Northeast Florida State Hospital Fire Alarm Replacement
Solicitation number
ITB-02620
Issued by
Baker County, Florida

About this file

This document is an Addendum to the Invitation to Bid (ITB) for the fire alarm system replacement project at the Northeast Florida State Hospital (NEFSH) in Florida. The Department of Children and Families (DCF) is soliciting bids from qualified vendors to provide installation, maintenance, alteration, repair, monitoring, inspection, replacement, and servicing of the fire alarms and fire alarm systems across multiple buildings on the NEFSH campus. The addendum includes responses to written inquiries from vendors, clarifying information about existing equipment, cabling, drawings, inspections, and other project requirements. The solicitation response due date is October 17, 2022.

The specifications indicate a preference for a specific fire alarm system manufacturer and require the awarded contractor to have a physical office location within 100 miles of the project site. The project involves maintaining existing fire alarm systems during the replacement process. Asbestos-containing materials may be present in some areas. The contractor will be responsible for coordinating training for the local fire department. Pricing details, funding sources, and incumbent information are not provided in this addendum.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Addendum No. 04 with Written Inquiry Responses

DCF ITB 2122 054

Northeast Florida State Hospital Fire Alarm Replacement

Solicitation Number: DCF ITB 2122 054 Solicitation Title: Northeast Florida State Hospital Fire Alarm Replacement Response(s) Due Date: 10/17/2022 Addendum Number: 04 Addendum Date: 10/24/2022

FAILURE TO FILE A PROTEST WITHIN THE TIME PRESCRIBED IN SECTION 120.57(3), FLORIDA STATUTES, OR FAILURE TO POST THE BOND OR OTHER SECURITY REQUIRED BY LAW WITHIN THE

TIME ALLOWED FOR FILING A BOND SHALL CONSTITUTE A WAIVER OF PROCEEDINGS UNDER

CHAPTER 120, FLORIDA STATUTES.

DCF ITB 2122 054 is hereby amended as follows, all other terms and conditions of the solicitation remain in effect. All additions are highlighted in yellow, and words stricken are deletions:

Change No. 1

Standard Contract Part 2, EXHIBIT L –TECHNICAL REQUIREMENTS

A copy of the Technical Requirements including Specifications, Bid Package A, Bid Package B, NEFSH Fire Alarm Reports, Asbestos Reports, and Contractor parameters for this project are available via email request to:

Sally.Johns@myflfamilies.com Please Copy:

HQW.Procurement.Team.Activities@myflfamilies.com

REMAINDER OF PAGE INTENTIONALLY LEFT BLANK

mailto:Sally.Johns@myflfamilies.com mailto:HQW.Procurement.Team.Activities@myflfamilies.com

Response to Written Inquiries:

Question Number

Vendor Name

Document and Section Reference

Question Department Response

1 of 18 ADT Commercial

Is the intent of this solicitation to provide complete fire alarm system replacements in all buildings on campus?

Refer to Section 1(1.1) Introduction to the Procurement.

Appendix V and Standard Contract Part 2 - Exhibit L for complete list of buildings on campus that require replacement.

2 of 18 ADT Commercial

If yes, will the existing fire alarm systems be required to remain in service during the system replacements?

(Note – this would require new conduit and cabling to be installed and significantly increase the replacement cost)

Refer to Exhibit L, Section 283100(1.9) & (1.10) – Existing Fire Alarm Equipment will be maintained and fully operational until new equipment has been tested and accepted.

3 of 18 ADT Commercial

Are there any known existing fire alarm cabling issues in any of the included buildings?

Existing cabling issues are unknown.

4 of 18 ADT Commercial

Is there a specification or preferred manufacturer?

Refer to Exhibit L, Section 283100(2.1)

5 of 18 ADT Commercial

Will as-built fire alarm drawings be made available to interested bidders?

No.

6 of 18 ADT Commercial

Will you provide the latest fire alarm inspection reports on all included buildings?

Yes, refer to Change No. 1.

7 of 18 W.W. Gay F&I Systems

PLEASE CONFIRM

WARRANTY

PERIOD FOR FIRE

ALARM SYSTEM

AND SERVER

WORKSTATION

Refer to Exhibit L, Section 284622 (1.11) Provide warranty for the entire fire alarm system in accordance with Specification Section.

8 of 18 W.W. Gay F&I Systems

PLEASE PROVIDE

PREFERED

SERVICE

PROVIDER FOR

EXISTING

MILESTONE VIDEO

MANAGEMENT

SYSTEM

Split Pine Technologies LLC, Tallahassee, FL 850-323-0600 Sam Waddill

9 of 18 W.W. Gay F&I Systems

Page 20, Section 26 05 30, Para.

3.18; (A) 1

SHALL ALL

CONDUCTORS

INSTALLED FOR

THE COMPLETE

FUNCTIONAL FIRE

ALARM SYSTEM BE

SUBJECT TO

INSULATION

"MEGGER"

TESTING.

Refer to Exhibit L, Section 260530(3.18) – General Tests and Inspections to be completed

10 of 18 W.W. Gay F&I Systems

Page E-501, Section 3

PLEASE CONFIRM

IT IS THE INTENT

TO INSTALL

ACCESS PANELS

AT EACH DAMPER

DUCT DETECTOR.

Refer to Exhibit L, Section 260530(1.6) (D) – Coordinate location of access panels and doors for electrical items that are concealed by finished surfaces.

11 of 18 W.W. Gay F&I Systems

IS THERE A

PREFERED

MECHANICAL

CONTRACTOR

CURRENTLY

SERVICING THE

HVAC SYSTEM

No

12 of 18 W.W. Gay F&I Systems

Page E-501, Section 3

CAN IT BE

CONFIRMED THAT

INSULATION ON

ALL DUCTED AIR

SYSTEM THAT WILL

REQUIRE DUCT

DETECTOR OR

DAMPER IS FREE

FROM ASBESTOS

OR HAZORDOUS

MATERIALS.

No, refer to Change No. 1.

13 of 18 W.W. Gay

Page 1, Section 28 31 00, Para.

1.4; (A)

PLEASE CLARIFY

THIS REFERENCE,

WILL INSTALLING

CONTRACTOR

HAVE A "BRICK

AND MORTOR"

LOCATION WITHIN

150 MILES FROM

7487 STATE ROAD

121, MACCLENNY,

FL

The intent of the specification is that the three-factory authorized, trained, and certified distributors/contractors have a physical, permanent office within a 150-mile radius of the project site. See response to question 17 for installing Contractor location specification.

14 of 18 W.W. Gay

WILL ANY

DRAWINGS, DATA

OR INSPECTIONS

BE REQUIRED BY

THE LOCAL BAKER

COUNTY FIRE

PREVENTION

No

15 of 18 W.W. Gay F&I Systems

WILL

CONTRACTOR BE

RESPONSIBLE FOR

PROVIDING ANY

NOX BOX

No

16 of 18 W.W. Gay F&I Systems

WILL

CONTRACTOR BE

RESPONSIBLE TO

CORIDINATE ANY

TRAINING FOR

LOCAL FIRE

DEPARTMENT AND

THEIR RESONSE

TRAINING

Provide training in accordance with Exhibit L, Section 283100(3.3) & (3.6), and Section 284622(3.8) (E.).

17 of 18 W.W. Gay F&I Systems

Page 1, Section 27 00 20, Para.

1.3; 1

PLEASE CLARIFY

THIS REFERENCE,

WILL INSTALLING

CONTRACTOR

HAVE A "BRICK

AND MORTOR"

LOCATION WITHIN

100 MILES FROM

7487 STATE ROAD

121, MACCLENNY,

FL.

Yes, the Contractor shall have an existing permanent office located within 100 miles of the job site from which installation and warranty service operations will be performed.

18 of 18 W.W. Gay

HAS AHCA

INSPECITONS

WENT TO FULL

LIVE IN PERSON

INSPECTIONS AND

NO LONGER

VIRTUAL

Contractor shall coordinate AHCA inspections, whether in-person or virtual.