Building 154 Replace Chilled Water and Condenser Water Shut Off Valves
Solicitation number
AG-6197-S-17-0013
Issued by

About this file

Q&A

View the file

Other files

Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1. What’s the elevation of the existing horizontal chilled water and condenser water lines? Elevation of the pipes from finish floor to estimated centerline of pipe are as follows:

· Chilled Water supply = 224” off finish floor

· Chilled Water return = 204” off finish floor

· Condenser Water supply = 236” off finish floor

· Condenser water return = 236” off finish floor

2. What height is the chain to be above the finished floor for the chain operators? The chain shall extend from the valve down to 36” off finish floor.