Addendum D-Narrative_all drawings and specs.pdf
PDF 3 MB Posted
- Attached to
- Lasata Senior Living Campus – New CBRF
- Solicitation number
- LAS2025-01
- Issued by
- Ozaukee County, Wisconsin
About this file
This document is an Addendum D for the Lasata Senior Living Campus New CBRF (Community Based Residential Facility) project located in Cedarburg, Wisconsin, issued by Dimension IV - Madison, LLC. The addendum modifies the original Contract Documents dated 5/9/2025, with previous addenda issued on 6/30/2025, 7/16/2025, and 8/5/2025. The bid submission deadline is set for Tuesday, August 19th, 2025 at 2:00 PM CST at the Ozaukee County Administrator's Office. The addendum includes changes to the Project Manual, specifically updating sections related to fiberglass windows, plastic laminate cabinets, and various drawing revisions for the new senior living facility.
The addendum provides technical specifications and clarifications for the project, including window performance requirements (U-factor of 0.29 and SHGC of 0.36), window hardware details, and interior finishes. It addresses multiple Request for Information (RFI) questions regarding window types, glazing, hardware, casework, and electrical systems. The changes impact various aspects of the project, such as window limiters, cabinet specifications, and electrical infrastructure. The document indicates that the electrical contractor's scope includes providing infrastructure and cabling for access control, security cameras, and nurse call systems, with some coordination required with the owner's vendor.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Addendum F-Narrative.pdf | ||
| Addendum C-Narrative_all drawings and specs_r.pdf | ||
| AddendumE-Narrative_alldrawingsandspecs.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
00901 - 1
ADDENDUM D
ISSUE DATE: 8/8/2025
RE: Lasata Senior Living Campus – CBRF & RCAC W76N677 Wauwatosa Road Cedarburg, WI 53012
FROM: Dimension IV – Madison, LLC 6515 Grand Teton Plaza, Suite 120 Madison, Wisconsin 53719
(P) 608.829.4444
(F) 608.829.4445
TO: Prospective Bidders
This addendum forms a part of the Contract Documents and modifies the original Contract Documents dated 5/9/2025, Addendum A dated 6/30/2025. Addendum B dated 7/16/2025, and Addendum C dated 8/5/2025. Acknowledge receipt of this Addendum by inserting the number and issue date of this addendum in the blank space provided on the Bid Form.
This Addendum consists of four (4) typed pages, as well as three (3) revised sections of Project Manual, and eight (8) 22 inch by 34 inch drawings.
CHANGES TO PROJECT MANUAL:
1. Section 00 1000 – Construction Manager Bid Submission Documents
a. Bid Advertisement – Bid due date
i. Revise “Bids must be submitted to the Ozaukee County
Adminstrator’s Office, 121 W. Main Street, Port Washington, WI no later than 2pm CST, Tuesday August 19th, 2025.”
b. Instruction to Bidders
i. Item A, Project Timeline
1. Revise Bid Submission deadline and Public Opening to Tuesday August 19th, 2025 @ 2:00pm
ii. Item C, Bid Closing
1. Revise “Bids must be submitted to the Ozaukee County
Administration Office 121 W Main Street, Port Washington, WI no later than 2pm CST, Tuesday, August 19th, 2025.”
iii. Item D, Bid Opening
1. Revise “Bid opening will take place on Tuesday, August 19, 2025 at 2:10pm CST, at the Ozaukee County Administration Office, 121 W Main Street, Port Washington, WI.”
2. Section 08 5413 – Fiberglass Windows
a. Part 2.2.C – Thermal Transmittance
i. Revise U-factor to 0.29
b. Part 2.2.D – Solar Heat Gain Coefficient
i. Revise SHGC to 0.36
c. Part 2.3.H – Projected Window Hardware
i. delete 4 and 4.a
d. Part 2.3.I – Hung window hardware
00901 - 2
i. Add 2.3.I.4 and 4.a – add limit devices as indicated on plan.
3. Section 12 3663 – Plastic Laminate Cabinets, Countertops & Shelves
a. Part 1.4 Quality Assurance
i. delete last line of 1.4 “Shop is a certified participant in AWI’s Quality
Certification Program.”
CHANGES TO THE DRAWINGS:
1. Sheet G0.1 – Cover Sheet
a. Revise Construction Manager to Catalyst Construction
2. Sheet G-0.1 – RCAC Cover Sheet
a. Revise Construction Manager to Catalyst Construction
3. Sheet A1.1 – First Floor Overall Plan
a. Add note “provide limiter at operable window”
i. At window W4 in unit 118
ii. At windows W3 and W2 in unit 120
4. Sheet A6.2 – Door Schedules
a. Add Door 100 to schedule.
b. Revise Door 101 to indicate HM frame.
5. Sheet A6.3 – Window Types & Elevations
a. Detail 2 – Window Elevations
i. Revise Glazing at window W1, W2, W3, W4 to GLT-15 as indicated
ii. Revise Window types W1, W2, W3, W4 to indicate double-hung
b. Detail 3 – Storefront Elevations
i. Revise Glazing at Storefront S1, S2, S5 to GLT-15 as indicated
6. Sheet A7.0 – Interior Elevations
a. Detail 1 – Kitchen Elevation
i. Revise upper cabinets to CAB-1
b. Detail 4 – Pantry Elevation
i. Revise countertop to PL-2
c. Detail 5 – Laundry Elevation
i. Revise countertop to PL-2
7. Sheet A7.1 – Interior Elevations
a. Detail 6 – Toilet 130 Sink Elevation
i. Revise sink skirt to PL-1
b. Detail 11 – Toilet 124 Sink Elevation
i. Revise sink skirt to PL-1
c. Detail 13 – Spa 134 Sink Elevation
i. Revise sink skirt to PL-1
d. Detail 17 – Medicine North Elevation
i. Revise countertop to PL-2
e. Detail 18 – Medicine East Elevation
i. Revise countertop to PL-2
8. Sheet A9.0 – Finish schedule
a. 127 - Medicine room – Revise Upper Cabinets to PL-1
00901 - 3
RFI QUESTIONS / CLARIFICATIONS:
Design team responses in red.
1. Clarification : Addendum A and B are included as part of the issued for Bid drawing set.
2. Fiberglass Windows - Please confirm all fiberglass units should be tempered due to cost – not all fiberglass window glazing needs to be tempered, Please see Addendum D - A6.3.
3. Fiberglass Windows - Please confirm limiters for hungs. Spec shows limiters for casements. – please see Addendum D, a note has been added on A1.0 indicating which windows require a limiter. Limiter is deleted from casement section and added to the hung window section.
4. Plam Countertop Casework and Shelving Spec Section - It in indicated on Spec Manual that Fabricator must be a certified participant in AWI, some of the bidders are asking, particularly those participating on the general trades if this certification is in strict compliance or rather than comply with AWS/AWI Standards. – Please see Addendum D.
line is deleted from spec section.
5. Millwork - Kitchen: Elevation 1/A7.0 calls for PL-1 upper cabinets, but the Room Finish
Schedule on A9.0 call for CAB-1 upper cabinets. Which is correct? Upper cabinets should be CAB-1, Please see Addendum D
6. Millwork - Medicine: Elevations 17,18/A7.1 calls for PL-1 countertop, but both the Room
Finish Schedule and Finish List on A9.0 call for PL-2 at the countertop. Which is correct?
Countertop should be PL-2, Please see Addendum D
7. Millwork - Pantry: Elevation 4/A7.0 calls for PL-1 countertop, but both the Room Finish
Schedule and Finish List on A9.0 call for PL-2 at the countertop. Which is correct?
Countertop should be PL-2, Please see Addendum D
8. Millwork - Laundry: Elevation 5/A7.0 calls for PL-1 countertop, but both the Room
Finish Schedule and Finish List on A9.0 call for PL-2 at the countertop. Which is correct?
Countertop should be PL-2, Please see Addendum D
9. Millwork - Spa & Toilet: Elevations 6,11,13/A7.1 calls for CAB-1 wood apron/skirt, but both the Room Finish Schedule on A9.0 calls for PL-1. Which is correct? Lav Apron/Skirt should be PL-1, Please see Addendum D
10. Millwork - Do you have a spec for the open shelving brackets (in the Pantry & the
Laundry), or will an allowance for KV 0208 series “Ultimate L-Brackets” be acceptable?
An allowance for brackets is acceptable.
11. Millwork - Is rail R1 in the custom millwork scope? Rail R1 per 1/A6.1 refers says to see
6/G0.2 for details. The handrail at 1/A6.1 shows a standard round handrail with brackets, but 6/G0.2 shows an accessible contoured handrail. Which is correct? Rail R1 should be standard round handrail with brackets. The G0.2 sheet is indicating the accessibility requirements of the railing, not the shape of the rail.
12. Access Control – Could you please confirm whether the electrical contractor’s scope is limited to providing infrastructure and cabling only, per the device locations indicated on the drawings? Correct. Additionally, what specific type(s) of cable should be provided?
00901 - 4
Or will the final cable specification and routing be determined by the owner’s vendor?
This should be confirmed with the owners vendor.
13. Nurse Call System - While the drawings indicate nurse call device locations, there is no accompanying specification, general notes, or direction. Can you clarify the intended scope? Should the electrical contractor provide conduit only, or also furnish and install cabling? If so, what system and cable type are expected? The intent is to extend into the existing system located in Maintenance Shop 007 of the Crossing Building. This would include conduit, wire, devices and programming.
14. Security Cameras (CCTV) - Please confirm the electrical contractor’s responsibilities are just to install conduits and CAT6A Jack and Cable? Correct
15. Ceiling Plenum Designation - Is the space above the suspended drop ceiling considered a plenum throughout the project? There are no plenum spaces in the new CBRF building.
The area above the kitchen work in the Crossings building has a current return air plenum. Note #5 on Sheets E2.0B and E2.0C is the only reference to plenum rating.
Please confirm whether this applies project-wide and the reasoning behind the plenum classification (e.g., return air path or specific code requirement). Note #5 will be removed from sheets E2.0B and E2.0C. It will then be added to sheet E1.1. (see Addendum C)
16. Acceptability of NM Cable - Lastly, is the use of NM (non-metallic) cable permissible in this project? Or should branch wiring be run in MC, EMT, or other approved wiring methods, particularly if the ceiling space is indeed plenum-rated? NM is to not be used on the project. At a minimum use EMT.
17. Acceptability of MC Cable - per specifications the electrical components must be compliant with the National Electrical Code, which they were saying that if at minimum
EMT will be used, it will be more expensive and overdesigned. They asking if the NM
Cable is not an option, can an MC Cable be considered? keep EMT as originally designed and specified, but the contractor may present MC as a value engineering item.
18. Referring to Sheet A9,0 – Room Finish Schedule, the table is lacking the typical unit finish schedule. Please see Unit Finishes in upper right corner of A9.0.
19. The specs call for double hung and the window schedule in the drawings show single hung. Double-Hung windows will be used. See Addendum D – A6.3 revised.
20. The specs call for U-Value of 0.30 and SHGC of 0.40 and the drawings call for U-Value of
0.29 and SHGC of 0.36. U 0.29 and SHGC of 0.36 should be used. See revised spec section Addendum D.
ATTACHMENTS:
Project Manual Specification Section 00 1000, 08 5413, 12 3663 Drawings G0.1, G-0.1, A1.1, A6.2, A6.3, A7.0, A7.1, A9.0 (All @ 22x34 sheet size)
END OF ADDENDUM
Dimension IV – Madison, LLC 6515 Grand Teton Plaza, Suite 120 Madison, Wisconsin 53719
LASATA SENIOR LIVING CAMPUS – NEW CBRF FIBERGLASS WINDOWS
Project No. 24039 08 5413 - 1
SECTION 08 5413 - FIBERGLASS WINDOWS
PART 1 - GENERAL
1.1 SUMMARY
A. Section includes fiberglass-framed windows.
1.2 PREINSTALLATION MEETINGS
A. Preinstallation Conference: Conduct conference at Project site.
1. Review and finalize construction schedule and verify availability of materials, Installer's personnel, equipment, and facilities needed to make progress and avoid delays.
2. Review, discuss, and coordinate the interrelationship of fiberglass windows with other exterior wall components. Include provisions for anchoring, flashing, weeping, sealing perimeters, and protecting finishes.
3. Review and discuss the sequence of work required to construct a watertight and weathertight exterior building envelope.
4. Inspect and discuss the condition of substrate and other preparatory work performed by other trades.
1.3 SUBMITTALS
A. Product Data: For each type of product.
1. Include construction details, material descriptions, glazing and fabrication methods, dimensions of individual components and profiles, hardware, and finishes for fiberglass windows.
B. Shop Drawings: For fiberglass windows.
1. Include plans, elevations, sections, hardware, accessories, insect screens, operational clearances, and details of installation, including anchor, flashing, and sealant installation.
C. Samples: For each exposed product and for each color specified, 2 by 4 inches in size.
D. Samples for Initial Selection: For units with factory-applied finishes.
1. Include Samples of hardware and accessories involving color selection.
E. Samples for Verification: For fiberglass windows and components required, prepared on Samples of size indicated below:
1. Exposed Finishes: 2 by 4 inches.
2. Exposed Hardware: Full-size units.
F. Product Schedule: For fiberglass windows. Use same designations indicated on Drawings.
G. Qualification Data: For manufacturer and Installer.
H. Product Test Reports: For each type of fiberglass window, for tests performed by a qualified testing agency.
cmiller Text Box Section revised as part of addendum D.
LASATA SENIOR LIVING CAMPUS – NEW CBRF FIBERGLASS WINDOWS
Project No. 24039 08 5413 - 2
I. Field quality-control reports.
J. Sample Warranties: For manufacturer's warranties.
1.4 QUALITY ASSURANCE
A. Manufacturer Qualifications: A manufacturer capable of fabricating fiberglass windows that meet or exceed performance requirements indicated and of documenting this performance by test reports and calculations.
B. Installer Qualifications: An installer acceptable to fiberglass window manufacturer for installation of units required for this Project.
C. Mockups: Build mockups to verify selections made under Sample submittals, to demonstrate aesthetic effects, and to set quality standards for materials and execution.
1. Build mockup of typical wall area as shown on Drawings.
2. Approval of mockups does not constitute approval of deviations from the Contract Documents contained in mockups unless Architect specifically approves such deviations in writing.
3. Subject to compliance with requirements, approved mockups may become part of the completed Work if undisturbed at time of Substantial Completion.
1.5 WARRANTY
A. Manufacturer's Warranty: Manufacturer agrees to repair or replace fiberglass windows that fail in materials or workmanship within specified warranty period.
1. Failures include, but are not limited to, the following:
a. Failure to meet performance requirements.
b. Structural failures including excessive deflection, water leakage, and air infiltration.
c. Faulty operation of movable sash and hardware.
d. Deterioration of materials and finishes beyond normal weathering.
e. Failure of insulating glass.
2. Warranty Period:
a. Window: 10 years from date of Substantial Completion.
b. Glazing Units, Non-Laminated: 20 years from date of Substantial Completion.
a. Glazing Units, Laminated: 10 years from date of Substantial Completion.
PART 2 - PRODUCTS
2.1 MANUFACTURERS
A. Source Limitations: Obtain fiberglass windows from single source from single manufacturer.
2.2 WINDOW PERFORMANCE REQUIREMENTS
A. Product Standard: Comply with AAMA/WDMA/CSA 101/I.S.2/A440 for definitions and minimum standards of performance, materials, components, accessories, and fabrication unless more stringent requirements are indicated.
LASATA SENIOR LIVING CAMPUS – NEW CBRF FIBERGLASS WINDOWS
Project No. 24039 08 5413 - 3
1. Window Certification: WDMA certified with label attached to each window.
B. Performance Class and Grade: AAMA/WDMA/CSA 101/I.S.2/A440 as follows:
1. Minimum Performance Class: LC.
2. Minimum Performance Grade: 30.
C. Thermal Transmittance: NFRC 100 maximum whole-window U-factor of 0.29 Btu/sq. ft. x h x deg F.
D. Solar Heat-Gain Coefficient (SHGC): NFRC 200 maximum whole-window SHGC of 0.36.
E. Sound Transmission Class (STC): Rated for not less than 24 STC when tested for laboratory sound transmission loss in accordance with ASTM E90 and determined by ASTM E413.
F. Outside-Inside Transmission Class (OITC): Rated for not less than 21 OITC when tested for laboratory sound transmission loss in accordance with ASTM E90 and determined by ASTM E1332.
2.3 FIBERGLASS WINDOWS
A. Basis-of-Design Product: Subject to compliance with requirements, provide Pella Corporation; Pella® Impervia® or a comparable product by one of the following:
1. Cascadia Windows.
2. Enerlux Windows & Doors.
3. Pella Corp.
4. Kolbe Windows & Doors. Forgent Series.
5. Or Approved Equal.
B. Accessible Units: Window operating hardware shall comply with A117.1 Chapter 309. Opening the window shall not require tight grasping, pinching, or twisting of the wrist; the force required to open the window shall not exceed 5.0 pounds.
C. Operating Types: Provide the following operating types in locations indicated on Drawings:
1. Double hung.
2. Operable.
D. Frames and Sashes: Pultruded fiberglass complying with AAMA/WDMA/CSA 101/I.S.2/A440 and with exposed exterior fiberglass surfaces finished with manufacturer's standard enamel coating complying with AAMA 624.
1. Exterior Color: White.
2. Interior Finish: White.
E. Glass: As specified in Section 08 8000 “Glazing.”.
F. Glazing System: Manufacturer's standard factory-glazing system that produces weathertight seal.
G. Hardware, General: Provide manufacturer's standard hardware fabricated from aluminum, stainless steel, carbon steel complying with AAMA 907, or other corrosion-resistant material compatible with adjacent materials; designed to smoothly operate, tightly close, and securely lock fiberglass windows, and sized to accommodate sash weight and dimensions.
1. Exposed Hardware Color and Finish: As selected by Architect from manufacturer's full range.
LASATA SENIOR LIVING CAMPUS – NEW CBRF FIBERGLASS WINDOWS
Project No. 24039 08 5413 - 4
H. Projected Window Hardware:
1. Gear-Type Rotary Operators: Complying with AAMA 901 when tested in accordance with ASTM E405, Method A. Provide operators that function without requiring the removal of interior screens or using screen wickets.
a. Type and Style: As selected by Architect from manufacturer's full range of types and styles.
2. Hinges: Manufacturer's standard type for sash weight and size indicated.
3. Single-Handle Locking System: Operates positive-acting arms that pull sash into locked position. Provide one arm on sashes up to 27-1/2 inches tall and two arms on taller sashes.
I. Hung Window Hardware:
1. Counterbalancing Mechanism: Complying with AAMA 902, concealed, of size and capacity to hold sash stationary at any open position.
2. Locks and Latches: Allow unobstructed movement of the sash across adjacent sash in direction indicated and operated from the inside only. Provide custodial locks.
3. Tilt Hardware: Releasing tilt latch allows sash to pivot about horizontal axis to facilitate cleaning exterior surfaces from the interior.
4. Limit Devices: Factory-Installed Opening Control Device per ASTM F2090-17
a. Limit clear opening to 4” for ventilation; with custodial key release.
J. Weather Stripping: Provide full-perimeter weather stripping for each operable sash unless otherwise indicated.
K. Fasteners: Noncorrosive and compatible with window members, trim, hardware, anchors, and other components.
1. Exposed Fasteners: Do not use exposed fasteners to greatest extent possible. For application of hardware, use fasteners that match finish hardware being fastened.
2.4 INSECT SCREENS
A. General: Fabricate insect screens to integrate with window frame. Provide screen for each operable exterior sash.
Screen wickets are not permitted.
1. Type and Location: Full, outside for double-hung sashes.
B. Aluminum Frames: Manufacturer's standard aluminum alloy complying with SMA 1004 or SMA 1201. Fabricate frames with mitered or coped joints or corner extrusions, concealed fasteners, and removable PVC spline/anchor concealing edge of frame.
1. Tubular Framing Sections and Cross Braces: Roll formed from aluminum sheet.
2. Finish for Interior Screens: Baked-on organic coating in color selected by Architect from manufacturer's full range.
3. Finish for Exterior Screens: Matching color and finish of unit.
C. Glass-Fiber Mesh Fabric: 18-by-14 mesh of PVC-coated, glass-fiber threads; woven and fused to form a fabric mesh resistant to corrosion, shrinkage, stretch, impact damage, and weather deterioration. Comply with
ASTM D3656/D3656M.
1. Mesh Color: Manufacturer's standard.
LASATA SENIOR LIVING CAMPUS – NEW CBRF FIBERGLASS WINDOWS
Project No. 24039 08 5413 - 5
2.5 FABRICATION
A. Fabricate fiberglass windows in sizes indicated. Include a complete system for installing and anchoring windows.
B. Glaze fiberglass windows in the factory.
C. Weatherstrip each operable sash to provide weathertight installation.
D. Complete fabrication, assembly, finishing, hardware application, and other work in the factory to greatest extent possible. Disassemble components only as necessary for shipment and installation. Allow for scribing, trimming, and fitting at Project site.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine openings, substrates, structural support, anchorage, and conditions, with Installer present, for compliance with requirements for installation tolerances and other conditions affecting performance of the Work.
B. Verify rough opening dimensions, levelness of sill plate, and operational clearances.
C. Examine wall flashings, vapor retarders, water and weather barriers, and other built-in components to ensure weathertight window installation.
D. Proceed with installation only after unsatisfactory conditions have been corrected.
3.2 INSTALLATION
A. Comply with manufacturer's written instructions for installing windows, hardware, accessories, and other components. For installation procedures and requirements not addressed in manufacturer's written instructions, comply with installation requirements in ASTM E2112.
B. Install windows level, plumb, square, true to line, without distortion, anchored securely in place to structural support, and in proper relation to wall flashing and other adjacent construction to produce weathertight construction.
3.3 FIELD QUALITY CONTROL
A. Testing Agency: Engage a qualified testing agency to perform tests and inspections.
1. Testing and inspecting agency will interpret tests and state in each report whether tested work complies with or deviates from requirements.
B. Testing Services: Testing and inspecting of installed windows shall take place as follows:
1. Testing Methodology: Testing of windows for air infiltration and water resistance shall be performed in accordance with AAMA 502.
2. Air-Infiltration Testing:
a. Test Pressure: That required to determine compliance with AAMA/WDMA/CSA 101/I.S.2/A440 performance class indicated.
LASATA SENIOR LIVING CAMPUS – NEW CBRF FIBERGLASS WINDOWS
Project No. 24039 08 5413 - 6
b. Allowable Air-Leakage Rate: 1.5 times the applicable AAMA/WDMA/CSA 101/I.S.2/A440 rate for product type and performance class rounded down to one decimal place.
3. Water-Resistance Testing:
a. Test Pressure: Two-thirds times test pressure required to determine compliance with AAMA/WDMA/CSA 101/I.S.2/A440 performance grade indicated.
b. Allowable Water Infiltration: No water penetration.
4. Testing Extent: Three windows of each type as selected by Architect and a qualified independent testing and inspecting agency. Windows shall be tested after perimeter sealants have cured.
5. Test Reports: Prepared in accordance with AAMA 502.
C. Windows will be considered defective if they do not pass tests and inspections.
D. Prepare test and inspection reports.
3.4 ADJUSTING, CLEANING, AND PROTECTION
A. Adjust operating sashes and hardware for a tight fit at contact points and weather stripping for smooth operation and weathertight closure.
B. Clean exposed surfaces immediately after installing windows. Remove excess sealants, glazing materials, dirt, and other substances.
1. Keep protective films and coverings in place until final cleaning.
C. Remove and replace sashes if glass has been broken, chipped, cracked, abraded, or damaged during construction period.
D. Protect window surfaces from contact with contaminating substances resulting from construction operations. If contaminating substances do contact window surfaces, remove contaminants immediately in accordance with manufacturer's written instructions.
END OF SECTION 08 5413
LASATA SENIOR LIVING CAMPUS – NEW CBRF PLASTIC-LAMINATE CABINETS, COUNTERTOPS & SHELVES Project No. 24039 12 3663-1
SECTION 12 3663 – PLASTIC-LAMINATE CABINETS, COUNTERTOPS & SHELVES
PART 1 - GENERAL
1.1 SUMMARY
A. This Section includes the following:
1. Plastic-laminate countertops.
2. Plastic-laminate cabinets.
3. Plastic-laminate shelving.
1.2 REFERENCES
A. Plastic Laminate: National Electrical Manufacturers Association (NEMA) Publication No. LD3-2005.
B. Particle Board Core: ANSI A208.1-2022.
C. Fiberboard Core: ANSI A208.2.
1.3 SUBMITTALS
A. Product Data: Manufacturer’s catalog information edited to indicate specific products and related accessories to be provided for this project.
B. Shop Drawings: Indicate dimensions, thicknesses, required clearances, tolerances, materials, colors, finishes, fabrication details, field joining, adjacent construction, methods of support, integration of plumbing components, and anchorages. Field measure for all components.
C. Samples:
1. Plastic-laminates, for each type, color, pattern, and surface finish.
1.4 QUALITY ASSURANCE
A. Fabricator Qualifications: Shop that employs skilled workers who specialize in fabricating products similar to those required for this Project and whose products have a record of successful in-service performance with a minimum of three (3) years documented experience.
1.5 DELIVERY, STORAGE AND HANDLING
A. Deliver items only when proper storage conditions will be available. Store in protected area until ready for installation.
B. Maintain optimum humidity and temperature conditions after receipt of materials.
C. Store in manner to allow free circulation of air around all items.
D. Maintain temperature of storage areas between 50 to 75 degrees Fahrenheit.
cmiller Text Box Section revised as part of addendum D.
Project No. 24039 12 3663-2
PART 2 - PRODUCTS
2.1 PLASTIC-LAMINATE MATERIALS
A. High-Pressure Decorative Laminate (HPDL) sheet bonded to substrate.
1. Plastic Sheet NEMA LD3, Grade HGP, 0.048 inch nominal thickness.
a. Manufacturers:
b. Surface Burning Characteristics: Flame spread index of 25, maximum; smoke developed index of 450, maximum; when tested in accordance with ASTM E84.
c. Finish: As indicated on Drawings.
d. Surface Color and Pattern: As indicated on Drawings.
2. Exposed Edge Treatment
3. Back and End Splashes: Same material, same construction.
2.2 PLASTIC-LAMINATE CABINETS
A. Bottoms, Sides and Subtop: 3/4 inch 45-47 pound density particle board.
B. Back Panel: 3/8 inch 45-47 pound density particle board.
C. Back panels rabbeted into sides, top and bottom. Secure with hot melt glue and mechanical fasteners.
D. Assemble tops and bottoms with concealed fasteners.
E. Provide finished panels at all exposed locations. Ands adjacent to appliances shall be considered as exposed ends.
F. Provide manufacturer’s standard construction to reinforce cabinets for all attachment; glued and mechanically fastened.
G. Door/Drawer Construction and Edging.
1. Door Fronts: 3/4-inch-thick core.
2. Exposed Edges, Endsplashes: Finished to match exposed face.
3. Laminate face/balancer to core with PVA rigid adhesives, under pressure, nor natural setting process. Heat process or contact adhesives not allowed.
4. Door/Drawer/Cabinet Body Edges: .020 inch laminate, hot melt applied.
5. Drawer Backs, Sides, Fronts: 1/2-inch thick 55 pound density fiberboard with white melamine overlay or hardboard with sealer and AWI premium finish.
6. Dovetail drawer fronts and backs, secure with glue.
7. Drawer Bottoms: 3/8-inch thick 45-47 pound density particle board.
8. Rabbet bottoms into sides, front and back; staple and glue.
9. Drawer fronts screwed on from drawer inside.
10. Drawer Reinforcement: 1/2-inch thick under-bottom stiffeners, 1 at 24 inch drawers, 2 at 36 inch drawers, 4 at
48 inch drawers.
11. Provide full extension glides at all drawer locations
H. Cabinet Hardware:
1. General: Manufacturer’s standard units complying with BHMA A156.9, of type, size, style, material, and finish as selected by Architect.
2. Pulls: As selected by Architect from manufacturer’s full range.
3. Hinges: Concealed European-stype self-closing hinges.
4. Drawer Guides: Epoxy-coated-metal, self-closing drawer guides; designed to prevent rebound when drawers are closed; with nylon-tied, ball-bearing rollers; and complying with BHMA A156.9, Type B05091.
Project No. 24039 12 3663-3
2.3 SHELVING
A. Shelves under 27 inches long: 3/4-inch-thick 45-47 pound density particle board.
B. Shelves over 27 inches long: 1-inch-thick pound density particle board.
C. Finished to match faces.
D. Edging: 0.20 inch laminate, hot melt applied.
2.4 FABRICATION
A. General: Complete fabrication to maximum extent possible before shipment to Project site. Where necessary for fitting at site, provide allowance for scribing, trimming, and fitting.
1. Shop cut openings to maximum extent possible. Sand edges of cutouts to remove splinters and burrs. Seal edges of openings with a coat of varnish.
B. Plastic-Laminate Countertops and Cabinets:
1. Fabricate tops and splashes in the largest sections practicable, with top surface of joints flush.
a. Join lengths of tops using best method recommended by manufacturer.
b. Fabricate to overhang fronts and ends of cabinets 1 inch except where top butts against cabinet or wall.
c. Prepare all cutouts accurately to size; replace tops having improperly dimensioned or unnecessary cutouts or fixture holes.
2. Provide back/end splash wherever counter edge abuts vertical surface unless otherwise indicated.
a. Secure to countertop with concealed fasteners and with contact surfaces set in waterproof glue.
b. Height: 4 inches unless otherwise indicated.
3. Cabinet parts shall be accurately machined utilizing hardwood dowels for premium quality grade joinery construction. Glue and mechanically fasten all joints for maximum rigidity.
4. All cabinets shall be square, plumb, true and self-supporting. Provide removable back panels and closure panels for plumbing access where indicated.
PART 3 - EXECUTION
3.1 EXAMINATION
A Do not begin installation until substrates have been properly prepared.
B. If substrate preparation is the responsibility of another installer, notify Architect of unsatisfactory preparation before proceeding.
C. Verify that wall surfaces have been finished and mechanical and electrical services and outlets are installed in proper locations.
D. Verify adequacy of backing and support framing.
E. Verify location and sizes of utility rough-ins associated with work in this Section.
3.2 PREPARATION
Project No. 24039 12 3663-4
A. Clean surfaces thoroughly prior to installation.
B. Prepare surfaces using the methods recommended by the manufacturer for achieving the best result for the substrate under the project conditions.
3.3 INSTALLATION
A. Remove and replace tops, backs, panels, shelves and other items necessary to allow sections to complete their work of connecting services.
B. Install components plumb, level, and true according to approved Shop Drawings and manufacturer’s published installation instructions. Use tools acceptable to manufacturer. Anchor securely.
C. Securely attach countertops to cabinets using concealed fasteners. Make flat surfaces level; shim where required.
D. Attach plastic laminate countertops using screws with minimum penetration into substrate board of 5/8 inch.
E. Seal joint between back/end splashes and vertical surfaces.
F. Provide all necessary fillers, panels, end panels, scribed required to make complete installation as detailed.
G. Seal joint between back/end splashes and vertical surfaces.
F. Install cabinets without distortion so doors and drawers fit openings properly and are accurately aligned. Adjust hardware to center doors and drawers in openings and to provide unencumbered operation.
G. Fasten wall cabinets through back, near top and bottom, at ends and not more than 16 inches o.c. with No. 10 wafer-head screws sized for 1-inch penetration into wood framing, blocking, or hanging strips.
3.4 TOLERANCES
A. Variation From Horizontal: 1/8 inch in 10 feet (3 mm in 3 m), maximum.
B. Offset From Wall, Countertops: 1/8 inch (3 mm) maximum; 1/16 inch (1.5 mm) minimum.
C. Where casework meets wall surfaces, set with uniform space not to exceed 1/8 inch.
D. Field Joints: 1/8 inch (3 mm) wide, maximum.
3.5 PROTECTION, REPAIRING AND CLEANING
A. Clean surfaces thoroughly. Use no acids or harsh abrasives.
B. Leave surfaces clean and without defects.
C. Protect installed products until completion of project.
D. Touch-up, repair or replace damaged products before Date of Substantial Completion.
END OF SECTION 12 3663
DU CHIEN
LA CROSSE
PRAIRIE
EAU CLAIRE
SUPERIOR
ASHLAND
FOND DU LAC
DODGEVILLE
JANESVILLE
MADISON
WISCONSIN
RICHLAND
CENTER
DELLS
WISCONSIN
TOMAH
RAPIDS
RACINE
KENOSHA
MILWAUKEE
APPLETON
OSHKOSH
SHEBOYGAN
MANITOWOC
FALLS
WAUSAU
STEVENS POINT
RHINELANDER
PARK
GREEN BAY
PROJECT 3D OVERVIEW
PROJECT/BUILDING DATA
BUILDING AREAS
NEW CBRF BUILDING AREA = 15,668 GSF
EXISTING RCAC WORK AREA = 1,450 GSF
BUILDING HEIGHT
TOTAL BUILDING HEIGHT = 24'-8"
NUMBER OF STORIES = 1 STORY
CONSTRUCTION TYPE
TYPE 5A
SPRINKLERS
BUILDING IS FULLY SPRINKLERED NFPA13
SITE DATA
ZONING: I-1 : INSTITUTIONAL AND PUBLIC SERVICE DISTRICT
ADDRESS: 677 WAUWATOSA RD,
CEDARBURG, WI 53012
SQUARE FOOTAGES
- LASATA CARE CENTER = 130,418 SF
- LASATA HEIGHTS PH1 = 91,776 SF (EST)
- LASATA HEIGHTS PH2 = 67,814 SF
- OUTBUILDINGS (GAZEBO, SHED, GARAGE) = 500 SF (EST)
- PROPOSED CBRF ADDITION = 15,668 SF
TOTAL = 306,176 SF
SITE COVERAGE
- TOTAL BUILDING AREA = 306,176 SF
- TOTAL SITE AREA = 22.476 AC = 979,054 SF
- FLOOR AREA RATIO = 31.2% FARARCHITECTURAL ABBREVIATIONS LEGEND
AB
AFF
ALT
ALUM
ARCH
BRD
BLK
BOT
CB
CIP
CJ
CL
CLG
CLJ
CLR
CMU
CO
COL
CONC
CONT
CPT
CU
DBL
DF
DIM
DN
DS
DTL
DWG
EA
EC
EIFS
EL
ELEV
ENG
EQ
EXIST
EXP
EXT
FD
FND
FE
FEC
FF
FIN
FLR
- AND
- AT
- ANCHOR BOLT
- ABOVE FINISH FLOOR
- ALTERNATE
- ALUMINUM
- ARCHITECT / ARCHITECTURAL
- BOARD
- BLOCK (CMU)
- BOTTOM
- CATCH BASIN
- CAST-IN-PLACE
- CONSTRUCTION JOINT
- CENTERLINE
- CEILING
- CONTROL JOINT
- CLEAR DISTANCE
- CONCRETE MASONRY UNIT
- CASED OPENING
- COLUMN
- CONCRETE
- CONTINUOUS
- COMMON PATH OF TRAVEL
- CUBIC
- DOUBLE
- DRINKING FOUNTAIN
- DIAMETER
- DOWN
- DOWN SPOUT
- DETAIL
- DRAWING
- EACH
- ELECTRICAL CONTRACTOR
- EXTERIOR INSULATION FINISH SYSTEM
- ELEVATION
- ELEVATOR
- ENGINEER
- EQUAL
- EXISTING
- EXPANSION
- EXTERIOR
- FLOOR DRAIN
- FOUNDATION
- FIRE EXTINGUISHER
- FIRE EXTINGUISHER CABINET
- FINISH FLOOR
- FINISH
- FLOOR
FND
FOM
FOS
FTG
FUT
FV
GA
GALV
GB
GC
GYP
HC
HM
HORIZ
HT
HVAC
HR
ID
I.F.
INSUL
INT
JBE
JT
L
LAM
LVL
MAX
MBW
MFG
MIN
MO
MTL
NIC
NOM
NTS
NO
OC
OD
O.F.
OH
OPCI
OPOI
OPNG
OPP
- FOUNDATION
- FACE OF MASONRY
- FACE OF STUD
- FOOTING
- FUTURE
- FIELD VERIFY
- GAUGE
- GALVANIZED
- GRAB BAR
- GENERAL CONTRACTOR
- GYPSUM
- HVAC CONTRACTOR
- HOLLOW METAL
- HORIZONTAL
- HEIGHT
- HEATING, VENTILATION & AIR CONDITIONING
- HOUR
- INSIDE DIAMETER
- INSIDE FACE
- INSULATION
- INTERIOR
- JOIST BEARING ELEVATION
- JOINT
- STEEL ANGLE DESIGNATION
- LAMINATE
- LAMINATED VENEER LUMBER
- MAXIMUM
- MASONRY BEARING WALL
- MANUFACTURER
- MINIMUM
- MASONRY OPENING
- METAL
- NOT IN CONTRACT
- NOMINAL
- NOT TO SCALE
- NUMBER
- ON CENTER
- OUTSIDE DIAMETER
- OUTSIDE FACE
- OVERHEAD
- OWNER PROVIDED, CONTRACTOR INSTALLED
- OWNER PROVIDED, OWNER INSTALLED
- OPENING
- OPPOSITE
PREFAB
PERIM
PC
P/C P/T
PT
PNL
PNV
R
RC
RD
REINF
REQD
RM
RNL
RNV
SCHED
SHT
SIM
SOG
SPEC
SQ
SS
STL
STR
THK
TOL
TOP
TP
TS
TYP
TOW
UL
UNO
VB
VERT
VIF
W W/ W/O
WC
WD
WRB
WWF
- PREFABRICATED
- PERIMETER
- PLUMBING CONTRACTOR
- PRECAST / PRESTRESSED
- POST TENSIONED
- PRESSURE TREATED
- PROVIDED NATURAL LIGHT
- PROVIDED NATURAL VENTILATION
- RADIUS
- RESILIENT CHANNEL
- ROOF DRAIN
- REINFORCING
- REQUIRED
- ROOM
- REQUIRED NATURAL LIGHT
- REQUIRED NATURAL VENTILATION
- SCHEDULE
- SHEET
- SIMILAR
- SLAB ON GRADE
- SPECIFICATION
- SQUARE
- STAINLESS STEEL
- STEEL
- STRUCTURAL
- THICKNESS
- TOP OF LEDGE ELEVATION
- TOP OF PIER ELEVATION
- TOILET PAPER DISPENSER
- (SEE HIGH STRENGTH STEEL
DESIGNATION)
- TYPICAL
- TOP OF WALL ELEVATION
- UNDERWRITERS LAB
- UNLESS NOTED OTHERWISE
- VAPOR BARRIER
- VERTICAL
- VERIFY IN FIELD
- WIDTH
- WITH
- WITHOUT
- WATER CLOSET
- WOOD
- WEATHER RESISTANT BARRIER
- WELDED WIRE FABRIC
WALL SECTION/
DETAIL REFERENCE
DETAIL / SECTION
NUMBER
SHEET
NUMBER
DETAIL
NUMBER
SHEET
NUMBER
WALL TYPE
DESIGNATION
SOUND
ATTENUATION
INSULATION
(IF APPLICABLE)
WALL RATING
(IF APPLICABLE)
SHEET
NUMBER
ELEVATION
NUMBER
REVISION NUMBER
AND CLOUD
STRUCTURAL
GRID LINE
DETAIL
REFERENCE
WALL
TYPES
DOOR
NUMBER
FLOOR
ELEVATION
MARKER
KEYNOTE
MARKERINTERIOR
ELEVATIONS
WINDOW TYPE
REFERENCE
ELEVATION
REFERENCE
STRUCTURAL
GRIDLINE
BUILDING
SECTION
REFERENCEROOM NAME
100'-0"
H 1t
S 1
1A
S 1
PROJECT
LOCATION -
CEDARBURG, WI
STATE MAP
VICINITY MAP PROJECT LOCATION -
LASATA SENIOR
LIVING CAMPUS,
CEDARBURG, WI
LASATA
CARE
CENTER
LASATA
HEIGHTS
CODE INFORMATION SUMMARY
APPLICABLE CODE
2015 INTERNATIONAL BUILDING CODE WITH WI AMMENDMENTS
2015 INTERNATIONAL EXISTING BUILDING CODE WITH WI AMMENDMENTS
2009 AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI) A117.1
WISCONSIN ADMINISTRATIVE CODE DHS CHAPTER 83 - CBRF FACILITIES
OCCUPANCY CLASSIFICATION - IBC 2015-CHAPTER 3
I-2 - INSTITUTIONAL (CBRF - CNA LICENSE)
21 RESIDENTS = LARGE CBRF PER DHS 83.04
CLASS C NON-AMBULATORY (CNA)
ALLOWABLE HEIGHTS & AREAS - IBC 2015-CHAPTER 5
ALLOWABLE HEIGHT ABOVE GRADE PLANE = 50'-0"
ACTUAL BUILDING HEIGHT ABOVE GRADE PLANE = 24'-8"
ALLOWABLE STORIES ABOVE GRADE PLANE = 1 PER DHS MEMO P-03538(1/2024)
ACTUAL BUILDING STORIES ABOVE GRADE PLANE = 1
FRONTAGE INCREASE = NOT USED
ALLOWABLE FLOOR AREA = 38,000 SF
ACTUAL BUILDING FLOOR AREA = 15,668 SF (NEW CBRF)
CONSTRUCTION TYPE & FIRE RESISTANCE RATINGS - IBC 2015-CHAPTER 6
TYPE-VA - PROTECTED WOOD FRAME
STRUCTURAL FRAME = 1 HOUR
EXTERIOR BEARING WALLS = 1 HOUR
INTERIOR BEARING WALLS = 1 HOUR
FLOOR ASSEMBLIES = 1 HOUR
ROOF ASSEMBLIES = 1 HOUR
FIRE & SMOKE PROTECTION FIRE RATINGS - CHAPTER 7
FIRE WALL: 2 HOUR
FIRE BARRIER: 2 HOUR
FIRE PARTITION: 1 HOUR
SMOKE BARRIER: 1 HOUR
SMOKE PARTITION: NO RATING REQUIRED
CORRIDOR WALL: 1 HOUR
DWELLING UNIT SEPARATION: 1 HOUR
ATTIC DRAFT STOPPING: DRAFTSTOPPING NOT REQUIRED IN BUILDINGS
EQUIPPED WITH AUTOMATIC SPRINKLER SYSTEM SECTION 903.1.1
FIREBLOCKING IN CONCEALED WALL SPACES: VERTICALLY AT CEILING AND
FLOOR LEVELS, HORIZONTALLY AT INTERVALS NOT EXCEEDING 10 FT.
FIRE SPRINKLER - IBC 2015 - CHAPTER 9
BUILDING IS FULLY SPRINKLERED
NFPA 13 = ENTIRE BUILDING
MANUAL FIRE ALARM = SHALL BE PROVIDED IN ACCORDANCE
WITH SECTION 907.2.6
AUTOMATIC FIRE DETECTION = SHALL BE PROVIDED AT CORRIDORS
PER SECTION 907.2.6.2
SEE CODE COMPLIANCE PLANS FOR ADDITIONAL INFORMATION
RCAC KITCHEN
AREA; SEE A5.4
WORK AREA
1,450 SF
KEY PLAN
LASATA CROSSINGS;
EXISTING RCAC BUILDING
NEW CBRF
BUILDING
N
RCAC ALTERATIONS TO BE
SUBMITTED TO DHS IN A
SEPARATE APPLICATION.
RCAC UNIT
MODIFICATION;
SEE A1.1B
WORK AREA
500 SF
6515 Grand Teton Plaza, Suite 120, Madison, Wisconsin 53719 p608.829.4444 f608.829.4445 dimensionivmadison.com
GENERAL
D G0.1 COVER SHEET
A G-0.2 RCAC AREA OF WORK KEY PLANS
G0.2 GENERAL ACCESSIBILITY REQUIRMENTS
C G1.1 CODE COMPLIANCE PLAN
C G1.2 CODE COMPLIANCE PLAN (LIGHT AND VENT)
CIVIL
C1.0 SITE PLAN
C1.1 EMERGENCY ACCESS PLAN
C2.0 SITE GRADING PLAN
C3.0 SITE UTILITY PLAN
C3.1 PUBLIC WATER MAIN PLAN
C4.0 SITE EROSION CONTROL PLAN
C5.0 SITE DETAILS
LSP1.0 GENERAL NOTES, SITE INFO, & PLANT MATERIAL
TABLES
LSP1.1 PROPOSED LANDSCAPE PLAN
LSP1.2 PROPOSED LANDSCAPE PLAN, PLANTING
DETAILS
V1.0 EXISTING CONDITIONS MAP
STRUCTURAL
S0.1 STRUCTURAL NOTES
A S0.2 STRUCTURAL SCHEDULES
S1.0 OVERALL FOUNDATION PLAN
S1.1 FOUNDATION PLAN - AREA A
S1.2 FOUNDATION PLAN - AREA B
S1.3 FOUNDATION PLAN - AREA C
S3.0 OVERALL ROOF FRAMING PLAN
A S3.1 ROOF FRAMING PLAN - AREA A
S3.2 ROOF FRAMING PLAN - AREA B
S3.3 ROOF FRAMING PLAN - AREA C
A S3.4 PLANS & DETAILS AT EXISTING KITCHEN
A S4.1 DINING ROOM MECH PLATFORM SECTIONS
S5.1 FOUNDATION DETAILS
S5.2 FOUNDATION DETAILS
A S5.3 FOUNDATION DETAILS
S6.1 MASONRY DETAILS
A S8.1 MECH PLATFORM STEEL DETAILS
S9.1 WOOD DETAILS
S9.2 WOOD DETAILS
S9.3 WOOD DETAILS
ARCHITECTURAL
D A1.1 FIRST FLOOR OVERALL PLAN
C A1.1A FIRST FLOOR PLAN_AREA A
A1.1B FIRST FLOOR PLAN_AREA B
C A1.1C FIRST FLOOR PLAN_AREA C
A1.2 ROOF PLAN
A2.0 EXTERIOR ELEVATIONS
A2.1 EXTERIOR ELEVATIONS
A3.0 BUILDING SECTIONS
A3.1 BUILDING SECTIONS
A3.2 BUILDING SECTIONS
A3.3 WALL SECTIONS
A3.4 EXTERIOR STAIR AND RAMP SECTIONS
A4.1 FIRST FLOOR REFLECTED CEILING PLAN
C A5.0 UNIT FLOOR PLANS
A A5.2 ENLARGED RAMP CONNECTION FLOOR PLANS &
DETAILS
A5.3 ENLARGED CANOPY PLANS & DETAILS
A A5.4 RCAC ENLARGED PLANS AND DETAILS
A A5.5 RCAC ENLARGED PLANS AND DETAILS
A A5.6 RCAC ENLARGED PLANS AND DETAILS
A6.0 ASSEMBLY TYPES
A A6.1 ASSEMBLY TYPES
D A6.2 DOOR SCHEDULES
D A6.3 WINDOW TYPES & ELEVATIONS
A6.4 WINDOW AND DOOR DETAILS
D A7.0 INTERIOR ELEVATIONS
D A7.1 INTERIOR ELEVATIONS
A8.0 DETAILS
A8.1 DETAILS
A8.2 DETAILS
A8.3 TRASH ENCLOSURE PLAN
D A9.0 FINISH SCHEDULE AND FINISH LIST
A9.1A FIRST FLOOR FINISH PLAN AREA A
A9.1B FIRST FLOOR FINISH PLAN AREA B
A9.1C FIRST FLOOR FINISH PLAN AREA C
FIRE PROTECTION
F0.0 SYMBOLS, ABBREVIATIONS AND NOTES - FIRE
PROTECTION
F1.0 RCAC KITCHEN PLAN - FIRE PROTECTION
F2.0 FIRST FLOOR PLAN - FIRE PROTECTION
PLUMBING
P0.0 SYMBOLS AND ABBREVIATIONS - PLUMBING
C P1.0 RCAC KITCHEN PLANS - PLUMBING
C P1.1 NEW WORK KITCHEN PLANS - PLUMBING
P2.0 UNDERFLOOR PLAN - PLUMBING
P2.0A UNDERFLOOR PLAN - AREA A - PLUMBING
P2.0B UNDERFLOOR PLAN - AREA B - PLUMBING
P2.0C UNDERFLOOR PLAN - AREA C - PLUMBING
P2.1 FIRST FLOOR PLAN - PLUMBING
P2.1A FIRST FLOOR PLAN - AREA A - PLUMBING
P2.1B FIRST FLOOR PLAN - AREA B - PLUMBING
P2.1C FIRST FLOOR PLAN - AREA C - PLUMBING
P2.2 ROOF PLAN - PLUMBING
P3.1 ENLARGED PLANS - PLUMBING
P4.0 WASTE AND VENT ISOMETRIC - AREA A -
PLUMBING
P4.1 WASTE AND VENT ISOMETRIC - AREA B -
PLUMBING
P4.2 WASTE AND VENT ISOMETRIC - AREA C -
PLUMBING
P4.3 DOMESTIC WATER ISOMETRIC - AREA C -
PLUMBING
P4.4 DOMESTIC WATER ISOMETRIC - AREA B -
PLUMBING
P4.5 DOMESTIC WATER ISOMETRIC - AREA A -
PLUMBING
P4.6 STORM ISOMETRIC - AREA A - PLUMBING
C P4.7 KITCHEN WASTE AND VENT ISOMETRIC -
PLUMBING
C P4.8 KITCHEN DOMESTIC WATER ISOMETRIC -
PLUMBING
P8.0 SCHEDULES - PLUMBING
P9.0 DETAILS - PLUMBING
MECHANICAL
M0.0 SYMBOLS AND ABBREVIATIONS - HVAC
A M1.0 BASEMENT PLAN - HVAC
A M1.1 KITCHEN PLAN-HVAC
A M1.2 KITCHEN ROOF HVAC
M2.0 FIRST FLOOR PLAN - HVAC DUCT
A M2.0A FIRST FLOOR PLAN - AREA A - HVAC DUCT
M2.0B FIRST FLOOR PLAN - AREA B - HVAC DUCT
M2.0C FIRST FLOOR PLAN - AREA C - HVAC DUCT
M2.1 FIRST FLOOR PLAN - HVAC PIPING
M2.1A FIRST FLOOR PLAN - AREA A - HVAC PIPING
M2.1B FIRST FLOOR PLAN - AREA B - HVAC PIPING
M2.1C FIRST FLOOR PLAN - AREA C - HVAC PIPING
M2.2 ROOF PLAN - HVAC
B M7.0 CONTROLS - SCHEMATICS - HVAC
B M7.1 CONTROLS - SCHEMATICS - HVAC
A M7.2 CONTROLS - SCHEMATICS - HVAC
B M7.3 CONTROLS - SCHEMATICS - HVAC
A M8.0 SCHEDULES - HVAC
A M8.1 SCHEDULES - HVAC
M9.0 DETAILS - HVAC
A M9.1 DETAILS - HVAC
A M9.2 DETAILS - HVAC
ELECTRICAL
E0.0 SYMBOLS AND ABBREVIATIONS - ELECTRICAL
E0.1 SITE PLAN - ELECTRICAL
C E1.0 RCAC KITCHEN PLANS - ELECTRICAL
C E1.1 NEW WORK KITCHEN PLANS - ELECTRICAL
E2.0 FIRST FLOOR PLAN - LIGHTING - OVERALL
E2.0A FIRST FLOOR PLAN - AREA A - LIGHTING
C E2.0B FIRST FLOOR PLAN - AREA B - LIGHTING
C E2.0C FIRST FLOOR PLAN - AREA C - LIGHTING
E2.1A FIRST FLOOR PLAN - AREA A - POWER
E2.1B FIRST FLOOR PLAN - AREA B - POWER
E2.1C FIRST FLOOR PLAN - AREA C - POWER
E2.2 FIRST FLOOR PLAN - SYSTEMS - OVERALL
E2.2A FIRST FLOOR PLAN - AREA A - SYSTEMS
E2.2B FIRST FLOOR PLAN - AREA B - SYSTEMS
E2.2C FIRST FLOOR PLAN - AREA C - SYSTEMS
REVISIONS
A ADDENDUM A - RCAC 06/30/2025
B ADDENDUM B - SPECIFICATIONS 07/16/2025
C ADDENDUM C 07/31/2025
D ADDENDUM D 08/08/2025
E2.3 ROOF PLAN - ELECTRICAL
E6.0 ONE-LINE DIAGRAM AND SCHEMATICS
A E8.0 SCHEDULES - PANELS
A E8.1 SCHEDULES - PANELS
A E8.2 SCHEDULES - PANELS
E8.3 ELECTRICAL DETAILS
A E8.4 SCHEDULES - EQUIPMENT AND LIGHTING
FOOD SERVICE AND EQUIPMENT
FS100 KITCHEN - LAYOUT AND PLUMBING ROUGH-INS
FS101 KITCHEN - ELECTRICAL ROUGH-INS AND BWP
FS200 PANTRY - LAYOUT AND ELECTRICAL ROUGH-INS
FS300 FOODSERVICE STORAGE - LAYOUT AND
ELECTRICAL ROUGH-INS
FS400 FOODSERVICE MEP SCHEDULE
FS500 FOODSERVICE ELEVATIONS AND DETAILS
FS600 FOODSERVICE DETAILS
FS700 EXHAUST HOOD SHOP DRAWINGS
D
DU CHIEN
LA CROSSE
PRAIRIE
EAU CLAIRE
SUPERIOR
ASHLAND
FOND DU LAC
DODGEVILLE
JANESVILLE
MADISON
WISCONSIN
RICHLAND
CENTER
DELLS
WISCONSIN
TOMAH
RAPIDS
RACINE
KENOSHA
MILWAUKEE
APPLETON
OSHKOSH
SHEBOYGAN
MANITOWOC
FALLS
WAUSAU
STEVENS POINT
RHINELANDER
PARK
GREEN BAY
ARCHITECTURAL ABBREVIATIONS LEGEND
AB
AFF
ALT
ALUM
ARCH
BRD
BLK
BOT
CB
CIP
CJ
CL
CLG
CLJ
CLR
CMU
CO
COL
CONC
CONT
CPT
CU
DBL
DF
DIM
DN
DS
DTL
DWG
EA
EC
EIFS
EL
ELEV
ENG
EQ
EXIST
EXP
EXT
FD
FND
FE
FEC
FF
FIN
FLR
- AND
- AT
- ANCHOR BOLT
- ABOVE FINISH FLOOR
- ALTERNATE
- ALUMINUM
- ARCHITECT / ARCHITECTURAL
- BOARD
- BLOCK (CMU)
- BOTTOM
- CATCH BASIN
- CAST-IN-PLACE
- CONSTRUCTION JOINT
- CENTERLINE
- CEILING
- CONTROL JOINT
- CLEAR DISTANCE
- CONCRETE MASONRY UNIT
- CASED OPENING
- COLUMN
- CONCRETE
- CONTINUOUS
- COMMON PATH OF TRAVEL
- CUBIC
- DOUBLE
- DRINKING FOUNTAIN
- DIAMETER
- DOWN
- DOWN SPOUT
- DETAIL
- DRAWING
- EACH
- ELECTRICAL CONTRACTOR
- EXTERIOR INSULATION FINISH SYSTEM
- ELEVATION
- ELEVATOR
- ENGINEER
- EQUAL
- EXISTING
- EXPANSION
- EXTERIOR
- FLOOR DRAIN
- FOUNDATION
- FIRE EXTINGUISHER
- FIRE EXTINGUISHER CABINET
- FINISH FLOOR
- FINISH
- FLOOR
FND
FOM
FOS
FTG
FUT
FV
GA
GALV
GB
GC
GYP
HC
HM
HORIZ
HT
HVAC
HR
ID
I.F.
INSUL
INT
JBE
JT
L
LAM
LVL
MAX
MBW
MFG
MIN
MO
MTL
NIC
NOM
NTS
NO
OC
OD
O.F.
OH
OPCI
OPOI
OPNG
OPP
- FOUNDATION
- FACE OF MASONRY
- FACE OF STUD
- FOOTING
- FUTURE
- FIELD VERIFY
- GAUGE
- GALVANIZED
- GRAB BAR
- GENERAL CONTRACTOR
- GYPSUM
- HVAC CONTRACTOR
- HOLLOW METAL
- HORIZONTAL
- HEIGHT
- HEATING, VENTILATION & AIR CONDITIONING
- HOUR
- INSIDE DIAMETER
- INSIDE FACE
- INSULATION
- INTERIOR
- JOIST BEARING ELEVATION
- JOINT
- STEEL ANGLE DESIGNATION
- LAMINATE
- LAMINATED VENEER LUMBER
- MAXIMUM
- MASONRY BEARING WALL
- MANUFACTURER
- MINIMUM
- MASONRY OPENING
- METAL
- NOT IN CONTRACT
- NOMINAL
- NOT TO SCALE
- NUMBER
- ON CENTER
- OUTSIDE DIAMETER
- OUTSIDE FACE
- OVERHEAD
- OWNER PROVIDED, CONTRACTOR INSTALLED
- OWNER PROVIDED, OWNER INSTALLED
- OPENING
- OPPOSITE
PREFAB
PERIM
PC
P/C P/T
PT
PNL
PNV
R
RC
RD
REINF
REQD
RM
RNL
RNV
SCHED
SHT
SIM
SOG
SPEC
SQ
SS
STL
STR
THK
TOL
TOP
TP
TS
TYP
TOW
UL
UNO
VB
VERT
VIF
W W/ W/O
WC
WD
WRB
WWF
- PREFABRICATED
- PERIMETER
- PLUMBING CONTRACTOR
- PRECAST / PRESTRESSED
- POST TENSIONED
- PRESSURE TREATED
- PROVIDED NATURAL LIGHT
- PROVIDED NATURAL VENTILATION
- RADIUS
- RESILIENT CHANNEL
- ROOF DRAIN
- REINFORCING
- REQUIRED
- ROOM
- REQUIRED NATURAL LIGHT
- REQUIRED NATURAL VENTILATION
- SCHEDULE
- SHEET
- SIMILAR
- SLAB ON GRADE
- SPECIFICATION
- SQUARE
- STAINLESS STEEL
- STEEL
- STRUCTURAL
- THICKNESS
- TOP OF LEDGE ELEVATION
- TOP OF PIER ELEVATION
- TOILET PAPER DISPENSER
- (SEE HIGH STRENGTH STEEL
DESIGNATION)
- TYPICAL
- TOP OF WALL ELEVATION
- UNDERWRITERS LAB
- UNLESS NOTED OTHERWISE
- VAPOR BARRIER
- VERTICAL
- VERIFY IN FIELD
- WIDTH
- WITH
- WITHOUT
- WATER CLOSET
- WOOD
- WEATHER RESISTANT BARRIER
- WELDED WIRE FABRIC
WALL SECTION/
DETAIL REFERENCE
DETAIL / SECTION
NUMBER
SHEET
NUMBER
DETAIL
NUMBER
SHEET
NUMBER
WALL TYPE
DESIGNATION
SOUND
ATTENUATION
INSULATION
(IF APPLICABLE)
WALL RATING
(IF APPLICABLE)
SHEET
NUMBER
ELEVATION
NUMBER
REVISION NUMBER
AND CLOUD
STRUCTURAL
GRID LINE
DETAIL
REFERENCE
WALL
TYPES
DOOR
NUMBER
FLOOR
ELEVATION
MARKER
KEYNOTE
MARKERINTERIOR
ELEVATIONS
WINDOW TYPE
REFERENCE
ELEVATION
REFERENCE
STRUCTURAL
GRIDLINE
BUILDING
SECTION
REFERENCEROOM NAME
100'-0"
H 1t
S 1
1A
S 1
PROJECT
LOCATION -
CEDARBURG, WI
STATE MAP
VICINITY MAP PROJECT LOCATION -
LASATA SENIOR
LIVING CAMPUS,
CEDARBURG, WI
LASATA
CARE
CENTER
LASATA
HEIGHTS
PROJECT/BUILDING DATA
BUILDING AREAS
NEW CBRF BUILDING AREA = 15,668 GSF - SEPARATE SUBMITTAL
EXISTING RCAC WORK AREA = 1,950 GSF
FIRST FLOOR
KITCHEN = 1,245 GSF
UNIT = 460 GSF
THIRD FLOOR
SPA & ROOFTOP = 245 GSF
EXISTING BUILDING HEIGHT (NO CHANGE)
EXISTING NUMBER OF STORIES (NO CHANGE)
EXISTING OCCUPANCY (NO CHANGE)
EXISTING CONSTRUCTION TYPE - TYPE 5A (NO CHANGE)
BUILDING IS FULLY SPRINKLERED NFPA13 (NO CHANGE)
NOTE TO REVIEWER
- THIS SUBMITTAL IS FOR A LEVEL 2 ALTERATION TO THE EXISTING LASATA
HEIGHTS RCAC BUILDING. THIS PROJECT IS PART OF AN OVERALL PROJECT
INCLUDING CONSTRUCTION OF A NEW CBRF THAT CONNECTS TO THE
EXISTING LASATA HEIGHTS BUILDING. THE CBRF AND RCAC PROJECTS ARE
PART OF A SINGLE DRAWING SET, BUT SUBMITTED TO DHS SEPARATELY.
THIS SUBMITTAL INCLUDES THE LIMITED SELECTION OF DRAWINGS
RELATING TO THE RCAC WORK AS WELL AS ADDITIONAL DRAWINGS FOR
PLAN REVIEWER REFERENCE THAT ARE NOT LISTED IN THE SHEET LIST OR
INCLUDED IN THE FOR CONSTRUCTION SET.
SCOPE OF RCAC REVIEW:
- MODIFY UNIT R116 AND R117 AT THE CONNECTION TO THE NEW CBRF
BUILDING.
- KITCHEN AND DINING ROOM ALTERATION.
- ADDITION OF ROOFTOP MECHANICAL EQUIPMENT PLATFORM FOR MAKEUP
AIR AND EXHAUST FAN.
- ADD MAINTENANCE ROOF ACCESS DOOR TO 3RD FLOOR SPA ROOM R332.
RCAC KITCHEN AREA WORK
AREA = 1,245 SF
RCAC 3RD FLOOR SPA = 245 SF;
SEE A5.4 & A5.5
KEY PLAN
LASATA CROSSINGS;
EXISTING RCAC BUILDING
PART OF SEPERATE
SUBMITTAL NEW
CBRF BUILDING
N
RCAC UNIT
MODIFICATION; SEE A5.6
WORK AREA = 460 SF
NEW CBRF -
SEPERATE SUBMITTAL
EXISTING RCACPROJECT 3D OVERVIEW
6515 Grand Teton Plaza, Suite 120, Madison, Wisconsin 53719
GENERAL
D G0.1 COVER SHEET
A G-0.2 RCAC AREA OF WORK KEY PLANS
G0.2 GENERAL ACCESSIBILITY REQUIRMENTS
C G1.1 CODE COMPLIANCE PLAN
C G1.2 CODE COMPLIANCE PLAN (LIGHT AND VENT)
CIVIL
C1.0 SITE PLAN
C1.1 EMERGENCY ACCESS PLAN
C2.0 SITE GRADING PLAN
C3.0 SITE UTILITY PLAN
C3.1 PUBLIC WATER MAIN PLAN
C4.0 SITE EROSION CONTROL PLAN
C5.0 SITE DETAILS
LSP1.0 GENERAL NOTES, SITE INFO, & PLANT MATERIAL
TABLES
LSP1.1 PROPOSED LANDSCAPE PLAN
LSP1.2 PROPOSED LANDSCAPE PLAN, PLANTING
DETAILS
V1.0 EXISTING CONDITIONS MAP
STRUCTURAL
S0.1 STRUCTURAL NOTES
A S0.2 STRUCTURAL SCHEDULES
S1.0 OVERALL FOUNDATION PLAN
S1.1 FOUNDATION PLAN - AREA A
S1.2 FOUNDATION PLAN - AREA B
S1.3 FOUNDATION PLAN - AREA C
S3.0 OVERALL ROOF FRAMING PLAN
A S3.1 ROOF FRAMING PLAN - AREA A
S3.2 ROOF FRAMING PLAN - AREA B
S3.3 ROOF FRAMING PLAN - AREA C
A S3.4 PLANS & DETAILS AT EXISTING KITCHEN
A S4.1 DINING ROOM MECH PLATFORM SECTIONS
S5.1 FOUNDATION DETAILS
S5.2 FOUNDATION DETAILS
A S5.3 FOUNDATION DETAILS
S6.1 MASONRY DETAILS
A S8.1 MECH PLATFORM STEEL DETAILS
S9.1 WOOD DETAILS
S9.2 WOOD DETAILS
S9.3 WOOD DETAILS
ARCHITECTURAL
D A1.1 FIRST FLOOR OVERALL PLAN
C A1.1A FIRST FLOOR PLAN_AREA A
A1.1B FIRST FLOOR PLAN_AREA B
C A1.1C FIRST FLOOR PLAN_AREA C
A1.2 ROOF PLAN
A2.0 EXTERIOR ELEVATIONS
A2.1 EXTERIOR ELEVATIONS
A3.0 BUILDING SECTIONS
A3.1 BUILDING SECTIONS
A3.2 BUILDING SECTIONS
A3.3 WALL SECTIONS
A3.4 EXTERIOR STAIR AND RAMP SECTIONS
A4.1 FIRST FLOOR REFLECTED CEILING PLAN
C A5.0 UNIT FLOOR PLANS
A A5.2 ENLARGED RAMP CONNECTION FLOOR PLANS &
DETAILS
A5.3 ENLARGED CANOPY PLANS & DETAILS
A A5.4 RCAC ENLARGED PLANS AND DETAILS
A A5.5 RCAC ENLARGED PLANS AND DETAILS
A A5.6 RCAC ENLARGED PLANS AND DETAILS
A6.0 ASSEMBLY TYPES
A A6.1 ASSEMBLY TYPES
D A6.2 DOOR SCHEDULES
D A6.3 WINDOW TYPES & ELEVATIONS
A6.4 WINDOW AND DOOR DETAILS
D A7.0 INTERIOR ELEVATIONS
D A7.1 INTERIOR ELEVATIONS
A8.0 DETAILS
A8.1 DETAILS
A8.2 DETAILS
A8.3 TRASH ENCLOSURE PLAN
D A9.0 FINISH SCHEDULE AND FINISH LIST
A9.1A FIRST FLOOR FINISH PLAN AREA A
A9.1B FIRST FLOOR FINISH PLAN AREA B
A9.1C FIRST FLOOR FINISH PLAN AREA C
FIRE PROTECTION
F0.0 SYMBOLS, ABBREVIATIONS AND NOTES - FIRE
PROTECTION
F1.0 RCAC KITCHEN PLAN - FIRE PROTECTION
F2.0 FIRST FLOOR PLAN - FIRE PROTECTION
PLUMBING
P0.0 SYMBOLS AND ABBREVIATIONS - PLUMBING
C P1.0 RCAC KITCHEN PLANS - PLUMBING
C P1.1 NEW WORK KITCHEN PLANS - PLUMBING
P2.0 UNDERFLOOR PLAN - PLUMBING
P2.0A UNDERFLOOR PLAN - AREA A - PLUMBING
P2.0B UNDERFLOOR PLAN - AREA B - PLUMBING
P2.0C UNDERFLOOR PLAN - AREA C - PLUMBING
P2.1 FIRST FLOOR PLAN - PLUMBING
P2.1A FIRST FLOOR PLAN - AREA A - PLUMBING
P2.1B FIRST FLOOR PLAN - AREA B - PLUMBING
P2.1C FIRST FLOOR PLAN - AREA C - PLUMBING
P2.2 ROOF PLAN - PLUMBING
P3.1 ENLARGED PLANS - PLUMBING
P4.0 WASTE AND VENT ISOMETRIC - AREA A -
PLUMBING
P4.1 WASTE AND VENT ISOMETRIC - AREA B -
PLUMBING
P4.2 WASTE AND VENT ISOMETRIC - AREA C -
PLUMBING
P4.3 DOMESTIC WATER ISOMETRIC - AREA C -
PLUMBING
P4.4 DOMESTIC WATER ISOMETRIC - AREA B -
PLUMBING
P4.5 DOMESTIC WATER…