Appendix C2 - CALT MAU Replacement.pdf
PDF 566 KB Posted
- Solicitation number
- BPM059224
- Issued by
- Anne Arundel County, Maryland
About this file
This file contains construction drawings and specifications for the replacement of a makeup air unit (MAU-1) at Anne Arundel Community College's Center for Applied Learning and Technology (CALT) facility located at 101 College Parkway, Arnold, Maryland 21012. The scope of work includes removing the existing makeup air unit while retaining the existing roof curb, installing a new makeup air unit on a curb adapter mounted on the existing roof curb, reconnecting gas piping to the new unit, and integrating the unit with both the existing fire alarm system and building automation system. The project is designed by KCI Engineers, Planners, Scientists, and Construction Managers, with a professional certification date of September 30, 2026, and includes comprehensive electrical, mechanical, and control system specifications and coordination requirements.
The construction documents specify that the new makeup air unit shall be a Trane GRAA model with an output capacity of 4,000 MBH, supply airflow of 4,000 CFM, outdoor air intake of 1,000 CFM, electrical requirements of 460V/60Hz/3-phase at 6.8 MCA, and weighing approximately 1,000 pounds. The design incorporates a manufacturer-supplied factory-mounted disconnect, a pressure switch across the filter with high-pressure drop alarm capability at the building automation system, fan status reporting at the BAS, 2-inch disposable filters, and integration with the existing smoke evacuation control sequence. The electrical contractor must disconnect and reuse existing conduit and wiring feeding MAU-1, extend existing conduit to accommodate the new disconnect location, and coordinate all installations with mechanical contractors and fire alarm system integrations. All work must comply with the 2021 International Building Code, Mechanical Code, and Energy Conservation Code as adopted by Maryland, with a two-year warranty on all materials, labor, and equipment commencing from the date of system acceptance.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
R
ID
G
E B
R O
O K
R D
S P
A R
K S
-G L
E N
C O
E M
D
P H
O N
E
-3
-7 w w .k c i.
c o m
E P S C
M
N G
IN
E
E R
S
L A
N N
E R
S
C
IE
N T
IS
T
S
O N
S T
R U
C T
IO
N
A N
A G
E R
S
CHECKED BY
PROJECT NUMBER
SUBMISSION DATE
DRAWN BY
SHEET NAME
SHEET NUMBER
SUBMISSION TYPE
ISSUE FOR CONSTRUCTION
PROFESSIONAL CERTIFICATION. I CERTIFY THAT THESE
DOCUMENTS WERE PREPARED OR APPROVED BY ME,
AND THAT I AM A DULY LICENSED ENGINEER UNDER THE
LAWS OF THE STATE OF MARYLAND,
C D
M S
\R e v it P ro je c ts
\R
C
A L
T M
E P
Ie s h a
.S tu rg e o n
M
V Q
.r v t
CS-1
09/30/2026
IRS
ELS
COVER SHEET
00057733_001
R E
P L
A C
E C
A L
T M
A U
C
O L L E
G E
P A
R K
W A
Y
A R
N O
L D
M
D
A N
N E
A R
U N
D E
L C
O M
M U
N
IT
Y C
O L L E
G E
ANNE ARUNDEL COMMUNITY COLLEGE
CALT MAU REPLACEMENT
101 COLLEGE PARKWAY
ARNOLD, MARYLAND 21012
DRAWINGS LIST
Sheet
Number Sheet Name
CS-1 COVER SHEET
E-001 ELECTRICAL LEGENDS
E-101 ELECTRICAL POWER PLAN
E-201 ELECTRICAL POWER PLAN
M-001 MECHANICAL COVER SHEET
M-101 MECHANICAL ROOF PLAN - DEMOLITION
M-201 MECHANICAL ROOF PLAN - NEW WORK
R
E V
IS
IO
N D
E S
C R
IP
T
IO
N
D A
T E
SCOPE OF WORK
1. REMOVE EXISTING MAKEUP AIR UNIT; EXISTING ROOF CURB TO
REMAIN.
2. INSTALL NEW MAKEUP AIR UNIT ON CURB ADAPTER MOUNTED
ON EXISTING ROOF CURB.
3. RECONNECT GAS PIPING TO NEW MAKEUP AIR UNIT.
4. TIE MAKEUP AIR UNIT INTO EXISTING FIRE ALARM SYSTEM.
5. TIE MAKEUP AIR UNIT INTO EXISTING BUILDING AUTOMATION
SYSTEM.
ELECTRICAL LEGEND
WP
(E)
(R)
(N)
CONDUIT RUN CONCEALED IN WALL OR CEILING
HOMERUN TO ELECTRICAL PANELBOARDS
MC
M
GROUND FAULT INTERRUPTOR (GFI) DUPLEX RECEPTACLE.
SIMILAR TO DUPLEX RECEPTACLE ABOVE.
DUPLEX RECEPTACLE, 20AMP, 125VOLT, 2POLE, 3WIRE,
GROUNDING TYPE, NEMA 5-20R UNO.
DEDICATED RECEPTACLE, PROVIDE GRAY COLOR (CONFIRM W/
ARCHITECT) RECEPTACLE AND COVER PLATE, WITH INTENDED
USAGES OF RECEPTACLES ENGRAVED ON COVERPLATE (E.G.
"COPIER"). ELECTRICIAN SHALL CONFIRM RECEPTACLE TYPE
REQUIRED WITH OWNER/EQPM VENDOR PRIOR TO INSTALL.
DOUBLE (QUAD) DUPLEX RECEPTACLE WITH COMMON COVER
PLATE. SIMILAR TO DUPLEX RECEPTACLE.
DISCONNECT SWITCH. ALL SWITCHES SHALL BE HEAVY DUTY TYPE
(E.G. 30A/3P/600/NF/NEMA 1)
JUNCTION BOX.
SWITCH, THREE-WAY MOMENTARY CONTACT TOGGLE TYPE WITH
CENTER NEUTRAL POSITION. SIMILAR TO ASCO # 173A2.
MANUAL MOTOR STARTER WITH PROPER THERMAL ELEMENT
INSTALLED.
SINGLE POLE SWITCH
ALL SYMBOLS SHOWN ARE NOT NECESSARILY USED IN THIS PROJECT
ELECTRICAL PANEL BOARDS.
EXIT LIGHT. PROVIDE DIRECTIONAL CHEVRON(S) ARROW(S) AS
INDICATED ON PLANS. PROVIDE WITH INTEGRAL BATTERY PACK
UNO. CONNECT TO UNSWITCHED POWER LEADS.
GROUND FAULT INTERRUPTOR (GFI) & WEATHERPROOF (WP)
DUPLEX RECEPTACLE. SIMILAR TO DUPLEX RECEPTACLE ABOVE.
POKE-THRU OR RECESSED FLOOR BOX FOR POWER. TYPE
SPECIFIED ON PLANS.
NEW OR RELOCATED LIGHT FIXTURE. LETTER INDICATES TYPE.
REFER TO LIGHT FIXTURE SCHEDULE FOR MORE INFORMATION.
DATA OUTLET. PROVIDE BACK BOX/COVER PLATE. INSTALL 3/4"C.
WITH BUSHING AND PULL STRING, STUBBED TO ACCESSIBLE
CEILING.
CONDUIT RUN CONCEALED IN FLOOR
NEW EMERGENCY LIGHT FIXTURE. PROVIDE WITH EMERGENCY
POWER SOURCE. REFER TO LIGHT FIXTURE SCHEDULE FOR MORE
INFORMATION.
RELOCATED
NEW
EXISTING
J
(D) DEMO
LEGEND NOTES:
1. THE WORD "PROVIDE" AS USED IN THESE DRAWINGS SHALL MEAN
"MATERIALS AND LABOR FURNISHED AND INSTALLED BY ELECTRICAL
CONTRACTOR".
CEILING MOUNTED DUPLEX RECEPTACLE, 20AMP, 125VOLT, 2POLE,
3WIRE, GROUNDING TYPE, NEMA 5-20R UNO.
UNDERGROUND CONDUIT
SIMPLEX RECEPTACLE. SIMILAR TO DUPLEX RECEPTACLE
SPLIT-WIRE RECEPTACLE WITH EACH HOT WIRE CONNECTED TO A
DOUBLE-POLE CIRCUIT BREAKER. SIMILAR TO DUPLEX
RECEPTACLE ABOVE.
POKE-THRU OR RECESSED FLOOR BOX FOR POWER AND DATA.
TYPE SPECIFIED ON PLANS.
SPECIALTY RECEPTACLE. REFER TO PLANS FOR EXACT NEMA
CONFIGURATION OF RECEPTACLE.
ELECTRICAL ABBREVIATIONS
(D) (E) (N) (R)
(RM)
(R'D)
AC
AF
AFF
AHJ
AIC
AMP
AT
ATS
AWG
C
CB
CFCI
CKT
CLG
CT
CU
DISC.
DIST.
EA
E.C.
FA
FAAP
FACP
FLA
FTL
G.C.
GFI
GRD
GRS
HP
IDF
I.P.S.
JB
KVA
KW
LAN
LTS
LTG
MCB
MDF
MLO
MTD
MTG
NEC
NEMA
NF
NTS
OFCI
OFOI
OC
OCP
OS
OSC
P
PA
PB
PC
PH
PNL
PS
RCPT
REC
RECP
REQ'D
SN
SPECS
SPKR
SWBD
SWGR
TEL
TTB
TVSS
TYP.
UC, U/C
U.N.O.
V
VA
VC
VS
VSD
W W/ W/O
WP
XFMR
XFR
DEMO
EXISTING
NEW
RELOCATE
REMOVE EXISTING EQUIPMENT
RELOCATED EQUIPMENT
ALTERNATING CURRENT
AMPERE FUSE
ABOVE FINISHED FLOOR
AUTHORITY HAVING JURISDICTION
AMPERE INTERRUPTING CAPACITY
AMPERE
AMPERE TRIP
AUTOMATIC TRANSFER SWITCH
AMERICAN WIRE GAUGE
CONDUIT
CIRCUIT BREAKER
CONTRACTOR FURNISHED CONTRACTOR INSTALLED
CIRCUIT
CEILING
CURRENT TRANSFORMER
COPPER
DISCONNECT
DISTRIBUTION
EACH
ELECTRICAL CONTRACTOR
FIRE ALARM
FIRE ALARM ANNUNCIATION PANEL
FIRE ALARM CONTROL PANEL
FULL LOAD AMPS
FEED THRU LUGS
GENERAL CONTRACTOR
GROUND FAULT INTERRUPTER
GROUND
GALVANIZED RIGID STEEL
HORSEPOWER
INTERMEDIATE DISTRIBUTION FRAME
INVERTER POWER SYSTEM
JUNCTION BOX
KILO-VOLT-AMPERE
KILOWATT
LOCAL AREA NETWORK
LIGHTS
LIGHTING
MAIN CIRCUIT BREAKER
MAIN DISTRIBUTION FRAME
MAIN LUGS ONLY
MOUNTED
MOUNTING
NATIONAL ELECTRICAL CODE
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION
NON-FUSED
NOT TO SCALE
OWNER FURNISHED CONTRACTOR INSTALLED
OWNER FURNISHED OWNER INSTALLED
OVERCURRENT
OVERCURRENT PROTECTION
OCCUPANCY SENSOR
OCCUPANCY SENSOR CONTROLS
POLE
PUBLIC ADDRESS
PUSH BUTTON
PHOTOCELL
PHASE
PANEL
PHOTOSENSOR
RECEPTACLE
RECEPTACLE
RECEPTACLE
REQUIRED
SOLID NEUTRAL
SPECIFICATIONS
SPEAKER
SWITCHBOARD
SWITCHGEAR
TELEPHONE
TELEPHONE TERMINAL BOARD
TRANSIENT VOLTAGE SURGE SUPPRESSOR
TYPICAL
UNDER COUNTER
UNLESS NOTED OTHERWISE
VOLT
VOLT-AMPERE
VACANCY CONTROLS
VACANCY SENSOR
VARIABLE SPEED DRIVE
WATT OR WIRE
WITH
WITHOUT
WEATHERPROOF
TRANSFORMER
TRANSFER
ELECTRICAL DEMOLITION GENERAL NOTES
A. PLANS DO NOT ATTEMPT TO SHOW ALL DEMOLITION ITEMS. SOME LIGHT FIXTURES,
SWITCHES/DIMMERS, EXIT LIGHTS, RECEPTACLES, TELEPHONE, DATA, MISC. OUTLETS ARE SHOWN
FOR INFORMATION PURPOSE. HOWEVER, THE ITEMS SHOWN ARE NOT NECESSARILY COMPLETE,
ELECTRICAL CONTRACTOR (E.C.) TO FIELD VERIFY ALL DEMOLITION ITEMS AND PROVIDE REMOVAL OF ALL DEVICES ACCORDINGLY. SEE RELATED NOTES ON MAINTAINING SEVICE TO NON-DEMOLITION AREAS. E.C. SHALL REMOVE ALL EXISTING LIGHTING FIXTURES, ASSOCIATED SWITCHES/DIMMERS, EXIT LIGHTS, RECEPTACLES, TELEPHONE, DATA, MISC. OUTLETS WHERE SHOWN IN DEMOLITION AREAS. REMOVE CONDUIT/WIRE BACK TO PANEL(S) UNLESS RE-USED FOR NEW AND/OR RELOCATED WORKS. EXISTING CONDUIT/WIRE WITH ADEQUATE CAPACITY FOR NEW AND/OR EXISTING LOADS MAY BE RE-USED. SIMILARLY FOR COMMUNICATION SYSTEM CONDUIT/WIRE (REMOVE BACK TO CONTROL PANEL(S) IF NOT RE-USED). LIGHT FIXTURES IN GOOD CONDITION MAY BE RE-USED IF SO INDICATED ON DRAWINGS. LIGHT FIXTURES TO BE RE-USED SHALL BE RE-LAMPED AND CLEANED. REPLACE BALLASTS IF NOISY OR INOPERATIVE. E.C. TO EXAMINE CONDITION OF ALL EXISTING BALLASTS, IF ANY BALLASTS ARE SUSPECTED TO CONTAIN PCB'S, DO NOT DISPOSE OF; SET SUCH ASIDE AND NOTIFY
OWNER FOR AUTHORIZED REMOVAL. REMOVE SUCH BALLASTS IN STRICT COMPLIANCE WITH
FEDERAL, STATE AND LOCAL LAWS AND ORDINANCES. BALLASTS DATED PRIOR TO 1976 OR NOT SPECIFICALLY MARKED "NO PCB'S" SHALL BE CONSIDERED TO CONTAIN PCB'S. FIXTURES NOT INDICATED FOR RE-USE SHALL BE DELIVERED TO A LOCATION TO BE SPECIFIED BY OWNER. ALL
FIXTURES UPSTREAM OR DOWNSTREAM OF DEMO'D FIXTURES AND ON THE SAME CKTS SHALL BE
RECONNECTED TO MAINTAIN SERVICE. PROVIDE NEW CONDUIT/WIRE AS REQ'D.
B. DAMAGE TO EXISTING MATERIALS/EQUIPMENT WILL BE REPAIRED AT NO ADDITIONAL COST TO
OWNER. RE-SUPPORT ANY REMAINING CONDUIT OR DEVICE THAT WERE SUPPORTED BY
WALLS/MILLWORK BEING REMOVED.
C. NON-DEMOLITION AREAS: DEMOLITION WORKS SHALL NOT AFFECT AREAS NOT INCLUDED IN
DEMOLITION. E.C. SHALL BE RESPONSIBLE FOR THE CONTINUITY OF ALL SERVICES (POWER,
TELEPHONE, FIRE ALARM, DATA) IN NON-DEMOLITION AREAS. ALL SERVICES SHALL BE MAINTAINED AT ALL TIMES. ELECTRICAL CONTRACTOR (E.C.) SHALL MAINTAIN SERVICE BY EXTENDING, REROUTING
AND/OR RE-CONNECTING ANY CIRCUITS AFFECTED BY DEMOLITION. PROVIDE ADDITIONAL
CONDUIT/WIRE AS REQUIRED TO MAINTAIN SERVICE. CIRCUITS IN NON-DEMOLITION AREAS THAT ARE CONNECTED TO DEMO'D PANELS AND/OR CIRCUITS SHALL BE RE-CIRCUITED TO A NEW SUB-PANEL (FURNISHED AND INSTALLED BY E.C., SIZE AS REQUIRED) IF SPACES/SPARES ARE NOT AVAILABLE IN
ANY NEW PANELS IN RENOVATION AREAS. PROVIDE TEMPORARY POWER AS REQUIRED DURING
CHANGE-OVER TO MAINTAIN CONTINUOUS SERVICE. PROVIDE TEMPORARY POWER FOR ALL
RELOCATED CIRCUITS AS REQUIRED TO MAINTAIN CONTINUOUS SERVICE. SIMILARLY FOR FIRE
ALARM, SECURITY, DATA SYSTEM.
D. E.C. SHALL FIELD INVESTIGATE EXISTING ELECTRICAL INSTALLATION. ALL EXISTING INSTALLATION IN
THE RENOVATION AREAS THAT ARE TO REMAIN BUT ARE NOT CURRENTLY IN COMPLIANCE WITH
CURRENT CODES SHALL BE CORRECTED BY E.C., INCLUDING BUT NOT LIMITED TO THE FOLLOWINGS:
• UN-SUPPORTED CONDUIT AND JUNCTION BOXES LAYING ON TOP OF CEILING TILES, CONDUIT
AND/OR JUNCTION BOXES SUPPORTED ONLY BY TIE-WIRE. RAISE AND SUPPORT CONDUIT WITH
STRAP PER SPECS. PROVIDE NEW CONDUIT/WIRE AS REQUIRED.
• CIRCUITS WITHOUT A SEPARATE GREEN GROUNDING WIRE - INSTALL A GREEN GROUNDING WIRE
FOR EVERY RECEPTACLE OUTLET AND DEVICES. INSTALLATION OF THE GREEN GROUNDING
WIRE MAY REQUIRE THE REMOVAL OF EXISTING WIRES. PROVIDE NEW WIRE AS REQUIRED.
• FIXTURES IMPROPERLY SUPPORTED OR INADEQUATELY SUPPORTED BY DEVICE BOXES -
PROVIDE PROPER SUPPORT PER N.E.C.
• SEAL ALL PENETRATIONS THROUGH RATED FLOORS/WALLS/CEILINGS/PARTITIONS WITH UL
LISTED FIRESAFING MATERIAL.
E. ALL EXISTING ABANDONED AND/OR UN-USED CONDUIT/WIRE, SWTCHES/STARTERS, J-BOXES, COMMUNICATION SYSTEM AND DEVICES IN PROJECT AREAS SHALL BE REMOVED BACK TO PANELS
AND/OR CONTROL PANELS. ALL ITEMS DEMO'D BY E.C. SHALL BE REMOVED BACK TO PANELS
AND/OR CONTROL PANELS.
• EMERGENCY AND NORMAL POWER CIRCUITS IN THE SAME CONDUIT - PROVIDE SEPARATION OF
EMERGENCY AND NORMAL CIRCUITS AND INSTALL IN SEPARATE CONDUIT.
ELECTRICAL GENERAL NOTES
• ALL CIRCUIT NUMBERS SHOWN ARE FOR REFERENCE ONLY. FIELD VERIFY ACTUAL CIRCUIT NUMBERS
REQ’D AND ADJUST ACCORDINGLY. PROVIDE TYPE-WRITTEN DIRECTOR(IES) REFLECTING ACTUAL
CIRCUIT NUMBERS USED, WITH FIELD REVISED/ RELOCATED CIRCUITS CLEARLY INDICATED.
DIRECTOR(IES) SHALL INCLUDE DATE AND PROJECT DESCRIPTION, EXAMPLE : 2006 NEW BLDG.
• EACH CIRCUIT IS SHOWN WITH AN INDIVIDUAL HOMERUN. E.C. MAY ELECT TO COMBINE TWO OR
MORE CIRCUITS IN ONE COMMON CONDUIT AND WITH COMMON NEUTRAL WHERE ALLOWED
(CIRCUITS WITH HIGH CONTENT OF HARMONIC CURRENTS MAY NOT USE COMMON NEUTRAL,
EXAMPLE: CIRCUITS WITH NON-LINEAR ELECTRONIC POWER SUPPLIES SUCH AS COMPUTERS,
COPIERS, PRINTERS, ETC). NOTE: AMPACITIES OF CONDUCTORS SHALL BE REDUCED IF MORE THAN
THREE CURRENT CARRYING CONDUCTORS ARE INSTALLED IN A RACEWAY. SEE N.E.C. ARTICLE
310.15(B)(2)(A) “ADJUSTMENT FACTORS”. CONDUCTORS SHALL BE DERATED IF 4 OR MORE WIRES ARE
INSTALLED IN ONE CONDUIT (SEE RELATED NOTE “G3” ON TEMPERATURE LIMITATION OF
CONDUCTOR AMPACITY), TYPICAL EXAMPLES FOR 20-AMP CIRCUITS ARE SHOWN BELOW:
• TEMPERATURE LIMITATIONS ON AMPACITY OF CONDUCTOR: THE AMPACITY OF A CONDUCTOR SHALL BE SELECTED BASED ON THE NATIONAL ELECTRICAL CODE ARTICLES 310.15 AND 110.14.(C)(1),(2). THE TEMPERATURE LIMITATIONS NOTED IN 110.14.(C)(1),(2) MAY BE PARAPHRASED AS FOLLOWS : (A) CIRCUITS RATED 100 AMP OR LESS: USE 60-DEGREE C RATED CONDUCTORS ONLY. 75-DEGREE C AND
90-DEGREE C CONDUCTOR MAY BE USED BUT ONLY AT 60-DEGREE C AMPACITY. EXCEPTIONS:
HIGHER TEMPERATURE CABLE ARE ALLOWED PROVIDED THE EQUIPMENT IS LISTED AND IDENTIFIED FOR USE WITH THE HIGHER RATED CONDUCTORS. (B) CIRCUITS RATED MORE THAN 100 AMP OR
CONDUCTOR LARGER THAN #1 AWG: USE 75-DEGREE C RATED CONDUCTORS ONLY. 90-DEGREE C
CONDUCTOR MAY BE USED BUT ONLY AT 75-DEGREE C AMPACITY. EXCEPTIONS: HIGHER
TEMPERATURE CABLE ARE ALLOWED PROVIDED THE EQUIPMENT IS LISTED AND IDENTIFIED FOR USE
WITH THE HIGHER RATED CONDUCTORS.
• WIRES OVERSIZED TO ALLEVIATE VOLTAGE DROP: WHERE OVERSIZED WIRES ARE USED TO
ALLEVIATE VOLTAGE DROP, CONTRACTOR TO PROVIDE REDUCER LUGS AND/OR J-BOXES AS
REQUIRED TO TERMINATE WIRES IN EQUIPMENT.
• ALL CONDUIT AND WIRE MUST BE CONCEALED FROM VIEW. EXPOSED CONDUIT AND WIRE ARE NOT
ACCEPTABLE, EXCEPTIONS ARE CENTRAL PLANT, MECHANICAL/ELECTRICAL ROOMS.
• EXISTING CONSTRUCTION: ALL NEW WIRINGS INSTALLED IN EXISTING WALL/CEILING/MILLWORK SHALL BE CONCEALED, INCLUDING CONCRETE BLOCK WALL. PATCH ANY CUT AREAS TO MATCH EXISTING
CONDITION.
• ALL ELECTRICAL AND COMMUNICATION DEVICES (LIGHT SWITCHES, RECEPTACLES, TELEPHONE, DATA ETC.) SHALL BE RECESSED MOUNTED UNLESS NOTED OTHERWISE. FIELD VERIFY RECEPTACLE MOUNTING REQUIREMENTS WITH OWNER/ ARCH., MOUNT ALL DUPLEX RECEPTACLES WITH THE “U”
GROUND TERMINAL ON TOP, UNLESS NOTED OTHERWISE OR AS REQUIRED BY OWNER/ARCH.
NEUTRAL TERMINAL SHALL BE ON TOP FOR HORIZONTALLY MOUNTED RECEPTACLES.
• ALL OUTLETS ON DEDICATED CIRCUITS (MARKED “DED” OR “D” ON PLANS) SHALL BE PROPERLY IDENTIFIED BY USING DISTINCTIVE COLOR DEVICES (USE BROWN OR GRAY DEVICES. CONFIRM COLOR REQUIREMENTS WITH ARCHITECT/OWNER.). COVER PLATES SHALL BE MARKED WITH CIRCUIT
NUMBER(S) AND LOADS SERVED. EXAMPLE : CKT # LA-1 COPY MACHINE.
• EQUIPMENT LAYOUT IS BASED ON SQUARE D AND/OR SIEMENS. EQUIPMENT BY OTHER
MANUFACTURERS SUCH AS GE MAY HAVE LARGER DIMENSIONS. IT IS THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR TO PROVIDE EQUIPMENT WITH SIMILAR DIMENSIONS THAT WOULD FIT IN
THE SPACE NOTED.
• VERIFY LOCATION OF ALL OUTLETS (POWER & COMMUNICATION) WITH OWNER/ARCH PRIOR TO ROUGH-IN. OWNER RESERVES THE RIGHT TO MOVE ANY OUTLETS 5 FEET IN ANY DIRECTION PRIOR TO ROUGH-IN. ALL RECEPTACLES WITHIN 6 FEET OF ANY WET AREA (EXAMPLE : SINK, DISHWASHER, ETC..) SHALL HAVE GROUND FAULT PROTECTION, WHETHER SPECIFICALLY INDICATED OR NOT ON
DRAWINGS.
• MOUNTING HEIGHTS OF ALL OUTLETS (RECEPTACLES, SWITCHES, TELEPHONE, DATA, ETC.) IN AREAS WITH COUNTERTOP SHALL BE VERIFIED WITH ARCH/OWNER. GENERALLY ALL OUTLETS ARE TO BE
MOUNTED ABOVE COUNTERTOP EXCEPT OUTLETS FOR DISPOSERS, UNDERCOUNTER DISHWASHER,
UNDERCOUNTER REFRIGERATORS ETC. REFER TO ARCH INTERIOR ELEVATIONS.
• ALL WEATHERPROOF/WET LOCATION AND/OR OUTDOOR RECEPTACLES SHALL HAVE
“WEATHERPROOF-IN-USE” COVERS (NEC ARTICLE 406.8(B)). PROVIDE RACO BELL RAYNTITE II COVERS
OR EQUAL.
• ESTIMATED LOADS : INFORMATION AND DATA ON SPECIALTY EQUIPMENT MAY NOT BE AVAILABLE
DURING THE DESIGN PROCESS. SOME LOADS ARE NECESSARILY ESTIMATED. SUCH ESTIMATED
LOADS ARE INDICATED AS (EST.) ON PLANS, RISER DIAGRAMS AND/OR PANEL SCHEDULES.
CONTRACTOR SHALL BID THE PROJECT USING THE ESTIMATED FEEDER/BREAKER/SWITCHES SHOWN
ON DRAWINGS. HOWEVER, THE CONTRACTOR IS RESPONSIBLE FOR CONFIRMATION AND
VERIFICATION OF ALL SUCH ESTIMATED LOADS WITH THE APPROPRIATE VENDORS/SUPPLIERS. ALL
SHOP DRAWINGS SUBMITTED BY THE CONTRACTOR SHALL INCLUDE CERTIFICATION THAT THE
CONTRACTOR HAS CONFIRMED/VERIFIED ANY ESTIMATED LOADS SHOWN ON THE DRAWINGS.
CONTRACTOR WILL NOT BE DUE ANY ADDITIONAL COMPENSATION FOR HIS FAILURE TO VERIFY THE ESTIMATED LOADS SHOWN ON DRAWINGS. PROVIDE CREDIT TO THE OWNER IF ACTUAL LOADS ARE SMALLER THAN ESTIMATED LOADS, CREDIT SHALL BE GIVEN FOR SIZE REDUCTION ON FEEDER/
BREAKER/ SWITCHES.
• EXAMPLE OF EQUIPMENT LOADS THAT ARE TYPICALLY ESTIMATED : SPECIAL COPY MACHINE, WELDING EQPT OUTLET, ELEVATOR MACHINERY, ...
• PROVIDE HOUSE KEEPING CONCRETE PAD (MINIMUM 4” HIGH) FOR ALL FLOOR MOUNTED ELECTRICAL
EQUIPMENT INCLUDING TRANSFORMERS, SWITCHBOARDS, M.C.C., TRANSFER SWITCHES ETC.
PROVIDE ALL REQUIRED AND NECESSARY GALVANIZED UNISTRUT SUPPORT FOR ALL
INDOOR/OUTDOOR ELECTRICAL EQUIPMENT.
• FIRE WALL : DO NOT INSTALL RECEPTACLES, TELEPHONE, DATA OUTLETS ETC. BACK-TO-BACK IN FIRE/SMOKE PARTITIONS OR WITHIN THE SAME SPACE ENCLOSED BY TWO ADJACENT STUDS. ALSO APPLY TO ALL CORRIDOR WALLS.FOR EACH 2-POLE OR 3-POLE BRANCH CIRCUIT, NEUTRAL WIRE MAY
BE OMITTED IF NOT REQUIRED BY EQUIPMENT.
• THE ELECTRICAL CONTRACTOR SHALL FAMILIARIZE THEMSELVES WITH THE DRAWINGS OF ALL
OTHER TRADES ON THE PROJECT. ELECTRICAL OR SYSTEMS CONNECTIONS INDICATED ON
ARCHITECTURAL, MECHANICAL, CIVIL, STRUCTURAL AND ALL OTHER DRAWINGS WHICH ARE PART OF THIS PROJECT SHALL BE CONSIDERED A PART OF THIS CONTRACT AND SHALL BE PROVIDED BY THE
ELECTRICAL CONTRACTOR AT NO EXTRA COST TO THE OWNER.
• THE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC IN NATURE AND AS SUCH SHALL NOT BE SCALED.
REFER TO THE ARCHITECTURAL DRAWINGS FOR EXACT LOCATION OF DEVICES AND EQUIPMENT AND
DIMENSIONAL INFORMATION PRIOR TO ROUGH-IN.
• COORDINATE LOCATIONS OF MECHANICAL EQUIPMENT WITH THE MECHANICAL CONTRACTOR PRIOR
TO ROUGH-IN OF SERVICE EQUIPMENT AND WIRING. COORDINATE MOUNTING HEIGHTS OF ALL
DEVICES WITH ARCHITECTURAL PLANS, SECTIONS, ELEVATIONS AND CASEWORK DRAWINGS.
• THE CONTRACTOR SHALL BE RESPONSIBLE FOR DETERMINING THE EXACT ROUTING OF WIRING AND CONDUITS AND SHALL BE RESPONSIBLE FOR SIZING ALL BRANCH CIRCUIT WIRING TO LIMIT VOLTAGE
DROP TO 3%. CONTRACTOR SHALL SIZE CONDUIT TO ACCOMMODATE WIRING PER NEC.
• WIRING AND CONDUIT SIZES INDICATED IN PANEL SCHEDULES ARE MINIMUM ONLY. CONTRACTOR SHALL BE RESPONSIBLE FOR DETERMINING EXACT WIRING AND CONDUIT SIZES. CONTRACTOR SHALL PROVIDE SPLICE BLOCKS AND REDUCING PINS AS REQUIRED TO TERMINATE WIRING AND MAKE FINAL
CONNECTIONS.
• ELECTRICAL BOXES IN FIRE RATED PARTITIONS SHALL NOT EXCEED 16 SQUARE INCHES IN AREA (IF 4" x 4"), SHALL BE MADE OF STEEL AND SHALL BE SUCH THAT THE CUMULATIVE AREA OF BOX "CUTOUTS" IN THE FIREWALL DOES NOT EXCEED 100 SQUARE INCHES PER 100 SQUARE FEET OF WALL AREA. ELECTRICAL BOXES ON OPPOSITE SIDES OF THE SAME FIREWALL SHALL BE SEPARATED
BY A HORIZONTAL AND VERTICAL DISTANCE OF NOT LESS THAT 24 INCHES. THE ELECTRICAL
CONTRACTOR SHALL MAKE MINOR ADJUSTMENTS, AS NECESSARY, TO ELECTRICAL BOX LOCATIONS
TO ENSURE COMPLIANCE WITH THIS REQUIREMENT SINCE BOX LOCATIONS ARE TYPICALLY NOT
DIMENSIONED ON THE DRAWINGS. CONSULT ARCHITECT IF CLARIFICATION IS REQUIRED.
• ALL CONDUIT SHALL BE CONCEALED IN WALLS, FLOORS, ABOVE CEILING OR THROUGH MILLWORK UNLESS OTHERWISE NOTED. AT TIMES CONDUIT ROUTING IS SHOWN FOR CLARITY AND IN NO WAY PROVIDES THE CONTRACTOR ABILITY TO NOT PROVIDE CONCEALED CONDUIT AT ANY POINT. REFER
TO SPECIFICATIONS FOR CONDUIT AND WIRING REQUIREMENTS BASED ON APPLICATION.
• IN ALL PARTITIONS AND WALLS REQUIRING ACOUSTIC INSULATION OR AN STC RATING, OUTLETS, SWITCHES, ETC. SHALL NOT BE LOCATED BACK TO BACK; THEY SHALL BE OFFSET AT LEAST 16", SHALL NOT OCCUPY THE SAME STUD CAVITY AND SHALL BE SEALED. PERIMETERS OF PARTITIONS AND WALLS (AT ADJACENT WALLS, COLUMNS, CELINGS, ETC.) AND ALL PENETRATIONS SHALL BE
SEALED WITH AN APPROVED ACOUSTIC SEALANT. INSTALL 3" ACOUSTIC BATT INSULATION.
4 THRU 6
7 THRU 9
10 THRU 20
21 THRU 30
31 THRU 40
IN TABLES AS
ADJUSTED FOR TEMP IF
NECESSARY
80%
70%
50%
45%
40%
OR MORE WIRE IN ONE
CONDUIT 60°C WIRE
(E.G.: TW)
#12
#10
#8
#6
#6
41 AND ABOVE 35% #4
CURRENT CARRYING
CONDUCTORS
OR MORE WIRE IN ONE
CONDUIT 75°C WIRE
(E.G.: THWN)
#12
#10
#8
#8
#8
#6
OR MORE WIRE IN ONE
CONDUIT 90°C WIRE
(E.G.: THHN)
#12
#12
#10
#8
#8
#6
ELECTRICAL HVAC EQUIPMENT NOTES
1. ALL ELECTRICAL SIZING OF HVAC EQUIPMENT INCLUDING OVERCURRENT DEVICES, DISCONNECT
SWITCHES, CONDUIT/WIRE, ETC. ARE SELECTED BASED ON EQUIPMENT SHOWN ON MECHANICAL
DRAWINGS. E.C. TO FIELD VERIFY EQUIPMENT SUPPLIED BY HVAC TO VERIFY ALL REQUIREMENTS
INCLUDING BUT NOT LIMITED TO VOLTAGE, PHASE, MOCP, AND SINGLE POINT CONNECTION
REQUIREMENTS. REVISE ELECTRICAL AS REQUIRED AND NOTIFY ELECTRICAL ENGINEER
IMMEDIATELY OF ALL NECESSARY CHANGES TO MATCH ACTUAL EQUIPMENT SUPPLIED BY
MECHANICAL CONTRACTOR.
2. COORDINATE LOCATION OF ALL DISCONNECT SWITCHES, STARTERS, CONTROL STATIONS, ETC CALLED OUT IN THE ELECTRICAL DRAWINGS. E.C. SHALL INSTALL SUCH DEVICES IN COMPLIANCE
WITH CODE REQUIRED CLEARANCE REQUIREMENTS. ALL SUCH DEVICES SHALL BE ACCESSIBLE
AFTER EQUIPMENT ARE IN PLACE AND SATISFY CODE CLEARANCE REQUIREMENTS. REMOVE AND RE- INSTALL DEVICES THAT ARE INACCESSIBLE OR WITH INADEQUATE CODE CLEARANCE. COORDINATE
INSTALLATION WITH MECHANICAL CONTRACTOR
3. E.C. TO FIELD VERIFY EXTERNAL STARTER REQUIREMENTS FOR HVAC EQUIPMENT BASED ON ACTUAL EQUIPMENT SUPPLIED. E.C. TO PROVIDE EXTERNAL STARTERS ONLY FOR REQUIRED EQUIPMENT
WITHOUT INTERNAL STARTER MEANS.
4. FOR OUTDOOR PAD-MOUNTED A/C EQUIPMENT, CONNECT A/C EQUIPMENT TO OUTDOOR NEMA 3R
DISCONNECT SWITCHES WITH UNDERGROUND RIGID CONDUIT FEEDER. STUB UP CONDUIT NEAR
EQUIPMENT CONNECTION POINT. PROVIDE SEALTITE FROM CONDUIT STUB UP TO EQUIPMENT,
MAXIMUM LENGTH OF SEALTITE 5 FEET. SEALTITE LONGER THAN 5 FEET IS NOT ALLOWED.
5. E.C. TO COORDINATE EXHAUST FAN CONTROL REQUIREMENTS WITH MECHANICAL DRAWING
SCHEDULES. WHERE EXHAUST FANS ARE INDICATED AS INTERLOCKED WITH HVAC EQUIPMENT, E.C.
SHALL PROVIDE ALL REQUIRED RELAYS, CONDUIT/CONTROL WIRES, ETC AS REQUIRED FOR A
COMPLETE AND OPERATING SYSTEM. COORDINATE INTERLOCK REQUIREMENTS WITH HVAC
CONTRACTOR.
REFER TO DRAWING M-1
FIRE ALARM NOTES
R
ID
G
E B
R O
O K
R D
S P
A R
K S
-G L
E N
C O
E M
D
P H
O N
E
-3
-7 w .k c i.
c o
IN
E
E R
S
L A
N N
E R
S
C
IE
N T
IS
T
S
O N
S T
R U
C T
IO
N
A N
A G
E R
S
CHECKED BY
PROJECT NUMBER
SUBMISSION DATE
DRAWN BY
SHEET NAME
SHEET NUMBER
SUBMISSION TYPE
ISSUE FOR CONSTRUCTION
PROFESSIONAL CERTIFICATION. I CERTIFY THAT THESE
DOCUMENTS WERE PREPARED OR APPROVED BY ME,
AND THAT I AM A DULY LICENSED ENGINEER UNDER THE
LAWS OF THE STATE OF MARYLAND,
C D
M S
\R e v it P ro je c ts
\R
C
A L
T M
E P
Ie s h a
.S tu rg e o n
M
V Q
.r v t
E-001
09/30/2026
IRS
ELS
ELECTRICAL
LEGENDS
00057733_001
R E
P L
A C
E C
A L
T M
A U
C
O L L E
G E
P A
R K
W A
Y
A R
N O
L D
M
D
A N
N E
A R
U N
D E
L C
O M
M U
N
IT
Y C
O L L E
G E
R
E V
IS
IO
N D
E S
C R
IP
T
IO
N
D A
T E
RA
K J
I
H
R4
R5
R9
R12 R11 R10
R8
R6
R7
R2
R3
R1
G F E D
7.1
9.1
8.1
RB
RC
C
B
A
2.1
6000#
19'-5"
ETR FAN-9
ETR FAN-16
ETR FAN-17
ETR FAN-12
ETR CU-3
ETR CU-2
ETR CU-1
RX MAU-1
ETR FAN-19
ETR FAN-20
ETR FAN-22
ETR FAN-14
ETR FAN-13
ETR FAN-8
ETR FAN-10
ETR FAN-21
ETR FAN-11
ETR FAN-18ETR CU-4
ETR VCU-2
ETR VCU-3
ETR VCU-1
0 8' 16' 32'4'
3/32" = 1'-0"
N
R
ID
G
E B
R O
O K
R D
S P
A R
K S
-G L
E N
C O
E M
D
P H
O N
E
-3
-7 w .k c i.
c o
IN
E
E R
S
L A
N N
E R
S
C
IE
N T
IS
T
S
O N
S T
R U
C T
IO
N
A N
A G
E R
S
CHECKED BY
PROJECT NUMBER
SUBMISSION DATE
DRAWN BY
SHEET NAME
SHEET NUMBER
SUBMISSION TYPE
ISSUE FOR CONSTRUCTION
PROFESSIONAL CERTIFICATION. I CERTIFY THAT THESE
DOCUMENTS WERE PREPARED OR APPROVED BY ME,
AND THAT I AM A DULY LICENSED ENGINEER UNDER THE
LAWS OF THE STATE OF MARYLAND,
C D
M S
\R e v it P ro je c ts
\R
C
A L
T M
E P
Ie s h a
.S tu rg e o n
M
V Q
.r v t
E-101
09/30/2026
IRS
ELS
ELECTRICAL
POWER PLAN
00057733_001
R E
P L
A C
E C
A L
T M
A U
C
O L L E
G E
P A
R K
W A
Y
A R
N O
L D
M
D
A N
N E
A R
U N
D E
L C
O M
M U
N
IT
Y C
O L L E
G E
3/32" = 1'-0"1
ELECTRICAL POWER PLAN - DEMO
KEYED NOTES
1 DISCONNECT EXISTING CONDUIT AND WIRING FEEDING MAU-1. EXISTING FEED TO BE
REUSED FOR NEW MAKE-UP AIR UNIIT.
R
E V
IS
IO
N D
E S
C R
IP
T
IO
N
D A
I
H
R4
R5
R9
R12 R11 R10
R8
R6
R7
R2
R3
R1
G F E D
7.1
9.1
8.1
RB
RC
C
B
A
2.1
6000#
19'-5"
ETR FAN-11
ETR FAN-18ETR CU-4
ETR FAN-21
ETR FAN-8
ETR FAN-10
ETR FAN-22
ETR FAN-14
ETR FAN-13
ETR FAN-20
ETR FAN-19
ETR CU-2
ETR CU-3
ETR CU-1
ETR FAN-12
ETR FAN-17
ETR FAN-16
ETR FAN-9
ETR VCU-2
ETR VCU-3
ETR VCU-1
MAU-1
0 8' 16' 32'4'
3/32" = 1'-0"
N
R
ID
G
E B
R O
O K
R D
S P
A R
K S
-G L
E N
C O
E M
D
P H
O N
E
-3
-7 w .k c i.
c o
IN
E
E R
S
L A
N N
E R
S
C
IE
N T
IS
T
S
O N
S T
R U
C T
IO
N
A N
A G
E R
S
CHECKED BY
PROJECT NUMBER
SUBMISSION DATE
DRAWN BY
SHEET NAME
SHEET NUMBER
SUBMISSION TYPE
ISSUE FOR CONSTRUCTION
PROFESSIONAL CERTIFICATION. I CERTIFY THAT THESE
DOCUMENTS WERE PREPARED OR APPROVED BY ME,
AND THAT I AM A DULY LICENSED ENGINEER UNDER THE
LAWS OF THE STATE OF MARYLAND,
C D
M S
\R e v it P ro je c ts
\R
C
A L
T M
E P
Ie s h a
.S tu rg e o n
M
V Q
.r v t
E-201
09/30/2026
IRS
ELS
ELECTRICAL
POWER PLAN
00057733_001
R E
P L
A C
E C
A L
T M
A U
C
O L L E
G E
P A
R K
W A
Y
A R
N O
L D
M
D
A N
N E
A R
U N
D E
L C
O M
M U
N
IT
Y C
O L L E
G E
3/32" = 1'-0"1
ELECTRICAL POWER PLAN - NEW WORK
KEYED NOTES
1 RECONNECT EXISTING WIRING AND CONDUIT TO NEW UNIT. EXTEND EXISTING CONDUIT AND
WIRE TO ACCOMMODATE NEW DISCONNECT LOCATION.
R
E V
IS
IO
N D
E S
C R
IP
T
IO
N
D A
GENERAL NOTES
INTERNATIONAL CODE COUNCIL
IBC - INTERNATIONAL BUIILDING CODE - 2021 EDITION - AS ADOPTED BY THE STATE OF MARYLAND
IMC - INTERNATIONAL MECHANICAL CODE - 2021 EDITION - AS ADOPTED BY THE STATE OF MARYLAND
IECC - INTERNATIONAL ENERGY CONSERVATION CODE - 2021 EDITION - AS ADOPTED BY THE STATE OF MARYLAND
APPLICABLE CODES AND STANDARDS
MECHANICAL LEGEND
BREAK LINE
FLOW ARROW
REDUCER (DUCTWORK)
SUPPLY DUCT UP/DN
RETURN DUCT UP/DN
EXHAUST DUCT UP/DN
EXTENT OF DEMOLITION
POINT OF RECONNECTION
EXISTING CONDITIONS
NEW WORK
DEMOLITION
1. DRAWINGS ARE DIAGRAMMATIC AND NOT ALL APPURTENANCES ARE SHOWN. ALLOW FOR ADDITIONAL PIPE/DUCT OFFSETS, AS REQUIRED.
PROVIDE ALL MATERIALS AND LABOR TO PROVIDE A COMPLETE AND OPERABLE SYSTEM IN ACCORDANCE WITH THE CONTRACT DRAWINGS, SPECIFICATIONS, AND AUTHORITY HAVING JURISDICTION.
2. COORDINATE INSTALLATION OF WORK WITH ALL OTHER TRADES.
3. COORDINATE SIZE AND LOCATION OF ROOFTOP CURBS WITH STRUCTURAL FRAMING.
4. COORDINATE SIZE AND LOCATIONS OF ALL ROOF OPENINGS REQUIRED TO INSTALL THE WORK WITH ALL OTHER TRADES.
5. COORDINATE DUCTWORK AND PIPING LAYOUT WITH OPENINGS IN STRUCTURAL BEAMS, WALLS, ELEMENTS, ETC.
6. DEVELOP AND MAINTAIN A SET OF COORDINATION DRAWINGS AT THE JOB SITE THAT ACCOUNTS FOR ALL TRADES. REVIEW THE COORDINATION
DRAWINGS, COORDINATE WITH ALL TRADES, AND RESOLVE ANY POTENTIAL CONFLICTS PRIOR TO ORDERING OR INSTALLING ANY PORTION OF
WORK.
7. SUBMIT WRITTEN REQUEST FOR INFORMATION WHERE CONSTRUCTABILITY ISSUES ARE ENCOUNTERED IN THE FIELD. PROVIDE A FULL DESCRIPTION OF THE ISSUE AND RECOMMENDED SOLUTIONS. INCLUDE SKETCHES FOR EACH OPTION ALONG WITH ANY ASSOCIATED CHANGE
ORDER COST ESTIMATES.
8. ANY DEVIATIONS FROM THE DRAWINGS MUST BE APPROVED IN WRITING BY THE ENGINEER OF RECORD. ANY CHANGES OR MODIFICATIONS MADE WITHOUT CONSENT MAY RESULT IN WORK BEING REMOVED AND INSTALLED ACCORDING TO THE PLANS.
9. SPECIFICATIONS AND DRAWINGS ARE COMPLEMENTARY, AND MUST BE USED IN COMBINATION TO OBTAIN COMPLETE CONSTRUCTION INFORMATION. SUBMIT WRITTEN REQUEST FOR INFORMATION IF ANY DISCREPANCIES BETWEEN SPECIFICATION AND DRAWINGS ARE FOUND.
10. PROVIDE ONLY NEW MATERIALS AND EQUIPMENT FROM REPUTABLE MANUFACTURERS REGULARLY ENGAGED IN THE MANUFACTURE OF SUCH PRODUCTS. PERFORM ALL WORK IN A PROFESSIONAL MANNER BY WORKERS SKILLED IN THE TYPE OF WORK BEING PERFORMED.
11. KEEP THE WORK SITE AND SURROUNDING AREA FREE FROM ACCUMULATION OF WASTE MATERIALS GENERATED BY WORK PERFORMED UNDER THIS CONTRACT. REMOVE CONSTRUCTION DEBRIS FROM THE WORK SITE DAILY AND DISPOSE OF IT IN A LEGAL MANNER.
12. PROVIDE TWO YEAR WARRANTY FOR ALL WORK (MATERIALS, LABOR, AND EQUIPMENT) FOR A PERIOD OF TWO YEARS COMMENCING WITH THE DATE OF ACCEPTANCE OF ALL WORK BY THE OWNER UNLESS OTHERWISE NOTED IN THE SPECIFICATIONS.
13. OBTAIN ALL LICENSES AND PERMITS REQUIRED BY STATE AND LOCAL JURISDICTIONAL AUTHORITIES FOR PERFORMANCE OF WORK.
14. MAINTAIN A RED LINE SET OF RECORD DRAWINGS AT THE JOB SITE THAT REFLECT ACTUAL EXECUTION OF THE WORK INCLUDING UPDATED
EQUIPMENT SCHEDULES, DETAILS, CONTROLS DIAGRAMS AND SEQUENCES AND LOCATIONS OF EQUIPMENT, PIPING, AND DUCTWORK.
PROVIDE THESE DRAWINGS IN CAD AND PDF FORMAT TO THE OWNER (AS-BUILT DRAWINGS) WITHIN 90 DAYS OF SYSTEM ACCEPTANCE.
15. DETAILS ARE DIAGRAMMATIC AND ARE INTENDED TO SHOW REQUIRED ACCESSORIES AND RELATIVE ARRANGEMENT OF ELEMENTS OF CONSTRUCTION. CONTRACTOR SHALL ADAPT INSTALLATION RELATIVE TO SITE CONDITIONS AND MANUFACTURER’S INSTALLATION
INSTRUCTIONS.
MECHANICAL INSTALLATION NOTES
1. COMPLETE ALL TESTS BEFORE ANY INSULATION IS APPLIED.
2. LOCATE PRESSURE, TEMPERATURE, AND FLOW MEASURING DEVICES IN ACCESSIBLE LOCATIONS WITH STRAIGHT SECTIONS OF DUCT/PIPE
UPSTREAM/DOWNSTREAM IN ACCORDANCE WITH MANUFACTURER’S RECOMMENDATIONS.
3. THE PRODUCT OF A SINGLE MANUFACTURER SHALL BE USED FOR EACH ITEM OF THE SAME EQUIPMENT TYPE.
4. INSTALL ALL CONTROL WIRE IN CONDUIT. CONTROL WIRE AND CONDUIT SHALL COMPLY WITH THE NATIONAL ELECTRIC CODE AND THE
ELECTRICAL SPECIFICATIONS.
5. PROVIDE ACCESS PANELS/DOORS IN CEILINGS, WALLS, FLOORS, AND DUCTWORK FOR ALL ITEMS REQUIRING ADJUSTMENT, TESTING, OR
INSPECTION INCLUDING SMOKE DETECTORS, FIRE DAMPERS, SMOKE DAMPERS, VOLUME DAMPERS, ACTUATORS, FANS, HUMIDIFIERS, COILS, ETC.
6. OF SLAB-TO-SLAB PARTITIONS AND SHAFTS AIRTIGHT TO PRESERVE RETURN AIR PATHWAYS.
7. ALL PIPE SIZES SHOWN ARE NOMINAL SIZES.
8. LOCATE HVAC AIR INTAKE A MINIMUM OF 10 FEET FROM PLUMBING VENTS, EXHAUST OUTLETS, GAS-FIRED EQUIPMENT VENTS, ETC.
MECHANICAL EQUIPMENT INSTALLATION NOTES
1. INSTALL ALL EQUIPMENT IN ACCORDANCE WITH MANUFACTURERS' INSTRUCTIONS AND PER CONTRACT DRAWINGS AND SPECIFICATIONS. IF
MANUFACTURERS' INSTRUCTIONS ARE IN DIRECT CONFLICT WITH INSTRUCTIONS ON THE DRAWINGS OR IN THE SPECIFICATIONS CONTACT THE
ENGINEER OF RECORD FOR CLARIFICATION.
2. COORDINATE WORK WITH OTHER TRADES TO PROVIDE ALL CLEARANCES FOR EQUIPMENT SERVICE AND MAINTENANCE INCLUDING ACCESS TO PANELS, CONTROLS, FILTERS, VALVING, ETC., VERIFY PHYSICAL DIMENSIONS OF EQUIPMENT TO ENSURE THAT ALL CLEARANCES CAN BE MET BEFORE PURCHASING EQUIPMENT. A MINIMUM OF 30 INCHES BY 30 INCHES SHALL BE PROVIDED AT EQUIPMENT ACCESS POINTS. APPLIANCES AND EQUIPMENT SHALL BE REPLACEABLE WITHOUT REMOVING PERMANENT CONSTRUCTION AND ACCESS TO EQUIPMENT SHALL BE PROVIDED PER IMC ACCESS AND SERVICE SPACE REQUIREMENTS WHERE APPLICABLE (E.G. PERMANENT LADDER, UNOBSTRUCTED PASSAGEWAYS, CONTINUOUS FLOORING, LIGHTING, ETC.).
3. WHERE EXPOSURE TO LIVE ELECTRICAL CONNECTIONS IS LIKELY DURING MAINTENANCE ACTIVITIES MAINTAIN NEC WORKING CLEARANCES: 36 INCHES WORKING CLEARANCE IN FRONT OF ELECTRICAL ACCESS PANELS LESS THAN 150 VOLTS (TO GROUND) AND 42 INCHES WORKING CLEARANCE IN FRONT OF ELECTRICAL ACCESS PANELS 151 VOLTS (TO GROUND) OR MORE WHILE ALSO MAINTAINING A CLEARANCE OF 30 INCH WIDTH OR THE WIDTH OF THE ELECTRICAL ACCESS PANEL, WHICHEVER IS LARGER. 48 INCHES WORKING CLEARANCE IS REQUIRED WHERE
ELECTRICAL ACCESS PANEL ARE FACING EACH OTHER.
4. COORDINATE EQUIPMENT CONNECTIONS WITH MANUFACTURER’S CERTIFIED DRAWINGS, PROVIDE ALL PIPE AND DUCT TRANSITIONS AS
REQUIRED TO CONNECT TO EQUIPMENT.
5. PROVIDE VIBRATION ISOLATION FOR ALL EQUIPMENT TO PREVENT TRANSMISSION OF VIBRATION TO BUILDING STRUCTURE.
6. PROVIDE FLEXIBLE DUCT CONNECTIONS AT DUCT CONNECTIONS TO AIR HANDLING UNITS, FANS, AND OTHER EQUIPMENT REQUIRING
VIBRATION ISOLATION.
7. PROVIDE EQUIPMENT DRAIN LINES TO NEAREST DRAIN, PIPE SIZE SHALL BE NO SMALLER THAN DRAIN CONNECTION SIZE. PROVIDE P-TRAP AT
UNIT FOR AIR CONDITIONING UNIT CONDENSATE DRAINS AND ROUTE TO STORM DRAIN / ROOF DRAIN. SLOPE CONDENSATE DRAIN AT A
MINIMUM OF 1/8 INCH PER FOOT.
8. FIELD-ERECTED AND FACTORY-ASSEMBLED AIR HANDLING UNIT COILS SHALL BE ARRANGED FOR REMOVAL FROM THE UPSTREAM SIDE WITHOUT DISMANTLING SUPPORTS. PROVIDE GALVANIZED STRUCTURAL STEEL SUPPORTS FOR ALL COILS IN BANKS OVER TWO COILS HIGH TO
PERMIT THE INDEPENDENT REMOVAL OF ANY COIL.
9. AIR HANDLING UNITS SHALL OPERATE WITH NO MOISTURE CARRYOVER FROM COOLING COIL.
10. PROVIDE EQUIPMENT WITH MANUFACTURER’S INTEGRAL DISCONNECT AND POWER RECEPTACLE UNLESS OTHERWISE NOTED.
11. REPLACE ALL AIR FILTERS PRIOR TO AIR BALANCING AND CLEAN OUT ALL PIPE STRAINERS PRIOR TO WATER BALANCING.
12. PROVIDE FULL SET OF LAMINATED AS-BUILT SCHEMATIC CONTROL DIAGRAMS, SEQUENCES, POINTS LISTS, AND WIRING DIAGRAMS IN
MECHANICAL ROOM PROVIDE THE SAME ON INSIDE DOOR OF EACH CONTROL PANEL FOR THAT PANEL’S EQUIPMENT.
13. ALL EQUIPMENT SHALL HAVE ENGRAVED NAMEPLATE REFLECTING EQUIPMENT CAPACITIES EITHER PROVIDED BY MANUFACTURER OR
CONTRACTOR. NAMEPLATE SHALL BE READILY VISIBLE AND UNOBSTRUCTED. EACH UNIT SHALL ALSO BE UNIQUELY LABELED AND THE LABEL
SHALL INDICATE THE AREA OF SERVICE FOR THOSE UNITS THAT SERVE REMOTE AREAS.
14. MAINTAIN 10 FEET SEPARATION BETWEEN ROOF MOUNTED EQUIPMENT AND UNPROTECTED ROOF EDGES.
15. PROVIDE DUCT SMOKE DETECTOR IN RETURN DUCT MAIN FOR UNITS WHOSE SUPPLY AIRFLOW EXCEEDS 2,000 CFM. HARD WIRE DUCT
DETECTOR TO AHU FOR SHUT DOWN UPON SMOKE DETECTION AND TIE INTO FIRE ALARM SYSTEM.
16. BASIS OF DESIGN MODEL NUMBERS ARE PROVIDED FOR REFERENCE / CONVENIENCE AND CAN BE ADJUSTED DURING FINAL EQUIPMENT
SELECTIONS. EQUIPMENT SHALL MEET ALL PERFORMANCE CRITERIA AND INCLUDE ALL ACCESSORIES AS SPECIFIED IN THE CONTRACT
DOCUMENTS.
17. AHU ACCESS DOORS SHALL OPEN INTO THE SIDE OF HIGHER STATIC PRESSURE.
MECHANICAL HVAC NOTES
1. RISES AND DROPS IN DUCTWORK, ACCESS DOORS, VOLUME DAMPERS, ETC. ARE INDICATED ON DRAWINGS FOR CLARITY FOR SPECIFIC
LOCATION REQUIREMENTS AND DO NOT INDICATE THE EXTENT OF THE REQUIREMENTS FOR THESE ITEMS.
2. DUCT DIMENSIONS ON DRAWINGS ARE INTERNAL CLEAR DIMENSIONS, INCREASE DUCT SIZE TO COMPENSATE FOR DUCT LINING THICKNESS.
3. PROVIDE SHEET METAL FLASHING FOR EXPOSED DUCTWORK WALL AND CEILING PENETRATIONS.
4. PROTECT ALL NEW AND EXISTING HVAC EQUIPMENT BEFORE AND AFTER INSTALLATION, INCLUDING DUCTWORK, VAV TERMINALS, ZONE
DAMPERS AND DIFFUSERS, FROM DUST AND CONTAMINATION. IF THE HVAC SYSTEM IS USED DURING FIT-OUT CONSTRUCTION, THE PRESCRIPTIVE MEASURES IN SMACNA (CHAPTER 3) SHALL BE FOLLOWED REGARDING SOURCE CONTROL, PATHWAY INTERRUPTION, HOUSEKEEPING AND CLEANUP. CONTRACTOR IS RESPONSIBLE FOR CLEANUP COST FOR EQUIPMENT AND DUCTWORK CONTAMINATED WITH CONSTRUCTION DUST INCLUDING VACUUM CLEANING THE PLENUM SPACE ABOVE THE CEILING. FOLLOWING ARE PROCEDURES TO PROTECT THE DUCTWORK: SEAL ALL DUCT OPENINGS, BOTH SUPPLY AND RETURN, AND WRAP ALL EQUIPMENT WITH PLASTIC. PLACE FILTER MEDIA (NO LESS THAN MERV 8 RATED FILTERS) AT ALL OPENINGS FOR RETURN AIR INCLUDING RETURN GRILLES IN THE CEILING OR NEGATIVE PRESSURE SIDE OF THE SYSTEM. REGULARLY REPLACE THE FILTER MEDIA, NO LESS THAN ONCE PER WEEK, FOR THE DURATION OF CONSTRUCTION.
INSTITUTE DAILY CLEANING ACTIVITIES, SUCH AS USING WETTING AGENTS TO MINIMIZE AIRBORNE DUSTS. VACUUM CLEAN WITH HEPA FILTERS
FOR FINAL CLEANING.
5. MAINTAIN 10 FEET SEPARATION BETWEEN MECHANICAL EXHAUST OUTLETS AND OUTDOOR AIR INTAKES.
6. AIR INTAKE OPENINGS LOCATED OUTDOORS SHALL BE PROTECTED WITH CORROSION-RESISTANT SCREENS, LOUVERS, OR GRILLES WITH
OPENINGS BETWEEN 1/4 INCH AND 1 INCH.
MECHANICAL PIPING NOTES
1. INSTALL PIPING SO THAT ALL VALVES, STRAINERS, UNIONS, TRAPS, AND OTHER APPURTENANCES REQUIRING MAINTENANCE ARE ACCESSIBLE.
2. SUPPORT PIPING SYSTEMS AND PROTECT AGAINST PHYSICAL DAMAGE AND EXCESSIVE STRESSES IN ACCORDANCE WITH MSS SP-58, PIPE
HANGERS AND SUPPORTS - MATERIALS, DESIGN, MANUFACTURE, SELECTION, APPLICATION, AND INSTALLATION.
3. PRESSURE TEST AND CLEAN/FLUSH ALL PIPING BEFORE PUTTING INTO SERVICE.
4. DO NOT ROUTE PIPING OVER ELECTRICAL PANELS, TRANSFORMERS, OR ELECTRICAL EQUIPMENT.
5. PROVIDE PROTECTIVE STEEL SHIELD PLATES PER IMC WHERE CONCEALED PIPING IS INSTALLED NEAR EDGE OF STUDS, JOISTS, RAFTERS, ETC.
MECHANICAL EXISTING CONDITIONS NOTES
1. COORDINATE ALL CONSTRUCTION ACTIVITY WITH THE OWNER OR HIS/HER REPRESENTATIVE TO MINIMIZE DISRUPTION TO BUILDING
OPERATIONS.
2. VISIT THE SITE AND FIELD VERIFY EXISTING CONDITIONS PRIOR TO BEGINNING WORK. COORDINATE WORK WITH EXISTING CONDITIONS. SUBMIT
WRITTEN REQUEST FOR INFORMATION IF ANY DISCREPANCIES OR INTERFERENCES ARE DETECTED.
3. PROTECT ALL EXISTING WORK WHICH IS TO REMAIN IN PLACE. ANY EXISTING WORK TO REMAIN WHICH IS DAMAGED DURING CONSTRUCTION
SHALL BE REPLACED AT NO ADDITIONAL COST TO THE OWNER. THE QUALITY OF REPLACED WORK SHALL MATCH THE EXISTING CONDITIONS.
4. REMOVE AND REINSTALL OR RELOCATE ANY MOVEABLE OBSTRUCTIONS THAT MAY IMPEDE WORK UNDER THIS CONTRACT. THESE INCLUDE, BUT ARE NOT LIMITED TO EQUIPMENT, PIPING, AND ANY SUPPORTING APPURTENANCES. ANY CONSTRUCTION REQUIRING WORK STATED ABOVE, SHALL BE RECONNECTED AFTER THE END OF CONSTRUCTION TO PROVIDE A FULLY FUNCTIONAL SYSTEM(S), AS FOUND PRIOR TO
COMMENCING CONTRACT WORK.
5. NEW EQUIPMENT PROTRUDES ABOVE THE HIGHEST POINT OF THE BUILDING OR EXISTING BUILDING EQUIPMENT, SUBMIT AN APPLICATION WITH
THE FAA TO DETERMINE REQUIREMENTS FOR OBSTRUCTION LIGHTING (REF SECTION 5.8.1).
6. XRAY EXISTING STRUCTURE AND LOCATE REINFORCEMENTS PRIOR TO CORE DRILLING/CUTTING.
7. ALL ROOFING WORK INCLUDING PENETRATIONS SHALL BE BY ONE OF THE FOLLOWING ROOFING CONTRACTORS: COLE ROOFING, RUFF
ROOFERS, CITIROOF, TECTA AMERICA. THE EXISTING ROOF WARRANTY SHALL BE MAINTAINED.
MECHANICAL DEMOLITION NOTES
1. VERIFY THAT SYSTEMS ARE NO LONGER IN SERVICE TO ANY AREAS OUTSIDE THE WORK AREA OF THIS CONTRACT PRIOR TO REMOVAL OF
EQUIPMENT, PIPING AND DUCTWORK.
2. FOR ALL AREAS ADJACENT TO THE CONSTRUCTION SITE THAT WILL REMAIN OCCUPIED MAINTAIN ALL SERVICES (AIR SYSTEMS, SERVICE
PIPING, ETC.) TO THESE AREAS AS INDICATED, AS REQUIRED AND AS DIRECTED BY THE OWNER’S REPRESENTATIVE IN THE FIELD.
3. NOTIFY THE OWNER AT LEAST 7 DAYS IN ADVANCE OF ANY REQUIRED SHUTDOWN OF SERVICE UTILITIES, HVAC SYSTEMS, ETC. UPON RECEIPT
OF APPROVAL FROM THE OWNER, PERFORM SHUTDOWNS ON PREMIUM TIME BETWEEN THE HOURS OF 7 PM AND 7 AM UNLESS OTHERWISE
DIRECTED BY THE OWNER.
4. DISCONNECT EXISTING PIPING AND DUCTS NO LONGER REQUIRED TO REMAIN IN SERVICE AND REMOVE BACK TO PIPE AND DUCT MAINS, INCLUDING ASSOCIATED HANGERS, SUPPORTS, AND AIR DEVICES. CAP EXISTING PIPE AND DUCTS AT EXTENT OF DEMOLITION. DUE TO CONCEALMENT, THE EXTENT OF THE EXISTING DUCTWORK AND PIPING SYSTEMS MAY NOT BE FULLY SHOWN OR MAY DIFFER FROM THAT SHOWN. CONTRACTOR IS RESPONSIBLE FOR REMOVING ALL EQUIPMENT, DUCTWORK, PIPING, HANGERS, INSULATION, CONTROLS, AND
APPURTENANCES AS PART OF SYSTEMS INDICATED TO BE REMOVED.
5. PATCH, REPAIR, AND PAINT ALL SURFACES TO MATCH ADJACENT SURFACES NOT SCHEDULED FOR DEMOLITION THAT ARE DAMAGED OR OTHERWISE MARKED DUE TO REMOVAL OF EXISTING EQUIPMENT, DUCTWORK AND RELATED APPURTENANCES.
6. INFILL, PATCH, REPAIR, AND PAINT ALL VOIDS IN WALLS / FLOORS / ROOFS WHERE MECHANICAL SYSTEMS WERE REMOVED. MATCH ADJACENT
EXISTING CONSTRUCTION AND MAINTAIN EXISTING FIRE RATINGS WHERE APPLICABLE.
7. PROTECT ALL EQUIPMENT AND MATERIALS WHICH ARE INDICATED TO BE RELOCATED, REUSED, OR SALVAGED THROUGHOUT THE WORK.
8. CAPTURE AND DISPOSE OF REFRIGERANT PER SECTION 608 OF THE CLEAN AIR ACT.
9. COORDINATE WITH OWNER WHAT EQUIPMENT IS TO BE SALVAGED AND TURN THIS EQUIPMENT OVER TO OWNER. REMOVE EQUIPMENT TO BE
DEMOLISHED FROM SITE AND DISPOSE OF IN ACCORDANCE WITH APPLICABLE REGULATIONS.
MECHANICAL SPECIFICATIONS
SECTION 013300 – SUBMITTAL PROCEDURES
1. COORDINATE TRANSMITTAL OF DIFFERENT TYPES OF SUBMITTALS FOR RELATED PARTS OF THE WORK SO PROCESSING WILL NOT BE
DELAYED BECAUSE OF NEED TO REVIEW SUBMITTALS CONCURRENTLY FOR COORDINATION.
2. ALLOW ENOUGH TIME FOR SUBMITTAL REVIEW, INCLUDING TIME FOR RESUBMITTALS. TIME FOR REVIEW SHALL COMMENCE ON THE ENGINEER OF RECORD'S RECEIPT OF SUBMITTAL. NO EXTENSION OF THE CONTRACT TIME WILL BE AUTHORIZED BECAUSE OF FAILURE TO TRANSMIT SUBMITTALS ENOUGH IN ADVANCE OF THE WORK TO PERMIT PROCESSING, INCLUDING RESUBMITTALS. ALLOW 15 WORKING DAYS FOR REVIEW OF INITIAL SUBMITTAL AND 10 WORKING DAYS FOR RESUBMITTALS.
3. INDICATE NAME AND CONTACT INFORMATION OF FIRM THAT PREPARED EACH SUBMITTAL, NUMBER AND TITLE OF APPROPRIATE SPECIFICATION SECTION, DATE SUBMITTED, AND PROJECT NAME. IF A RESUBMITTAL INDICATE AS SUCH VIA A NUMERICAL SUFFIX (E.G.
REV 2) ASSOCIATED WITH THE NUMBER OF RESUBMISSIONS.
4. MAKE RESUBMITTALS IN THE SAME FORM AND CONTENT AS INITIAL SUBMITTAL, INDICATE EXTENT OF REVISIONS. INDICATE ANY CHANGES TO ORIGINAL CONTENT, ORIGINAL CONTENT WILL NOT BE REVIEWED IN RESUBMITTALS.
5. ORGANIZE AND PACKAGE SUBMITTALS INDIVIDUALLY PER SPECIFICATION NUMBER / SCOPE. SUBMITTALS SHALL BE A COMPLETE PACKAGE PER ASSOCIATED SPECIFICATION SECTION, E.G. DO NOT SUBMIT PARTIAL SUBMITTALS SUCH AS INDOOR DUCT INSULATION SEPARATE FROM OUTDOOR DUCT INSULATION. INDICATE WHICH MATERIALS ARE INTENDED FOR WHICH SYSTEMS, E.G. DIFFERENTIATE CHILLED WATER PIPING INSULATION FROM HOT WATER PIPING INSULATION. DO NOT MIX MATERIALS FROM DIFFERING SPECIFICATION SECTIONS UNDER A COMMON SUBMITTAL SUCH AS COMBINING HYDRONIC PIPING AND DOMESTIC WATER PIPING.
6. LABEL EQUIPMENT/FIXTURE SUBMITTALS AND CUT SHEETS WITH IDENTIFICATION MARK FROM DESIGN SCHEDULE. ORGANIZE WITH
TABLE OF CONTENTS COVER SHEET.
7. REVIEW EACH SUBMITTAL AND CHECK FOR COORDINATION WITH OTHER WORK OF THE CONTRACT AND FOR COMPLIANCE WITH THE CONTRACT DOCUMENTS. MARK WITH APPROVAL STAMP BEFORE SUBMITTING. STAMP SHALL INCLUDE PROJECT NAME AND LOCATION, SUBMITTAL NUMBER, SPECIFICATION SECTION TITLE AND NUMBER, NAME OF REVIEWER, DATE OF CONTRACTOR'S APPROVAL, AND STATEMENT CERTIFYING THAT SUBMITTAL HAS BEEN REVIEWED, CHECKED, AND APPROVED FOR COMPLIANCE WITH THE CONTRACT
DOCUMENTS.
8. INDICATE ALL SELECTED FEATURES VIA COVER SHEET MEMO, HIGHLIGHTS, OR MARKUPS ON THE SUBMITTAL.
9. IDENTIFY ANY REQUESTED VARIATIONS / SUBSTITUTIONS (WHERE ALLOWED) THAT DO NOT CONFORM WITH THE CONTRACT
DOCUMENTS VIA COVER SHEET MEMO. CHANGE ORDERS ASSOCIATED WITH SUBSTITUTIONS WILL NOT BE APPROVED.
10. PROVIDE SUBMITTALS FOR SCHEDULED EQUIPMENT AND INCLUDE A COVER SHEET MEMO THAT STATES THE NOTES / REMARKS FROM
THE DESIGN SCHEDULE AND INDICATES COMPLIANCE OR REQUESTED VARIANCE FROM EACH REQUIREMENT. SUBMITTALS SHALL BE
PROJECT SPECIFIC REGARDING EQUIPMENT PERFORMANCE, ORIENTATION, AND CLEARANCES.
11. IN EACH SUBMITTAL INCLUDE THE FOLLOWING INFORMATION: MANUFACTURER'S WRITTEN RECOMMENDATIONS, MANUFACTURER'S PRODUCT SPECIFICATIONS, MANUFACTURER’S OPERATION AND MAINTENANCE MANUAL, MANUFACTURER'S INSTALLATION INSTRUCTIONS, MANUFACTURER'S CATALOG CUTS, WIRING DIAGRAMS SHOWING FACTORY-INSTALLED WIRING, PRINTED PERFORMANCE CURVES, OPERATIONAL RANGE DIAGRAMS, COMPLIANCE WITH SPECIFIED REFERENCED STANDARDS, TESTING BY
RECOGNIZED TESTING AGENCY.
12. PROVIDE SUBMITTALS IN PDF FORMAT THAT CONTAIN REAL TEXT AND ARE SEARCHABLE VIA PDF SOFTWARE.
13. PROVIDE UPDATED SUBMITTAL LOG WITH EACH SUBMITTAL THAT INDICATES STATUS OF EACH SUBMITTAL ORDERED BY SPECIFICATION
SECTION. INCLUDE SUBMITTAL SPECIFICATION NUMBER, NAME, DATES OF SUBMISSION / REVIEW / ACTION, AND CURRENT STATUS /
RESPONSIBLE PARTY.
14. PROVIDE SUBMITTALS FOR ENGINEER’S AND OWNER'S REVIEW.
SECTION 230513 - COMMON MOTOR REQUIREMENTS FOR HVAC EQUIPMENT
1. COMPLY WITH NEMA MG 1 UNLESS OTHERWISE INDICATED. DUTY: CONTINUOUS DUTY AT AMBIENT TEMPERATURE OF 40 DEG C AND AT
ALTITUDE OF 3300 FEET ABOVE SEA LEVEL
2. POLYPHASE MOTORS: NEMA MG 1, DESIGN B, MEDIUM INDUCTION MOTOR, PREMIUM EFFICIENT, AS DEFINED IN NEMA MG SERVICE
FACTOR: 1.15
SECTION 230519 - METERS AND GAGES FOR HVAC PIPING
1. METAL-CASE, COMPACT-STYLE, LIQUID-IN-GLASS THERMOMETERS. ASME B40.200. CAST ALUMINUM 6 INCH NOMINAL SIZE. TUBE: GLASS
WITH MAGNIFYING LENS AND BLUE ORGANIC LIQUID. ACCURACY: PLUS OR MINUS 1 PERCENT OF SCALE RANGE OR ONE SCALE
DIVISION, TO A MAXIMUM OF 1.5 PERCENT OF SCALE RANGE.
2. DIRECT-MOUNTED, METAL-CASE, DIAL-TYPE PRESSURE GAGES. STANDARD: ASME B40.100. CASE: LIQUID FILLED, 4-1/2 INCH NOMINAL DIAMETER. DIAL: NONREFLECTIVE ALUMINUM WITH PERMANENTLY ETCHED SCALE MARKINGS GRADUATED IN PSI. ACCURACY:
GRADE A, PLUS OR MINUS 1 PERCENT OF MIDDLE HALF OF SCALE RANGE.
3. SNUBBERS: ASME B40.100, BRASS; WITH NPS 1/4 ASME B1.20.1 PIPE THREADS AND PISTON-TYPE SURGE-DAMPENING DEVICE. INCLUDE
EXTENSION FOR USE ON INSULATED PIPING.
4. VALVES: BRASS BALL, WITH NPS 1/4 ASME B1.20.1 PIPE THREADS.
5. INSTALL VALVE AND SNUBBER IN PIPING FOR EACH PRESSURE GAGE FOR FLUIDS.
6. INSTALL PRESSURE GAUGES AT INLET AND OUTLET OF EACH PIECE OF EQUIPMENT WITH A HOT WATER CONNECTION.
7. INSTALL THERMOMETERS AT INLET AND OUTLET OF EACH PIECE OF EQUIPMENT WITH A HOT WATER CONNECTION.
8. ADJUST FACES OF METERS AND GAGES TO PROPER ANGLE FOR BEST VISIBILITY.
SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT
1. CARBON-STEEL PIPE HANGERS AND SUPPORTS. DESCRIPTION: MSS SP-58, TYPES 1 THROUGH 58, FACTORY-FABRICATED
COMPONENTS. GALVANIZED METALLIC COATINGS: PREGALVANIZED, HOT-DIP GALVANIZED, OR ELECTRO-GALVANIZED. HANGER RODS:
CONTINUOUS-THREAD ROD, NUTS, AND WASHER MADE OF CARBON STEEL.
2. TRAPEZE PIPE HANGERS. DESCRIPTION: MSS SP-58, TYPE 59, SHOP- OR FIELD-FABRICATED PIPE-SUPPORT ASSEMBLY MADE FROM STRUCTURAL CARBON-STEEL SHAPES WITH MSS SP-58 CARBON-STEEL HANGER RODS, NUTS, SADDLES, AND U-BOLTS.
3. INSULATION-INSERT MATERIAL FOR HOT PIPING. WATER-REPELLENT-TREATED, ASTM C533, TYPE I CALCIUM SILICATE WITH 100-PSI MINIMUM COMPRESSIVE STRENGTH. FOR TRAPEZE OR CLAMPED SYSTEMS: INSERT AND SHIELD SHALL COVER ENTIRE CIRCUMFERENCE OF PIPE. FOR CLEVIS OR BAND HANGERS: INSERT AND SHIELD SHALL COVER LOWER 180 DEGREES OF PIPE. INSERT LENGTH: EXTEND 2 INCHES BEYOND SHEET METAL SHIELD FOR PIPING OPERATING BELOW AMBIENT AIR TEMPERATURE.
4. DELEGATED DESIGN: DESIGN TRAPEZE PIPE HANGERS AND EQUIPMENT SUPPORTS, INCLUDING COMPREHENSIVE ENGINEERING ANALYSIS PREPARED AND SIGNED AND SEALED BY A QUALIFIED PROFESSIONAL ENGINEER. HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT SHALL WITHSTAND THE EFFECTS OF GRAVITY LOADS AND STRESSES WITHIN LIMITS AND UNDER CONDITIONS INDICATED ACCORDING TO ASCE/SEI 7. DESIGN SUPPORTS FOR MULTIPLE PIPES CAPABLE OF SUPPORTING COMBINED WEIGHT OF SUPPORTED SYSTEMS, SYSTEM CONTENTS, AND TEST WATER. DESIGN EQUIPMENT SUPPORTS CAPABLE OF SUPPORTING COMBINED
OPERATING WEIGHT OF SUPPORTED EQUIPMENT AND CONNECTED SYSTEMS AND COMPONENTS.
SECTION 230548.13 - VIBRATION CONTROLS FOR HVAC
1. ELASTOMERIC ISOLATION PADS. SINGLE OR MULTIPLE LAYERS OF SUFFICIENT DUROMETER STIFFNESS FOR UNIFORM LOADING OVER
PAD AREA. PAD MATERIAL: OIL- AND WATER-RESISTANT RUBBER
2. COIL-SPRING AND ELASTOMERIC-INSERT HANGER WITH SPRING AND INSERT IN COMPRESSION. FRAME: STEEL, FABRICATED FOR
CONNECTION TO THREADED HANGER RODS AND TO ALLOW FOR A MAXIMUM OF 30 DEGREES OF ANGULAR HANGER-ROD MISALIGNMENT WITHOUT BINDING OR REDUCING ISOLATION EFFICIENCY. OUTSIDE SPRING DIAMETER: NOT LESS THAN 80 PERCENT OF THE COMPRESSED HEIGHT OF THE SPRING AT RATED LOAD. MINIMUM ADDITIONAL TRAVEL: 50 PERCENT OF THE REQUIRED DEFLECTION AT RATED LOAD. OVERLOAD CAPACITY: SUPPORT 200 PERCENT OF RATED LOAD, FULLY COMPRESSED, WITHOUT DEFORMATION OR FAILURE. ELASTOMERIC ELEMENT: MOLDED, OIL-RESISTANT RUBBER OR NEOPRENE. STEEL-WASHER-REINFORCED
CUP TO SUPPORT SPRING AND BUSHING PROJECTING THROUGH BOTTOM OF FRAME.
SECTION 230553 - IDENTIFICATION FOR EQUIPMENT
1. METAL LABELS FOR EQUIPMENT. ANODIZED ALUMINUM, 0.032-INCH MINIMUM THICKNESS, AND HAVING PREDRILLED OR STAMPED
HOLES FOR ATTACHMENT HARDWARE. FASTENERS: STAINLESS-STEEL RIVETS OR SELF-TAPPING SCREWS.
2. PIPE LABELS: PREPRINTED, COLOR-CODED, WITH LETTERING INDICATING SERVICE, AND SHOWING FLOW DIRECTION ACCORDING TO
ASME A13.1. PRETENSIONED PIPE LABELS: PRECOILED, SEMIRIGID PLASTIC FORMED TO COVER FULL CIRCUMFERENCE OF PIPE AND TO
ATTACH TO PIPE WITHOUT FASTENERS OR ADHESIVE.
3. DUCT LABEL CONTENTS: INCLUDE IDENTIFICATION OF DUCT SERVICE USING SAME DESIGNATIONS OR ABBREVIATIONS AS USED ON DRAWINGS; ALSO INCLUDE DUCT SIZE AND AN ARROW INDICATING FLOW DIRECTION. ADHESIVE: CONTACT-TYPE PERMANENT ADHESIVE, COMPATIBLE WITH LABEL AND WITH SUBSTRATE. MULTILAYER, MULTICOLOR, PLASTIC LABELS FOR MECHANICAL
ENGRAVING.
SECTION 230593 - TESTING, ADJUSTING, AND BALANCING FOR HVAC
1. PROVIDE THE FOLLOWING SUBMITTALS: CERTIFIED TAB REPORT, INSTRUMENT CALIBRATION REPORTS.
2. TAB SPECIALISTS QUALIFICATIONS, CERTIFIED BY NEBB OR TABB. INSTRUMENTATION TYPE, QUANTITY, ACCURACY, AND CALIBRATION:
COMPLY WITH REQUIREMENTS IN ASHRAE 111, SECTION 4, "INSTRUMENTATION. ASHRAE/IES 90.1 COMPLIANCE: APPLICABLE
REQUIREMENTS IN ASHRAE/IES 90.1, SECTION 6.7.2.3 - "SYSTEM BALANCING.”
3. EXAMINE THE CONTRACT DOCUMENTS TO BECOME FAMILIAR WITH PROJECT REQUIREMENTS AND TO DISCOVER CONDITIONS IN SYSTEMS DESIGNS THAT MAY PRECLUDE PROPER TAB OF SYSTEMS AND EQUIPMENT. EXAMINE INSTALLED SYSTEMS FOR BALANCING DEVICES, SUCH AS TEST PORTS, GAUGE COCKS, THERMOMETER WELLS, FLOW-CONTROL DEVICES, BALANCING VALVES AND FITTINGS, AND MANUAL VOLUME DAMPERS. VERIFY THAT LOCATIONS OF THESE BALANCING DEVICES ARE APPLICABLE FOR INTENDED PURPOSE AND ARE ACCESSIBLE. EXAMINE THE APPROVED SUBMITTALS FOR HVAC SYSTEMS AND EQUIPMENT. EXAMINE TEMPORARY AND PERMANENT STRAINERS. VERIFY THAT TEMPORARY STRAINER SCREENS USED DURING SYSTEM CLEANING AND FLUSHING HAVE BEEN
REMOVED AND PERMANENT STRAINER BASKETS ARE INSTALLED AND CLEAN.
4. PERFORM TESTING AND BALANCING PROCEDURES ON EACH SYSTEM IN ACCORDANCE WITH THE PROCEDURES CONTAINED IN AABC'S "NATIONAL STANDARDS FOR TOTAL SYSTEM BALANCE" AND IN THIS SECTION. MARK EQUIPMENT AND BALANCING DEVICES, INCLUDING DAMPER-CONTROL POSITIONS, VALVE POSITION INDICATORS, FAN-SPEED-CONTROL LEVERS, AND SIMILAR CONTROLS AND DEVICES, WITH PAINT OR OTHER SUITABLE, PERMANENT IDENTIFICATION MATERIAL TO SHOW FINAL SETTINGS.
SECTION 230923.23 – PRESSURE INSTRUMENTS
1. DUCT INSERTION STATIC PRESSURE SENSOR. SENSOR WITH FOUR RADIAL HOLES OF 0.04-INCH DIAMETER. BRASS OR STAINLESS-
STEEL CONSTRUCTION. SENSOR WITH THREADED END SUPPORT, SEALING WASHERS AND NUTS.
2. LIQUID-PRESSURE DIFFERENTIAL TRANSMITTER. RANGE: APPROXIMATELY 2 TIMES SET POINT. SPAN: ADJUSTABLE PLUS OR MINUS ONE
MILLIAMP, NONINTERACTIVE. ACCURACY: WITHIN 0.25 PERCENT OF FULL SCALE. PRESSURE: MAXIMUM OPERATING PRESSURE 2.5 TIMES RANGE. ALUMINUM AND STAINLESS-STEEL ENCLOSURE WITH REMOVABLE COVER. WETTED PARTS OF TRANSMITTER
CONSTRUCTED OF 17-4 PH OR 300 SERIES STAINLESS STEEL.
SECTION 230923.27 – TEMPERATURE INSTRUMENTS
1. THERMISTOR, SINGLE-POINT DUCT AIR TEMPERATURE SENSORS. PROBE: SINGLE-POINT SENSOR WITH A STAINLESS-STEEL SHEATH.
LENGTH: AS REQUIRED BY APPLICATION TO ACHIEVE TIP AT MIDPOINT OF AIR TUNNEL, UP TO 18 INCHES. ENCLOSURE: JUNCTION BOX WITH REMOVABLE COVER; NEMA 250, TYPE 1 FOR INDOOR APPLICATIONS AND TYPE 4 FOR OUTDOOR APPLICATIONS.
2. THERMOWELLS. BRASS OR STAINLESS STEEL FURNISHED WITH HEAT-TRANSFER COMPOUND TO ELIMINATE AIR GAP BETWEEN WALL
OF SENSOR AND THERMOWELL AND TO REDUCE TIME CONSTANT.
SECTION 231123 - FACILITY NATURAL-GAS PIPING
1. PROVIDE THE FOLLOWING SUBMITTALS: PRODUCT DATA.
2. NATURAL-GAS SYSTEM PRESSURES WITHIN BUILDINGS: TWO PRESSURE RANGES. PRIMARY PRESSURE IS MORE THAN 0.5 PSIG BUT
NOT MORE THAN 2 PSIG, AND IS REDUCED TO SECONDARY PRESSURE OF 0.5 PSIG OR LESS.
3. ABOVEGROUND PIPING: STEEL PIPE: ASTM A53/A53M, BLACK STEEL, SCHEDULE 40, TYPE E OR S, GRADE B. MALLEABLE-IRON THREADED
FITTINGS: ASME B16.3, CLASS 150, STANDARD PATTERN.
4. OUTDOOR, APPLIANCE FLEXIBLE CONNECTORS: COMPLY WITH ANSI Z21.75. MAXIMUM LENGTH: 72 INCHES.
5. QUICK-DISCONNECT DEVICES: COMPLY WITH ANSI Z21.41. COPPER-ALLOY CONVENIENCE OUTLET AND MATCHING PLUG CONNECTOR.
HAND OPERATED WITH AUTOMATIC SHUTOFF WHEN DISCONNECTED. ADJUSTABLE, RETRACTABLE RESTRAINING CABLE.
6. Y-PATTERN STRAINERS. BODY: ASTM A126, CLASS B, CAST IRON WITH BOLTED COVER AND BOTTOM DRAIN CONNECTION. STRAINER
SCREEN: 40 MESH STARTUP STRAINER, AND PERFORATED STAINLESS-STEEL BASKET WITH 50 PERCENT FREE AREA. CWP RATING: 125
PSIG.
7. WEATHERPROOF VENT CAP: CAST- OR MALLEABLE-IRON INCREASER FITTING WITH CORROSION-RESISTANT WIRE SCREEN, WITH FREE AREA AT LEAST EQUAL TO CROSS-SECTIONAL AREA OF CONNECTING PIPE AND THREADED-END CONNECTION.
8. TWO-PIECE, FULL-PORT, BRONZE BALL VALVES WITH BRONZE TRIM: MSS SP-110. BODY: BRONZE, COMPLYING WITH ASTM B584. BALL:
CHROME-PLATED BRONZE. SERVICE: SUITABLE FOR NATURAL-GAS SERVICE WITH "WOG" INDICATED ON VALVE BODY.
9. LINE…
This is the start of the file's text. The full file is on GovTribe.