Addendum 4 provides clarification and modifications to the original project scope. Key details include revised product specifications for the field lighting fixtures and poles, changes to the project timeline with a new bid due date of June 1st, and the addition of a mandatory pre-bid conference scheduled for May 15th. The project term is 1 year with up to 3 optional 1-year renewals. No other significant changes have been made to the original solicitation requirements or evaluation criteria.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

City of Peachtree City 151 Willowbend Road Peachtree City, GA 30269 Phone: 770-631-2515 Fax: 770-631-2507 PeachtreeCityGA.gov Purchasing Department

CITY OF PEACHTREE CITY

MEADE FIELD LIGHTING REPLACEMENT PROJECT

24-104BRS

ADDENDUM #4

SECOND REVISED BID DUE DATE: The date for submittal of bids has been extended to Thursday, March 14, 2024, at 3:00 pm local time.

APPROVED ALTERNATIVE: City staff was asked to review Ephesus Lighting as an approved alternative. The City’s response is as follows:

Based on the data you originally supplied and the responses to our follow up questions, staff approves Ephesus as an approved alternative with the following point of clarification:

The City’s bid specifications are clear, the only acceptable product is one with the maintenance ability of having the driver and ballasts at the bottom of the pole and not the top by the light. To offer/supply any other product would not be acceptable.

In addition, as Ephesus Lighting is approved as an alternative, any award for construction using Ephesus Lighting product will include all submitted documentation of compliance with the project specifications. If this product is part of the winning bid a signed copy of the Submittal Checklist will be required prior to award.

1. QUESTION: The electrical plans call for replacing all electrical feeders to poles.

That said, the Ephesus system’s wattage per pole and total system wattage is less than or equal to the currently installed system and the newly specified LED system. If the current electrical system will support our LED product as designed then does this infrastructure need to be included in our bid? It would seem to be an awful waste of money. Our system’s total kW is 65.96 as per our lighting design while the basis of design’s kW is listed at 73.54 per spec which may be necessitating the electrical engineer’s requirement that it be replaced. CITY’S RESPONSE: Yes, all of the electrical work shown on the design plans shall be included in the proposed bid. The City has elected to replace all of these components because of their age, not due to a change in electrical load.

2. QUESTION: Specification section 1.4, D dictates light spill and candela criteria

150’ away from the fields. Ephesus lighting systems are installed at existing facilities throughout the state of GA (see attached submittal for partial list) using our “playability” focused lighting and product design which balances the needs of the players, spectators, and surrounding community. Instead, the basis of design uses a much less efficient product and lighting design. The result in this case is that the electrical infrastructure now must be changed out as part of the project due to their inefficient product. Will our system as designed be acceptable?

CITY’S RESPONSE: All proposed alternative products must meet all of the requirements stated in the project bid documents. This includes all of the elements listed in Section 1.4 Environmental Light Control on sheet E000.

The fields are located next to a residential neighborhood and therefore, light spill away from the fields is a matter of concern to the City.

3. CLARIFICATION: The selected lighting design will have to provide targeted up lighting for all fields per Section 1.4 B on sheet E000.

4. CLARIFICATION: The Bid Bond Form needs to be amended. See attached for revised bid due date.

Attachment: Amended Bid Bond Form Ephesus Documents

5 March 2024

Jim Meade Memorial Fields softball fields lighting replacement

24-104PRS

00 43 13-1

AMENDED BID SECURITY FORM

SECTION 00 43 13

BID SECURITY FORM

BIDDER (Name and Address):

SURETY (Name and Address of Principal Place of Business):

OWNER (Name and Address):

BID

City of Peachtree City 151 Willowbend Road Peachtree City, GA 30269

Bid Due Date: March 14 (amended), 2024/3:00 pm local time

Description:

Replace site lighting for Jim Meade Field girls softball lights and electrical service components as detailed in plans.

BOND

Bond Number:

Date (Not earlier than Bid due date):

Penal sum $

(Words) (Figures)

Surety and Bidder, intending to be legally bound hereby, subject to the terms set forth below, do each cause this Bid Bond to be duly executed by an authorized officer, agent, or representative.

BIDDER SURETY

(Seal) (Seal)

Bidder’s Name and Corporate Seal Surety’s Name and Corporate Seal

By: By:

Signature Signature (Attach Power of Attorney)

Print Name Print Name

Title Title

Attest: Attest:

Signature Signature

Title Title

Jim Meade Memorial Fields softball fields lighting replacement 00 43 13-2

24-104PRS BID SECURITY FORM

Note: Surety companies executing bonds must appear on the Treasury Department’s most current list (Circular 570 as amended) and be authorized to transact business in the state where the project is located.

1. Bidder and Surety, jointly and severally, bind themselves, their heirs, executors, administrators, successors, and assigns to pay to Owner upon default of Bidder the penal sum set forth on the face of this Bond. Payment of the penal sum is the extent of Bidder’s and Surety’s liability. Recovery of such penal sum under the terms of this Bond shall be Owner’s sole and exclusive remedy upon default of Bidder.

2. Default of Bidder shall occur upon the failure of Bidder to deliver within the time required by the Bidding Documents (or any extension thereof agreed to in writing by Owner) the executed Agreement required by the Bidding Documents and any performance and payment bonds required by the Bidding Documents.

3. This obligation shall be null and void if:

3.1 Owner accepts Bidder’s Bid and Bidder delivers within the time required by the Bidding

Documents (or any extension thereof agreed to in writing by Owner) the executed Agreement required by the Bidding Documents and any performance and payment bonds required by the Bidding Documents, or

3.2 All Bids are rejected by Owner, or

3.3 Owner fails to issue a Notice of Award to Bidder within the time specified in the Bidding

Documents (or any extension thereof agreed to in writing by Bidder and, if applicable, consented to by Surety when required by Paragraph 5 hereof).

4. Payment under this Bond will be due and payable upon default of Bidder and within 30 calendar days after receipt by Bidder and Surety of written notice of default from Owner, which notice will be given with reasonable promptness, identifying this Bond and the Project and including a statement of the amount due.

5. Surety waives notice of any and all defenses based on or arising out of any time extension to issue Notice of Award agreed to in writing by Owner and Bidder, provided that the total time for issuing Notice of Award including extensions shall not in the aggregate exceed 120 days from Bid due date without Surety’s written consent.

6. No suit or action shall be commenced under this Bond prior to 30 calendar days after the notice of default required in Paragraph 4 above is received by Bidder and Surety and in no case later than one year after Bid due date.

7. Any suit or action under this Bond shall be commenced only in a court of competent jurisdiction located in the state in which the Project is located.

8. Notices required hereunder shall be in writing and sent to Bidder and Surety at their respective addresses shown on the face of this Bond. Such notices may be sent by personal delivery, commercial courier, or by United States Registered or Certified Mail, return receipt requested, postage pre-paid, and shall be deemed to be effective upon receipt by the party concerned.

9. Surety shall cause to be attached to this Bond a current and effective Power of Attorney evidencing the authority of the officer, agent, or representative who executed this Bond on behalf of Surety to execute, seal, and deliver such Bond and bind the Surety thereby.

10. This Bond is intended to conform to all applicable statutory requirements. Any applicable requirement of any applicable statute that has been omitted from this Bond shall be deemed to be included herein as if set forth at length. If any provision of this Bond conflicts with any applicable statute, then the provision of said statute shall govern and the remainder of this Bond that is not in

Jim Meade Softball Peachtree City, GA

2 26 4

Jim Meade Softball Lighting Project

Table of Contents

1.

2.

3.

4. Project References 5.

6. Product

7. AirMesh Controls

8. Warranty

Project References

Photometry

D is c la im e r:

W e m a k e n o r e p re s e n ta ti o n a s t o i ts c o m p le te n e s s c u rr e n c y o r a c c u ra c y b e c a u s e o f re a s o n s i n h e re n t to

C A

D a n d t h e a d d it io n a l d ig it a l d a ta u s e d t o p ro d u c e a l ig h ti n g a p p lic a ti o n

T h e e n d u s e r o f th is d a ta t a k e s f u ll re s p o n s ib ili ty f o r th e a c c u ra c y a n d c o rr e c tn e s s o f a ll m e a s u re m e n ts a re a in v e n to ri e s o r o th e r d a ta e x tr a c te d f ro m t h is w it h t h e u s e o f a c o m p u te r, o r o th e r m e a s u ri n g i n s tr u m e n ts e it h e r m a n u a l o r d ig it a l in n a tu re

T h is p h o to m e tr ic a n a ly s is i s a n e s ti m a te o n ly a n d i s b a s e d o n e s ti m a te d r e fl e c ta n c e v a lu e s f o r in te ri o r a p p lic a ti o n s o r e s ti m a te d p o le l o c a ti o n s b a s e d o n s p e c if ie d l ig h t le v e ls f o r e x te ri o r a p p lic a ti o n s

A n y v a ri a n c e f ro m r e fl e c ta n c e v a lu e s o b s tr u c ti o n s lig h t lo s s fa c to rs in c lu d in g b o th p h y s ic a l a n d e le c tr ic a l in n a tu re o r d im e n s io n a l d a ta w ill a ff e c t th e a c tu a l lig h t le v e ls o b ta in e d

T h is a n a ly s is i s a m a th e m a ti c a l m o d e l a n d c a n b e o n ly a s a c c u ra te a s i s p e rm it te d b y t h e t h ir d p a rt y s o ft w a re a n d t h e re q u e s te d l ig h ti n g l e v e ls o r

IE

S s ta n d a rd s u s e d

In a d d it io n c a lc u la te d v a lu e s m a y v a ry f ro m a c tu a l m e a s u re m e n ts i n c e rt a in s it u a ti o n s d u e t o v a ri a n c e s s u c h a s b u t n o t lim it e d t o la m p o u tp u t, i n p u t v o lt a g e v a ri a n c e s m a n u fa c tu ri n g t o le ra n c e s a n d a p p lic a ti o n v a ri a n c e s

T h e p re s e n c e o f o b je c ts i.

e c u b ic a l w a lls fo lia g e e tc w ill d e c re a s e l ig h t le v e ls a n d m a y c a u s e s h a d o w in g

L ig h ti n g a p p lic a ti o n d ra w in g s a re b e in g p ro v id e d t o t h e r e c ip ie n t o f th is d is c la im e r.

P ro je c t N o

S J

A

.A G

I D ra w n B y J

R

/1

/2

D a te

P ro je c t:

C u s to m e r:

S c a le

J im

M e a d e P a rk

P e a c th re e

C it y

G A

A u s ti n

G a in e s S o u th C o n

Luminaire Schedule Calculation Summary

LabelSymbol Qty Label Arrangement LLF Description Luminaire Watts Luminaire Lumens Total Watts CalcType Units Avg Max Min Avg/Min Max/Min

01 Infield Illuminance Fc 54.49 70.7 42.6 1.28 1.66

01 Outfield Illuminance Fc 32.11 43.8 19.9 1.61 2.20

02 Infield Illuminance

6 LSR-2 Single 0.920 EPH-08-680R-57-70-2S-HEG-S 703.6 105744 4221.6

Fc 53.43 70.2 42.1 1.27 1.67

02 Outfield Illuminance Fc 32.16 43.8 21.7 1.48 2.02

03 Infield Illuminance Fc 55.05 71.3 40.9 1.35 1.74

03 Outfield Illuminance Fc 32.11 43.9 18.1 1.77 2.43

10 LSR-5 Single

64 LSR-3 Single 0.920 EPH-08-680R-57-70-3S-HEG-S 697.5 107852 44640

12 LSR-4 Single 0.920 EPH-08-680R-57-70-4S-HEG-S 697.5 108978 8370

0.920 EPH-08-680R-57-70-5S-HEG-S 697.5 109206 6975

04 Infield Illuminance Fc 54.84 74.4 41.4 1.32 1.80

04 Outfield Illuminance Fc 34.85 52.3 21.8 1.60 2.40

60'

60'

60'

60'

04 Fixtures

04 Fixtures

04 Fixtures

04 Fixtures

06 Fixtures

06 Fixtures

04 Fixtures

04 Fixtures

F ix tu re s

F ix tu re s

04 Fixtures

04 Fixtures

-325 -300 -275 -250 -225 -200 -175 -150 -125 -100 -75 -50 -25 0 25 50 75 100 125 150 175 200 225 250 275 300 325 350

-25

-50

-75

-100

-125

-150

-175

-200

-225

-250

-275

-300

04 Fixtures

04 Fixtures

03 Fixtures

03 Fixtures

F ix tu re s

F ix tu re s

04 Fixtures

F ix tu re s

F ix tu re s

05 Fixtures

(291, 164)

MH: 60

LSR-3

(291, 164)

LSR-3

MH: 60MH: 60

(291, 164)

LSR-3

LSR-4

(291, 164)

MH: 60

(162, 293)

LSR-3

MH: 60

(162, 293)

LSR-3

MH: 60

(162, 293)

MH: 60

LSR-4

(162, 293)

LSR-3

MH: 60

(1, 71)

LSR-3

MH: 60

(1, 71)

LSR-3

MH: 60

(1, 71)

LSR-3

MH: 60

MH: 60

LSR-4

(1, 71)(-1, 71)

LSR-3

MH: 60

(-1, 71)

LSR-3

MH: 60

(-1, 71)

LSR-3

MH: 60

(-1, 71)

LSR-4

MH: 60

(-1, 167)

LSR-3

MH: 60

(-1, 167)

LSR-3

MH: 60

(-1, 167)

LSR-3

MH: 60

(-1, 167)

LSR-5

MH: 60

(-3, 167)

LSR-3

MH: 60

(-3, 167)

LSR-5

MH: 60

MH: 60

LSR-3

(-3, 167)

LSR-3

(-3, 167)

MH: 60

(-159, 292)

LSR-3

MH: 60MH: 60

(-159, 292)

LSR-4

LSR-3

(-159, 292)

MH: 60

(-159, 292)

LSR-3

MH: 60

(-295, 164)

MH: 60

LSR-3

LSR-4

(-295, 164)

MH: 60

(-295, 164)

LSR-3

MH: 60

(-295, 164)

MH: 60

LSR-3

MH: 60

LSR-5

(-169, 3)(-169, 3)

LSR-3

MH: 60MH: 60

(-169, 3)

LSR-3

MH: 60

(-169, 3)

LSR-3

LSR-4

(-73, 3)

MH: 60MH: 60

(-73, 3)

LSR-3

(-73, 3)

LSR-3

MH: 60

(-73, 3)

LSR-3

MH: 60

(-237, -51)

LSR-5

MH: 60

(-237, -51)

LSR-2

MH: 60

MH: 60

(-237, -51)

LSR-2

(-237, -51)

LSR-3

MH: 60

(-237, -51)

LSR-3

MH: 60

MH: 60

(-237, -51)

LSR-3

(-43, -46)

LSR-5

MH: 60

(-43, -46)

LSR-3

MH: 60

(-43, -46)

LSR-3

MH: 60

(-43, -46)

LSR-2

MH: 60

(-43, -46)

LSR-3

MH: 60

MH: 60

(-10, -278)

LSR-2

LSR-2

MH: 60

(-10, -278)(-10, -278)

MH: 60

LSR-3

MH: 60

(-10, -278)

LSR-3

MH: 60

LSR-5

(-10, -278)

MH: 60

(-10, -278)

LSR-3

(-2, -70)

MH: 60

LSR-5

LSR-3

MH: 60

(-2, -70)(-2, -70)

LSR-3

MH: 60

(-2, -70)

LSR-3 MH: 60

LSR-2

(-2, -70)

MH: 60

(-1, -70)

LSR-3

MH: 60

(-1, -70)

LSR-4

MH: 60

(-1, -70)

LSR-3

MH: 60

(-1, -70)

LSR-3

MH: 60

MH: 60

(15, -163)

LSR-3

MH: 60

(15, -163)

LSR-3

(15, -163)

LSR-5

MH: 60

(15, -163)

LSR-3

MH: 60

(125, -271)

LSR-3

MH: 60

(125, -271)

LSR-4

MH: 60MH: 60

LSR-3

(125, -271)

(278, -115)

LSR-3

MH: 60

(278, -115)

LSR-4

MH: 60

(278, -115)

LSR-3

MH: 60

(69, 1)

LSR-4

MH: 60

(69, 1)

LSR-3

MH: 60

(69, 1)

LSR-3

MH: 60

(69, 1)

LSR-3

MH: 60

(69, 3)

LSR-3

MH: 60

(69, 3)

LSR-3

MH: 60

(69, 3)

LSR-3

MH: 60MH: 60

(69, 3)

LSR-4

(165, 1)

LSR-3

MH: 60MH: 60

(165, 1)

LSR-5

MH: 60

(165, 1)

LSR-3

(165, 1)

MH: 60

LSR-3

(165, 3)

LSR-5

MH: 60

MH: 60

(165, 3)

LSR-3

LSR-3

(165, 3)

MH: 60

(165, 3)

LSR-3

MH: 60

51.7 50.2 44.8 42.6 47.0 47.6 39.4 30.3 42.0 43.8 34.5 39.4 35.1 23.2

51.7 69.7 70.4 55.7 55.7 57.4 49.4 35.8 30.7 40.0 39.7 37.9 42.7 42.2 31.9

50.3 70.4 70.7 57.1 64.0 62.2 45.5 31.0 31.1 38.5 34.8 30.0 32.6 35.1 31.4

45.1 55.7 57.0 59.1 64.2 62.2 46.4 33.3 35.0 38.7 34.2 26.4 25.3 27.7 27.7

43.0 55.7 63.8 64.2 63.3 58.7 47.5 38.9 37.1 37.4 31.7 25.7 24.3 26.3 27.2

47.1 57.2 62.1 62.2 58.8 53.8 47.1 40.8 37.7 35.0 30.1 25.9 24.8 27.8

47.9 48.9 45.4 46.6 47.7 47.2 43.7 39.5 36.4 33.4 29.5 26.4 25.9 28.1

39.5 36.0 31.5 33.9 39.1 40.8 39.5 37.6 35.0 32.2 29.2 27.1 27.6 29.4

30.9 31.6 31.9 35.1 36.8 37.4 36.2 35.0 32.8 30.9 28.9 27.7 28.2

42.1 39.1 37.9 37.8 36.7 34.5 33.0 32.1 30.9 29.3 27.1 25.4

42.1 38.4 33.9 33.3 31.1 29.7 29.2 29.1 28.8 27.1 23.6 19.9

33.8 36.3 29.1 25.9 25.5 25.7 26.3 27.0 27.7 25.3 19.9

39.2 41.8 31.9 25.2 24.4 24.8 25.9 27.5 28.1

35.9 41.9 34.7 27.6 26.5 27.9 28.1 29.4

24.1 32.0 31.3 27.7 27.3

25.6 37.6 39.4 33.8 41.5 38.9 26.9 37.0 46.4 45.2 42.4 44.8 53.2 53.9

33.5 40.9 39.5 34.8 36.5 36.5 27.6 33.1 47.2 56.5 55.1 54.6 70.2 68.4 51.5

30.7 32.6 29.9 28.0 34.1 37.6 30.1 30.1 45.1 61.5 62.7 56.0 68.2 66.4 48.5

27.2 26.8 24.2 26.4 33.8 37.9 34.4 34.0 46.6 61.0 62.7 60.2 58.8 54.4 43.7

26.4 24.2 25.8 31.7 36.8 36.8 39.0 47.3 57.0 61.6 63.6 65.4 57.6 43.1

27.8 25.0 26.1 30.3 34.6 37.3 40.1 45.7 51.0 55.1 58.3 59.9 57.1 47.3

28.1 26.3 26.7 29.6 33.3 36.0 38.8 42.1 44.6 44.0 42.5 42.7 47.1 46.3

27.6 27.3 29.6 32.2 34.6 37.0 38.6 39.5 37.5 33.1 30.3 34.5 36.4

28.3 27.6 29.1 31.0 32.8 34.9 35.9 36.9 37.2 36.2 33.7 34.0 32.1

24.5 26.6 29.2 30.9 31.8 32.6 34.2 36.5 38.0 38.0 40.4 43.4

22.9 27.1 29.1 29.0 28.9 29.2 30.6 32.3 33.0 38.1 39.8

25.8 28.6 27.8 26.9 26.1 25.7 25.8 30.3 37.7 34.3

29.2 28.9 27.4 26.4 25.9 27.2 34.0 43.8 39.0

29.9 30.4 28.5 29.6 36.0 41.7 33.1

28.9 29.3 31.3 29.9 21.7

22.0 24.9 25.3 26.2 32.6 27.5

21.8 27.3 32.5 35.4 33.5 29.2 31.3 28.4

18.2 21.9 25.8 29.9 33.7 34.9 33.8 31.4 30.0 25.2

18.2 20.6 23.0 26.0 28.2 30.6 33.2 36.7 37.7 36.4 34.3

18.1 20.5 22.0 23.4 25.2 27.4 30.3 35.0 39.0 40.2 40.7 38.2

21.6 22.7 23.2 24.5 26.7 29.9 33.7 37.3 39.7 41.0 41.4 39.2

21.6 25.4 25.6 24.8 26.6 30.3 35.3 39.6 41.4 42.2 42.1 42.1 38.7

27.3 29.7 27.8 27.1 29.8 35.4 41.4 46.7 48.7 48.5 47.5 44.9 40.9

22.3 32.8 33.8 30.7 30.6 34.3 40.5 47.6 54.2 58.5 58.7 56.6 51.9 44.0

25.3 36.0 35.5 34.1 36.4 38.5 42.6 51.1 60.6 67.2 68.6 67.1 59.9 47.9

25.9 34.3 34.9 39.2 41.3 41.8 43.9 51.0 63.2 71.3 70.9 70.4 63.1 50.4

26.8 30.2 33.6 40.9 43.3 43.0 43.3 48.0 58.8 69.1 68.6 63.0 59.5 49.4

33.3 32.5 32.5 38.7 42.1 42.1 42.7 45.4 52.0 60.5 63.4 61.9 60.0 49.2

28.2 29.6 26.3 34.4 37.6 38.0 38.1 40.9 44.4 49.4 53.7 54.1 52.3 41.1

32.0 46.8 41.8 34.8 32.5 27.8

35.9 49.2 42.8 34.7 30.5 25.9 22.1 22.9

32.3 43.4 39.2 33.0 29.6 26.2 24.9 25.9 28.0 24.1

45.4 52.3 43.9 38.8 35.6 31.4 29.6 29.5 30.2 27.6 21.8

44.8 50.8 42.9 42.3 40.7 38.0 35.1 33.4 32.7 31.3 27.0 22.8

31.6 35.6 32.6 35.4 38.6 39.4 37.6 36.1 34.4 32.7 30.6 27.7

37.7 39.9 33.1 32.1 37.9 40.1 39.0 37.3 35.4 33.1 30.5 28.1 26.0

45.8 54.6 49.2 46.3 45.5 45.2 42.2 38.3 35.9 33.5 29.8 26.7 24.8 21.8

45.4 60.7 64.3 61.3 56.3 51.2 45.1 39.2 36.6 34.5 30.0 25.6 23.9 25.3

42.1 55.4 63.6 62.3 60.6 56.2 45.6 37.5 36.3 37.5 33.0 28.4 28.6 32.1

48.2 57.6 56.3 57.6 62.1 60.1 45.0 32.8 35.2 40.1 37.4 31.8 33.8 36.4

64.8 73.4 70.4 55.0 61.8 60.3 44.5 30.9 32.0 40.9 39.3 37.1 41.2 41.5

59.4 72.8 74.4 56.9 53.0 55.1 48.4 35.8 31.9 42.7 44.1 44.0 48.4 45.3

41.4 61.1 67.1 48.4 41.5 44.8 46.7 39.5 31.3 43.9 47.0 37.9 42.4 36.4

01 Field @ 3' AFF

Max/Min Ratio = 2.20

Coeff. of Variation = 0.17

01 Outfield

Illuminance (Fc)

Average = 32.11

Maximum = 43.8

Minimum = 19.9

Avg/Min Ratio = 1.61

01 Infield

Illuminance (Fc)

Average = 54.49

Maximum = 70.7

Minimum = 42.6

Avg/Min Ratio = 1.28

Max/Min Ratio = 1.66

Coeff. of Variation = 0.15

Illuminance (Fc)

Average = 34.85

Maximum = 52.3

Minimum = 21.8

Avg/Min Ratio = 1.60

Max/Min Ratio = 2.40

04 Outfield

Coeff. of Variation = 0.19

04 Infield

Illuminance (Fc)

Average = 54.84

Maximum = 74.4

Minimum = 41.4

Avg/Min Ratio = 1.32

Max/Min Ratio = 1.80

Coeff. of Variation = 0.16

02 Outfield

Illuminance (Fc)

Average = 32.16

Maximum = 43.8

Minimum = 21.7

Avg/Min Ratio = 1.48

Max/Min Ratio = 2.02

Coeff. of Variation = 0.15

Illuminance (Fc)

Average = 55.05

Maximum = 71.3

Minimum = 40.9

Avg/Min Ratio = 1.35

Max/Min Ratio = 1.74

Coeff. of Variation = 0.16

03 Infield

02 Infield

Illuminance (Fc)

Average = 53.43

Maximum = 70.2

Minimum = 42.1

Avg/Min Ratio = 1.27

Max/Min Ratio = 1.67

Coeff. of Variation = 0.15

03 Outfield

Illuminance (Fc)

Average = 32.11

Maximum = 43.9

Minimum = 18.1

Avg/Min Ratio = 1.77

Max/Min Ratio = 2.43

Coeff. of Variation = 0.21

P a r a m e t r i c

M i r r o r

P a ra m e tric

M irro r

Product Cutsheets

Project Catalog # Type

Prepared by Notes Date

TD52807722EN page 1 September 7, 2023 3:22 PM

Interactive Menu

• System Topology & Benefit Features page 2

• Order Information page 3

• Sample Order: New Installation page 5

• Sample Order: Retrofit Installation page 5

• Light Head Overview page 6

• Power and Controls Box Overview page 13

• Distribution Box Overview page 17

• Example Electrical System Configuration page 22

• Example System Topologies page 23

Typical Applications Outdoor Stadiums • Outdoor Ball Fields • Outdoor Multi-Event Spaces

Ephesus Remote Power System:

LUMASPORT 8

The Ephesus Remote Power System for the LUMASPORT 8 delivers full turn-key sports lighting solutions for both new and retrofit applications.

• New Applications - A streamlined full turn-key system solution backed with industry leading reliability and performance.

• Retrofit Applications - The minimally invasive retrofit kit enables the opportunity to keep existing remote power infrastructure (poles, cross arm, & wiring) providing the lowest total cost of ownership.

System Certifications

AVA IL A B LE

CO

MPLIANT OPTIONS

TA A

TRADE AGREEMENTS ACT

http://https://www.designlights.org/search/?search=ephesus

LUMASPORT 8 REMOTE SYSTEM

TD52807722EN page 2 September 7, 2023 3:22 PM

Lowest Total Cost of Ownership in the Industry

• Modular system options to locate power, controls, and surge at the base of the pole for easy access.

Custom Controls

• Wired DMX or Wireless AirMesh controls options to suit your needs.

System Performance

• Put the light exactly where you want it with our award-winning glare and cutoff control via Hybrid Reflector and TIR Optical System.

System Reliability

• Industry leading light source reliability with

Chip-on-Board LEDs

• Greater than 92% lumen maintenance at 55,000 hours

• Exceeds the requirements of the Cooper Lighting Solutions rigorous product testing program that analyzes the performance and lifespan of the system with extensive focus on efficacy, thermal, ingress, vibration, and durability characteristics.

Easy Installation Assembly

• Three easy-to-install system components: the light head, the

PAC Box, and a Distribution Box.

• Reduce install time with pre-aimable single-piece light head assembly.

SYSTEM TOPOLOGY & BENEFIT FEATURES

Note:

Light Head example shown in a Top Mount Yoke (TY = Top Mount Yoke) configuration for new remote system installations. Mounting infrastructure (ie, Crossarms) ordered separately.

LUMASPORT 8 LIGHT HEADS

(Details on pages 6-12)

POWER & CONTROLS (PAC) BOX

+ MOUNTING RAILS

(Details on pages 13-16)

Note:

1 qty. PAC Box can support 4 qty. LUMASPORT 8 remote power light heads.

DISTRIBUTION BOX

(Details on pages 17-21)

Note:

1 qty. Distribution Box can support 6 qty. PAC Boxes.

• POLES

• CROSS ARMS

• DROP CABLES

• FOUNDATION DESIGN

• LIGHTING DESIGN

IF YOU NEED CUSTOM SYSTEM COMPONENTS

OR SERVICES PLEASE CONTACT EPHESUS:

WWW.COOPERLIGHTING.COM/GLOBAL/CONTACT-US/EPHESUS

http://www.cooperlighting.com/global/contact-us/ephesus

TD52807722EN page 3 September 7, 2023 3:22 PM

Brand Family Model Power

Configuration Color¹ CCT CRI Optic2 Light Head Cable (DC)4

EPH = Ephesus, Standard TAA=Trade Agreements Act¹

LS = Lumasport 08 = 8 Optics 0640R = 640W Remote Power 0680R = 680W Remote Power

BLK = Black 40 = 4000K 57 = 5700K

70 = 70 CRI

80 = 80 CRI

1S³ = NEMA 3 | 17.5 | 33.3

2S = NEMA 3 | 21.9 | 40.2

3S = NEMA 3 | 25.4 | 45.7

4S = NEMA 4 | 36.0 | 64.4

5S = NEMA 5 | 46.6 | 82.6

7F = NEMA 7 | 72.5 | 131.0

BH3 = 3ft, 3 pin C105 = 10ft Cable RAC = 3ft, Retrofit Adapter Cable

Notes:

(1)Only product configurations with this designated prefix are built to be compliant with the Trade Agreements Act of 1979 (TAA). Please refer to DOMESTIC PREFERENCES website for more information. Components shipped separately may be separately analyzed under domestic preference requirements.

Notes:

(1) Not coastal rated. Contact Ephesus for coastal fixture options.

Notes:

(2) Optic = NEMA TYPE; BEAM ANGLE; FIELD ANGLE. Additional optical performance data within spec sheet.

(3) Optic type 1S not available with the 0680R configuration

Notes:

(4) DC Cable connecting the light head to the driver box.

(5) C10 = 10ft Cable is intended to be used with the Ephesus Catwalk Bracket.

Light Head Mount6 7 Options Special Options

TY = Top Mount Yoke QC8 = Quick Clamp

HEG = No Visor, high efficiency glass VHE = Visor, high efficiency glass lens CV1 = Cut-off visor, 1 CV2 = Cut-off visor, 2 CV5 = Cut-off visor, 5

ST = Standard

Notes:

(6) Light Head Mounts shipped assembled to Light head

(7) Installation type may vary with lighting design

(8) QC = Quick Clamp is intended to be used to mount the light head to a 2 inch by 4 inch tubular crossarm.

LIGHT HEADS

Brand Family Power

Configuration Color¹ AC Input Voltage

Control Light Heads Mounting

Option Special Options

EPH = Ephesus, Standard TAA=Trade Agreements Act¹

PAC = Power and controls box

0640R = 640W Remote Power 0680R = 680W Remote Power

GRY = Grey 208 = 208V AC

240 = 240V AC

277 = 277V AC

347 = 347V AC

480 = 480V AC

AM = Wireless Air Mesh Individual LB = Landburst (DMX) Individual NC = No Control

1 = 1 qty Light Head 2 = 2 qty Light Heads 3 = 3 qty Light Heads 4 = 4 qty Light Heads

MR = Mounting Rails

ST = Standard 15ft Cables² XL = Extended 30ft Cables³

Notes:

(1)Only product configurations with this designated prefix are built to be compliant with the Trade Agreements Act of 1979 (TAA). Please refer to DOMESTIC PREFERENCES website for more information. Components shipped separately may be separately analyzed under domestic preference requirements.

Notes:

(1) Not coastal rated.

Contact Ephesus for coastal fixture options.

Notes:

(2) 15ft standard for up to 3 PAC boxes high

(3) 30ft supports for more than 3 PAC boxes high

POWER AND CONTROLS (PAC) BOX

ORDER INFORMATION

NOTE: A complete LumaSport Remote System order requires a selection entry for:

LIGHT HEADS - SAMPLE ORDER NUMBER: EPH-LS-08-0680R-BLK-57-80-5S-BH3-TY-CV5-ST

POWER & CONTROLS BOX + MOUNTING RAILS - SAMPLE ORDER NUMBER: EPH-PAC-0680R-GRY-240-AM-4-MR-ST

DISTRIBUTION BOX - SAMPLE ORDER NUMBER: EPH-DST-6PC-GRY-240-CP-ST

OPTIONAL: BANDING ACCESORIES - SAMPLE ORDER NUMBER: EPH-RPB-KIT

QUANTITY OF FIXTURES PER POLE

LUMASPORT 8 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

QUANTITY OF PAC BOXES 1 PAC BOX 2 PAC BOXES 3 PAC BOXES 4 PAC BOXES 5 PAC BOXES 6 PAC BOXES

QUANTITY OF DISTRIBUTION BOXES 1 DISTRIBUTION BOX

TD52807722EN page 4 September 7, 2023 3:22 PM

Brand Family Configuration Color AC Input Voltage Pole Access Mounting

Option

EPH = Ephesus, Standard TAA=Trade Agreements Act¹

DST = Distribution Box 6PC = Compatible with up to 6 Power & Control Boxes GRY = Grey 208 = 208V AC

240 = 240V AC

277 = 277V AC

347 = 347V AC

480 = 480V AC

CP = Cover Plate & Adapter, Standard ST = Standard

Notes:

(1)Only product configurations with this designated prefix are built to be compliant with the Trade Agreements Act of 1979 (TAA). Please refer to DOMESTIC PREFERENCES website for more information. Components shipped separately may be separately analyzed under domestic preference requirements.

DISTRIBUTION BOX

Brand Accessory Option

EPH = Ephesus RPB = Remote Power Pole Banding

KIT = Banding Kit (Banding, Buckles, Tool) BND = Banding, 100ft roll BKL = Buckle, 100 quantity per pack BTL = Banding Tool

Notes:

The quantity of banding and banding buckles needed is determined by the circumference of the pole, the quantity of PAC Boxes (quantity 3 bands per PAC Box required for mounting), and Distribution Boxes (quantity 2 bands per Distribution Box required for mounting). A typical 18-inch diameter pole using quantity 3 PAC boxes and quantity 1 Distribution box will utilize 60-70 feet of banding per pole.

ACCESSORY ORDER INFORMATION

EPH-RPB-KIT = Banding Kit Components Banding Tool (EPH-RPB-BTL) Banding (EPH-RPB-BND) Banding Buckle (EPH-RPB-BKL)

Description Tensioning tool for 3/4 inch stainless steel banding Heavy duty 3/4 inch x .030 inch thick type 201 stainless steel banding.

Type 201 stainless steel banding buckle for 3/4 inch stainless steel banding.

Quantity 1 tool 2 rolls, 100 foot per roll 1 box, 100 qty per box.

TD52807722EN page 5 September 7, 2023 3:22 PM

SAMPLE ORDER: RETROFIT INSTALLATION

SAMPLE ORDER: NEW INSTALLATION

Example Order - Retrofit (277VAC, AM CONTROLS)

Cat Logic Description Qty.

EPH-LS-08-0680R-BLK-57-70-XX-RAC-QC-HEG-ST LIGHT HEAD, RETROFIT ADAPTER CABLE, QUICK CLAMP

(VARIOUS OPTICS) 12

EPH-PAC-0680R-GRY-277-AM-4-MR PAC, 4 QTY. LIGHT HEAD PER PAC 3

EPH-DST-6PC-GRY-277-CP-ST DISTRIBUTION BOX 1

EPH-RPB-KIT BANDING KIT (1 TOOL, 200FT BANDING, 100 QTY. BUCKLES) 1

Example Order - New (277VAC, AM CONTROLS)

Cat Logic Description Qty.

EPH-LS-08-0680R-BLK-57-70-XX-BH3-TY-HEG-ST LIGHT HEAD, 3 PIN CONNECTOR, TOP MOUNT

YOKE (VARIOUS OPTICS) 12

EPH-PAC-0680R-GRY-277-AM-4-MR PAC, 4 QTY. LIGHT HEAD PER PAC 3

EPH-DST-6PC-GRY-277-CP-ST DISTRIBUTION BOX 1

EPH-LTGSTR-P NEW CROSSARMS & CABLING VARIES

TD52807722EN page 6 September 7, 2023 3:22 PM

LIGHT HEAD OVERVIEW

LUMASPORT 8 (640W/680W)

Lumen Output Range2 80,572 - 110,982lm

Nominal Power3 640W / 680W

Efficacy Range2 117.5 - 159.1lm/W

CRI4 70, 80

TLCI5 75

CCT Range 4000K, 5700K

Distribution (NEMA)6 NEMA 3 - 5

Dimming Range DIM TO OFF, 10%-100%

Operating Temperature Range -40°C to +40°C

Usage INDOOR7, OUTDOOR

Mounting Options (3G

RATED)

TOP YOKE;

QUICK CLAMP

Electrical Certifications FCC, UL8750, UL1598

Environmental Certifications IP66, NEMA4X8

Vibration ANSI C136.31-2010 3G9

Effective Projected Area (EPA) 1.8 (sq. ft.)

Effective Projected Area

(EPA)

with Visor (VHE , CV1, CV2, CV5)10

1.8 - 2.5 (sq. ft.)

Approximate Weight¹¹

Light Head | 35 LBS Visor | + 4LBS Remote Top Yoke | + 6LBS Quick Clamp Yoke | + 12LBS

Performance Data¹

NOTES:

(1) Specifications are subject to change without notice.

(2) Refer to LUMASPORT 8 Optical Performance Data.

(3) Values are +/- 4% when fixture is operated at 25°C ambient

(4) Values are +/- 2%

(5) Values are +/- 3 points.

(6) Optic = NEMA TYPE; BEAM ANGLE; FIELD ANGLE. Additional optical performance data within spec sheet.

(7) Indoor use limited to input voltages 277-480V.

(8) Light Head Enclosure meets NEMA4X Certification. Steel Yokes are excluded.

(9) LumaSport 8 with with Quick Clamp or visors (VHE, CV1, CV2, CV5) qualifies for ANSI C136, 31-2010 1.5G

(10) EPA may vary depending on the aiming angle of the fixture.

(11) Weight may vary depending on mounting bracket, visor option, and light head configuration.

Light Head Electrical Specifications

* Light Head cannot be powered independently from the PAC

* 14 AWG, 600V wire required. Rated and installed per electrical standard (contractor supplied)

* 200ft Max separation from PAC

* Electrical System (Light Head, PAC, Distribution Box) must be grounded per electrical standard

**This is the power to the Light Head - for system input power, see sheet 13 for the PAC electrical performance data

Product Drive Current DC Voltage Light Head Power

EPH-LS-08-0640R 2.25 A 285 VDC 640 W

EPH-LS-08-0680R 2.35 A 285 VDC 680 W

TD52807722EN page 7 September 7, 2023 3:22 PM

B

ATITLE:

SIZE: DWG NO: REV:

SHEET

WT:

SCALE:

APPR:

CHKD:

DRWN:

DATEAPPROVALS

C EEL-R2-0003 1

PH

EE

L-

R2

_M ar ke tin g_

LS

re mo te

Lig hth ea d

L MOD: 670247206 7/8/2022

7 OF C

oo pe r L ig ht in g

S ol ut io ns T em pl at e

R ev

A

IP LEVEL:

B

ATITLE:

SIZE: DWG NO: REV:

SHEET

WT:

SCALE:

APPR:

CHKD:

DRWN:

DATEAPPROVALS

C EEL-R2-0003 1

PH

EE

L-

R2

_M ar ke tin g_

LS

re mo te

Lig hth ea d

L MOD: 670247206 7/8/2022

7 OF C

oo pe r L ig ht in g

S ol ut io ns T em pl at e

R ev

A

IP LEVEL:

• B

•••• A

TI

TL

E

SI

ZE

DW

G

NO

RE

V:

SH

EE

T W

T:

SC

AL

E:

AP

PR

CH

KD

DR

W

N:

D A

TE

A

P P

R O

V A

LS

C E

E L-

R 2-

P H

EEL-R2-

0003_Marketing_LS 8 remote Lighthead

L M

OD

:6

7/

8/

O

F

Cooper Lighting Solutions Template Rev A

IP

L

E V

E L:

18.3in [464.56mm]

12.4in [314.70mm] 13.8in

[350.26mm]

Light Head: TY = Top Yoke Dimensional Details

Light Head: TY = Top Yoke Mounting Attachment Method

[20.66mm] .813in

[11.11mm] .44in

[73.66mm]

2.90in

.75in [19.05mm]

BASE

THICKNESS

BOLT PATTERN

.4in [11.11mm]

Ø2.9in [73.66mm]

Ø.8in [20.66mm]

HEAD ON

BOTTOM VIEW LEFT PROFILE

LEFT PROFILE

• B

•••• A

TI

TL

E

SI

ZE

DW

G

NO

RE

V:

SH

EE

T W

T:

SC

AL

E:

AP

PR

CH

KD

DR

W

N:

D A

TE

A

P P

R O

V A

LS

C E

E L-

R 2-

P H

EEL-R2-

0003_Marketing_LS 8 remote Lighthead

L M

OD

:6

7/

8/

O

F

Cooper Lighting Solutions Template Rev A

IP

L

E V

E L:

LIGHT HEAD: DIMENSIONAL DETAILS

*Note: mounting hardware ordered separately for top mount yoke

TD52807722EN page 9 September 7, 2023 3:22 PM

MALE FACE VIEW

2.38 .03 in

1.66

Ø2.4in [60.45mm]

1.7in [42.16mm]

RAC = 3 Foot, Retrofit Adapter Cable Electrical Connector Details

BH3 = 3 foot, 3 Pin Electrical Connector Details

LIGHT HEAD: ELECTRICAL ATTACHMENT METHODS

*Note: electrical splice connectors not included. Refer to install manual for connector requirements.

TD52807722EN page 13 September 7, 2023 3:22 PM

Power and Controls (PAC) Box Electrical Specifications (4x LS 8 Light Heads)*

POWER AND CONTROLS BOX OVERVIEW

Product Input Voltage

Surge Protection

Power Per Light Head

System Power (4X Light Heads)

Input Current (A)

Power Factor THD Inrush period (ms) Peak

Inrush (A)

EPH-PAC-640R

(LV Drivers)

208 VAC

10KV 700 W 2801 W

13.6 >0.9 <10% 28.4 28.0

240 VAC 11.6

EPH-PAC-640R

(HV Drivers)

277 VAC

10KV 703 W 2802 W

10.0

>0.9 <10% 13.12 35.4347 VAC 8.0

480 VAC 6.0

EPH-PAC-680R

(LV Drivers)

208 VAC

10KV 717 W 2854 W

13.6 >0.9 <10% 28.4 28.0

240 VAC 12.0

EPH-PAC-680R

(HV Drivers)

277 VAC

10KV 712 W 2846 W

10.4

>0.9 <10% 13.12 35.4347 VAC 8.0

480 VAC 6.0

*Measured at 25°C ambient

TD52807722EN page 14 September 7, 2023 3:22 PM

990.60 39.00

AC WIREWAY

DC WIREWAY

HEAD ON

100.43 3.95

196.85 7.75

TOP VIEW

RIGHT PROFILE

PAC BOX: DIMENSIONAL DETAILS

Mounting Rail for PAC Box Dimensional Details

PAC REQUIRES MOUNTING RAIL TO BE ATTACHED TO A POLE OR SURFACE1.

2.

B

ATHIRD ANGLE PROJECTION

MATERIAL:

METRIC (mm)

ENGLISH (IN) .X

.XX

.XXX

X.

.X

.XX

DIMENSIONS ARE IN INCHES

DIMENSIONS IN [ ] ARE IN mm

ELECTRONIC CAD DRAWING. DO

NOT REVISE MANUALLY.

TITLE:

SIZE: DWG NO: REV:

SHEETVOL:WT:SCALE:SURFACE AREA:DO NOT SCALE DRAWING

FINISH:

APPR:

CHKD:

DRWN:

DATEAPPROVALS

.040 .020 .010 0.5 0.25 x.x x.x

DENOTES CRITICAL

DIMENSIONS AND

GAUGE CHECK POINTS

DENOTES FIRST

PIECE

INSPECTION ONLY

FPC

PRODUCT MUST CONFORM TO ROHS

COOPER LIGHTING SOLUTIONS - CONFIDENTIAL AND PROPRIETARY

NOTICE TO PERSONS RECEIVING THIS DOCUMENT AND/OR TECHNICAL INFORMATION

THIS DOCUMENT, INCLUDING THE DRAWING AND INFORMATION CONTAINED THEREON, IS CONFIDENTIAL AND IS THE EXCLUSIVE PROPERTY OF COOPER LIGHTING SOLUTIONS, AND IS MERELY ON LOAN AND SUBJECT TO RECALL BY COOPER LIGHTING SOLUTIONS AT ANY TIME. BY TAKING POSSESSION OF THIS DOCUMENT, THE RECIPIENT ACKNOWLEDGES AND AGREES THAT THIS DOCUMENT CANNOT BE USED IN ANY MANNER ADVERSE TO THE INTERESTS OF COOPER LIGHTING SOLUTIONS, AND THAT NO PORTION

OF THIS DOCUMENT MAY BE COPIED OR OTHERWISE REPRODUCED WITHOUT THE PRIOR WRITTEN

CONSENT OF COOPER LIGHTING SOLUTIONS. IN THE CASE OF CONFLICTING CONTRACTUAL

PROVISIONS, THIS NOTICE SHALL GOVERN THE STATUS OF THIS DOCUMENT. MATERIAL MASTER

PAC BOX

C EEL-R2-0005 1

45.37 LB 3

WPO

EE

L-

R2 -0

L MOD: 670247206 7/5/2022

DIMENSIONS THAT AFFECT

SAFE HANDLING OR

OPERATION

S

TOLERANCE GENERAL

• • • • •• • ••• • • • • • • • • • • • • • • • •• • ••• • • • • • • • • • • •1 OF

ANGLES ALL 1.0

C oo pe r L ig ht in g

S ol ut io ns T em pl at e

R ev

A

IP LEVEL:

DENOTES FIRST PIECE

AND IN-PROCESS

INSPECTION

PAC REQUIRES MOUNTING RAIL TO BE ATTACHED TO A POLE OR SURFACE1.

2.

B

ATHIRD ANGLE PROJECTION

MATERIAL:

METRIC (mm)

ENGLISH (IN) .X

.XX

.XXX

X.

.X

.XX

DIMENSIONS ARE IN INCHES

DIMENSIONS IN [ ] ARE IN mm

ELECTRONIC CAD DRAWING. DO

NOT REVISE MANUALLY.

TITLE:

SIZE: DWG NO: REV:

SHEETVOL:WT:SCALE:SURFACE AREA:DO NOT SCALE DRAWING

FINISH:

APPR:

CHKD:

DRWN:

DATEAPPROVALS

.040 .020 .010 0.5 0.25 x.x x.x

DENOTES CRITICAL

DIMENSIONS AND

GAUGE CHECK POINTS

DENOTES FIRST

PIECE

INSPECTION ONLY

FPC

PRODUCT MUST CONFORM TO ROHS

COOPER LIGHTING SOLUTIONS - CONFIDENTIAL AND PROPRIETARY

NOTICE TO PERSONS RECEIVING THIS DOCUMENT AND/OR TECHNICAL INFORMATION

THIS DOCUMENT, INCLUDING THE DRAWING AND INFORMATION CONTAINED THEREON, IS CONFIDENTIAL AND IS THE EXCLUSIVE PROPERTY OF COOPER LIGHTING SOLUTIONS, AND IS MERELY ON LOAN AND SUBJECT TO RECALL BY COOPER LIGHTING SOLUTIONS AT ANY TIME. BY TAKING POSSESSION OF THIS DOCUMENT, THE RECIPIENT ACKNOWLEDGES AND AGREES THAT THIS DOCUMENT CANNOT BE USED IN ANY MANNER ADVERSE TO THE INTERESTS OF COOPER LIGHTING SOLUTIONS, AND THAT NO PORTION

OF THIS DOCUMENT MAY BE COPIED OR OTHERWISE REPRODUCED WITHOUT THE PRIOR WRITTEN

CONSENT OF COOPER LIGHTING SOLUTIONS. IN THE CASE OF CONFLICTING CONTRACTUAL

PROVISIONS, THIS NOTICE SHALL GOVERN THE STATUS OF THIS DOCUMENT. MATERIAL MASTER

PAC BOX

C EEL-R2-0005 1

45.37 LB 3

WPO

EE

L-

R2 -0

L MOD: 670247206 7/5/2022

DIMENSIONS THAT AFFECT

SAFE HANDLING OR

OPERATION

S

TOLERANCE GENERAL

• • • • •• • ••• • • • • • • • • • • • • • • • •• • ••• • • • • • • • • • • •1 OF

ANGLES ALL 1.0

C oo pe r L ig ht in g

S ol ut io ns T em pl at e

R ev

A

IP LEVEL:

DENOTES FIRST PIECE

AND IN-PROCESS

INSPECTION

PAC REQUIRES MOUNTING RAIL TO BE ATTACHED TO A POLE OR SURFACE1.

2.

B

ATHIRD ANGLE PROJECTION

MATERIAL:

METRIC (mm)

ENGLISH (IN) .X

.XX

.XXX

X.

.X

.XX

DIMENSIONS ARE IN INCHES

DIMENSIONS IN [ ] ARE IN mm

ELECTRONIC CAD DRAWING. DO

NOT REVISE MANUALLY.

TITLE:

SIZE: DWG NO: REV:

SHEETVOL:WT:SCALE:SURFACE AREA:DO NOT SCALE DRAWING

FINISH:

APPR:

CHKD:

DRWN:

DATEAPPROVALS

.040 .020 .010 0.5 0.25 x.x x.x

DENOTES CRITICAL

DIMENSIONS AND

GAUGE CHECK POINTS

DENOTES FIRST

PIECE

INSPECTION ONLY

FPC

PRODUCT MUST CONFORM TO ROHS

COOPER LIGHTING SOLUTIONS - CONFIDENTIAL AND PROPRIETARY

NOTICE TO PERSONS RECEIVING THIS DOCUMENT AND/OR TECHNICAL INFORMATION

THIS DOCUMENT, INCLUDING THE DRAWING AND INFORMATION CONTAINED THEREON, IS CONFIDENTIAL AND IS THE EXCLUSIVE PROPERTY OF COOPER LIGHTING SOLUTIONS, AND IS MERELY ON LOAN AND SUBJECT TO RECALL BY COOPER LIGHTING SOLUTIONS AT ANY TIME. BY TAKING POSSESSION OF THIS DOCUMENT, THE RECIPIENT ACKNOWLEDGES AND AGREES THAT THIS DOCUMENT CANNOT BE USED IN ANY MANNER ADVERSE TO THE INTERESTS OF COOPER LIGHTING SOLUTIONS, AND THAT NO PORTION

OF THIS DOCUMENT MAY BE COPIED OR OTHERWISE REPRODUCED WITHOUT THE PRIOR WRITTEN

CONSENT OF COOPER LIGHTING SOLUTIONS. IN THE CASE OF CONFLICTING CONTRACTUAL

PROVISIONS, THIS NOTICE SHALL GOVERN THE STATUS OF THIS DOCUMENT. MATERIAL MASTER

PAC BOX

C EEL-R2-0005 1

45.37 LB 3

WPO

EE

L-

R2 -0

L MOD: 670247206 7/5/2022

DIMENSIONS THAT AFFECT

SAFE HANDLING OR

OPERATION

S

TOLERANCE GENERAL

• • • • •• • ••• • • • • • • • • • • • • • • • •• • ••• • • • • • • • • • • •1 OF

ANGLES ALL 1.0

C oo pe r L ig ht in g

S ol ut io ns T em pl at e

R ev

A

IP LEVEL:

DENOTES FIRST PIECE

AND IN-PROCESS

INSPECTION

8.8in [223.26mm]

18.6in [471.67mm]

34.6in [878.07mm]

39.0in [990.6mm]

3.9in [99.82mm]

7.8in [196.85mm]

EPH-PAC-0640R / EPH-PAC-0680R (4x LumaSPORT 8 Light Heads)

Operating Temperature Range -40C to 40C

Usage Indoor¹ / Outdoor

Environmental Certifications IP66

Complaince UL1598, UL8750, FCC

Effective Projected Area (EPA) 5.5 ft^2

Weight 65 lbs

EPH-PAC-0640R / EPH-PAC-0680R (4x LumaSPORT 8 Light Heads)

Mounting Rail Data

Weight 10 lbs

Mounting Options Pole New, Pole Retrofit, Wall Mount

(1) Indoor use limited to input voltages 277-480V.

* The mounting rail can be pole or wall mounted and is required to install the PAC

PROFILE

PROFILE HEAD ON

TOP

HEAD ON

BOTTOM

AC

AC WIREWAY

DC

DC WIREWAY

DMX

TD52807722EN page 16 September 7, 2023 3:22 PM

PAC Box: Attaching Mounting Rail with Banding

ISOMETRIC

PROFILE

TOP

NOTE: PAC Box AC & DC Cables are factory installed.

TD52807722EN page 17 September 7, 2023 3:22 PM

Distribution Box Electrical Specifications

DISTRIBUTION BOX OVERVIEW

Product Input Voltage¹ Phase Max Input Current (A) Surge Rating Input Wire Gauge Output Wire Gauge

EPH-DST-6PC 208 - 480 VAC Single Phase or 3 Phase 55 A 50 kA 8-1/0 AWG 18-12AWG

(1) Load balancing is necessary

TD52807722EN page 18 September 7, 2023 3:22 PM

769.21 30.28

278.07 10.95

461.65 18.18

769.21 30.28

278.07 10.95

461.65 18.18

769.21 30.28

278.07 10.95

461.65 18.18

769.21 30.28

278.07 10.95

461.65 18.18

DISTRIBUTION BOX: DIMENSIONAL DETAILS

EPH - DST

Operating Temperature Range -40C to 40C

Usage Indoor* / Outdoor

Enclosure Type Weatherproof

Environmental Certifications IP66

Effective Projected Area (EPA) 5.5 ft^2

Weight 40 lbs

AC Input Configuration 4” Port or 1 1/4” Conduit

Mounting Options Pole New, Pole Retrofit, Wall Mount

30.3in [769.11mm]

18.2in [461.77mm]

10.9in [278.13mm]

PROFILEHEAD ON BACK

POLE ATTACHMENT DETAIL

TOP

4.00Ø4.0in

[Ø101.6mm]

TD52807722EN page 20 September 7, 2023 3:22 PM

Retrofit Installation: Attaching Distribution Box with Banding

ISOMETRIC

PROFILE

TOP

NOTE: Distribution Box to be installed prior to PAC Boxes. Distribution is designed to be located over or near pole wiring access.

TD52807722EN page 21 September 7, 2023 3:22 PM

DISTRIBUTION BOX: ELECTRICAL DETAILS

Power Disconnect

System Surge Protection

Ground Bar (DC Ground)

AC Distribution Blocks

Ground Bar (AC Ground)

DC Splice Connectors

AC DISTRIBUTION

THIS SIDE

DC SPLICE

THIS SIDE

Ground Landing

Main Ground Landing

TD52807722EN page 22 September 7, 2023 3:22 PM

EXAMPLE ELECTRICAL SYSTEM CONFIGURATION

LIGHT HEADLIGHT HEAD

PAC PAC

PAC

DISTRIBUTION

BOX

AC TO PAC

AC INPUT TO SYSTEM

DC OUTAC TO PAC

D C

T O

L

IG

H T

H E

A D

D C

T O

L

IG

H T

H E

A D

DC OUT

CAUTION: ALL SYSTEM COMPONENTS TO BE GROUNDED

DO NOT INSTALL IN UNGROUNDED CONFIGURATIONS

TD52807722EN page 23 September 7, 2023 3:22 PM

EXAMPLE SYSTEM TOPOLOGIES

Wireless AirMesh Controls Example system topology showing the LUMASPORT 8 System in a Wireless AirMesh Control Installation.

NOTE: Laptop and mobile device not included. A cellular network connection requires a cellular carrier network plan.

INTERNET CONNECTED DEVICES

ALLOW SECURE ACCESS TO

LIGHTING SYSTEM CONTROLS WEB PAGE

OR WEB APPLICATION

AIRMESH HUB

LAN CONNECTION

CELLULAR

CONNECTION MESH NETWORK

Ethernet

KEY

Electrical Power Wire

DC Electrical Power Wire

EPHESUS LIGHT HEADS

PAC

DISTRIBUTION BOX

Wired DMX Controls Example system topology showing the LUMASPORT 8 System in a commonly used wired DMX Control Installation.

Refer to the specifications and limitations of your wired DMX control device before installing this configuration.

KEY

RDM/DMX (BELDEN 9729 CABLE)

EPHESUS LIGHT HEADS

Wired DMX Control Device

DISTRIBUTION BOX

PAC

Electrical Power Wire DC Electrical Power Wire

OPTIONAL

COMPONENTS

Jim Meade Memorial Fields softball fields lighting replacement 00 43 13-3

24-104PRS BID SECURITY FORM

conflict therewith shall continue in full force and effect.

11. The term “Bid” as used herein includes a Bid, offer, or proposal as applicable.

END OF SECTION

Classified

Description QTY PACs 1 Distribution box 1 Towers 1

TOP VIEWDISTRIBUTION BOX

TOWER 1

Classified

Description QTY PACs 2 Distribution box 1 Towers 1

TOP VIEWDISTRIBUTION BOX

TOWER 1

- 10 years of cloud service and cellular data communication included

-Card reader integration included via sensor input to AirMesh hub

Project Catalog # Type

Prepared by Notes Date

TD528020 page 1 September 23, 2021 12:48 PM

Top Product Features

• Can be installed anywhere you need wireless, push-button control

• Five-button, pre-programmed switch provides easy control of all lights at specified dimming levels (0%,25%, 50%, 75%, 100%)

Interactive Menu

• AirMesh Hub page 1

• Product Overview page 2

• Dynamic Scenes page 3

Typical Indoor/Outdoor Applications

• Professional Stadiums & Arenas University/Collegiate Stadiums & Arenas

• K-12 Stadiums & Arenas • Game Fields • Practice Fields • Multi-use Recreational & Municipal Fields • Public Assembly & Convention Centers

• Gymnasiums & Field Houses • Unmanned Sports Facilities

Ephesus AirMesh Hub

Wireless Lighting System Controls

Dimensional Details

HEAD ON BOTTOMLEFT PROFILE

• Can communicate via LAN connection, Wi-Fi, or through a cellular network*

• Weather-protected for outdoor venues

• Includes internal surge protection

• Enables Static and Dynamic Scenes

13.5 in.

342 mm

13.5 in.

342 mm

7.7 in.

195 mm

7.7 in.

195 mm

15.5 in.

393 mm

15.5 in.

393 mm

Due to our continuous improvement efforts, specifications are subject to change without notice.

*Cellular and/or data charges may apply

Product Certification

AirMesh Hub

TD528020 page 2 September 23, 2021 12:48 PM

Example System Topology (Wireless AirMesh Controls) Example system topology showing the LUMASPORT System in a Wireless AirMesh Control Installation.

Note: Laptop or mobile device not included. A cellular network connection requires a cellular carrier network plan.

AirMesh Function

AirMesh Hub Specifications

Description

Maximum number of lights controlled by hub Up to 1000

Maximum distance of fixture from location of hub 500 feet

Maximum allowable distance from one fixture to next 500 feet

Maximum number of programmable pre-set scenes 25 (5 per button)

Individual light control Preprogrammed via 5-button hub.

Additional scenes and light control obtained via web interface with hub

Health monitoring3

Real-time monitoring of lighting status at the fixture and system level, outage notifications, storage of power consumption, temperature and other system parameters which can be retrieved for later analysis*

Remote Connectivity

Web interface can be accessed by direct Wi-Fi connection or through internet via Ethernet or built-in cellular*

Alerts Email alerts available when connected to internet via Ethernet or built-in cellular*

Users User and administrative accounts with multiple permission levels available

Sensors

Voltage-sourcing sensors can be added to the system to turn lights on/off with daylight or occupancy sensors. Multiple output levels in response to light sensors (daylight harvesting)

Map View Ability to view light state (on/off/ alarm) in graphical map/satellite view

Scheduling Ability to schedule recurring events at fixed times or based on astronomical clock

Compatibility

Ability to add control modules to existing lighting fixtures to add Air-Mesh functionality to entire facility

Dimensions 15.5” x 13.5” x 7.7” (393 x 342 x 195 mm)

Input Power Outdoor rated power supply 90-120VAC; 8W max, 6kV surge protection

Operating Environment

Outdoor rated at -20°C to +55°C, IP65 (when latched)

Cellular Verizon 4G LTE

Wi-Fi 802.11 b/g/n

Radio SNAP 2.4GHz 802.15.4 Wi-Fi 2.4Ghz 802.11 b/g/n

Certifications FCC/IC; Tested to CAN/CSA C22.2 No. 60950-1/A2:2014 and

UL 60950-1/R:2014-10

Ratings IP651 2 Notes:

Due to our continuous improvement efforts, specifications are subject to change without notice.

¹To maintain IP rating of the unit, it must be installed with a IP65/NEMA 4X fitting at the power and ethernet entry points ²The AirMesh Hub holds a rating of IP65 for outdoor when the door is latched and all entry ports (power and Ethernet) are properly sealed. Failure to properly seal entry ports and latch the door will void the IP65 rating.

3Refer to the functionality of your Ephesus fixture for health monitoring capability.

Product Overview The AirMesh Hub is an Ephesus component that can be installed anywhere you need wireless push-button lighting control, such as municipal ballparks, hockey arenas, basketball facilities, and other multi-use complexes. The AirMesh Hub is easy for certified electricians to install in both indoor and outdoor applications that’s contained in the NEMA 4X enclosure. The 5-button 25 scenes (5 per button) controller allow for local manual access to facility lighting across specific zones or over the entire lighting installation. The AirMesh Hub enables quick and simple access to a switch station that can be programmed with unlimited options to meet the needs of the end-user.

INTERNET CONNECTED DEVICES

ALLOW SECURE ACCESS TO

LIGHTING SYSTEM CONTROLS WEB PAGE

OR WEB APPLICATION

AIRMESH HUB

MESH NETWORK

EPHESUS LUMINAIRES

AirMesh Hub

TD528020 page 4 September 23, 2021 12:48 PM

LUMASPORT 8

Dynamic Scenes

White LED Lumen(lm) Output:

55,000 & 90,000

KEY

OFF DIM ON

Unless otherwise stated for a particular scene affects independently and the scene will remain in operation until another scene or mode of operation is selected.

1For each flash period, a light will have a 10% chance of turning on under Paparazzi, and a 20% chance under Fast Paparazzi. For each flash period, a light will have a 10% chance of turning on under Paparazzi, and a 20% chance under Fast Paparazzi.

2For each flash period, a light will have a 10% chance of turning on under Sparkle, and a 20% chance under Fast Sparkle.

Paparazzi [Standard & Fast]1

Each light illuminates briefly in a random manner that resembles paparazzi flash bulbs.

When entering this mode, all fixtures will immediately turn OFF. Fast paparazzi fires faster than standard paparazzi.

Sparkle [Standard & Fast]2

Each light illuminates briefly in a random manner mimicking a glittery, sparkling appearance.

When entering this mode, all fixtures will immediately turn ON. Fast Sparkle fires more rapidly than standard sparkle.

Random Lights illuminate throughout the installation in a random manner.

All fixtures will immediately turn ON to a random dimming level between 0 and 100%. Every 100 milliseconds, each fixture will change to another random dimming level.

© 2020 Cooper Lighting, All Rights Reserved

Effective Date: 04/09/2020

Ephesus Lighting System Parts and Labor Warranty

I. What the Warranty Covers

Cooper Lighting, LLC (“Cooper Lighting”) warrants to the purchaser (“You” or “User”) of the new Ephesus fixtures from Cooper Lighting or an authorized distributor for the original installation location (“Covered Products”) that the Covered Products shall, for a period of ten (10) years from the date of original shipment (the “Fixture Warranty Period”), be free from defects in material and workmanship. During the Fixture Warranty Period, Cooper Lighting will repair or replace Covered Products to restore the operation of the Covered Products to original design criteria as necessitated by failure of the Covered Products during normal usage. For a period of ten (10 years) after the 31st day following installation (“Labor Warranty Period”), Cooper Lighting will also provide labor to restore the operation of the Covered Products to original design criteria (“Covered Service”).

Cooper Lighting’s Warranty obligations are triggered only after You experience failure of 10% of the Covered Products.

If there is any conflict between the terms of this Warranty and information communicated either orally or in writing by Cooper Lighting employees or agents, including any statements made by distributors or re-sellers, this Warranty controls.

II. Warranty Activation / Service Claims

You must make a valid claim to Cooper Lighting to receive coverage under the Warranty. Warranty claims can be serviced by contacting Cooper Lighting’s customer service and sales center:

Phone: (315) 579-2873 Email: ephesuswarranty@cooperlighting.com

If you are unsure whether a situation exists that is covered by the Warranty, please contact Cooper Lighting’s customer service and sales center at the phone number or email address listed above for assistance.

If Cooper Lighting determines that a Labor Warranty Claim exists, You must submit to Cooper Lighting quotes from at least two (2) authorized Cooper Lighting service providers for the performance of the Covered Service. Cooper Lighting will, at its discretion: (i) authorize You to accept one (1) quote from an authorized Cooper Lighting service provider and to proceed with the Covered Service with such service provider consistent with the quote; (2) obtain quotes from additional service providers and engage one of such service providers to provide the Covered Service; or (3) perform the Covered Service using its own personnel.

III. What Is Not Covered Under the Warranty

This Warranty does not cover:

a) cosmetic defects;

b) damage, defects, or failure caused by:

i. acts of God (including but not limited to floods, tornadoes, lightning or earthquakes);

ii. accident, theft, vandalism, abuse, animal or insect infestation, or negligence;

iii. sport or other related activity or other regular use of the installation location;

iv. misuse, misapplication, or modification of any part of the Covered Product;

v. improper storage, installation, repair, operation, inspection or maintenance;

vi. the use of unauthorized components, parts, accessories, or other materials or by equipment or products…