Addendum No. 4.pdf
PDF 44 MB Posted
- Attached to
- RFB-45-26 Parks Lake Barkley Lodge Renovations
- Solicitation number
- RFB-785-2600000071-9
- Issued by
- Spencer County, Kentucky
About this file
This document is an Addendum (No. 4) issued by the Commonwealth of Kentucky Department for Facilities and Support Services, Division of Engineering and Contract Administration for the Lake Barkley Lodge Repairs and Renovations project. The project is divided into four volumes: Volume A focuses on Structural Repairs for Guest Wing Buildings and Walkways, Volume B involves Demolition and Construction of a New Pool, Volume C addresses Accommodations and Hospitality Upgrades, and Volume D covers the Lodge Main Building Roof Replacement. The addendum, dated September 2, 2025, provides clarifications, revisions, and responses to bidder questions across various technical and design aspects of the renovation, including finish schedules, tile selections, stair finishes, and door hardware specifications.
The addendum includes detailed modifications to architectural drawings, civil engineering plans, and structural details, specifically addressing drainage plans, roof designs, conduit routing, and construction methodologies. Key technical clarifications include confirming floor and wall tile selections, specifying commercial service rating classifications for ceramic tiling, and resolving discrepancies in room finish schedules. The document provides precise instructions for contractors regarding material selections, installation methods, and design intent, ensuring consistency and clarity in the renovation project's execution. Additional notes address specific technical requirements such as subfloor preparations, cleaning equipment specifications, and integration of electrical and mechanical systems within the renovation scope.
View the file
Other files
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
COMMONWEALTH OF KENTUCKY
DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES
DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION
INVITATION TO BID NO: RFB-45-26
FOR: Lake Barkley Lodge Repairs and Renovations Volume A - Structural Repairs Guest Wing Buildings & Walkways Volume B - Demo and Construct New Pool Volume C - Accomodations and Hospitality Upgrades Volume D - Lodge - Main Building Roof Replacement
DATE: September 2, 2025
RFB-785-2600000071
ADDENDUM NO. Four (4)
BIDDER SHALL CONFORM TO THE FOLLOWING CHANGES AS SAME SHALL BECOME BINDING
UPON THE CONTRACT TO BE ISSUED IN RESPONSE TO THIS INVITATION TO BID.
Item 1: Refer to addendum to be distributed by Lynn Imaging for all additions, deletions, and/or changes to specifications and/or drawings.
END OF ADDENDUM
Invitation to Bid No. RFB-45-26 For: Lake Barkley Lodge Repairs and Renovations Volume A - Structural Repairs Guest Wing Buildings & Walkways Volume B - Demo and Construct New Pool Volume C - Accomodations and Hospitality Upgrades Volume D - Lodge - Main Building Roof Replacement
Kristi Sharp, Statewide Procurement Manager Division of Engineering and Contract Administration
_Addendum 4- written summary.docx
COMMONWEALTH OF KENTUCKY
DEPARTMENT FOR FACILITIES + SUPPORT SERVICES
DIVISION OF ENGINEERING + CONTRACT ADMINISTRATION
INVITATION TO BID NO: RFB-45-26 DATE: Sept 2, 2025
FOR: Lake Barkley Lodge Repairs + Renovations
Volume A – Structural Repair Guest Wing Buildings + Walkways
Volume B – Demo + Construct New Pool
Volume C – Accommodations + Hospitality Upgrades
Volume D – Lodge – Main Building Roof Replacement RFB-785-2600000071
ADDENDUM NO. 4
This Addendum is incorporated into the Proposal Documents and will become part of the Contract
Documents for the successful bidder(s).
DRAWINGS:
Item #1: Sheet A-A2.3
• Model view 5/A-A2.3 has been added to show the path of the conduit.
• Section 1/A-A2.2 and Section 2/A-A2.2 have been updated to show the correct conduit path.
Item #2: Sheet A-G0.3 and A-A1.0
• A portion of the deck floor has been changed from new to existing to remain.
• Demo sheets 2/A-G0.2 and 7/A-D1.0 have also been changed.
• Detail 5/A-A5.0 has been updated.
Item #3: Sheet A-A1.2 and A-A1.3
• The new roof plan on 4/A-A1.3 has been corrected to show the walkway roof stopping 2” before column cluster W-1.
• Detail 1/A-A1.2 has been corrected to show the correct walkway roof design.
• The RCP on 3/A-A1.2 has also been corrected.
• See Structural written summary- item #1
Item #4: Concrete Board Form Texture Question
• Question: Which board quality is required for Board Textured Finish Concrete Walls?
(No.1 Grade or Rough Grade)?
o Answer: The boards will originate as clear, No 1 grade Douglas Fir
(033000.2.1.D.1). The Contractor will sandblast the boards (o@-site) to open the grain (033000.2.1.D.1) to a level which will be established during the mockup process. Once approved, those boards roughened by the sandblast process are to be used
_Addendum 4- written summary.docx
Item #5: Drain Line Connection- Vol. A to B
• Question: New drainage line from Volume A Civil drawings does not align with
Volume B drain line. Is this intentional?
o Answer: refer to attached, updated Civil drawing and written summary
Item #6: A-A1.4
• Details have been updated to reflect the structural design and intention for the existing roof rafter. See structural drawings for more information.
Item #7: A-A2.3
• Elevation 2/A-A2.3 has been updated to show more of the scope of work in the area.
• Section 3/A-A2.3 has been added to show the relationship between Volume A work to Volume B work.
• Refer to attached, updated structural drawings and written summary.
Item #8: Handrail + Integrated Light
• Add the following manufacturers to Specification 055213 ‘Pipe and Tube Railings’ in order to meet State requirements re: competitive bidding and ensure the same rail + integrated light will occur throughout the project:
o Hollaender Manufacturing Company o Tuttle Aluminum + Bronze
See attached written summary and drawings for Civil (Element Design) and Structural responses (Brown Kubican Engineers)
END OF ADDENDUM
landscape architecture + civil engineering + planning 366 South Broadway 720 Applewood Road 1018 East Jefferson Street Lexington, Kentucky 40508 Murray, KY Louisville, KY 40206
859.389.6533 270.210.6644 www.element-site.com
September 2, 2025
Addendum #4
Lake Barkley Lodge – Structural Repairs, Volume A
Evan McDaniel, Project Manager – element design
Civil Clarifications / Revisions:
1. Sheet A-C2.0. Both planter terraces shall receive pine bark mulch.
2. Sheet A-C3.0. Revise drainage plan to delete JB-8 (east side) and JB -11 (west side). The pipes will continue to pool deck structures in Volume B. See drawings for more information.
3. Sheet A-C3.1. Revise west drainage plan to delete JB -11 and extend pipe PWL-7 to pool deck structure in Volume B plans.
4. Sheet A-C3.2 - Enlargement B: Delete JB -11 and extend pipe PWL-7 to pool deck structure in Volume B plans.
5. Sheet A-C3.3. Revise east drainage plan to delete JB-8 and extend pipe PEL-7 to pool deck structure in Volume B plans.
6. Sheet A-C3.4 – Enlargement G: Delete JB -8 and extend pipe PEL-7 to pool deck structure in Volume B plans.
7. Sheet A-C3.5 – Storm Profiles: Revise storm profiles to delete JB-8 (east side) and JB -11 (west side). The pipes will continue to pool deck structures in Volume B. See drawings for more information.
http://www.element-site.com/ www.brownkubican.com Page 1 | 1
LEXINGTON
546 E. Main Street, Ste 100
Lexington, KY 40508
(859) 543-0933 www.brownkubican.com
August 25, 2025
Re: Addendum 004 Lake Barkley Lodge – Structural Repairs Phase 3
Curtis, Please issue the following changes and clarifications to the structural drawings and specifications as part of Addendum No. 004. The addendum includes the following written descriptions
1. Sheets A-S2.11C & A-S4.10: The deck edge spanning parallel to existing grid ‘W1’, shown by the 1’-3 ¾” dimension on plan A/A-S2.11C, shall be terminated at the plan west edge of the column cluster. The new deck edge shall be 7 ¾” from grid ‘W1’ in the plan westward direction.
2. Sheets A-S3.2, A-S3.3, A-S3.4: Omit the sloping timber guard rail and steel pickets at the lower stair runs denoted by “TIMBER GUARD W/ STEEL PICKET INFILL CENTERED ABOUT PLANTER WALLS” in the following details: D/A-S3.2, A/A-S3.3, B/A-S3.3, B/A-S3.4, and E/A-S3.4.
If you have any questions, please do not hesitate to call.
Sincerely, Spencer E. Price www.brownkubican.com Page 1 | 2
August 25, 2025
Re: Addendum 004 Lake Barkley Lodge – Structural Repairs Phase 3
Curtis, Please issue the following changes and clarifications to the structural drawings and specifications as part of Addendum No. 004. The addendum includes the following written descriptions
1. Sheets A-S2.9C & A-S2.10C: Omit the two (2) concrete walls that are along existing gridline ‘W1’
(shown in the red ellipse below) that occur at the interface between ‘Volume A’ & ‘Volume B’ construction. The terraced retaining walls from ‘Volume A’ shall terminate into the side of the ‘Volume B’ storage or restroom concrete wall at the east and west wings respectively.
o Upon omission of the walls noted above. A new pier shall be added to support the spandrel beam along gridline ‘W1’. This pier shall be similar in construction to that which occurs at the end of the beam along gridline ‘W1.5’ (shown in the green ellipse below), and is also shown in details H/A- S4.13 & D/A-S3.4. Tag note 20, and the U-Bracket detailing noted therein shall apply atop the new pier at this location, see the details noted above.
A-S2.9C – LOWER LEVEL FOUNDATION PLAN – AREA C
2. Sheet A-S3.4: Omit the concrete walls along gridline ‘W1’ that occur in detail B/A-S3.4 & D/A-S3.4. A new pier shall be shown in detail D/A-S3.4, supporting the spandrel beam along gridline ‘W1’, similar to that which is shown at the end of the beam along gridline ‘W1.5’. The U-Bracket and related detailing shall also apply to support the spandrel beam atop this new pier.
www.brownkubican.com Page 2 | 2
If you have any questions, please do not hesitate to call.
Sincerely, Spencer E. Price
401 400 399400401
TOP OF WALL = 399.5
BACK OF WALL = 398.83 (-8")
TOP OF WALL = 399.5
EXISTING TOP OF
WALL = ~398.3
TOP OF WALL = 399.5
BACK OF WALL = 399.0 (EXISTING)
TOP OF WALL = 399.5
BACK OF WALL = 399.25 (EXISTING)
TOP OF WALL = 399.5
BACK OF WALL = 398.83 (-8")
TOP OF WALL = 399.5
BACK OF WALL = 398.83 (-8")
TOP OF STEP = 401.5
BOTTOM OF STEP = 396.5
RIM = 398.5
TOP OF WALL = 399.5
BACK OF WALL = 398.83 (-8")
401.0
TOP OF WALL = 399.5
BACK OF WALL = 398.83 (-8")
TOP OF WALL = 398.0
401.5
HP 402.3
TRENCH DRAIN RIM
(EXISTING) = ~396.5
BACK OF WALL = 398.75
BACK OF WALL
= ~397.8
398.75
399.75
397.8
398.75 397.8
399.75
397.8
EXISTING TOP OF
WALL = ~398.3
RIM = 398.5
RIM = 396.25
RIM = 396.4
RIM = 398.5
EXISTING TRENCH
DRAIN RIM = ~396.4
EXISTING TOP OF
WALL = ~398.3
EXISTING TRENCH
DRAIN RIM = ~396.4
RIM = 398.5
RIM = 398.5
RIM = 398.5
RIM = 397.75
RIM = 397.75
RIM = 397.75
RIM = 397.75
RIM = 397.75
RIM = 397.75
RIM = 397.75
RIM = 397.75
RIM = 397.75
RIM = 397.80
RIM = 396.35
RIM = MATCH EXISTING
RIM = MATCH EXISTING
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D D
D
D
D
D
D
D
D
D
D
D
D
D
D
ACCOUNT NO.
785CA7UBH0600
DRAWING INFORMATION
CHECKED BY
DRAWN BY
DRAWING DATE
A&E FILE NO.
PHASE
RTA DATE
REVISION HISTORY OF THIS DRAWING
DATEDESCRIPTION OF THE REVISIONS DESCRIPTION OF THE REVISIONS DATE
DECA LOG #
AS BUILT DATE
DRAWING NO.
K. NORMAN BERRY ASSOCIATES ARCHITECTS, PLLC
815 WEST MARKET STREET, SUITE 502
LOUISVILLE, KENTUCKY 40202
PHONE: 502-582-2500
WEBSITE: WWW.KNBARCH.COM
C
RDM
EPM/AS
08/01/2025
Project Number
Structural Repairs + Renovation PH-3 Volume A
COMMONWEALTH OF KENTUCKY
FINANCE AND ADMINISTRATION CABINET
DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES
DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION
FRANKFORT, KENTUCKY
element design landscape architecture+civil engineering+planning
366 South Broadway Lexington, KY 40508
p. 859.389.6533
1018 E. Jefferson St Louisville, KY 40206
p. 502.489.4221
720 Applewood Road Murray, KY 42071
p. 270.210.6644
08/01/2025
A-C2.0
OVERALL SITE IMPROVEMENTS AND GRADING PLAN
SCALE: 1" = 30'
OVERALL SITE IMPROVEMENTS AND GRADING PLAN
15 60
TRUE NORTH
SITE IMPROVEMENTS KEYNOTES: #
1. FRENCH DRAIN BEHIND NEW RETAINING WALL. SEE DRAINAGE PLANS AND DETAIL SECTIONS ON A-C4.3
2. FRENCH DRAIN BEHIND EXISTING RETAINING WALL. EXCAVATE SOILS BEHIND RETAINING WALL TO INSTALL STORM PIPING PER THE DRAINAGE PLANS. ADJUST GRADES TO CREATE FRENCH DRAIN; SEE DETAIL
SECTIONS ON A-C4.3. BANK SLOPE AT MAX 2:1. PATCH CRACKS/HOLES ON BACK SIDE OF WALL WITH HYDRAULIC WATER-STOP CEMENT PRIOR TO APPLYING DAMPPROOFING. SEE STRUCTURAL PLANS FOR
MORE INFORMATION.
3. NEW RETAINING WALL. SEE STRUCTURAL PLANS.
4. EXISTING RETAINING WALL
5. REMOVE AND REPLACE RETAINING WALL SEGMENT TO INSTALL STORM PIPE. REINSTALL TO MATCH EXISTING HEIGHT AND LAYOUT. REFER TO STRUCTURAL PLANS AND DETAILS.
6. REPLACE CONCRETE WALK AFTER STORM PIPE INSTALLATION. ADD FLOOR DRAIN AND CONNECT TO STORM PIPE BELOW. SLOPE WALKWAY 2% MAX., 1% MIN. TO FLOOR DRAIN. REMOVE TRENCH DRAIN
SEGMENT WHERE WALKWAYS ABUT AND CONNECT REMAINING TRENCH DRAIN CHANNELS WITH 8" PVC PIPE; POUR NEW WALKWAY OVER PIPE.
7. ADD EROSION CONTROL MATTING TO SLOPE 15' MINIMUM FROM BACK EDGE OF FRENCH DRAIN STONE (COVER ALL EXPOSED SOIL). COVER EXPOSED SOILS IMMEDIATELY AFTER GRADING. SEED WITH
KENTUCKY 31 AND ANNUAL RYE.
8. SEE STRUCTURAL PLANS FOR CHEEKWALLS AT EXISTING CONCRETE STAIR .
9. NEW TRENCH DRAIN (REINSTALL EXISTING GRATES). SEE DRAINAGE PLANS AND SECTION DETAILS ON SHEET A-C4.3.
10. ADD 4' WIDE DECORATIVE RIVER STONE STRIP AROUND EXISTING BUILDING. REMOVE 4-6" OF EXISTING SOIL TO STAY BELOW EXISTING SIDING. ADJUST GRADE TO DRAIN AROUND BUILDING.
11. REPLACE WALK REPLACE CONCRETE WALK AFTER STORM PIPE INSTALLATION. SLOPE WALKWAY 2% MAX., 1% MIN. TO MIDDLE OF WALK AND ADD 2% CROSS SLOPE TO DRAIN INTO LANDSCAPE BED.
REMOVE TRENCH DRAIN SEGMENT WHERE WALKWAYS ABUT AND CONNECT REMAINING TRENCH DRAIN CHANNELS WITH 8" PVC PIPE; POUR NEW WALKWAY OVER PIPE.
12. TOP OF RIVER STONE IN LANDSCAPE BED TO BE 3" BELOW EDGE OF WALKWAYS.
13. GRADE ALONG BUILDING TO FOLLOW BOTTOM OF SIDING SLOPE. TOP OF STONE TO BE 6" BELOW SIDING.
14. HYDRO SEED HILL SIDE WITH IN LIMITS AFTER SITE WORK IS COMPLETED. DISTURBED SOILS SHALL BE MAINTAINED WITH SEED AND STRAW MATTING DURING CONSTRUCTION TO PREVENT EROSION; SEE ESCP
A-C1.0.
15. HEADWALL OUTLET. SEE DRAINAGE PLANS. CONTOURS SHOWN ON DRAINAGE PLAN WERE ADDED VIA LiDAR DATA. CONTRACTOR TO STAKE OUT HEADWALL LOCATION AND CONFIRM GRADES.
HEADWALLS TO BE LOCATED ADJACENT EXISTING HEADWALLS AND BLEND RIP-RAP WITH EXISTING DITCH. SEE DETAIL H/A-C4.1
16. PATCH CONCRETE WALKWAY AND CURB. SEE STRUCTURAL PLANS FOR TYPICAL CONCRETE PAVEMENT DETAIL. SEE DETAIL B/A-C4.2 FOR INTEGRAL CURB DETAIL.
17. PATCH ASPHALT PAVEMENT AFTER STORM PIPE INSTALLATION. SAW-CUT AND EDGE KEY PAVEMENT. RE-STRIPE AFFECTED PARKING SPACES. SEE DETAIL A/A-C4.2.
18. PATCH CURB AFTER PIPE INSTALLATION. MATCH EXISTING CURB TYPE. SEE DETAIL C/A-C4.2.
19. REMOVE RUST AND REPAINT BOLLARDS WITH EXTERIOR ACRYLIC PAINT - 3 COATS.
SITE LEGEND:
79.2
PROPOSED CONTOUR
PROPOSED SPOT ELEVATION
M.E. MATCH EXISTING
T.C. TOP OF CURB
B.C. BOTTOM OF CURB
H.P. HIGH POINT
FFE FINISH FLOOR ELEVATION
T.R. TOP OF RAMP
B.R. BOTTOM OF RAMP
T.W. TOP OF WALL
B.W. BOTTOM OF WALL (FINISHED GRADE)
EXISTING CONTOUR
SHEET FLOW DIRECTION
T.S. TOP STEP
B.S. BOTTOM STEP
GENERAL SITE NOTES:
A. THE EXISTING TOPOGRAPHIC AND SITE INFORMATION SHOWN HAS BEEN PROVIDED BY BFW ENGINEERS. THIS INFORMATION IS
PROVIDED FOR THE CONVENIENCE OF THE CONTRACTOR. THE ARCHITECT SHALL NOT BE RESPONSIBLE FOR THE ACCURACY OF THE INFORMATION SHOWN THEREON. CONTRACTOR TO VERIFY ALL INFORMATION SHOWN; THE CONTRACTOR SHALL BE RESPONSIBLE
FOR REPAIRING ANY DAMAGE TO UTILITIES SHOWN ON THE SURVEY.
B. SEE THE SURVEY AND SITE UTILITY PLANS FOR EXISTING AND PROPOSED UNDERGROUND INFRASTRUCTURE. THE CONTRACT DRAWINGS SHOW THE APPROXIMATE LOCATION OF EXISTING UTILITY LINES. THESE LINES HAVE BEEN IDENTIFIED AND LOCATED AS ACCURATELY AS POSSIBLE USING AVAILABLE INFORMATION. THE CONTRACTOR IS RESPONSIBLE FOR VERIFYING UTILITY LOCATIONS ON THE SURVEY WITH LOCATIONS IN THE FIELD, AND COORDINATING WITH UTILITY COMPANIES FOR DEMOLITION OF UTILITIES INDICATED.
C. PROTECT EXISTING TREES FROM POTENTIAL DAMAGE OF CONSTRUCTION OPERATIONS. STEEPEN GRADES UPHILL FROM EXISTING
TREES TO A MAX. OF 2:1 TO AVOID FILLING SOILS ONTO TRUNKS.
D. UNLESS OTHERWISE INDICATED TO BE REMOVED, ALL ITEMS REMAINING WITHIN THE LIMIT OF CONTRACT ARE TO REMAIN AND BE
PROTECTED FROM DAMAGE DURING CONSTRUCTION.
E. THE CONTRACTOR SHALL MAINTAIN STORM DRAINAGE SYSTEMS TO FUNCTION THROUGHOUT THE CONSTRUCTION PERIOD.
F. PROPOSED GRADES SHOWN ARE FINISHED GRADES.
G. LIMIT OF GRADING INCLUDES ALL AREAS DISTURBED BY ALL SITE UTILITY WORK, REFER TO SITE UTILITY DRAWINGS FOR LOCATIONS OF
PROPOSED SITE UTILITIES.
H. REFER TO SPECIFICATIONS / PROJECT MANUAL FOR ADDITIONAL REQUIREMENTS.
I. ADJUST RIM ELEVATIONS OF ALL EXISTING UTILITY STRUCTURES TO MATCH PROPOSED FINISHED GRADES.
J. ALL EXISTING LAWN AREAS DISTURBED BY CONSTRUCTION INCLUDING BUT NOT LIMITED TO GRADING & EARTHWORK AND SITE UTILITY WORK ARE TO RECEIVE SOD UNLESS OTHERWISE INDICATED. EXTEND LIMITS OF SOD TO INCLUDE ALL AREAS DISTURBED BY CONSTRUCTION. SEE SPECIFICATIONS 'LAWNS AND GRASSES' FOR FINE GRADING AND GRASS REQUIREMENTS.
K. PROVIDE EROSION CONTROL BLANKET FOR ALL SEEDED SLOPES 3:1 OR STEEPER. SEE 'EARTH MOVING' & 'TURF AND GRASSES'
SPECIFICATIONS FOR ADDITIONAL INFORMATION AND REQUIREMENTS.
L. FOR PROPOSED DRAINAGE STRUCTURES, INVERT ELEVATIONS ARE APPROXIMATE AND BASED ON INFORMATION PROVIDED FOR EXISTING DRAINAGE STRUCTURES AND GRADES. FIELD VERIFY ELEVATIONS PRIOR TO INSTALLATION OF STORM STRUCTURES AND
NOTIFY LANDSCAPE ARCHITECT OF ANY CONFLICTS.
M. FOR PROPOSED DRAINAGE PIPE, PIPE LENGTHS & SLOPES ARE APPROXIMATE & SHOULD BE ADJUSTED AS NECESSARY TO MEET
EXISTING AND PROPOSED STORM STRUCTURES.
N. GRADE ALL NEW PAVEMENTS TO DRAIN. GRADE ALL NEW WALKS AT MAX. 2% CROSS SLOPE. GRADE ALL NEW WALKS TO MAX. 5% LONGITUDINAL SLOPE UNLESS OTHERWISE SPECIFICALLY INDICATED ON PLANS TO BE A RAMP.
O. CONTRACTOR TO CONFIRM SPOT GRADES WHERE MATCHING EXISTING PAVEMENTS. NOTIFY LANDSCAPE ARCHITECT/CIVIL ENGINEER WITH ANY DISCREPANCIES, OR IF PROPOSED GRADES TO NOT ALIGN WITH DESIGN INTENT. SEE NOTE "N".
P. ALL DRAINAGE SWALES SHALL BE SODDED WITH MIN. 6' WIDE SOD FOR FULL LENGTH OF SWALE, Q. SEE MEP DRAWINGS FOR ADDITIONAL EARTHWORK ASSOCIATED WITH DEMOLITION AND CONSTRUCTION OF OTHER SITE UTILITIES.
R. THE CONTRACTOR SHALL REFER TO GEOTECHNICAL ENGINEER REQUIREMENTS FOR ALL EARTHWORK, FILL MATERIALS, AND SUBGRADE CONDITIONS. A QUALIFIED TESTING AGENCY SHALL SHALL SUPERVISE THAT SUBGRADE MEET SPECIFICATIONS AND GEOTECHNICAL ENGINEERING REQUIREMENTS. THE LANDSCAPE ARCHITECT/CIVIL ENGINEER IS NOT RESPONSIBLE FOR SUBGRADE CONDITIONS. SEE THE EARTH MOVING SPECIFICATIONS AND GEOTECHNICAL REPORT FOR MORE INFORMATION. PAVEMENT DESIGNS SHALL BE REVIEWED BY THE GEOTECHNICAL ENGINEER FOR FINAL APPROVAL BASED ON SITE AND SUBGRADE CONDITIONS BEFORE ANY SITE
MATERIALS ARE CONSTRUCTED.
D
BRIDGE / DECK OVERHEAD
DECORATIVE RIVER STONE:
4" LAYER OVER WEED FABRIC
PINE BARK MULCH:
3" LAYER OVER WEED FABRIC.
NEW TRENCH DRAIN (REUSED GRATES)
EXISTING TRENCH DRAIN TO REMAIN
STORM DRAINAGE MANHOLE
YARD INLET DRAINAGE STRUCTURE
FLOOR / TERRACE DRAIN
DOWN SPOUT BOOT
NEW RETAINING WALL SEE
STRUCTURAL PLANS
ROOF OVERHANG
PROPOSED HEADWALL OUTLET
SEE SCOPE B
SEE SCOPE B
FOR DRAINAGE CONTINUATION.
CONTRACTOR TO COORDINATE
DRAINAGE DESIGNS FROM EACH
DESIGN PACKAGE
SEE DRAINAGE PLANS
FOR LIDAR CONTOURS
SEE DRAINAGE PLANS
FOR LIDAR CONTOURS
COORDINATION NOTE:
SITE/CIVIL PLANS ARE BASED ON SURVEYED EXISTING CONDITIONS AND MAY VARY
SLIGHTLY FROM ARCHITECTURAL/STRUCTURAL PLANS. THESE CIVIL SITE PLANS COVER
SCOPE OF WORK RELATED TO REVISED GRADING, STORM DRAINAGE PIPING AND
STRUCTURES, LIMITED EARTHWORK, VEGETATION, AND EROSION CONTROL
PROCEDURES.
SEE STRUCTURAL PLANS FOR RETAINING WALLS, STAIRS, AND CONCRETE PAVEMENTS.
SEE SCOPE B PLANS FOR ADDITIONAL SITE IMPROVEMENTS. CONTRACTOR TO
COORDINATE STORM DRAINAGE CONTINUATION INTO SCOPE B LIMITS AT POOL
DECK.
CONTRACTOR TO COORDINATE ARMY CORPS. OF ENGINEERING PERMITS WITH
SCOPE B CONSULTANT.
ADDENDUM #3 8-22-25
ADDENDUM #4 8-27-25
AutoCAD SHX Text T
AutoCAD SHX Text P.
AutoCAD SHX Text
AutoCAD SHX Text
EVAN
AutoCAD SHX Text
MCDANIEL
AutoCAD SHX Text C
AutoCAD SHX Text A
AutoCAD SHX Text P
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text L
AutoCAD SHX Text S
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text D
AutoCAD SHX Text S
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text C
AutoCAD SHX Text H
AutoCAD SHX Text A
AutoCAD SHX Text R
AutoCAD SHX Text C
AutoCAD SHX Text K
AutoCAD SHX Text C
AutoCAD SHX Text T
AutoCAD SHX Text Y
AutoCAD SHX Text I
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text K
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text T
AutoCAD SHX Text U
AutoCAD SHX Text
400401
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D D
D
D
D
D
D
D
D
D
D
D
D
D
D
MATCHLINE B
MATCHLINE B
E-2
MATCHLINE H
MATCHLINE G
E-1
MATCHLINE H
E-1
MATCHLINE I
E-1
E-2
E-3
MATCHLINE J
E-2
E-3
E-3
E-3 E-2
E-1
MATCHLINE CW
-1
W -2
W -3
MATCHLINE C
MATCHLINE D
MATCHLINE D
MATCHLINE E
W -3W
-2
W -1
W -1
W -2
W -3
W-1
W-2
W-3
PEU-3
PEU-2
PEU-1
MATCHLINE A
PWU-12
PWU-4
PWU-6B
PWU-9
PWU-10
PWU-11
PWU-7
PWU-6A
PWU-3
PWU-2 PWU-1
MATCHLINE E
MATCHLINE F
MATCHLINE I
MATCHLINE J
MATCHLINE K
MATCHLINE K
MATCHLINE L
PWL-1
PWL-4
PWL-7
PEU-6A
PEU-6B
PEU-8
PEU-10
PEU-9
PEU-12
PEU-13
PEU-4
P E
L-
PWL-2
PWL-3
PWL-5
PWL-6
PEL-7
PEL-6
PEL-5
PEL-4
PEL-3
PEL-2
PEU-15
P
EU
-1
PWU-14
PWU-13
MH-3
STA: 1+42.06
N = 3476265.51 E = 4283072.08
YI-12
STA: 5+57.73
N = 3476549.80 E = 4282835.91
YI-13
STA: 5+02.11
N = 3476533.39 E = 4282888.69
YI-14
STA: 4+46.64
N = 3476506.00 E = 4282936.61
YI-15
STA: 3+70.44
N = 3476452.75 E = 4282990.48
YI-16
STA: 3+44.53
N = 3476431.26 E = 4283004.86
YI-18
STA: 2+98.40
N = 3476389.77 E = 4283024.77
MH-4
STA: 1+70.05
N = 3476263.51 E = 4283044.16
MH-2
STA: 0+52.61
N = 3476185.00 E = 4283111.06
MH-1
STA: 0+25.00
N = 3476175.03 E = 4283136.80
HW-1
STA: 0+00.00
N = 3476166.00 E = 4283160.12
YI-11
STA: 1+27.17
N = 3476465.39 E = 4282802.76
CO
STA: 0+74.06
N = 3476468.33 E = 4282855.79
YI-19
STA: 2+29.83
N = 3476323.11 E = 4283039.67
YI-20
STA: 2+05.26
N = 3476298.61 E = 4283041.52
FLOOR DRAIN-2
STA: 2+21.44
N = 3476314.76 E = 4283040.44
YI-17
STA: 3+24.47
N = 3476413.66 E = 4283014.43
JB-1
STA: 3+98.85
N = 3476291.98 E = 4283070.75
JB-8
STA: 0+00.38
N = 3476578.19 E = 4282840.80
JB-7
STA: 0+20.73
N = 3476573.77 E = 4282860.67
JB-6
STA: 0+64.87
N = 3476559.13 E = 4282902.34
JB-5
STA: 1+44.30
N = 3476517.03 E = 4282969.60
JB-4
STA: 2+37.70
N = 3476446.06 E = 4283029.89
JB-3
STA: 3+38.02
N = 3476352.51 E = 4283064.95
JB-2
STA: 3+86.63
N = 3476304.19 E = 4283070.18
MH-12
STA: 1+29.02
N = 3476225.41 E = 4282513.20
MH-11
STA: 1+57.01
N = 3476227.41 E = 4282541.12
YI-9
STA: 5+37.97
N = 3476538.64 E = 4282700.03
YI-3
STA: 2+65.20
N = 3476335.45 E = 4282538.39
YI-4
STA: 3+24.16
N = 3476392.51 E = 4282552.87
YI-6
STA: 3+74.41
N = 3476437.36 E = 4282575.40
YI-7
STA: 4+28.64
N = 3476479.80 E = 4282609.21
YI-8
STA: 4+83.53
N = 3476514.31 E = 4282651.70
JB-18
STA: 3+85.73
N = 3476267.10 E = 4282509.18
JB-11
STA: 0+00.00
N = 3476568.77 E = 4282699.10
MH-13
STA: 0+65.29
N = 3476177.00 E = 4282471.75
HW-2
STA: 0+00.44
N = 3476175.41 E = 4282406.92
MH-14
STA: 0+37.23
N = 3476176.31 E = 4282443.70
JB-17
STA: 3+73.00
N = 3476279.79 E = 4282508.17
JB-16
STA: 3+24.64
N = 3476328.07 E = 4282508.60
JB-15
STA: 2+35.73
N = 3476413.92 E = 4282530.31
JB-14
STA: 1+46.89
N = 3476488.32 E = 4282578.20
JB-12
STA: 0+06.37
N = 3476566.42 E = 4282693.18
JB-13
STA: 0+67.54
N = 3476539.66 E = 4282638.34
YI-10
STA: 1+26.60
N = 3476460.33 E = 4282731.27
CO
STA: 0+75.59
N = 3476456.32 E = 4282680.42
YI-2
STA: 2+13.60
N = 3476283.84 E = 4282536.80
FLOOR DRAIN 1
STA: 2+08.21
N = 3476278.47 E = 4282537.17
YI-1
STA: 1+92.80
N = 3476263.09 E = 4282538.37
PWU-5B
PWU-5A
PEU-5B
PEU-5A
YI-5
STA: 3+37.87
N = 3476405.16 E = 4282558.11
PWU-8
PEU-7
39539
38037
CO
CO
CO
CO
CO
CO
CO
CO
COCOCO
CO
CO
CO CO
CO
CO
CO
CO
CO
CO
CO CO
CO
CO
CO
CO
CO
CO
CO
CO
CO
CO
CO
CO
CO
CO
CO
CO
CO CO
CO CO
CO CO
CO
CO
CO
CO
CO
CO
CO
CO
CO
CO
CO
CO
CO
CO
ACCOUNT NO.
785CA7UBH0600
DRAWING INFORMATION
CHECKED BY
DRAWN BY
DRAWING DATE
A&E FILE NO.
PHASE
RTA DATE
REVISION HISTORY OF THIS DRAWING
DATEDESCRIPTION OF THE REVISIONS DESCRIPTION OF THE REVISIONS DATE
DECA LOG #
AS BUILT DATE
DRAWING NO.
K. NORMAN BERRY ASSOCIATES ARCHITECTS, PLLC
815 WEST MARKET STREET, SUITE 502
LOUISVILLE, KENTUCKY 40202
PHONE: 502-582-2500
WEBSITE: WWW.KNBARCH.COM
C
RDM
EPM/AS
08/01/2025
Project Number
Structural Repairs + Renovation PH-3 Volume A
COMMONWEALTH OF KENTUCKY
FINANCE AND ADMINISTRATION CABINET
DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES
DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION
FRANKFORT, KENTUCKY
element design landscape architecture+civil engineering+planning
366 South Broadway Lexington, KY 40508
p. 859.389.6533
1018 E. Jefferson St Louisville, KY 40206
p. 502.489.4221
720 Applewood Road Murray, KY 42071
p. 270.210.6644
08/01/2025
SITE DRAINAGE PLAN
SCALE: 1" = 30'
OVERALL SITE DRAINAGE PLAN
15 60
TRUE NORTH
WEST WING - C201 EAST WING - C202
M A
TC
HL
IN
E
EA
ST
W
IN
G
GENERAL DRAINGE NOTES:
A. THE EXISTING TOPOGRAPHIC AND SITE INFORMATION SHOWN HAS BEEN PROVIDED BY BFW ENGINEERS. THIS INFORMATION IS
PROVIDED FOR THE CONVENIENCE OF THE CONTRACTOR. THE ARCHITECT SHALL NOT BE RESPONSIBLE FOR THE ACCURACY OF THE INFORMATION SHOWN THEREON. CONTRACTOR TO VERIFY ALL INFORMATION SHOWN; THE CONTRACTOR SHALL BE RESPONSIBLE
FOR REPAIRING ANY DAMAGE TO UTILITIES SHOWN ON THE SURVEY.
B. SEE THE SURVEY AND SITE UTILITY PLANS FOR EXISTING AND PROPOSED UNDERGROUND INFRASTRUCTURE. THE CONTRACT DRAWINGS SHOW THE APPROXIMATE LOCATION OF EXISTING UTILITY LINES. THESE LINES HAVE BEEN IDENTIFIED AND LOCATED AS ACCURATELY AS POSSIBLE USING AVAILABLE INFORMATION. THE CONTRACTOR IS RESPONSIBLE FOR VERIFYING UTILITY LOCATIONS ON THE SURVEY WITH LOCATIONS IN THE FIELD, AND COORDINATING WITH UTILITY COMPANIES FOR DEMOLITION OF UTILITIES INDICATED.
C. PROTECT EXISTING TREES FROM POTENTIAL DAMAGE OF CONSTRUCTION OPERATIONS. STEEPEN GRADES UPHILL FROM EXISTING
TREES TO A MAX. OF 2:1 TO AVOID FILLING SOILS ONTO TRUNKS.
D. UNLESS OTHERWISE INDICATED TO BE REMOVED, ALL ITEMS REMAINING WITHIN THE LIMIT OF CONTRACT ARE TO REMAIN AND BE
PROTECTED FROM DAMAGE DURING CONSTRUCTION.
E. THE CONTRACTOR SHALL MAINTAIN STORM DRAINAGE SYSTEMS TO FUNCTION THROUGHOUT THE CONSTRUCTION PERIOD.
F. PROPOSED GRADES SHOWN ARE FINISHED GRADES.
G. LIMIT OF GRADING INCLUDES ALL AREAS DISTURBED BY ALL SITE UTILITY WORK, REFER TO SITE UTILITY DRAWINGS FOR LOCATIONS OF
PROPOSED SITE UTILITIES.
H. REFER TO SPECIFICATIONS / PROJECT MANUAL FOR ADDITIONAL REQUIREMENTS.
I. ADJUST RIM ELEVATIONS OF ALL EXISTING UTILITY STRUCTURES TO MATCH PROPOSED FINISHED GRADES.
J. ALL EXISTING LAWN AREAS DISTURBED BY CONSTRUCTION INCLUDING BUT NOT LIMITED TO GRADING & EARTHWORK AND SITE UTILITY WORK ARE TO RECEIVE SOD UNLESS OTHERWISE INDICATED. EXTEND LIMITS OF SOD TO INCLUDE ALL AREAS DISTURBED BY CONSTRUCTION. SEE SPECIFICATIONS 'LAWNS AND GRASSES' FOR FINE GRADING AND GRASS REQUIREMENTS.
K. PROVIDE EROSION CONTROL BLANKET FOR ALL SEEDED SLOPES 3:1 OR STEEPER. SEE 'EARTH MOVING' & 'TURF AND GRASSES'
SPECIFICATIONS FOR ADDITIONAL INFORMATION AND REQUIREMENTS.
L. FOR PROPOSED DRAINAGE STRUCTURES, INVERT ELEVATIONS ARE APPROXIMATE AND BASED ON INFORMATION PROVIDED FOR EXISTING DRAINAGE STRUCTURES AND GRADES. FIELD VERIFY ELEVATIONS PRIOR TO INSTALLATION OF STORM STRUCTURES AND
NOTIFY LANDSCAPE ARCHITECT OF ANY CONFLICTS.
M. FOR PROPOSED DRAINAGE PIPE, PIPE LENGTHS & SLOPES ARE APPROXIMATE & SHOULD BE ADJUSTED AS NECESSARY TO MEET
EXISTING AND PROPOSED STORM STRUCTURES.
N. GRADE ALL NEW PAVEMENTS TO DRAIN. GRADE ALL NEW WALKS AT MAX. 2% CROSS SLOPE. GRADE ALL NEW WALKS TO MAX. 5% LONGITUDINAL SLOPE UNLESS OTHERWISE SPECIFICALLY INDICATED ON PLANS TO BE A RAMP.
O. CONTRACTOR TO CONFIRM SPOT GRADES WHERE MATCHING EXISTING PAVEMENTS. NOTIFY LANDSCAPE ARCHITECT/CIVIL ENGINEER WITH ANY DISCREPANCIES, OR IF PROPOSED GRADES TO NOT ALIGN WITH DESIGN INTENT. SEE NOTE "N".
P. ALL DRAINAGE SWALES SHALL BE SODDED WITH MIN. 6' WIDE SOD FOR FULL LENGTH OF SWALE, Q. SEE MEP DRAWINGS FOR ADDITIONAL EARTHWORK ASSOCIATED WITH DEMOLITION AND CONSTRUCTION OF OTHER SITE UTILITIES.
R. THE CONTRACTOR SHALL REFER TO GEOTECHNICAL ENGINEER REQUIREMENTS FOR ALL EARTHWORK, FILL MATERIALS, AND SUBGRADE CONDITIONS. A QUALIFIED TESTING AGENCY SHALL SHALL SUPERVISE THAT SUBGRADE MEET SPECIFICATIONS AND GEOTECHNICAL ENGINEERING REQUIREMENTS. THE LANDSCAPE ARCHITECT/CIVIL ENGINEER IS NOT RESPONSIBLE FOR SUBGRADE CONDITIONS. SEE THE EARTH MOVING SPECIFICATIONS AND GEOTECHNICAL REPORT FOR MORE INFORMATION. PAVEMENT DESIGNS SHALL BE REVIEWED BY THE GEOTECHNICAL ENGINEER FOR FINAL APPROVAL BASED ON SITE AND SUBGRADE CONDITIONS BEFORE ANY SITE
MATERIALS ARE CONSTRUCTED.
(A)
(B)
(C)
(D)
(E)
(F)
(G)
(H)
(I)
(J) M
A
TC
HL
IN
E W
ES
T
W
IN
G
(K)
(L)
A-C3.0
KEY NOTES:
1. STRUCTURE TO CONNECT TO LINES INSTALLED AS PART OF POOL DECK PROJECT. COORDINATE CONNECTION WITH POOL DECK
CONTRACTOR.
2. PROPOSED PIPES EXTENDS BEYOND SURVEY LIMITS, LIDAR DATA HAS BEEN USED FOR SUPPLEMENTAL SURFACE INFORMATION.
ELEVATIONS SHALL BE FIELD VERIFIED AND ROUTE SHALL BE STAKED BY CONTRACTOR PRIOR TO SHOP DRAWINGS BEING PREPARED
AND SHALL BE APPROVED BY ENGINEERS REPRESENTATIVE AND OWNER.
NOTES:
EXISTING SURVEY CONTOURS TUNED OF FOR
VISIBILITY PURPOSES. REFER TO GRADING SHEET
FOR CONTOUR INFORMATION.
SITE LEGEND:
79.2
PROPOSED CONTOUR
PROPOSED SPOT ELEVATION
M.E. MATCH EXISTING
x
T.C. TOP OF CURB
B.C. BOTTOM OF CURB
H.P. HIGH POINT
FFE FINISH FLOOR ELEVATION
T.R. TOP OF RAMP
B.R. BOTTOM OF RAMP
T.W. TOP OF WALL
B.W. BOTTOM OF WALL (FINISHED GRADE)
EXISTING CONTOUR
T.S. TOP STEP
B.S. BOTTOM STEP
PROPOSED STORM MANHOLE
PROPOSED YARD INLET /JUNCTION BOX
PROPOSED HEADWALL OUTFALL
PIPE FLOW DIRECTION
PROPOSED UNDER DRAIN PIPE
PROPOSED TRENCH DRAIN
PROPOSED DRAIN PIPE
PROPOSED CLEAN OUTCO
DRAINAGE LEGEND:
D DOWN SPOUT
PROPOSED 6" PIPE DOWN SPOUT CONNECTION
ADDENDUM #3 8-22-25
DELETE JB-11 FROM SCOPE AND EXTEND
PIPE TO POOL DECK STRUCTURE "S-128" IN
VOLUME B SCOPE. MAINTAIN PIPE SLOPE AND
COORDINATE SHOP DRAWINGS.
DELETE JB-8 FROM SCOPE AND EXTEND PIPE TO POOL
DECK STRUCTURE "S-115" IN VOLUME B SCOPE. MAINTAIN
PIPE SLOPE. COORDINATE SHOP DRAWINGS.
ADDENDUM #4 8-27-25
AutoCAD SHX Text evan Snapshot
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D D
D
D
D
D
D
D
D
D
D
MATCHLINE B
MATCHLINE B
MATCHLINE CW
-1
W -2
W -3
MATCHLINE C
MATCHLINE D
MATCHLINE D
MATCHLINE E
W -3W
-2
W -1
W -1
W -2
W -3
W-1
W-2 W-3
MATCHLINE A
PWU-12
PWU-4
PWU-6B
PWU-9
PWU-10
PWU-11
PWU-7
PWU-6A
PWU-3
PWU-2 PWU-1
MATCHLINE E
MATCHLINE F
PWL-1
PWL-4
PWL-7
PWL-2
PWL-3
PWL-5
PWL-6
PWU-14
PWU-13
MH-12
STA: 1+29.02
N = 3476225.41 E = 4282513.20
MH-11
STA: 1+57.01
N = 3476227.41 E = 4282541.12
YI-9
STA: 5+37.97
N = 3476538.64 E = 4282700.03
YI-3
STA: 2+65.20
N = 3476335.45 E = 4282538.39
YI-4
STA: 3+24.16
N = 3476392.51 E = 4282552.87
YI-6
STA: 3+74.41
N = 3476437.36 E = 4282575.40
YI-7
STA: 4+28.64
N = 3476479.80 E = 4282609.21
YI-8
STA: 4+83.53
N = 3476514.31 E = 4282651.70
JB-18
STA: 3+85.73
N = 3476267.10 E = 4282509.18
JB-11
STA: 0+00.00
N = 3476568.77 E = 4282699.10
MH-13
STA: 0+65.29
N = 3476177.00 E = 4282471.75
HW-2
STA: 0+00.44
N = 3476175.41 E = 4282406.92
MH-14
STA: 0+37.23
N = 3476176.31 E = 4282443.70
JB-17
STA: 3+73.00
N = 3476279.79 E = 4282508.17
JB-16
STA: 3+24.64
N = 3476328.07 E = 4282508.60
JB-15
STA: 2+35.73
N = 3476413.92 E = 4282530.31
JB-14
STA: 1+46.89
N = 3476488.32 E = 4282578.20
JB-12
STA: 0+06.37
N = 3476566.42 E = 4282693.18
JB-13
STA: 0+67.54
N = 3476539.66 E = 4282638.34
YI-10
STA: 1+26.60
N = 3476460.33 E = 4282731.27
CO
STA: 0+75.59
N = 3476456.32 E = 4282680.42
YI-2
STA: 2+13.60
N = 3476283.84 E = 4282536.80
FLOOR DRAIN 1
STA: 2+08.21
N = 3476278.47 E = 4282537.17
YI-1
STA: 1+92.80
N = 3476263.09 E = 4282538.37
PWU-5B
PWU-5A
YI-5
STA: 3+37.87
N = 3476405.16 E = 4282558.11
PWU-8
38037
CO
CO
CO
CO
CO
CO
CO
CO
COCOCO
CO
CO
CO CO
CO
CO
CO
CO
CO
CO
CO CO
CO
CO
CO
CO
CO
CO
CO
CO
CO
WEST LOWER LEVEL-STORM STRUCTURE CHART
STRUCTURE NAME
JB-11
JB-12
JB-13
JB-14
JB-15
JB-16
JB-17
JB-18
RIM ELEVATIONS
387.70
387.70
387.70
387.70
387.70
387.70
387.70
387.70
INVERT IN
PWL-7 = 383.22
PWL-6 = 383.25
PWL-5 = 383.56
PWL-4 = 383.95
PWL-3 = 384.40
PWL-2 = 384.84
PWL-1 = 385.08
INVERT OUT
PWL-7 = 383.25
PWL-6 = 383.55
PWL-5 = 383.96
PWL-4 = 384.40
PWL-3 = 384.84
PWL-2 = 385.08
PWL-1 = 385.14
NOTES
WEST UPPER PIPE-STORM STRUCTURE CHART
STRUCTURE NAME
CO
FLOOR DRAIN 1
HW-2
MH-11
MH-12
MH-13
MH-14
YI-1
YI-2
YI-3
YI-4
YI-5
YI-6
YI-7
YI-8
YI-9
YI-10
RIM ELEVATIONS
417.39
396.30
362.84
397.03
396.20
396.00
377.70
397.75
397.75
397.75
397.75
397.75
397.75
397.75
397.75
397.75
416.63
INVERT IN
PWU-14 = 411.70
PWU-6A = 391.37
PWU-1 = 360.28
PWU-5A = 391.12
PWU-4 = 390.98
PWU-3 = 388.61
PWU-2 = 371.00
PWU-5B = 391.30
PWU-6B = 391.40
PWU-7 = 391.66
PWU-8 = 391.95
PWU-9 = 392.02
PWU-10 = 392.20
PWU-11 = 392.48
PWU-13 = 393.44
PWU-12 = 392.75
INVERT OUT
PWU-13 = 411.02
PWU-5B = 391.37
PWU-4 = 391.12
PWU-3 = 389.74
PWU-2 = 388.71
PWU-1 = 371.00
PWU-5A = 391.30
PWU-6A = 391.40
PWU-6B = 391.66
PWU-7 = 391.95
PWU-8 = 392.02
PWU-9 = 392.20
PWU-10 = 392.48
PWU-11 = 392.75
PWU-12 = 393.02
PWU-14 = 411.95
NOTES
WEST LOWER LEVEL-PIPE TABLE
Pipe Name
PWL-1
PWL-2
PWL-3
PWL-4
PWL-5
PWL-6
PWL-7
Length
12.729
48.327
88.910
88.865
79.309
61.144
6.373
Size
18.000
18.000
18.000
18.000
18.000
18.000
18.000
Slope
0.50%
0.50%
0.50%
0.50%
0.50%
0.50%
0.50%
Notes
PIPE
PIPE
PIPE
PIPE
PIPE
PIPE
PIPE
WEST UPPER PIPE-PIPE TABLE
Pipe Name
PWU-1
PWU-2
PWU-3
PWU-4
PWU-5A
PWU-5B
PWU-6A
PWU-6B
PWU-7
PWU-8
PWU-9
PWU-10
PWU-11
PWU-12
PWU-13
PWU-14
Length
36.795
28.056
63.729
27.990
35.789
15.417
5.390
51.726
59.008
13.690
36.576
54.368
54.854
54.202
74.976
51.007
Size
24.000
24.000
24.000
24.000
24.000
24.000
24.000
24.000
24.000
24.000
24.000
24.000
24.000
24.000
6.000
6.000
Slope
29.12%
63.14%
1.77%
0.50%
0.50%
0.50%
0.50%
0.50%
0.50%
0.50%
0.50%
0.50%
0.50%
0.50%
23.44%
0.50%
Notes
PIPE
PIPE
PIPE
PIPE
PIPE
PIPE
PIPE
PIPE
PIPE
PIPE
PIPE
PIPE
PIPE
PIPE
PIPE
PIPE
(CONCRETE)
(CONCRETE)
(CONCRETE)
ACCOUNT NO.
785CA7UBH0600
DRAWING INFORMATION
CHECKED BY
DRAWN BY
DRAWING DATE
A&E FILE NO.
PHASE
RTA DATE
REVISION HISTORY OF THIS DRAWING
DATEDESCRIPTION OF THE REVISIONS DESCRIPTION OF THE REVISIONS DATE
DECA LOG #
AS BUILT DATE
DRAWING NO.
K. NORMAN BERRY ASSOCIATES ARCHITECTS, PLLC
815 WEST MARKET STREET, SUITE 502
LOUISVILLE, KENTUCKY 40202
PHONE: 502-582-2500
WEBSITE: WWW.KNBARCH.COM
C
RDM
EPM/AS
08/01/2025
Project Number
Structural Repairs + Renovation PH-3 Volume A
COMMONWEALTH OF KENTUCKY
FINANCE AND ADMINISTRATION CABINET
DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES
DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION
FRANKFORT, KENTUCKY
element design landscape architecture+civil engineering+planning
366 South Broadway Lexington, KY 40508
p. 859.389.6533
1018 E. Jefferson St Louisville, KY 40206
p. 502.489.4221
720 Applewood Road Murray, KY 42071
p. 270.210.6644
08/01/2025
SITE DRAINAGE PLAN - WEST WING
SCALE: 1" = 20'
DRAINAGE PLAN - WEST WING
TRUE NORTH
1. STRUCTURE TO CONNECT TO LINES INSTALLED AS PART OF POOL DECK PROJECT. COORDINATE CONNECTION WITH POOL DECK CONTRACTOR.
2. PROPOSED PIPES EXTENDS BEYOND SURVEY LIMITS, LIDAR DATA HAS BEEN USED FOR SUPPLEMENTAL SURFACE INFORMATION. ELEVATIONS SHALL
BE FIELD VERIFIED AND ROUTE SHALL BE STAKED BY CONTRACTOR PRIOR TO SHOP DRAWINGS BEING PREPARED AND SHALL BE APPROVED BY
ENGINEERS REPRESENTATIVE AND OWNER.
3. HEADWALL OUTFALL. REFER TO DETAIL H/C4.1
4. 24" PERFORATED HDPE DRAIN PIPE IN 6'' WIDE FRENCH DRAIN REFER TO DETAIL A/A-C3.1
5. TRENCH DRAIN; REFER TO STRUCTURAL DRAWINGS DETAIL.
6. 4" PERFORATED HDPE DRAIN PIPE IN EACH PLANTER TERRACE. CONNECT TO 18" STORM BRANCH AS SHOWN IN DETAIL D/C4.2
7. 18" HDPE STORM PIPE. COLLECTS RETAINING WALL FOUNDATION DRAINS, TRENCH DRAINS AND DOWNSPOUTS. REFER TO DETAIL A/A-C3.1 AND
DETAIL D/C4.2
8. 6" PERFORATED HDPE DRAIN PIPE. CONNECT TO 24" STORM BRANCH AS SHOWN IN DETAIL D/C4.2
9. EXISTING CONCRETE RETAINING WALL
(A)
(B)
(C)
(D)
(E)
A-C3.1
PWU: PIPE WEST UPPER LEVEL
PWL: PIPE WEST LOWER LEVEL
M A
TC
HL
IN
E
W
ES
T W
IN
G
M A
TC
HL
IN
E
EA
ST
W
IN
G
W-1: UNDERDRAIN
W-2: UNDERDRAIN
W-3: UNDERDRAIN
(F)
WT: WEST TRENCH DRAIN
GENERAL DRAINAGE NOTES:
A. THE EXISTING TOPOGRAPHIC AND SITE INFORMATION SHOWN HAS BEEN PROVIDED BY BFW ENGINEERS. THIS INFORMATION IS
PROVIDED FOR THE CONVENIENCE OF THE CONTRACTOR. THE ARCHITECT SHALL NOT BE RESPONSIBLE FOR THE ACCURACY OF THE INFORMATION SHOWN THEREON. CONTRACTOR TO VERIFY ALL INFORMATION SHOWN; THE CONTRACTOR SHALL BE RESPONSIBLE
FOR REPAIRING ANY DAMAGE TO UTILITIES SHOWN ON THE SURVEY.
B. SEE THE SURVEY AND SITE UTILITY PLANS FOR EXISTING AND PROPOSED UNDERGROUND INFRASTRUCTURE. THE CONTRACT DRAWINGS SHOW THE APPROXIMATE LOCATION OF EXISTING UTILITY LINES. THESE LINES HAVE BEEN IDENTIFIED AND LOCATED AS ACCURATELY AS POSSIBLE USING AVAILABLE INFORMATION. THE CONTRACTOR IS RESPONSIBLE FOR VERIFYING UTILITY LOCATIONS ON THE SURVEY WITH LOCATIONS IN THE FIELD, AND COORDINATING WITH UTILITY COMPANIES FOR DEMOLITION OF UTILITIES INDICATED. CONFLICTS MAY EXIST BETWEEN EXISTING AND PROPOSED UTILITIES. THE CONTRACTOR IS RESPONSIBLE FOR VERIFYING IF CONFLICT EXIST PRIOR TO BEGINNING INSTALLATION OF PROPOSED UTILITIES AND SHALL REPORT FINDINGS TO DESIGN TEAM.
C. PROTECT EXISTING TREES FROM POTENTIAL DAMAGE OF CONSTRUCTION OPERATIONS. STEEPEN GRADES UPHILL FROM EXISTING
TREES TO A MAX. OF 2:1 TO AVOID FILLING SOILS ONTO TRUNKS.
D. UNLESS OTHERWISE INDICATED TO BE REMOVED, ALL ITEMS REMAINING WITHIN THE LIMIT OF CONTRACT ARE TO REMAIN AND BE
PROTECTED FROM DAMAGE DURING CONSTRUCTION.
E. THE CONTRACTOR SHALL MAINTAIN STORM DRAINAGE SYSTEMS TO FUNCTION THROUGHOUT THE CONSTRUCTION PERIOD.
F. PROPOSED GRADES SHOWN ARE FINISHED GRADES.
G. LIMIT OF GRADING INCLUDES ALL AREAS DISTURBED BY ALL SITE UTILITY WORK, REFER TO SITE UTILITY DRAWINGS FOR LOCATIONS OF
PROPOSED SITE UTILITIES.
H. REFER TO SPECIFICATIONS / PROJECT MANUAL FOR ADDITIONAL REQUIREMENTS.
I. ADJUST RIM ELEVATIONS OF ALL EXISTING UTILITY STRUCTURES TO MATCH PROPOSED FINISHED GRADES.
J. ALL EXISTING LAWN AREAS DISTURBED BY CONSTRUCTION INCLUDING BUT NOT LIMITED TO GRADING & EARTHWORK AND SITE UTILITY WORK ARE TO RECEIVE SOD UNLESS OTHERWISE INDICATED. EXTEND LIMITS OF SOD TO INCLUDE ALL AREAS DISTURBED BY CONSTRUCTION. SEE SPECIFICATIONS 'LAWNS AND GRASSES' FOR FINE GRADING AND GRASS REQUIREMENTS.
K. PROVIDE EROSION CONTROL BLANKET FOR ALL SEEDED SLOPES 3:1 OR STEEPER. SEE 'EARTH MOVING' & 'TURF AND GRASSES'
SPECIFICATIONS FOR ADDITIONAL INFORMATION AND REQUIREMENTS.
L. FOR PROPOSED DRAINAGE STRUCTURES, INVERT ELEVATIONS ARE APPROXIMATE AND BASED ON INFORMATION PROVIDED FOR EXISTING DRAINAGE STRUCTURES AND GRADES. FIELD VERIFY ELEVATIONS PRIOR TO INSTALLATION OF STORM STRUCTURES AND
NOTIFY LANDSCAPE ARCHITECT OF ANY CONFLICTS.
M. FOR PROPOSED DRAINAGE PIPE, PIPE LENGTHS & SLOPES ARE APPROXIMATE & SHOULD BE ADJUSTED AS NECESSARY TO MEET
EXISTING AND PROPOSED STORM STRUCTURES.
N. GRADE ALL NEW PAVEMENTS TO DRAIN. GRADE ALL NEW WALKS AT MAX. 2% CROSS SLOPE. GRADE ALL NEW WALKS TO MAX. 5% LONGITUDINAL SLOPE UNLESS OTHERWISE SPECIFICALLY INDICATED ON PLANS TO BE A RAMP.
O. CONTRACTOR TO CONFIRM SPOT GRADES WHERE MATCHING EXISTING PAVEMENTS. NOTIFY LANDSCAPE ARCHITECT/CIVIL ENGINEER WITH ANY DISCREPANCIES, OR IF PROPOSED GRADES TO NOT ALIGN WITH DESIGN INTENT. SEE NOTE "N".
P. ALL DRAINAGE SWALES SHALL BE SODDED WITH MIN. 6' WIDE SOD FOR FULL LENGTH OF SWALE, Q. SEE MEP DRAWINGS FOR ADDITIONAL EARTHWORK ASSOCIATED WITH DEMOLITION AND CONSTRUCTION OF OTHER SITE UTILITIES.
R. THE CONTRACTOR SHALL REFER TO GEOTECHNICAL ENGINEER REQUIREMENTS FOR ALL EARTHWORK, FILL MATERIALS, AND SUBGRADE CONDITIONS. A QUALIFIED TESTING AGENCY SHALL SHALL SUPERVISE THAT SUBGRADE MEET SPECIFICATIONS AND GEOTECHNICAL ENGINEERING REQUIREMENTS. THE LANDSCAPE ARCHITECT/CIVIL ENGINEER IS NOT RESPONSIBLE FOR SUBGRADE CONDITIONS. SEE THE EARTH MOVING SPECIFICATIONS AND GEOTECHNICAL REPORT FOR MORE INFORMATION. PAVEMENT DESIGNS SHALL BE REVIEWED BY THE GEOTECHNICAL ENGINEER FOR FINAL APPROVAL BASED ON SITE AND SUBGRADE CONDITIONS BEFORE ANY SITE
MATERIALS ARE CONSTRUCTED.
S. ALL CLEANOUTS SHALL BE TWO WAY CLEANOUTS WITH THE ECEPTION OF CLEANOUTS LOCATED AT THE END OF A LINE.
CONTRACTOR SHALL BE RESPONSIBLE FOR ENSURING ALL STRUCTURES ARE SUFFICIENTLY SIZED TO ACCOMMODATE ALL INLET PIPE SIZES, SIZE STRUCTURES ACCORDINGLY. CUSTOM STRUCTURES MAY BE REQUIRED TO ACCOMMODATE SHALLOW PIPES AND SHALL BE THE CONTRACTORS REAPOSIBILITY.
PROVIDE 42" TALL CHAINLINK FENCING IF FACE OF HEADWALL IS TALLER THAN 30"
NOTE: ALL PIPE LENGTHS ARE APPROXIMATE AND ARE PROVIDED
FOR THE CONVENIENCE OF THE CONTRACTOR ONLY. CONTRACTOR TO
FIELD VERIFY LENGTHS AND SLOPES NEED TO MEET THE REQUIREMENTS
OF THE STORM SYSTEM AS INDICATED. CONTRACTOR MAY CHOOSE TO
USE HDPE, HP STORM OR RCP FORTHE MATERIAL UNLESS OTHERWISE
NOTED. WHERE MATERIAL IS SPECIFIED IN THE CHART ABOVE, THE
CONTRACTOR IS TO USE THAT MATERIAL.
NOTES:
EXISTING SURVEY CONTOURS TUNED OF FOR
VISIBILITY PURPOSES. REFER TO GRADING SHEET
FOR CONTOUR INFORMATION.
SITE LEGEND:
79.2
PROPOSED CONTOUR
PROPOSED SPOT ELEVATION
M.E. MATCH EXISTING
x
T.C. TOP OF CURB
B.C. BOTTOM OF CURB
H.P. HIGH POINT
FFE FINISH FLOOR ELEVATION
T.R. TOP OF RAMP
B.R. BOTTOM OF RAMP
T.W. TOP OF WALL
B.W. BOTTOM OF WALL (FINISHED GRADE)
EXISTING CONTOUR
T.S. TOP STEP
B.S. BOTTOM STEP
PROPOSED STORM MANHOLE
PROPOSED YARD INLET /JUNCTION BOX
PROPOSED HEADWALL OUTFALL
PIPE FLOW DIRECTION
PROPOSED UNDER DRAIN PIPE
PROPOSED TRENCH DRAIN
PROPOSED DRAIN PIPE
PROPOSED CLEAN OUTCO
DRAINAGE LEGEND:
D DOWN SPOUT
PROPOSED 6" PIPE DOWN SPOUT CONNECTION
T/WALL
T/WALL
UPPER FLOOR
LOWER FLOOR
NOTES:
1. REFER TO STRUCTURAL DRAWINGS FOR WALL DETAILS AND
DIMENSIONS. WALLS SHOWN IN THIS DETAIL ARE NOT FOR
CONSTRUCTION PURPOSES.
2. REFER TO STRUCTURAL DRAWINGS FOR EXACT LOCATION AND
ELEVATIONS OF THE UNDER DRAIN PIPES AND TRENCH DRAINS. THE
UNDER DRAIN PIPES AND TRENCH DRAINS SHALL BE SLOPED TO THE
DRAINAGE SYSTEM POINTS OF INTERCONNECTION.
3. REFER TO STORM PROFILES FOR ELEVATION OF 18" AND 24" STORM
LINES
6'-0"
4" (TYP.)
8"
S T A
T E OF KENT UCKY
P
ROFES S IONA L ENGIN
EE
R
R. DEREK
MOTSCH
26439
L IC ENS ED
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
WEST WING DRAINAGE KEYNOTES
AutoCAD SHX Text
WESTERN SIDE DRAINAGE ILLUSTRATION
AutoCAD SHX Text N.T.S.
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
PIPE PWL
AutoCAD SHX Text
TRENCH DRAIN WT
AutoCAD SHX Text
UNDER DRAIN PIPE W1: 4" PERFORATED PIPE W/ FILTER SOCK
AutoCAD SHX Text
UNDER DRAIN PIPE W2: 4" PERFORATED PIPE W/ FILTER SOCK
AutoCAD SHX Text
UNDER DRAIN PIPE W3: 6" PERFORATED PIPE WITH FILTER SOCK
AutoCAD SHX Text
PIPE PWU
AutoCAD SHX Text DOWNSPOUTS CONNECT WITH INSERTA-TEE ALONG THE PIPES LENGTH, UNLESS DOWNSPOUT IS AT JUNCTION BOX LOCATION, THEN CONNECT TO JUNCTION BOX.
AutoCAD SHX Text C/L
AutoCAD SHX Text
3.77' TO BUILDING FACE
AutoCAD SHX Text
EXISTING GRADE (VARIES)
AutoCAD SHX Text
PROPOSED GRADE; 2:1 MAX. INSTALL EROSION CONTROL MATTING
AutoCAD SHX Text
LANDSCAPE EDGING; SEE DETAIL
AutoCAD SHX Text
WASHED #2 STONE BACK FILL. COMPACT IN 8" LIFTS
AutoCAD SHX Text
GEOTEXTILE FILTER FABRIC
AutoCAD SHX Text 4" LAYER OF DECORATIVE RIVER STONE: STONE TO BE 2-3" DIAMETER. CONTRACTOR TO SUBMIT SAMPLES
AutoCAD SHX Text
GEOTEXTILE FILTER FABRIC; PIN BEHIND LANDSCAPE EDGING
AutoCAD SHX Text
TOP OF EXISTING RETAINING WALL = 398.3
AutoCAD SHX Text
3" LAYER OF PINE BARK MULCH OVER WEED FABRIC
AutoCAD SHX Text
18" OF PLANTING SOIL. TOPSOIL AND COMPOST BLEND. SEE SPECS.
AutoCAD SHX Text WASHED 57s DRAINAGE STONE
AutoCAD SHX Text
3" LAYER OF PINE BARK MULCH OVER WEED FABRIC
AutoCAD SHX Text
18" OF PLANTING SOIL. TOPSOIL AND COMPOST BLEND. SEE SPECS.
AutoCAD SHX Text WASHED 57s DRAINAGE STONE evan Callout
DELETE JB-11 FROM SCOPE AND EXTEND
PIPE TO POOL DECK STRUCTURE "S-128" IN
VOLUME B SCOPE. MAINTAIN PIPE SLOPE AND
COORDINATE SHOP DRAWINGS.
evan Line evan Cloud evan Snapshot
D D
MH-11
STA: 1+57.01
N = 3476227.41 E = 4282541.12
MATCHLINE B
MATCHLINE CW
-1
MH-12
STA: 1+29.02
N = 3476225.41 E = 4282513.20
MATCHLINE A
PWU-4
PWU-6A
PWU-3
PWL-1
JB-18
STA: 3+85.73
N = 3476267.10 E = 4282509.18
JB-17
STA: 3+73.00
N = 3476279.79 E = 4282508.17
YI-2
STA: 2+13.60
N = 3476283.84 E = 4282536.80
FLOOR DRAIN 1
STA: 2+08.21
N = 3476278.47 E = 4282537.17
YI-1
STA: 1+92.80
N = 3476263.09 E = 4282538.37
PWU-5B
PWU-5A
CO
COCOCO
CO
CO
CO CO
D
D
D
D
D
D
D
D
YI-3
STA: 2+65.20
N = 3476335.45 E = 4282538.39
MATCHLINE B
W -2
W -3
MATCHLINE D
W -3W
-2
W -1
PWU-6B
PWU-6A
JB-17
STA: 3+73.00
N = 3476279.79 E = 4282508.17
JB-16
STA: 3+24.64
N = 3476328.07 E = 4282508.60
PWL-2
YI-2
STA: 2+13.60
N = 3476283.84 E = 4282536.80
CO
CO
CO
CO
CO CO
CO CO
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
YI-4
STA: 3+24.16
N = 3476392.51 E = 4282552.87
YI-6
STA: 3+74.41
N = 3476437.36 E = 4282575.40
MATCHLINE C
W -3W
-2
W -1
W -1
PWU-9
PWU-7
MATCHLINE E
JB-15
STA: 2+35.73
N = 3476413.92 E = 4282530.31
PWL-3
PWU-8
CO
CO
CO
CO
CO
CO
CO
CO
D
D
D
D
D
D
D
D
D
D
YI-6
STA: 3+74.41
N = 3476437.36 E = 4282575.40
YI-7
STA: 4+28.64
N = 3476479.80 E = 4282609.21
MATCHLINE D
MATCHLINE E
W -1
W -2
W -3
W-1
W-2
PWU-10
PWU-11
MATCHLINE F
PWL-4
JB-14
STA: 1+46.89
N = 3476488.32 E = 4282578.20
PWL-5
PWU-13
CO
CO
CO
CO
CO
CO
CO
CO
MATCHLINE B
MH-13
STA: 0+65.29
N = 3476177.00 E = 4282471.75
HW-2
STA: 0+00.44
N = 3476175.41 E = 4282406.92
MH-14
STA: 0+37.23
N = 3476176.31 E = 4282443.70
PWU-3
PWU-2 PWU-1
38037
D
D
D
D
D D
D
YI-8
STA: 4+83.53
N = 3476514.31 E = 4282651.70
JB-11
STA: 0+00.00
N = 3476568.77 E = 4282699.10
MATCHLINE E
W-1
W-2
W-3 YI-9
STA: 5+37.97
N = 3476538.64 E = 4282700.03
PWU-12
PWL-7
JB-12
STA: 0+06.37
N = 3476566.42
E = 4282693.18JB-13
STA: 0+67.54
N = 3476539.66
E = 4282638.34 PWL-6
CO
COCO
CO
CO
CO
CO
CO
CO
ACCOUNT NO.
785CA7UBH0600
DRAWING INFORMATION
CHECKED BY
DRAWN BY
DRAWING DATE
A&E FILE NO.
PHASE
RTA DATE
REVISION HISTORY OF THIS DRAWING
DATEDESCRIPTION OF THE REVISIONS DESCRIPTION OF THE REVISIONS DATE
DECA LOG #
AS BUILT DATE
DRAWING NO.
K. NORMAN BERRY ASSOCIATES ARCHITECTS, PLLC
815 WEST MARKET STREET, SUITE 502
LOUISVILLE, KENTUCKY 40202
PHONE: 502-582-2500
WEBSITE: WWW.KNBARCH.COM
C
RDM
EPM/AS
08/01/2025
Project Number
Structural Repairs + Renovation PH-3 Volume A
COMMONWEALTH OF KENTUCKY
FINANCE AND ADMINISTRATION CABINET
DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES
DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION
FRANKFORT, KENTUCKY
element design landscape architecture+civil engineering+planning
366 South Broadway Lexington, KY 40508
p. 859.389.6533
1018 E. Jefferson St Louisville, KY 40206
p. 502.489.4221
720 Applewood Road Murray, KY 42071
p. 270.210.6644
08/01/2025
SITE DRAINAGE PLAN - WEST WING ENLARGEMENTS
SCALE: 1" = 10'
DRAINAGE ENLARGEMENT PLAN - WEST WING
TRUE NORTH
ENLARGEMENT- A ENLARGEMENT - C
ENLARGEMENT - DENLARGEMENT - B
ENLARGEMENT - E
A-C3.2
ENLARGEMENT- F
CO
CO
CO
CO
CO
PWU: PIPE WEST UPPER LEVEL
PWL: PIPE WEST LOWER LEVEL
W-1: UNDERDRAIN
W-2: UNDERDRAIN
W-3: UNDERDRAIN
NOTES:
EXISTING SURVEY CONTOURS TUNED OF FOR
VISIBILITY PURPOSES. REFER TO GRADING SHEET
FOR CONTOUR INFORMATION.
SITE LEGEND:
79.2
PROPOSED CONTOUR
PROPOSED SPOT ELEVATION
M.E. MATCH EXISTING
x
T.C. TOP OF CURB
B.C. BOTTOM OF CURB
H.P. HIGH POINT
FFE FINISH FLOOR ELEVATION
T.R. TOP OF RAMP
B.R. BOTTOM OF RAMP
T.W. TOP OF WALL
B.W. BOTTOM OF WALL (FINISHED GRADE)
EXISTING CONTOUR
T.S. TOP STEP
B.S. BOTTOM STEP
PROPOSED STORM MANHOLE
PROPOSED YARD INLET /JUNCTION BOX
PROPOSED HEADWALL OUTFALL
PIPE FLOW DIRECTION
PROPOSED UNDER DRAIN PIPE
PROPOSED TRENCH DRAIN
PROPOSED DRAIN PIPE
PROPOSED CLEAN OUTCO
DRAINAGE LEGEND:
D DOWN SPOUT
PROPOSED 6" PIPE DOWN SPOUT CONNECTION
S T A
T E OF KENT UCKY
P
ROFES S IONA L ENGIN
EE
R
R. DEREK
MOTSCH
26439
L IC ENS ED
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text evan Callout
CONNECT FLOOR DRAIN AND DOWNSPOUT TO JB-18
evan Cloud evan Callout
DELETE JB-11 FROM SCOPE AND EXTEND
PIPE TO POOL DECK STRUCTURE "S-128" IN
VOLUME B SCOPE. MAINTAIN PIPE SLOPE AND
COORDINATE SHOP DRAWINGS.
evan Line evan Cloud evan Snapshot evan Snapshot
400401
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D D
D
D
D
D
D
D
D
E-2
MATCHLINE H
MATCHLINE G
E-1
MATCHLINE H
E-1
MATCHLINE I
E-1
E-2
E-3
MATCHLINE J
E-2
E-3
E-3
E-3 E-2
E-1
PEU-3
PEU-2
PEU-1
MATCHLINE I
MATCHLINE J
MATCHLINE K
MATCHLINE K
MATCHLINE L
PEU-6A
PEU-6B
PEU-8
PEU-10
PEU-9
PEU-12
PEU-13
PEU-4
P E
L-
PEL-7
PEL-6
PEL-5
PEL-4
PEL-3
PEL-2
PEU-15
P
EU
-1
MH-3
STA: 1+42.06
N = 3476265.51 E = 4283072.08
YI-12
STA: 5+57.73
N = 3476549.80 E = 4282835.91
YI-13
STA: 5+02.11
N = 3476533.39 E = 4282888.69
YI-14
STA: 4+46.64
N = 3476506.00 E = 4282936.61
YI-15
STA: 3+70.44
N = 3476452.75 E = 4282990.48
YI-16
STA: 3+44.53
N = 3476431.26 E = 4283004.86
YI-18
STA: 2+98.40
N = 3476389.77 E = 4283024.77
MH-4
STA: 1+70.05
N = 3476263.51 E = 4283044.16
MH-2
STA: 0+52.61
N = 3476185.00 E = 4283111.06
MH-1
STA: 0+25.00
N = 3476175.03 E = 4283136.80
YI-11
STA: 1+27.17
N = 3476465.39 E = 4282802.76
CO
STA: 0+74.06
N = 3476468.33 E = 4282855.79
YI-19
STA: 2+29.83
N = 3476323.11 E = 4283039.67
YI-20
STA: 2+05.26
N = 3476298.61 E = 4283041.52
FLOOR DRAIN-2
STA: 2+21.44
N = 3476314.76 E = 4283040.44
YI-17
STA: 3+24.47
N = 3476413.66 E = 4283014.43
JB-1
STA: 3+98.85
N = 3476291.98 E = 4283070.75
JB-8
STA: 0+00.38
N = 3476578.19 E = 4282840.80
JB-7
STA: 0+20.73
N = 3476573.77 E = 4282860.67
JB-6
STA: 0+64.87
N = 3476559.13 E = 4282902.34
JB-5
STA: 1+44.30
N = 3476517.03 E = 4282969.60
JB-4
STA: 2+37.70
N = 3476446.06 E = 4283029.89
JB-3
STA: 3+38.02
N = 3476352.51 E = 4283064.95
JB-2
STA: 3+86.63
N = 3476304.19 E = 4283070.18
HW-1
STA: 0+00.00
N = 3476166.00 E = 4283160.12
PEU-5B
PEU-5A
PEU-7
CO
CO
CO
CO
CO
CO
CO
CO CO
CO CO
CO CO
CO
CO
CO
CO
CO
CO
CO
CO
CO
CO
CO
CO
CO
CO
EAST LOWER LEVEL-STORM STRUCTURE CHART
STRUCTURE NAME
JB-1
JB-2
JB-3
JB-4
JB-5
JB-6
JB-7
JB-8
RIM ELEVATIONS
387.70
387.70
387.70
387.70
387.70
387.70
387.70
387.70
INVERT IN
PEL-2 = 384.93
PEL-1 = 385.18
PEL-3 = 384.43
PEL-4 = 383.96
PEL-5 = 383.57
PEL-6 = 383.35
PEL-7 = 383.25
INVERT OUT
PEL-1 = 385.24
PEL-3 = 384.93
PEL-2 = 385.18
PEL-4 = 384.43
PEL-5 = 383.97
PEL-6 = 383.58
PEL-7 = 383.35
NOTES
EAST UPPER LEVEL-STORM STRUCTURE CHART
STRUCTURE NAME
CO
FLOOR DRAIN-2
HW-1
MH-1
MH-2
MH-3
MH-4
YI-11
YI-12
YI-13
YI-14
YI-15
YI-16
YI-17
YI-18
YI-19
YI-20
RIM ELEVATIONS
418.66
396.40
372.43
382.00
395.11
395.96
396.85
418.05
398.50
398.50
398.50
398.50
396.25
396.25
398.50
398.50
398.50
INVERT IN
PEU-15 = 412.92
PEU-6A = 390.87
PEU-1 = 369.88
PEU-2 = 376.00
PEU-3 = 387.97
PEU-4 = 390.47
PEU-5A = 390.61
PEU-13 = 392.28
PEU-14 = 391.12
PEU-12 = 392.00
PEU-10 = 391.62
PEU-9 = 391.49
PEU-8 = 391.39
PEU-7 = 391.26
PEU-6B = 390.91
PEU-5B = 390.79
INVERT OUT
PEU-14 = 409.57
PEU-5B = 390.87
PEU-1 = 376.00
PEU-2 = 388.00
PEU-3 = 389.90
PEU-4 = 390.61
PEU-15 = 413.18
PEU-13 = 392.55
PEU-12 = 392.28
PEU-10 = 392.00
PEU-9 = 391.62
PEU-8 = 391.49
PEU-7 = 391.39
PEU-6B = 391.26
PEU-6A = 390.91
PEU-5A = 390.78
NOTES
EAST LOWER LEVEL-PIPE TABLE
Pipe Name
PEL-1
PEL-2
PEL-3
PEL-4
PEL-5
PEL-6
PEL-7
Length
12.217
48.633
100.428
93.549
79.617
44.206
20.368
Size
18.000
18.000
18.000
18.000
18.000
18.000
18.000
Slope
0.50%
0.50%
0.50%
0.50%
0.50%
0.50%
0.48%
Notes
PIPE
PIPE
PIPE
PIPE
PIPE
PIPE
PIPE
EAST UPPER LEVEL-PIPE TABLE
Pipe Name
PEU-1
PEU-2
PEU-3
PEU-4
PEU-5A
PEU-5B
PEU-6A
PEU-6B
PEU-7
PEU-8
PEU-9
PEU-10
PEU-12
PEU-13
PEU-14
PEU-15
Length
25.000
27.607
89.453
27.990
35.206
16.180
8.390
68.513
26.045
20.032
25.870
76.051
55.307
55.387
72.910
53.108
Size
24.000
24.000
24.000
24.000
24.000
24.000
24.000
24.000
24.000
24.000
24.000
24.000
24.000
24.000
6.000
6.000
Slope
24.50%
43.47%
2.16%
0.50%
0.47%
0.46%
0.50%
0.50%
0.50%
0.50%
0.50%
0.50%
0.50%
0.50%
25.30%
0.49%
Notes
PIPE
PIPE
PIPE
PIPE
PIPE
PIPE
PIPE
PIPE
PIPE
PIPE
PIPE
PIPE
PIPE
PIPE
PIPE
PIPE
(CONCRETE)
(CONCRETE)
(CONCRETE)
ACCOUNT NO.
785CA7UBH0600
DRAWING INFORMATION
CHECKED BY
DRAWN BY
DRAWING DATE
A&E FILE NO.
PHASE
RTA DATE
REVISION HISTORY OF THIS DRAWING
DATEDESCRIPTION OF THE REVISIONS DESCRIPTION OF THE REVISIONS DATE
DECA LOG #
AS BUILT DATE
DRAWING NO.
K. NORMAN BERRY ASSOCIATES ARCHITECTS, PLLC
815 WEST MARKET STREET, SUITE 502
LOUISVILLE, KENTUCKY 40202
PHONE: 502-582-2500
WEBSITE: WWW.KNBARCH.COM
C
RDM
EPM/AS
08/01/2025
Project Number
Structural Repairs + Renovation PH-3 Volume A
COMMONWEALTH OF KENTUCKY
FINANCE AND ADMINISTRATION CABINET
DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES
DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION
FRANKFORT, KENTUCKY
element design landscape architecture+civil engineering+planning
366 South Broadway Lexington, KY 40508
p. 859.389.6533
1018 E. Jefferson St Louisville, KY 40206
p. 502.489.4221
720 Applewood Road Murray, KY 42071
p. 270.210.6644
08/01/2025
SITE DRAINAGE PLAN - EAST WING
SCALE: 1" = 20'
DRAINAGE ENLARGEMENT PLAN - EAST WING
TRUE NORTH
M
A
TC
HL
IN
E W
ES
T
W
IN
G
(G)
(H)
(I)
(J)
A-C3.3
(K)
(L)
PEU: PIPE EAST UPPER LEVEL
PEL: PIPE EAST LOWER LEVEL
M A
TC
HL
IN
E
EA
ST
W
IN
G
E-1: UNDERDRAIN
E-2: UNDERDRAIN
E-3: UNDERDRAIN
ET: EAST TRENCH DRAIN
GENERAL DRAINAGE NOTES:
A. THE EXISTING TOPOGRAPHIC AND SITE INFORMATION SHOWN HAS BEEN PROVIDED BY BFW ENGINEERS. THIS INFORMATION IS
PROVIDED FOR THE CONVENIENCE OF THE CONTRACTOR.
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .