The file's text, extracted by GovTribe without its formatting.
Sheet1
| LOCATION | DATE - 1 | TIME | DISTANCE | |
| Clayton Tower | 12-Jun | 9:00 | 75 miles | Wayne |
| 49 Kennedy Tower Rd | | | | |
| Clayton, Alabama 36016 | | | | |
| Decatur Post | 9-Jun | 9:30 | Kerri |
| 207 Commerce Circle SW, Suite A | | | |
| Decatur, Alabama 35601 | | | |
| | | 35 miles | |
| Monte Sano Tower | 9-Jun | 11:30 | | Kerri |
| Monte Sano State Park | | | | |
| 5105 Nolen Ave., Building T | | | | |
| Huntsville, Alabama 35801 | | | | |
| Evergreen Post | 10-Jun | 9:00 | 82 miles | Michael |
| 106 Hillcrest Drive | | | | |
| Evergreen, Alabama 36401 | | | | |
| Hamilton Post | 17-Jun | 10:00 | 176 miles | Kerri |
| 4521 Military Street | | | | |
| Hamilton, Alabama 35570 | | | | |
| Jacksonville Post | 11-Jun | 10:00 | Robbie |
| 1703 Pelham Road South | | | |
| Jacksonville, Alabama 36265 | | | |
| | | 82 miles | |
| Alexander City Tower | 11-Jun | 12:00 | | Robbie |
| 421 Adams Circle | | | | |
| Alexander City, Alabama 35010 | | | | |
| Montgomery Post | 15-Jun | 2:00 | Wayne & Michael |
| 1708 Congressman W. L. Dickinson Drive | | | |
| Montgomery, Alabama 36109 | | | |
| Montgomery Radio Shop | 15-Jun | 2:30 | Wayne & Michael |
| 1038 Coliseum Blvd. | | | |
| Montgomery, Alabama 36109 | | | |
| Tuscaloosa Tower | 23-Jun | 10:00 | Robbie |
| 2715 Skyland Blvd | | | |
| Tuscaloosa, Alabama 35010 | | | |
| | | 50 miles | |
| Birmingham Post | 23-Jun | 12:00 | | Robbie |
| 908 Bankhead Hwy West | | | | |
| Birmingham, Alabama 35204 | | | | |
Sheet2 5/11 - Track-It - 184682 / 5/12 - RQ260000351367 / FY26/ RADIO - Clayton Tower Generator
5/11 - Track-It - 184683 / 5/12 - RQ260000351434 / FY26 / RADIO - Decatur Post Generator
5/11 - Track-It - 184685 / 5/12 - RQ260000351446 / FY26 / RADIO - Evergreen Post Generator
5/11 - Track-It - 184686 / 5/12 - RQ260000351456 / FY26 / RADIO - Hamilton Post Generator
5/12 - Track-It - 184749 / 5/13 - RQ260000351488 / FY26 / RADIO - Jacksonville Post Generator
5/12 - Track-It - 184750 / 5/13 - RQ260000351489 / FY26 / RADIO - Monte Sano Tower Generator
5/12 - Track-It - 184751 / 5/13 - RQ260000351494 / FY26 / RADIO - Montgomery Post Generator
5/12 - Track-It - 184752 / 5/13 - RQ260000351498 / FY26 / RADIO - Montgomery Radio Shop Generator
5/12 - Track-It - 184753 / 5/13 - RQ260000351514 / FY26 / RADIO - Tuscaloosa Tower Generator
5/12 - Track-It - 184754 / 5/13 - RQ260000351519 / FY26 / RADIO - Alexander City Tower Generator
5/12 - Track-It - 184758 / 5/13 - RQ260000351531 / FY26 / RADIO - Birmingham Post Generator
Sheet3
| Clayton | The requirements for a certified electrician will need to be added. |
| Will a Plumber/Gas Fitter’s license be required? |
| Is ALEA okay with sub-contracting different parts of this work, such as the electrical, gas fitting/propane disconnect? If the answer is yes, we will need to require a GC license. |
| Please remove all terms not related directly to the scope of work. We will add the site visit information and any standard terms and conditions. |
| The specifications will need to start off with a purpose summary, the contact information needs to be modified to remove any phone numbers or emails until after the bid has been awarded |
| We need an insurance amount for Liability, and we will add Workman’s comp, too. |
| Please change RFB to ITB in General section. |
| Under Scope of Work, #2, where it states, “All wiring, connections, and grounding should (change to shall) be installed per local code (change to industry standard).” |
| Decatur | The requirements for a certified electrician will need to be added. |
| Will a Plumber/Gas Fitter’s license be required? |
| Is ALEA okay with sub-contracting different parts of this work, such as the electrical, gas fitting/propane disconnect? If the answer is yes, we will need to require a GC license. |
| Please remove all terms not related directly to the scope of work. We will add the site visit information and any standard terms and conditions. |
| The specifications will need to start off with a purpose summary, the contact information needs to be modified to remove any phone numbers or emails until after the bid has been awarded |
| We need an insurance amount for Liability, and we will add Workman’s comp, too. |
| Please change RFB to ITB in General section. |
| Under Scope of Work, #2, where it states, “All wiring, connections, and grounding should (change to shall) be installed per local code (change to industry standard).” |
| Evergreen | The requirements for a certified electrician will need to be added. |
| Will a Plumber/Gas Fitter’s license be required? |
| Is ALEA okay with sub-contracting different parts of this work, such as the electrical, gas fitting/propane disconnect? If the answer is yes, we will need to require a GC license. |
| Please remove all terms not related directly to the scope of work. We will add the site visit information and any standard terms and conditions. |
| The specifications will need to start off with a purpose summary, the contact information needs to be modified to remove any phone numbers or emails until after the bid has been awarded |
| We need an insurance amount for Liability, and we will add Workman’s comp, too. |
| Please change RFB to ITB in General section. |
| Under Scope of Work, #2, where it states, “All wiring, connections, and grounding should (change to shall) be installed per local code (change to industry standard).” |
| Hamilton | The requirements for a certified electrician will need to be added. |
| Will a Plumber/Gas Fitter’s license be required? |
| Is ALEA okay with sub-contracting different parts of this work, such as the electrical, gas fitting/propane disconnect? If the answer is yes, we will need to require a GC license. |
| Please remove all terms not related directly to the scope of work. We will add the site visit information and any standard terms and conditions. |
| The specifications will need to start off with a purpose summary, the contact information needs to be modified to remove any phone numbers or emails until after the bid has been awarded |
| We need an insurance amount for Liability, and we will add Workman’s comp, too. |
| Please change RFB to ITB in General section. |
| Under Scope of Work, #2, where it states, “All wiring, connections, and grounding should (change to shall) be installed per local code (change to industry standard).” |
| Jacksonville | The requirements for a certified electrician will need to be added. |
| Will a Plumber/Gas Fitter’s license be required? |
| Is ALEA okay with sub-contracting different parts of this work, such as the electrical, gas fitting/propane disconnect? If the answer is yes, we will need to require a GC license. |
| Please remove all terms not related directly to the scope of work. We will add the site visit information and any standard terms and conditions. |
| The specifications will need to start off with a purpose summary, the contact information needs to be modified to remove any phone numbers or emails until after the bid has been awarded |
| We need an insurance amount for Liability, and we will add Workman’s comp, too. |
| Please change RFB to ITB in General section. |
| Under Scope of Work, #2, where it states, “All wiring, connections, and grounding should (change to shall) be installed per local code (change to industry standard).” |
| Monte Sano | The requirements for a certified electrician will need to be added. |
| Will a Plumber/Gas Fitter’s license be required? |
| Is ALEA okay with sub-contracting different parts of this work, such as the electrical, gas fitting/propane disconnect? If the answer is yes, we will need to require a GC license. |
| Please remove all terms not related directly to the scope of work. We will add the site visit information and any standard terms and conditions. |
| The specifications will need to start off with a purpose summary, the contact information needs to be modified to remove any phone numbers or emails until after the bid has been awarded |
| We need an insurance amount for Liability, and we will add Workman’s comp, too. |
| Please change RFB to ITB in General section. |
| Under Scope of Work, #2, where it states, “All wiring, connections, and grounding should (change to shall) be installed per local code (change to industry standard).” |
| Montgomery | The requirements for a certified electrician will need to be added. |
| Will a Plumber/Gas Fitter’s license be required? |
| Is ALEA okay with sub-contracting different parts of this work, such as the electrical, gas fitting/propane disconnect? If the answer is yes, we will need to require a GC license. |
| Please remove all terms not related directly to the scope of work. We will add the site visit information and any standard terms and conditions. |
| The specifications will need to start off with a purpose summary, the contact information needs to be modified to remove any phone numbers or emails until after the bid has been awarded |
| We need an insurance amount for Liability, and we will add Workman’s comp, too. |
| Please change RFB to ITB in General section. |
| Under Scope of Work, #2, where it states, “All wiring, connections, and grounding should (change to shall) be installed per local code (change to industry standard).” |
| Montgomery Radio | The requirements for a certified electrician will need to be added. |
| Will a Plumber/Gas Fitter’s license be required? |
| Is ALEA okay with sub-contracting different parts of this work, such as the electrical, gas fitting/propane disconnect? If the answer is yes, we will need to require a GC license. |
| Please remove all terms not related directly to the scope of work. We will add the site visit information and any standard terms and conditions. |
| The specifications will need to start off with a purpose summary, the contact information needs to be modified to remove any phone numbers or emails until after the bid has been awarded |
| We need an insurance amount for Liability, and we will add Workman’s comp, too. |
| Please change RFB to ITB in General section. |
| Under Scope of Work, #2, where it states, “All wiring, connections, and grounding should (change to shall) be installed per local code (change to industry standard).” |
| Tuscaloosa | The requirements for a certified electrician will need to be added. |
| Will a Plumber/Gas Fitter’s license be required? |
| Is ALEA okay with sub-contracting different parts of this work, such as the electrical, gas fitting/propane disconnect? If the answer is yes, we will need to require a GC license. |
| Please remove all terms not related directly to the scope of work. We will add the site visit information and any standard terms and conditions. |
| The specifications will need to start off with a purpose summary, the contact information needs to be modified to remove any phone numbers or emails until after the bid has been awarded |
| We need an insurance amount for Liability, and we will add Workman’s comp, too. |
| Please change RFB to ITB in General section. |
| Under Scope of Work, #2, where it states, “All wiring, connections, and grounding should (change to shall) be installed per local code (change to industry standard).” |
| Alexander City | The requirements for a certified electrician will need to be added. |
| Will a Plumber/Gas Fitter’s license be required? |
| Is ALEA okay with sub-contracting different parts of this work, such as the electrical, gas fitting/propane disconnect? If the answer is yes, we will need to require a GC license. |
| Please remove all terms not related directly to the scope of work. We will add the site visit information and any standard terms and conditions. |
| The specifications will need to start off with a purpose summary, the contact information needs to be modified to remove any phone numbers or emails until after the bid has been awarded |
| We need an insurance amount for Liability, and we will add Workman’s comp, too. |
| Please change RFB to ITB in General section. |
| Under Scope of Work, #2, where it states, “All wiring, connections, and grounding should (change to shall) be installed per local code (change to industry standard).” |
| Birmingham | The requirements for a certified electrician will need to be added. |
| Will a Plumber/Gas Fitter’s license be required? |
| Is ALEA okay with sub-contracting different parts of this work, such as the electrical, gas fitting/propane disconnect? If the answer is yes, we will need to require a GC license. |
| Please remove all terms not related directly to the scope of work. We will add the site visit information and any standard terms and conditions. |
| The specifications will need to start off with a purpose summary, the contact information needs to be modified to remove any phone numbers or emails until after the bid has been awarded |
| We need an insurance amount for Liability, and we will add Workman’s comp, too. |
| Please change RFB to ITB in General section. |
| Under Scope of Work, #2, where it states, “All wiring, connections, and grounding should (change to shall) be installed per local code (change to industry standard).” |