Appendix D - TAB Pre-Const Deficiency Report.pdf
PDF 2 MB Posted
- Solicitation number
- BPM059224
- Issued by
- Anne Arundel County, Maryland
About this file
This is a Pre-Construction Deficiency Report prepared by Integra Testing Services for Anne Arundel Community College (AACC) on the AMIL Building HVAC system located at 709 Arundel Mills Circle in Hanover, Maryland. The report documents findings from a First and Fourth Floor HVAC Survey conducted on September 15-16, 2026, in connection with Project 26-0937 for Air Handling Unit and Makeup Air Unit replacements. The survey identified sixteen open deficiencies, all involving fan CFM operational failures across multiple FPVAV (Fan Powered VAV) units and one room unit designated FPVAV-B-Room 4. All deficiencies have been assigned to the Owner for resolution.
The deficiencies center on non-functional fan motors across the surveyed HVAC systems. Specific issues include multiple units (FPVAV-4-011, 4-012, 4-013, 4-010, 4-003, 4-005, 4-007, 1-009, 1-012, and B-Room 4) with bad fan motors that are not running despite receiving proper voltage of 278 volts. Additional deficiencies include units with operational anomalies such as loud humming without corresponding airflow changes when adjusting speed controllers (FPVAV-1-013), non-responsive fans at maximum speed controller settings (FPVAV-1-011, 1-020, 1-014), and one unit (FPVAV-1-024) lacking a speed controller entirely with suspected internal wiring issues. The report recommends replacement of fan motors and, in at least one case, installation of a speed controller. All deficiencies were documented by Josh Wright between September 15-16, 2026, and remain open as of the report date of September 17, 2026.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Section 5.0 Project References.xlsx | XLSX spreadsheet | |
| Appendix C1 - AMIL RTU Replacement Phase 2.pdf | ||
| Appendix B - Prevailing Wage Determination.pdf | ||
| Appendix C2 - CALT MAU Replacement.pdf | ||
| C2027-13-P AMIL-CALT RTU-MAU Replacements.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FIRM:
Integra Testing Services - NY/MD/MO
4 Chelsea Place Suite 102 Clifton Park NY 12065
PHONE:
(518) 450-7292
FAX:
(518) 450-7295
CUSTOMER:
Budova Engineering
PROJECT #:
26-0937
PROJECT ADDRESS:
709 Arundel Mills Circle Hanover MD 21076
DATE:
2026-09-17
CONTACT:
Josh Wright
Open Deficiency Report
AACC AMIL Bldg 1st & 4th Flr HVAC Survey
DEFICIENCY REPORT
No. Component/Question Type Status Assigned To Deficiency Issue Created
1 FPVAV-4-011 / Fan CFM Operational Open Owner Bad fan motor. Fan not running.
Comments:
On: 2026-09-15
By: Josh Wright
2 FPVAV-4-012 / Fan CFM Operational Open Owner Bad fan motor. Fan not running.
Comments:
On: 2026-09-15
By: Josh Wright
3 FPVAV-4-013 / Fan CFM Operational Open Owner Bad fan motor. Fan not running.
Comments:
On: 2026-09-15
By: Josh Wright
4 FPVAV-4-010 / Fan CFM Operational Open Owner Bad fan motor. Fan not running.
Comments:
On: 2026-09-15
By: Josh Wright
5 FPVAV-4-003 / Fan CFM Operational Open Owner Bad fan motor. Fan not running.
Comments:
On: 2026-09-15
By: Josh Wright
6 FPVAV-4-005 / Fan CFM Operational Open Owner Bad fan motor. Fan not running.
Comments:
On: 2026-09-15
By: Josh Wright
7 FPVAV-4-007 / Fan CFM Operational Open Owner Bad fan motor. Fan not running.
Comments:
On: 2026-09-15
By: Josh Wright
8 FPVAV-4-009 / Fan CFM Operational Open Owner Potentially bad motor i would suggest to replace.
Comments:
On: 2026-09-15
By: Josh Wright
9 FPVAV-1-009 / Fan CFM Operational Open Owner Bad fan motor. Fan not running
Comments:
On: 2026-09-16
By: Josh Wright
10 FPVAV-1-012 / Fan CFM Operational Open Owner Bad fan motor. Fan not running
Comments:
On: 2026-09-16
By: Josh Wright
PROJECT NUMBER:
26-0937
CONTACT:
Josh Wright
LOCATION:
AACC AMIL Bldg 1st & 4th Flr HVAC Survey 709 Arundel Mills Circle Hanover MD 21076
Page 2 of 4 2026-09-17
11 FPVAV-1-013 / Fan CFM Operational Open Owner Fan has 278 volts going to it but it is humming really loud. Speed controller is on max speed setting but airflow does not change when trying to slow it down. I would recommend to replace fan motor.
Comments:
On: 2026-09-16
By: Josh Wright
12 FPVAV-1-011 / Fan CFM Operational Open Owner Fan has 278 volts but does not seem to be running. Most likely needs to be replaced.
Comments:
On: 2026-09-16
By: Josh Wright
13 FPVAV-1-020 / Fan CFM Operational Open Owner Fan is getting 278 volts but fan does not seem like it is running.
Speed controller is at max position. Would recommend that fan be replaced.
Comments:
On: 2026-09-16
By: Josh Wright
14 FPVAV-1-024 / Fan CFM Operational Open Owner Fan has 278 volts but there is no speed controller. There is a red and black wire connected to the terminal block and the relay and then it goes into the body of the vav. There might be a speed controller inside the vav but would have to take the bottom cover of the vav off to trace out the wires. The fan is not running and the air coming from the supply diffusers is from the primary air and it is pushing past the fan. Fan may need to be replaced as well as adding a speed controller.
Comments:
On: 2026-09-16
By: Josh Wright
15 FPVAV-1-014 / Fan CFM Operational Open Owner Fan was turned off when we first came to vav. turned fan on but the fan never came on. The electric heat came on though and with no fan running we left the fan turn off. We did verify the fan had 278 volts when it was turned on and also that the speed controller was at it max position. Fan should be replaced.
Comments:
On: 2026-09-16
By: Josh Wright
16 FPVAV-B-Room 4 / Fan CFM Operational Open Owner Fan is getting 278 volts but is not running. speed controller is at max position as well. Motor should be replaced.
Comments:
On: 2026-09-16
By: Josh Wright
No. Component/Question Type Status Assigned To Deficiency Issue Created
PROJECT NUMBER:
26-0937
CONTACT:
Josh Wright
LOCATION:
AACC AMIL Bldg 1st & 4th Flr HVAC Survey 709 Arundel Mills Circle Hanover MD 21076
Page 3 of 4 2026-09-17
1 2
3 4
2 3
3 4
3 4 1 2
Not installed