Amendment 3- Medical Gas Panel Manufacturer Specs.pdf
PDF 1 MB Posted
- Solicitation number
- 36C225
About this file
This document provides installation instructions and specifications for an Amico 3-gas medical panel system. The instructions specify the wall framing and rough-in requirements, attachment of the back box and gas connections, installation of the art panel and frame movement assembly, and final connection to the hospital gas pipeline system. Product details include 16 gauge steel enclosure options for 3-gas or 5-gas configurations, swivel mounted gas outlets, and optional electrical receptacles. The installing contractor is responsible for mounting, overhead bracing, clean up, and final medical gas and electrical connections in accordance with all applicable codes.
The related federal contract opportunity is solicitation number 36C225 to relocate a community living center for veterans. Proposals are due by June 18, 2020 for the Department of Veterans Affairs project located at the Veterans Health Administration Veterans Integrated Service Network 15. The amendment provides questions and answers and attachments regarding the project scope and requirements.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Amendment 3-OIT.pdf | ||
| Amendment 3-GWN.pdf | ||
| 36C25520R0021 Amendment 0003.docx | DOCX document | |
| Amendment 3 -ACTIVATION INC1592685 - Predictive Analysis.pdf | ||
| Amendment 3-GUEST WIFI.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Corporation
Installation Instructions
Reflection Series Artwall
Note
Before Installation
ArtWall installation should conform to local building codes
The installation instructions provided are for the Amico standard products. Slight modifications to the installations may be required. The product shipped to the job site may not be exactly as shown on the installation drawings.
Review a copy of the final approved shop drawing(s) and/or submittal package. These docu-ments will include technical information specific to the installation, such as:
- equipment types & quantities
- room numbers and location
- shop drawings of each unit type
- wiring diagrams and rough-in locations
Locate the headwall unit from the shipping boxes.
The contents of each shipping box are listed on the shipping document(s).
Ensure wall is framed and roughed in as per applicable building standards to accept art wall back box. Allow 1/8” space on each side to allow for adjustment. Back box sizes are as follows:
3-gas box - 30 1/8 w x 21 1/8 h 5-gas box - 42 5/8 w x 21 1/8 h
1.
2.
3.
2 Amico Architectural
Typical example of 3-gas box with 3 gases note: vertical studs face each other top view
Attach art wall back box to wall structure using hardware compliant to applicable building codes. Allow gap between back box flange to stud faces for drywall to be attached later.
1.
www.amico.com 3 wall structure artwall back box gap for drywall
Make all medical gas connections from art wall to rough-ins. Medical gas pipes are terminated as per shop drawings.
Insert art into frame, then attach frame to backing plate and movement assembly, using hard-ware (provided by others). Ensure frame is centered on backing plate. Place assembly in a safe location.
Note: At this point, it is recommended for the wall to be finished, before proceeding. This will minimize interference of unit with trades, and keep remaining parts clean.
3.
typical gas termination location on artwall
2.
4 Amico Architectural
Attach frame and movement assembly to back box using hardware provided at loca-tions shown. Move frame as necessary to reach all of the hardware.
Tighten whiz flange screws using a 5/16” wrench.
Note: Frame shown removed to show parts behind. Do not remove!
4.
screw locations www.amico.com 5
Amico Architectural | www.amico.com
85 Fulton Way, Richmond Hill Ontario, L4B 2N4, Canada
71 East Industry Court, Deer Park
NY 11729, U.S.A
Toll Free Tel: 1.877.264.2697 Toll Free Fax: 1.866.440.4986 Tel: 905.763.7778 Fax: 905.763.8587 Email: info@amico.com INSTALL INSTR. ARTWALL 10.25.2013 www.amico.com
Reflection Series Artwall
Submittals and Verifications
Job specific shop drawings shall be produced for each project. These shop drawings will clearly indicate the area of Medical Gas termination. As Built drawings will be produced, and emailed at the time of shipment.
Amico Corporation will manufacture equipment as per signed approval drawings and verifications documents, which are provided in the job specific submittal package.
General Specifications
The Amico Reflection Series Artwalls shall be manufactured by Amico Corporation, in accordance with job specific shop drawings and documents. The following is a general specification, and components listed may not be present or required in final product.
The Reflection Series Artwall System complies with the seismic requirements of, and is approved by the State of California’s Office of Statewide Health Planning and Development (OSPHD). Amico Corporation manufactures all products in accordance with the National Fire Protection Association (NFPA), NFPA-99c (current edition) and National Electric Code (NEC).
The installation contractor is responsible for compliance with all local, state, and federal codes applicable to the installation of medical gas and electrical systems.
Figure 1. Reflection Series Artwalls
Distributed By:
Amico Corporation 85 Fulton Way, Richmond Hill, ON L4B 2N4, Canada | 71 East Industry Court, Deer Park, NY 11729, USA Toll Free Tel: 1.877.462.6426 | Toll Free Fax: 1.866.440.4986 | Tel: 905.764.0800 | Fax: 905.764.0862 www.amico.com
Reflection Series Artwall
Materials and Construction
Enclosure of the recessed unit shall be constructed of 16 gauge steel with a textured off-white powder coated paint finish.
Standard Reflection Series Artwalls are available in 3 and 5 gas configurations.
3 gas units are available in diagonal or horizontal left or right hand sliding Artwall configurations. These units accept framed prints 35" wide x 25" high (889 mm x 635 mm).
5 gas units are available in diagonal left or right hand sliding Artwall configurations. These units accept framed prints 46" wide x 25" high (1168 mm x 635 mm).
Units can accommodate up to two (2) one-gang electrical devices as an option.
Medical Gas Outlets Shall be recessed swivel mounted outlets to allow for use of secondary equipment while unit is closed. Amico Corporation manufactures several compatible connection types for Medical Gas and Vacuum Outlets. The outlet connection type shall be as called for on the signed approval documents. Medical gas piping for each outlet shall extend 5" (127 mm) above the unit for connection to the hospital medical gas pipeline.
Electrical Receptacles (Optional) Shall be Hospital Grade 15 or 20 amp, 120 or 277 volt, UL listed and marked Hospital Grade. Quantity and type as shown on drawings. Amico shall furnish and install receptacles as shown on submittal shop drawings. Electrical contractor shall insure compatibility of plug on accessory equipment to be used with these devices:
Duplex Receptacles shall be NEMA style 5-15R or 5-20R, color Ivory for use on normal power circuits, and color Red for use on critical branch power circuits.
Simplex Receptacles shall be NEMA style 5-15R or 5-20R, color Ivory for use on normal power circuits, and color Red for use on critical branch power circuits.
Safety Receptacles (if required) shall be duplex type, be NEMA style 5-15R or 5-20R, color Ivory for use on normal power circuits, and color Red for use on critical branch power circuits. Receptacles shall limit proper access to energized contracts and shall accept both 2 wire and 3 wire plugs.
Locking Receptacles (if required) shall be simplex type, 20 amp, 120 or 277 volt, color black, and be HUBBELL lock 23000 HG style, or equivalent.
Installation Mounting and final connections are the responsibility of the installing contractor. This includes receiving, storage, erection, overhead bracing, clean up, touch up, and carton disposal.
The contractor shall supply all necessary installation materials, including such items as tools, fasteners, calking and electrical lamps.
The medical gas contractor shall be responsible for piping and final connection of all medical gas services. The medical gas contractor shall be responsible for purging, pressure testing, gas identification and system certification in accordance with NFPA 99c (current edition) or CSA-Z7396.01-06.
Please refer to the Reflection Series Artwall installation instructions for further detail.
Product Code Definition
W-ARTWALL-XXY
• XX = Number of Gases (03, 05)
• Y = Direction of Artwall movement (L, R)
• VAC SLIDE = W-ART-SLIDE
AC-SP-ARTWALL 03.17.2017
O VA
AMICO 3-GAS ARTWALL SYSTEM
(M/N: W-ARTWALL-03L)
FEATURES:
-RECESSED ENCLOSURE (Ga. #16 PAINTED
STEEL)
-SWIVEL GAS OUTLETS
-FLOWMETERS & REGULATORS CAN BE
ATTACHED TO SWIVEL OUTLETS
-UPWARD PICTURE FRAME (DIAGONAL
LEFT) OR (DIAGONAL RIGHT) REFER TO
DRAWING
SYM QTY DESCRIPTION
O 1 AMICO GAS OUTLET, OXYGEN
A 1 AMICO GAS OUTLET, MED AIR
V 1 AMICO GAS OUTLET, VACUUM
SLM 1 VACUUM SLIDE
SYSTEM DETAILS
DRAWING # 00
PATIENT ROOM
HOSPITAL
LOCATION
MFGR. : TBC MODEL No. : TBC
MFGR. : AMICO TYPE CONNECTION : TBC
TBC N/A
IMPORTANT: PLEASE VERIFY THAT THE ABOVE INFORMATION IS
CORRECT, AND PROVIDE THE REMAINING DETAILS. APPROVAL - PRINT AND SIGNATURE DATE PHONE NO.
UNIT AS SHOWN - N.T.S.
File details come from the government source that posted it. Updated .