Addendum 2 to IFB FR-2026-02.pdf
PDF 384 KB Posted
- Attached to
- Arc Flash Coordination Study
- Solicitation number
- 2138244
- Issued by
- Genesee County, New York
About this file
This Addendum 2 to IFB FR-2026-02 is a comprehensive equipment list for an Arc Flash/Coordination Study at Franklin Correctional Facility in New York. The addendum details the electrical equipment across the facility's 47 buildings and structures requiring arc flash analysis and coordination study, including medium voltage switches, medium voltage transformers, branch circuit panels, molded case circuit breakers, disconnects, combination motor starters, variable speed drives, switchgear, bus ducts, transformers, generators, transfer switches, and uninterruptible power sources. The equipment inventory spans diverse facility areas including dormitories, administrative buildings, industrial shops, guard shacks, utility buildings, and specialized facilities such as the infirmary, school, commissary, and sewage treatment plants. The study must comply with the 2024 NFPA 70E standard and IEEE 1584 technical requirements. The addendum is a binding document that must be signed and returned with the bid submission as a condition of bid acceptance.
The arc flash coordination study is being conducted for Franklin Correctional Facility under an invitation for bid process with a response deadline of September 30, 2026. An SDVOB contracting goal of 6.00% applies to this procurement, while MBE, WBE, and DBE contracting goals are each 0.00%. No business has been awarded an identical or substantially similar contract within the past five years. Bidders must demonstrate qualification to perform specialized engineering and electrical safety assessment work in conformance with the referenced standards, with detailed technical and procedural requirements established in Appendix B of the primary IFB document. The pricing terms, contract duration, and renewal options are specified in the primary IFB FR-2026-02 document.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Addendum # 2 to IFB # FR-2026-02 Arc Flash / Coordination Study
ANNEX Yard - Building 81
Electric Room
2 Branch Circuit Panel
15 Molded Case Circuit Breaker
1 Transformer
Industry - Building 31
Electric Room
5 Branch Circuit Panel
26 Molded Case Circuit Breaker
2 Disconnect
4 Combination Motor Starter
Outside
1 Medium Voltage Switch
1 Medium Voltage Transformer
Floor Equipment
1 Branch Circuit Panel
9 Molded Case Circuit Breaker
9 Disconnect
I Dorm - Building 34
Electric Room
1 Medium Voltage Switch (Outside)
1 Medium Voltage Transformer (Outside)
5 Branch Circuit Panel
21 Molded Case Circuit Breaker
2 Disconnect
4 Combination Motor Starter
L Dorm - Building 37
Electric Room
1 Medium Voltage Switch (Outside)
1 Medium Voltage Transformer (Outside)
5 Branch Circuit Panel
21 Molded Case Circuit Breaker
2 Disconnect
4 Combination Motor Starter
M Dorm - Building 38
Electric Room
1 Medium Voltage Switch (Outside)
1 Medium Voltage Transformer (Outside)
5 Branch Circuit Panel
Franklin Correctional Facility
Arc Flash Equipment List
21 Molded Case Circuit Breaker
2 Disconnect
4 Combination Motor Starter
K Dorm - Building 36
Electric Room
1 Medium Voltage Switch (Outside)
1 Medium Voltage Transformer (Outside)
5 Branch Circuit Panel
21 Molded Case Circuit Breaker
2 Disconnect
4 Combination Motor Starter
H Dorm - Building 33
Electric Room
1 Medium Voltage Switch (Outside)
1 Medium Voltage Transformer (Outside)
5 Branch Circuit Panel
21 Molded Case Circuit Breaker
2 Disconnect
4 Combination Motor Starter
N Dorm - Buiding 32
Electric Room
1 Medium Voltage Switch (Outside)
1 Medium Voltage Transformer (Outside)
5 Branch Circuit Panel
21 Molded Case Circuit Breaker
2 Disconnect
4 Combination Motor Starter
J Dorm - Building 35
Electric Room
5 Branch Circuit Panel
21 Molded Case Circuit Breaker
2 Disconnect
4 Combination Motor Starter
ANNEX School - Building 30
Electric Room
1 Medium Voltage Switch
1 Medium Voltage Transformer
5 Branch Circuit Panel
20 Molded Case Circuit Breaker
2 Disconnect
4 Combination Motor Starter
1 Breaker (Outside)
Building 73
Electric Room
1 Branch Circuit Panel
5 Molded Case Circuit Breaker
Building 49 - Guard Shack
Shack
1 Branch Circuit Panel
1 Molded Case Circuit Breaker
Building 39 - Guard Shack
Shack
1 Branch Circuit Panel
Activity Gym - Building 8
Electric Room
1 Medium Voltage Switch (Outside)
1 Medium Voltage Transformer (Outside)
6 Branch Circuit Panel
27 Molded Case Circuit Breaker
1 Transformer
Building 48 - Guard Shack
Electric Room
1 Branch Circuit Panel
3 Molded Case Circuit Breaker
Gym - Building 39
Mezzanine
2 Disconnect
Gym Floor Equipment
4 Disconnect
Bubble - Building 25
Cage Area
1 Branch Circuit Panel
3 Molded Case Circuit Breaker
1 Disconnect (2nd Floor)
F Dorm - Building 19
Electric Room
1 Medium Voltage Switch (Outside)
1 Medium Voltage Transformer (Outside)
4 Branch Circuit Panel
13 Molded Case Circuit Breaker
E Dorm - Building 7
Electric Room
1 Medium Voltage Switch (Outside)
1 Medium Voltage Transformer (Outside)
4 Branch Circuit Panel
13 Molded Case Circuit Breaker
2 Disconnect
4 Combination Motor Starter
D Dorm - Building 5
Electric Room
1 Medium Voltage Switch (Outside)
1 Medium Voltage Transformer (Outside)
4 Branch Circuit Panel
13 Molded Case Circuit Breaker
2 Disconnect
4 Combination Motor Starter
C Dorm - Building 4
Outside
1 Medium Voltage Switch (Outside)
1 Medium Voltage Transformer (Outside)
Electric Room
4 Branch Circuit Panel
15 Molded Case Circuit Breaker
2 Disconnect
4 Combination Motor Starter
A Dorm - Building 9
Electric Room
1 Medium Voltage Switch (Outside)
1 Medium Voltage Transformer (Outside)
4 Branch Circuit Panel
14 Molded Case Circuit Breaker
2 Disconnect
4 Combination Motor Starter
G Dorm - Building 18
Electric Room
1 Medium Voltage Switch (Outside)
1 Medium Voltage Transformer (Outside)
4 Branch Circuit Panel
14 Molded Case Circuit Breaker
East Gate - Building 44
Closet
1 Branch Circuit Panel
Storehouse/Mess Hall - Building 12
Floor Equipment
2 Branch Circuit Panel
8 Molded Case Circuit Breakers
2 Disconnect
Electric Room
1 Medium Voltage Switch (Outside)
1 Medium Voltage Transformer (Outside)
2 Switchgear
2 Branch Circuit Panel
14 Molded Case Circuit Breaker
2 Disconnect
4 Combination Motor Starter
Kitchen
4 Branch Circuit Panel
28 Molded Case Circuit Breaker
5 Disconnect
Mechanical Room 1
1 Branch Circuit Panel
4 Molded Case Circuit Breaker
1 Variable Speed Drive
Mechanical Room 2
1 Branch Circuit Panel
4 Molded Case Circuit Breaker
1 Variable Speed Drive
Recycling Building
Floor Equipment
2 Branch Circuit Panel
7 Molded Case Circuit Breakers
3 Disconnect
Infirmary Building 11
Electric Closet
4 Branch Circuit Panel
4 Molded Case Circuit Breakers
Main Electric Room
5 Branch Circuit Panel
14 Molded Case Circuit Breakers
1 Combination Motor Starter
Outside
1 Medium Voltage Switch
1 Medium Voltage Transformer
3 Disconnect
Penthouse
1 Branch Circuit Panel
4 Molded Case Circuit Breakers
2 Combination Motor Starter
2 Variable Speed Drive
Basement
2 Switchgear
5 Branch Circuit Panel
22 Molded Case Circuit Breakers
3 Disconnect
3 Combination Motor Starter
6 Variable Speed Drive
1 Transformer
1 Uninterrupable Power Source
INFWORK Control - Building 10
Shop Area
2 Branch Circuit Panel
5 Molded Case Circuit Breaker
4 Disconnect
2 Combination Motor Starter (In Mech Rm)
200' Bus Duct
22 Bus Duct Switch
Electric Room
1 Medium Voltage Switch (Outside)
1 Medium Voltagte Transformer (Outside)
3 Branch Circuit Panel
12 Molded Case Circuit Breaker
Draft/Grounds - Building 28
Garage
1 Branch Circuit Panel
4 Molded Case Circuit Breaker
Outside
1 Medium Voltage Switch (Outside)
1 Medium Voltagte Transformer (Outside)
1 Branch Circuit Panel
4 Molded Case Circuit Breaker
SHU - Building 16
Electric Closet
1 Medium Voltage Switch (Outside)
1 Medium Voltagte Transformer (Outside)
2 Branch Circuit Panel
7 Molded Case Circuit Breaker
Commissary - Building 13
Laundry
1 Medium Voltage Switch (Outside)
1 Medium Voltagte Transformer (Outside)
1 Branch Circuit Panel
14 Molded Case Circuit Breaker
7 Disconnect
Mechanical Room
1 Disconnect
2 Combination Motor Starter
Electric Closet
1 Branch Circuit Panel
4 Molded Case Circuit Breaker
Storage
1 Branch Circuit Panel
Horticulture - Building 9
Electric Closet
1 Branch Circuit Panel
6 Molded Case Circuit Breaker
School - Building 14
Electric Closet
1 Medium Voltage Switch (Outside)
1 Medium Voltagte Transformer (Outside)
3 Switchgear
4 Branch Circuit Panel
20 Molded Case Circuit Breaker
Computer Class
1 Branch Circuit Panel
4 Molded Case Circuit Breaker
Hallway
2 Branch Circuit Panel
2 Molded Case Circuit Breaker
Flooring Class Room
1 Branch Circuit Panel
2 Molded Case Circuit Breaker
Building Maintenance Class 1
2 Branch Circuit Panel
5 Molded Case Circuit Breaker
2 Disconnect
60' Bus Duct
6 Bus Duct Switch
Building Maintenance Class 2
1 Branch Circuit Panel
4 Molded Case Circuit Breaker
50' Bus Duct
8 Bus Duct Switch
Auto Shop
2 Branch Circuit Panel
2 Molded Case Circuit Breaker
5 Disconnect
1 Transformer
Driving Classroom
1 Branch Circuit Panel
3 Molded Case Circuit Breaker
Custodial Maintenance Class
1 Branch Circuit Panel
3 Molded Case Circuit Breaker
50' Bus Duct
1 Bus Duct Switch
Painting Class
1 Branch Circuit Panel
3 Molded Case Circuit Breaker
1 Disconnect
50' Bus Duct
4 Bus Duct Switch
Electrical Class
2 Branch Circuit Panel
2 Molded Case Circuit Breaker
3 Disconnect
50' Bus Duct
6 Bus Duct Switch
Welding Class
1 Branch Circuit Panel
5 Molded Case Circuit Breaker
8 Disconnect
80' Bus Duct
9 Bus Duct Switch
Visitor - Building 2
Electric Closet
2 Branch Circuit Panel
4 Molded Case Circuit Breaker
1 Disconnect
SallyPort - Guard Shack - Building 15
Electric Closet
2 Branch Circuit Panel
6 Molded Case Circuit Breaker
Rear Tower - Building 47
Electric Closet
2 Molded Case Circuit Breaker
Admin - Building 1
Electric Room
4 Branch Circuit Panel
22 Molded Case Circuit Breaker
1 Disconnect
1 Transformer
Outside
1 Medium Voltage Switch
1 Medium Voltage Transformer
1 Branch Circuit Panel
2 Molded Case Circuit Breaker
2 Combination Motor Starter
Mechanical Room
3 Branch Circuit Panel
8 Molded Case Circuit Breaker
Hospitality - Building 26
Mechnical Room
1 Branch Circuit Panel
3 Molded Case Circuit Breaker
Reginal Training - Building 24
Mechanical Room
1 Branch Circuit Panel
4 Molded Case Circuit Breaker
OGS - Building 118
Trailer
2 Branch Circuit Panel
4 Molded Case Circuit Breaker
Red Garage
Across from OGS Floor
1 Branch Circuit Panel
4 Molded Case Circuit Breaker
Vehicle Storage - Building 107
Floor
1 Branch Circuit Panel
1 Molded Case Circuit Breaker
Recycling Storage - Building 106
Floor
2 Branch Circuit Panel
9 Molded Case Circuit Breaker
5 Disconnect
Truck - Building 17
Floor
2 Branch Circuit Panel
4 Molded Case Circuit Breaker
5 Disconnect
GEN - Building 20
Floor
1 Medium Voltage Switch (Outside)
2 Medium Voltage Transformer (Outside)
9 Switchgear
1 Branch Circuit Panel
12 Molded Case Circuit Breaker
5 Disconnect
GEN - Building 43
Floor
3 Switchgear
3 Branch Circuit Panel
17 Molded Case Circuit Breaker
1 Disconnect
2 Combination Motor Starter
1 Transformer
1 Generator
Powerhouse - Building 42
Electric Room
2 Medium Voltage Switch (Outside)
2 Medium Voltage Transformer (Outside)
5 Branch Circuit Panel
28 Molded Case Circuit Breaker
2 Disconnect
2 Variable Speed Drive
1 Transformer
Garage - Building 21
Electric Room
2 Branch Circuit Panel
8 Molded Case Circuit Breaker
2 Disconnect
Equipment Storage 1 - Building 51
Floor
1 Molded Case Circuit Breaker
Sewage Plant - Building 22
Outside Building
1 Medium Voltage Switch
1 Medium Voltage Transformer
1 Branch Circuit Panel
2 Molded Case Circuit Breaker
5 Disconnect
Sewage Plant - Building 119
Outside Building
2 Branch Circuit Panel
5 Molded Case Circuit Breaker
1 Disconnect
2 Combination Motor Starter
3 Variable Speed Drive
1 Transfer Switch
1 Transformer
Compost - Building 117
On Building
1 Branch Circuit Panel
1 Molded Case Circuit Breaker
Salt Storage - Building 108
On Building
1 Branch Circuit Panel
1 Molded Case Circuit Breaker
Water Tower 114
Outside
1 Branch Circuit Panel
3 Disconnect
QWL - Building 78
Basement
1 Branch Circuit Panel
4 Molded Case Circuit Breaker