Amendment 1 Answers for Kewanee Fire Alarm Repair Bid 05.20.26.pdf
PDF 46 KB Posted
- Attached to
- IDOC - Kew-Fire Alarm system Repairs-SRN
- Solicitation number
- 26-426DOC-KEWAN-B-52426
- Issued by
- Hardin County, Illinois
About this file
This is Amendment 1 to a Request for Quote issued by the Illinois Department of Corrections (IDOC) for fire alarm system repairs at the Kewanee Life Skills Re-Entry Center. The amendment provides vendor responses to pre-bid conference questions regarding the scope and condition of the existing fire alarm safety system. An inspection was completed on October 15, 2025, identifying multiple deficiencies requiring repair and replacement across five fire alarm panels distributed throughout the facility. The work includes troubleshooting communication network failures between panels and remote annunciators, replacing failed batteries in the main building and Housing Units 1, 2, and 3, programming heat detectors in the Security Building, addressing communication faults and fan shutdown relay replacement in Housing Units 4, 5, and 6, replacing a burned-out LCD screen on the Housing Units 1, 2, and 3 panel, and replacing failed strobe and heat detectors in Housing Unit 2. The amendment confirms that control panels are not currently communicating despite having functioned previously, and that fiber optics infrastructure is in place and has been tested as acceptable. A mandatory pre-bid conference and site visit is scheduled for May 20, 2026, with bids due by May 29, 2026, and all work completion required by September 30, 2026.
All work must be performed by EST-certified technicians during business hours (Monday through Friday, 7:30 a.m. to 3:00 p.m., excluding holidays) and includes labor, materials, equipment, and tools. Vendors must comply with prevailing wage requirements per the Illinois Department of Labor, maintain General Commercial Liability insurance of $1,000,000 per occurrence and $2,000,000 annual aggregate, Auto Liability insurance of $1,000,000 per occurrence, and Worker's Compensation Insurance as required by law. All vendor personnel are subject to background investigations including drug screening and must comply with facility security protocols. Subcontracting is not permitted. The contract will be awarded to the responsive and responsible vendor offering the lowest price, with vendor bids remaining firm for 120 days from opening. The vendor is responsible for all transportation and delivery costs on an FOB Destination basis, with travel time and expenses not reimbursable. The specific maximum contract amount has not been disclosed and will be entered by the State prior to contract execution.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| B-52426 Fire Alarm System Repairs RFQ~1.docx | DOCX document | |
| Standard Illinois Certifications V.26.2~43.pdf | ||
| standard-terms-and-conditions V.23.2_13~82.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DOC-KEW-Fire Alarm System Repairs Bid #26-426DOC-KEWAN-B-52426
Amendment #1 Response to Vendor’s Questions Pre-Bid Conference
Below is the response to the questions IDOC received regarding the above RFQ:
1. Vendor: Has there been an inspection completed?
Answer: Yes, an inspection was completed on October 15, 2025
2. Vendor: What were the deficiencies found during the inspection?
Answer: This information was received via the Kewanee Fire Chief of the Kewanee Fire Department: Communication network not functioning correctly as all panel due not communicate properly with each other or with its remote annunciators. This si causing communication trouble at the first alarm panel.
Issue need to be troubleshoot by an EST technician. There are 5 fire alarm panels on site, 1 for every building.
Batteries for the following buildings have failed the load test due to a low internal charge when they were tested. Main building, main FACP in VR RM across from East dining NAC (RIGHT), Housing untis 1, 2, 3. Main FACP NAC in FACP room Security Building – Heat Detector in the Fire Safety Storage Room reports to the fire alarm panel when in alarm, but does not activate the horns and strobes in the building. Programming for this device needs to be checked by an EST Technician.
Housing Unit 4, 5, 6 Building Panel has a communication fault for Fan shutdown relay on H6 Mezzanine and needs to be replaced after issue Housing unit 1, 2, 3 building LCD Screen for the fire alarm panel is burned out and needs to be replaced. Strobe and heat detector in H2 failed and needs to be replaced.
3. Are the control panels communicating?
Answer: NO
4. Have they ever communicated?
Answer: Yes, prior to replacement panels and upgrades
5. Is there Fibre Optics?
Answer: Yes
6. Have they been tested?
Answer: Yes all we deemed good