Air Balancing Spreadsheet.xlsx

XLSX spreadsheet 17 KB Posted

Attached to
H245--Ventilation Testing and Air Balancing Services | Baltimore VAMC-Amendment 0001
Solicitation number
36C24523Q0593
Issued by

About this file

This document contains an air balancing spreadsheet and information on a related federal contract opportunity.

The air balancing spreadsheet lists various rooms in an animal research area, endoscopy suite, and operating room suite. It includes details on room numbers, required and actual room volumes, required air changes per hour, and direction of air flow. The related federal contract opportunity is solicitation number 36C24523Q0593 from the Department of Veterans Affairs for ventilation testing and air balancing services at the Baltimore VA Medical Center. The solicitation provides information on an amendment to the opportunity. Services required include testing and balancing of the ventilation systems and air flows listed in the spreadsheet. Relevant details such as response dates, pricing terms, or set-asides are not included in the provided information.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Sheet1

BB ANIMAL RESEARCG AREA ROOMLEVEL 3 ENDOSCOPY SUITE ROOMLEVEL B SPS SUITE ROOM
RoomRequiredRequiredActualRoomRequiredRequiredActualRoomRequiredRequiredActual
Room #VolumeACHDirectionDirectionRoom #VolumeACHDirectionDirectionRoom #VolumeACHDirectionDirection
BB1064494NegativeNegative3D146214610PositiveNegativeBD123A788312NegativeNegative
BB106A153915NegativeNegative3D147176910PositivePositiveBD124H2151.7212**NegativeNegative
BB106B137615NegativeNegative3D142213210PositiveNegativeBD124E1137012PositivePositive
BB1094724NegativeNegative3D141147510PositivePositiveBD124I1751.4912NegativeNegative
BB109A138415NegativeNegative3D1448264PositiveNegativeBD127A STERILE STORAGE1100638*4PositivePositive
BB109B139815NegativeNegative3D1457604NegativePositive
BB11011484+/-PositiveISOLATION/ANTEROOM
BB110A5794+/-PositiveRoomRequiredRequiredActual
BB110B8564+/-PositiveRoom #VolumeACHDirectionDirection
BB113401415NegativeNegative
BB1142684+/-Negative1D106127612NegativeNegative
BB115138715NegativeNegative1D10474810NegativeNegative
BB11690315NegativeNegative3A-121274310NegativeNegative
BB117636915NegativeNegative3A-123204512NegativeNegative
BB11812956+/-Positive3A-124A192412NegativeNegative
BB119134815Negative*3A-127170812NegativeNegative
BB120133115NegativeNegative3B-199145312NegativeNegative
BB1214814PositivePositive3B-199A46510NegativeNegative
BB12220784PositivePositive3B-201138512NegativeNegative
BB123337220NegativeNegative3B-201A48910NegativeNegative
BB124194215NegativeNegative4C-114205412NegativeNegative
BB125194115NegativeNegative4C-114A26910NegativeNegative
BB12622766+/-+/-4C-115194512NegativeNegative
BB127194215NegativeNegative4C-115A26110NegativeNegative
BB128194315NegativeNegative4C-127187412NegativeNegative
BB12914476+/-Negative4C-127A35310NegativeNegative
BB13113876NegativeNegative4C-128168812NegativeNegative
BB132121710NegativeNegative4C-128A32310NegativeNegative
BB132A100515NegativeNegative5B-199152312NegativeNegative
BB132B108415NegativeNegative5B-199A46910NegativeNegative
BB13822596+/-Negative5B-201138312NegativeNegative
BB139108715NegativeNegative5B-201A49510NegativeNegative
BB14097515NegativeNegativeLEVEL 5 OR SUITE ROOM
BB141106715NegativeNegativeRoomRequiredRequiredActual
BB14211724+/-NegativeRoom #VolumeACHDirectionDirection
BB14321954NegativeNegative5D121473220PositivePositive
BB143A134015NegativeNegative5D123476220PositiveNeg/Pos
BB143B120715NegativeNegative5D110433620PositivePositive
BB14413794+/-Negative5D109430320PositivePositive
BB14511156NegativeNegative5D105557520PositivePositive
BB14610554PositivePositive5D104549520PositivePositive
BB1478494PositivePositive5D103538520
CB-1650064NegativeNegative5D10153454PositivePositive
CB-1747154NegativeNegative5D100485020PositivePositive
CB-1944774+/-Neutral5D124110760Neutral
CB-2010754NANA5D124 DIRTY38249NegativeNegative
CB-2216534+/-Positive5D124 CLEAN6356PositivePositive
CB-2315604+/-Positive5D10850520PositiveNegative
CB-249664+/-PositiveC5-52*183616PositivePositive
CB-2529234NegativeNegative
CB-266274NegativeNegative