The attached document is an inventory of cross-connection control and backflow prevention assemblies (BFPAs) at Fort Hamilton in Brooklyn, New York. It identifies the location of 364 BFPAs across various buildings on the installation, including fire suppression systems, building main services, boiler feeds, irrigation systems, kitchen equipment, and hose bibbs. For each BFPA, the inventory provides details on the asset identification number, degree of hazard, type of assembly installed including manufacturer and serial number, required assembly, deficiencies, and comments. The purpose is to conduct testing, repairs, and installations of cross-connection controls and BFPAs at Fort Hamilton under solicitation number W15QKN-20-Q-5417 from the Department of the Army Materiel Command Contracting Command at Picatinny Arsenal. Response is due by dates listed in the solicitation.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| W15QKN-20-Q-5417 Amendment 0002.pdf | ||
| W15QKN-20-Q-5417 Amendment 0001.pdf | ||
| W15QKN-20-Q-5417 CCC_BFPA.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
APPENDIX D
CROSS-CONNECTION CONTROL AND BACKFLOW PREVENTION
TOTAL INVENTORY,
U.S. ARMY GARRISON FORT HAMILTON,
NEW YORK
Cross-Connection Control and Backflow Prevention Survey No. S.0052012a-17, 21–31 Aug 17
This appendix provides an inventory of the backflow prevention assemblies (BFPAs) and backflow devices at Fort Hamilton. This table was derived to summarize the findings, and any corrective measures required to eliminate or prevent cross-connections. The table includes the following:
(1) Building number
(2) Location and description of the cross-connection.
(3) Fort Hamilton’s building asset identification number.
(4) Degree of Hazard: High or Low.
(5) The type of BFPA installed, if applicable.
(6) If assembly/device is installed, the information, such as, the make, model, serial number, and size of assembly/device are listed.
(7) If an assembly/device is required at that location it is listed in the table. At some locations, the assembly/device installed is not the BFPA that is required at that location. At various locations, the type of assembly/device installed does not suit the degree of hazard. Therefore, the assembly/device required column is the necessary action needed to correct the deficiency.
(8) If a deficiency or cross-connection is identified and the correction action to eliminate or prevent a cross-connection, it is listed in the deficiency/corrective action column.
(9) Any additional comment(s) or recommendation(s) are listed in the comment/recommendation column and who has ownership and/or operation and maintenance (O&M) responsibility for that building.
(10) Regular lettering indicates domestic water lines and the bold lettering indicates fire lines that are connected to the domestic water line with or without a backflow preventer. The National Standard Plumbing Code, strongly recommends, but does NOT require, the installation of BFPA at these buildings. Where renovations are made to these buildings, the structures would become subject to current regulations necessitating BFPA installations. The italic lettering indicates that a tenant has O&M and testing responsibilities of the device.
D-2
Installation Name: U.S. Army Garrison - Fort Hamilton, New York; Cross-Connection Control Survey, BFPA Total Inventory; 21 - 31 August 2017
BLDG. #
LOCATION & DESCRIPTION OF XC
ASSET ID
| HAZARD CLASS |
| ASSEMBLY INSTALLED |
| MANUFACTURER OF ASSEMBLY |
| MODEL OF ASSEMBLY |
| SERIAL |
NUMBER OF ASSEMBLY
SIZE
| ASSEMBLY REQUIRED |
| DEFICIENCY/CORRECTIVE ACTION |
COMMENT/RECOMMENDATION
| 101 |
| ARNG Storage |
No potable water connection.
| 102 |
| ARNG Storage |
No potable water connection.
ARNG Vehicle Maint. Building's Main Service Maintenance Bay (Wall East Side)
High
DC
Watts
007 M1QT
168777
2 "
RP
Insufficient protection for this type of building hazard (i.e., auto/ maintenance shop). Replace the existing assembly that is on the building's domestic water service line with an approved RP assembly. Also, the assembly will be required to be inspected and tested semiannually.
No inspection tag.
ARNG Vehicle Maint. Potable Hose Bibbs (3) Inside Maintenance Bay
Low
HBVB (3)
N/A
N/A
N/A
N/A
HBVB (3)
N/A
ARNG Vehicle Maint. Potable Hose Bibbs (5) Inside Maintenance Bay
Low
None
N/A
N/A
N/A
N/A
HBVB (5)
Unprotected cross-connections. Install an approved HBVB device on each hose bibb.
These hose bibbs were located on the eyewash temper water lines.
ARNG Vehicle Maint. Potable Hose Bibbs (2) Outside (West Side of Bldg.)
Low
HBVB (2)
N/A
N/A
N/A
N/A
HBVB (2)
| 104 |
| ARNG Storage |
No potable water connection.
ARNG Vehicle Maint. Fire Suppression System Maintenance Bay (East Side)
Low
DC
Ames
2000 SS
166981 1010
6 "
DC
Ensure that the assembly meets all inspection and testing requirements (i.e., annually).
ARNG Vehicle Maint. Building's Main Service Maintenance Bay (Wall East Side)
High
RP
Watts
009 M2QT
140073
1.5 "
RP
Ensure that the assembly meets all inspection and testing requirements (i.e., semiannually).
ARNG Vehicle Maint.
Utility Sink Bathroom Section (East Side)
High
AVB
N/A
N/A
N/A
0.75 "
AVB
ARNG Vehicle Maint. Potable Hose Bibb Outside (North Side of Bldg.)
Low
HBVB
N/A
N/A
N/A
N/A
HBVB
ARNG Vehicle Maint. Potable Hose Bibb Outside (South Side of Bldg.)
Low
None
N/A
N/A
N/A
N/A
Unprotected cross-connection. Install an approved HBVB device on the hose bibb.
| 106 |
| Washing Platform |
No potable water connection.
D-3
Installation Name: U.S. Army Garrison - Fort Hamilton, New York; Cross-Connection Control Survey, BFPA Total Inventory; 21 - 31 August 2017
LOCATION & DESCRIPTION OF XC
ASSET ID
| HAZARD CLASS |
| ASSEMBLY INSTALLED |
| MANUFACTURER OF ASSEMBLY |
| MODEL OF ASSEMBLY |
| SERIAL |
NUMBER OF ASSEMBLY
SIZE
| ASSEMBLY REQUIRED |
| DEFICIENCY/CORRECTIVE ACTION |
COMMENT/RECOMMENDATION
IHG Hotel Fire Suppression System Sprinkler/Mechanical Room
Low
DCDA
Febco
F0408301303
6 "
DCDA
The inspection tag was dated 25 January 2017. The IHG Hotel has the responsibility to inspect and test the assembly.
IHG Hotel Fire Suppression System (Bypass Assembly) Sprinkler/Mechanical Room
Low
DC
Febco
805 YB
F 000103
0.75 "
DC
The inspection tag was dated 25 January 2017. The IHG Hotel has the responsibility to inspect and test the assembly.
IHG Hotel Building's Main Service Sprink ler/Mechanical Room
Low
RP
Wilkins
124482
3 "
RP
N/A The inspection tag was dated 25 January 2017. The IHG Hotel has the responsibility to inspect and test the assembly.
IHG Hotel Potable Hose Bibbs (4) Outside
Low
AVB (4)
N/A
N/A
N/A
N/A
AVB (4)
Garrison Headquarters Fire Suppression System Mechanical Room (Basement)
Low
DC
Ames
2000 SS
127174 0602
4 "
DC
N/A No inspection tag. However, the assembly was tested in May 2017, which was obtained from the Installation O&M Contractor's annual test report.
Garrison Headquarters Building's Main Service Mechanical Room (Basement)
Low
RP
Conbraco
42208 A2
PG320
2 "
DC
N/A No inspection tag. However, the assembly was tested in May 2017, which was obtained from the Installation O&M Contractor's
Garrison Headquarters Boiler Feed Makeup Mechanical Room (Basement)
High
RP
Wilkins
975 XL2
3968990
1 "
RP
Ensure that the assembly meets all inspection and testing requirements (i.e., annually).
Garrison Headquarters Janitor Sink Janitor Closet (Men's Restroom)
High
AVB
N/A
N/A
N/A
N/A
Garrison Headquarters Potable Hose Bibb Outside
Low
HBVB
N/A
N/A
N/A
N/A
Administrative (Former Health Clinic) Fire Suppression System Logistics NCO Room (Basement)
Low
Single Check
Kennedy Automatic Sprinkler
Model E
N/A
6 "
Single Check
Ensure that the single check valve parts are replaced every five years and record the date of installation of the new parts on the inspection tag.
A single check valve or fire alarm valve is not considered an adequate BFPA. Strongly recommend the installation of a BFPA (DC or DCDA) on the intake line supplying the fire system; however, it is NOT a requirement, and would require hydraulic analysis.
D-4
Installation Name: U.S. Army Garrison - Fort Hamilton, New York; Cross-Connection Control Survey, BFPA Total Inventory; 21 - 31 August 2017
LOCATION & DESCRIPTION OF XC
ASSET ID
| HAZARD CLASS |
| ASSEMBLY INSTALLED |
| MANUFACTURER OF ASSEMBLY |
| MODEL OF ASSEMBLY |
| SERIAL |
NUMBER OF ASSEMBLY
SIZE
| ASSEMBLY REQUIRED |
| DEFICIENCY/CORRECTIVE ACTION |
Administrative (Former Health Clinic) Building's Main Service Communication Room B115 (Basement)
Low
None
N/A
N/A
N/A
2 "
DC
| Unprotected cross-connection for this type of building hazard. Install an approved DC assembly on the building's domestic water service connection. Also, the assembly will be required to be inspected and tested annually. |
| The water purveyor (NYC DEP) requires an approved DC assembly to be installed on the building's domestic water service connection due to the treated water for the boiler and chiller units. Plus the building had a complex plumbing |
system.
Administrative (Former Health Clinic) Boiler Feed Makeup Mechanical Room (Basement)
High
RP
Watts
009 M3QT
A 54722
0.75 "
RP
Administrative (Former Health Clinic) Chiller Water Feed Makeup Mechanical Room (Basement)
High
None
N/A
N/A
N/A
0.75 "
RP
Unprotected high-hazard (chemical inhibitor additive) cross-connection. Install an approved RP assembly on the makeup water line to the chiller unit. Also, this assembly will be required to be inspected and tested annually.
Administrative (Former Health Clinic) Janitor Sinks (2) Janitor Closets (Basement & Room 111)
High
AG (1)
& AVB (1)
N/A
N/A
N/A
N/A
AG (1)
& AVB (1)
Administrative (Former Health Clinic) Utility Sink w/Soap Janitor Closet Room 238
High
AVB/DCIAV
N/A
N/A
N/A
N/A
AVB/DCIAV
The installed soap dispenser was ASSE 1055 B approved (i.e., built-in AG/DCIAV).
Administrative (Former Health Clinic) Potable Hose Bibb Inside Janitor Closet (Basement)
Low
None
N/A
N/A
N/A
N/A
Unprotected cross-connection. Install an approved HBVB device on the hose bibb.
Administrative (Former Health Clinic) Potable Hose Bibbs (2) Inside (Basement Bathrooms)
Low
None
N/A
N/A
N/A
N/A
HBVB (2)
Unprotected cross-connections. Install an approved HBVB device on each hose bibb.
The hose bibbs were located in the basement bathrooms.
Administrative (Former Health Clinic) Potable Hose Bibbs (2) Inside Mechanical Room
Low
None
N/A
N/A
N/A
N/A
D-5
Installation Name: U.S. Army Garrison - Fort Hamilton, New York; Cross-Connection Control Survey, BFPA Total Inventory; 21 - 31 August 2017
LOCATION & DESCRIPTION OF XC
ASSET ID
| HAZARD CLASS |
| ASSEMBLY INSTALLED |
| MANUFACTURER OF ASSEMBLY |
| MODEL OF ASSEMBLY |
| SERIAL |
NUMBER OF ASSEMBLY
SIZE
| ASSEMBLY REQUIRED |
| DEFICIENCY/CORRECTIVE ACTION |
Administrative (Former Health Clinic) Potable Hose Bibbs (3) Cooling Tower Roof Top
Low
None
N/A
N/A
N/A
N/A
Administrative (Former Health Clinic) Potable Hose Bibbs (2) Outside
Low
AVB (1) &
HBVB (1)
N/A
N/A
N/A
N/A
AVB (1) &
HBVB (1)
The HBVB was located on the west side of the building and the AVB was located on the east side of the building.
Administrative (Former Health Clinic) Potable Hose Bibbs (2) Outside
Low
None
N/A
N/A
N/A
N/A
Commissary Fire Suppression System Sprinkler Control Room (Admin. Area)
Low
RP
Ames
4000 SS
4HN0478
6 "
DC
Commissary Building's Main Service Sprinkler Control Room (Admin. Area)
Low
RP
Febco
9712221350
2.5 "
RP
Ensure that the assembly meets all inspection and testing requirements (i.e., semiannually).
Commissary Boiler Feed Makeup Mechanical Room (Near Boiler Room) 2nd Floor
High
RP
Watts
009 QT
Unknown
1 "
RP
No inspection tag. Also, the serial number on the assembly's information tag was unreadable.
Commissary Heat Coils Feed Makeup Mechanical Room (Near Boiler Room) 2nd Floor
High
RP
Watts
009 QT
Unknown
1 "
RP
No inspection tag. Also, the serial number on the assembly's information tag was unreadable.
Commissary Garbage Disposal Deli Area
High
AVB
T & S
B 969
Unknown
0.5 "
Commissary Kitchen Sinks (3) Produce Area
High
AG (3)
N/A
N/A
N/A
N/A
AG (3)
Commissary Ice Machine Inside (Produce Area)
Low
AG
N/A
N/A
N/A
N/A
AG
D-6
Installation Name: U.S. Army Garrison - Fort Hamilton, New York; Cross-Connection Control Survey, BFPA Total Inventory; 21 - 31 August 2017
LOCATION & DESCRIPTION OF XC
ASSET ID
| HAZARD CLASS |
| ASSEMBLY INSTALLED |
| MANUFACTURER OF ASSEMBLY |
| MODEL OF ASSEMBLY |
| SERIAL |
NUMBER OF ASSEMBLY
SIZE
| ASSEMBLY REQUIRED |
| DEFICIENCY/CORRECTIVE ACTION |
Commissary Kitchen Sinks (3) w/ Soap (1) (4) Meat Area
High
AG (3) & AG/DCIAV (1)
N/A
N/A
N/A
N/A
AG (3) & AG/DCIAV (1)
Commissary Kitchen Sinks (6) Deli Area
High
AG (6)
N/A
N/A
N/A
N/A
AG (6)
Commissary Kitchen Sink Damaged Merchandise Storage
Low
AG
N/A
N/A
N/A
N/A
Commissary Utility Sink Janitor Closet Warehouse Area
High
AVB
N/A
N/A
N/A
N/A
Commissary Potable Hose Bibbs (3) Inside Front Entrance (2) & Office Area (1) Bathrooms
Low
AVB (3)
N/A
N/A
N/A
N/A
AVB (3)
N/A The hose bibbs were located in the customer's men and women bathrooms near the front entrance, and the other was located in the employee's men bathroom near the front admin office.
Commissary Potable Hose Bibbs (2) Outside
Low
HBVB (2)
N/A
N/A
N/A
N/A
Military Entrance Processing Station Fire Suppression System Emergency Exit Room 149
Low
Single Check
Globe Automatic Sprinkler
Model E
N/A
6 "
Single Check
Ensure that the single check valve parts are replaced every five years and record the date of installation of the new parts on the inspection tag.
A single check valve or fire alarm valve is not considered an adequate BFPA. Strongly recommend the installation of a BFPA (DC or DCDA) on the intake line supplying the fire system; however, it is NOT a requirement, and would require
Military Entrance Processing Station Building's Main Service Mechanical Room (Basement)
Low
None
N/A
N/A
N/A
2 "
DC
| Unprotected cross-connection for this type of building hazard. Install an approved DC assembly on the building's domestic water service connection. Also, the assembly will be required to be inspected and tested annually. |
| The water purveyor (NYC DEP) requires an approved DC assembly to be installed on the building's domestic water service connection due to the treated water for the boiler and chiller units. Plus the building had a complex plumbing |
Military Entrance Processing Station Boiler Feed Makeup Mechanical Room (Basement)
High
RP
Watts
009 M3QT
412169
0.75 "
RP
D-7
Installation Name: U.S. Army Garrison - Fort Hamilton, New York; Cross-Connection Control Survey, BFPA Total Inventory; 21 - 31 August 2017
LOCATION & DESCRIPTION OF XC
ASSET ID
| HAZARD CLASS |
| ASSEMBLY INSTALLED |
| MANUFACTURER OF ASSEMBLY |
| MODEL OF ASSEMBLY |
| SERIAL |
NUMBER OF ASSEMBLY
SIZE
| ASSEMBLY REQUIRED |
| DEFICIENCY/CORRECTIVE ACTION |
Military Entrance Processing Station Chiller Feed Makeup Mechanical Room (Basement)
High
RP
Watts
909 QT
580828
0.75 "
RP
Military Entrance Processing Station Garbage Disposal Kitchen Area
High
AVB
Watts
288 A
9436 E
0.5 "
Military Entrance Processing Station Kitchen Sinks (4) Kitchen Area
High
AG (4)
N/A
N/A
N/A
N/A
AG (4)
Military Entrance Processing Station Janitor Sink w/Soap (3) Janitor Closets (1st, 2nd, & 3rd Floors)
High
AVB/DCIAV (3)
N/A
N/A
N/A
N/A
AVB/DCIAV (3)
Military Entrance Processing Station Potable Hose Bibb Outside
Low
HBVB
N/A
N/A
N/A
N/A
HBVB
The HBVB was located on the north side of the building.
Military Entrance Processing Station Potable Hose Bibbs (3) Outside
Low
None
N/A
N/A
N/A
N/A
Administrative Fire Suppression System Waiting Room Entrance (Basement Left Side)
Low
RP
WATTS
909 QT
206677
4 "
DC
The BFPA's drain system was plugged with debris. Remove the debris from the assembly's drain system or replace RP with an approved DC assembly.
No inspection tag. However, the assembly was tested in May 2017, which was obtained from the Installation O&M Contractor's
Administrative Building's Main Service Kitchen Area Entrance (Basement Right Side)
Low
None
N/A
N/A
N/A
2 "
DC or None
Unprotected cross-connection for this type of building hazard. Install an approved DC assembly on the building's domestic water service connection. Also, the assembly will be required to be inspected and tested annually.
The water purveyor (NYC DEP) requires an approved DC assembly to be installed on the building's domestic water service connection due to the treated water for the boiler. However, the building can be rated as non-hazardous (i.e., removal of the chemically treated boiler) and qualify for an exemption from backflow prevention requirements.
D-8
Installation Name: U.S. Army Garrison - Fort Hamilton, New York; Cross-Connection Control Survey, BFPA Total Inventory; 21 - 31 August 2017
LOCATION & DESCRIPTION OF XC
ASSET ID
| HAZARD CLASS |
| ASSEMBLY INSTALLED |
| MANUFACTURER OF ASSEMBLY |
| MODEL OF ASSEMBLY |
| SERIAL |
NUMBER OF ASSEMBLY
SIZE
| ASSEMBLY REQUIRED |
| DEFICIENCY/CORRECTIVE ACTION |
Administrative Boiler Feed Makeup Kitchen Area Entrance (Basement Right Side)
High
None
N/A
N/A
N/A
0.5 "
RP or DCIAV Unprotected high-hazard (chemical inhibitor additive) cross-connection. Install an approved RP assembly or DCIAV device (if no conditioning chemicals are added) on the makeup water line to the boiler unit. Also, the assembly will be required to be inspected and tested annually or annual visual inspection for the DCIAV device.
Administrative Utility Sink Waiting Room Entrance (Basement Left Side)
High
AG
N/A
N/A
N/A
N/A
Administrative Potable Hose Bibbs (3) Waiting Room Entrance (Basement Left Side)
Low
None
N/A
N/A
N/A
N/A
HBVB (3)
Unprotected cross-connections. Install an approved HBVB device on each hose bibb.
If the two hose connections for the washing machine's were no longer used, cap or remove and isolate from the building's plumbing
Administrative Potable Hose Bibb Outside
Low
None
N/A
N/A
N/A
N/A
HBVB
Unprotected cross-connection. Install an approved HBVB device on the hose bibb.
The hose bibb was located on the west side of the building.
No potable water connection.
| 118 A |
| Access Control Facility |
No potable water connection.
118 B
DES Break Room Building's Main Service Bathroom
118 B
Low
None
N/A
N/A
N/A
0.75 "
None
N/A The premise rating for the building is non-hazardous and is qualified for exemption from backflow prevention requirements. The building had a very simple plumbing system (i.e., sink and bathroom only) and these fixture outlets had the appropriate isolation backflow protection.
118 C
Visitor Control Center Building's Main Service Janitor Closet
118 C
Low
None
N/A
N/A
N/A
1 "
None
N/A The premise rating for the building is non-hazardous and is qualified for exemption from backflow prevention requirements. The building had a very simple plumbing system (i.e., sink and bathroom only) and these fixture outlets had the appropriate
Visitor Control Center Utility Sink Janitor Closet
118 C
High
AG
N/A
N/A
N/A
N/A
Visitor Control Center Potable Hose Bibb Outside
118 C
Low
AVB
N/A
N/A
N/A
N/A
AVB
Improper installation. A shutoff valve was installed downstream of an approved AVB device., which needs to be removed.
| 118 E |
| Guard House |
No potable water connection.
D-9
Installation Name: U.S. Army Garrison - Fort Hamilton, New York; Cross-Connection Control Survey, BFPA Total Inventory; 21 - 31 August 2017
LOCATION & DESCRIPTION OF XC
ASSET ID
| HAZARD CLASS |
| ASSEMBLY INSTALLED |
| MANUFACTURER OF ASSEMBLY |
| MODEL OF ASSEMBLY |
| SERIAL |
NUMBER OF ASSEMBLY
SIZE
| ASSEMBLY REQUIRED |
| DEFICIENCY/CORRECTIVE ACTION |
118 F
Guard Shack
118 F
Low
None
N/A
N/A
N/A
0.75 "
None
N/A The premise rating for the building is non-hazardous and is qualified for exemption from backflow prevention requirements. The building had a very simple plumbing system (i.e., sink and bathroom only) and these fixture outlets had the appropriate
Behind the Bldg.
Post Exchange Fire Suppression System & Bldg.'s Main Service Outside Hot Box (Behind the Bldg. 123)
Behind the Bldg.
High
RP
Ames
4000 SS
124209 0910
6 "
RP
The assembly was leaking. Repair or replace assembly. Also, ensure that the assembly meets all inspection and testing requirements (i.e., annually).
Post Exchange Fire Suppression System Class 6 Store (Main Floor Ceiling)
Low
RP
Ames
4000 SS
26987 0313
2.5 "
DC
| May want to remove and plug the BFPA's relief valve or replace RP with an approved DC assembly. |
| No inspection tag. However, the assembly was tested in May 2017, which was obtained from the Installation O&M Contractor's |
Post Exchange Building's Main Service Mechanical Room (Basement)
High
None
N/A
N/A
N/A
2.5 "
RP
Unprotected high-hazard cross- connection for this type of building hazard (i.e., food service/ restaurants and barber shop). Install an approved RP assembly on the building's domestic water service connection. Also, the assembly will be required to be inspected and tested semannually.
Post Exchange Hose Connection Feed Makeup Outside (West side of Bldg.)
High
None
N/A
N/A
N/A
0.75 "
RP
Unprotected high-hazard cross- connection (i.e., food service). Install an approved RP assembly on the makeup water line to the hose connection that supplied domestic water to the vendor. Also, the assembly will be required to be inspected and tested annually.
Post Exchange Kitchen Sinks (2) w/ Soap (2) (4) Burger King Kitchen Area
High
AG (2) AG/DCIAV (2)
N/A
N/A
N/A
N/A
AG (2) AG/DCIAV (2)
Post Exchange Coffee Beverage Feed Makeup Burger King Soda Counter Area
Low
Dual Check
Wilkins
N/A
0.75 "
Dual Check
Ensure to record the installation date on the inspection tag.
The dual check needs to be replaced every 5 years.
D-10
Installation Name: U.S. Army Garrison - Fort Hamilton, New York; Cross-Connection Control Survey, BFPA Total Inventory; 21 - 31 August 2017
LOCATION & DESCRIPTION OF XC
ASSET ID
| HAZARD CLASS |
| ASSEMBLY INSTALLED |
| MANUFACTURER OF ASSEMBLY |
| MODEL OF ASSEMBLY |
| SERIAL |
NUMBER OF ASSEMBLY
SIZE
| ASSEMBLY REQUIRED |
| DEFICIENCY/CORRECTIVE ACTION |
Post Exchange Carbonated Beverage Dispensers (2) Burger King Soda Counter Area
Low
Beverage CO2 Device (2)
N/A
N/A
N/A
N/A
Beverage CO2 Device (2)
Post Exchange Kitchen Sink (1) w/ Soap (1) (2) Subway Kitchen Area
High
AG (1) AG/DCIAV (1)
N/A
N/A
N/A
N/A
AG (1) AG/DCIAV (1)
Post Exchange Carbonated Beverage Dispenser Subway Soda Counter Area
Low
Beverage CO2 Device
N/A
N/A
N/A
N/A
Beverage CO2 Device
Post Exchange Utility Sinks (2) Janitor Closets (Front Entrance & Admin Office Area)
High
AVB (2)
N/A
N/A
N/A
0.75 "
AVB (2)
Post Exchange Utility Sink Burger King (Kitchen Area)
High
AG/DCIAV
N/A
N/A
N/A
0.75 "
AG/DCIAV
The installed soap dispenser was ASSE 1055 B approved (i.e., built-in AG/DCIAV).
Post Exchange Utility Sink Subway (Kitchen Area)
High
AVB/DCIAV
N/A
N/A
N/A
0.75 "
AVB/DCIAV
Improper installation. The shutoff valves (2) were installed downstream of the AVB backflow device.
Remove the device that had the shutoff valve and replace with a device without a shutoff valve or install a field testable hose connection (i.e., ASSE 1052 approval device).
Post Exchange Potable Hose Bibbs (2) Outside
Low
None
N/A
N/A
N/A
N/A
HBVB (2)
Unprotected cross-connections. Install an approved HBVB device on each hose bibb, if needed.
The handle was removed on the south side hose bibb.
Bowling Alley Fire Suppression System Bowling Pin Area (North Side of Bldg.)
Low
Single Check
Kennedy
Model E
N/A
8 "
Single Check
Ensure that the single check valve parts are replaced every five years and record the date of installation of the new parts on the inspection tag.
A single check valve or fire alarm valve is not considered an adequate BFPA. Strongly recommend the installation of a BFPA (DC or DCDA) on the intake line supplying the fire system; however, it is NOT a requirement, and would require
D-11
Installation Name: U.S. Army Garrison - Fort Hamilton, New York; Cross-Connection Control Survey, BFPA Total Inventory; 21 - 31 August 2017
LOCATION & DESCRIPTION OF XC
ASSET ID
| HAZARD CLASS |
| ASSEMBLY INSTALLED |
| MANUFACTURER OF ASSEMBLY |
| MODEL OF ASSEMBLY |
| SERIAL |
NUMBER OF ASSEMBLY
SIZE
| ASSEMBLY REQUIRED |
| DEFICIENCY/CORRECTIVE ACTION |
Bowling Alley Building's Main Service (Top Assembly) Storage Room 104
High
RP
Febco
H 03385
2 "
RP
| Insufficient air gap between the RP assembly and the waste relief system drain cup. Lower the drain cup 1 inch. |
| No inspection tag. However, the assembly was tested in May 2017, which was obtained from the Installation O&M Contractor's |
Bowling Alley Building's Main Service (Bottom Assembly) Storage Room 104
High
RP
Febco
H 03361
2 "
RP
Insufficient air gap between the RP assembly and the waste relief system drain cup. Lower the drain cup 1 inch.
No inspection tag. However, the assembly was tested in May 2017, which was obtained from the Installation O&M Contractor's annual test report. Also, the assembly was shutoff.
Bowling Alley Soap Dispenser Feed Makeup Kitchen Area (Utility Sink)
High
RP
Wilkins
975 XL
W 258508
0.5 "
AG/DCIAV
Overkill for this type of hazard, the assembly may be removed. There was sufficient protection within the soap dispenser (i.e., ASSE 1055 B approved). If not removed, annual inspection and testing will be required.
No inspection tag. The installed soap dispenser was ASSE 1055 B approved (i.e., built-in AG/DCIAV).
Bowling Alley Utility Sink Kitchen Area
High
AVB
N/A
N/A
N/A
0.75 "
Bowling Alley Kitchen Sinks (2) w/ Soap (1) (3) Kitchen Area
High
AG (2) AG/DCIAV (1)
N/A
N/A
N/A
N/A
AG (2) AG/DCIAV (1)
Bowling Alley Beverage Dispenser Feed Makeup Front Counter Area
Low
Dual Check
Wilkins
N/A
0.75 "
Dual Check
Bowling Alley Ice Machine Kitchen Area
Low
Dual Check
Unknown
Unknown
Unknown
0.5 "
Dual Check
| Ensure to record the installation date on the inspection tag. |
| The dual check needs to be replaced every 5 years. Also, the |
device information was unreadable.
Bowling Alley Carbonated Beverage Dispensers (2) Kitchen Area
Low
Beverage CO2 Device (2)
N/A
N/A
N/A
N/A
Beverage CO2 Device (2)
Bowling Alley N-Espresso Machine Feed Makeup Café Room
Low
AVB
Watts
288 A
N/A
0.5 "
Dual Check Insufficient installation of the AVB (i.e., not 6 inches above all downstream piping); however, the machine was no longer being used (i.e., shutoff). If used, replace the AVB device with an approved dual check. Also, ensure to record the installation date on the inspection tag.
D-12
Installation Name: U.S. Army Garrison - Fort Hamilton, New York; Cross-Connection Control Survey, BFPA Total Inventory; 21 - 31 August 2017
LOCATION & DESCRIPTION OF XC
ASSET ID
| HAZARD CLASS |
| ASSEMBLY INSTALLED |
| MANUFACTURER OF ASSEMBLY |
| MODEL OF ASSEMBLY |
| SERIAL NUMBER OF |
ASSEMBLY
SIZE
| ASSEMBLY REQUIRED |
| DEFICIENCY/CORRECTIVE ACTION |
Bowling Alley Kitchen Sink Café Room
Low
AG
N/A
N/A
N/A
N/A
Bowling Alley Kitchen Sink Party Room
Low
AG
N/A
N/A
N/A
N/A
Bowling Alley Utility Sink Storage Room 104
High
AVB
N/A
N/A
N/A
0.75 "
Exchange Warehouse Ice Machine Inside (Warehouse Area)
Low
AG
N/A
N/A
N/A
N/A
Exchange Warehouse Potable Hose Bibb Inside (Warehouse Area)
Low
None
N/A
N/A
N/A
N/A
Unprotected cross-connection. Install an approved HBVB device on the hose bibb.
Bowling Alley Potable Hose Bibb Outside (South Side of Bldg.)
Low
HBVB
N/A
N/A
N/A
N/A
Exchange Warehouse Potable Hose Bibb Outside (North Side of Bldg.)
Low
None
N/A
N/A
N/A
N/A
Unprotected cross-connection. Install an approved HBVB device on the hose bibb.
Warehouse & MWR Area Fire Suppression System MWR Gym Area
Low
Single Check
Globe Automatic Sprinkler
Model E
N/A
6 "
Single Check
Ensure that the single check valve parts are replaced every five years and record the date of installation of the new parts on the inspection tag.
A single check valve or fire alarm valve is not considered an adequate BFPA. Strongly recommend the installation of a BFPA (DC or DCDA) on the intake line supplying the fire system; however, it is NOT a requirement, and would require
Warehouse & MWR Area Building's Main Service MWR Gym Area (Behind Old Refrigerator)
Low
None
N/A
N/A
N/A
2 "
None
N/A The premise rating for the building is non-hazardous and is qualified for exemption from backflow prevention requirements. The building had a very simple plumbing system (i.e., sinks and bathrooms only) and these fixture outlets had the appropriate isolation backflow protection.
Warehouse & MWR Area Utility Sink w/ Threads Janitor Closet Near MWR Bathrooms
High
AG
N/A
N/A
N/A
N/A
AG
Insufficient air gap (the hose line nullifies the air gap). After every use, detach the hose line to create an approved size air gap. Continue this practice until the installation of a service sink faucet or the HBVB on the sink outlet.
The survey team removed the hose line while onsite.
D-13
Installation Name: U.S. Army Garrison - Fort Hamilton, New York; Cross-Connection Control Survey, BFPA Total Inventory; 21 - 31 August 2017
LOCATION & DESCRIPTION OF XC
ASSET ID
| HAZARD CLASS |
| ASSEMBLY INSTALLED |
| MANUFACTURER OF ASSEMBLY |
| MODEL OF ASSEMBLY |
| SERIAL |
NUMBER OF ASSEMBLY
SIZE
| ASSEMBLY REQUIRED |
| DEFICIENCY/CORRECTIVE ACTION |
Warehouse & MWR Area Utility Sink Janitor Closet Thrift Shop Area
High
AG
N/A
N/A
N/A
N/A
Warehouse & MWR Area Drinking Water Fountain Feed Makeup Janitor Closet Near MWR Bathrooms
Low
Dual Check
Unknown
Unknown
Unknown
0.75 "
None
No inspection tag. The dual check needs to be replaced every 5 years. Also, the device information was unreadable.
Warehouse & MWR Area Potable Hose Bibb Inside (Near MWR Bathrooms)
Low
HBVB
N/A
N/A
N/A
N/A
DPW Pest Control Shop Utility Sink DPW/BASOPS Utility Area
High
AG & PVB
Wilkins
290097
1 "
AG & PVB
| Ensure that the assembly meets all inspection and testing requirements (i.e., annually). |
| No inspection tag. Also, the building received domestic water from Building 127 W. |
DPW Pest Control Shop Potable Hose Connection Outside (West Side of Bldg.)
High
BFP
Dual Check
Cash Acme
N/A
N/A
0.5 "
RP
Insufficient protection for this type of hazard (i.e., mixing pesticides).
Install an approved an approved RP assembly on the makeup water line to the outside hose connection.
Also the assembly will be required to be inspected and tested annually.
DPW/BASOPS & LRC
Maintenance Shops Fire Suppression System Maintenance Bay Area
Low
Dry Valve System
Viking
F -1
N/A
3 "
Dry Valve System
DPW/BASOPS & LRC
Maintenance Shops Utility Sinks (3) Laundry, Breakroom, & Welding Areas
High
AG (3)
N/A
N/A
N/A
0.75 "
AG (3)
The building received domestic water from Building 127 W.
127 W
DPW/BASOPS & LRC
Maintenance Shops Fire Suppression System Maintenance Bay Area
127 W
Low
Single Check Alarm Valve
Hodgeman
N/A
N/A
6 "
Single Check Alarm Valve
Ensure that the single check valve parts are replaced every five years and record the date of installation of the new parts on the inspection tag.
A single check valve or fire alarm valve is not considered an adequate BFPA. Strongly recommend the installation of a BFPA (DC or DCDA) on the intake line supplying the fire system; however, it is NOT a requirement, and would require
D-14
Installation Name: U.S. Army Garrison - Fort Hamilton, New York; Cross-Connection Control Survey, BFPA Total Inventory; 21 - 31 August 2017
LOCATION & DESCRIPTION OF XC
ASSET ID
| HAZARD CLASS |
| ASSEMBLY INSTALLED |
| MANUFACTURER OF ASSEMBLY |
| MODEL OF ASSEMBLY |
| SERIAL |
NUMBER OF ASSEMBLY
SIZE
| ASSEMBLY REQUIRED |
| DEFICIENCY/CORRECTIVE ACTION |
DPW/BASOPS & LRC
Maintenance Shops Building's Main Service Mechanical Room
127 W
High
None
N/A
N/A
N/A
2 "
RP
Unprotected high-hazard cross-connection for this type of building hazard (i.e., maintenance shop). Install an approved RP assembly on the building's domestic water service line. Also, the assembly will be required to be inspected and tested semiannually.
Building 127 W also feeds domestic water to Buildings 126 and 127.
DPW/BASOPS & LRC
Maintenance Shops Utility Sink Maintenance Bay Area
127 W
High
AVB
N/A
N/A
N/A
0.75 "
DPW/BASOPS & LRC
Maintenance Shops Potable Hose Bibb Inside (Battery Shop Area)
127 W
Low
None
N/A
N/A
N/A
N/A
DPW/BASOPS & LRC
Maintenance Shops Potable Hose Bibbs (2) Outside
127 W
Low
None
N/A
N/A
N/A
N/A
HBVB (2)
The hose bibbs were located on the north and south side of the building.
RBS BASOPS
Contractor Admin./Shop Fire Suppression System HVAC Area
Low
DCDA
Wilkins
350 ADA
V 05669
6 "
DCDA
N/A No inspection tag. However, the assembly was tested in May 2017, which was obtained from the Installation O&M Contractor's annual test report. Also, the small assembly was removed.
RBS BASOPS Contractor Admin./Shop Building's Main Service Mechanical Room
Low
None
N/A
N/A
N/A
2 "
DC or None
Unprotected cross-connection for this type of building hazard. Install an approved DC assembly on the building's domestic water service connection. Also, the assembly will be required to be inspected and tested annually.
The water purveyor (NYC DEP) requires an approved DC assembly to be installed on the building's domestic water service connection due to the treated water for the boiler. However, the building can be rated as non-hazardous (i.e., removal of the chemically treated boiler) and qualify for an exemption from backflow prevention
RBS BASOPS Contractor Admin./Shop Boiler Feed Makeup Mechanical Room
High
None
N/A
N/A
N/A
0.75 "
RP or DCIAV Unprotected high-hazard (chemical inhibitor additive) cross-connection. Install an approved RP assembly or DCIAV device (if no conditioning chemicals are added) on the makeup water line to the boiler unit. Also, the assembly will be required to be inspected and tested annually or annual visual inspection for the
D-15
Installation Name: U.S. Army Garrison - Fort Hamilton, New York; Cross-Connection Control Survey, BFPA Total Inventory; 21 - 31 August 2017
LOCATION & DESCRIPTION OF XC
ASSET ID
| HAZARD CLASS |
| ASSEMBLY INSTALLED |
| MANUFACTURER OF ASSEMBLY |
| MODEL OF ASSEMBLY |
| SERIAL |
NUMBER OF ASSEMBLY
SIZE
| ASSEMBLY REQUIRED |
| DEFICIENCY/CORRECTIVE ACTION |
RBS BASOPS Contractor Admin./Shop Utility Sink Maintenance Bay Area
High
AVB
N/A
N/A
N/A
0.75 "
RBS BASOPS Contractor Admin./Shop Potable Hose Bibbs (2) Inside (Men/Women Bathrooms)
Low
None
N/A
N/A
N/A
N/A
HBVB (2)
The hose bibbs were located in the men's and women's bathrooms. The hose line to the utility sink in the men's bathroom was removed onsite by the survey team.
RBS BASOPS Contractor Admin./Shop Potable Hose Bibb Inside Mechanical Room
Low
None
N/A
N/A
N/A
N/A
HBVB
Unprotected cross-connection. Install an approved HBVB device on the hose bibb.
The hose bibb was located on the domestic water line connection.
RBS BASOPS Contractor Admin./Shop Potable Hose Bibbs (2) Outside
Low
AVB (1) &
HBVB (1)
N/A
N/A
N/A
N/A
AVB (1) &
HBVB (1)
These hose bibbs were located on the east side of the building.
RBS BASOPS Contractor Admin./Shop Potable Hose Bibbs (4) Outside
Low
None
N/A
N/A
N/A
N/A
HBVB (4)
DPW Administrative Fire Suppression System Office Room (East side of Bldg.)
Low
Single Check Alarm Valve
Victaulic
S/175
N/A
6 "
Single Check Alarm Valve
Ensure that the single check valve parts are replaced every five years and record the date of installation of the new parts on the inspection tag.
A single check valve or fire alarm valve is not considered an adequate BFPA. Strongly recommend the installation of a BFPA (DC or DCDA) on the intake line supplying the fire system; however, it is NOT a requirement, and would require
DPW Administrative Building's Main Service Inside
Low
None
N/A
N/A
N/A
2 "
DC or None
Unprotected cross-connection for this type of building hazard. Install an approved DC assembly on the building's domestic water service connection. Also, the assembly will be required to be inspected and tested annually.
The water purveyor (NYC DEP) requires an approved DC assembly to be installed on the building's domestic water service connection due to the treated water for the boiler. However, the building can be rated as non-hazardous (i.e., removal of the chemically treated boiler) and qualify for an exemption from backflow prevention
D-16
Installation Name: U.S. Army Garrison - Fort Hamilton, New York; Cross-Connection Control Survey, BFPA Total Inventory; 21 - 31 August 2017
LOCATION & DESCRIPTION OF XC
ASSET ID
| HAZARD CLASS |
| ASSEMBLY INSTALLED |
| MANUFACTURER OF ASSEMBLY |
| MODEL OF ASSEMBLY |
| SERIAL |
NUMBER OF ASSEMBLY
SIZE
| ASSEMBLY REQUIRED |
| DEFICIENCY/CORRECTIVE ACTION |
DPW Administrative Boiler Feed Makeup Mechanical Room
High
DCIAV
Watts
BBFP
1520 W
0.5 "
RP
Insufficient protection for this type of hazard (chemical inhibitor additive). Replace the existing device that is on the makeup waterline to the boiler unit with an approved RP assembly. Also, the assembly will be required to be inspected and tested annually.
DPW Administrative Utility Sink Men's Bathroom (South Side of Bldg.)
High
AVB
N/A
N/A
N/A
0.75 "
DPW Administrative Potable Hose Bibbs (3) Outside
Low
HBVB (3)
N/A
N/A
N/A
N/A
DPW Administrative Potable Hose Bibbs (2) Outside
Low
None
N/A
N/A
N/A
N/A
HBVB (2)
| Unprotected cross-connections. Install an approved HBVB device on each hose bibb. |
| These hose bibbs were located on the east and south side of the building. |
Army Corps of Engineers Building's Main Service Mechanical Room (Basement)
Low
None
N/A
N/A
N/A
2 "
DC or None
Unprotected cross-connection for this type of building hazard. Install an approved DC assembly on the building's domestic water service connection. Also, the assembly will be required to be inspected and tested annually.
The water purveyor (NYC DEP) requires an approved DC assembly to be installed on the building's domestic water service connection due to the treated water for the boiler. However, the building can be rated as non-hazardous (i.e., removal of the chemically treated boiler) and qualify for an exemption from backflow prevention
Army Corps of Engineers Boiler Feed Makeup Mechanical Room (Basement)
High
RP
Wilkins
975 XL
2194407
1 "
RP
Ensure that the assembly meets all inspection and testing requirements (i.e., annually).
DPW Administrative Utility Sink Women's Bathroom
High
AVB
N/A
N/A
N/A
0.75 "
Army Corps of Engineers Potable Hose Bibb Inside Mechanical Room
Low
None
N/A
N/A
N/A
N/A
HBVB
Unprotected cross-connections.
Install an approved HBVB device on each hose bibb.
The hose bibb was located on the domestic water line connection.
Army Corps of Engineers Potable Hose Bibb Outside
Low
AVB & HBVB
N/A
N/A
N/A
N/A
AVB & HBVB
Army Corps of Engineers Potable Hose Bibb Outside
Low
None
N/A
N/A
N/A
N/A
HBVB
Unprotected cross-connection. Install an approved HBVB device on the hose bibb.
This hose bibb was located on the south side of the building.
| 133 |
| Transformers |
No potable water connection.
D-17
Installation Name: U.S. Army Garrison - Fort Hamilton, New York; Cross-Connection Control Survey, BFPA Total Inventory; 21 - 31 August 2017
LOCATION & DESCRIPTION OF XC
ASSET ID
| HAZARD CLASS |
| ASSEMBLY INSTALLED |
| MANUFACTURER OF ASSEMBLY |
| MODEL OF ASSEMBLY |
| SERIAL |
NUMBER OF ASSEMBLY
SIZE
| ASSEMBLY REQUIRED |
| DEFICIENCY/CORRECTIVE ACTION |
COMMENT/RECOMMENDATION
| 137 |
| Barracks |
Not surveyed. The building was scheduled to be demolished.
| 137 A |
| Barracks |
Not surveyed. The building was
| 137 C |
| Barracks |
Not surveyed. The building was
AAFES Service Station Building's Main service Inside
Low
None
N/A
N/A
N/A
2 "
RP
Unprotected high-hazard cross- connection for this type of building hazard [i.e., gas stations and/or mini marts with soda dispensing machine(s) and coffee line(s)].
Install an approved RP assembly on the building's domestic water service connection. Also, the assembly will be required to be
AAFES Service Station Beverage Dispenser Feed Makeup Java Snack Avenue Area
Low
None
N/A
N/A
N/A
0.5 "
Dual Check Unprotected low-hazard cross- connection. Install an approved dual check on the makeup water line to the beverage machines. Also, ensure to record the installation date on the inspection tag.
AAFES Service Station Potable Hose Bibb Inside (Employee's Only Restroom)
Low
None
N/A
N/A
N/A
N/A
AAFES Service Station Potable Hose Bibb Inside (Customer's Restroom)
Low
HBVB
N/A
N/A
N/A
N/A
AAFES Service Station Potable Hose Bibb Outside
Low
None
N/A
N/A
N/A
N/A
HBVB
Unprotected cross-connection. Install an approved HBVB device on the hose bibb.
| T 203 |
| Family Housing Garage |
No potable water connection.
| 205 |
| Vehicle Storage |
No potable water connection.
DIM Administrative Fire Suppression System Closet
Low
Detector Single Check Valve
Ames
N/A
4 "
Detector Single Check Valve
Ensure that the single check valve parts are replaced every five years and record the date of installation of the new parts on the inspection tag.
A single check valve or fire alarm valve is not considered an adequate BFPA. Strongly recommend the installation of a BFPA (DC or DCDA) on the intake line supplying the fire system; however, it is NOT a requirement, and would require
D-18
Installation Name: U.S. Army Garrison - Fort Hamilton, New York; Cross-Connection Control Survey, BFPA Total Inventory; 21 - 31 August 2017
LOCATION & DESCRIPTION OF XC
ASSET ID
| HAZARD CLASS |
| ASSEMBLY INSTALLED |
| MANUFACTURER OF ASSEMBLY |
| MODEL OF ASSEMBLY |
| SERIAL |
NUMBER OF ASSEMBLY
SIZE
| ASSEMBLY REQUIRED |
| DEFICIENCY/CORRECTIVE ACTION |
DIM Administrative Building's Main Service Mechanical Room (Basement)
Low
None
N/A
N/A
N/A
2 "
DC or None
Unprotected cross-connection for this type of building hazard. Install an approved DC assembly on the building's domestic water service connection. Also, the assembly will be required to be inspected and tested annually.
The water purveyor (NYC DEP) requires an approved DC assembly to be installed on the building's domestic water service connection due to the treated water for the boiler. However, the building can be rated as non-hazardous (i.e., removal of the chemically treated boiler) and qualify for an exemption from backflow prevention requirements. Also, the domestic water to Building 208 was shutoff.
DIM Administrative Building's Main Service for Building 208 Bathroom
Low
None
N/A
N/A
N/A
1 "
None
N/A Building 208 was condemned and used for storage only. Also, the domestic water to the building was shutoff.
DIM Administrative Boiler Feed Makeup Mechanical Room (Basement)
High
None
N/A
N/A
N/A
0.75 "
RP or DCIAV Unprotected high-hazard (chemical inhibitor additive) cross-connection. Install an approved RP assembly or DCIAV device (if no conditioning chemicals are added) on the makeup water line to the boiler unit. Also, the assembly will be required to be inspected and tested annually or annual visual inspection for the
DIM Administrative Utility Sink Bathroom
High
AVB
N/A
N/A
N/A
0.75 "
DIM Administrative Potable Hose Bibb Inside Mechanical Room
Low
None
N/A
N/A
N/A
N/A
HBVB
Unprotected cross-connection.
Install an approved HBVB device on the hose bibb.
The hose bibb was located on the domestic water line connection.
Community Club Fire Suppression System Mechanical Room (Basement)
Low
DCDA
Ames
3000 SS
174062 0211
6 "
DCDA
Community Club Fire Suppression System (Bypass Assembly) Mechanical Room (Basement)
Low
DC
Watts
007 M1QT
17552
0.75 "
DC
Ensure that the assembly meets all inspection and testing requirements (i.e., annually).
No inspection tag. This assembly was shutoff and missing the water meter. The small DC assembly may be removed if metering the unauthorized use of water on the fire system is not necessary.
D-19
Installation Name: U.S. Army Garrison - Fort Hamilton, New York; Cross-Connection Control Survey, BFPA Total Inventory; 21 - 31 August 2017
LOCATION & DESCRIPTION OF XC
ASSET ID
| HAZARD CLASS |
| ASSEMBLY INSTALLED |
| MANUFACTURER OF ASSEMBLY |
| MODEL OF ASSEMBLY |
| SERIAL |
NUMBER OF ASSEMBLY
SIZE
| ASSEMBLY REQUIRED |
| DEFICIENCY/CORRECTIVE ACTION |
Community Club Building's Main Service Mechanical Room (Outside Stairwell Main Entrance)
High
None
N/A
N/A
N/A
2 "
RP
Unprotected high-hazard cross- connection for this type of building hazard (i.e., food service/ restaurant). Install an approved RP assembly on the building's domestic water service line. Also, the assembly will be required to be inspected and tested semiannually.
Community Club Boiler Feed Makeup Mechanical Room (Basement)
High
RP
Watts
A 84810
0.75 "
RP
Ensure that the assembly meets all inspection and testing requirements (i.e., annually).
Community Club Swimming Pool Feed Makeup Pump Room
High
RP
Watts
009 M2QT
A 61498
2 "
RP
Ensure that the assembly meets all inspection and testing requirements (i.e., annually).
Community Club Commercial Dishwasher
(1) w/Soap (1) (2) Cafeteria Area
High
AVB (2)
Watts
288 A
14397 15527
0.5 " (1) 0.38" (1)
Community Club Kitchen Sinks (5) w/ Soap (3) (8) Cafeteria Area
High
AG (5) AG/DCIAV (3)
N/A
N/A
N/A
N/A
AG (5) AG/DCIAV (3)
The installed soap dispensers were ASSE 1055 B approved (i.e., built-in AG/DCIAV).
Community Club Coffee Um & Ice Machine Feed Makeup Cafeteria Area
Low
None
N/A
N/A
N/A
0.5 "
Dual Check Unprotected low-hazard cross- connection. Install an approved dual check on the makeup water line to the coffee um and ice machine.
Also, ensure to record the installation date on the inspection tag.
Community Club Utility Sink w/Soap Cafeteria Area
High
AG/DCIAV
N/A
N/A
N/A
0.75 "
AG/DCIAV
N/A The installed soap dispensers were ASSE 1055 B approved (i.e., built-in
AG/DCIAV).
Community Club Utility Sink w/Soap Near Pool Table
High
AG/DCIAV
N/A
N/A
N/A
0.75 "
AG/DCIAV
N/A The installed soap dispensers were ASSE 1055 B approved (i.e., built-in AG/DCIAV).
Community Club Potable Hose Bibb Inside Pump Room
Low
None
N/A
N/A
N/A
N/A
HBVB
Unprotected cross-connection.
The hose bibb was located on the domestic water line connection.
Community Club Potable Hose Bibbs (2) Outside (Near Pump Room)
Low
None
N/A
N/A
N/A
N/A
D-20
Installation Name: U.S. Army Garrison - Fort Hamilton, New York; Cross-Connection Control Survey, BFPA Total Inventory; 21 - 31 August 2017
LOCATION & DESCRIPTION OF XC
ASSET ID
| HAZARD CLASS |
| ASSEMBLY INSTALLED |
| MANUFACTURER OF ASSEMBLY |
| MODEL OF ASSEMBLY |
| SERIAL |
NUMBER OF ASSEMBLY
SIZE
| ASSEMBLY REQUIRED |
| DEFICIENCY/CORRECTIVE ACTION |
DIM Administrative
Not surveyed. The building was condemned and used for storage only. Also, the domestic water to the building was shutoff.
Single Soldier Housing Fire Suppression System Storage/Utility Room (Basement)
Low
DCDA
Wilkins
350 ADA
N 06605
6 "
DCDA
N/A No inspection tag. However, the assembly was tested in May 2017, which was obtained from the Installation O&M Contractor's
Single Soldier Housing Fire Suppression System (Bypass Assembly) Storage/Utility Room (Basement)
Low
DC
Wilkins
950 XL
1465272 XLD
0.75 "
DC
No inspection tag. However, the assembly was tested in May 2017, which was obtained from the Installation O&M Contractor's annual test report.
Single Soldier Housing Building's Main Service Mechanical Room (Basement)
Low
None
N/A
N/A
N/A
4 "
DC
Unprotected cross-connection for this type of building hazard. Install an approved DC assembly on the building's domestic water service connection. Also, the assembly will be required to be inspected and tested annually.
The water purveyor (NYC DEP) requires an approved DC assembly to be installed on the building's domestic water service connection due to the treated water for the boiler unit. Plus the building had a complex plumbing system.
Single Soldier Housing Boiler Feed Makeup Mechanical Room (Basement)
High
RP
Febco
825 Y
H 09469
0.75 "
RP
Ensure that the assembly meets all inspection and testing requirements (i.e., annually).
Single Soldier Housing Utility Sinks (4) Janitor Closets 1st, 2nd, 3rd Floors, & Laundry Room Basement
High
AG (3) &
AVB (1)
N/A
N/A
N/A
0.75 "
AG (3) &
AVB (1)
The survey team did not have access to the 2nd and 3rd floors. Reportedly, we were told that the utility sinks had air gaps.
Single Soldier Housing Potable Hose Bibb Inside Mechanical Room
Low
None
N/A
N/A
N/A
N/A
HBVB
Unprotected cross-connection.
The hose bibb was located upstream of the RP assembly.
Single Soldier Housing Potable Hose Bibb Outside (North Side of Bldg.)
Low
HBVB
N/A
N/A
N/A
N/A
JTF Empire Shield Housing (ARNG) Fire Suppression System Storage Room (Basement)
Low
DCDA
Wilkins
350 ADA
N 06555
6 "
DCDA
No inspection tag. However, the assembly was tested in May 2017, which was obtained from the Installation O&M Contractor's annual test report.
D-21
Installation Name: U.S. Army Garrison - Fort Hamilton, New York; Cross-Connection Control Survey, BFPA Total Inventory; 21 - 31 August 2017
LOCATION & DESCRIPTION OF XC
ASSET ID
| HAZARD CLASS |
| ASSEMBLY INSTALLED |
| MANUFACTURER OF ASSEMBLY |
| MODEL OF ASSEMBLY |
| SERIAL |
NUMBER OF ASSEMBLY
SIZE
| ASSEMBLY REQUIRED |
| DEFICIENCY/CORRECTIVE ACTION |
JTF Empire Shield Housing (ARNG) Fire Suppression System (Bypass Assembly) Storage Room (Basement)
Low
DC
Wilkins
950 XL
W 061612
0.75 "
DC
No inspection tag. However, the assembly was tested in May 2017, which was obtained from the Installation O&M Contractor's annual test report.
JTF Empire Shield Housing (ARNG) Building's Main Service Mechanical Room (Basement)
Low
None
N/A
N/A
N/A
4 "
DC
Unprotected cross-connection for this type of building hazard. Install an approved DC assembly on the building's domestic water service connection. Also, the assembly will be required to be inspected and tested annually.
The water purveyor (NYC DEP) requires an approved DC assembly to be installed on the building's domestic water service connection due to the treated water for the boiler unit. Plus the building had a
JTF Empire Shield Housing (ARNG) Boiler Feed Makeup Mechanical Room (Basement)
High
RP
Febco
825 Y
H 09521
0.75 "
RP
JTF Empire Shield Housing (ARNG) Ice Machine Feed Makeup 2nd Floor
Low
AG
N/A
N/A
N/A
N/A
JTF Empire Shield Housing (ARNG) Utility Sinks (4) Janitor Closets 1st, 2nd, 3rd Floors, & Laundry Room Basement
High
AG (3) &
AVB (1)
N/A
N/A
N/A
0.75 "
AG (3) &
AVB (1)
The utility sink with the AVB device was located on the 1st floor.
JTF Empire Shield Housing (ARNG) Potable Hose Bibb Inside Mechanical Room
Low
None
N/A
N/A
N/A
N/A
HBVB
Unprotected cross-connection. Install an approved HBVB device on the hose bibb.
The hose bibb was located upstream of the RP assembly.
JTF Empire Shield Housing (ARNG) Potable Hose Bibb Outside (North Side of Bldg.)
Low
None
N/A
N/A
N/A
N/A
Armed Forces Reserve Center Fire Suppression System Mechanical Room 129
Low
DC
Ames
2000 SS
166747 0910
8 "
DC
N/A No inspection tag. However, the assembly was tested in May 2017, which was obtained from the Installation O&M Contractor's
Armed Forces Reserve Center Building's Main Service Mechanical Room 129
Low
DC
Watts
188544
4 "
DC
N/A No inspection tag. However, the assembly was tested in May 2017, which was obtained from the Installation O&M Contractor's
D-22
Installation Name: U.S. Army Garrison - Fort Hamilton, New York; Cross-Connection Control Survey, BFPA Total Inventory; 21 - 31 August 2017
LOCATION & DESCRIPTION OF XC
ASSET ID
| HAZARD CLASS |
| ASSEMBLY INSTALLED |
| MANUFACTURER OF ASSEMBLY |
| MODEL OF ASSEMBLY |
| SERIAL |
NUMBER OF ASSEMBLY
SIZE
| ASSEMBLY REQUIRED |
| DEFICIENCY/CORRECTIVE ACTION |
Armed Forces Reserve Center Boiler Feed Makeup Mechanical Room 129
High
DC
Watts
007 M1QT
23839
0.75 "
RP
Insufficient protection for this type of hazard (chemical inhibitor additive). Replace the existing assembly that is on the makeup waterline to the boiler unit with an approved RP assembly. Also, the assembly will be required to be inspected and
Armed Forces Reserve Center Irrigation System Feed Makeup Janitor Closet (Cafeteria Area)
High
RP
Watts
009 M2QT
283810
2 "
RP
If the irrigation system was no longer in service, remove assembly and isolate from the building's plumbing system. Also, this assembly is required to be
No inspection tag. The domestic water to the irrigation system was valved off.
Armed Forces Reserve Center Garbage Disposals (3) Cafeteria Area
High
AVB (3)
N/A
N/A
N/A
0.75 "
AVB (3)
Armed Forces Reserve Center Steamers/Peeler (4) Cafeteria Area
High
AG (4)
N/A
N/A
N/A
N/A
AG (4)
Armed Forces Reserve Center Commercial Dishwasher Cafeteria Area
High
AVB
Watts
288 A
N/A
0.5 "
Armed Forces Reserve Center Kitchen Sinks (7) Cafeteria Area
High
AG (7)
N/A
N/A
N/A
N/A
AG (7)
The installed soap dispenser was ASSE 1055 B approved (i.e., built-in AG & DCIAV).
Armed Forces Reserve Center Utility Sinks (3) Janitor Closets 1st, 2nd, & 3rd Floors
High
AVB (3)
N/A
N/A
N/A
0.75 "
Armed Forces Reserve Center Utility Sink Janitor Closet Cafeteria Area
High
AVB
N/A
N/A
N/A
0.75 "
D-23
Installation Name: U.S. Army Garrison - Fort Hamilton, New York; Cross-Connection Control Survey, BFPA Total Inventory; 21 - 31 August 2017
LOCATION & DESCRIPTION OF XC
ASSET ID
| HAZARD CLASS |
| ASSEMBLY INSTALLED |
| MANUFACTURER OF ASSEMBLY |
| MODEL OF ASSEMBLY |
| SERIAL |
NUMBER OF ASSEMBLY
SIZE
| ASSEMBLY REQUIRED |
| DEFICIENCY/CORRECTIVE ACTION |
Armed Forces Reserve Center Potable Hose Bibbs (6) Inside (Men's & Womens Bathrooms) 1st, 2nd, & 3rd Floors
Low
None
N/A
N/A
N/A
N/A
HBVB (6)
Armed Forces Reserve Center Potable Hose Bibbs (5) Outside
Low
HBVB (5)
N/A
N/A
N/A
N/A
HBVB (5)
| 217 |
| Vehicle Garage |
No potable water connection.
Child Development Center Fire Suppression System Sprinkler Closet (Room 1)
Low
Single Check
Rasco
Model E
N/A
4 "
Single Check
Ensure that the single check valve parts are replaced every five years and record the date of installation of the new parts on the inspection tag.
A single check valve or fire alarm valve is not considered an adequate BFPA.