Addendum No Four.pdf
PDF 6 MB Posted
- Attached to
- RFB-109-26 KVA Replace Roof EKVC
- Solicitation number
- RFB-785-2600000183-4
- Issued by
- Montgomery County, Kentucky
About this file
This is Addendum No. 4 to Request for Bid No. RFB-109-26 issued by the Commonwealth of Kentucky Department for Facilities and Support Services Division of Engineering and Contract Administration for roof replacement at the Eastern Kentucky Veterans Center in Perry County, Kentucky. The project involves the installation of a two-ply styrene-butadiene-styrene (SBS) modified bituminous membrane roofing system over existing roof membranes across multiple roof areas designated A through Q, with total roof areas ranging from 33 square feet to 23,211 square feet depending on the section. The addendum, dated December 4, 2025, makes modifications to specifications and drawings by omitting the original Specification Section 075216 and replacing it with an updated version, and by omitting Sheets A.1 through A.5 and replacing them with revised sheets. The project includes installation of 1/2-inch cover board insulation, base and cap sheet installation, metal flashing, gutters, downspouts, walkway pads, roof drains, and various penetration details. Acceptable roofing system manufacturers include Johns Manville, Siplast, Soprema Inc., and Elevate (formerly Firestone Building Products).
The contractor must comply with a 20-year manufacturer warranty without dollar limitation and non-prorated coverage for wind speeds up to 72 miles per hour, plus a two-year installer warranty from the date of substantial completion. The specification requires that the roofing system installer be approved and certified by the roofing membrane manufacturer and eligible to receive the manufacturer's special warranty. Installation must proceed in the presence of the manufacturer's technical representative and include preliminary and preinstallation roofing conferences with the owner, architect, installer, and manufacturer. Final inspection must be arranged with the manufacturer's technical personnel within 48 hours notice to the architect and owner. Weather limitations apply, with work proceeding only when conditions permit installation in accordance with manufacturer specifications and warranty requirements. The project includes detailed submittals for product data, shop drawings, samples for verification, manufacturer certificates, and qualification statements prior to installation.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
COMMONWEALTH OF KENTUCKY
DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES
DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION
INVITATION TO BID NO: RFB-109-26
FOR: Roof Replacement Eastern Kentucky Veterans Center Kentucky Department of Veterans Affairs Perry County, Kentucky
DATE: December 5, 2025
RFB-785-2600000183
ADDENDUM NO. Four (4)
BIDDER SHALL CONFORM TO THE FOLLOWING CHANGES AS SAME SHALL BECOME BINDING
UPON THE CONTRACT TO BE ISSUED IN RESPONSE TO THIS INVITATION TO BID.
Item 1: Refer to attached addendum for all additions, deletions, and/or changes to specifications and/or drawings.
END OF ADDENDUM
Invitation to Bid No. RFB-109-26 For: Roof Replacement Eastern Kentucky Veterans Center Kentucky Department of Veterans Affairs Perry County, Kentucky
Kristi Sharp, Statewide Procurement Manager Division of Engineering and Contract Administration
PATRICK D. MURPHY CO., INC. ARCHITECTS
4606 Illinois Avenue • Louisville, Kentucky 40213-1923 • (502) 454-5632
Member - American Institute of Architects
ADDENDUM NO. 4 December 4, 2025
RE: Request for Bid No. RFB-109-26
Roof Replacements Eastern Kentucky Veterans Center Kentucky Department of Veterans Affairs
Perry County, Kentucky
From: Patrick D. Murphy Co., Inc. Architects
4606 Illinois Avenue Louisville, KY 40213
To: Prospective Bidders
BIDDER SHALL CONFORM TO THE FOLLOWING CHANGES AS SAME SHALL BECOME BINDING
UPON THE CONTRACT TO BE ISSUED IN RESPONSE TO THE INVITATION TO BID.
Note: Acknowledgement of this Addendum shall be made on the “Bid Document”
CHANGES TO PROJECT MANUAL
1. N/A
CHANGES TO SPECIFICATIONS
1. Omit Specification 014110 Section 075216 - STYRENE-BUTADIENE-STYRENE (SBS) MODIFIED BITUMINOUS MEMBRANE ROOFING and replace with attached Specification Section 075216 - STYRENE-BUTADIENE-STYRENE (SBS) MODIFIED
BITUMINOUS MEMBRANE ROOFING (ADD #4)
CHANGES TO DRAWINGS
1. Omit Sheets A.1 - A.5 and replace with attached Sheets A.1 – A.5 (ADD #4)
GENERAL ITEMS
1. N/A
END OF ADDENDUM NO. 4
Patrick D Murphy Co. Inc.
074-CBNJ-EK16-00
K.V.A. – Replace Roof Eastern Kentucky Veterans Center
Hazard, Kentucky
STYRENE-BUTADIENE-STYRENE (SBS)
MODIFIED BITUMINOUS MEMBRANE
ROOFING
075216 - 1
SECTION 075216 - STYRENE-BUTADIENE-STYRENE (SBS) MODIFIED
BITUMINOUS MEMBRANE ROOFING (ADDENDUM #4)
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Styrene-butadiene-styrene (SBS) modified bituminous membrane roofing system.
2. Base sheet.
3. Cap sheet.
4. Base flashing sheet.
5. Asphalt materials.
6. Accessory roofing system materials.
7. Roof insulation and accessories.
8. Cover board.
9. Walkways.
B. Related Requirements:
1. Section 061000 "Rough Carpentry" for wood nailers, curbs, and blocking, and for wood-based, structural-use roof deck panels.
2. Section 076200 "Sheet Metal Flashing and Trim" for metal roof flashings and counterflashings.
3. Section 077200 "Roof Accessories" for manufactured roof curbs, equipment supports, roof hatches, vents, and other manufactured roof accessory units.
4. Section 079200 "Joint Sealants" for joint sealants, joint fillers, and joint preparation.
1.2 DEFINITIONS
A. Roofing Terminology: Definitions in ASTM D1079 and glossary of NRCA's "Roofing Manual: Membrane Roof Systems" apply to Work of this Section.
1.3 PREINSTALLATION MEETINGS
A. Preliminary Roofing Conference: Before starting roof deck construction, conduct conference at Project site.
1. Meet with Owner, Architect, Owner's insurer if applicable, testing and inspecting agency representative, Roofing System Installer, roofing system manufacturer's representative, and other installers whose work interfaces with or affects roofing, including installers of roof accessories and roof-mounted equipment.
2. Review methods and procedures related to roofing system installation, including
K.V.A. – Replace Roof Eastern Kentucky Veterans Center
Hazard, Kentucky
STYRENE-BUTADIENE-STYRENE (SBS)
MODIFIED BITUMINOUS MEMBRANE
ROOFING
075216 - 2 manufacturer's written instructions.
3. Review and finalize construction schedule, and verify availability of materials, Installer's personnel, equipment, and facilities needed to make progress and avoid delays.
4. Review structural loading limitations of roof deck during and after roofing.
5. Review base flashings, special roofing details, roof drainage, roof penetrations, equipment curbs, and condition of other construction that affects roofing system.
6. Review governing regulations and requirements for insurance and certificates if applicable.
7. Review temporary protection requirements for roofing system during and after installation.
8. Review roof observation and repair procedures after roofing installation.
B. Preinstallation Roofing Conference: Conduct conference at Project site.
1. Meet with Owner, Architect, Owner's insurer if applicable, Roofing System Installer, roofing system manufacturer's representative, and other installers whose work interfaces with or affects roofing, including installers of roof accessories and roof-mounted equipment.
2. Review methods and procedures related to roofing system installation, including manufacturer's written instructions.
3. Review and finalize construction schedule, and verify availability of materials, Installer's personnel, equipment, and facilities needed to make progress and avoid delays.
4. Review structural loading limitations of roof deck during and after roofing.
5. Review base flashings, special roofing details, roof drainage, roof penetrations, equipment curbs, and condition of other construction that affects roofing system.
6. Review governing regulations and requirements for insurance and certificates if applicable.
7. Review temporary protection requirements for roofing system during and after installation.
8. Review roof observation and repair procedures after roofing installation.
1.4 ACTION SUBMITTALS
A. Product Data:
1. For each type of product.
B. Shop Drawings: Include roof plans, sections, and attachment details, including the following:
1. Layout and thickness of insulation.
2. Base flashings and membrane termination details.
3. Flashing details at penetrations.
4. Roof plan showing orientation of roof deck and orientation of roofing membrane, fastener spacings, and pattern for corner, perimeter, and field-of-roof locations.
5. Insulation fastening patterns for corner, perimeter, and field-of-roof locations.
6. Crickets, saddles, and tapered edge strips, including slopes.
K.V.A. – Replace Roof Eastern
075216 - 3
7. Tie-in with adjoining wall system air barrier.
C. Samples for Verification: Actual sample of finished products for the following products:
1. Cap Sheet: Samples of manufacturer's standard colors for selection by Architect.
2. Base Flashing Sheet: Samples of manufacturer's standard colors for selection by Architect.
3. Walkways: Samples of manufacturer's standard colors for selection by Architect.
D. Wind-Uplift-Resistance Submittal: For roofing system, indicating compliance with wind-uplift performance requirements.
1.5 INFORMATIONAL SUBMITTALS
A. Manufacturer Certificates:
1. Performance Requirement Certificate: Signed by roofing membrane manufacturer certifying that roofing system complies with requirements specified in "Performance Requirements" Article.
a. Submit evidence of complying with performance requirements.
2. Special Warranty Certificate: Signed by roofing membrane manufacturer, certifying that all materials supplied under this Section are acceptable for special warranty.
B. Qualification Statements: For roofing system Installer and manufacturer.
C. Sample warranties.
1.6 CLOSEOUT SUBMITTALS
A. Maintenance Data: For roofing system.
B. Certified statement from existing roofing system manufacturer stating that existing roof warranty has not been affected by Work performed under this Section.
1.7 QUALITY ASSURANCE
A. Manufacturer Qualifications: A qualified manufacturer that is UL listed and listed in FM Approvals' RoofNav for roofing system identical to that used for this Project.
B. Installer Qualifications: A qualified firm that is approved, authorized, certified, or licensed by roofing system manufacturer to install manufacturer's product and that is eligible to receive manufacturer's special warranty.
K.V.A. – Replace Roof Eastern
075216 - 4
1.8 DELIVERY, STORAGE, AND HANDLING
A. Deliver roofing system materials to Project site in original containers with seals unbroken and labeled with manufacturer's name, product brand name and type, date of manufacture, approval or listing agency markings, and directions for storing and mixing with other components.
B. Store liquid materials in their original undamaged containers in a clean, dry, protected location and within the temperature range required by roofing system manufacturer.
1. Protect stored liquid material from direct sunlight.
2. Discard and legally dispose of liquid material that cannot be applied within its stated shelf life.
C. Protect roof insulation materials from physical damage and from deterioration by sunlight, moisture, soiling, and other sources.
1. Store in a dry location.
2. Comply with insulation manufacturer's written instructions for handling, storing, and protecting during installation.
D. Handle and store roofing system materials, and place equipment in a manner to avoid permanent deflection of deck.
1.9 FIELD CONDITIONS
A. Weather Limitations: Proceed with installation only when existing and forecasted weather conditions permit roofing to be installed in accordance with roofing system manufacturer's written installation instructions and warranty requirements.
1.10 WARRANTY
A. Special Warranty: Manufacturer agrees to repair or replace components of roofing system that fail in materials or workmanship within specified warranty period.
1. Special warranty to include all components of roofing system, such as roof insulation, fasteners, adhesives, cover board, roofing membranes, base flashing sheet, walkway products, and other components of roofing system.
2. Warranty Period: 20-years from date of Substantial Completion.
3. Manufacturers No Dollar Limit (NDL) Total Systems Warranty Form, without monetary limitation, non-prorated.
4. Warranty shall cover wind speeds less than, or equal to 72 MPH.
5. Where more than one building is part of the project, a separate warranty shall be issued for each building.
B. Roofing System Installer's Warranty: Submit Roofing System Installer's warranty, on warranty form at end of this Section, signed by Roofing System Installer, covering the Work of this Section, including all components of roofing system, such as roof insulation, fasteners, adhesives, cover board, roofing membranes, base flashing
K.V.A. – Replace Roof Eastern
075216 - 5 sheet, walkway products, and other components of roofing system.
1. Warranty Period: Two-years from date of Substantial Completion.
PART 2 - PRODUCTS
2.1 SOURCE LIMITATIONS
A. Obtain components for roofing system from roofing membrane manufacturer.
2.2 PERFORMANCE REQUIREMENTS
A. General Performance: Installed roofing system and flashings to withstand specified uplift pressures, thermally induced movement, and exposure to weather without failure due to defective manufacture, fabrication, installation, or other defects in construction.
Roofing system and flashings to remain watertight.
1. Accelerated Weathering: Roofing membrane to withstand 2000 hours of exposure when tested in accordance with ASTM G152, ASTM G154, or ASTM G155.
2. Impact Resistance: Roofing membrane to resist impact damage when tested in accordance with ASTM D3746/D3746M, ASTM D4272/D4272M, or the Resistance to Foot Traffic Test section in FM Approvals 4470.
B. Material Compatibility: Roofing system materials to be compatible with one another and adjacent materials under conditions of service and installation required, as demonstrated by roofing membrane manufacturer based on testing and field experience.
C. Wind-Uplift Resistance: Design roofing system to resist the following wind-uplift pressures when tested in accordance with FM Approvals 4474, UL 580, or UL 1897:
1. Zone 1' (Roof Area Interior): <18 lbf/sq. ft.>.
2. Zone 1 (Roof Area Field): <28 lbf/sq. ft.>.
3. Zone 3 (Roof Area Corners): <42 lbf/sq. ft.>.
a. Location: 10’-5” in each direction from each building corner.
D. FM Approvals' RoofNav Listing: Roofing membrane, base flashings, and component materials comply with requirements in FM Approvals 4450 or FM Approvals 4470 as part of a roofing system and are listed in FM Approvals' RoofNav for Class 1 or noncombustible construction, as applicable. Identify materials with FM Approvals Certification markings.
1. Fire/Windstorm Classification: Class 1A-90.
2. Hail-Resistance Rating: FM 1-34 SH.
E. Fire-Resistance Ratings: Comply with fire-resistance-rated assembly designs
K.V.A. – Replace Roof Eastern
075216 - 6 indicated.
1. Identify products with appropriate markings of applicable testing agency.
2.3 STYRENE-BUTADIENE-STYRENE (SBS) MODIFIED BITUMINOUS MEMBRANE
ROOFING SYSTEM
A. Roofing System Components: See the following articles for individual roof materials required for two- ply roofing system; hot-applied asphalt, cold-applied adhesive, heat-welded laps installation method.
1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
a. Johns Manville; a Berkshire Hathaway company
b. Siplast
c. Soprema, Inc.
d. Elevate (formerly Firestone Building Products)
2.4 BASE FLASHING SHEET
A. SBS-Modified Bitumen, Smooth-Surfaced Backer Sheet: Matching base sheet, suitable for installation method specified.
B. Asphalt-Coated, Glass-Fiber-Mat Backer Sheet: ASTM D4601/D4601M, Type I or Type II, asphalt-impregnated and coated glass-fiber sheet, dusted with fine mineral surfacing on both sides, suitable for installation method specified.
C. SBS-Modified Bitumen, Metal-Surfaced Base Flashing Sheet: ASTM D6298/D6298M, metal-foil-surfaced sheet, reinforced with glass fibers, suitable for installation method specified, and as follows:
1. Metal Surfacing: Aluminum.
D. Liquid Base Flashing System: Roofing membrane manufacturer's standard moisture curing resin with low solvent content, consisting of a primer, flashing cement, and reinforcing scrim, suitable for installation method specified.
2.5 ASPHALT MATERIALS
A. Asphalt Primer: ASTM D41/D41M.
B. Roofing Asphalt: ASTM D312/D312M, Type III or IV as recommended by roofing system manufacturer, suitable for installation method specified.
K.V.A. – Replace Roof Eastern
075216 - 7
2.6 ACCESSORY ROOFING SYSTEM MATERIALS
A. General: Accessory materials as recommended in writing by roofing membrane manufacturer for intended use, compatible with other roofing system components, and suitable for installation method specified.
1. Adhesives and Sealants: Comply with VOC limits of authorities having jurisdiction.
B. Prefabricated Pipe Flashings: As recommended in writing by roofing membrane manufacturer.
C. Roof Vents: As recommended in writing by roofing membrane manufacturer.
1. Size: Not less than 4-inch diameter.
D. Sheathing Paper: Red-rosin type, minimum 3 lb/100 sq. ft..
E. Metal Termination Bars: Manufacturer's standard, predrilled stainless steel or aluminum bars, approximately 1 by 1/8 inch thick; with anchors.
F. Cold-Applied Trichloroethylene Asphalt Adhesive: ASTM D3019, Type III, roofing membrane manufacturer's standard asphalt-based, one- or two-part, asbestos-free, cold-applied adhesive, specially formulated for compatibility and use with roofing membrane sheets and base flashing sheets; designed for adhering roofing system components to substrate and each other, tested by roofing system manufacturer to meet performance requirements.
G. Cold-Applied Polymer-Modified Asphalt Adhesive: Roofing membrane manufacturer's standard solvent- and asbestos-free, cold-applied adhesive, specially formulated for compatibility and use with roofing membrane sheets and base flashing sheets;
designed for adhering roofing system components to substrate and each other, tested by roofing system manufacturer to meet performance requirements.
H. Asphalt Roofing Cement: ASTM D4586/D4586M, asbestos free, of consistency required by roofing membrane manufacturer.
I. Mastic Sealant: Polyisobutylene, plain or modified bitumen; nonhardening, nonmigrating, nonskinning, and nondrying.
J. Self-Adhered Primer: Roofing membrane manufacturer's standard primer to enhance the adhesion of membrane to substrate.
K. Fasteners: Factory-coated steel fasteners and metal or plastic plates complying with corrosion-resistance provisions in FM Approvals 4470, designed for fastening roofing components to substrate; tested for required pullout strength, and acceptable to roofing membrane manufacturer.
L. Roofing Granules: Roofing membrane manufacturer's standard ceramic-coated mineral roofing granules, No. 11 screen size with 100 percent passing No. 8 sieve and 98 percent of mass retained on No. 40 sieve; color matching cap sheet.
K.V.A. – Replace Roof Eastern
075216 - 8
M. Safety Accessories: Roofing membrane manufacturer's standard yellow seaming tape for designating safety perimeters and rooftop hazards.
N. Miscellaneous Accessories: As recommended in writing by roofing membrane manufacturer.
2.7 ROOF INSULATION AND ACCESSORIES
A. General: Preformed roof insulation boards, manufactured or approved by roofing membrane manufacturer, approved for use in FM Approvals' RoofNav listed roof assemblies.
B. Tapered Insulation: Where indicated on drawings. Provide factory-tapered insulation boards.
1. Material: Match roof insulation.
2. Minimum Thickness: 1/4 inch.
3. Slope:
a. Roof Field: 1/4 inch per foot unless otherwise indicated on Drawings.
b. Saddles and Crickets: 1/2 inch per foot unless otherwise indicated on
Drawings.
C. Roof Insulation Accessories, General: As recommended in writing by insulation manufacturer for intended use, compatible with other roofing system components and suitable for installation method specified.
D. Insulation Fasteners: Factory-coated steel fasteners and metal or plastic plates complying with corrosion-resistance provisions in FM Approvals 4470, designed for fastening roof insulation to substrate, and acceptable to roofing membrane manufacturer.
E. Insulation Cant Strips: ASTM C728, perlite insulation board or ASTM C208, Type II, Grade 1, cellulosic-fiber insulation board.
F. Tapered Edge Strips: ASTM C728, perlite insulation board or ASTM C208, Type II, Grade 1, cellulosic-fiber insulation board.
2.8 COVER BOARD
A. General: Cover board as recommended in writing by roofing membrane manufacturer for intended use; compatible with other roofing system components and suitable for installation method specified.
B. Cellulosic-Fiber Cover Board: ASTM C208, Type II, Grade 2, high-density cellulosic-fiber insulation board, having a minimum compressive strength of 40 psi.
1. Thickness: 1/2 inch.
2. Size: 48 x 48 inches or 48 x 96 inches.
K.V.A. – Replace Roof Eastern
075216 - 9
3. Surface Finish: Primed one side.
C. High-Density Polyisocyanurate Cover Board: ASTM C1289, Type II, Class 4, Grade 1, 1/2 inch thick, having a minimum compressive strength of 80 psi.
D. Polyisocyanurate Cover Board: ASTM C1289, Type II, Class 1, 1/2 inch thick.
2.9 WALKWAYS
A. Walkway Pads: Reinforced asphaltic composition pads with slip-resisting mineral-granule surface, manufactured as a traffic pad for foot traffic and acceptable to roofing membrane manufacturer.
1. Pad Size: Approximately 36 by 60 inches or 30 by 30 inches.
2. Color: Match cap sheet.
B. Walkway Cap Sheet Strips: Matching cap sheet; suitable for installation method specified, and as follows:
1. Size: 36 by 60 inches.
2.10 BASE SHEET MATERIALS
A. SBS-Modified Bitumen Fiberglass Mat Base Sheet: ASTM D6163, Type I or Type II, Grade S, SBS-modified asphalt sheet, reinforced with fiberglass fabric; smooth surfaced; suitable for cold adhesive or hot asphalt application method.
1. Maximum filler content in elastomeric blend – 35% by weight.
2. Ultimate Elongation @ 73ºF (23ºC): 50% (ASTM D 5147)
2.11 CAP SHEET MATERIAL
A. Granule-Surfaced Roofing Cap Sheet: ASTM D6163, Type I, Grade G, SBS-modified asphalt sheet, reinforced with fiberglass fabric; suitable for cold adhesive asphalt application method.
1. Granule Color: White.
2. Maximum filler content in elastomeric blend – 35% by weight.
3. Ultimate Elongation @ 73ºF (23ºC): 55% (ASTM D 5147)
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine substrates, areas, and conditions, with Roofing System Installer present, for
K.V.A. – Replace Roof Eastern
075216 - 10 compliance with requirements and other conditions affecting performance of the Work.
1. Verify that roof openings and penetrations are in place, curbs are set and braced, and roof-drain bodies are securely clamped in place.
2. Verify that wood cants, blocking, curbs, and nailers are securely anchored to roof deck at penetrations and terminations and that nailers match thicknesses of insulation.
B. Proceed with installation only after unsatisfactory conditions have been corrected.
3.2 PREPARATION
A. Clean substrate of dust, debris, moisture, and other substances detrimental to roofing system installation in accordance with roofing system manufacturer's written installation instructions.
1. Remove sharp projections.
B. Prevent materials from entering and clogging roof drains and conductors and from spilling or migrating onto surfaces of other construction.
1. Remove roof-drain plugs when no work is taking place or when rain is forecast.
3.3 SUMMARY OF WORK
A. The following is a general outline of roof work to be performed:
1. Roofing System Description Over Existing Roof Membrane:
a. Mechanically fasten 1-layer ½” roof insulation over existing roof membrane, as per manufacturers latest recommendations.
b. Install one (base) flashing ply of smooth surface SBS modified bitumen fiberglass mat base sheet with hot roofing asphalt or cold adhesive. Verify manufacturers requirements.
c. Install one (base) ply of smooth surface SBS modified bitumen fiberglass mat base sheet with hot roofing asphalt to roof surface.
d. Install one ply of granule surfaced SBS modified bitumen cap sheet with cold-applied asphalt adhesive.
e. On cap sheet, hold back cold adhesive 2” from side and end laps and heat weld side and end laps and roll laps with ¼” bleed out.
f. Adhere foil faced modified flashings at walls and curbs.
3.4 INSTALLATION OF ROOF INSULATION AND ACCESSORIES
A. Coordinate installation of roofing system components, so insulation is not exposed to precipitation or left exposed at end of workday.
B. Comply with roofing system and insulation manufacturer's written installation
K.V.A. – Replace Roof Eastern
075216 - 11 instructions. Install minimum of two layers of insulation under area of roofing to achieve required thickness.
C. Insulation Cant Strips: Install and secure preformed 45-degree insulation cant strips at junctures of roofing system with vertical surfaces or angle changes greater than 45 degrees.
3.5 INSTALLATION OF COVER BOARD
A. Comply with roofing system and insulation manufacturer's written installation instructions.
B. Install 1/2” cover board insulation over existing roof membrane with long joints in continuous straight lines, with end joints staggered between rows. Offset joints of insulation below a minimum of 6 inches in each direction.
1. Trim cover board neatly to fit around penetrations and projections, and to fit tight to intersecting sloping roof decks.
2. At internal roof drains, conform to slope of drain sump.
3. Trim cover board, so that water flow is unrestricted.
4. Cut and fit cover board tight to nailers, projections, and penetrations.
5. Secure cover board to insulation in accordance with FM Approvals' RoofNav listed roof assembly requirements for specified Windstorm Resistance Classification and FM Global Property Loss Prevention Data Sheet 1-29.
6. Secure cover board to resist specified uplift pressure at corners, perimeter, and field of roof.
3.6 INSTALLATION OF SBS ROOFING MEMBRANE, GENERAL
A. Install roofing membrane in accordance with roofing system manufacturer's written installation instructions and applicable recommendations in NRCA's "Quality-Control Guidelines for the Application of Polymer-Modified Bitumen Roofing."
B. Start installation of roofing in presence of roofing system manufacturer's technical personnel.
C. Coordinate installation of roofing system so insulation and other components of roofing system not permanently exposed are not subjected to precipitation or left uncovered at end of workday or when rain is forecast.
1. Provide tie-offs at end of each day's work to cover exposed roofing sheets and insulation with a course of coated felt set in adhesive, with joints and edges sealed.
2. Complete terminations and base flashings and provide temporary seals to prevent water from entering completed sections of roofing system.
3. Remove and discard temporary seals before beginning work on adjoining roofing.
K.V.A. – Replace Roof Eastern
075216 - 12
3.7 INSTALLATION OF BASE SHEET
A. Before installing, unroll base sheet, cut into workable lengths, and allow to lie flat for a time period recommended by roofing membrane manufacturer for the ambient temperature at which base sheet will be installed.
B. Installation of Base Sheet:
1. Install base sheet in accordance with roofing membrane manufacturer's written installation instructions, starting at low point of roof.
2. Extend base sheet over and terminate above cants.
3. Install base sheet in a shingle fashion.
4. Adhere base sheet to substrate in a uniform coating of hot-applied asphalt.
5. Install base sheet without wrinkles or rears, and free from air pockets.
6. Laps: Accurately align base sheet, without stretching, and maintain uniform side and end laps.
a. Lap side laps as recommended by roofing membrane manufacturer but not less than 3 inches.
b. Lap end laps as recommended by roofing membrane manufacturer but not less than 12 inches. Stagger end laps not less than 18 inches.
c. Completely bond and seal laps, leaving no voids.
7. Repair tears and voids in laps and lapped seams not completely sealed.
8. Apply pressure to body of base sheet in accordance with roofing membrane manufacturer's written installation instructions, to remove air pockets and to result in complete adhesion of base sheet to substrate.
3.8 INSTALLATION OF CAP SHEET
A. Before installing, unroll cap sheet, cut into workable lengths, and allow to lie flat for a time period recommended by roofing membrane manufacturer for the ambient temperature at which cap sheet will be installed.
B. Install cap sheet in accordance with roofing membrane manufacturer's written installation instructions, starting at low point of roof.
1. Extend cap sheet over and terminate above cants.
2. Install cap sheet in a shingle fashion.
3. Adhere cap sheet to bottom layer in a uniform coating of cold-applied adhesive.
4. Install cap sheet without wrinkles or tears, and free from air pockets.
5. Install cap sheet so side and end laps shed water.
C. Laps: Accurately align roof sheets, without stretching, and maintain uniform side and end laps.
1. Lap side laps as recommended by roofing membrane manufacturer but not less than 3 inches.
2. Lap end laps as recommended by roofing membrane manufacturer but not less than 12 inches. Stagger end laps not less than 18 inches.
K.V.A. – Replace Roof Eastern
075216 - 13
3. Heat-weld side and end laps, leaving no voids.
4. Roll laps with a 20 lb roller.
5. Repair tears and voids in laps and lapped seams not completely sealed.
D. Apply pressure to body of cap sheet in accordance with roofing membrane manufacturer's written installation instructions, to remove air pockets and result in complete adhesion of cap sheet to substrate.
E. Apply roofing granules of same color as cap sheet to cover exuded bead at laps while bead is hot, to provide a continuous color appearance.
3.9 INSTALLATION OF BASE FLASHING AND STRIPPING
A. Install base flashing sheet over cant strips and other sloped and vertical surfaces, at roof edges, and at penetrations through roof, and secure to substrates in accordance with roofing system manufacturer's written installation instructions and as follows:
1. Prime substrates with asphalt primer if required by roofing system manufacturer.
2. Base Flashing Sheet Installation, Hot: Adhere base flashing sheet to substrate in a solid mopping of hot-applied asphalt applied at asphalt temperature recommended by base flashing sheet manufacturer. Apply hot-applied asphalt to back of base flashing sheet if recommended by roofing system manufacturer.
3. Base Flashing Sheet Installation, Cold: Adhere base flashing sheet to substrate in cold-applied adhesive at rate required by roofing system manufacturer.
B. Extend base flashing sheet up walls or parapets a minimum of 8 inches above roofing membrane and 4 inches onto field of roofing membrane.
C. Mechanically fasten top of base flashing sheet securely at terminations and perimeter of roof.
1. Seal top termination of base flashing sheet.
D. Install liquid flashing system in accordance with roofing system manufacturer's written installation instructions.
1. Extend liquid flashing not less than 3 inches in all directions from edges of item being flashed.
2. Embed granules, matching color of cap sheet, into wet compound.
E. Install cap sheet stripping where metal flanges and edgings are set on roof in accordance with roofing system manufacturer's written installation instructions.
F. Roof Drains: Set 30-by-30-inch-4 lb flashing in bed of adhesive on completed roofing membrane.
1. Cover flashing with cap sheet stripping, and extend a minimum of 4 inches to 6 inches beyond edge of metal flashing onto field of roofing membrane.
2. Clamp roofing membrane, metal flashing, and stripping into roof-drain clamping
K.V.A. – Replace Roof Eastern
075216 - 14 ring.
3. Install stripping in accordance with roofing system manufacturer's written installation instructions.
3.10 INSTALLATION OF WALKWAYS
A. Walkway Pads: Install walkway pads using units of size indicated or, if not indicated, of manufacturer's standard size; secure to cap sheet in accordance with roofing system manufacturer's written installation instructions.
1. Install walkways at the following locations: See drawings for additional information.
a. Perimeter of each rooftop unit.
b. Between each rooftop unit location, creating a continuous path connecting rooftop unit locations.
c. Between each roof hatch and each rooftop unit location or path connecting rooftop unit locations.
d. Top and bottom of each roof access ladder.
e. Between each roof access ladder and each rooftop unit location or path connecting rooftop unit locations.
f. Locations indicated on Drawings.
g. As required by roofing system manufacturer's warranty requirements.
2. Provide 3-inch clearance between adjoining pads.
B. Walkway Cap Sheet Strips: Install walkway cap sheet strips over roofing membrane, using same installation method as that used for cap sheet.
1. Install walkways strips at the following locations:
a. Perimeter of each rooftop unit.
b. Between each rooftop unit location, creating a continuous path connecting rooftop unit locations.
c. Between each roof hatch and each rooftop unit location or path connecting rooftop unit locations.
d. Top and bottom of each roof access ladder.
e. Between each roof access ladder and each rooftop unit location or path connecting rooftop unit locations.
f. Locations indicated on Drawings.
g. As required by roofing membrane manufacturer's warranty requirements.
2. Provide 3-inch clearance between adjoining strips.
3.11 FIELD QUALITY CONTROL
A. Final Roof Inspection: Arrange for roofing system manufacturer's technical personnel to inspect roofing installation on completion, in presence of Architect, and to prepare inspection report.
K.V.A. – Replace Roof Eastern
075216 - 15
1. Notify Architect and Owner 48 hours in advance of date and time of inspection.
B. Repair or remove and replace components of roofing system where inspections indicate that they do not comply with specified requirements.
1. Roofing system will be considered defective if it does not pass tests and inspections.
C. Additional testing and inspecting, at Contractor's expense, will be performed to determine if replaced or additional work complies with specified requirements.
D. Prepare test and inspection reports.
3.12 PROTECTION AND CLEANING
A. Protect roofing system from damage and wear during remainder of construction period.
1. When remaining construction does not affect or endanger roofing, inspect roofing system for deterioration and damage, describing its nature and extent in a written report, with copies to Architect and Owner.
B. Correct deficiencies in or remove roofing system that does not comply with requirements, repair substrates, and repair or reinstall roofing system to a condition free of damage and deterioration at time of Substantial Completion and in accordance with warranty requirements.
C. Clean overspray and spillage from adjacent construction using cleaning agents and procedures recommended by manufacturer of affected construction.
END OF SECTION 075216
PV
± 313'-0"± 53'-71 2"
'-1 0"
'-6
'-5 1 2"
'-9
± 34'-7"
± 47'-51 2"
± 6'-2"
± 55'-41 2" ± 86'-2" ± 12'-4" ± 158'-41
2"
± 212'-11"
'-6
'-9
± 35'-6"
± 14'-8"
'-1
PV PV PV
PV PV
PV
PV
PV
PV
PVPV
PV
PV
PV
PV
PV
PV
PV
PV
PV
PV
PV
PV
PV
PVPV
PV PV
PV PV
PVPVPVPV
PV
PV
PV
PV
PV
PV PV
PV
PV PV
PV
PV
PV
OF OF
OF OF
RDRD
RD RD
EV
VC
HAT
EV
EV
VC
VC
HAT
EV
PV
PVDS
DS
DS
DS
DS
DS
DS
DS
DSDSDSDS
DS DS DS DS DS DS DS DS
DS
DS
DS
DSDSDSDSDSDS
DS
DS
DSDS
DSDS
DS
DSDS
DS DS
DS
EJ
EJ
DS
ROOF "B"
ROOF "B"
ROOF "B"ROOF "A"
ROOF "A"
ROOF "A"
EJ
ROOF "C"
ROOF "D"
ROOF "E"
R O
O F
"G
ROOF "H"
ROOF "J"
R O
O F
"F
ROOF "K" ROOF "L"
ROOF "M"
ROOF "N"
ROOF "P"
ROOF "Q"
SCUPSCUP
EVEV
EV
HS
HS
HS
SP
SP
SP
SP
EV EV
PV
LAD
E
A.2
E A.2
E A.2
J A.2
E A.2
E A.2
E A.2
E A.2E
A.2 E
A.2
E A.2
A.2
F A.2
E A.2
E A.2
E A.2
E A.2
F A.2
E & J A.2
H A.2
H A.2
PV
E A.2
F A.2
F A.2
ROOF "D"
E A.2
F A.2
F A.2
P A.3
F A.2
F A.2
F A.2
J A.2
L A.2
F A.2
F A.2
F & J A.2
F & J A.2
P A.3
P A.3
R O
O F
"N
OF
RD RD OF
EV EV
RTU E
A.?
P A.3
P A.3
P A.3
K A.2
K A.2
H A.2J
A.2
F A.2
L A.2
L A.2
F A.2
J A.2
GAS GAS GAS GAS GAS GAS GAS GAS
G
AS
GAS GAS GAS GAS GAS GAS GAS
G
AS
GAS GAS GAS GAS GAS GAS GAS
G
AS
G
AS
GAS
SP SP
SP
SP
SP
SP
SP
SP
G
AS
GAS GAS GAS GAS
PP
L A.2
A.1
Q A.3
Q A.3
Q A.3
U A.3
U A.3
T A.3
± 3 1'-
7"± 31'-7"
'-8
4 4
E & J A.2
E & J A.2
G
AS
G
AS
PP
PP
EXISTING ROOF DECK
EXISTING ROOF
SYSTEM
PERLITE COVER
BOARD (R-1.3)
2-PLY MODIFIED BITUMEN
ROOF MEMBRANE
KEYED ROOF PLAN NOTES:
- REMOVE AREAS OF MOISTURE (± 30 FT2) IN THE
EXISTING ROOF & REPLACE w/ LIKE MATERIALS
BEFORE INSTALLATION OF ROOF OVER LAY
SYSTEM
- H.V.A.C. PLATFORMS ON SURFACE MOUNTED LEGS;
RAISE LEGS INDIVIDUALLY FOR INSTALLATION OF
OVERLAY ROOF SYSTEM; PROVIDE NEW SLIP
SHEET UNDER EACH LEG
- ALTERNATE #1 - PROVIDE & INSTALL ONLY THE
STRUCTURAL SUPPORTS FOR NEW FLAG SUPPORT
FRAME; THROUGH THE EXISTING ROOF TO ROOF
DECK & STRUCTURE; REFER Y/A.3 & TO
STRUCTURAL DRAWINGS
ALTERNATE #2 - METAL FLAG SUPPORT FAME; TO
BE ATTACHED TO NEW STRUCTURAL SUPPORTS
- PROVIDE PRE-FINISHED METAL WATER KICK-OUT
FLASHING IN THIS LOCATION @ SIDING OVER
GUTTER
- PROVIDE NEW WALK PADS AS SHOWN IN PLAN;
ADHERE TO CAP SHEET
- LIQUID APPLIED FLASHING AROUND LADDER
SUPPORT FEET; REFER TO X/A.3
- PAINT ALL EXISTING GAS LINES; RE-USE ALL
EXISTING SUPPORT BLOCKS; PROVIDE SLIP
SHEETS UNDER ALL SUPPORT BLOCKS
- PROVIDE DOWNSPOUT EXTENSION TO LOWER
GUTTER; DO NOT ATTACH TO ROOF, SECURE @
ENDS
- PROVIDE EXPANSION JOINT IN GUTTERS @
EXPANSION JOINTS IN ROOF
- REFER TO D1/A.4 FOR VERTICAL FLASHING DETAIL
@ PARAPET HEIGHT CHANGE
P A.3
P A.3
P A.3
P A.3
P A.3
P A.3
P A.3
P A.3
P A.3
DS
DS
DS DS
GUTTER
GUTTER
G U
TT
ER
G U
TT
ER
G U
TT
ER
G U
TT
ER
GUTTER
GUTTERGUTTER
G U
TT
ER
G U
TT
ER
G U
TT
ER
G U
TT
ER
G U
TT
ER
GUTTER
HIP
HIP
HIP
HIP
HIP
HIP
HIP
HIPVALLEYVALL
EY
R
ID
G E
R
ID
G E
HIP
HIP
'-5
4"
'-1
1 4"
'-0 1 4"
'-7
35'-53 4"
'-5
4"
14'-715 16"
DS
RIDGE
HIP
HIP
VALLEY
VALLEYVALL
EY
VALL
EY
Q A.3
Q A.3
Q A.3
Q A.3
Q A.3
Q A.3
Q A.3
Q A.3
S A.3
P A.3
P A.3Q
A.3 Q
A.3
R A.3
R A.3
R A.3
ROOF "N"
ROOF "N"
ROOF "N"
R A.3
T A.3
T A.3
4:12 4:124:124:12
4:12 4:12
4:12
4:124:12
4:
4:
4:
4:
4:
4:
4:
12 4:
P A.3
P A.3
P A.3
RTA DATE
DECA LOG #
A&E FILE NO.
CHECKED BY
DRAWN BY
DRAWING DATE
DRAWING INFORMATION
DRAWING NO.
AS BUILT DATE
PHASE
DATEDESCRIPTION OF REVISIONS
REVISION HISTORY OF THIS DRAWING
DATEDESCRIPTION OF REVISIONS
FRANKFORT, KENTUCKY
DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION
DEPARTMENT FOR FACILITIES & SUPPORT SERVICES
FINANCE AND ADMINISTRATION CABINET
COMMONWEALTH OF KENTUCKY
PATRICK D. MURPHY CO., INC.
ARCHITECTS
P.O. BOX 20835
LOUISVILLE, KENTUCKY 40250
ACCOUNT NO.
EASTERN KENTUCKY VETERANS CENTER24-732-22
08-26-2025
09-29-2025
RBSII
JPG
R.T.A.
074-CBNJ-EK16-00
A.1
ROOF PLAN & DETAILS
K.V.A. - REPLACE ROOF EASTERN KENTUCKY VETERANS CENTER
200 VETERANS DR., HAZARD, KY 41701
SCALE: 1/16" = 1'-0"
ROOF PLAN1
EXISTING ROOF COMPOSITION
ROOF AREA DECK EXISTING CORE
A ± 15,480 ft2 METAL (SLOPED) 2-PLY MOD-BIT ON 3 4" COVER BOARD OVER RIGID INSULATION ON 5 8" GYP.
B ± 23,211 ft2 METAL (SLOPED) 2-PLY MOD-BIT ON 3 4" COVER BOARD OVER RIGID INSULATION ON 5 8" GYP.
C ± 4,572 ft2 METAL (SLOPED) 2-PLY MOD-BIT ON 3 4" COVER BOARD OVER RIGID INSULATION ON 5 8" GYP.
D ± 2,475 ft2 METAL (SLOPED) 2-PLY MOD-BIT ON 3 4" COVER BOARD OVER RIGID INSULATION ON 5 8" GYP.
E ± 663 ft2 METAL (SLOPED) 2-PLY MOD-BIT ON 3 4" COVER BOARD OVER RIGID INSULATION ON 5 8" GYP.
F ± 837 ft2 METAL 2-PLY MOD-BIT ON 3 4" COVER BOARD OVER TAPERED RIGID INSULATION
ON 5 8" GYP.
G ± 762 ft2 METAL (SLOPED) 2-PLY MOD-BIT ON 3 4" COVER BOARD OVER RIGID INSULATION ON 5 8" GYP.
H ± 663 ft2 METAL / WOOD
2-PLY MOD-BIT ON 3 4" COVER BOARD OVER TAPERED RIGID INSULATION
ON 5 8" GYP.; ASPHALT SHINGLES OVER FELT
J ± 917 ft2 WOOD (SLOPED) ASPHALT SHINGLES OVER FELT
K ± 314 ft2 METAL (SLOPED) 2-PLY MOD-BIT ON 3 4" COVER BOARD OVER RIGID INSULATION ON 5 8" GYP.
L ± 270 ft2 METAL (SLOPED) 2-PLY MOD-BIT ON 3 4" COVER BOARD OVER RIGID INSULATION ON 5 8" GYP.
M ± 69 ft2 METAL 2-PLY MOD-BIT ON 3 4" COVER BOARD OVER TAPERED RIGID INSULATION
N ± 2,384 ft2 WOOD (SLOPED) ASPHALT SHINGLES OVER FELT
P ± 33 ft2 METAL (SLOPED) 2-PLY MOD-BIT ON 3 4" COVER BOARD OVER TAPERED RIGID INSULATION
Q ± 33 ft2 METAL (SLOPED) 2-PLY MOD-BIT ON 3 4" COVER BOARD OVER TAPERED RIGID INSULATION
GENERAL ROOF NOTES
1. INSTALL NEW METAL COMPONENTS AT HEAT STACKS, A/C
PENETRATIONS, EXHAUST FANS, ETC.; ALL PIPING, DUCTWORK, LINES,
ELECTRICAL, ETC. THRU THE ROOF SHALL BE RAISED TO 8" (MIN.) ABOVE
THE NEW ROOF INSULATION
2. ROOF INSTALLATION HOURS ARE APPROXIMATELY 7:00 AM - 5:00 PM,
M-F.; THIS WILL BE COVERED AT THE PRE-BID CONFERENCE.
3. STAGING & STORAGE AREAS TO BE DISCUSSED AT THE PRE-BID
CONFERENCE.
4. CONTRACTOR TO COORDINATE w/ OWNER REGARDING DISCONNECT/
RECONNECT OF MECHANICAL WORK.
5. PROVIDE NEW JACKS & COLLARS AT ALL HEAT & VENT STACKS.
6. PROVIDE NEW PIPE SUPPORTS FOR ALL CONDENSATE LINES FROM ALL
R.T.U.
7. PROVIDE NEW METAL SPLASH PANS @ ALL DOWNSPOUTS THAT EMPTY
TO A ROOF; PROVIDE NEW CONCRETE SPLASH BLOCKS @
DOWNSPOUTS WITHOUT THAT EMPTY TO GRADE
DRAWING KEY
PV PLUMBING VENT; REFER TO N/A.2
SCUP EXISTING DRAINAGE SCUPPER; REFER TO G/A.2
EV EXHAUST VENT; REFER TO B/A.2
HAT ROOD ACCESS HATCH; REFER TO D/A.2
DS DOWNSPOUT LOCATION
HS HEAT STACK; REFER TO C/A.2
VC VENTILATION CURB; REFER TO B/A.2
SP
STRUCTURAL PENETRATION; REFER TO G1/A.4
(ALT #1: M/A.2)
RD ROOF DRAIN; REFER TO V/A.3
PP PIPE PENETRATION; REFER TO W/A.3
OF DRAIN OVERFLOW; REFER TO V/A.3
EJ EXPANSION JOINT; REFER TO H/A.2
RTU ROOFTOP MECHANICAL CURB; REFER TO Q/A.3
SCALE: 3" = 1'-0"
TYP. NEW LOW SLOPE ASSEMBLYA
SCALE: 1/8" = 1'-0"
ENTRY ROOF PLAN2
1 ADD #4: ROOF PLAN NOTES
12-04-25
AutoCAD SHX Text
8" M
IN
. H
T.
EXISTING EQUIPMENT; REMOVE & STORE IN A SAFE
& SECURE LOCATION WHILE ROOFING; RE-SET &
RE-SECURE; CONTRACTOR RESPONSIBLE FOR
TEMPORARY WATERTIGHTING OPEN AREA, SAFETY
COMPLIANCE, DISCONNECT / RECONNECT OF UNIT,
DUCT / ELECTRICAL EXTENSIONS, ETC.
FOIL FACED FLASHING
NEW 2-PLY MOD-BIT
ROOF MEMBRANE
INSTALL NEW STAINLESS
STEEP FASTENERS
THROUGHOUT
CANT STRIP
(CONTINUOUS)
EXISTING CURB
TO REMAIN
ADD WOOD BLOCKING
AS NEEDED FOR MIN.
HEIGHT
EXISTING ROOF DECK
EXISTING ROOF
SYSTEM
PRE-FINISHED METAL
WATERTIGHT COLLAR
OVERLAPPING JACK (SET
IN SEALANT); 24 ga. MIN.
STAINLESS STEEL
CLAMP & BAND
HIGH TEMPERATURE
SEALANT
8" M
.I.
N
.PRE-FINISHED METAL JACK;
VERIFY STACK SIZES
EXISTING HEAT
STACK
JACK FLANGE; PRIME
& SET IN MASTIC
BASE SHEET
FLASHING
SEALANT
EXISTING ROOF DECK
EXISTING ROOF
SYSTEM
EXISTING ROOF DECK
EXISTING ROOF
SYSTEM
NEW 2-PLY MOD-BIT
ROOF SYSTEM ON
COVER BOARD
FOIL FACED
FLASHING
MODIFIED
BASE SHEET
NEW METAL ROOF
HATCH & CURB
WOOD BLOCKING UNDER
HATCH LIP TO SECURE
TOP OF FLASHING
FASTEN BLOCKING
UNDER FLANGE
THROUGH INSIDE
NEW CANT STRIP;
CONTINUOUS
NEW 2-PLY MOD-BIT
ROOF SYSTEM ON
COVER BOARD
EXISTING METAL DECK EXISTING BLOCKING
TO REMAIN
EXISTING ROOF
SYSTEM
PRE-FINISHED METAL
COUNTER FLASHING
TERMINATION BAR w/
SEALANT @ TOP (CONT.)
2-PLY MOD-BIT
MEMBRANE ON
COVERBOARD
FOIL FACED
FLASHING
BASE SHEET
FLASHING
EXISTING ROOF
SYSTEM
EXISTING METAL DECK
EXISTING PRE-FINISHED
METAL COPING TO
REMAIN
8" M
IN
EXISTING ROOF
SYSTEM
2-PLY MOD-BIT MEMBRANE
ON COVER BOARD
REMOVE EXISTING ROOF FROM TOP
EXTERIOR WALL & PROVIDE WOOD
BLOCKING
PRE-FINISHED DRIP EDGE @
GUTTER (CONTINUOUS)
PRE-FINISHED METAL
SPACERS @ 3'-0" O.C.
NEW 6"x6" PRE-FINISHED BOX
GUTTER; PROVIDE SELF
ADHERED E.P.D.M. @ ALL JOINTS
PRE-FINISHED 14" x 11 2"
UNDER STRAP HANGERS
@ 3'-0" O.C.
3"x4" PRE-FINISHED DOWNSPOUT;
MATCH EXISTING LOCATIONS;
CONNECT TO EXISTING HUBS;
WATER TEST HUBS
NEW PRE-FINISHED METAL
FASCIA w/ DRIP & WIND
CLEAT @ BOTTOM
SEALANT (CONTINUOUS)
STRIP IN EDGE
METAL w/ BASE
SHEET FLASHING
NOTE:
PROVIDE SELF ADHERED E.P.D.M.
STRIPS ON INTERIOR OF ALL GUTTER
MATERIAL LAP JOINTS.
8" M
IN
PRE-FINISHED METAL
COUNTER FLASHING
TERMINATION BAR w/
SEALANT @ TOP (CONT.)
2-PLY MOD-BIT
MEMBRANE ON
COVERBOARD
FOIL FACED
FLASHING
BASE SHEET
FLASHING
EXISTING PRE-FINISHED
METAL FLASHING TO
REMAIN
EXISTING E.F.I.S.
EXISTING ROOF
SYSTEM
EXISTING METAL DECK
E E+1"
E
SLOPE
FOIL FACED
FLASHING
2-PLY MOD-BIT
MEMBRANE ON
COVERBOARD
BASE SHEET
FLASHING
CANT STRIP
DRIVE CLEAT @ ALL
MATERIAL JOINTS
4" 1
2" 3 4"
DRIVE CLEAT
SECTION
.060 E.P.D.M. INSULATION
RETAINER; ANCHOR TO TOP
EDGE OF CURBS @ 9" O.C. & FILL
w/COMPRESSIBLE INSULATION
NEW 2x12 EXPANSION
JOINT BLOCKING
PRE-FINISHED METAL EXPANSION JOINT
COVER (FASTENERS w/NEOPRENE
WASHERS @ 18" O.C. BOTH SIDES)
EXTEND ROOF MEMBRANE &
FLASHING OVER BLOCKING
EXISTING METAL DECK EXISTING METAL DECK
EXISTING ROOF
SYSTEM
EXISTING ROOF
SYSTEM
A.4
EXISTING ROOF DECK
FOIL FACED
FLASHING
2-PLY MOD-BIT
MEMBRANE ON
COVERBOARD
EXISTING SCUPPER SLEEVE TO REMAIN;
PAINT INTERIOR OF SCUPPER SLEEVE (2
COATS) COLOR TO MATCH EXISTING
EXTEND FOIL
FACED FLASHING
UP WALL
EXISTING ROOF
SYSTEM
EXISTING METAL WATER
HEAD; PAINT INTERIOR OF
COLLECTOR BOX (2
COATS) COLOR TO MATCH
EXISTING
EXISTING METAL DECK
3"
3"
PRE-FINISHED
METAL EDGE
EXTEND BASE SHEET
OVER SHINGLES
ICE & WATER SHIELD @
SHINGLE AREA PERIMETER
NEW ASPHALT
SHINGLES
EXISTING VENTED
DECK OVER METAL
DECK
EXISTING BLOCKING
TO REMAIN
2-PLY MOD-BIT
MEMBRANE ON
COVERBOARD
EXISTING ROOF
SYSTEM
MOD-BIT BASE SHEET
FLASHING STRIP
NEW BLOCKING
@ EDGE SEALANT
(CONTINUOUS)
1"
REMOVE EXISTING ROOF FROM TOP
EXTERIOR WALL & PROVIDE NEW
WOOD BLOCKING OVER EXISTING
PRE-FINISHED DRIP
EDGE w/ CONTINUOUS
WIND CLEAT
SEALANT (CONTINUOUS)
STRIP IN EDGE METAL w/
BASE SHEET FLASHING
EXISTING BLOCKING
TO REMAIN
EXISTING ROOF
SYSTEM
2-PLY MOD-BIT MEMBRANE
ON COVER BOARD
EXISTING METAL DECK
EXISTING E.F.I.S.
NEW STRUCTURAL
SUPPORT; REFER TO
STRUCTURAL
8"
EXTEND BASE SHEET
FLASHING UP SUPPORT
LIQUID APPLIED
FLASHING
RIGID INSULATION
FILL
RIGID INSULATION
FILL
NEW 5 8" G.W.B. TO MATCH
EXISTING; ATTACH TO
METAL ROOF DECK
PROVIDE BLOCKING
@ UNSUPPORTED
DECK EDGES
REFER TO STRUCTURAL
FOR ATTACHMENT
1'-0"
2-PLY MOD-BIT MEMBRANE
ON COVER BOARD
4' ' M
IN
IM
U M
FL
A
S H
IN
G
H E
IG
H
T
6'' (MIN.)
EXISTING
PLUMBING
VENT STACK
CONTINUOUS SEALANT
@ PERIMETER OF PIPE;
MUST BE COMPATIBLE
w/ LIQUID FLASHING
REINFORCED LIQUID
APPLIED FLASHING
NEW 2-PLY MOD-BIT
ROOF MEMBRANE
ON COVER BOARD
8" M
IN
PROVIDE EXTENSION AS
NEEDED FOR MINIMUM
HEIGHT
CONTINUOUS SEALANT @
EXTENSION JOINT; COVER
w/ LIQUID FLASHING
EXISTING ROOF
ASSEMBLY
RTA DATE
DECA LOG #
A&E FILE NO.
CHECKED BY
DRAWN BY
DRAWING DATE
DRAWING INFORMATION
DRAWING NO.
AS BUILT DATE
PHASE
DATEDESCRIPTION OF REVISIONS
REVISION HISTORY OF THIS DRAWING
DATEDESCRIPTION OF REVISIONS
FRANKFORT, KENTUCKY
DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION
DEPARTMENT FOR FACILITIES & SUPPORT SERVICES
FINANCE AND ADMINISTRATION CABINET
COMMONWEALTH OF KENTUCKY
PATRICK D. MURPHY CO., INC.
ARCHITECTS
P.O. BOX 20835
LOUISVILLE, KENTUCKY 40250
ACCOUNT NO.
EASTERN KENTUCKY VETERANS CENTER24-732-22
08-26-2025
09-29-2025
RBSII
JPG
R.T.A.
074-CBNJ-EK16-00
A.2
DETAILS
K.V.A. - REPLACE ROOF EASTERN KENTUCKY VETERANS CENTER
200 VETERANS DR., HAZARD, KY 41701
SCALE: 3" = 1'-0"
TYP. EXHAST VENT / VENTILATION CURBB
SCALE: 3" = 1'-0"
TYP. HEAT STACKC
SCALE: 3" = 1'-0"
HATCH CURBD
SCALE: 3" = 1'-0"
TYP. PARAPETE
SCALE: 3" = 1'-0"
TYP. GUTTER EDGEF
SCALE: 3" = 1'-0"
ROOF @ E.F.I.S.J
SCALE: 3" = 1'-0"
TYP. EXPANSION JOINTH
SCALE: 3" = 1'-0"
DRAINAGE SCUPPERG
SCALE: 3" = 1'-0"
FLAT TO SHINGLE TRANSITIONK
SCALE: 3" = 1'-0"
TYP. LOW-SLOPE PEAK / RAKEL
SCALE: 3" = 1'-0"
ALT. #1 - TYP. STRUCTURAL PENETRATIONM
NOT TO SCALE
TYP. PLUMBING VENTN
1 ADD #4: GUTTER NOTES 12-04-25
NAIL¾
MAX 12" O.C.
PRE-FINISHED METAL
GUTTER SPACERS
L- OR T-TYPE
DRIP EDGE
METAL
ASPHALT
SHINGLES
STARTER COURSE
w/ SEALING STRIP;
FASTENERS @ 3"
(MAX.) FROM
BOTTOM EDGE
3" MIN.
STRIPPING
PLY
4" (MAX.) OVERHANG @
L-TYPE METAL DRIP EDGE
PRE-FINISHED METAL
GUTTER & SUPPORTS
ICE & WATER
THROUGHOUT
NOTE:
PROVIDE SELF ADHERED E.P.D.M.
STRIPS ON INTERIOR OF ALL GUTTER
MATERIAL LAP JOINTS.
NAIL @ HIP SHINGLE
MUST PENETRATE ALL
LAYERS OF ROOFING
MATERIAL & DECK
ASPHALT
SHINGLES
ASPHALT
SHINGLES
ASPHALT HIP
SHINGLES
S
LO
P
E PRE-FINISHED METAL VALLEY
FLASHING; FABRICATE FROM
24'' (MIN.) WIDE SHEET; LAP
VALLEY METAL 8" (MIN.) & SET
IN SEALANT; HEMMED EDGES
TRIM CORNER OF
SHINGLES @ VALLEY
FLASHING
SEALANT INSIDE
VALLEY METAL HEM
(CONTINUOUS)
2" WIDE METAL CLIP; 2
FASTENERS / CLIP; @
12" O.C.
6" MIN.
ASPHALT
SHINGLES
ASPHALT
SHINGLES
ICE & WATER STRIP
@ EDGE OF VALLEY
FLASHING (BOTH
SIDES; CONTINUOUS)
ICE & WATER SHIELD
THROUGHOUT
CONTINUOUS
RIDGE VENT
EXISTING
ROOF DECK
SEALING
STRIPS
NEW UNDERLAYMENT
THOUGHOUT
NEW ICE & WATER
MEMBRANE: @
PERIMETER
ASPHALT
SHINGLES
6" M
IN
EXISTING PRE-FINISHED
METAL FLASHING TO
REMAIN
EXISTING E.F.I.S.
EXISTING VENTED
ROOF DECK
NEW ASPHALT SHINGLES
(THROUGHOUT)
NEW ICE & WATER
MEMBRANE @ PERIMETERS
PRE-FINISHED
METAL STEP
FLASHINGS
3"
MIN.
10"
MIN.
6"
MIN.
2-PLY MOD-BIT
MEMBRANE ON
COVER BOARD
FOIL FACED
FLASHING
EXISTING ROOF
SYSTEM
EXISTING VENTED
DECK OVER METAL
DECK
ICE & WATER
SHIELD @ SHINGLE
AREA PERIMETER
NEW ASPHALT
SHINGLES
BASE SHEET FLASHING;
EXTEND 18" UP SHINGLE
SLOPE
PROVIDE CONTINUOUS
TERMINATION BAR w/
SEALANT
4"4"
MODIFIED
BASE SHEET
FLASHING AROUND
INSERT DRAIN
FLANGE
NEW STRAINER &
CLAMPING RING
INSERT DRAIN
FLANGE
MODIFIED
CAP SHEET
PLAN VIEW
NEW 2-PLY MODIFIED
BITUMEN ROOF SYSTEM
ON COVER BOARD
SLOPE ROOF TOWARD DRAIN
@ 18:12 TO WALL (MIN.)
MODIFIED CAP
SHEET
NEW INSERT DRAINS
& STRAINERS
LIQUID APPLIED
FLASHING
LIQUID APPLIED
FLASHING
EXISTING ROOF DECK
EXISTING ROOF
SYSTEM
VARIES
4" M
IN
4"
MIN.
EXISTING
PENETRATION
NEW LIQUID APPLIED
FLASHING SYSTEM
NEW MODIFIED
ROOF SYSTEM
COVER BOARD
ON TAPERED
INSULATION
EXISTING ROOF
SYSTEM
EXISTING ROOF
SYSTEM
EXISTING METAL DECK EXISTING METAL DECK
NEW OVERLAY ROOF SYSTEM
(REFER TO A/A.1)
TYP. EXISTING ROOF SYSTEM:
- 2-PLY MOD-BIT MEMBRANE
- 3 4" COVER BOARD
- RIGID INSULATION
- 5 8" GYPSUM BOARD
- METAL DECK
EXISTING BAR JOISTS
EXISTING 5 8" GYPSUM BOARD ON 7 8"
METAL FURRING @ 24" O.C.; REPAIR
AFTER WORK
NOTE:
ALL STRUCTURAL WORK TO BE DONE
FOR ALTERNATE #1 OR ALTERNATE #2
WILL REQUIRE PENETRATION OF
EXISTING U.L. RATED 1-HOUR FIRE
RATED ASSEMBLY (U.L DESIGN #P519) @
THE ROOF STRUCTURE. THIS ASSEMBLY
IS TO BE RESTORED & MAINTAINED IN
ALL AREAS WHERE STRUCTURAL WORK
IS CONDUCTED
SOME AREAS HAVE A.C.T. FINISHED
CEILINGS; REMOVE TILES & GRID AS
NEEDED; RE-INSTALL AFTER WORK
SOME AREAS HAVE SUSPENDED G.W.B.
FINISHED CEILINGS; REMOVE ONLY AS
NEEDED FOR WORK; REPAIR & REFINISH
TO MATCH ADJACENT CEILING AFTER
WORKVA
R
IE
S
PRE-FINISHED METAL
COUNTER FLASHING
TERMINATION BAR w/
SEALANT @ TOP (CONT.)
2-PLY MOD-BIT
MEMBRANE ON
COVER BOARD
FOIL FACED
FLASHING
BASE SHEET
FLASHING
EXISTING ROOF
SYSTEM
EXISTING PRE-FINISHED
METAL COPING TO
REMAIN
8" M
IN
EXISTING ROOF
SYSTEM
EXISTING SUPPORT
BLOCKING
4"
LIQUID APPLIED FLASHING
OVER EXISTING STAIR
BLOCKING
EXISTING METAL DECK
EXTEND LIQUID
APPLIED FLASHING
TO 1st STAIR
EXISTING METAL
STAIR
CANT STRIP
(CONTINUOUS)
MODIFIED BITUMEN
ROOF SYSTEM
PIPE/ CONDUIT
MODIFIED PROTECTION MAT;
ADHERE TO ROOF SURFACE
IN A FULL BED OF MODIFIED
CEMENT
RUBBER PIPE SUPPORT
w/ GALVANIZED CHANNEL;
DURA-BLOCK OR EQUAL.
MODIFIED BITUMEN
ROOF SYSTEM
2"
(MIN.)
SIDE VIEW
OVERHEAD VIEW
FRONT VIEW
2"
(MIN.)
GALVANIZED BRACKET; ALLOW
FOR FREE MOVEMENT OF PIPE
V.I.F.
V.
I.F
MODIFIED
CAP SHEET
NEW WALK PAD
UNDERNEATH
SPLASH PANS
WIDTH @ BACK =
4" GREATER THAN
DOWNSPOUT
4"
1"
MIN.
WIDTH @
FRONT= 18"
RIBS
30"
NOTE:
ALL SPLASH PANS TO BE
22ga. PRE-FINISHED METAL
RTA DATE
DECA LOG #
A&E FILE NO.
CHECKED BY
DRAWN BY
DRAWING DATE
DRAWING INFORMATION
DRAWING NO.
AS BUILT DATE
PHASE
DATEDESCRIPTION OF REVISIONS
REVISION HISTORY OF THIS DRAWING
DATEDESCRIPTION OF REVISIONS
FRANKFORT, KENTUCKY
DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION
DEPARTMENT FOR FACILITIES & SUPPORT SERVICES
FINANCE AND ADMINISTRATION CABINET
COMMONWEALTH OF KENTUCKY
PATRICK D. MURPHY CO., INC.
ARCHITECTS
P.O. BOX 20835
LOUISVILLE, KENTUCKY 40250
ACCOUNT NO.
EASTERN KENTUCKY VETERANS CENTER24-732-22
08-26-2025
09-29-2025
RBSII
JPG
R.T.A.
074-CBNJ-EK16-00
A.3
DETAILS
K.V.A. - REPLACE ROOF EASTERN KENTUCKY VETERANS CENTER
200 VETERANS DR., HAZARD, KY 41701
NOT TO SCALE
TYP. GUTTER @ SHINGLESP
NOT TO SCALE
TYP. HIPQ
NOT TO SCALE
TYP. VALLEYR
NOT TO SCALE
TYP. RIDGES
SCALE: 3" = 1'-0"
TYP. STEP FLASHINGT
SCALE: 3" = 1'-0"
SHINGLE TO LOW SLOPE TRANSITIONU
SCALE: 3" = 1'-0"
TYP. ROOF DRAIN/OVERFLOWV
SCALE: 3" = 1'-0"
TYP. PIPE PENETRATIONW
SCALE: 3" = 1'-0"
ALT #1 & #2: TYP. BUILDING ROOF STUCTUREY SCALE: 3" = 1'-0"
STAIR BASE @ ROOF 'A' (SIM. @ ROOF 'C')Z
SCALE: 3" = 1'-0"
SPLASH PANX
SCALE: 3" = 1'-0"
TYP. NEW CONDUIT/PIPE SUPPORTA1
1 ADD #4: GUTTER NOTES
12-04-25
AIR FLOW
AIR FLOW
NEW ASPHALT
SHINGLES
ICE & WATER SHIELD @
SHINGLE AREA PERIMETER
EXISTING VENTED
DECK OVER METAL
DECK
PROVIDE CONTINUOUS
WIND CLEAT
± 65
8" 1 12" THICK VENT MATERIAL;
CONTINUOUS
EXISTING E.F.I.S.
TO REMAIN
EXISTING EMBEDED FLASHING TO REMAIN;
CUT FOR REMOVAL OF EXISTING FLASHINGS
PRE-FINISHED METAL
HEAD WALL FLASHING
2" MIN.
PRE-FINISHED METAL
COUNTER FLASHING
TERMINATION BAR w/
SEALANT @ TOP (CONT.)
2-PLY MOD-BIT
MEMBRANE ON
COVER BOARD
FOIL FACED
FLASHING
BASE SHEET
FLASHING
8" M
IN
EXISTING ROOF
SYSTEM
EXISTING
BLOCKING
TO REMAIN
NEW CANT STRIP
(CONTINUOUS)
EXISTING ROOF DECK
EXISTING METAL PANEL
SILL TO REMAIN
EXISTING METAL
WALL PANELS
8"
8"
8" 8"
6"
8"
6"
VA
R
IE
S
MOD. CAP SHEET
MOD. BASE SHEET
6"
MIN.
6"
MIN.
" M
IN
NEW…