Addendum One .pdf

PDF 8 MB Posted

Attached to
RFB-211-24 DJJ Adair YDC Sewage Grinder Pit Relocation
Solicitation number
RFB 785 2400000488 5
Issued by
Adair County, Kentucky

About this file

This is Addendum One to an Invitation to Bid (RFB-211-24) issued by the Commonwealth of Kentucky Department for Facilities and Support Services, Division of Engineering and Contract Administration, for the Sewage Grinder Pit Relocation project at the Adair Youth Development Center operated by the Department of Juvenile Justice in Adair County, Kentucky. The project involves the relocation and installation of a new duplex submersible grinder pump station to replace an existing pump station, including associated plumbing, electrical, and site work. The scope includes removal of the existing pump station and control panel, installation of new underground gravity sanitary piping routed to a new duplex grinder pump station with traffic-rated split cover, installation of new pump discharge piping approximately 750 linear feet around the building, electrical feeder installation from the existing emergency power panel, and replacement of pavement and concrete slabs as required. The addendum, dated March 6, 2024, directs bidders to refer to specifications and drawings to be distributed by Lynn Imaging for all additions, deletions, and changes to specifications and drawings. The documents include detailed plumbing plans (existing, demolition, and new work), electrical power plans, and comprehensive specifications for the duplex pump package manufactured by Landia.

The project specifications require the duplex pump station to operate at 150 gallons per minute at 11 feet of total dynamic head with two submersible chopper pumps (Model DG-I-65 or approved equal), powered by 17.9 horsepower motors at 208 volts, 60 Hz, three-phase. The contractor must provide a one-year warranty from the date the pump station is tested and placed in service, including all necessary adjustments, repairs, and maintenance to ensure guaranteed capacities and performances. All work must comply with current state and local building codes, with permits and fees secured by the contractor and included in the bid price. The contractor is required to provide temporary restroom facilities throughout construction, maintain the existing pump station operational until the new system is tested and reconnected, and ensure that a manufacturer's accredited representative supervises installation and testing and provides operating and maintenance instruction to owner personnel. The existing pump station equipment to be removed must be returned to the owner in good condition, and the contractor must contact all utility companies prior to demolition and excavation work.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

COMMONWEALTH OF KENTUCKY

DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES

DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION

INVITATION TO BID NO: RFB-211-24

FOR: Sewage Grinder Pit Relocation Adair Youth Development Center Department of Juvenile Justice Adair County, Kentucky

DATE: March 6, 2024

RFB-785-2400000488

ADDENDUM NO. One (1)

BIDDER SHALL CONFORM TO THE FOLLOWING CHANGES AS SAME SHALL BECOME BINDING

UPON THE CONTRACT TO BE ISSUED IN RESPONSE TO THIS INVITATION TO BID.

Item 1: Refer to addendum to be distributed by Lynn Imaging for all additions, deletions, and/or changes to specifications and/or drawings.

END OF ADDENDUM

Invitation to Bid No. RFB-211-24 For: Sewage Grinder Pit Relocation Adair Youth Development Center Department of Juvenile Justice Adair County, Kentucky

Susan Ward, Statewide Procurement Analyst II Division of Engineering and Contract Administration

4"PD

(E )3

/4 "G

(E )1

"C W

(E)3/4"G

(E)3"CW

(E)ELEC

(E)ELEC

(E)ELEC

(E)3"G (E)3"G (E)3"G

(E)3"CW (E)3"CW

(E)ELEC

VRH

TRG

ACCOUNT NO.

523-CAWT-AC12-00

TRG PSCArchitects - Engineers - Landscape Architects The Roberts Group

239 Southland Drive - Lexington, KY 40503 859-276-2006 - 859-276-2901 Facsimile

DJJ - ADAIR YDC SEWAGE GRINDER PIT RELOCATION

DEPARTMENT FOR JUVENILE JUSTICE

COLUMBIA, KY

DRAWING NO.

DECA REVIEWED

PHASE

FOR INTENT ONLY

DRAWING INFORMATION

DRAWING DATE

DRAWN BY

CHECKED BY

A&E FILE NO.

DECA LOG #

"D"

COMMONWEALTH OF KENTUCKY

FINANCE AND ADMINISTRATION CABINET

DEPARTMENT FOR FACILITIES MANAGEMENT

DIVISION OF ENGINEERING

FRANKFORT, KENTUCKY

02/16/2024

ST

ATE OF KENTUCKY

P R

O

FESS I ONA L ENG

I N E

E R

L

I C E N S E

D

DATEDESCRIPTION OF REVISIONS

REVISION HISTORY OF THIS DRAWING

DATEDESCRIPTION OF REVISIONS

XXX

P:

\K

YS

ta te \2

-C O

LU

M

BI

A-

KY

-D

JJ

P

LB

G

P R

O

JE

C T\

-E

LE

C

\2

E1 .0

PA

R

TI

AL

E

LE

C

TR

IC

AL

P

O W

ER

P

LA

N

.d w g

W ed ne sd ay , M ar ch

6, 7:

A

M Th e R ob er ts G ro up

G re g

El am

TRG #23035

E1.0

EXPIRATION: 06/30/2025

RTA 02/16/2024

PARTIAL ELECTRIC POWER PLAN - NEW WORK

1 PARTIAL ELECTRICAL PLAN - NEW WORK

1/8" = 1'-0"

GENERAL NOTES:

A. EXISTING UTILITY LOCATIONS INDICATED ON THESE DRAWINGS ARE

BASED ON AS-BUILT DRAWINGS PROVIDED AFTER COMPLETION OF THE

ORIGINAL PROJECT. IN ADDITION TO CONTACTING ALL SUPPORTING

UTILITY COMPANIES AND SERVICES TO PROVIDE A MORE PRECISE UP TO

DATE LOCATION OF EACH SERVICE. LOCATIONS INDICATED ARE SHOWN

TO THE BEST OUR ABILITY. HOWEVER, THE CONTRACTOR SHALL STILL

CONFIRM EXACT UTILITY LOCATIONS AND TAKE PROPER PRECAUTIONS

DURING EXCAVATION AND CONSTRUCTION.

SHEET KEYED NOTES:

1. EXISTING PANEL EB, 120/208 VOLT, 3-PHASE WITH 3-POLE, 50 AMP BREAKER

FEEDING EXISTING PUMP STATION CONTROL PANEL. BREAKER TO BE RE-LABELED

AS SPARE AFTER NEW PUMP STATION IS ON LINE.

2. EXISTING OVERHEAD CONDUIT AND FEEDER TO EXISTING PUMP STATION

CONTROL PANEL. DISCONNECT AND REMOVE COMPLETE AFTER NEW PUMP

STATION IS ON LINE.

3. EXISTING PUMP STATION AND CONTROL PANEL TO BE REMOVED AFTER NEW

PUMP STATION IS ON LINE. RETURN CONTROL PANEL AND PUMPS TO OWNER IN

GOOD CONDITION.

4. NEW SUBMERSIBLE GRINDER PUMP STATION. PROVIDE POWER AND CONTROLS

FROM CONTROL PANEL TO PUMPS AS REQUIRED.

5. NEW PUMP STATION CONTROL PANEL PROVIDED WITH EQUIPMENT, INSTALLED

BY CONTRACTOR. COORDINATE EXACT LOCATION AND METHOD OF MOUNTING

WITH PUMP STATION SUPPLIER. PROVIDE STATUS AND CONTROL SIGNALS FROM

PANEL TO BUILDING AS REQUIRED BY OWNER.

6. EXISTING 1200 AMP, 120/208 VOLT, 3-PHASE EMERGENCY POWER PANEL EDP.

INSTALL A 175 AMP, 3-POLE CIRCUIT BREAKER IN EXISTING SPACE IN PANEL TO

FEED NEW PUMP STATION CONTROL PANEL.

7. NEW FEEDER FROM PANEL EDP TO NEW PUMP STATION, 3-#1/0, 1-#6 GROUND

IN 2" CONDUIT. INTERIOR CONDUIT TO BE TYPE EMT, EXTERIOR EXPOSED

CONDUIT TO BE SCHEDULE 80 PVC OR RIGID GALVANIZED STEEL AS DIRECTED BY

OWNER. UNDERGROUND CONDUIT TO BE SCHEDULE 40 PVC.

8. ROUTE FEEDER ACROSS ELECTRICAL ROOM NEAR CEILING. COORDINATE EXACT

ROUTING WITH EXISTING SITE CONDITIONS.

9. PENETRATE EXTERIOR WALL WITH CONDUIT AND COMPLETELY SEAL AROUND

CONDUIT PENETRATION. TURN CONDUIT DOWN WALL TO UNDERGROUND.

10. UNDERGROUND FEEDER TO NEW CONTROL PANEL, TURN UP INTO BOTTOM OF

PANEL. CONDUIT TO BE BURIED MINIMUM 24" DEEP TO TOP OF CONDUIT. USE

4" SAND BELOW AND ALL AROUND CONDUIT. BACKFILL REMAINDER OF TRENCH

WITH CLEAN EARTH BACKFILL.

KEY PLAN

4"

PD

6"SAN6"SAN

EXIST

XFRMR

(E )4"

GW

4"PD

DUPLEX

PUMP

STATIONEXIST

GREASE

TRAP

(E)6"SAN

(E)CO

(E)CO

(E)4"SAN

(E)4"SAN

(E )4

"S

AN

(E)4"SAN

(E)3"G (E)3"G (E)3"G

(E)6"SAN

(E )6

"S

AN

(E)ELEC

(E)ELEC

(E)ELEC

(E)ELEC

(E)6"SAN

CO

CO

CO (E)CO

VALVE

VAULT

UG

X

AutoCAD SHX Text

VAUGHN

AutoCAD SHX Text

ROBERTS

AutoCAD SHX Text

HILL

AutoCAD SHX Text 13329

(E)4"PD

MECH

CORRIDOR

DAYROOM

DAYROOM

105F

CELL

105E

CELL

105G

CELL

105H

CELL

106F

CELL

106E

CELL

106G

CELL

106H

CELL

VEST

STORAGE

COMMUNICATIONS

JANITOR

INTERVIEW

OFFICE

R.R.

VEST

OUTDOOR

STORAGE

406A

GYM

STORAGE

FREEZER

COOLER

VOCATIONAL

VOCATIONAL

TIME

OUT

CONFERENCE

PSY.

OFFICE

WORK

ROOM

CORRIDOR

CORRIDOR

C O

R R

ID

O

R

R.R.

R.R.

STAFF

R.R.

STAFF

R.R.

CLASSROOM

CLASSROOM

CLASSROOM

LIBRARY/

COMPUTER

CLASSROOM/

REMEDIAL

JANITOR

406B

OFFICE

OFFICE

OFFICE

OFFICE

M104

STORAGE

BAY

M103

SHOP

BAY

M100A

MAINT.

BAY

M102 R.R.

OFFICE

(E)CO

(E)CO

(E)CO

(E)CO(E)CO

(E)CO

(E)CO

(E)CO(E)6"SAN

(E)4"SAN

(E)4"SAN

WH(E)

(E )6

"S

AN

(E )6

"S

AN

(E)6"SAN

(E )4

"S

AN

(E )3

/4 "G

(E )1

"C W

(E)3/4"G

(E)3"CW

(E)CO

(E)CO

(E )4

"P D

(E)CO

(E)6"SAN

(E)ELEC

(E)ELEC

(E)ELEC

(E)4"SAN

(E)3"G (E)3"G (E)3"G

(E)4"GW

(E )4"

GW

(E )6

"S

AN

(E )6

"S

AN

(E )6

"S

AN

(E )6

"S

AN

(E )6

"S

AN

6"

ST

M (E

6"

ST

M

(E

(E)3"CW (E)3"CW

(E)ELEC

(E)6"SAN

(E )4"

SAN

VRH

TRG

ACCOUNT NO.

523-CAWT-AC12-00

TRG PSCArchitects - Engineers - Landscape Architects The Roberts Group

239 Southland Drive - Lexington, KY 40503 859-276-2006 - 859-276-2901 Facsimile

DJJ - ADAIR YDC SEWAGE GRINDER PIT RELOCATION

DEPARTMENT FOR JUVENILE JUSTICE

COLUMBIA, KY

DRAWING NO.

DECA REVIEWED

PHASE

FOR INTENT ONLY

DRAWING INFORMATION

DRAWING DATE

DRAWN BY

CHECKED BY

A&E FILE NO.

DECA LOG #

"D"

COMMONWEALTH OF KENTUCKY

FINANCE AND ADMINISTRATION CABINET

DEPARTMENT FOR FACILITIES MANAGEMENT

DIVISION OF ENGINEERING

FRANKFORT, KENTUCKY

02/16/2024

ST

ATE OF KENTUCKY

P R

O

FESS I ONA L ENG

I N E

E R

L

I C E N S E

D

DATEDESCRIPTION OF REVISIONS

REVISION HISTORY OF THIS DRAWING

DATEDESCRIPTION OF REVISIONS

XXX

P:

\K

YS

ta te \2

-C O

LU

M

BI

A-

KY

-D

JJ

P

LB

G

P R

O

JE

C T\

-P

LU

M

\2

P1 .0

PA

R

TI

AL

P

LU

M

BI

N

G P

LA

N

EX

IS

TI

N G

.d w g

W ed ne sd ay , F eb ru ar y

, 2

8:

A M

Th e

R ob er ts

G ro up

G re g El am

TRG #23035

P1.0

EXPIRATION: 06/30/2025

RTA 02/16/2024

PARTIAL PLUMBING PLAN -EXISTING

1 PARTIAL PLUMBING PLAN - EXISTING

1/8" = 1'-0"

GENERAL NOTES:

A. EXISTING UTILITY LOCATIONS INDICATED ON THESE DRAWINGS ARE

BASED ON AS-BUILT DRAWINGS PROVIDED AFTER COMPLETION OF THE

ORIGINAL PROJECT. IN ADDITION TO CONTACTING ALL SUPPORTING

UTILITY COMPANIES AND SERVICES TO PROVIDE A MORE PRECISE UP TO

DATE LOCATION OF EACH SERVICE. LOCATIONS INDICATED ARE SHOWN

TO THE BEST OUR ABILITY. HOWEVER, THE CONTRACTOR SHALL STILL

CONFIRM EXACT UTILITY LOCATIONS AND TAKE PRECAUTIONS DURING

EXCAVATION DURING CONSTRUCTION.

B. CONTRACTOR TO PROVIDE TEMPORARY RESTROOM FACILITIES WITH

REGULARLY SCHEDULED PUMPING AND SERVICE CYCLES FOR THE FULL

DURATION OF CONSTRUCTION.

C. THE EXISTING PUMP STATION IS TO REMAIN INTACT AND OPERATIONAL

UNTIL THE NEW PUMP STATION HAS BEEN STARTED, TESTED, AND

RECONNECTED TO EXISTING BUILDING MAIN SANITARY.

SHEET KEYED NOTES:

1. EXISTING REDUCED PRESSURE BACKFLOW PREVENTER.

2. EXISTING GREASE TRAP.

3. EXISTING WATER HEATERS.

4. EXISTING 4" VENT UP TO EXISTING 4" VTR.

5. EXISTING 4" SANITARY DISCHARGE ROUTED IN CEILING SPACE ABOVE.

KEY PLAN

EXISTING LEGEND

CW(EX) EXISTING COLD WATER

G(EX) EXISTING GAS SUPPLY

SAN(EX) EXISTING SANITARY SEWER

SAN-PD(EX) EXISTING SANITARY PUMP DISCHARGE

GW(EX) EXISTING GREASE WASTE

ELEC(EX) EXISTING ELECTRICAL

STM(EX) EXISTING STORM SEWER

CO(EX) EXISTING SEWER CLEANOUT

(E)4"PD

MECH

CORRIDOR

DAYROOM

DAYROOM

105F

CELL

105E

CELL

105G

CELL

105H

CELL

106F

CELL

106E

CELL

106G

CELL

106H

CELL

VEST

STORAGE

COMMUNICATIONS

JANITOR

INTERVIEW

OFFICE

R.R.

VEST

OUTDOOR

STORAGE

406A

GYM

STORAGE

FREEZER

COOLER

VOCATIONAL

VOCATIONAL

TIME

OUT

CONFERENCE

PSY.

OFFICE

WORK

ROOM

CORRIDOR

CORRIDOR

C O

R R

ID

O

R

R.R.

R.R.

STAFF

R.R.

STAFF

R.R.

CLASSROOM

CLASSROOM

CLASSROOM

LIBRARY/

COMPUTER

CLASSROOM/

REMEDIAL

JANITOR

406B

OFFICE

OFFICE

OFFICE

OFFICE

M104

STORAGE

BAY

M103

SHOP

BAY

M100A

MAINT.

BAY

M102 R.R.

OFFICE

(E)CO

(E)CO

(E)CO

(E)CO(E)CO

(E)CO

(E)CO

(E)CO(E)6"SAN

(E)4"SAN

(E)4"SAN

WH(E)

(E )6

"S

AN

(E )6

"S

AN

(E)6"SAN

(E )4

"S

AN

(E )3

/4 "G

(E )1

"C W

(E)3/4"G

(E)3"CW

(E)CO

(E)CO

(E )4

"P D

(E)CO

(E)6"SAN

(E)ELEC

(E)ELEC

(E)ELEC

(E)4"SAN

(E)3"G (E)3"G (E)3"G

(E)4"GW

(E )4"

GW

(E )6

"S

AN

(E )6

"S

AN

(E )6

"S

AN

(E )6

"S

AN

(E )6

"S

AN

6"

ST

M (E

6"

ST

M

(E

(E)3"CW (E)3"CW

(E)ELEC

(E)6"SAN

(E )4"

SAN

VRH

TRG

ACCOUNT NO.

523-CAWT-AC12-00

TRG PSCArchitects - Engineers - Landscape Architects The Roberts Group

239 Southland Drive - Lexington, KY 40503 859-276-2006 - 859-276-2901 Facsimile

DJJ - ADAIR YDC SEWAGE GRINDER PIT RELOCATION

DEPARTMENT FOR JUVENILE JUSTICE

COLUMBIA, KY

DRAWING NO.

DECA REVIEWED

PHASE

FOR INTENT ONLY

DRAWING INFORMATION

DRAWING DATE

DRAWN BY

CHECKED BY

A&E FILE NO.

DECA LOG #

"D"

COMMONWEALTH OF KENTUCKY

FINANCE AND ADMINISTRATION CABINET

DEPARTMENT FOR FACILITIES MANAGEMENT

DIVISION OF ENGINEERING

FRANKFORT, KENTUCKY

02/16/2024

ST

ATE OF KENTUCKY

P R

O

FESS I ONA L ENG

I N E

E R

L

I C E N S E

D

DATEDESCRIPTION OF REVISIONS

REVISION HISTORY OF THIS DRAWING

DATEDESCRIPTION OF REVISIONS

XXX

P:

\K

YS

ta te \2

-C O

LU

M

BI

A-

KY

-D

JJ

P

LB

G

P R

O

JE

C T\

-P

LU

M

\2

P1 .1

PA

R

TI

AL

P

LU

M

BI

N

G P

LA

N

D

EM

O

LI

TI

O N

.d w g

W ed ne sd ay , F eb ru ar y

, 2

8:

A M

Th e

R ob er ts

G ro up

G re g El am

TRG #23035

P1.1

EXPIRATION: 06/30/2025

RTA 02/16/2024

PARTIAL PLUMBING PLAN - DEMOLITION

1 PARTIAL PLUMBING PLAN - DEMOLITION

1/8" = 1'-0"

GENERAL NOTES:

A. EXISTING UTILITY LOCATIONS INDICATED ON THESE DRAWINGS ARE

BASED ON AS-BUILT DRAWINGS PROVIDED AFTER COMPLETION OF THE

ORIGINAL PROJECT. IN ADDITION TO CONTACTING ALL SUPPORTING

UTILITY COMPANIES AND SERVICES TO PROVIDE A MORE PRECISE UP TO

DATE LOCATION OF EACH SERVICE. LOCATIONS INDICATED ARE SHOWN

TO THE BEST OUR ABILITY. HOWEVER, THE CONTRACTOR SHALL STILL

CONFIRM EXACT UTILITY LOCATIONS AND TAKE EVERY PRECAUTION TO

AVOID DAMAGE TO EXISTING UTILITIES DURING CONSTRUCTION.

SHEET KEYED NOTES:

1. EXISTING REDUCED PRESSURE BACKFLOW PREVENTER.

2. EXISTING GREASE TRAP TO REMAIN.

3. EXISTING DUPLEX PUMP STATION. REMOVE COVER, PUMPS, VALVES,

FITTINGS, PIPING, CONTROL PANEL, CONDUIT, WIRING ETC. ASSOCIATED

WITH PUMP STATION. PIT SHALL BE BACKFILLED WITH ROCK TO A POINT

TO ALLOW FOR A MINIMUM 6" OF CONCRETE TO REPAIR SLAB.

COORDINATE REMOVAL OF ALL ITEMS WITH OWNERS REPRESENTATIVE.

TURN OVER ALL ITEMS OWNER ELECTS TO KEEP OR TO BE REUSED.

4. EXISTING 4" VENT UP TO EXISTING 4" VTR.

5. EXISTING 4" SANITARY PUMP DISCHARGE ROUTED ELEVATED THROUGH

SPACE.

6. EXISTING UNDERGROUND PUMP DISCHARGE ROUTED UP EXPOSED ON

WALL TO REMAIN.

7. EXISTING PUMP DISCHARGE DRAIN DOWN VALVE AND TERMINATION AT

EXTERIOR WALL TO REMAIN.

8. EXISTING TRANSFORMER TO REMAIN.

9. EXISTING EMERGENCY GENERATOR TO REMAIN.

10. EXISTING CHILLER TO REMAIN.

11. REMOVE EXISTING SLAB AND PIT AS REQUIRED TO EXPOSE BUILDING

EXISTING MAIN GRAVITY DISCHARGE. EXISTING GRAVITY DISCHARGE WILL

BE REROUTED TO NEW EXTERIOR DUPLEX PUMP STATION, SEE NEW

WORK DRAWINGS FOR MORE INFORMATION.

12. APPROXIMATE OUTLINE OF PAVEMENT REMOVAL AND EXCAVATION TO

ALLOW FOR NEW SANITARY PIPING AND DUPLEX PUMP STATION

INSTALLATION. SEE NEW WORK DRAWINGS FOR MORE INFORMATION.

13. EXISTING DUPLEX PUMP STATION CONTROL PANEL TO BE REMOVED.

14. EXISTING GAS REGULATOR AND SHUTOFF VALVE TO REMAIN.

15. EXISTING GAS MAIN BUILDING ENTRY TO REMAIN.

KEY PLAN

LEGEND

(E)CW EXISTING COLD WATER

(E)G EXISTING GAS SUPPLY

(E)SAN EXISTING SANITARY SEWER

(E)SAN-PD EXISTING SANITARY PUMP DISCHARGE

(E)GW EXISTING GREASE WASTE

(E)ELEC EXISTING ELECTRICAL

(E)STM EXISTING STORM SEWER

(E)CO EXISTING SEWER CLEANOUT

PIPE TURNING UP

PIPE TURNING DOWN

BFF BELOW FINISH FLOOR

AFF ABOVE FINISH FLOOR

VTR VENT THRU ROOF

ABV ABOVE

BLW BELOW

GAS COCK

GAS REGULATOR

CO CLEANOUT

4"PD

(E )3

/4 "G

(E )1

"C W

(E)3/4"G

(E)3"CW

(E)ELEC

(E)ELEC

(E)ELEC

(E)3"G (E)3"G (E)3"G

(E)3"CW (E)3"CW

(E)ELEC

VRH

TRG

ACCOUNT NO.

523-CAWT-AC12-00

TRG PSCArchitects - Engineers - Landscape Architects The Roberts Group

239 Southland Drive - Lexington, KY 40503 859-276-2006 - 859-276-2901 Facsimile

DJJ - ADAIR YDC SEWAGE GRINDER PIT RELOCATION

DEPARTMENT FOR JUVENILE JUSTICE

COLUMBIA, KY

DRAWING NO.

DECA REVIEWED

PHASE

FOR INTENT ONLY

DRAWING INFORMATION

DRAWING DATE

DRAWN BY

CHECKED BY

A&E FILE NO.

DECA LOG #

"D"

COMMONWEALTH OF KENTUCKY

FINANCE AND ADMINISTRATION CABINET

DEPARTMENT FOR FACILITIES MANAGEMENT

DIVISION OF ENGINEERING

FRANKFORT, KENTUCKY

02/16/2024

ST

ATE OF KENTUCKY

P R

O

FESS I ONA L ENG

I N E

E R

L

I C E N S E

D

DATEDESCRIPTION OF REVISIONS

REVISION HISTORY OF THIS DRAWING

DATEDESCRIPTION OF REVISIONS

XXX

P:

\K

YS

ta te \2

-C O

LU

M

BI

A-

KY

-D

JJ

P

LB

G

P R

O

JE

C T\

-P

LU

M

\2

P2 .0

PA

R

TI

AL

P

LU

M

BI

N

G P

LA

N

N

EW

W

O R

K.

dw g

W ed ne sd ay , F eb ru ar y

, 2

8:

A M

Th e

R ob er ts

G ro up

G re g El am

TRG #23035

P2.0

EXPIRATION: 06/30/2025

RTA 02/16/2024

PARTIAL PLUMBING PLAN - NEW WORK

1 PARTIAL PLUMBING PLAN - NEW WORK

1/8" = 1'-0"

GENERAL NOTES:

A. EXISTING UTILITY LOCATIONS INDICATED ON THESE DRAWINGS ARE

BASED ON AS-BUILT DRAWINGS PROVIDED AFTER COMPLETION OF THE

ORIGINAL PROJECT. IN ADDITION TO CONTACTING ALL SUPPORTING

UTILITY COMPANIES AND SERVICES TO PROVIDE A MORE PRECISE UP TO

DATE LOCATION OF EACH SERVICE. LOCATIONS INDICATED ARE SHOWN

TO THE BEST OUR ABILITY. HOWEVER, THE CONTRACTOR SHALL STILL

CONFIRM EXACT UTILITY LOCATIONS AND TAKE PROPER PRECAUTIONS

DURING EXCAVATION AND CONSTRUCTION.

SHEET KEYED NOTES:

1. CONNECT NEW GRAVITY BUILDING MAIN SANITARY TO EXISTING IN THIS

APPROXIMATE LOCATION. CONTRACTOR TO FIELD VERIFY EXACT

LOCATION. NEW PUMP STATION AND PIPING ARE TO BE TESTED AND

OPERATIONAL PRIOR TO THIS MAIN SANITARY LINE BEING SEVERED AND

THE NEW CONNECTION MADE.

2. CONNECT NEW SANITARY TO EXISTING.

3. CONNECT NEW SANITARY TO EXISTING GREASE TRAP.

4. NEW DUPLEX GRINDER PUMP STATION WITH TRAFFIC RATED SPLIT

COVER.

5. NEW PUMP STATION CONTROL PANEL. COORDINATE LOCATION WITH

EXISTING MOTOR OPERATED GATE.

6. NEW UNDERGROUND GRAVITY SANITARY PIPING ROUTED TO NEW DUPLEX

PUMP STATION CONNECTION AS INDICATED.

7. NEW UNDERGROUND PUMP DISCHARGE PIPING ROUTED TO CONNECTION

AS INDICATED.

8. CONNECT NEW PUMP DISCHARGE TO VALVED EXISTING DRAIN DOWN FOR

EXISTING SYSTEM. CAP EXISTING DISCHARGE INSIDE BUILDING AT FLOOR

LEVEL BELOW SHUTOFF VALVE.

9. EXISTING PUMP STATION POWERED FROM PANEL "EB" IN THIS

APPROXIMATE LOCATION.

10. NEW PUMP DISCHARGE TO BE ROUTED UNDERGROUND AROUND

BUILDING AND CONNECTING BACK INTO EXISTING NEAR GAZEBO

APPROXIMATELY 750LF. SEE SHEET P4.0 FOR MORE INFORMATION.

11. CONTRACTOR SHALL FIELD VERIFY EXACT MAIN BUILDING POWER

LOCATION. EVERY PRECAUTION SHALL BE TAKEN NOT LIMITED TO HAND

EXCAVATION TO AVOID DISRUPTION TO POWER.

12. APPROXIMATE LIMITS OF PAVEMENT AND SLAB REPLACEMENT.

CONTRACTOR TO REPLACE ANY PAVEMENT AND/OR SLAB REQUIRED TO

BE REMOVED FOR THIS PROJECT. ADDITIONAL PAVEMENT REMOVAL AND

REPLACEMENT WILL BE REQUIRED IF OWNER ELECTS TO PROCEED WITH

THE ALTERNATE ROUTING AROUND BUILDING. SEE SHEET P4.0 FOR

PROPOSED ROUTING.

13. SEE DETAIL #2 THIS SHEET FOR MORE INFORMATION.

KEY PLAN

4"

PD

6"SAN6"SAN

4"SAN

EXIST

XFRMR

(E )4"

GW

4"PD

DUPLEX

PUMP

STATION NEW PD ROUTING

EXIST

GREASE

TRAP

(E)6"SAN

(E)CO

(E)CO

(E)4"SAN

(E)4"SAN

(E )4

"S

AN

(E)4"SAN

(E)3"G (E)3"G (E)3"G

(E)6"SAN

(E )6

"S

AN

(E)ELEC

(E)ELEC

(E)ELEC

(E)ELEC

(E)6"SAN

CO

CO

CO (E)CO

VALVE

VAULT

2 ENLARGEMENT

1/4" = 1'-0"

6"SAN(E)6"SAN

ABANDON EXISTING PUMP

STATION CONNECTION.

CONNECT EXISTING MAIN

TO NEW ROUTED TO NEW

PUMP STATION.

CONNECT EXISTING SANITARY

MAIN TO NEW SANITARY MAIN

ROUTED TO NEW PUMP STATION.

EXISTING

PUMP

STATION TO

BE GRAVEL

FILLED

VRH

TRG

ACCOUNT NO.

523-CAWT-AC12-00

TRG PSCArchitects - Engineers - Landscape Architects The Roberts Group

239 Southland Drive - Lexington, KY 40503 859-276-2006 - 859-276-2901 Facsimile

DJJ - ADAIR YDC SEWAGE GRINDER PIT RELOCATION

DEPARTMENT FOR JUVENILE JUSTICE

COLUMBIA, KY

DRAWING NO.

DECA REVIEWED

PHASE

FOR INTENT ONLY

DRAWING INFORMATION

DRAWING DATE

DRAWN BY

CHECKED BY

A&E FILE NO.

DECA LOG #

"D"

COMMONWEALTH OF KENTUCKY

FINANCE AND ADMINISTRATION CABINET

DEPARTMENT FOR FACILITIES MANAGEMENT

DIVISION OF ENGINEERING

FRANKFORT, KENTUCKY

02/16/2024

ST

ATE OF KENTUCKY

P R

O

FESS I ONA L ENG

I N E

E R

L

I C E N S E

D

DATEDESCRIPTION OF REVISIONS

REVISION HISTORY OF THIS DRAWING

DATEDESCRIPTION OF REVISIONS

XXX

P:

\K

YS

ta te \2

-C O

LU

M

BI

A-

KY

-D

JJ

P

LB

G

P R

O

JE

C T\

-P

LU

M

\2

P3 .0

PL

U M

BI

N

G G

EN

ER

AL

N

O

TE

S

AN

D D

ET

AI

LS

.D

W G

W ed ne sd ay

, F eb ru ar y

, 2

8:

A

M Th e R ob er ts G ro up

G re g

El am

TRG #23035

P3.0

EXPIRATION: 06/30/2025

RTA 02/16/2024

PLUMBING - GENERAL NOTES AND SPECS FOR

DUPLEX GRINDER PUMP

1. DO NOT SCALE THIS DRAWING. REFER TO ARCHITECTURAL FLOOR PLANS FOR BUILDING DIMENSIONS.

2. THE SUBMISSION OF A PROPOSAL WILL BE CONSTRUED AS EVIDENCE THAT THE CONTRACTOR HAS FAMILIARIZED

HIMSELF WITH THE PLANS AND BUILDING SITE. CLAIMS MADE SUBSEQUENT TO THE PROPOSAL FOR MATERIALS AND LABOR BECAUSE OF DIFFICULTIES ENCOUNTERED WILL NOT BE RECOGNIZED, IF THEY COULD HAVE BEEN FORESEEN

HAD PROPER EXAMINATION BEEN MADE.

3. VERIFY SERVICE POINTS AND METERING LOCATIONS FOR PROJECT WITH LOCAL UTILITIES (DOMESTIC WATER, SANITARY SEWER, GAS, ETC.)

4. THE CONTRACTOR SHALL COOPERATE FULLY AMONG THE TRADES.

5. WASTE AND VENT PIPING SHALL BE SCHEDULE 40 OR 80, TYPE 1, GRADE 1, POLYVINYL CHLORIDE COMPOUNDS AS

DEFINED AND DESCRIBED IN TENTATIVE SPECIFICATIONS FOR RIGID PVC (ASTM DESIGNATION: D 2665, D 2949, F891 OR SCHEDULE 40 OR 30 ACRYLONITRILE-BUTADIENE-STYRENE COMPOUND AS DEFINED AND DESCRIBED IN STANDARD SPECIFICATIONS FOR ABS (ASTM DESIGNATION: D2661 OR F 628) IN LIEU OF CAST IRON WASTE AND VENT PIPING IF PERMITTED BY CODE. INSTALL PVC OR ABS PIPING PER CODE. PLUMBING CONTRACTOR SHALL INSTALL 4" SOIL, WASTE AND GREASE WASTE PIPING WITH A MINIMUM SLOPE OF 1/8" PER FOOT OR AS REQUIRED BY CODE.

6. ALL INSTALLED SYSTEMS, DEVICES AND RELATED ITEMS SHALL BE TESTED IN PLACE ON SITE PER LOCAL CODE REQUIREMENTS. REPLACE ANY AND ALL CONTRACTOR SUPPLIED DEFECTIVE DEVICES, ITEMS OR SYSTEMS AT

CONTRACTOR'S OWN EXPENSE BEFORE COMPLETION OF PROJECT.

7. WHERE JOB CONDITIONS REQUIRE CHANGES FROM THE CONTRACT DOCUMENTS THAT DO NOT CHANGE THE SCOPE OR NATURE OF THE WORK REQUIRED, THE CONTRACTOR SHALL MAKE SUCH CHANGES WITHOUT ADDITIONAL COST TO THE OWNER. NO OTHER CHANGES MAY BE MADE WITHOUT WRITTEN PERMISSION OF THE OWNER.

8. ALL EQUIPMENT, FIXTURES AND MATERIALS SHALL BE NEW AND UNUSED, AND INSTALLED IN STRICT CONFORMANCE TO MANUFACTURER'S RECOMMENDATIONS (U.O.N.). THEY MUST COMPLY WITH ALL FEDERAL A.D.A. REGULATIONS.

9. CONTRACTOR SHALL GUARANTEE ALL WORK FOR WHICH MATERIALS ARE FURNISHED, FABRICATED OR FIELD ERECTED, ALL FACTORY ASSEMBLED EQUIPMENT FOR WHICH NO SPECIFIC MANUFACTURER'S GUARANTEE IS FURNISHED AND ALL WORK IN CONNECTION WITH THE INSTALLATION OF MANUFACTURER'S GUARANTEED EQUIPMENT. THIS CONTRACTOR'S GUARANTEE SHALL EXIST FOR A PERIOD OF ONE (1) YEAR FROM THE DATE OF FINAL OWNER ACCEPTANCE OF THE WORK AND SHALL APPLY TO ALL DEFECTS IN MATERIALS AND/OR WORKMANSHIP

OF ANY KIND.

10. BIDDERS SHALL BE LICENSED CONTRACTORS IN ACCORDANCE WITH LOCAL AND AND STATE LAWS.

11. ALL PERMITS AND FEES REQUIRED FOR THE WORK SHALL BE SECURED AND PAID FOR BY THE CONTRACTOR AND

INCLUDED IN THE BID PRICE.

12. ALL PIPING SYSTEMS SHALL BE INSTALLED IN ACCORDANCE WITH THE LATEST EDITION OF STATE AND/OR LOCAL

CODES. COOPERATE AS REQUIRED WITH ALL AUTHORITIES HAVING JURISDICTION TO INSURE THAT PROPER MATERIALS AND WORKMANSHIP ARE USED. REQUIREMENTS OF STATE AND LOCAL CODES AND AUTHORITIES TAKE

PRECEDENCE OVER ANY INFORMATION WHICH IS INDICATED OR IMPLIED ON THESE DRAWINGS.

13. THE CONTRACTOR SHALL PERFORM AN ONSITE REVIEW OF DEMOLITION AREAS TO ACKNOWLEDGE ANY POSSIBLE

DIFFICULTIES OR CONCERNS.

14. ALL WORK SHALL COMPLY WITH THE LATEST ADOPTED VERSION OF THE BUILDING CODE INCLUDING ALL THE SUPPLEMENTAL SECTIONS, AS WELL AS ANY APPLICABLE STATE, COUNTY OR LOCAL REGULATIONS.

15. VERIFY EXISTING CONDITIONS PRIOR TO START OF DEMOLITION AND CONSTRUCTION AND NOTIFY OWNER CONSTRUCTION MANAGER OF ANY DISCREPANCIES. PERFORM DEMOLITION AS REQUIRED FOR TIE-IN OF NEW WORK.

16. CONTRACTOR RESPONSIBLE FOR CONTACTING ALL UTILITY COMPANIES PRIOR TO DEMOLITION AND EXCAVATION TO

BE PERFORMED OUTSIDE.

17. LOCATIONS OF UTILITIES SHOWN ON PLANS ARE APPROXIMATE, VERIFY WITH LOCAL UTILITY PRIOR TO BIDDING

18. CONTRACTOR SHALL VERIFY EXACT LOCATION, SIZE AND ELEVATION OF ALL EXISTING SERVICES PRIOR TO

INSTALLING ANY NEW PIPE.

19. ALL HORIZONTAL SANITARY PIPING IS RUN BELOW GROUND UNLESS OTHERWISE NOTED.

1 GENERAL NOTES

NO SCALE

2 DUPLEX PUMP PACKAGE SPECIFICATIONS

NO SCALE

DEPARTMENT OF JUVENILE JUSTICE YOUTH DEVELOPMENT CENTER ADAIR COUNTY - COLUMBIA, KENTUCKY

3 DUPLEX PUMP DETAIL

NO SCALE

TOP RAIL SUPPORT

(BOLTS TO COVER FRAME)

GATE

VALVE

FLASHING ALARM LIGHT

FLOAT MTG.

BRACKET

PIPE

ELBOW

WEATHERPROOF CONTROL BOX

CHECK

VALVE

GATE

VALVE

POWER SUPPLY CONDUIT

L

CORD SEAL CONNECTORS FOR

POWER AND CONTROL CORDS

(NOT SHOWN)

" INLET

PIPE

PUMP #2 ON

BOTTOM OF BASIN MUST HAVE SMOOTH

TROWELED SURFACE FOR MTG. SUPPORT CASTING

PIPE

TEE

HIGH WATER ALARM

BELOW

FROST

LEVEL

CL

CL

C PIPE

X

HATCH OPNG.

" DISCH. PIPING - CAN BE

GALV. STEEL OR DUCTILE IRON

2" SS PIPE GUIDE RAILS

MUST BE PLUMB

LIFT OUT ASSEMBLY - NON-SPARKING - UL LISTED

LC PIPE

PUMP #1 ON

PUMPS OFF

LIFTING CHAIN

CHECK

VALVE

6' DIA.

30" OPNG.

PUMP SERIES:

DUPLEX 4" SUBMERSIBLE CHOPPER

INTERMEDIATE RAIL SUPPORT

TYPICAL INSTALLATION

ES-2229B Landia

MODEL

SUBMERSIBLE CHOPPER PUMP

(ONE REQUIRED FOR EACH 20 FEET OF

BASIN DEPTH IN EXCESS OF 20 FEET.)

4" EMERGENCY PUMP CONNECTIONS

4" GATE VALVE & MALE ALUMINUM CAM LOCK

4 WAY CROSS

90 DEG.

REDUCING

ELBOW

LANDIA DG-I-65

4"EMERGENCY

PUMP CONNECTION

48" OPNG.

24"

13 13

15'

11'

X

DG-I-65

1/4" S.S.

HINGED ACCESS DOOR

ALUM. 300 PSF Rating Angle Frame

HINGED ACCESS DOOR

ALUM. 300 PSF Rating Angle Frame

3 Gauge taps for Pressure Gauge

NEMA 4X - Alum.

Alarm Horn

DUAL PEDESTAL SYSTEM

6' DIA.

PART 1 GENERAL

1.01 SCOPE

THE WORK COVERED BY THE SECTION CONSISTS OF FURNISHING ALL LABOR, EQUIPMENT AND MATERIALS REQUIRED TO INSTALL, TEST AND PLACE INTO SATISFACTORY OPERATION THE SEWAGE PUMPING STATION INCLUDING PUMPS, MOTORS, CONTROLS AND APPURTENANCES AS SHOWN ON THE DRAWINGS AND DETAILED HEREIN.

1.02 DEFINITIONS

WHEN THE TERM "PUMPING UNIT" IS USED, IT SHALL BE DEEMED TO MEAN A PUMP OR PUMPS, COMPLETE WITH, BUT NOT LIMITED TO, DRIVE MOTOR, ACCESSORIES, APPURTENANCES AND ALL ASSOCIATED EQUIPMENT.

1.03 DESIGN REQUIREMENTS

PUMPS AND ACCESSORIES SHALL BE AS OUTLINED IN THESE SPECIFICATIONS.

1.04 SUBMITTALS

A. SUBMIT SHOP DRAWINGS AND ENGINEERING DATA IN ACCORDANCE WITH THE REQUIREMENTS OF SECTION 01340 OF

THESE SPECIFICATIONS.

B. OPERATION AND MAINTENANCE MANUALS SHALL BE FURNISHED IN ACCORDANCE WITH THE REQUIREMENTS OF

SECTION 01730 OF THESE SPECIFICATIONS.

1.05 STORAGE AND PROTECTION

A. PUMP ACCESSORIES SHALL BE STORED AND PROTECTED IN ACCORDANCE WITH THE MANUFACTURER'S

RECOMMENDATIONS. PUMP SHALL NOT BE STORED OUTSIDE OR EXPOSED TO THE WEATHER.

B. PUMP SHALL BE COMPLETELY DRAINED PRIOR TO SHIPMENT. SUCTION AND DISCHARGE PORTS SHALL BE PROVIDED WITH PLASTIC PLUGS. THE PUMP SHALL BE SECURED TO A WOODEN SKID AND CRATED TO FACILITATE HANDLING AND

STORAGE.

1.06 QUALITY ASSURANCE

A. THE MANUFACTURER SHALL PROVIDE A WRITTEN CERTIFICATION TO THE ENGINEER, WITH THE SHOP DRAWINGS, THAT ALL EQUIPMENT FURNISHED COMPLIES WITH ALL APPLICABLE REQUIREMENTS OF THESE SPECIFICATIONS.

B. ALL PUMPING UNITS SHALL BE AN APPROVED DESIGN, MAKE AND PRODUCTS OF MANUFACTURERS

WHO HAVE BUILT EQUIPMENT OF SIMILAR TYPE, SIZE, AND CAPACITY.

C. THE CONTRACTOR SHALL SUBMIT, UPON REQUEST, ANY ADDITIONAL INFORMATION THAT THE ENGINEER AND/OR OWNER MAY DEEM NECESSARY TO DETERMINE THE ABILITY OF THE PROPOSED MANUFACTURER TO PRODUCE THE

SPECIFIED EQUIPMENT.

D. PUMPING UNITS SHALL BE PRODUCTS OF MANUFACTURERS WHO CAN PRODUCE EVIDENCE OF THEIR ABILITY TO PROMPTLY FURNISH ANY AND ALL INTERCHANGEABLE REPLACEMENT PARTS AS MAY BE NEEDED AT ANY TIME WITHIN

THE EXPECTED LIFE OF THE PUMPS.

E. APPROVAL OF MANUFACTURERS OR SUPPLIERS WILL NOT BE GIVEN UNTIL ALL INFORMATION REQUIRED BY THE SPECIFICATIONS OR REQUESTED BY THE ENGINEER HAS BEEN SUBMITTED AND FOUND ACCEPTABLE.

F. THE CONTRACTOR SHALL PROVIDE AT NO COST TO THE OWNER, THE SERVICES OF AN ACCREDITED REPRESENTATIVE OF THE PUMP MANUFACTURER WHO SHALL SUPERVISE THE INSTALLATION AND TESTING OF EACH PUMPING UNIT AND ALSO GIVE OPERATING AND MAINTENANCE INSTRUCTION TO THE OWNER'S PERSONNEL. PUMPING EQUIPMENT SHALL BE TESTED FOR PERFORMANCE ACCORDING TO CURVES AND OTHER APPROVED DATA. FAILURE OF THE EQUIPMENT TO PERFORM AS CURVES INDICATE AND WITH OTHER APPROVED DATA SHALL BE SUFFICIENT CAUSE FOR REJECTION.

AS ONE CONDITION NECESSARY TO ACCEPTANCE OF ANY PUMPING UNIT, THE CONTRACTOR SHALL SUBMIT A CERTIFICATE FROM THE MANUFACTURER, STATING THAT THE INSTALLATION OF THE PUMPING UNIT IS SATISFACTORY, THAT THE UNIT IS READY FOR OPERATION, AND THAT THE OWNER'S OPERATING PERSONNEL HAVE BEEN SUITABLY

INSTRUCTED IN THE OPERATION AND MAINTENANCE OF THE UNIT.

1.07 PUMP STATION WARRANTY

THE CONTRACTOR GUARANTEES AND WARRANTS THAT DURING THE FIRST YEAR OF OPERATION, (DATE THE PUMP STATION IS TESTED, PLACED IN SERVICE AND A WRITTEN ACCEPTANCE LETTER ISSUED BY THE OWNER) THE PUMP STATIONS WILL OPERATE SATISFACTORILY AND CONTINUOUSLY ACCORDING TO THE PUMP REQUIREMENTS SPECIFIED HEREIN, AND THAT AFTER DUE NOTICE HAS BEEN GIVEN BY THE OWNER, HE OR THE PUMP MANUFACTURER WILL PROCEED, WITHIN A REASONABLE TIME TO ADJUST, REGULATE, REPAIR AND RENEW AT HIS EXPENSE SUCH PART OR PARTS, EQUIPMENT, AUXILIARIES APPURTENANCES OR PERFORM SUCH WORK AS IS

NECESSARY TO MAINTAIN THE GUARANTEED CAPACITIES, EFFICIENCIES AND PERFORMANCES.

PART 2 PRODUCTS

2.01 ACCEPTABLE MANUFACTURERS

ALL PUMPS SHALL BE MODEL DG-I 65 AS MANUFACTURED BY LANDIA OR APPROVED EQUAL.

2.02 GENERAL

A. FURNISH LANDIA DG SERIES SUBMERSIBLE CHOPPER PUMPS AS SPECIFIED HEREIN.

THE PUMP SHALL BE NON-OVERLOADING THROUGHOUT THE ENTIRE RANGE OF OPERATION WITHOUT EMPLOYING SERVICE FACTOR. THE PUMP SHALL RESERVE A MINIMUM SERVICE FACTOR OF 1.15. THE PERFORMANCE CURVE SUBMITTED FOR APPROVAL SHALL STATE IN ADDITION TO HEAD AND CAPACITY PERFORMANCE, THE PUMP

EFFICIENCY, SOLID HANDLING CAPACITY, AND REFLECT MOTOR SERVICE FACTOR.

DJJ ADAIR CO LIFT STATION DETAILS:

§NUMBER OF PUMPS: 2

§OPERATING CONDITION: 150 GPM @ 11' TDH

§ IMPELLER: 150MM TRIM

§DISCHARGE: SHALL BE 2.5" ANSI FLANGE.

§MOTOR: SHALL BE 17.9 HP 208V 60 HZ 3-PHASE, AIR FILLED DESIGN.

§POWER CORD: SHALL BE EPOXY POTTED AND EQUIPPED WITH A MINIMUM OF 35' OF POWER CORD.

CONSTRUCTION

CASTINGS - CORD CAP / MOTOR HOUSING / BEARING HOUSING / SEAL PLATE SHALL BE ASTM A48 CLASS 30 CAST IRON

SHAFT SHALL BE 416 STAINLESS STEEL

IMPELLER- ASTM A48 CAST IRON CLASS 30 OR ASTM A536 DUCTILE IRON CLASS 65

FASTENERS / HARDWARE SHALL BE 300 SERIES STAINLESS STEEL

ELASTOMERS - O-RINGS / MECHANICAL SEALS / CORD GRIP GROMMETS SHALL BE NITRILE

MECHANICAL SEALS SHALL BE CARBON / SILICON CARBIDE

POWER CABLE SHALL BE TYPE SOOW OR W WHILE CONTROL CABLE SHALL BE SOOW

LIFTING BAIL SHALL BE WELDED OR FORGED 300 SERIES STAINLESS

ELECTRICAL POWER CORD

THE POWER CORD WILL BE SOOW OR W, OIL AND WATER RESISTANT 600V, 90C, UL AND CSA APPROVED AND APPLIED PER NEC AMPACITIES RATINGS AT THE CABLES RATED TEMPERATURE FOR INTERMITTENT / CONTINUOUS DUTY. THE PUMP SHALL BE DOUBLE PROTECTED WITH A COMPRESSION FITTING AND AN EPOXY POTTED AREA THAT SEALS EACH CONDUCTOR AT THE POWER CORD ENTRY TO THE PUMP. THE POWER CABLE ENTRY INTO THE CORD CAP ASSEMBLY SHALL FIRST BE MADE WITH A COMPRESSION FITTING. EACH INDIVIDUAL LEAD SHALL BE STRIPPED DOWN TO BARE WIRE AT STAGGERED INTERVALS AND EACH STRAND INDIVIDUALLY SEPARATED. THIS AREA OF THE CORD CAP SHALL THEN BE FILLED WITH AN EPOXY COMPOUND POTTING. THIS ASSEMBLY WILL PREVENT WATER CONTAMINATION FROM GAINING ENTRY EVEN IN THE EVENT OF WICKING OR CAPILLARY ACTION. THE POWER CORD LEADS SHALL BE CONNECTED TO THE MOTOR LEADS WITH A TERMINAL BLOCK OR EXTRA HEAVY CONNECTORS. THE CORD CAP ASSEMBLY WHERE BOLTED TO THE MOTOR HOUSING SHALL BE SEALED WITH A NITRILE O-RING ON A BEVELED EDGE TO ASSURE PROPER SEALING. WIRING CONNECTION SHALL BE DONE THROUGH A TERMINAL BLOCK ELIMINATING WIRE

NUTS OR USE OF HEAVY-DUTY CRIMP CONNECTORS.

MOTOR

THE MOTORS SHALL MEET PREMIUM EFFICIENCY IN ACCORDANCE WITH IEC 60034-30, LEVEL IE3 AND NEMA MG1 [NEMA

12.60 ENCLOSED MOTOR]. MOTOR RATING TESTS SHALL BE CONDUCTED IN ACCORDANCE WITH CSA C390-10 REQUIREMENTS. A CERTIFICATE SHALL BE AVAILABLE UPON REQUEST. THE MOTORS ARE SUBMERGED IN NON-TOXIC, OIL FILLED, COOL RUNNING DESIGN PROVIDING SIGNIFICANTLY REDUCED OPERATING TEMPERATURES. PUMP DESIGNS REQUIRING A SECONDARY COOLING APPARATUS SHALL BE DEEMED UNAPPROVED AND NOT EQUAL. AIR

FILLED PUMP DESIGNS SHALL NOT BE CONSIDERED EQUAL OR APPROVED.

THE COPPER STATOR WINDINGS SHALL BE INSULATED WITH MOISTURE RESISTANT CLASS H INSULATION MATERIALS, RATED FOR 180° C (356° F). [PER NEMA MG1 1.66]

THE SERVICE FACTOR SHALL BE 1.3 IN WET PIT SERVICE AND 1.0 FOR VFD OPERATION (AS DEFINED BY MG1 STANDARD). THE MOTOR SHALL HAVE A VOLTAGE TOLERANCE OF +/- 10% FROM NOMINAL, AND A PHASE-TO-PHASE

VOLTAGE IMBALANCE TOLERANCE OF 1%.

THE ROTOR BARS AND SHORT CIRCUIT RINGS SHALL BE MADE OF CAST ALUMINUM.

THE MOTOR SHALL BE DESIGNED FOR CONTINUOUS DUTY. THE MAXIMUM CONTINUOUS TEMPERATURE OF THE PUMPED LIQUID SHALL BE 40 C (104 F), AND INTERMITTENTLY UP TO 50 C (122 F). EACH OF THE THREE PHASES WILL HAVE A UL/FM APPROVED THERMOSTAT OR THERMISTOR. THE WINDING OPERATING TEMPERATURE AT RATED

HORSEPOWER AND SERVICE FACTOR WILL BE A MAXIMUM OF 130 C @ 40 C AMBIENT.

THE MOTOR SHALL BE CAPABLE OF HANDLING UP TO 15 (>=20KW) AND 20 (<20KW) EVENLY SPACED STARTS PER HOUR

WITHOUT OVERHEATING. [PER NEMA MG1 12.54]

THE MOTOR SHALL MEET THE REQUIREMENTS OF NEMA MG1 PART 30 AND 31 FOR OPERATION ON PWM TYPE VARIABLE FREQUENCY DRIVES. THE ROTORS WILL HAVE HIGH EFFICIENCY LAMINATED STEEL WITH DIE CAST BARS AND SHORTING RINGS. THE STATORS WILL HAVE HIGH EFFICIENCY LAMINATED STEEL (IF REQUIRED TO MEET PREMIUM EFFICIENCY), WITH INVERTER DUTY RATED, CLASS H MAGNET WIRE & INSULATION MATERIALS. EACH OF THE THREE PHASES WILL HAVE A UL/FM APPROVED THERMOSTAT OR THERMISTOR SET FOR 130C +/-5. (150C +/-5 FOR

320/360 FRAME HPE PRODUCT)

BEARINGS

THE UPPER BEARING SHALL BE A HEAVY-DUTY RADIAL SINGLE ROW BALL BEARING WHILE THE LOWER BEARING SHALL BE A DOUBLE ROW HEAVY-DUTY ANGULAR CONTACT BALL BEARING OF THE THRUST LIMITING DESIGN. MINIMUM OF 50,000 HOURS OF B10 BEARING LIFE FOR RADIAL & THRUST BEARINGS WHILE OPERATING ACROSS ENTIRE HYDRAULIC OPERATING RANGE OF THE PUMP. ANY PUMPS HAVING RATED B10 LIFE ONLY AT THE BEP SHALL NOT BE CONSIDERED EQUAL OR APPROVED. BEARING SHALL BE LUBRICATED FOR LIFE FROM THE FACTORY AND WILL BE ACCOMPLISHED THROUGH THE NON-TOXIC, LOW VISCOUS, DIELECTRIC OIL IN THE FRAME. PUMP DESIGNS REQUIRING PERIODIC SCHEDULED BEARING SERVICE SHALL NOT BE CONSIDERED EQUAL OR APPROVED. SINGLE ROW OR SLEEVE LOWER

BEARINGS SHALL NOT BE ACCEPTABLE.

SHAFT

THE PUMP SHAFT SHALL BE AN INTEGRAL, ONE-PIECE UNIT ADEQUATELY DESIGNED TO MEET THE MAXIMUM TORQUE REQUIRED AT ANY NORMAL START UP CONDITION OR OPERATING POINT IN THE SYSTEM. SHAFTS OF CARBON STEEL, CHROME PLATED, OR SPIN WELDED SHAFTS SHALL NOT BE CONSIDERED ADEQUATE OR EQUAL. MATERIAL OF SHAFT

SHALL BE 416 STAINLESS STEEL CONFORMING TO ASTM 8582.

FLUID END

THE IMPELLER SHALL BE ASTM CLASS 30 CAST IRON OR ASTM CLASS 65 DUCTILE IRON WITH OPTIONAL SST AVAILABLE. THE IMPELLER MOUNTING IS TO BE A SLIP FIT ONTO A TAPERED SHAFT AND A DRIVE KEY. THE IMPELLER SHALL BE ATTACHED TO THE SHAFT BY A SST FASTENER AND IMPELLER WASHER. THE IMPELLER IS TO BE BALANCED TO ISO1940-1 GRADE G6.3 STANDARD. IMPELLER DESIGNS THAT RELY ON FINS OR PINS PROTRUDING INTO THE SUCTION PATH TO ASSIST IN THE HANDLING OF FIBROUS MATERIAL SHALL NOT BE CONSIDERED EQUAL. IMPELLERS SHALL BE OF THE RADIAL SINGLE OR TWO VANE TYPE OR A VORTEX IMPELLER HAVING THE ABILITY TO PASS A WIDE RANGE OF SOLIDS. ANY IMPELLER DESIGN REQUIRING MECHANICAL BYPASS MECHANISM LOCATED IN THE VOLUTE IN

ORDER TO HANDLE SOLIDS SHALL NOT BE CONSIDERED EQUAL OR ACCEPTABLE.

THE VOLUTE SHALL BE ASTM CLASS 30 ALSO WITH OPTIONAL SST. IT WILL CONSIST OF A CENTERLINE DISCHARGE ONE PIECE DESIGN. THE PASSAGES ARE TO BE LARGE ENOUGH TO PASS THE SAME SOLID SIZE AS THE IMPELLER. THE DISCHARGE AND INLET FLANGES SHALL BE ANSI CLASS 125 AND BE INTEGRATED INTO THE VOLUTE CASE. THE WEAR RINGS SHALL BE REPLACEABLE RADIAL WEAR RINGS CONSTRUCTED OF 85-5-5-5 BRONZE THAT COME STANDARD IN

THE VOLUTE CASE WITH OPTIONAL SST AVAILABLE IN 304, 316 OR 410.

CHOPPER FLUID END

CHOPPING/MACERATION OF SOLIDS SHALL BE ACCOMPLISHED BY THE ACTION OF TWO ROTATING BLADES MOVING ACROSS ONE FIXED BLADE ALTERNATIVELY THREE FIXED BLADES MOUNTED BY THE PUMP INLET EXTERNAL OF THE PUMP CASING. THE CHOPPING SYSTEM SHALL BE DESIGNED TO PREVENT THE PUMP INLET FROM CLOGGING.

ROTATING AND FIXED BLADES SHALL BE EASILY REPLACEABLE WITHOUT THE USE OF SPECIAL TOOLS OR

REQUIREMENT OF PUMP DISASSEMBLY. FIXED AND ROTATING BLADES SHALL BE OF STEEL AISI A570 GR.36 AND HEAT

TREATED TO 60 ROCKWELL C HARDNESS.

IMPELLER SHALL BE OPEN TYPE CAST IRON AISI A48-40B AND DYNAMICALLY BALANCED. THE IMPELLER SHALL BE RIGIDLY HELD IN PLACE WITH AN IMPELLER BOLT AND HAVE NO AXIAL ADJUSTMENTS AND NO SET SCREWS. PUMP DESIGNS THAT REQUIRE AXIAL ADJUSTMENT OF THE IMPELLER WILL NOT BE ACCEPTED. THE IMPELLER SHALL NOT BE REQUIRED TO ASSIST IN ANY CHOPPING/MACERATING FUNCTION. PUMP DESIGNS THAT REQUIRE THE IMPELLER TO

CHOP SOLIDS WILL NOT BE ACCEPTED.

SEALS

EACH PUMP MUST BE EQUIPPED WITH A SWITCHABLE SEAL DESIGN ALLOWING FOR THE USE OF EITHER TANDEM MECHANICAL SEALS OR A CARTRIDGE DUAL SEAL DESIGN (ON 210 FRAME HPE PRODUCT) WITHOUT VOIDING THE AGENCY RATING OF THE PUMP. PUMPS UTILIZING ONE SEAL TECHNOLOGY SHALL NOT BE CONSIDERED EQUAL OR APPROVED. IN THE STANDARD TANDEM MECHANICAL SEAL CONFIGURATION THE LOWER SEAL SHALL BE OF THE TYPE 2 DESIGN AND CONSTRUCTED OF CARBON/ SILICON CARBIDE AND BE REPLACEABLE WITHOUT DISASSEMBLY OF THE SEAL CHAMBER AND WITHOUT THE USE OF SPECIAL TOOLS. THE UPPER SEAL SHALL OF THE TYPE 2100 DESIGN AND CONSTRUCTED OF CARBON/SILICON CARBIDE. EACH SEAL WILL NOT REQUIRE ROUTINE MAINTENANCE OR ADJUSTMENT. FOR EASE OF MAINTENANCE BOTH THE LOWER AND UPPER SEALS SHALL BE LOCALLY AVAILABLE AND OF A STANDARD DESIGN. FOR EASE OF SERVICE THE PUMPS SHALL BE AVAILABLE WITH A DROP IN CARTRIDGE SEAL CONSTRUCTED OF SILICON CARBIDE/CARBON. THE CARTRIDGE SEAL DESIGN SHALL FIT INTO THE SEAL CHAMBER WITH A SWITCHABLE SEAL PLATE ALLOWING FOR RETROFIT IN THE FIELD. UNITS EQUIPPED WITH OPPOSING MECHANICAL SEALS SHALL NOT BE ACCEPTABLE. ALL LOWER SEALS SHALL BE OPTIONALLY AVAILABLE IN TUNGSTEN

CARBIDE CONSTRUCTION.

EQUIPMENT MONITORING

THE INTEGRITY OF THE MECHANICAL SEAL SYSTEM SHALL BE CONTINUOUSLY MONITORED DURING PUMP OPERATION AND STAND BY TIME. TWO ELECTRICAL PROBES SHALL BE PROVIDED IN A SENSING CHAMBER POSITIONED BETWEEN THE PRIMARY AND SECONDARY MECHANICAL SEAL FOR DETECTING THE PRESENCE OF WATER CONTAMINATION WITHIN THE CHAMBER. THE SENSING CHAMBER SHALL BE FITTED WITH ENVIRONMENTALLY SAFE NONTOXIC OIL. A SOLID STATE RELAY MOUNTED IN THE PUMP CONTROL PANEL OR IN A SEPARATE ENCLOSURE SHALL SEND A LOW VOLTAGE, LOW AMPERAGE SIGNAL TO THE PROBE, CONTINUOUSLY MONITORING THE CONDUCTIVITY OF THE LIQUID IN THE SENSING CHAMBER. IF SUFFICIENT WATER ENTERS THE SENSING CHAMBER THROUGH THE PRIMARY MECHANICAL SEAL, THE PROBE SHALL SENSE THE INCREASE IN CONDUCTIVITY AND SIGNAL THE SOLID STATE RELAY IN THE CONTROL PANEL. THE RELAY SHALL THEN ENERGIZE A WARNING LIGHT ON THE CONTROL PANEL, OR OPTIONALLY, CAUSE THE PUMP TO SHUT DOWN. THIS SYSTEM SHALL PROVIDE AN EARLY WARNING OF MECHANICAL SEAL LEAKAGE, THEREBY PREVENTING DAMAGE TO THE SUBMERSIBLE PUMP AND ALLOWING SCHEDULED RATHER THAN EMERGENCY MAINTENANCE. SYSTEMS UTILIZING FLOAT SWITCHES OR ANY OTHER MONITORING DEVICES LOCATED IN THE STATOR HOUSING RATHER THAN IN A SENSING CHAMBER BETWEEN THE MECHANICAL SEALS ARE

NOT CONSIDERED TO BE EARLY WARNING SYSTEM, AND SHALL NOT BE CONSIDERED EQUAL.

SERVICEABILITY

THE COMPLETE ROTATING ASSEMBLY SHALL BE CAPABLE OF BEING REMOVED FROM THE VOLUTE WITHOUT DISTURBING THE SUCTION PIPING, DISCHARGE PIPING, AND VOLUTE. THE MOTOR HOUSING, SEAL HOUSING WITH SEAL PLATE AND IMPELLER STILL ATTACHED TO THE SHAFT SHALL BE CAPABLE OF BEING LIFTED OUT OF THE VOLUTE CASE FROM THE TOP AS ONE ASSEMBLY. FOR EASE OF REPAIR, THE MOTOR STATOR SHALL BE SECURELY HELD IN PLACE BY AN END RING SO IT CAN BE EASILY REMOVED WITHOUT THE USE OF HEAT OR A PRESS. NO SPECIAL TOOLS SHALL BE REQUIRED FOR PUMP AND MOTOR DISASSEMBLY. STATORS HELD IN PLACE BY HEAT SHRINK FIT SHALL NOT BE

ACCEPTABLE.

TESTING

ALL PUMPS SHALL BE BUILT IN A DEDICATED DOMESTIC FACTORY WITH FIFTY YEARS OF CONTINUOUS OPERATION.

ALL PUMPS SHALL BE VISUALLY INSPECTED TO CONFIRM THAT IT IS BUILT IN ACCORDANCE WITH THE SPECIFICATION AS TO HP, VOLTAGE, PHASE AND HERTZ. THE MOTOR SEAL AND HOUSING CHAMBERS SHALL BE MEGGERED FOR INFINITY TO TEST FOR MOISTURE CONTENT OR INSULATION DEFECTS. THE MOTOR HOUSING WILL BE FILLED WITH DIELECTRIC OIL AND SHALL BE ALLOWED TO RUN DRY TO CHECK FOR PROPER ROTATION. DISCHARGE PIPING SHALL BE ATTACHED, THE PUMP SUBMERGED IN WATER, AND AMP READINGS SHALL BE TAKEN ON EACH PHASE TO VERIFY BALANCED STATOR WINDINGS. THE PUMP SHALL BE REMOVED FROM THE WATER, MEGGERED AGAIN, AND DRIED.

VOLUTES CAN RECEIVE HYDROSTATIC TESTING TO ENSURE HIGH QUALITY CASTINGS ARE BEING PROVIDED. ALL PUMPS SHALL RECEIVE STANDARD HYDRAULIC INSTITUTE (HI) NON-WITNESSED TESTING AT A THIRD-PARTY AGENCY-CERTIFIED TEST LAB. PUMP MOTORS CAN BE TESTED ON A FACTORY DYNAMOMETER CAPABLE OF SIMULTANEOUSLY MEASURING TORQUE AND ROTATIONAL SPEED. TESTING CONDUCTED OFF SITE SHALL NOT BE

CONSIDERED EQUAL OR APPROVED.

PAINT

THE PUMP SHALL BE PAINTED WITH WATERBORNE HYBRID ACRYLIC/ALKYD PAINT. THIS CUSTOM ENGINEERED, QUICK DRY, LOW VOC PAINT SHALL PROVIDE SUPERIOR LEVELS OF CORROSION AND CHEMICAL PROTECTION. OPTIONAL COATINGS ARE AVAILABLE THROUGH THE FACTORY OF CHLORINATED RUBBER, COAL TAR EPOXY AND POLYAMIDE

EPOXY.

2.03 CONTROL PANEL

THE INCOMING POWER SHALL BE 208-VOLT, THREE-PHASE.

A NEMA 4X STAINLESS STEEL CONTROL PANEL SHALL BE FURNISHED AND INSTALLED APPROPRIATE FOR THE ELECTRICAL CHARACTERISTICS OF THE PUMP STATION. ENCLOSURE SHALL BE PROVIDED WITH A THREE-POINT LATCH. ENCLOSURE SHALL BE OF A STRONG AND RIGID CONSTRUCTION. CONTROL PANEL SHALL HAVE A FULL INNER DOOR FOR MOUNTING LIGHTS AND SWITCHES, AND TO PROTECT PERSONNEL FROM LIVE ELECTRICAL CIRCUITS. THE ENCLOSURE SHALL BE SIZED TO INCLUDE THE REQUIRED VARIABLE FREQUENCY DRIVES WHICH ARE BEING USED FOR PHASE CONVERSION. IN ADDITION, A PROPERLY SIZED AIR CONDITIONER SHALL BE PROVIDED TO MAINTAIN AN

ACCEPTABLE TEMPERATURE WITHIN THE ENCLOSURE.

THE CONTROL CIRCUIT SHALL BE 120 VOLT WITH DISCONNECT CIRCUIT BREAKER AND OVERLOAD PROTECTION. THE CONTROL SYSTEMS SHALL ALSO HAVE NECESSARY LOGIC TO PREVENT THE START OF MORE THAN ONE (1) PUMP AT THE SAME TIME. THE CONTROL SYSTEM SHALL HAVE NECESSARY LOGIC SUCH THAT THE PUMP STATION PERFORMS IN THE FOLLOWING MANNER. PUMP #1 AND PUMP #2 WILL ACT AS THE LEAD AND LAG PUMPS AND ALTERNATE UNDER

NORMAL CONDITIONS.

IN ADDITION, THE PANEL SHALL INCLUDE THE FOLLOWING FEATURES:

1. MAIN POWER CIRCUIT BREAKER

2. CIRCUIT BREAKER FOR EACH PUMP

3. DANFOSS FC-202 CONSTANT TORQUE VARIABLE FREQUENCY DRIVES SIZED FOR THE SPECIFIED PUMPS AT 208V, 3-PHASE.

4. ALTERNATING RELAY WITH LEAD PUMP SELECTOR SWITCH

5. HIGH WET WELL LEVEL OVERRIDE RELAY TO ACTIVE BOTH PUMPS SHOULD THE LIQUID LEVEL CONTINUE TO RISE

WHILE ONE PUMP IS IN OPERATION.

6. EACH PUMP SHALL INCLUDE AN HOA SWITCH, RED SEAL FAIL PILOT LIGHT, GREEN RUN PILOT LIGHT AND AN

ELAPSED TIME METER. THESE COMPONENTS SHALL BE INNER DOOR MOUNTED.

7. TO REDUCE CONDENSATION BUILD UP, THE PANEL SHALL INCLUDE A THERMOSTATICALLY CONTROLLED STRIP

HEATER.

8. INNER DOOR MOUNTED GFI RECEPTACLE WITH CIRCUIT BREAKER.

9. GENERAL ALARM LIGHT MOUNTED ON TOP OF THE ENCLOSURE WITH AN AUDIBLE ALARM (WITH SILENCE SWITCH)

TO INDICATE HIGH LEVEL ALARM OR SEAL FAIL.

THE PANEL SHALL BE MOUNTED WITH AN 18” LEG KIT AND INCLUDE APPROPRIATELY SIZED CORD GRIPS FOR SEALING

GASES OUT OF THE PANEL ENCLOSURE.

OPERATION SEQUENCE:

ON SUMP LEVEL RISE LOWER FLOAT SWITCH SHALL BE ENERGIZED. WHEN LEVEL RISES TO NEXT FLOAT, FLOAT SHALL BE ENERGIZED, AND LEAD PUMP SHALL START. WITH LEAD PUMP OPERATING, SUMP LEVEL SHALL LOWER TO LOW LEVEL FLOAT TURN-OFF SETTING AND PUMP WILL STOP. ALTERNATING RELAY WILL INDEX IN STOPPING OF PUMP SO THAT LAG PUMP WILL BECOME LEAD PUMP ON NEXT OPERATION. IF SUMP LEVEL CONTINUES TO RISE WHEN LEAD PUMP IS OPERATING, OVERRIDE FLOAT SWITCH SHALL OPERATE TOGETHER UNTIL LOW-LEVEL FLOAT SWITCH TURNS OFF BOTH PUMPS. IF LEVEL CONTINUES TO RISE WHEN BOTH PUMPS ARE OPERATING, ALARM FLOATS SWITCH WILL

ENERGIZE AND SIGNAL ALARM.

LEVEL CONTROLS:

SEALED MERCURY FLOAT SWITCHES SHALL BE PROVIDED AND INSTALLED. FOUR FLOATS SHALL BE REQUIRED FOR DUPLEX STATIONS. FLOATS SHALL BE ATTACHED TO SPECIAL MOUNTING BRACKET NEAR THE TOP OF THE BASIN SO

THAT LEVELS CAN BE CHANGED WITHOUT ENTERING THE SUMP BASINS.

2.17 ACCESS HATCHES WITH SAFETY GRATE

THERE SHALL BE FURNISHED AND INSTALLED AT EACH PUMP STATION, ONE (1) ALUMINUM ACCESS HATCHES AT THE PUMP STATION, AND ONE (1) FOR THE VALVE VAULT. HATCH SHALL BE SIZED TO ALLOW REMOVAL OF ALL PUMPING EQUIPMENT. HATCH SIZE SHALL BE DETERMINED BY THE PUMP SUPPLIER TO ALLOW FOR PROPER PUMP REMOVAL CLEARANCES. THE HATCH SHALL BE OF NON_SKID DESIGN AND DESIGNED TO HANDLE H-20 LOADING (OCCASIONAL

TRAFFIC LOAD).

A POSITIVE HOLD OPEN BAR SHALL BE PROVIDED TO SECURE THE HATCH IN THE OPEN POSITION. STAINLESS STEEL BOLTS FOR MOUNTING EACH RAIL SUPPORT PLATE SHALL BE FURNISHED SO THAT EACH SET OF GUIDE RAILS CAN

MOUNT DIRECTLY TO THE ACCESS HATCH.

ALL HINGES AND HINGE BOLTS SHALL BE STAINLESS STEEL. ALL HINGE BOLT NUTS SHALL BE TACK WELDED TO PREVENT REMOVAL OF BOLTS. ALL FASTENERS USED ON THE HATCHES SHALL BE NON-CORROSIVE. ALL AREAS OF HATCH FRAME THAT WILL BE IN CONTACT WITH CONCRETE SHALL BE COATED WITH BITUMASTIC PAINT.

EACH WET WELL HATCH SHALL BE PROVIDED WITH A FALL THROUGH PROTECTION SAFETY GRATE. GRATES SHALL BE ADEQUATELY SIZED TO ALLOW A CLEAR OPENING LARGE ENOUGH FOR PUMP TO CLEANLY PASS THROUGH.

PART 3 EXECUTION

BOOSTER PUMP 3.01 INSTALLATION

INSTALLATION SHALL BE IN STRICT ACCORDANCE WITH THE RESPECTIVE MANUFACTURER'S INSTRUCTIONS AND RECOMMENDATIONS IN THE LOCATIONS SHOWN ON THE DRAWINGS. INSTALLATION SHALL INCLUDE FURNISHING ANY REQUIRED OIL AND GREASE IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS. ANCHOR BOLTS SHALL BE STAINLESS STEEL AND SHALL BE SET BY THE CONTRACTOR, IN ACCORDANCE WITH THE MANUFACTURER'S

RECOMMENDATIONS AND APPROVED SHOP DRAWINGS.

3.02 TESTING

EACH PUMP AND MOTOR SHALL BE TESTED (WIRE TO WATER) AT THE FACTORY TO INSURE CONFORMANCE WITH APPROVED CHARACTERISTIC CURVE AND EFFICIENCIES. A CERTIFIED TEST CURVE FOR EACH PUMP SHALL BE SUBMITTED TO THE ENGINEER SHOWING AT LEAST FIVE (5) TEST POINTS. ONE OF THESE POINTS SHALL BE AT SHUT-OFF AND ANOTHER AT THE SPECIFIED OPERATING CONDITION. AT LEAST ONE OF THE POINTS SHALL BE TO THE RIGHT OF THE OPERATING CONDITION. ACCEPTANCE OF THESE CURVES SHALL BE MADE BY THE ENGINEER BEFORE

SHIPMENT.

3.03 MANUFACTURER SERVICE

A. FURNISH THE SERVICES OF A FACTORY REPRESENTATIVE FOR ONE, EIGHT-HOUR DAY DURING THE INSTALLATION

PHASE OF THE EQUIPMENT. THE FACTORY REPRESENTATIVE SHALL HAVE FULL

KNOWLEDGE AND EXPERIENCE IN THE INSTALLATION OF THE TYPE OF EQUIPMENT BEING INSTALLED.

B. THE DISTRIBUTOR FOR THE PUMP AND CONTROL PANEL MUST SHOW EVIDENCE OF A SERVICE DEPARTMENT. THE SERVICE DEPARTMENT MUST BE REGULARLY ENGAGED IN SERVICE WORK FOR AT LEAST ONE FULL YEAR PRIOR TO

THE BID DATE.

C. AFTER THE STATION IS INSTALLED, BUT PRIOR TO PUTTING IT INTO SERVICE, THE MANUFACTURER OR THE MANUFACTURER'S AUTHORIZED DISTRIBUTOR MUST PROVIDE START-UP SERVICES TO INCLUDE: VOLTAGE CHECK;

AMP CHECK; INSTALLATION CHECK; ROTATION CHECK; AND DRAW DOWN TEST TO ESTABLISH PUMP CAPACITY. A

WRITTEN REPORT TO THE ENGINEER MUST BE SUBMITTED AFTER START-UP.

END OF SECTION

30' 60' 90' 120'0'

NEW DUPLEX

VALVE PIT

NEW 3" PUMP

DISCHARGE

CONNECT NEW 3"

PUMP DISCHARGE

TO EXISTING

NEW 3" PUMP

DISCHARGE

VRH

TRG

ACCOUNT NO.

523-CAWT-AC12-00

TRG PSCArchitects - Engineers - Landscape Architects The Roberts Group

239 Southland Drive - Lexington, KY 40503 859-276-2006 - 859-276-2901 Facsimile

DJJ - ADAIR YDC SEWAGE GRINDER PIT RELOCATION

DEPARTMENT FOR JUVENILE JUSTICE

COLUMBIA, KY

DRAWING NO.

DECA REVIEWED

PHASE

FOR INTENT ONLY

DRAWING INFORMATION

DRAWING DATE

DRAWN BY

CHECKED BY

A&E FILE NO.

DECA LOG #

"D"

COMMONWEALTH OF KENTUCKY

FINANCE AND ADMINISTRATION CABINET

DEPARTMENT FOR FACILITIES MANAGEMENT

DIVISION OF ENGINEERING

FRANKFORT, KENTUCKY

02/16/2024

ST

ATE OF KENTUCKY

P R

O

FESS I ONA L ENG

I N E

E R

L

I C E N S E

D

DATEDESCRIPTION OF REVISIONS

REVISION HISTORY OF THIS DRAWING

DATEDESCRIPTION OF REVISIONS

XXX

P:

\K

YS

ta te \2

-C O

LU

M

BI

A-

KY

-D

JJ

P

LB

G

P R

O

JE

C T\

-P

LU

M

\2

P4 .0

PA

R

TI

AL

S

IT

E

U

TI

LI

TY

P

LA

N

AL

TE

R N

AT

E.

dw g

W ed ne sd ay

, F eb ru ar y

, 2

8:

A

M Th e R ob er ts G ro up

G re g

El am

TRG #23035

P4.0

EXPIRATION: 06/30/2025

RTA 02/16/2024

PARTIAL SITE UTILITY PLAN - PUMP DISCHARGE ROUTING

GENERAL NOTES:

A. EXISTING UTILITY LOCATIONS INDICATED ON THESE DRAWINGS ARE

BASED ON AS-BUILT DRAWINGS PROVIDED AFTER COMPLETION OF THE

ORIGINAL PROJECT. IN ADDITION TO CONTACTING ALL SUPPORTING

UTILITY COMPANIES AND SERVICES TO PROVIDE A MORE PRECISE UP TO

DATE LOCATION OF EACH SERVICE. LOCATIONS INDICATED ARE SHOWN

TO THE BEST OUR ABILITY. HOWEVER, THE CONTRACTOR SHALL STILL

CONFIRM EXACT UTILITY LOCATIONS AND TAKE EVERY PRECAUTION TO

AVOID DAMAGE TO EXISTING UTILITIES DURING CONSTRUCTION.

SHEET KEYED NOTES:

1. PROVIDE THRUST BLOCKS AT EVERY ELBOW AND TEE. SEE THRUST BLOCK DETAIL THIS

SHEET. TYPICAL.

2. NEW DUPLEX GRINDER PUMP STATION. SEE SHEET P3.0 FOR ADDITIONAL INFORMATION.

3. NEW PIPING TO BE INSTALLED UNDER EXISTING PAVEMENT. NEW PAVEMENT REPAIR

SHALL MATCH EXISTING PAVEMENT CONSTRUCTION. CONTRACTOR TO FIELD VERIFY

EXACT SQUARE FOOTAGE OF PAVEMENT REPLACEMENT.

1 PARTIAL SITE UTILITY PLAN - PUMP DISCHARGE ROUTING

5 FORCE MAIN BEDDING & BACKFILL

NO SCALE

2 HORIZONTAL THRUST BLOCKS

NO SCALE

3 FORCE MAIN BEDDING & BACKFILL

UNDER PAVEMENT CUT

SCALE

4 SANITARY SEWER AIR RELEASE

VALVE

SCALE

Addendum One
23035 - DJJ COLUMBIA COMBINED DWGS (1)
23035 - P1.0 - PARTIAL PLUMBING PLAN - EXISTING-P1.0
23035 - P1.1 - PARTIAL PLUMBING PLAN - DEMOLITION-P1.1
23035 - P2.0 - PARTIAL PLUMBING PLAN - NEW WORK-P2.0
23035 - P3.0 - PLUMBING GENERAL NOTES AND DETAILS-P3.0
23035 - P4.0 - PARTIAL SITE UTILITY PLAN - ALTERNATE-P4.0

File details come from the government source that posted it. Updated .