J.1.4 ADAAG 404 - Doors, Doorways, and Gates.pdf

PDF 518 KB Posted

Attached to
Automatic Door Operator (ADO) Inspection and Maintenance Program
Solicitation number
Not on record
Issued by

About this file

This document is a reference guide for ADA 2010 Standards compliance, specifically Section 404 addressing doors, doorways, and gates. It is not a solicitation, contract, or procurement document, but rather an informational resource explaining accessibility requirements.

The document details technical requirements for doors, doorways, and gates that are part of accessible routes. Key requirements include: manual doors must provide a minimum 32-inch clear opening width, with specific maneuvering clearances varying by approach direction and door type (ranging from 42 to 60 inches perpendicular to doorway); thresholds must not exceed 1/2 inch in height, with beveled edges required for raised thresholds exceeding 1/4 inch; door hardware must be operable between 34 and 48 inches above the finish floor; door closing speed must meet specific timing requirements (5 seconds minimum from 90 degrees to 12 degrees from latch for closers); and opening force must not exceed 5 pounds for interior hinged doors and sliding or folding doors. Automatic and power-assisted doors must comply with ANSI/BHMA standards, provide 32-inch minimum clear openings in both power-on and power-off modes, include maneuvering clearance or standby power for emergency operation, and have 32-inch minimum break-out openings when without standby power. The document provides detailed maneuvering clearance tables, diagrams, and exceptions for specific door types including revolving doors (which cannot be part of accessible routes), vision lights, recessed doors, doors in series, and specialized applications such as hospital patient rooms and pool access gates.

View the file

Other files

Show all 16

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ADA Compliance Directory E-Mail

ADA Contractors

Search

Search ...

Login Form

Log in

Forgot your username?

Forgot your password?

ADA 2010 Standards

Support ADA Compliance Directory Click HERE.

ADA Compliance Contractors

ADA Links and Contacts

ADA Contractor site

Usernam

Password

ADA 2010 Standards

ADA Compliance standards

102 Dimensions Adults Children

103 Equivalent Facilitation

104 Convensions

105 Referenced Standards

201 Application

404 Doors, Doorways, and Gates

Automatic Door Break Out Openings. The 1991 Standards do not contain any technical requirement for automatic door break out openings. The 2010 Standards at sections 404.1, 404.3, 404.3.1, and 404.3.6 require automatic doors that are part of a means of egress and that do not have standby power to have a 32-inch minimum clear break out opening when operated in emergency mode. The minimum clear opening width for automatic doors is measured with all leaves in the open position. Automatic bi-parting doors or pairs of swinging doors that provide a

32-inch minimum clear break out opening in emergency mode when both leaves are opened manually meet the technical requirement. Section 404.3.6 of the 2010 Standards includes an exception that exempts automatic doors from the technical requirement for break out openings when accessible manual swinging doors serve the same means of egress.

Maneuvering Clearance or Standby Power for Automatic Doors. Section 4.13.6 of the 1991

Standards does not require maneuvering clearance at automatic doors. Section 404.3.2 of the

2010 Standards requires automatic doors that serve as an accessible means of egress to either provide maneuvering clearance or to have standby power to operate the door in emergencies.

This provision has limited application and will affect, among others, in-swinging automatic doors that serve small spaces.

Commenters urged the Department to reconsider provisions that would require maneuvering clearance or standby power for automatic doors. They assert that these requirements would impose unreasonable financial and administrative burdens on all covered entities, particularly smaller entities. The Department declines to change these provisions because they are fundamental life-safety issues. The requirement applies only to doors that are part of a means of egress that must be accessible in an emergency. If an emergency-related power failure prevents the operation of the automatic door, a person with a disability could be trapped unless there is either adequate maneuvering room to open the door manually or a back-up power source.

Thresholds at Doorways. The 1991 Standards, at section 4.13.8, require the height of thresholds at doorways not to exceed 1/2 inch and thresholds at exterior sliding doors not to exceed 3/4 inch. Sections 404.1 and 404.2.5 of the 2010 Standards require the height of thresholds at all doorways that are part of an accessible route not to exceed 1/2 inch. The 1991 Standards and the 2010 Standards require raised thresholds that exceed ¼ inch in height to be beveled on each

404 DOORS, DOORWAYS, AND GATES

HOME ADA DIRECTORY ADA CONTRACTOR GALLERY CONTACT US

11/18/26, 7:27 AM 404 Doors, Doorways, and Gates - ADA Compliance - ADA Compliance https://www.ada-compliance.com/ada-compliance/404-doors-doorways-and-gates 1/9 http://www.ada.directory/ mailto:info@ada-compliance.com?Subject=ADA%20%20Compliance https://www.ada-compliance.com/user/remind https://www.ada-compliance.com/user/reset http://ada.directory/donation.html http://www.ada.directory/ http://www.ada.directory/ https://www.ada-compliance.com/ada-compliance/ada-contractors https://www.ada-compliance.com/ada-compliance/ada-useful-links-and-contacts.html http://www.ada-contractor.com/ https://www.ada-compliance.com/ada-compliance/2010-ada-standards https://www.ada-compliance.com/ada-compliance/2010-ada-standards https://www.ada-compliance.com/ada-compliance/102-dimensions-for-adults-and-children https://www.ada-compliance.com/ada-compliance/103-equivalent-facilitation.html https://www.ada-compliance.com/ada-compliance/104-conventions https://www.ada-compliance.com/ada-compliance/105-referenced-standards.html https://www.ada-compliance.com/ada-compliance/201-application https://www.ada-compliance.com/ http://www.ada-compliance.directory/ https://www.ada-compliance.com/ada-compliance/ada-contractors https://www.ada-compliance.com/ada-compliance/ada-phot-gallery.html https://www.ada-compliance.com/contact-us/view/form

202 Existing Buildings and Facilities

203 General Exceptions

203 Employee Work Areas

204 Protruding Objects

205 Operable Parts

206 Accessible Routes

207 Accessible Means of Egress

208 Parking Spaces

209 Loading Zones & Bus Stops

210 Stairways

211 Drinking Fountains

212 Kitchens Lavatories Sinks

213 Toilet & Bathing

214 Washing Drying Machines

215 Fire Alarm Systems

216 Signs

217 Telephones

218 Transportation Facilities

219 Assistive Listening Systems

220 Automatic Tellers

221 Assembly Areas

222 Dressing Fitting Locker Room

223 Medical Care Long Term Facilities

224 Transient Lodging Guess Room

225 Storage

226 Dining & Work Surfaces

227 Sales & Servcie

228 Dispensers Machines Mail Fuel

229 Windows

230 Two Way Com Systems

231 Judicial Facilities & Courtrooms

232 Detention & Correctional

Facilities

233 Residential Facilities

234 Amusement Rides

235 Boating Facilities

236 Exercise Machines

237 Fishing Piers & Platforms

238 Golf Facilities

239 Miniature Golf Facilities

240 Play Areas

241 Sauna & Steam Room

242 Swimming Pools Spas

243 Shooting Facilities

301 General

302 Floor & Ground Surfaces

303 Change in Level

304 Turning Spaces

305 Clear Floor & Ground Spaces

306 Knee and Toe Clearance

307 Protruding Objets

308 Reach Ranges

309 Operable Parts

401 General

401 New Construction

36.402 Alterations

403 Walking Surfaces

36.403 Alteration: Path of Travel

404 Doors Doorways & Gates

36.404 Alteration: Elevator Exemption

side with a slope not steeper than 1:2. The 2010 Standards include an exception that exempts existing and altered thresholds that do not exceed 3/4 inch in height and are beveled on each side from the requirement.

404 Doors, Doorways, and Gates

404.1 General. Doors, doorways, and gates that are part of an accessible route shall comply with 404.

EXCEPTION: Doors, doorways, and gates designed to be operated only by security personnel shall not be required to comply with 404.2.7, 404.2.8, 404.2.9, 404.3.2 and 404.3.4 through

404.3.7.

Advisory 404.1 General Exception. Security personnel must have sole control of doors that are eligible for the Exception at 404.1. It would not be acceptable for security personnel to operate the doors for people with disabilities while allowing others to have independent access.

404.2 Manual Doors, Doorways, and Manual Gates. Manual doors and doorways and manual gates intended for user passage shall comply with 404.2.

404.2.1 Revolving Doors, Gates, and Turnstiles. Revolving doors, revolving gates, and turnstiles shall not be part of an accessible route.

404.2.2 Double-Leaf Doors and Gates. At least one of the active leaves of doorways with two leaves shall comply with 404.2.3 and 404.2.4.

404.2.3 Clear Width. Door openings shall provide a clear width of 32 inches (815 mm) minimum.

Clear openings of doorways with swinging doors shall be measured between the face of the door and the stop, with the door open 90 degrees. Openings more than 24 inches (610 mm) deep shall provide a clear opening of 36 inches (915 mm) minimum. There shall be no projections into the required clear opening width lower than 34 inches (865 mm) above the finish floor or ground. Projections into the clear opening width between 34 inches (865 mm) and

80 inches (2030 mm) above the finish floor or ground shall not exceed 4 inches (100 mm).

EXCEPTIONS:

1. In alterations, a projection of 5/8 inch (16 mm) maximum into the required clear width shall be permitted for the latch side stop.

2. Door closers and door stops shall be permitted to be 78 inches (1980 mm) minimum above the finish floor or ground.

Figure 404.2.3 Clear Width of Doorways

404.2.4 Maneuvering Clearances. Minimum maneuvering clearances at doors and gates shall comply with 404.2.4. Maneuvering clearances shall extend the full width of the doorway and the required latch side or hinge side clearance.

EXCEPTION: Entry doors to hospital patient rooms shall not be required to provide the clearance beyond the latch side of the door.

11/18/26, 7:27 AM 404 Doors, Doorways, and Gates - ADA Compliance - ADA Compliance https://www.ada-compliance.com/ada-compliance/404-doors-doorways-and-gates 2/9 https://www.ada-compliance.com/ada-compliance/202-existing-buildings-and-facilities https://www.ada-compliance.com/ada-compliance/203-general-exceptions https://www.ada-compliance.com/ada-compliance/203-206-and-215-employee-work-areas https://www.ada-compliance.com/ada-compliance/204-protruding-objects https://www.ada-compliance.com/ada-compliance/205-and-309-operable-parts https://www.ada-compliance.com/ada-compliance/206-and-chapter-4-accessible-routes https://www.ada-compliance.com/ada-compliance/207-accessible-means-of-egress https://www.ada-compliance.com/ada-compliance/208-and-502-parking-spaces https://www.ada-compliance.com/ada-compliance/209-and-503-passenger-loading-zones-and-bus-stops https://www.ada-compliance.com/ada-compliance/210-and-504-stairways https://www.ada-compliance.com/ada-compliance/211-and-602-drinking-fountains https://www.ada-compliance.com/ada-compliance/212-and-606-kitchens-kitchenettes-lavatories-and-sinks https://www.ada-compliance.com/ada-compliance/213-603-604-and-608-toilet-and-bathing-facilities-rooms-and-compartments https://www.ada-compliance.com/ada-compliance/214-and-611-washing-machines-and-clothes-dryers https://www.ada-compliance.com/ada-compliance/215-fire-alarm-systems https://www.ada-compliance.com/ada-compliance/216-and-703-signs https://www.ada-compliance.com/ada-compliance/217-and-704-telephones https://www.ada-compliance.com/ada-compliance/218-and-810-transportation-facilities https://www.ada-compliance.com/ada-compliance/219-and-706-assistive-listening-systems https://www.ada-compliance.com/ada-compliance/220-and-707-automatic-teller-machines-and-fare-machines https://www.ada-compliance.com/ada-compliance/221-assembly-areas https://www.ada-compliance.com/ada-compliance/222-and-803-dressing-fitting-and-locker-rooms https://www.ada-compliance.com/ada-compliance/223-medical-care-and-long-term-care-facilities https://www.ada-compliance.com/ada-compliance/224-and-806-transient-lodging-guest-rooms https://www.ada-compliance.com/ada-compliance/225-and-811-storage https://www.ada-compliance.com/ada-compliance/226-and-902-dining-surfaces-and-work-surfaces https://www.ada-compliance.com/ada-compliance/227-and-904-sales-and-service https://www.ada-compliance.com/ada-compliance/228-depositories-vending-machines-change-machines-mail-boxes-and-fuel-dispensers https://www.ada-compliance.com/ada-compliance/229-windows https://www.ada-compliance.com/ada-compliance/230-and-708-two-way-communication-systems.html https://www.ada-compliance.com/ada-compliance/231-and-808-judicial-facilities-and-courtrooms https://www.ada-compliance.com/ada-compliance/232-detention-facilities-and-correctional-facilities https://www.ada-compliance.com/ada-compliance/232-detention-facilities-and-correctional-facilities https://www.ada-compliance.com/ada-compliance/233-residential-facilities https://www.ada-compliance.com/ada-compliance/234-and-1002-amusement-rides https://www.ada-compliance.com/ada-compliance/235-and-1003-recreational-boating-facilities https://www.ada-compliance.com/ada-compliance/236-and-1004-exercise-machines-and-equipment https://www.ada-compliance.com/ada-compliance/237-and-1005-fishing-piers-and-platforms https://www.ada-compliance.com/ada-compliance/238-and-1006-golf-facilities https://www.ada-compliance.com/ada-compliance/239-and-1007-miniature-golf-facilities https://www.ada-compliance.com/ada-compliance/240-and-1008-play-areas https://www.ada-compliance.com/ada-compliance/241-and-612-saunas-and-steam-rooms.html https://www.ada-compliance.com/ada-compliance/242-and-1009-swimming-pools-wading-pools-and-spas https://www.ada-compliance.com/ada-compliance/243-shooting-facilities-with-firing-positions.html https://www.ada-compliance.com/ada-compliance/301-general.html https://www.ada-compliance.com/ada-compliance/302-floor-or-ground-surfaces https://www.ada-compliance.com/ada-compliance/303-changes-in-level https://www.ada-compliance.com/ada-compliance/304-turning-space https://www.ada-compliance.com/ada-compliance/305-clear-floor-or-ground-space.html https://www.ada-compliance.com/ada-compliance/306-knee-and-toe-clearance https://www.ada-compliance.com/ada-compliance/307-protruding-objects https://www.ada-compliance.com/ada-compliance/308-reach-ranges https://www.ada-compliance.com/ada-compliance/309-operable-parts https://www.ada-compliance.com/ada-compliance/401-general.html https://www.ada-compliance.com/ada-compliance/36401-new-construction https://www.ada-compliance.com/ada-compliance/36402-alterations https://www.ada-compliance.com/ada-compliance/403-walking-surfaces https://www.ada-compliance.com/ada-compliance/36403-alterations-path-of-travel https://www.ada-compliance.com/ada-compliance/404-doors-doorways-and-gates https://www.ada-compliance.com/ada-compliance/36404-alterations-elevator-exemption

405 Ramps

36.405 Alteration: Historic

Preservation

406 Curb Ramp

36.406 Standard New & Existing

407 Elevators

408 Limited Use Elevators

409 Residence Elevators

410 Platform Lift

501 General

502 Parking Spaces

503 Passenger Loading Zone

504 Stairways

505 Handrails

601 General

602 Drinking Fountains

603 Toilets & Bathrooms Room

604 Water Closets & Toilets

605 Urinals

606 Lavatories and Sinks

607 Bathtubs

608 Shower Compartments

609 Grab Bars

610 Seats

611 Washing Drying Machines

612 Sauna & Steam Room

701 General

702 Fire Alarm Systems

703 Signs

704 Telephones

705 Detectable Warnings

706 Assistive Listening Systems

707 Teller & Fare Machines

708 Two Way Com Systems

801 General

802 WheelShare & Companion

Spaces

802 Design Aisle Seats

803 Dressing Fitting Locker Room

804 Kitchens & Kitchenettes

805 Medical & Long-Term Care

806 Transient Lodging Guest Rooms

807 Holding & Housing Cells

808 Courtrooms

809 Residential Dwelling Units

810 Transportation Facilities

811 Storage

901 General

902 Dinning & Work Surface

903 Benches

904 Check Out & Service Counters

1001 General

1002 Amusement Rides

1003 Recreation Boat Facilities

1004 Exercise Machines

1005 Fishing Piers & Platforms

1006 Golf Facilities

1007 Miniature Golf Facilities

1008 Play Access

1009 Swimming Pools Spas

404.2.4.1 Swinging Doors and Gates. Swinging doors and gates shall have maneuvering clearances complying with Table 404.2.4.1.

Table 404.2.4.1 Maneuvering Clearances at Manual Swinging Doors and Gates (text version)

Type of Use Minimum Maneuvering Clearance

Approach

Direction

Door or

Gate Side

Perpendicular to

Doorway

Parallel to Doorway

(beyond latch side unless noted)

From front Pull 60 inches (1525 mm) 18 inches (455 mm)

From front Push 48 inches (1220 mm) 0 inches (0 mm)1

From hinge side Pull 60 inches (1525 mm) 36 inches (915 mm)

From hinge side Pull 54 inches (1370 mm) 42 inches (1065 mm)

From hinge side Push

42 inches (1065 mm)2 22 inches (560 mm)3

From latch side Pull

48 inches (1220 mm)4 24 inches (610 mm)

From latch side Push

42 inches (1065 mm)4 24 inches (610 mm)

1. Add 12 inches (305 mm) if closer and latch are provided.

2. Add 6 inches (150 mm) if closer and latch are provided.

3. Beyond hinge side.

4. Add 6 inches (150 mm) if closer is provided.

11/18/26, 7:27 AM 404 Doors, Doorways, and Gates - ADA Compliance - ADA Compliance https://www.ada-compliance.com/ada-compliance/404-doors-doorways-and-gates 3/9 https://www.ada-compliance.com/ada-compliance/405-ramps https://www.ada-compliance.com/ada-compliance/36405-alterations-historic-preservation https://www.ada-compliance.com/ada-compliance/36405-alterations-historic-preservation https://www.ada-compliance.com/ada-compliance/406-curb-ramps https://www.ada-compliance.com/ada-compliance/36406-standards-for-new-construction-and-alterations https://www.ada-compliance.com/ada-compliance/407-elevators https://www.ada-compliance.com/ada-compliance/408-limited-use/limited-application-elevators https://www.ada-compliance.com/ada-compliance/409-private-residence-elevators https://www.ada-compliance.com/ada-compliance/410-platform-lifts https://www.ada-compliance.com/ada-compliance/501-general.html https://www.ada-compliance.com/ada-compliance/502-parking-spaces https://www.ada-compliance.com/ada-compliance/503-passenger-loading-zones https://www.ada-compliance.com/ada-compliance/504-stairways https://www.ada-compliance.com/ada-compliance/505-handrails https://www.ada-compliance.com/ada-compliance/601-general.html https://www.ada-compliance.com/ada-compliance/602-drinking-fountains https://www.ada-compliance.com/ada-compliance/603-toilet-and-bathing-rooms https://www.ada-compliance.com/ada-compliance/604-water-closets-and-toilet-compartments https://www.ada-compliance.com/ada-compliance/605-urinals https://www.ada-compliance.com/ada-compliance/606-lavatories-and-sinks https://www.ada-compliance.com/ada-compliance/607-bathtubs https://www.ada-compliance.com/ada-compliance/608-shower-compartments https://www.ada-compliance.com/ada-compliance/609-grab-bars https://www.ada-compliance.com/ada-compliance/610-seats https://www.ada-compliance.com/ada-compliance/611-washing-machines-and-clothes-dryers https://www.ada-compliance.com/ada-compliance/612-saunas-and-steam-rooms https://www.ada-compliance.com/ada-compliance/701-general.html https://www.ada-compliance.com/ada-compliance/702-fire-alarm-systems https://www.ada-compliance.com/ada-compliance/703-signs https://www.ada-compliance.com/ada-compliance/704-telephones https://www.ada-compliance.com/ada-compliance/705-detectable-warnings https://www.ada-compliance.com/ada-compliance/706-assistive-listening-systems https://www.ada-compliance.com/ada-compliance/707-automatic-teller-machines-and-fare-machines https://www.ada-compliance.com/ada-compliance/708-two-way-communication-systems https://www.ada-compliance.com/ada-compliance/801-general.html https://www.ada-compliance.com/ada-compliance/802-wheelchair-spaces-companion-seats-and-designated-aisle-seats https://www.ada-compliance.com/ada-compliance/802-wheelchair-spaces-companion-seats-and-designated-aisle-seats https://www.ada-compliance.com/ada-compliance/802-wheelchair-spaces-companion-seats-and-designated-aisle-seats https://www.ada-compliance.com/ada-compliance/803-dressing-fitting-and-locker-rooms https://www.ada-compliance.com/ada-compliance/804-kitchens-and-kitchenettes https://www.ada-compliance.com/ada-compliance/805-medical-care-and-long-term-care-facilities https://www.ada-compliance.com/ada-compliance/806-transient-lodging-guest-rooms https://www.ada-compliance.com/ada-compliance/807-holding-cells-and-housing-cells https://www.ada-compliance.com/ada-compliance/808-courtrooms https://www.ada-compliance.com/ada-compliance/809-residential-dwelling-units https://www.ada-compliance.com/ada-compliance/810-transportation-facilities https://www.ada-compliance.com/ada-compliance/811-storage https://www.ada-compliance.com/ada-compliance/901-general.html https://www.ada-compliance.com/ada-compliance/902-dining-surfaces-and-work-surfaces https://www.ada-compliance.com/ada-compliance/903-benches https://www.ada-compliance.com/ada-compliance/904-check-out-aisles-and-sales-and-service-counters https://www.ada-compliance.com/ada-compliance/1001-general https://www.ada-compliance.com/ada-compliance/1002-amusement-rides https://www.ada-compliance.com/ada-compliance/1003-recreational-boating-facilities https://www.ada-compliance.com/ada-compliance/1004-exercise-machines-and-equipment https://www.ada-compliance.com/ada-compliance/1005-fishing-piers-and-platforms https://www.ada-compliance.com/ada-compliance/1006-golf-facilities https://www.ada-compliance.com/ada-compliance/1007-miniature-golf-facilities https://www.ada-compliance.com/ada-compliance/1008-play-areas https://www.ada-compliance.com/ada-compliance/1009-swimming-pools-wading-pools-and-spas http://www.ada.gov/regs2010/2010ADAStandards/2010ADAstandards.htm#12 http://www.ada.gov/regs2010/2010ADAStandards/2010ADAstandards.htm#6 http://www.ada.gov/regs2010/2010ADAStandards/2010ADAstandards.htm#anchor22 http://www.ada.gov/regs2010/2010ADAStandards/2010ADAstandards.htm#48 http://www.ada.gov/regs2010/2010ADAStandards/2010ADAstandards.htm#48

ADA 1990 Standards

Business Guideline

1010 Shooting Facilities

ADA 1990 Standards

ADA Purpose

ADA Introduction & Definition

Accessible Elements & Space

Minimum Requirements

Space Allowance & Reach

Accessible Route

Protruding Objects

Ground & Floor Surfaces

Curb Ramp

Parking

ADA Ramp

Stairs

Elevators

Platform Lifts

Windows

Doors

Entrances

Drinking Fountains Water Coolers

Water Closets

Toilet Stalls

Urinals

Lavatories Mirrorsada-lavatories-mirrors

Bathtubs

Small Business Guideline

Introduction

Existing Facilities

Architectural Barriers

Priorities for Barrier Removal

Accessible Parking

Accessible Entrance

Doors at Entrances to Businesses

Turnstiles/Security Gates at Entrances

Shelves and Maneuvering Space

Sales and Service Counters

Serving Counters

Fixed Seating and Tables

Policies and Procedures

Communicating with Customers

Tax Credits and Deductions

11/18/26, 7:27 AM 404 Doors, Doorways, and Gates - ADA Compliance - ADA Compliance https://www.ada-compliance.com/ada-compliance/404-doors-doorways-and-gates 4/9 https://www.ada-compliance.com/ada-compliance/1010-shooting-facilities-with-firing-positions http://www.ada-compliance.com/ada-compliance/ada-compliance-terms https://www.ada-compliance.com/ada-compliance/ada-purpose https://www.ada-compliance.com/ada-compliance/ada-compliance-terms https://www.ada-compliance.com/accessible-elements-and-spaces https://www.ada-compliance.com/ada-accessible-elements-space https://www.ada-compliance.com/space-allowance-reach-ranges https://www.ada-compliance.com/ada-accessible-route https://www.ada-compliance.com/ada-compliance/ada-protruding-objects https://www.ada-compliance.com/ada-ground-floor-surfaces https://www.ada-compliance.com/ada-compliance/cub-ramp https://www.ada-compliance.com/ada-compliance/ada-parking-loding-zone https://www.ada-compliance.com/ada-compliance/ada-ramp https://www.ada-compliance.com/ada-compliance/ada-stairs.html https://www.ada-compliance.com/ada-compliance/ada-elevators.html https://www.ada-compliance.com/ada-compliance/ada-platform-lifts.html https://www.ada-compliance.com/ada-compliance/ada-windows.html https://www.ada-compliance.com/ada-compliance/ada-doors.html https://www.ada-compliance.com/ada-compliance/ada-entrances.html https://www.ada-compliance.com/ada-compliance/drinking-fountain-water-coolers.html https://www.ada-compliance.com/ada-compliance/ada-water-closets.html https://www.ada-compliance.com/ada-compliance/ada-toilet-stalls.html https://www.ada-compliance.com/ada-compliance/ada-urinals.html https://www.ada-compliance.com/ada-compliance/ada-lavatories-mirrors.html https://www.ada-compliance.com/ada-compliance/ada-lavatories-mirrors.html https://www.ada-compliance.com/ada-compliance/ada-bathtubs.html https://www.ada-compliance.com/ada-compliance/small-business-guideline.html https://www.ada-compliance.com/ada-compliance/small-business-introduction.html https://www.ada-compliance.com/ada-compliance/small-business-existing-facilities.html https://www.ada-compliance.com/ada-compliance/small-business-architectural-barriers.html https://www.ada-compliance.com/ada-compliance/small-business-priorities-for-barrier-removal https://www.ada-compliance.com/ada-compliance/small-business-accessible-parking.html https://www.ada-compliance.com/ada-compliance/small-business-accessible-entrance https://www.ada-compliance.com/ada-compliance/small-business-doors-at-entrances-to-businesses https://www.ada-compliance.com/ada-compliance/small-business-turnstiles-and-security-gates-at-entrances https://www.ada-compliance.com/ada-compliance/small-business-shelves-and-maneuvering-space https://www.ada-compliance.com/ada-compliance/small-business-sales-and-service-counters https://www.ada-compliance.com/ada-compliance/small-business-serving-counters https://www.ada-compliance.com/ada-compliance/small-business-fixed-seating-and-tables https://www.ada-compliance.com/ada-compliance/small-business-policies-and-procedures https://www.ada-compliance.com/ada-compliance/small-business-communicating-with-customers https://www.ada-compliance.com/ada-compliance/small-business-tax-credits-and-deductions

New Construction and Alterations

New construction alterations 2010

Helpfull Articles

Checklist for Existing Facilities

Restriping Parking Lots

ADA Investigating Agency

Toilet Layouts

Figure 404.2.4.1 Maneuvering Clearances at Manual Swinging Doors and Gates

404.2.4.2 Doorways without Doors or Gates, Sliding Doors, and Folding Doors. Doorways less than 36 inches (915 mm) wide without doors or gates, sliding doors, or folding doors shall have maneuvering clearances complying with Table 404.2.4.2.

Table 404.2.4.2 Maneuvering Clearances at Doorways without Doors or Gates, Manual Sliding Doors, and Manual Folding Doors

Minimum Maneuvering Clearance

Approach Direction Perpendicular to

Doorway

Parallel to Doorway (beyond stop/latch side unless noted)

From Front 48 inches (1220 mm) 0 inches (0 mm)

From side1 42 inches (1065 mm) 0 inches (0 mm)

From pocket/hinge side 42 inches (1065 mm) 22 inches (560 mm)2

11/18/26, 7:27 AM 404 Doors, Doorways, and Gates - ADA Compliance - ADA Compliance https://www.ada-compliance.com/ada-compliance/404-doors-doorways-and-gates 5/9 https://www.ada-compliance.com/ada-compliance/small-business-new-construction-and-alterations https://www.ada-compliance.com/28-cfr-35-151-new-construction-and-alterations.html https://www.ada-compliance.com/ada-compliance/helpfull-articles.html https://www.ada-compliance.com/ada-compliance/checklist-for-existing-facilities https://www.ada-compliance.com/ada-compliance/restriping-parking-lots.html https://www.ada-compliance.com/ada-compliance/investigative-agency.html https://www.ada-compliance.com/ada-compliance/comparison-of-single-user-toilet-room-layouts http://www.ada.gov/regs2010/2010ADAStandards/2010ADAstandards.htm#fnt1 http://www.ada.gov/regs2010/2010ADAStandards/2010ADAstandards.htm#fnt2

From stop/latch side 42 inches (1065 mm) 24 inches (610 mm)

1. Doorway with no door only.

2. Beyond pocket/hinge side.

Figure 404.2.4.2 Maneuvering Clearances at Doorways without Doors, Sliding Doors, Gates, and Folding Doors

404.2.4.3 Recessed Doors and Gates. Maneuvering clearances for forward approach shall be provided when any obstruction within 18 inches (455 mm) of the latch side of a doorway projects more than 8 inches (205 mm) beyond the face of the door, measured perpendicular to the face of the door or gate.

Advisory 404.2.4.3 Recessed Doors and Gates. A door can be recessed due to wall thickness or because of the placement of casework and other fixed elements adjacent to the doorway. This provision must be applied wherever doors are recessed.

Figure 404.2.4.3 Maneuvering Clearances at Recessed Doors and Gates

404.2.4.4 Floor or Ground Surface. Floor or ground surface within required maneuvering clearances shall comply with 302. Changes in level are not permitted.

11/18/26, 7:27 AM 404 Doors, Doorways, and Gates - ADA Compliance - ADA Compliance https://www.ada-compliance.com/ada-compliance/404-doors-doorways-and-gates 6/9

EXCEPTIONS:

1. Slopes not steeper than 1:48 shall be permitted.

2. Changes in level at thresholds complying with 404.2.5 shall be permitted.

404.2.5 Thresholds. Thresholds, if provided at doorways, shall be 1/2 inch (13 mm) high maximum. Raised thresholds and changes in level at doorways shall comply with 302 and 303.

EXCEPTION: Existing or altered thresholds 3/4 inch (19 mm) high maximum that have a beveled edge on each side with a slope not steeper than 1:2 shall not be required to comply with 404.2.5.

404.2.6 Doors in Series and Gates in Series. The distance between two hinged or pivoted doors in series and gates in series shall be 48 inches (1220 mm) minimum plus the width of doors or gates swinging into the space.

Figure 404.2.6 Doors in Series and Gates in Series

404.2.7 Door and Gate Hardware. Handles, pulls, latches, locks, and other operable parts on doors and gates shall comply with 309.4. Operable parts of such hardware shall be 34 inches

(865 mm) minimum and 48 inches (1220 mm) maximum above the finish floor or ground. Where sliding doors are in the fully open position, operating hardware shall be exposed and usable from both sides.

EXCEPTIONS:

1. Existing locks shall be permitted in any location at existing glazed doors without stiles, existing overhead rolling doors or grilles, and similar existing doors or grilles that are designed with locks that are activated only at the top or bottom rail.

2. Access gates in barrier walls and fences protecting pools, spas, and hot tubs shall be permitted to have operable parts of the release of latch on self-latching devices at 54 inches

(1370 mm) maximum above the finish floor or ground provided the self-latching devices are not also self-locking devices and operated by means of a key, electronic opener, or integral combination lock.

Advisory 404.2.7 Door and Gate Hardware. Door hardware that can be operated with a closed fist or a loose grip accommodates the greatest range of users. Hardware that requires simultaneous hand and finger movements require greater dexterity and coordination, and is not recommended.

https://www.ada-compliance.com/ada-compliance/404-doors-doorways-and-gates 7/9

404.2.8 Closing Speed. Door and gate closing speed shall comply with 404.2.8.

404.2.8.1 Door Closers and Gate Closers. Door closers and gate closers shall be adjusted so that from an open position of 90 degrees, the time required to move the door to a position of 12 degrees from the latch is 5 seconds minimum.

404.2.8.2 Spring Hinges. Door and gate spring hinges shall be adjusted so that from the open position of 70 degrees, the door or gate shall move to the closed position in 1.5 seconds minimum.

404.2.9 Door and Gate Opening Force. Fire doors shall have a minimum opening force allowable by the appropriate administrative authority. The force for pushing or pulling open a door or gate other than fire doors shall be as follows:

1. Interior hinged doors and gates: 5 pounds (22.2 N) maximum.

2. Sliding or folding doors: 5 pounds (22.2 N) maximum.

These forces do not apply to the force required to retract latch bolts or disengage other devices that hold the door or gate in a closed position.

Advisory 404.2.9 Door and Gate Opening Force. The maximum force pertains to the continuous application of force necessary to fully open a door, not the initial force needed to overcome the inertia of the door. It does not apply to the force required to retract bolts or to disengage other devices used to keep the door in a closed position.

404.2.10 Door and Gate Surfaces. Swinging door and gate surfaces within 10 inches (255 mm) of the finish floor or ground measured vertically shall have a smooth surface on the push side extending the full width of the door or gate. Parts creating horizontal or vertical joints in these surfaces shall be within 1/16 inch (1.6 mm) of the same plane as the other. Cavities created by added kick plates shall be capped.

EXCEPTIONS:

1. Sliding doors shall not be required to comply with 404.2.10.

2. Tempered glass doors without stiles and having a bottom rail or shoe with the top leading edge tapered at 60 degrees minimum from the horizontal shall not be required to meet the 10 inch (255 mm) bottom smooth surface height requirement.

3. Doors and gates that do not extend to within 10 inches (255 mm) of the finish floor or ground shall not be required to comply with 404.2.10.

4. Existing doors and gates without smooth surfaces within 10 inches (255 mm) of the finish floor or ground shall not be required to provide smooth surfaces complying with 404.2.10 provided that if added kick plates are installed, cavities created by such kick plates are capped

404.2.11 Vision Lights. Doors, gates, and side lights adjacent to doors or gates, containing one or more glazing panels that permit viewing through the panels shall have the bottom of at least one glazed panel located 43 inches (1090 mm) maximum above the finish floor.

EXCEPTION: Vision lights with the lowest part more than 66 inches (1675 mm) from the finish floor or ground shall not be required to comply with 404.2.11.

404.3 Automatic and Power-Assisted Doors and Gates. Automatic doors and automatic gates shall comply with 404.3. Full-powered automatic doors shall comply with ANSI/BHMA A156.10

(incorporated by reference, see "Referenced Standards" in Chapter 1). Low-energy and power-https://www.ada-compliance.com/ada-compliance/404-doors-doorways-and-gates 8/9

© 2026 ADA Compliance | Web Design by Biz Wiz Support

SubscribeYou are here: Home // ADA 2010 Standards // 404 Doors Doorways & Gates

Joomla SEO by AceSEF assisted doors shall comply with ANSI/BHMA A156.19 (1997 or 2002 edition) (incorporated by reference, see "Referenced Standards" in Chapter 1).

404.3.1 Clear Width. Doorways shall provide a clear opening of 32 inches (815 mm) minimum in power-on and power-off mode. The minimum clear width for automatic door systems in a doorway shall be based on the clear opening provided by all leaves in the open position.

404.3.2 Maneuvering Clearance. Clearances at power-assisted doors and gates shall comply with 404.2.4. Clearances at automatic doors and gates without standby power and serving an accessible means of egress shall comply with 404.2.4.

EXCEPTION: Where automatic doors and gates remain open in the power-off condition, compliance with 404.2.4 shall not be required.

404.3.3 Thresholds. Thresholds and changes in level at doorways shall comply with 404.2.5.

404.3.4 Doors in Series and Gates in Series. Doors in series and gates in series shall comply with 404.2.6.

404.3.5 Controls. Manually operated controls shall comply with 309. The clear floor space adjacent to the control shall be located beyond the arc of the door swing.

404.3.6 Break Out Opening. Where doors and gates without standby power are a part of a means of egress, the clear break out opening at swinging or sliding doors and gates shall be 32 inches (815 mm) minimum when operated in emergency mode.

EXCEPTION: Where manual swinging doors and gates comply with 404.2 and serve the same means of egress compliance with 404.3.6 shall not be required.

404.3.7 Revolving Doors, Revolving Gates, and Turnstiles. Revolving doors, revolving gates, and turnstiles shall not be part of an accessible route.

11/18/26, 7:27 AM 404 Doors, Doorways, and Gates - ADA Compliance - ADA Compliance https://www.ada-compliance.com/ada-compliance/404-doors-doorways-and-gates 9/9 http://bizwizsupport.com/ https://plus.google.com/u/0/b/106876080158662018973/ https://twitter.com/ada_compliance https://www.facebook.com/adaComplianceService https://www.pinterest.com/alcconstruction/ada-compliance/ https://www.youtube.com/watch?v=5I5m9trg50U http://www.vimeo.com/ http://www.flickr.com/ https://www.linkedin.com/company/3604848?trk=tyah&trkInfo=clickedVertical%3Acompany%2Cidx%3A1-4-4%2CtarId%3A1431354452032%2Ctas%3Aalc%20cons http://www.instagram.com/ http://www.rss.com/ https://www.ada-compliance.com/ https://www.ada-compliance.com/ada-compliance/2010-ada-standards https://www.ada-compliance.com/banner/medical-supply-depot-wheelchairs https://www.ada-compliance.com/banner/medical-supply-depot-wheelchairs https://www.ada-compliance.com/banner/biz-wiz-support https://www.ada-compliance.com/banner/biz-wiz-support https://www.ada-compliance.com/banner/alc-construction-llc.html https://www.ada-compliance.com/banner/alc-construction-llc.html http://www.joomace.net/joomla-extensions/acesef

ada-compliance.com
404 Doors, Doorways, and Gates - ADA Compliance - ADA Compliance

File details come from the government source that posted it. Updated .