | 909 MOD CW | 1 | 1" RP on make-up water supply line to Low Temperature Heating System located approximately 10' high on east wall |
| 1467 | MA-1467-01-001-RP | 1000 / 0247 | Low | Ames | 4000 SS | 4 | 4" RP on water supply line to fire suppression system located in northwest corner |
| 1467 | MA-1467-01-002-RP | 1000 / 0248 | High | Watts | 909 MOD CW | 2 | 2" RP on main water supply line to washrack located approximately 10' high on the west end |
| 1469 | MA-1469-01-003-AV | 1000 / 0252 | Low | T&S | B969 | 3/4 | Slop sink with AV located in locker room |
| 1469 | MA-1469-01-004-AV | 1000 / 0251 | Low | T&S | B969 | 3/4 | Slop sink with AV located in janitor's closet |
| 1469 | MA-1469-OO-002-AV | 1000 / 0249 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located on west wall |
| 1469 | MA-1469-OO-005-AV | 1000 / 0250 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located on east wall |
| 1469 | MA-1469-OO-001-PV | 1000 / 0253 | High | Wilkins | 720 A | 1 | 1" PV on water supply line to irrigation located on northwest corner |
| 1469 | MA-1469-01-006-RP | 1000 / 0254 | High | Watts | 909 MOD CW | 3/4 | 3/4" RP on make-up water supply line Low Temperature Heating System located in northwest corner |
| 1482 | MA-1482-01-001-RP | 1000 / 0255 | High | Watts | 909 MOD QT | 3/4 | 3/4" RP on make-up water supply line to Low Temperature Heating System located approximately 10' high on west end |
| Building Number | BPD ID Full | RWP Equipment Type / Number | Hazard Rank | Manufacturer | Model | Size | Point of Use |
| 152 | MA-152-OO-001-AV | 1000 / 0256 | Low | Watts | NF 8 | 3/4 | Hand hydrant with AV located southeast of building |
| 1535 | MA-1535-01-001-DC | 1000 / 0257 | Low | Ames | 2000 SS | 6 | 6" DC on water supply line to fire suppression system located on east side of building |
| 1590 | MA-1590-OO-001-PV | 1000 / 0258 | High | Watts | 800 M4 | 1.5 | 1.5" PV on water supply line to irrigation located at the T intersection of Aspen and Cedar |
| 160 | MA-160-OO-004-AV | 1000 / 0259 | Low | Watts | NF 8 | 3/4 | Hand hydrant with AV located south of building in center of lawn |
| 160 | MA-160-OO-001-AV | 1000 / 0260 | Low | Watts | NF 8 | 3/4 | Hand hydrant with AV located north of building in grassy area |
| 160 | MA-160-01-002-RP | 1000 / 0261 | High | Watts | 909 QT | 3/4 | 3/4" RP on make-up water to boiler and Low Temperature Heating System located in center of room just above boiler |
| 160 | MA-160-01-003-RP | 1000 / 0262 | High | Watts | 909MODCW | 3/4 | 3/4" RP on make-up water to Low Temperature Heating System located on north side of room and east of heat exchanger |
| 1600 | MA-1600-01-006-AV | 1000 / 0266 | Low | Watts | 388A | 3/4 | 3/4" AV on water supply line to dishwasher located on top of machine on north wall |
| 1600 | MA-1600-01-005-AV | 1000 / 0265 | Low | Watts | 288A | 1/2 | 1/2" AV on water supply line to dishwasher machine located on top of machine on north wall |
| 1600 | MA-1600-OO-002-AV | 1000 / 0267 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located on south end of east wall |
| 1600 | MA-1600-01-004-AV | 1000 / 0264 | Low | Watts | 188A | 1/4 | 1/4" AV on water supply line to soap dispenser located on dishwasher on east end of north wall |
| 1600 | MA-1600-01-003-AV | 1000 / 0263 | Low | chicago | B641 | 3/4 | Slop sink with AV |
| 1600 | MA-1600-BM-001-RP | 1000 / 0268 | High | Watts | 909 MOD QT | 3/4 | 3/4" RP on make-up water supply line to Low Temperature Heating System located in center of room on west end |
| Building Number | BPD ID Full | RWP Equipment Type / Number | Hazard Rank | Manufacturer | Model | Size | Point of Use |
| 1620 | MA-1620-OO-001-AV | 1000 / 0273 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located on west end of north wall |
| 1620 | MA-1620-OO-007-AV | 1000 / 0272 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located on west end of south wall |
| 1620 | MA-1620-OO-008-AV | 1000 / 0271 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located on east end of south wall |
| 1620 | MA-1620-OO-002-AV | 1000 / 0274 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located on east end of north wall |
| 1620 | MA-1620-02-004-AV | 1000 / 0269 | Low | chicago | B641 | 3/4 | Slop sink with AV located in janitor's closet |
| 1620 | MA-1620-01-003-AV | 1000 / 0270 | Low | chicago | b641 | 3/4 | Slop sink with AV located in janitor's closet |
| 1620 | MA-1620-BM-006-RP | 1000 / 0276 | High | Watts | 909QT | 3/4 | 3/4" RP on make-up water supply line to Low Temperature Heating System located in center of room |
| 1620 | MA-1620-BM-005-RP | 1000 / 0275 | High | Wilkins Zurn | 975 XL | 1.5 | 1.5" RP on water supply line to irrigation located in southeast corner |
| 165 | MA-165-OO-004-AV | 1000 / 0279 | Low | Watts | NF 8 | 3/4 | Hand hydrant located north of building in grassy area |
| 165 | MA-165-01-001-AV | 1000 / 0278 | Low | Arrowhead | |||
| No.58 ABP | 3/4 | Hose bibb with AV located on north end of west wall | |||||
| 165 | MA-165-01-003-AV | 1000 / 0277 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located on north end of east wall |
| 165 | MA-165-01-006-OT | 1000 / 0280 | High | Watts | 9D | 3/4 | 3/4" non-testable DC on water supply line to chemical feed tank located on north end of east wall |
| 165 | MA-165-01-002-OT | 1000 / 0281 | High | Watts | No. 7 702-2 | 3/4 | 3/4" non-testable DC on water supply to hose bibb used to make-up water to chiller |
| Building Number | BPD ID Full | RWP Equipment Type / Number | Hazard Rank | Manufacturer | Model | Size | Point of Use |
| 165 | MA-165-01-005-RP | 1000 / 0282 | High | Watts | 909 MOD QT | 3/4 | 3/4" RP on make-up water supply line to boiler located on east end of north wall |
| 1680 | MA-1680-OO-002-AV | 1000 / 0284 | Low | Zurn | Z-1321 | 3/4 | Hose bibb with AV located on center of east wall |
| 1680 | MA-1680-OO-003-AV | 1000 / 0285 | Low | Zurn | Z-1321 | 3/4 | Hose bibb with AV located on west wall |
| 1680 | MA-1680-OO-004-AV | 1000 / 0286 | Low | Zurn | Z-1321 | 3/4 | Hose bibb with AV located on north wall |
| 1680 | MA-1680-BM-005-DC | 1000 / 0648 | Low | Ames | Maxim 200 | 4 | 4" DC on fire suppression system located in lower mechanical room on south side of building. |
| 1680 | MA-1680-OO-001-AV | 1000 / 0283 | Low | Zurn | Z-1321 | 3/4 | Hose bibb with AV located on center of south wall |
| 1681 | MA-1681-OO-005-AV | 1000 / 0289 | Low | Zurn | Z-1321 | 3/4 | Hose bibb with AV located on center of south wall |
| 1681 | MA-1681-01-002-AV | 1000 / 0287 | Low | chicago | B969 | 3/4 | Slop sink with AV |
| 1681 | MA-1681-OO-003-AV | 1000 / 0291 | Low | Zurn | Z-1321 | 3/4 | Hose bibb with AV located on center of north wall |
| 1681 | MA-1681-OO-006-AV | 1000 / 0288 | Low | Zurn | Z-1321 | 3/4 | Hose bibb with AV located on center of west wall |
| 1681 | MA-1681-OO-004-AV | 1000 / 0290 | Low | Zurn | Z-1321 | 3/4 | Hose bibb with AV located on center of east wall |
| 1681 | MA-1681-01-007-RP | 1000 / 0293 | High | Wilkins Zurn | 975 XL | 2 | 2" RP on water supply line to irrigation located on east wall |
| 1681 | MA-1681-01-001-RP | 1000 / 0292 | Low | Febco | 825 Y | 1.5 | 1.5" RP on water supply line to fire suppression system located on north end of building |
| Building Number | BPD ID Full | RWP Equipment Type / Number | Hazard Rank | Manufacturer | Model | Size | Point of Use |
| 1682 | MA-1682-01-002-AV | 1000 / 0295 | Low | T&S | B969 | 3/4 | Slop sink with AV |
| 1682 | MA-1682-OO-003-AV | 1000 / 0296 | Low | Zurn | Z-1321 | 3/4 | Hose bibb with AV located on center of east wall |
| 1682 | MA-1682-OO-004-AV | 1000 / 0298 | Low | Zurn | Z-1321 | 3/4 | Hose bibb with AV located on center of south wall |
| 1682 | MA-1682-OO-005-AV | 1000 / 0297 | Low | Zurn | Z-1321 | 3/4 | Hose bibb with AV located on center of west wall |
| 1682 | MA-1682-OO-006-AV | 1000 / 0294 | Low | Zurn | Z-1321 | 3/4 | Hose bibb with AV located on center of north wall |
| 1682 | MA-1682-01-001-RP | 1000 / 0299 | Low | Febco | 825 Y | 1.25 | 1.25" RP on water supply line to fire suppression system located on east end of building |
| 1683 | MA-1683-01-002-AV | 1000 / 0304 | Low | T&S | B969 | 3/4 | Slop sink with AV |
| 1683 | MA-1683-OO-006-AV | 1000 / 0301 | Low | Zurn | Z-1321 | 3/4 | Hose bibb with AV located on center of west wall |
| 1683 | MA-1683-OO-005-AV | 1000 / 0300 | Low | Zurn | Z-1321 | 3/4 | Hose bibb with AV located on center of south wall |
| 1683 | MA-1683-OO-003-AV | 1000 / 0303 | Low | Zurn | Z-1321 | 3/4 | Hose bibb with AV located on center of north wall |
| 1683 | MA-1683-OO-004-AV | 1000 / 0302 | Low | Zurn | Z-1321 | 3/4 | Hose bibb with AV located on center of east wall |
| 1683 | MA-1683-01-001-RP | 1000 / 0306 | Low | Febco | 825 Y | 1.25 | 1.25" RP on water supply line to fire suppression system located on north end of building |
| 1683 | MA-1683-01-007-RP | 1000 / 0305 | High | Wilkins Zurn | 975 XL | 2 | 2" RP on water supply line to irrigation located on east wall (IRRIGATION) |
| Building Number | BPD ID Full | RWP Equipment Type / Number | Hazard Rank | Manufacturer | Model | Size | Point of Use |
| 1684 | MA-1684-OO-001-AV | 1000 / 0308 | Low | Zurn | Z-1321 | 3/4 | Hose bibb with AV located on south wall |
| 1684 | MA-1684-01-003-AV | 1000 / 0307 | Low | T&S | 3/4 | Slop sink with AV in janitor's closet | |
| 1684 | MA-1684-01-002-RP | 1000 / 0310 | Low | Ames | 2000 SS | 3 | 3" RP on water supply line to fire suppression system located near east wall |
| 1684 | MA-1684-01-004-RP | 1000 / 0309 | High | Watts | 909 M1 QT | 2 | 2" RP on main water supply line to the building located in northeast corner |
| 1702 | MA-1702-01-001-AV | 1000 / 0313 | Low | T&S | B969 | 1/2 | Slop sink with AV in janitor's closet |
| 1705 | MA-1705-01-001-RP | 1000 / 0315 | High | Watts | 909 MOD QT | 3/4 | 3/4" RP on make-up water supply line to boiler located in northeast corner |
| 1708 | MA-1708-01-001-RP | 1000 / 603 | HIGH | Watts | 909 MOD CW | 3/4 | 3/4" RP on make up water supply line to low temp heating system--- located west of heat exchanger in center of room. |
| 1835 | MA-1835-01-001-RP | 1000 / 605 | HIGH | Wilkens Zurn | 975 xl | 3/4 | Upper Device --- 3/4" RP on water supply line to heating system --- Located along West wall in Mechanical room next to water heater. |
| 1835 | MA-1835-01-002-RP | 1000 / 606 | HIGH | Wilkens Zurn | 975 xl | 3/4 | Lower Device --- 3/4" RP on water supply line to heating system --- Located along west wall in mechanical room next to water heater. |
| 1840 | MA-1840-01-001-RP | 1000 / 0316 | HIGH | Watts | 909 MODQT | 2 | 2" RP on make-up water supply line to low temp heating system --- Located in #2 Equip Room along east wall next to transformer. |
| 1840 | MA-1840-01-002-RP | 1000 / 607 | HIGH | Watts | 909 MODQT | 3/4 | 3/4" RP on make-up water supply line --- Located above boiler in center of Equipment Room #3. |
| 1844 | MA-1844-01-001-DC | 1000 / 0781 | High | Watts | 007M1QT | 1" | 1" DC located on North Wall of Mechanical Room |
| 1845 | MA-1845-01-001-RP | 1000 / 0782 | Low | Watts | 909 MODQT | 2" | 2" RP Located on fire system line in fire mechainical room on east wall. |
| Building Number | BPD ID Full | RWP Equipment Type / Number | Hazard Rank | Manufacturer | Model | Size | Point of Use |
| 1867 | MA-1867-01-001-RP | 1000 / 608 | HIGH | Watts | 909 MODQT | 3/4 | REMOVED |
| 1869 | MA-1869-01-001-RP | 1000 / 0317 | High | Watts | 909 MODQT | 3/4 | 3/4" RP on water supply line to heating system --- Located on North wall in Mechanical room. |
| 1879 | MA-1879-01-001-RP | 1000 / 0318 | High | Watts | 909 MOD QT | 3/4 | 3/4" RP on make-up water supply line to boiler located in southwest corner |
| 1890 | MA-1890-01-001-DC | 1000/0783 | LOW | AMES | 2000 SS | 8" | 8" Double check on Fire Suppression System located in fire protection room in nw corner of bldg. |
| 192 | MA-192-01-001-AV | 1000 / 0319 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located in southwest corner |
| 192 | MA-192-01-002-AV | 1000 / 0320 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located on west wall |
| 192 | MA-192-OO-003-AV | 1000 / 0321 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located on west wall |
| 192 | MA-192-OO-004-PV | 1000 / 0322 | High | Wilkins | 720A | 1.5 | 1.5" PV on water supply line to irrigation located on west end of south wall |
| 1996 | MA-1996-BM-001-RP | 1000 / 0323 | High | Watts | 909 MOD CW | 3/4 | 3/4" RP on main water supply line to building located on south end of west wall |
| 200 | MA-200-01-001-AV | 1000 / 0324 | Low | Arrowhead | No.58 ABP | 3/4 | Hose bibb with AV located on east wall just north of battery shops |
| Building Number | BPD ID Full | RWP Equipment Type / Number | Hazard Rank | Manufacturer | Model | Size | Point of Use |
| 219 | MA-219-01-006-AV | 1000 / 0354 | Low | chicago | B641 | 3/4 | Slop sink with AV located on east wall |
| 219 | MA-219-01-007-AV | 1000 / 0355 | Low | Watts | |||
| 288a | 3/4 | Hose reel with AV located on east wall | |||||
| 219 | MA-219-01-005-AV | 1000 / 0353 | Low | Watts | 288a | 3/4 | Hose reel with AV located on west wall |
| 219 | MA-219-01-004-AV | 1000 / 0356 | Low | Watts | 288a | 3/4 | Hose reel with AV located on east wall |
| 219 | MA-219-01-003-AV | 1000 / 0352 | Low | chicago | b641 | 3/4 | Slop sink with AV located in janitor's closet |
| 219 | MA-219-01-002-RP | 1000 / 0358 | Low | Hersey | 6C-M | 6 | Removed under Project Nzas-200007. (April, 2005) |
| 219 | MA-219-01-008-RP | 1000 / 800 | High | Wilkens / Zurn | 975 XL | 1" | 1" RP located next to W/H on mezzinine in mechanical room. |
| 219 | MA-219-01-001-DC | 1000 / 0357 | Low | Ames | Maxim 200 | 6 | 6" DC on water supply line to fire suppression system located in Security Forces hangar behind offices. |
| 220 | MA-220-01-006-DC | 1000 / 0634 | Low | Ames | Maxim 200 | 4" | 4" RP on water supply line to fire suppression system located in tool room on Utility Shop Side of building. |
| 220 | MA-220-02-004-AV | 1000 / 0360 | Low | Watts | 288a | 3/4 | Hose bibb with AV located on north wall |
| 220 | MA-220-OO-002-AV | 1000 / 0361 | Low | Nidel | 34a | 3/4 | Hose bibb with AV located on east end of north wall |
| 220 | MA-220-01-003-AV | 1000 / 0359 | Low | T&S | B969 | 3/4 | Slop sink with AV located in janitor's closet |
| 220 | MA-220-01-005-OT | 1000 / 0362 | High | Watts | 9D | 3/4 | 3/4" non-testable backflow preventer on make-up water supply line to Low Temperature Heating System located approximately 10' h |
| 220 | MA-220-01-007-RP | 1000/0825 | High | Watts | 909M1QT | 2" | 2' RP on water supply line to fill stand and backflow system trainers. Located in Tool room along north wall on WFSM side of bldg. |
| 220 | MA-220-OO-001-PV | 1000 / 0363 | High | Watts | 800M4 | 1 | 1" PV on water supply line to irrigation located southeast of building and west of side parking lot |
| Building Number | BPD ID Full | RWP Equipment Type / Number | Hazard Rank | Manufacturer | Model | Size | Point of Use |
| 226 | MA-226-01-001-DC | 1000 / 0780 | Low | Ames | Maxim 200 | 6" | 6" DC on fire suppression system located on Utility Shop side of building along west wall. |
| 250 | MA-250-BM-001-AV | 1000 / 0364 | High | Nidel | 34 hd | 3/4 | Hose bibb with AV located on east wall used to manually make up water to chiller |
| 250 | MA-250-BM-002-DC | 1000 / 0367 | Low | Ames | Maxim 200 | 4 | 4" DC on water supply line to fire suppression system located on center of north wall |
| 250 | MA-250-BM-005-DC | 1000 / 0365 | High | Watts | 009M2QT RP | 2 | 2" DC on water supply line to irrigation located approximately 14' high in center of north side of room |
| 250 | MA-250-BM-004-RP | 1000 / 0366 | High | Watts | 909 OT RP2 | 3/4 | 3/4" RP on make-up water supply line to Low Temperature Heating System located approximately 3' high on south side of room |
| 250 | MA-250-BM-003-RP | 1000 / 0368 | High | Watts | 909 OT RP2 | 3/4 | 3/4" RP on make-up water supply line to Low Temperature Heating System located near center wall next to stairs |
| 295 | MA-295-01-002-AV | 1000 / 0369 | Low | T&S | b969 | 3/4 | Slop sink with AV located in laundry room |
| 295 | MA-295-01-001-RP | 1000 / 0370 | High | Watts | 909MODQT | 3/4 | 3/4" RP on make-up water supply line to Low Temperature Heating System located in center of room |