Addendum 3

5 MB Posted

Attached to
Int'l Studies Elementary School HVAC and Plumbing
Solicitation number
22-FAC-013
Issued by
Douglas County, Georgia

About this file

This addendum document represents modifications to the original contract specifications and drawings for HVAC and Plumbing Upgrades at International Studies Elementary School located at 2237 Cutts Drive in Albany, Georgia, under the jurisdiction of the Dougherty County Board of Education. Addendum No. 3, dated June 15, 2022, modifies the original specifications and drawings dated May 20, 2022. The document includes changes to Section 015000 (Temporary Facilities and Controls) regarding modular classroom specifications of 68' x 28' minimum dimensions to accommodate two standard-size classrooms (600-700 square feet) and two ADA-accessible restrooms, with detailed equipment requirements including fire alarm systems, intercom speakers, lighting fixtures, HVAC equipment capable of maintaining 70-75 degrees Fahrenheit, and above-ground septic tanks with weekly pumping service. Two modular classroom distributors are listed: Wilscot in Tallahassee, Florida, and Mobile Modular in Arcade, Georgia. The addendum also includes revisions to Section 095113 (Acoustical Panel Ceilings) and Section 234100 (Particulate Air Filtration and Bi-Polar Ionization Units), specifying that bi-polar ionization units shall be manufactured by Global Plasma Solutions or an approved equal. Drawing revisions include updated Title Sheet T100, Mechanical Demo Plans (MD101 and MD102), Mechanical New Work Plan M101, new Mechanical/Structural Details sheet M504, and Electrical Overall Plan E001 and Electrical Schedules and Legend E801, all revised as of June 15, 2022.

The addendum requires bidders to acknowledge receipt of this modification on the Bid Price Form, with failure to do so potentially resulting in bidder disqualification. Specific product manufacturers are designated for acoustical ceiling panels and suspension systems, including Armstrong World Industries, CertainTeed Corp., and USG Interiors. The project includes comprehensive mechanical and electrical work including VRF heat recovery units, ceiling cassettes, wall-mounted ductless units, kitchen hood exhaust systems, particulate air filtration units, intercom system expansions with 83 existing ceiling-mounted speakers to be replaced with Bogen #ACD2X2U or approved equal, and electrical distribution to modular classrooms with temporary power service coordination through the utility company. The contract specifies that the owner shall pay all meter fees and utility usage costs for modular units during the project duration. No pricing information, contract award dates, or specific completion timelines are provided in this addendum document.

Text of this file

International Studies Elementary School May 20, 2022 HVAC & Plumbing Upgrades Dougherty County Board of Education Albany, Georgia

Addendum No. 3- Page 1 of 3

ANDREWS, HAMMOCK & POWELL, INC. 250 CHARTER LANE, SUITE 100, MACON, GA 31210

ADDENDUM NUMBER: THREE DATED: June 15, 2022

To: All contract bidders of record.

This addendum forms a part of the Contract Documents and modifies the original Specifications and Drawings dated May 20, 2022, as noted below. Acknowledge receipt of this Addendum in the space provided on the Bid Price Form; failure to do so may subject bidder to disqualification.

CHANGES TO SPECIFICATIONS

1. SECTION 015000 - TEMPORARY FACILITIES AND CONTROLS

A. On page 015000-3, delete paragraph 2.2.C. in its entirety and replace with the following:

“C. Modular Classrooms: Of sufficient size (68’ x 28’ minimum) to accommodate two

(2) standard size classrooms (600-700 s.f.) and two (2) restrooms with ADA access. Furnish and equip modular classrooms as follows:

1. Fire Alarm Pull Station at door (one in each classroom). Connect pull station to the main building Fire Alarm Panel.

2. Fire Alarm Horn/Strobe (one in each classroom). Connect fire alarm to the main building Fire Alarm Panel.

3. Exit Light/Emergency Light (one in each classroom at egress).

4. Computer Hub/Switch. Connect to nearest IDF in the main building.

5. Wireless internet access, associated with main building. Connect portable classroom hub/switch to nearest IDF in the main building.

6. Wireless Access Point (one in each classroom). Connect to hub/switch.

7. Intercom Speaker (one in each classroom). Bogen model number

MB8TSL(VR) or approved equal.

8. Relay Board/s and Analog Card to Main Intercom Head End to support the additional temporary classroom intercom speakers.

9. Intrusion Alarm on Exterior Doors. Connect to main building alarm panel.

10. ADA Accessible Rest Room (one in each classroom).

11. Cooling and heating equipment necessary to maintain a uniform indoor temperature of 70-75 deg. F.

12. Lighting fixtures capable of maintaining average illumination of 50fc at desk height

13. One Set of Steps and One ADA Ramp.

14. Above ground septic tank, which will include weekly pumping service.

15. Exterior Light (Hubbell Model # LMC-30LU-4K-3-1-BZ or equal (one each portable).

16. Above ground septic tank, which will include weekly pumping service.

Addendum No. 3- Page 2 of 3

17. Modular Classroom Distributers:

a. Wilscot, 4742 Blountstown Hwy., Tallahassee, FL 3204;

(850) 574-9222, Contact Person; Rusty Young (850) 228-6575.

b. Mobile Modular, 530 Etheridge Rd., Arcade GA 30549,

(770) 366-3356, wendy.grenske@mobilemodular.com”

2. SECTION 095113 - ACOUSTICAL PANEL CEILINGS

A. Delete Section 095113 - Acoustical Panel Ceilings dated May 20, 2022, in its entirety and replace with Section 095113 - Acoustical Panel Ceilings, revised June 15, 2022, included herewith.

3. SECTION 234100 - PARTICULATE AIR FILTRATION AND BI-POLAR IONIZATION

UNITS

A. On page 234100-3, paragraph 2.3.A, delete the last sentence of this paragraph in its entirety and replace with the following:

“Bi-polar ionization unit shall be manufactured by Global Plasma Solutions or prior approved equal.”

CHANGES TO DRAWINGS

1. SHEET T100 - TITLE SHEET

A. Delete Sheet T100 in its entirety and replace with Sheet T100, revised 06/15/2022, included herewith.

2. SHEET MD101 - MECHANICAL DEMO PLAN -SECTOR A

B. Delete Sheet MD101 in its entirety and replace with Sheet MD101, revised 06/15/2022, included herewith.

3. SHEET MD102 - MECHANICAL DEMO PLAN - SECTOR B & C

A. Delete Sheet MD102 in its entirety and replace with Sheet MD102, revised 06/15/2022, included herewith.

4. SHEET M101 - MECHANICAL NEW WORK PLAN -SECTOR A

A. Delete Sheet M101 in its entirety and replace with Sheet M101, revised 06/15/2022, included herewith.

5. SHEET M504 - MECHANICAL/STRUCTURAL DETAILS

A. Add Sheet M504 Mechanical/Structural Details dated 06/15/2022, included herewith.

Addendum No. 3- Page 3 of 3

6. SHEET E001- ELECTRICAL OVERALL PLAN

A. Delete Sheet E001 in its entirety and replace with Sheet E001, revised 06/15/2022, included herewith.

7. SHEET E801- ELECTRICAL SCHEDULES AND LEGEND

A. Delete Sheet E801 in its entirety and replace with Sheet E801, revised 06/15/2022, included herewith.

END OF ADDENDUM #3

International Studies Elementary School Revised June 15, 2022

ACOUSTICAL PANEL CEILINGS 095113 - 1

SECTION 095113 - ACOUSTICAL PANEL CEILINGS

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

1.2 SUMMARY

A. Section includes acoustical panels and exposed suspension systems for ceilings.

1.3 ACTION SUBMITTALS

A. Product Data: For each type of product.

1.4 CLOSEOUT SUBMITTALS

A. Maintenance Data: For finishes to include in maintenance manuals.

1.5 MAINTENANCE MATERIAL SUBMITTALS

A. Furnish extra materials that match products installed and that are packaged with protective covering for storage and identified with labels describing contents.

1. Acoustical Ceiling Panels: Furnish 100 full-size panels of APC #1 and 25 full-size panels of APC #2.

2. Suspension-System Components: Furnish 100 lineal feet of each exposed component for suspension system for APC #1.

1.6 DELIVERY, STORAGE, AND HANDLING

A. Deliver acoustical panels, suspension-system components, and accessories to Project site in original, unopened packages and store them in a fully enclosed, conditioned space where they will be protected against damage from moisture, humidity, temperature extremes, direct sunlight, surface contamination, and other causes.

B. Before installing acoustical panels, permit them to reach room temperature and a stabilized moisture content.

C. Handle acoustical panels carefully to avoid chipping edges or damaging units in any way.

1.7 FIELD CONDITIONS

A. Environmental Limitations: Do not install acoustical panel ceilings until spaces are enclosed and weatherproof, wet work in spaces is complete and dry, work above ceilings is complete, and ambient temperature and humidity conditions are maintained at the levels indicated for Project when occupied for its intended use.

ACOUSTICAL PANEL CEILINGS 095113 - 2

B. Above-Ceiling Observation: Before Contractor installs acoustical panel ceilings, Architect will conduct an above-ceiling observation and report deficiencies in the Work observed.

Do not proceed with installation of ceilings until deficiencies have been corrected.

1. Notify Architect seven days in advance of date and time when Project, or part of Project, will be ready for above-ceiling observation.

2. Before notifying Architect, complete the following in areas to receive ceilings:

a. Installation of lighting fixtures, powered for operation.

b. Installation, insulation, and leak and pressure testing of water piping systems.

c. Installation of air-duct systems.

d. Installation of air devices.

e. Installation of mechanical system control-air tubing.

f. Installation of ceiling support framing.

C. Coordinate with fire marshal prior to installing ceilings. Most jurisdictions require above-ceiling inspections prior to installing ceilings.

PART 2 - PRODUCTS

2.1 PERFORMANCE REQUIREMENTS

A. Surface-Burning Characteristics: Comply with ASTM E 84; testing by a qualified testing agency. Identify products with appropriate markings of applicable testing agency.

1. Flame-Spread Index: Comply with ASTM E 1264 for Class A materials.

2. Smoke-Developed Index: 450 or less.

2.2 ACOUSTICAL PANELS, GENERAL

A. Source Limitations: Obtain acoustical ceiling panels and supporting suspension system from single source from single manufacturer.

B. Acoustical Panel Standard: Provide manufacturer's standard panels of configuration indicated that comply with ASTM E 1264 classifications as designated by types, patterns, acoustical ratings, and light reflectances unless otherwise indicated.

C. Acoustical Panel Colors and Patterns: Match appearance characteristics indicated for each product type.

2.3 ACOUSTICAL PANELS <APC #1> (NON WET AREAS)

A. Acoustical tile ceiling in non-wet areas shall be provided by one of the following:

1. Armstrong World Industries, Inc.

2. CertainTeed Corp.

3. USG Interiors, Inc.

ACOUSTICAL PANEL CEILINGS 095113 - 3

B. Classification: Provide panels complying with ASTM E 1264 for type, form, and pattern as follows:

1. Type and Form: Type XII, mineral fiber with transparent membrane, non-directional fissured design; Form 2, water felted.

2. Pattern: E.

C. Color: White.

D. LR: Not less than 0.90.

E. NRC: Not less than 0.95.

F. Humidity/Sag Resistance: Humiguard Plus.

G. Edge/Joint Detail: Square edge.

H. Thickness: 5/8 inch.

I. Modular Size: 24 by 24 inches.

2.4 ACOUSTICAL PANELS <APC #2> (WET AREAS)

A. Manufacturers/Products: Subject to compliance with requirements, provide one of the following:

1. Armstrong World Industries, Inc.; Clean Room VL

2. CertainTeed Corp.; Performa, Vinyrock

3. USG Interiors, Inc.; Subsidiary of USG Corporation.; Gypsum Lay-in Clima Plus

B. Classification: Provide panels complying with ASTM E 1264 for type, form, and pattern as follows:

1. Type and Form: Type IV or Type XX other types; described as high-density, ceramic- and mineral base panels with scrubbable finish, resistant to heat, moisture, and corrosive fumes. Provide gypsum core and stippled pattern tile.

2. Pattern: As indicated by manufacturer’s designation.

C. Color: White.

D. LR: Not less than 0.78.

E. CAC: Not less than 38.

F. Edge/Joint Detail: Square.

G. Thickness: 1/2 inch.

H. Modular Size: 24 by 24 inches.

ACOUSTICAL PANEL CEILINGS 095113 - 4

2.5 METAL SUSPENSION SYSTEMS, GENERAL

A. Metal Suspension-System Standard: Provide manufacturer's standard direct-hung metal suspension systems of types, structural classifications, and finishes indicated that comply with applicable requirements in ASTM C 635/C 635M.

1. High-Humidity Finish: Comply with ASTM C 635/C 635M requirements for "Coating Classification for Severe Environment Performance" where high-humidity finishes are indicated.

B. Wire Hangers, Braces, and Ties: Provide wires complying with the following requirements:

1. Zinc-Coated, Carbon-Steel Wire: ASTM A 641/A 641M, Class 1 zinc coating, soft temper.

2. Size: Select wire diameter so its stress at three times hanger design load (ASTM C 635/C 635M, Table 1, "Direct Hung") will be less than yield stress of wire, but provide not less than 0.106-inch-diameter wire.

2.6 METAL SUSPENSION SYSTEM <For APC #1 Ceilings>

A. Basis-of-Design Product: Subject to compliance with requirements, provide Armstrong World Industries; Suprafine ML or a comparable product by another manufacturer:

1. Armstrong World Industries, Inc.

2. CertainTeed Corp.

3. USG Interiors, Inc.; Subsidiary of USG Corporation

B. 15/16-Inch Capped, Double-Web, Steel Suspension System: Main and cross runners roll formed from cold-rolled steel sheet; prepainted, electrolytically zinc coated, or hot-dip galvanized according to ASTM A 653/A 653M, not less than G30 coating designation; with prefinished 15/16-inch-wide metal caps on flanges.

1. Structural Classification: Intermediate-duty system.

2. End Condition of Cross Runners: Override (stepped) type.

3. Face Design: Flat, flush.

4. Cap Material: Steel cold-rolled sheet.

5. Cap Finish: Painted white.

2.7 METAL SUSPENSION SYSTEM <For APC #2 Ceilings>

A. Manufacturers/Products: Subject to compliance with requirements, provide one of the following:

1. Armstrong World Industries, Inc.; Prelude Plus XL Fireguard

2. CertainTeed Corp.; Classic Environmental Stab

3. USG Interiors, Inc.; Subsidiary of USG Corporation; Don ZXLA

ACOUSTICAL PANEL CEILINGS 095113 - 5

B. 15/16-Inch Capped, Double-Web, Hot-Dip Galvanized, G60, Steel Suspension System:

Main and cross runners roll formed from cold-rolled steel sheet; hot-dip galvanized according to ASTM A 653/A 653M, G60 coating designation; with prefinished, cold-rolled, 15/16-inch-wide aluminum caps on flanges.

1. Structural Classification: Intermediate-duty system.

2. Face Design: Flat, flush.

3. Face Finish: Painted white.

2.8 METAL EDGE MOLDINGS AND TRIM

A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

1. Armstrong World Industries, Inc.

2. CertainTeed Corp.

3. USG Interiors, Inc.; Subsidiary of USG Corporation.

B. Roll-Formed, Sheet-Metal Edge Moldings and Trim: Type and profile indicated or, if not indicated, manufacturer's standard moldings for edges and penetrations that comply with seismic design requirements; formed from sheet metal of same material, finish, and color as that used for exposed flanges of suspension-system runners.

1. Provide manufacturer's standard edge moldings that fit acoustical panel edge details and suspension systems indicated and that match width and configuration of exposed runners unless otherwise indicated.

2. For lay-in panels in corridors, provide stepped edge molding that forms reveal of same depth and width as that formed between edge of panel and flange at exposed suspension member.

3. For circular penetrations of ceiling, provide edge moldings fabricated to diameter required to fit penetration exactly.

PART 3 - EXECUTION

3.1 EXAMINATION

A. Examine substrates, areas, and conditions, including structural framing to which acoustical panel ceilings attach or abut, with Installer present, for compliance with requirements specified in this and other Sections that affect ceiling installation and anchorage and with requirements for installation tolerances and other conditions affecting performance of acoustical panel ceilings.

B. Examine acoustical panels before installation. Reject acoustical panels that are wet, moisture damaged, or mold damaged.

C. Proceed with installation only after unsatisfactory conditions have been corrected.

ACOUSTICAL PANEL CEILINGS 095113 - 6

3.2 PREPARATION

A. Measure each ceiling area and establish layout of acoustical panels to balance border widths at opposite edges of each ceiling. Avoid using less-than-half-width panels at borders, and comply with layout shown on reflected ceiling plans.

3.3 INSTALLATION

A. General: Install acoustical panel ceilings to comply with ASTM C 636/C 636M and seismic design requirements indicated, according to manufacturer's written instructions and CISCA's "Ceiling Systems Handbook."

B. Suspend ceiling hangers from building's structural members and as follows:

1. Install hangers plumb and free from contact with insulation or other objects within ceiling plenum that are not part of supporting structure or of ceiling suspension system.

2. Splay hangers only where required to miss obstructions; offset resulting horizontal forces by bracing, countersplaying, or other equally effective means.

3. Where width of ducts and other construction within ceiling plenum produces hanger spacings that interfere with location of hangers at spacings required to support standard suspension-system members, install supplemental suspension members and hangers in form of trapezes or equivalent devices.

4. Secure wire hangers to ceiling-suspension members and to supports above with a minimum of three tight turns. Connect hangers directly either to structures or to inserts, eye screws, or other devices that are secure and appropriate for substrate and that will not deteriorate or otherwise fail due to age, corrosion, or elevated temperatures.

5. Secure flat, angle, channel, and rod hangers to structure, including intermediate framing members, by attaching to inserts, eye screws, or other devices that are secure and appropriate for both the structure to which hangers are attached and the type of hanger involved. Install hangers in a manner that will not cause them to deteriorate or fail due to age, corrosion, or elevated temperatures.

6. Do not support ceilings directly from permanent metal forms or floor deck. Fasten hangers to cast-in-place hanger inserts, postinstalled mechanical or adhesive anchors, or power-actuated fasteners that extend through forms into concrete.

7. When steel framing does not permit installation of hanger wires at spacing required, install carrying channels or other supplemental support for attachment of hanger wires.

8. Do not attach hangers to steel deck tabs.

9. Do not attach hangers to steel roof deck. Attach hangers to structural members.

10. Space hangers not more than 48 inches o.c. along each member supported directly from hangers unless otherwise indicated; provide hangers not more than 8 inches from ends of each member.

11. Size supplemental suspension members and hangers to support ceiling loads within performance limits established by referenced standards and publications.

ACOUSTICAL PANEL CEILINGS 095113 - 7

C. Secure bracing wires to ceiling suspension members and to supports with a minimum of four tight turns. Suspend bracing from building's structural members as required for hangers, without attaching to permanent metal forms, steel deck, or steel deck tabs. Fasten bracing wires into concrete with cast-in-place or post installed anchors.

D. Install edge moldings and trim of type indicated at perimeter of acoustical ceiling area and where necessary to conceal edges of acoustical panels.

1. Screw attach moldings to substrate at intervals not more than 16 inches o.c. and not more than 3 inches from ends, leveling with ceiling suspension system to a tolerance of 1/8 inch in 12 feet. Miter corners accurately and connect securely.

2. Do not use exposed fasteners, including pop rivets, on moldings and trim.

E. Install suspension-system runners so they are square and securely interlocked with one another. Remove and replace dented, bent, or kinked members.

F. Install acoustical panels with undamaged edges and fit accurately into suspension-system runners and edge moldings. Scribe and cut panels at borders and penetrations to provide a neat, precise fit.

1. Arrange directionally patterned acoustical panels as follows:

a. Install panels in a basket-weave pattern.

2. For square-edged panels, install panels with edges fully hidden from view by flanges of suspension-system runners and moldings.

3. Paint cut edges of panel remaining exposed after installation; match color of exposed panel surfaces using coating recommended in writing for this purpose by acoustical panel manufacturer.

3.4 CLEANING

A. Clean exposed surfaces of acoustical panel ceilings, including trim, edge moldings, and suspension-system members. Comply with manufacturer's written instructions for cleaning and touchup of minor finish damage. Remove and replace ceiling components that cannot be successfully cleaned and repaired to permanently eliminate evidence of damage.

END OF SECTION 095113

ACOUSTICAL PANEL CEILINGS 095113 - 8

THIS PAGE INTENTIONALLY LEFT BLANK

D A

D E

BLECKLEY LAURENS

CHATHAM

EFFINGHAM

IRWIN

BERRIEN

LOWNDESGRADY

SE

M

IN

OL

E

DECATUR

EARLY

MILLER

BAKER

THOMAS

BROOKS

COLQUITT

MITCHELL

COOK

TIFT

SCHLEY

TERRELL

DOUGHERTY

WEBSTER

RANDOLPH

QUITMAN

CLAY

CALHOUN

CHATTAHOOCHEE

STEWART

MARION

WILCOX

CRISP

WORTH

LEE

TURNER

DOOLY

MACON

SUMTER

HOUSTON

PULASKI

McINTOSH

PIERCE

CHARLTON

LA

NI

ER

CLINCH

ECHOLS

ATKINSON

WARE

CAMDEN

BRANTLEY

GLYNN

TOOMBS

APPLING

COFFEE

BEN HILL

TELFAIR

DAVIS

JEFF

WHEELER

DODGE

TREUTLEN

M

ON

TG

OM

ER

Y

LONG

WAYNE

LIBERTY

BULLOCH

EVANS

CANDLER

TATTNALL

BRYAN

DAWSON FRANKLIN

CLARKE

OCONEE

PUTNAM

BALDWIN

TWIGGS

HENRY

FA

YE

TT

E

PIKE

UPSON

SPALDING

M

ER

IW

ET

HER

HARRIS

MUSCOGEE

TALBOT

COWETA

HEARD

TROUP

PEACH

CRAWFORD

TAYLOR

BIBB

MONROE

LAMAR

BUTTS

JASPER

JONES

CHEROKEE

FULTON

PAULDING

HARALSON

CARROLL

DOUGLAS

BARTOWFLOYD

POLK

COBB

NEWTON

DEKALB

CL

AY

TO

N

ROCKD

AL

E

WALTON

MORGAN

GWINNETT

FORSYTH

JACKSON

HALL BANKS

BARROW

M cD

U F

F

IE

JEFFERSON

EMANUEL

WASHINGTON

WILKINSON

JOHNSON

HANCOCK

WARREN

GLASCOCK

JENKINS

SCREVEN

RICHMOND

BURKE

COLUMBIA

OGLETHORPE

WILKES

TALIAFERROGREENE

LINCOLN

ELBERT

HART

MADISON

RABUN

STEPHENS

FANNIN

PICKENS

GILMER

WHITF

IELD

GORDON

C H

AT

TO

O G

A

WALKER M

U

R R

A Y

CATOOSA

UNION

LUMPKIN

WHITE

HABERSHAM

TOWNS

BACON

DOUGHERTY

PROJECT NUMBER:

DATE:

DRAWN BY:

CHECKED BY:

TITLE:

SUBJECT TO GENERAL

COPYRIGHT LAWS ©

REVISIONS

INDEX OF DRAWINGS GEORGIA/COUNTY MAP PROJECT LOCATION

PROJECT NUMBER: 5056

T100

TITLE SHEET

2021204

IN

T

E R

N A

T

IO

N A

L S

T U

D

IE

S E

L E

M E

N T

A R

Y S

C H

O O

L

H V

A C

P

L U

M B

IN

G

U P

G R

A D

E S

05/20/2022

HHP

JA3

C

U T

T S

D R

A

L B

A N

Y G

A

INTERNATIONAL STUDIES ELEMENTARY

SCHOOL - HVAC & PLUMBING UPGRADES

2237 CUTTS DR, ALBANY, GA 31705

T100 TITLE SHEET

C101 SITE PLAN

A100 CONSTRUCTION PHASING PLAN

A200 ARCHITECTURAL CEILING PLAN - OVERALL

MD100 MECHANICAL DEMO PLAN - OVERALL

MD101 MECHANICAL DEMO PLAN - SECTOR A

MD102 MECHANICAL DEMO PLAN - SECTOR B & C

M100 MECHANICAL OVERALL NEW WORK PLAN

M101 MECHANICAL NEW WORK PLAN - SECTOR A

M102 MECHANICAL NEW WORK PLAN - SECTOR B & C

M201 MECHANICAL NEW WORK PIPING PLAN

M301 VRF WIRING DIAGRAMS

M302 VRF PIPING DIAGRAMS

M501 MECHANICAL DETAILS

M502 MECHANICAL DETAILS

M503 MECHANICAL DETAILS

M504 MECHANICAL/STRUCTURAL DETAILS

M601 MECHANICAL SCHEDULES

M602 MECHANICAL SCHEDULES, LEGEND & GENERAL NOTES

P101 PLUMBING PLAN - SECTOR A

P102 PLUMBING PLAN - SECTORS B & C

E001 ELECTRICAL OVERALL PLAN

ED101 ELECTRICAL DEMOLITION PLAN - SECTOR A

ED102 ELECTRICAL DEMOLITION PLAN - SECTORS B & C

E101 ELECTRICAL NEW WORK PLAN - SECTOR A

E102 ELECTRICAL NEW WORK PLAN - SECTORS B & C

E801 ELECTRICAL SCHEDULES & LEGEND

GA DOE ID #: 5056

No. Description Date

2 ADDENDUM #3 06/15/22

T

TT

TT

TT TT TT TT TT

TT TT TT TT TT TT TT

TT TT TT TT TT

TTTT TT TT TT TT TT TT

TT

1 1 1 1 1 1 1

11111111

4 4

2 2

2 2

6 6 6 6 6

2 2

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

SP. ED. RESOURCE

SP. ED.

CAFETERIA

GIRLS TOILET

BOYS TOILET

GIRLS TOILET

BOYS TOILET

Room

Room

ART ROOM

CONF.

RECEPTION

VAULT

PRINCIPAL

CLINIC

Room

COUNSELOR

ASST. PRINCIPAL

ART STORAGE

KILN

JANITOR

DRESSING

Room

PARENT

KITCHEN

Room

Room

TOILET

OFFICE

DRY STORAGE

Room

Room

Room

Room

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

15 15

18 18 18

PROJECT NUMBER:

DATE:

DRAWN BY:

CHECKED BY:

TITLE:

SUBJECT TO GENERAL

COPYRIGHT LAWS ©

REVISIONS

A

B

C

GA DOE ID #: 5056

MD101

MECHANICAL DEMO PLAN -

SECTOR A

2021204

IN

T

E R

N A

T

IO

N A

L S

T U

D

IE

S E

L E

M E

N T

A R

Y S

C H

O O

L

H V

A C

P

L U

M B

IN

G

U P

G R

A D

E S

05/20/2022

HHP

JA3

C

U T

T S

D R

A

L B

A N

Y G

A

1/8" = 1'-0"1 MECHANICAL DEMO PLAN - SECTOR A

11 . EXISTING DISHWASHER EXHAUST FAN TO REMAIN IN THIS APPROXIMATE LOCATION.

12 . EXISTING KITCHEN EXHAUST FAN TO BE REMOVED IN THIS APPROXIMATE LOCATION. SEE NEW WORK PLAN FOR REPLACEMENT. ASSOCIATED

DUCTWORK TO REMAIN FOR REUSE.

13 . EXISTING KITCHEN MAKE UP AIR UNIT TO BE REMOVED IN THIS APPROXIMATE LOCATION. SEE NEW WORK PLAN FOR REPLACEMENT. ASSOCIATED

DUCTWORK TO REMAIN FOR REUSE.

14 . REMOVE EXISTING PACKAGED TERMINAL HEAT PUMP. SEE NEW WORK PLAN FOR INSTALLATION OF NEW PTHP IN SAME LOCATION.

15 . EXISTING GRAVITY VENTILATOR TO REMAIN FOR REUSE

16 . EXISTING GOOSNECK TO REMAIN FOR REUSE.

17 . REMOVE EXISTING CEILING MOUNTED EXHAUST FAN FROM THIS APPROXIMATE LOCATION. DEMO DUCTWORK TO GOOSENECK. PATCH AND EXISTING

DUCT TO REMAIN.

18 . DEMO EXISTING DUCTWORK.

19 . REMOVE EXISTING HEAT PUMP ON ROOF FROM THIS APPROXIMATE LOCATION. REMOVE ANY ASSOCIATED REFRIGERANT PIPES (ON ROOF AND INSIDE BUILDING). EQUIPMENT SUPPORT RAILS TO REMAIN FOR REUSE. ROOF PITCH POCKET SHALL DEMOED AND ROOF OPENING WILL BE USED FOR A NEW

PIPE BOX. SEE NEW WORK DRAWINGS FOR PIPE BOX

20 . PATCH AND SEAL OPENING IN DUCT AIR TIGHT. REINSULATE AS NEEDED.

21 . EXISTING GOOSENECK AND EXHASUT DUCT FOR KILN TO REMAIN.

1 . REMOVE EXISTING WALL HUNG HEAT PUMP AND ASSOCIATED DISCONNECT. SALVAGE EXISTING GPS BIPOLAR IONIZATION UNIT FOR INSTALLATION IN

NEW WALL HUNG HEAT PUMP SAME LOCATION.

2 . REMOVE EXISTING CEILING HEATER. FIELD VERIFY EXACT LOCATION. CAREFULLY REMOVE CEILING TILE / GRID AS REQUIRED FOR REMOVAL AND INSTALLATION OF NEW CEILING HEATER IN SAME LOCATION. REPAIR / REPLACE CEILING TILE / GRID DAMAGED DURING DEMOLITION.

3 . REMOVE EXISTING VERTICAL FAN COIL UNIT FROM THIS APPROXIMATE LOCATION. EXISTING SUPPLY AND RETURN DUCT TO BE REUSED FOR WITH NEW UNIT. SALVAGE EXISTING GPS BIPOLAR IONIZATION UNIT FOR INSTALLATION IN NEW VRF FAN COIL UNIT. SEE NEW WORK DRAWING FOR NEW FAN COIL

UNIT AND DUCTWORK.

4 . REMOVE EXISTING ROOF EXHAUST FAN FROM THIS APPROXIMATE LOCATION. SEE NEW WORK DRAWING FOR EXHAUST FAN REPLACEMENT.

6 . REMOVE EXISTING FAN COIL UNIT IN CEILING FROM THIS APPROXIMATE LOCATION. REMOVE EXISTING SUPPLY AND RETURN DUCT FROM FAN COIL UNIT UP TO THE SCOPE OF WORK SYMBOL. SALVAGE EXISTING GPS BIPOLAR IONIZATION UNIT FOR INSTALLATION IN NEW VRF FAN COIL UNIT. SEE NEW

WORK DRAWING FOR NEW FAN COIL UNIT AND DUCTWORK.

7 . REMOVE EXISTING AIR HANDLING UNIT FROM THIS APPROXIMATE LOCATION. REMOVE EXISTING SUPPLY AND RETURN DUCT FROM AIR HANDLING UNIT UP TO THE SCOPE OF WORK SYMBOL. SALVAGE EXISTING GPS BIPOLAR IONIZATION UNIT FOR INSTALLATION IN NEW VRF FAN COIL UNIT. SEE NEW

WORK DRAWING FOR NEW AIR HANDLING UNIT AND DUCTWORK.

8 . REMOVE EXISTING CEILING MOUNTED EXHAUST FAN FROM THIS APPROXIMATE LOCATION. SEE NEW WORK DRAWING FOR EXHAUST FAN REPLACEMENT.

9 . REMOVE EXISTING HEAT PUMP ON ROOF FROM THIS APPROXIMATE LOCATION. REMOVE ANY ASSOCIATED REFRIGERANT PIPES (ON ROOF AND INSIDE BUILDING). ROOF PITCH POCKET SHALL BE FILLED WITH EXPANDED FOAM INSULATION AND CAPPED WITH AN 18 GAUGE GALVANIZED SHEET METAL CAP OVER PITCH POCKET. GALVANIZED CAP EDGE SHALL BE BROKEN, CORNERS WELDED, AND SCREWED TO VETICAL FACE OF PITCH POCKET. CAP SHALL

BE CAULKED WATER TIGHT.

10 . EXISTING ROOF INTAKE SHALL BE REMOVED. THE EXISTING CURB SHALL BE CAPPED AND SEALLED. SEE ROOF CURB CAP DETAIL.

NOTES: (THIS SHEET ONLY)

GENERAL NOTE: OWNERSHIP OF ALL REMOVED EQUIPMENT NOT RETAINED BY

THE OWNER SHALL BECOME PROPERTY OF THE CONTRACTOR. COORDINATE

WITH OWNER FOR SALVAGE OF ANY EQUIPMENT TO BE RETAINED BY THE OWNER.

GENERAL NOTE: GPS NEEDLEPOINT BIPOLAR IONIZATION DEVICES (NPBI) SHALL

BE REMOVED FROM THE EXISTING HVAC UNITS BY THE CONTROLS CONTRACTOR.

NPBI DEVICE(S) SHALL BE LABELED, PROPERLY AND SAFELY STORED, AND

REINSTALLED IN THE NEW UNIT IN THE SAME LOCATION. NPBI DEVICE(S) FROM

HVAC UNITS REMOVED AND NOT REPLACED SHALL BE TURNED OVER TO THE

OWNER.

No. Description Date

1 ADDENDUM #2 06/06/22

TT

TT

TT TT TT TT TT

TTTTTT TTTT

1 1 1 1 1 1 1

11111

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

MEDIA

WORK ROOM

CLASSROOM

OFFICE

STORAGE

STORAGE

JANITOR

GIRLS

BOYS

BOYS

GIRLS

A.V. STORAGE

MEDIA PRODUCTION

GROUP ROOM

BOYS

GIRLS

IDF

TT

TT

4 4

GYM

STORAGE

CLOSET

EXTENDED DAY

P.E. OFFICE

GIRLS

BOYS

PROJECT NUMBER:

DATE:

DRAWN BY:

CHECKED BY:

TITLE:

SUBJECT TO GENERAL

COPYRIGHT LAWS ©

REVISIONS

A

B

C

GA DOE ID #: 5056

MD102

MECHANICAL DEMO PLAN -

SECTOR B & C

2021204

IN

T

E R

N A

T

IO

N A

L S

T U

D

IE

S E

L E

M E

N T

A R

Y S

C H

O O

L

H V

A C

P

L U

M B

IN

G

U P

G R

A D

E S

05/20/2022

HHP

JA3

C

U T

T S

D R

A

L B

A N

Y G

A

1/8" = 1'-0"1 MECHANICAL DEMO PLAN - SECTOR B

1/8" = 1'-0"2 MECHANICAL DEMO PLAN - SECTOR C

NOTES: (THIS SHEET ONLY)

1 . REMOVE EXISTING WALL HUNG HEAT PUMP AND ASSOCIATED DISCONNECT. REMOVE EXISTING GPS BIPOLAR IONIZATION AND

STORE UNIT FOR INSTALLATION IN NEW WALL HUNG HEAT PUMP SAME LOCATION.

2 . REMOVE EXISTING CEILING HEATER FROM THIS APPROXIMATE LOCATION. SEE NEW WORK DRAWING FOR CEILING HEATER

REPLACEMENT.

3 . REMOVE EXISTING PAD MOUNTED PACKAGED HEAT PUMP, ASSOCIATED DUCTWORK, AND DUCT COVER UP TO LOCATION SHOWN. REMOVE EXISTING GPS BIPOLAR IONIZATION UNIT AND STORE FOR REINSTALLATION IN NEW PACKAGED HEAT PUMP

SAME LOCATION.

4 . REMOVE EXISTING CEILING MOUNTED EXHAUST FAN FROM THIS APPROXIMATE LOCATION. SEE NEW WORK DRAWING FOR

EXHAUST FAN REPLACEMENT.

5 . REMOVE EXISTING PACKAGED TERMINAL HEAT PUMP. SEE NEW WORK PLAN FOR INSTALLATION OF NEW PTHP IN SAME

LOCATION.

6 . REMOVE EXISTING WALL HEATER IN THIS APPROXIMATE LOCATION. SEE NEW WORK DRAWINGS FOR NEW WALL HEATER.

GENERAL NOTE: OWNERSHIP OF ALL REMOVED EQUIPMENT NOT RETAINED BY

THE OWNER SHALL BECOME PROPERTY OF THE CONTRACTOR. COORDINATE

WITH OWNER FOR SALVAGE OF ANY EQUIPMENT TO BE RETAINED BY THE OWNER.

GENERAL NOTE: GPS NEEDLEPOINT BIPOLAR IONIZATION DEVICES (NPBI) SHALL

BE REMOVED FROM THE EXISTING HVAC UNITS BY THE CONTROLS CONTRACTOR.

NPBI DEVICE(S) SHALL BE LABELED, PROPERLY AND SAFELY STORED, AND

REINSTALLED IN THE NEW UNIT IN THE SAME LOCATION. NPBI DEVICE(S) FROM

HVAC UNITS REMOVED AND NOT REPLACED SHALL BE TURNED OVER TO THE

OWNER.

No. Description Date

1 ADDENDUM #2 06/06/22

WHHP-1 WHHP-2 WHHP-3 WHHP-4 WHHP-5 WHHP-6 WHHP-7 WHHP-8

WHHP-17WHHP-16WHHP-15WHHP-14WHHP-13WHHP-12WHHP-11

WHHP-9

WHHP-10

ECH-1

ECH-2 ECH-3

ECH-4

ECH-5

EF-1 EF-2

EF-3

EF-5 EF-4

EF-6 EF-7 EF-8

EF-10EF-9

EF-15

HP-1

HP-2

IU-2.1

IU-2.2 IU-2.3

IU-2.4

IU-2.5

IU-1.4IU-1.3IU-1.2IU-1.1

IU-1.6

IU-1.7

IU-1.8

HRU-1

HRU-2

MBC-2

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

Room

Room

Room

Room

KITCHEN

DRY STORAGE

OFFICE

TOILET

Room

Room

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

SP. ED.

SP. ED. RESOURCE

CONF.

PRINCIPAL

VAULT

TOILET

TOILET

CLINIC

TOILET

TEST

COUNSELOR

ASST. PRINCIPAL

ART STORAGE

KILN

ART ROOM

JANITOR

DRESSING

BOYS TOILET

GIRLS TOILET

GIRLS TOILET

BOYS TOILET

CAFETERIA

Room

BOYS

Room

GIRLS

Room

PARENT

TEACHER WORKWOOM

CLASSROOM

RECEPTION

OAU-1

1 1 1 1 1

1 1 1 1 1 1 1 1

CC

CC

CCCC

OA-150

OA-50

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

AHU-1

AHU-2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A1

A1

"x

16"x16"14"x14"12"ø10"ø

75 CFM

IU-1.9

550 550

550 550

550 550

550 550

550 550

550 550

510 510

510 510

510 510

510 510

510510

510510

510510510

OAU-2

A2

10"ø

"ø

8"ø

750 750 750 750 750

750750750750750

B1

B1

B1

B1

B1

B1

B1

B1

KEF-1

1100 1100 1100 1100

1100 1100 1100 1100

275 275 275 2751360

DCU-1

PTHP-1

4 4

4 4

4 4

4 4 4 4 4 4 4

4 4 4 4 4

IU-1.5

8 8

DFCU-1

MBC-1

TT TT TT TT TT TT TT

TTTTTTTT

TT

TT

TT TT TT TT

TT TT TT TT TT TT TTTT

TT

TT

TT

TT

IU-1.10

IU-1.11

IU-2.8

IU-2.7

IU-2.6

EF-12

KSF-2 KSF-1

8"ø

8"ø 8"ø

8"ø

8"ø

8"ø 8"ø

8"ø

14"x14"

20"x12" 20"x12"

20"x20" 20"x20"

20"x20"

8"x20"

20"x20"

8"ø

8"ø 8"ø 6"ø

6"ø

8"ø

20"x20"

8"ø

"ø

16"x16"

6"ø

8"ø

20"x20" 20"x20"

12"ø 14"x14"

8"ø 8"ø

8"ø

8"ø

8"ø

20"x20"

10"ø

8"ø

8"ø

10"ø

10"ø 12"x12"

12"x12"

10"ø

8"x14"

12"ø

MM

MM

MM

MM

MM

"x

"x

10"ø

10"ø 10"ø

10"ø

TT

TT

A1

10"x10"

TT

EF-118

MM

MM MM

A2

10"ø

180180

"x

12"x12"

"x

"ø

12"ø

MVD

MVD

8"x14"

"x

11"x18"

"x

20"x20"

171717

17 17

OA CFM - 500

OA CFM - 500

TT

TT

181818 18 18 18

18 18

PROJECT NUMBER:

DATE:

DRAWN BY:

CHECKED BY:

TITLE:

SUBJECT TO GENERAL

COPYRIGHT LAWS ©

REVISIONS

A

B

C

GA DOE ID #: 5056

M101

MECHANICAL NEW WORK

PLAN - SECTOR A

2021204

IN

T

E R

N A

T

IO

N A

L S

T U

D

IE

S E

L E

M E

N T

A R

Y S

C H

O O

L

H V

A C

P

L U

M B

IN

G

U P

G R

A D

E S

05/20/2022

HHP

JA3

C

U T

T S

D R

A

L B

A N

Y G

A

1/8" = 1'-0"1 MECHANICAL NEW WORK PLAN - SECTOR A

NOTES: (THIS SHEET ONLY)

28 . VRF CENTRALIZED CONTROLLER MOUNTED ON WALL WITH B.E. 4' 6" A.F.F.13 . NEW HEAT PUMP MOUNTED ON EXISITNG ROOF SUPPORTS IN THSI APPROXIMATE LOCATION. SEE M201 FOR PIPING. VERIFY EQUIPMENT SUPPORTS

ARE ADEQUATE. ADD ADDITION SUPPORTS AS NEEDED.

14 . KITCHEN HOOD EXHAUST FAN MOUNTED ON EXISTING CURB. PROVIDE CURB ADAPTER AS NEEDED.

15 . KITCHEN HOOD SUPPLY FAN MOUNTED ON EXISTING CURB. PROVIDE CURB ADAPTER AS NEEDED.

16 . EXISTING DISHWASHER EXHAUST FAN TO REMAIN.

17 . FACTORY WALL MOUNTED VRF WIRED UNIT THERMOSTAT/CONTROLLER. MOUNT B.E. 4' 6" A.F.F..

18 . WALL MOUNTED DDC SPACE TEMPERATURE/HUMIDITY SENSOR. MOUNT B.E. OF SENSOR 4' 6" A.F.F..

19 . FACTORY WALL MOUNTED DUCTLESS UNIT THERMOSTAT. MOUNT B.E. 4' 6" A.F.F..

20 . DDC TEMERATURE SENSOR TO MONITOR IDF SPACE TEMPERATURE. MOUNT B.E. 4' 6" A.F.F..

21 . WALL MOUNTED DUCTLESS FAN COIL UNIT. MOUNT B.E. OF UNIT 6' 8" A.F.F.

22 . ROOF MOUNTED DUCTLESS CONDENSING UNIT. SEE DUCTLESS UNIT ATOP EQUIPMENT SUPPORT RAIL DETAIL.

23 . ATTACH NEW DUCT TO EXISTING DUCTWORK.

25 . INSTALL 6' TALL CHAINLINK FENCE AROUND EQUIPMENT YARD IN ACCORDANCE TO SPECIFICATIONS. INSTALL 3'GATE IN FENCE FOR SERVICE

ACCESS.

26 . APPROXIMATE LOCATION AND SEPERATION OF JOISTS. FEILD VERFIY EXACT LOCATIONS AND CONDITIONS PRIOR TO INSTALLING THE UNIT. SEE

M504 FOR STRUCTURAL REINFORCEMENT PLANS.

27 . NEW DDC PANEL MOUNTED ON WALL.

1 . WALL HUNG HEAT PUMP. SEE WALL HUNG HEAT PUMP DETAIL - DUCTED SUPPLY.

2 . ROOF MOUNTED CENTRIFUGAL EXHAUST FAN. SEE ROOF MOUNTED CENTRIFUGAL EXHAUST FAN DETAIL.

3 . CEILING HEATER. CEILING HEATER SHALL BE MOUNTED RECESSED IN T-BAR CEILING. SEE CEILING HEATER SCHEDULE.

4 . ATTACH NEW DUCT TO EXISTING DUCTWORK AT THIS APPROXIMATE LOCATION.

5 . VRF HEAT RECOVERY UNIT MOUNTED ON CONCRETE EQUIPMENT PAD. SEE CONCRETE EQUIPMENT PAD DETAIL. SEE M201 FOR PIPING.

6 . NEW VRF AIR HANDLING UNIT MOUNTED IN CEILING IN THE SAME APPROXIMATE LOCATION AS THE EXISING UNIT. SEE M201 FOR PIPING.

7 . VRF CEILING CASSETTE. SUSPENDED FROM DROP RODS (MIN 3/8") CONNECTED TO OVERHEAD STRUCTURE WITH SUPPLEMENTAL 2"X2"X1/4" ANGLE

IRON. SEE M201 FOR PIPING.

8 . CEILING MOUNTED EXHAUST FAN. CONNECT NEW DUCTWORK TO EXISITNG DUCT. PROVIDE DUCT OFFSET AND FITTINGS AS REQUIRED. FEILD

COORDINATE.

9 . 100% OUTSIDE AIR UNIT MOUNTED ATOP CUSTOM STRUCTURAL LARGE BASE ROOF CURB. SEE M504 FOR STRUCTURAL SHEETS S-1 & S-2 FOR STRUCTURAL DRAWINGS FOR STRUCTURE REINFORCEMENT. SEE LARGE BASE ROOF CURB WITH CURB ADAPTER DETAIL.

10 . MAIN/SUB VRF BRANCH CONTROLLER. BRANCH CONTROLLER SHALL BE MOUNTED ABOVE CEILING. SUSPEND FROM DROP RODS (MIN 3/8") AND CONNECTED TO OVERHEAD STRUCTURE WITH 2"X2"X1/4" ANGLE IRON. PROVIDE DRAIN PAN BELOW MBC/SBC.SEE VRF DRAIN PAN DETAIL. SEE M201

FOR PIPING.

11 . BALANCE MANUAL VOLUME DAMPER TO 500 CFM OF OUTSIDE AIR.

12 . HORIZONTAL AIR HANDLER SUSPENDED FROM CEILING IN SAME LOCATION AS OLD AIR HANDLE.

GENERAL NOTE: PROVIDE LINTELS AT ALL NEW DUCT PENETRATIONS

THRU EXISTING WALLS. SEE LINTEL DETAIL AT EXISTING WALL.

No. Description Date

NOTES: (THIS DETAIL ONLY)

1. MATERIAL: 18 GA. GALVANIZED STEEL.

2. FULLY WELDED.

3. FULLY INSULATED: 1", 1.5# INSULATION.

4. 1" X 4" PRESSURE TREATED WOOD NAILER.

5. UNIT TIE DOWN/LIFTING LUG.

6. PROVIDE 2 PIECES, BASE CURB AND ADAPTER.

7. ALL ROOF CURBS SHALL BE PLACED IN LOCATIONS AS SHOWN ON SHEET M101. SEE

S-1 AND S-2 ON M504 FOR ALL SECTIONS AND DETAILS FOR PLACEMENT.

8. CURB SHALL BE BY ALADDIN METAL PRODUCTS OR MGM PRODUCTS.

9. SEE SHEET M101 FOR NOTES REGARDING SUPPLY DROP. ALL DIMENSIONS SHALL BE

FIELD VERIFIED.

TOP BASE WIDTH/LENGTH OF CURB SHALL

SPECIFICALLY MATCH THE EXACT DIMENSIONS

OF THE ROOFTOP UNIT BEING INSTALLED.

ALSO SUPPLY CONNECTION SHALL

MATCH UP EXACTLY TO SPECIFIC MODEL

OF ROOFTOP UNIT.

INSULATED DECK PAN

THIS DIMENSION IS APPROXIMATE AND SHOULD BE

FIELD VERIFIED. VERTICAL PORTION OF CURB SIDES

SHOULD BE CENTERLINE TO BAR JOISTS/TEE. SEE

STRUCT. DRAWINGS ON M504. OVERALL CURB

DIMENSION INCULDING 2" LIP IS 144" X 52.5" +/-.

CONTRACTOR SHALL VERIFY 24" WILL

ALLOW 12" MIN. ABOVE ROOF AS SHOWN.

BACK CURB

1" X 4"

NAILER

ADAPTER

2" BASE FLANGE OUT (FULL

PERIMETER)

LINE OF ROOF

12" MIN. ABOVE ROOF FINISH LEVEL

TOP VIEW

SIDE VIEWEND VIEW

12' 0"4' 4.5" +/-

THIS DIMENSION IS APPROXIMATE AND SHOULD BE

FIELD VERIFIED. VERTICAL PORTION OF CURB SIDES

SHOULD BE CENTERLINE TO BAR JOISTS/TEE. SEE

STRUCT. DRAWINGS ON M504. OVERALL CURB

DIMENSION INCULDING 2" LIP IS 144" X 52.5" +/-.

PROJECT NUMBER:

DATE:

DRAWN BY:

CHECKED BY:

TITLE:

SUBJECT TO GENERAL

COPYRIGHT LAWS ©

REVISIONS

GA DOE ID #: 5056

M504

MECHANICAL/STRUCTURAL

DETAILS

2021204

IN

T

E R

N A

T

IO

N A

L S

T U

D

IE

S E

L E

M E

N T

A R

Y S

C H

O O

L

H V

A C

P

L U

M B

IN

G

U P

G R

A D

E S

06/15/2022

HHP

JA3

C

U T

T S

D R

A

L B

A N

Y G

A

NOT TO SCALE

LARGE BASE CURB WITH CURB ADAPTER

IDF

MDF

FIRE

ALARM

PANELMASTER

INTERCOM

CONSOL

PRIMARY

ELECTRICAL

ROOM

1. APPROXIMATE LOCATION OF EXISTING FIRE ALARM PANEL (SECUTRON MODEL MR-2400)

2. APPROXIMATE LOCATION OF EXISTING INTERCOM SYSTEM HEAD END (BOGEN MULTICOM 2000)

3. APPROXIMATE LOCATION OF EXISTING DATA MAIN DISTRIBUTION FRAME (MDF)

4. GENERAL: HATCHED AREAS SHOW LOCATIONS WHERE CEILING TILE AND GRID ARE BEING

REMOVED FOR DEMOLITION AND REPLACEMENT OF HVAC EQUIPMENT. SEE GENERAL NOTES

THIS SHEET FOR ADDITIONAL WORK.

NOTES: (THIS SHEET ONLY)

PROJECT NUMBER:

DATE:

DRAWN BY:

CHECKED BY:

TITLE:

SUBJECT TO GENERAL

COPYRIGHT LAWS ©

REVISIONS

A

B

C

GA DOE ID #: 5056

E001

ELECTRICAL SITE PLAN

2021204

IN

T

E R

N A

T

IO

N A

L S

T U

D

IE

S E

L E

M E

N T

A R

Y S

C H

O O

L

H V

A C

P

L U

M B

IN

G

U P

G R

A D

E S

05/20/2022

KLS

KAB

C

U T

T S

D R

A

L B

A N

Y G

A

SCALE: 1/16" = 1'-0"

ELECTRICAL OVERALL PLAN

GENERAL NOTES: (MODULAR CLASSROOMS)

GENERAL NOTES: (CEILING REMOVAL WORK)1 PROVIDE A NEMA 3R 24"X24"X8" LOCKABLE LOW VOLTAGE SYSTEM CABINET FOR

MOBILE CLASSROOM SYSTEMS CABLING EXTENSION. INSTALL CABINET ON

STANCHION AT 24" ABOVE FINISHED GRADE. COORDINATE EXACT LOCATION WITH

THE OWNER.

2 PROVIDE TWO (2) 3" CONDUITS. PROVIDE THE FOLLOWING CABLES AS SPECIFIED

FROM THE DATA CABINET TO THE LOCATION INDICATED:

A. 48 PAIR INTERCOM CABLE AND 12 STRAND FIBER OPTIC CABLE IN

11/2" INNERDUCT TO INTERCOM CABINET (MIC) THROUGH TEL.

B. 12 STRAND FIBER OPTIC CABLE TO MDF RACK.

C. 24 PAIR TELEPHONE CABLE.

PROVIDE SURGE SUPPRESSION FOR ALL COPPER CABLES ENTERING THE

BUILDING. ROUTE CABLES CONCEALED ABOVE ACCESSIBLE CEILINGS INSIDE

THE BUILDING. LEAVE MIN. 10' OF SLACK CABLES COILED AT EACH END. MAKE ALL

CONNECTIONS.

3 CONTRACTOR SHALL PROVIDE AND INSTALL DATA NETWORK AND INTERCOM

SYSTEM EXTENSION INCLUDING ALL CONNECTIVITY AND ELECTRONIC

EQUIPMENT TO THE CONTRACTOR PROVIDED MODULAR CLASSROOMS. ROUTE

SPECIFIED SYSTEM CABLES FROM THE LOCKABLE LOW VOLTAGE SYSTEM

CABINET TO EACH MODULAR CLASSROOM. PROVIDE FIBER OPTIC CABLE FROM

THE MODULAR CLASSROOM IDF CORE SWITCH LOCATION TO EACH MODULAR

CLASSROOM FOR DATA NETWORK BACKBONE AND CONNECTIVITY AS SPECIFIED.

PROVIDE INTERCOM SYSTEM EXTENSION CABLES, COMPONENTS, SPEAKER, AND

CONNECTIVITY TO THE MAIN BUILDING INTERCOM SYSTEM VIA THE SPECIFIED

MULTI-ZONE INTERCOM EXTENSION PANEL. THE INTERCOM SYSTEM EXTENSION

SHALL ALLOW EMERGENCY TONE ANNUNCIATION FROM THE MAIN BUILDING

INTERCOM SYSTEM. MAKE ALL CONNECTIONS.

4 GENERAL: MODULAR CLASSROOMS ARE BEING PROVIDED BY THE CONTRACTOR

PRIOR TO THE START OF CONSTRUCTION. THE CONTRACTOR WILL REMOVE THESE

CLASSROOMS NEAR COMPLETION OF CONSTRUCTION. THE QUANTITY OF

MODULAR CLASSROOM UNITS IS SHOWN ON THIS SHEET. CONTRACTOR SHALL

PROVIDE ALL POWER SERVICE CONNECTIONS TO EACH UNIT. CONTRACTOR

SHALL PROVIDE TEMPORARY POWER SERVICE BY COORDINATING WITH THE

POWER UTILITY COMPANY. OWNER SHALL PAY ALL METER FEES AND SHALL PAY

FOR UTILITY USAGE FOR ALL MODULAR UNITS FOR THE DURATION OF THE

PROJECT. PROVIDE 120/240V, 1PH, 150A SERVICE INCLUDING SECONDARY

CONDUCTORS FROM THE UTILITY COMPANY TRANSFORMERS, WEATHERHEADS,

METER SOCKETS, CONNECTION TO MODULAR CLASSROOM SERVICE PANEL,

GROUNDING, RACEWAYS, AND ETC FOR EACH MODULAR CLASSROOM.

5 GENERAL: CONTRACTOR SHALL PROVIDE AN EXIT UNIT COMBO BY LITHONIA,

LHQMLED R, OR EQUAL IN EACH MODULAR CLASSROOM. MOUNT THIS EXIT UNIT

COMBO ABOVE ONE OF THE EXIT DOORS INSIDE THE MODULAR CLASSROOMS AS

SHOWN ON THE ARCHITECTURAL DRAWINGS. CONNECT THIS UNIT TO THE UN-

SWITCHED LIGHTING CIRCUIT IN THE SPACE WITH 2#12, #12G CONDUCTORS IN 1/2"

CONDUIT. MAKE ALL CONNECTIONS. THE QUANTITY OF MODULAR CLASSROOM

UNITS IS SHOWN ON THIS SHEET.

A. SECURE ALL EXISTING INTERIOR AND EXTERIOR LIGHT FIXTURES AND EXIT SIGNS

IN THE BUILDING, INCLUDING CIRCUIT CONDUCTORS, CONDUITS, AND SWITCHES

ETC. UNLESS NOTED OTHERWISE.

B. DISCONNECT POWER FROM ALL MECHANICAL EQUIPMENT

SHOWN ON THE DEMOLITION DRAWINGS UNLESS OTHERWISE NOTED, INCLUDING

ROOF TOP UNITS, EXHAUST FANS, WALL HEATERS, AIR HANDLERS, WATER

SOURCE HEAT PUMPS, COOLING TOWERS, BOILERS, UNIT VENTILATORS AND ETC.

ALL ELECTRICAL PANELS SHOWN ARE EXISTING TO REMAIN UNLESS OTHERWISE

NOTED.

C. ALL EXISTING COMPUTER DATA OUTLETS, CABLES, AND

RACEWAYS SHALL REMAIN. ALL EXISTING COMPUTER DATA

OUTLETS, CABLES, AND RACEWAYS THAT ARE ASSOCIATED WITH THE EXISTING

MDF'S AND IDF'S TO REMAIN SHALL REMAIN UNLESS NOTED OTHERWISE.

CONTRACTOR SHALL BE RESPONSIBLE FOR THE PROTECTION OF EXISTING DATA

OUTLETS AND ALL ASSOCIATED DATA NETWORKING ELECTRONIC

EQUIPMENT DURING DEMOLITION AND RENOVATIONS OF ALL AREAS.

D. ALL EXISTING FIRE ALARM SYSTEM DEVICES INCLUDING SMOKE DETECTORS,

HORNS, STROBES, PULL STATIONS, PANELS AND ETC. SHALL REMAIN IN THEIR

ENTIRETY UNLESS NOTED OTHERWISE.

E. ALL EXISTING INTERCOM SYSTEM COMPONENTS INCLUDING WALL AND CEILING

SPEAKERS, HANDSETS, PUSH BUTTONS, CLOCKS, CABLES, AND RACEWAYS SHALL

REMAIN IN THEIR ENTIRETY.

F. ALL EXISTING CEILING MOUNTED EQUIPMENT AD DEVICES FOR VIDEO

SURVEILLANCE, INTRUSION DETECTION / SECURITY, AND WIRELESS DATA

NETWORK SYSTEMS SHALL BE SECURED AND REINSTALLED IN NEW CEILINGS PER

ARCHITECTURAL DRAWINGS UNLESS NOTED OTHERWISE. CONTRACTOR SHALL

BE RESPONSIBLE FOR ANY DAMAGE TO THIS EQUIPMENT DURING

CONSTRUCTION. ANY EXISTING DAMAGED EQUIPMENT SHALL BE REPORTED TO

THE ENGINEER AND OWNER PRIOR TO COMMENCEMENT OF WORK. CONTRACTOr

SHALL COORDINATE AIMING OF EACH SECURITY CAMERA TOUCHED AS PART OF

THIS PROJECT WITH OWNER. DURING REINSTALLATION OWNER’S REP SHALL

VERIFY FIELD OF VIEW IS ACCEPTABLE. CONTRACTOR SHALL NOTIFY OWNER 7

DAYS IN ADVANCE OF INSTALLATION SO OWNER’S REPRESENTATIVES MAY BE

SCHEDULED TO BE AVAILABLE ON SITE.

G. ALL EXISTING AUDIO- VISUAL COMPONENTS AND CABLING IN CONFERENCE

ROOMS INCLUDING THE PROJECTORS, SPEAKERS, AUDIO ENHANCEMENT

SYSTEM, TV TUNERS, AND CONNECTIVITY SHALL REMAIN AND BE REINSTALLED.

PROTECT, SECURE, AND CLEAN THESE COMPONENTS DURING CONSTRUCTION.

REINSTALL THIS EQUIPMENT IN NEW CEILINGS AND NEW CEILING ENCLOSURES.

CONTRACTOR SHALL BE RESPONSIBLE FOR ANY DAMAGE TO THIS EQUIPMENT

DURING CONSTRUCTION. ANY EXISTING DAMAGED EQUIPMENT SHALL BE

REPORTED TO THE ARCHITECT AND OWNER PRIOR TO COMMENCEMENT OF

WORK.

H. ALL EXISTING ELECTRICAL CIRCUITS FOR TELEPHONE, INTERCOM, TV,

SECURITY, AND VIDEO SURVEILLANCE SHALL BE MAINTAINED IN THE OCCUPIED

AREAS DURING CONSTRUCTION UNLESS NOTED OTHERWISE.CONTRACTOR IS

CAUTIONED THAT NOT ALL OF THE EXISTING LOW VOLTAGE SYSTEM CABLING IS

IN CONDUIT.

I. ALL EXISTING VIDEO SURVEILLANCE SYSTEM CAMERAS AND RECORDER HEAD-

END EQUIPMENT INCLUDING NVR, MONITORS AND CABLES SHALL REMAIN.

SECURE, PROTECT, AND RE- MOUNT EXISTING IP VIDEO SURVEILLANCE

CAMERAS IN NEW CEILING TILES.

J. ALL EXISTING WIRELESS DATA NETWORK ACCESS POINTS SHALL REMAIN. THIS

CONTRACTOR SHALL SECURE, PROTECT, AND REINSTALL ALL EXISTING ACCESS

POINTS AND ASSOCIATED CIRCUITRY ENTIRELY.

K. CEILING MOUNTED LIGHT FIXTURES IN THE AREAS OF MECHANICAL EQUIPMENT

DEMOLITION AND INSTALLATION SHALL BE EMPORARILY SECURED TO

STRUCTURE, PROTECTED, AND REINSTALLED IN NEW OR EXISTING CEILINGS

PER MECHANICAL DRAWINGS UNLESS NOTED OTHERWISE. CONTRACTOR

SHALL BE RESPONSIBLE FOR ANY DAMAGE TO LIGHT FIXTURES DURING

CONSTRUCTION.

No. Description Date

1 ADDENDUM #3 6/15/22

1. CONTRACTOR SHALL REPLACE 83 EXISTING CEILING MOUNTED INTERCOM

SPEAKERS WITH NEW AS PART OF THIS PROJECT. IT IS THE INTENT OF

THE OWNER TO REPLACE ALL CEILING MOUNTED INTERCOM

SPEAKERS BUILDING WIDE WITH NEW. NEW SPEAKER PROVIDED BY THIS

CONTRACTOR SHALL BE BOGEN #ACD2X2U OR APPROVED EQUAL.

CONTRACTOR SHALL BE RESPONSIBLE FOR DISPOSAL OF DEMOLISHED

SPEAKERS AND MOUNTING HARDWARE.

GENERAL NOTES: (INTERCOM SYSTEM)

J

ATS

J

M

R

C

FACTORY INSTALLED PIGTAIL

INSUL. BUSHING (TYP)

TO 120 VAC

PROVIDE IN-WALL JUNCTION BOX

WITH STAINLESS STEEL COVER

PLATE AND HOLE FOR CABLE

BUT SPLICE

BUTT SPLICE BY DIV. 16 MADE

INSIDE IN-WALL BOX

DUPLEX OUTLET

HARD CEILING 1' X 1' REMOVABLE ACCESS

PANEL (TYPICAL)

OBTAIN STD. &

HANDICAP SINK

MTG. HEIGHT FROM

DIV. 15 " ROUGH-IN"

DRAWING

1/2"MIN, 2"MAX

BENEATH LOWER

EDGE OF SINK

1/2"C IN WALL BY DIV. 16

FOR LOW VOLTAGE

(ONE PER LAV.)

120/24 VAC XFMR

BY DIV. 15

FIELD INSTALLED

MIN.18-2 PLENUM

RATED CABLE UP

TO XFMR IIN CELL

CAVITY BY DIV.16

MAXIMUM OF 1 LAVORATORIES, TOILET

OR URINAL PER XFMR/J BOX

(PER OWNER'S REQUEST)

SCALE: NONE

TYPICAL ELECTRIC FAUCET, TOILET OR URINAL SENSOR DETAIL

ELECTRICAL LEGEND

CONVENIENCE OUTLETS

SPECIAL PURPOSE OUTLET- WALL, CEILING

DUPLEX OUTLET- WALL, CEILING

ELECTRICAL PANELS- SEE SCHEDULE AND RISERS

SIMPLEX

JUNCTION BOX- WALL, CEILING

ONE SECTION PANEL

TWO SECTION PANEL

THREE SECTION PANEL

TRANSFORMER

AUTO TRANSFER SWITCH

GENERAL EQUIPMENT

CIRCUITS

RACEWAY IN CEILING OR WALL

ONE CROSSMARK PER WIRE, 2 WIRES UNLESS SHOWN

HOMERUN - ONE ARROW PER CIRCUIT

RACEWAY UNDER FLOOR OR SLAB

EXPOSED RACEWAY

FLEXIBLE RACEWAY

CONDUIT - UP, DOWN

CABLE TRAY

MOTOR CONTROLLER

STARTER / DISCONNECT

ENCLOSED CIRCUIT BREAKER

DISCONNECT (SEE DRAWING FOR F= FUSED, NR= NON-FUSED)

PUSH BUTTON

SINGLE POLE, MOTOR RATED

CONTACTOR

RELAY

NOTE

IG = ISOLATED GROUND

GFCI = GROUND FAULT CIRCUIT INTERRUPTER

PROJECT NUMBER:

DATE:

DRAWN BY:

CHECKED BY:

TITLE:

SUBJECT TO GENERAL

COPYRIGHT LAWS ©

REVISIONS

A

B

C

GA DOE ID #: 5056

E801

ELECTRICAL SCHEDULES &

LEGEND

2021204

IN

T

E R

N A

T

IO

N A

L S

T U

D

IE

S E

L E

M E

N T

A R

Y S

C H

O O

L

H V

A C

P

L U

M B

IN

G

U P

G R

A D

E S

05/20/2022

KLS

KAB

C

U T

T S

D R

A

L B

A N

Y G

A

1 ADDENDUM #3 6/15/22

ANDREWS, HAMMOCK & POWELL, INC. 250 CHARTER LANE, SUITE 100, MACON, GA 31210
ADDENDUM NUMBER: THREE DATED: June 15, 2022
CHANGES TO SPECIFICATIONS
CHANGES TO DRAWINGS
095113 - Acoustical Panel Ceilings_06152022.pdf
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section includes acoustical panels and exposed suspension systems for ceilings.
1.3 ACTION SUBMITTALS
A. Product Data: For each type of product.
1.4 CLOSEOUT SUBMITTALS
A. Maintenance Data: For finishes to include in maintenance manuals.
1.5 MAINTENANCE MATERIAL SUBMITTALS
A. Furnish extra materials that match products installed and that are packaged with protective covering for storage and identified with labels describing contents.
1. Acoustical Ceiling Panels: Furnish 100 full-size panels of APC #1 and 25 full-size panels of APC #2.
2. Suspension-System Components: Furnish 100 lineal feet of each exposed component for suspension system for APC #1.
1.6 DELIVERY, STORAGE, AND HANDLING
A. Deliver acoustical panels, suspension-system components, and accessories to Project site in original, unopened packages and store them in a fully enclosed, conditioned space where they will be protected against damage from moisture, humidity, tempe...
B. Before installing acoustical panels, permit them to reach room temperature and a stabilized moisture content.
C. Handle acoustical panels carefully to avoid chipping edges or damaging units in any way.
1.7 FIELD CONDITIONS
A. Environmental Limitations: Do not install acoustical panel ceilings until spaces are enclosed and weatherproof, wet work in spaces is complete and dry, work above ceilings is complete, and ambient temperature and humidity conditions are maintained ...
B. Above-Ceiling Observation: Before Contractor installs acoustical panel ceilings, Architect will conduct an above-ceiling observation and report deficiencies in the Work observed. Do not proceed with installation of ceilings until deficiencies hav...
1. Notify Architect seven days in advance of date and time when Project, or part of Project, will be ready for above-ceiling observation.
2. Before notifying Architect, complete the following in areas to receive ceilings:
a. Installation of lighting fixtures, powered for operation.
b. Installation, insulation, and leak and pressure testing of water piping systems.
c. Installation of air-duct systems.
d. Installation of air devices.
e. Installation of mechanical system control-air tubing.
f. Installation of ceiling support framing.

C. Coordinate with fire marshal prior to installing ceilings. Most jurisdictions require above-ceiling inspections prior to installing ceilings.

PART 2 - PRODUCTS
2.1 PERFORMANCE REQUIREMENTS
A. Surface-Burning Characteristics: Comply with ASTM E 84; testing by a qualified testing agency. Identify products with appropriate markings of applicable testing agency.
1. Flame-Spread Index: Comply with ASTM E 1264 for Class A materials.
2. Smoke-Developed Index: 450 or less.
2.2 ACOUSTICAL PANELS, GENERAL
A. Source Limitations: Obtain acoustical ceiling panels and supporting suspension system from single source from single manufacturer.
B. Acoustical Panel Standard: Provide manufacturer's standard panels of configuration indicated that comply with ASTM E 1264 classifications as designated by types, patterns, acoustical ratings, and light reflectances unless otherwise indicated.
C. Acoustical Panel Colors and Patterns: Match appearance characteristics indicated for each product type.
2.3 ACOUSTICAL PANELS <APC #1> (NON WET AREAS)
A. Acoustical tile ceiling in non-wet areas shall be provided by one of the following:
1. Armstrong World Industries, Inc.
2. CertainTeed Corp.
3. USG Interiors, Inc.
B. Classification: Provide panels complying with ASTM E 1264 for type, form, and pattern as follows:
1. Type and Form: Type XII, mineral fiber with transparent membrane, non-directional fissured design; Form 2, water felted.
2. Pattern: E.
C. Color: White.
D. LR: Not less than 0.90.
E. NRC: Not less than 0.95.
F. Humidity/Sag Resistance: Humiguard Plus.
G. Edge/Joint Detail: Square edge.
H. Thickness: 5/8 inch.
I. Modular Size: 24 by 24 inches.
2.4 ACOUSTICAL PANELS <APC #2> (WET AREAS)
A. Manufacturers/Products: Subject to compliance with requirements, provide one of the following:
1. Armstrong World Industries, Inc.; Clean Room VL
2. CertainTeed Corp.; Performa, Vinyrock
3. USG Interiors, Inc.; Subsidiary of USG Corporation.; Gypsum Lay-in Clima Plus
B. Classification: Provide panels complying with ASTM E 1264 for type, form, and pattern as follows:
1. Type and Form: Type IV or Type XX other types; described as high-density, ceramic- and mineral base panels with scrubbable finish, resistant to heat, moisture, and corrosive fumes. Provide gypsum core and stippled pattern tile.
2. Pattern: As indicated by manufacturer’s designation.
C. Color: White.
D. LR: Not less than 0.78.
E. CAC: Not less than 38.
F. Edge/Joint Detail: Square.
G. Thickness: 1/2 inch.
H. Modular Size: 24 by 24 inches.
2.5 METAL SUSPENSION SYSTEMS, GENERAL
A. Metal Suspension-System Standard: Provide manufacturer's standard direct-hung metal suspension systems of types, structural classifications, and finishes indicated that comply with applicable requirements in ASTM C 635/C 635M.
1. High-Humidity Finish: Comply with ASTM C 635/C 635M requirements for "Coating Classification for Severe Environment Performance" where high-humidity finishes are indicated.
B. Wire Hangers, Braces, and Ties: Provide wires complying with the following requirements:
1. Zinc-Coated, Carbon-Steel Wire: ASTM A 641/A 641M, Class 1 zinc coating, soft temper.
2. Size: Select wire diameter so its stress at three times hanger design load (ASTM C 635/C 635M, Table 1, "Direct Hung") will be less than yield stress of wire, but provide not less than 0.106-inch-diameter wire.
2.6 METAL SUSPENSION SYSTEM <For APC #1 Ceilings>
A. Basis-of-Design Product: Subject to compliance with requirements, provide Armstrong World Industries; Suprafine ML or a comparable product by another manufacturer:
1. Armstrong World Industries, Inc.
2. CertainTeed Corp.
3. USG Interiors, Inc.; Subsidiary of USG Corporation

This is the start of the file's text. The full file is on GovTribe.

Other files

File Type Posted
Addendum 2 —