Paraloft Roof Replacement
AG-04GG-S-17-0006
Redmond Air Center
Additional Question and Answer from Site Visit:
Question: Will exposed fasteners be acceptable on the underside of the roof deck or can we omit the base sheet and adhere all layers of roofing to avoid mechanical fasteners?
Answer: 1. For sheathing, reference Specification 061600, para 2.02, Fasteners.
2. For the TPO roofing, reference Specification 075423, para. 2.2.B, Attachment System.
In both cases, the specifications require that whatever approach you use, it must comply with manufacturer requirements.
This response does NOT change the requirements of the specifications attached to the solicitation.