Addendum #2 Revised Electrical drawings- Part 2.pdf
PDF 23 MB Posted
- Attached to
- RFP NORTH CAMPUS BID PKG #2
- Solicitation number
- RFP JCI 260000001841 8
- Issued by
- Michigan
About this file
This is Addendum #2 to the electrical drawings for the JCIS Dorrant Center Additions & Renovations project in Michigan, providing revised electrical schematics and detailed specifications for the North Campus Bid Package #2. The addendum comprises comprehensive electrical floor plans for Areas D through M, establishing new power distribution systems, panel layouts, lighting controls, and site electrical details. The drawings specify equipment installations including rooftop units (RTUs), packaged terminal air conditioners (PTACs), exhaust fans, door operators, and various electrical units across multiple building zones, with detailed electrical key notes providing contractor instructions for equipment relocation, conduit and wire installation, power provision for owner-supplied signage, and control system modifications. The scope includes the installation of new electrical panels (MDP, DP2, H, and R), modifications to existing panels, breaker replacements, load rebalancing across panel schedules, and the provision of arc-flash studies as required by the National Electrical Code (NEC).
The electrical work encompasses load calculations across all affected panels with net load adjustments ranging from negative 2,926 watts to positive 719 watts depending on the specific panel. The drawings detail lighting control systems compliant with Michigan Energy Code based on ASHRAE 90.1-2013 standards, including occupancy sensors, photocell controls, and dimming capabilities utilizing Acuity Nlight controls with approved alternates from Hubbell, Lutron, Legrand, and Leviton. Exterior lighting specifications include McGraw Edison LED fixtures with varying configurations and light output ranging from 7,399 to 85,116 lumens, all equipped with integral photocells and 0-10V dimming. Site electrical details address light pole installations, electrical handholes, underfloor conduit in slab-on-grade construction, and grounding requirements including ground rods and copper clad connections. The contractor is required to provide a complete arc-flash study with available fault current ratings listed on all building panels, to be delivered within the project closeout package.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CONV
CONV
RTU-6
208V-1Ø, 17.0A
J
DOOR OPERATOR
(TYP.)
J-15
J-17
CU-5B
208V-1Ø, 15.1MCA
UV-5
120V-1Ø, 6.3MCA
WP
A-8
A-32,34
J
J-15
WP
EXIST. PNL
"M"
EXIST. PNL
"L"
EXIST. PNL
"X"
EXIST. PNL
"K"
EXIST. PNL
"J"
NEW PNL
"MDP"
WP
GFI
A-36
WP
EWC
J-16
ELECTRICAL KEY NOTES
RELOCATED EQUIPMENT. CONTRACTOR SHALL EXTEND ASSOCIATED
BRANCH CIRCUIT CONDUIT AND WIRE TO NEW LOCATION.
CONTRACTOR SHALL PROVIDE AND INSTALL POWER FOR OWNER PROVIDED
SIGNAGE. VERIFY LOCATION WITH OWNER, PRIOR TO ROUGH-IN.
CONTRACTOR SHALL REUSE EXISTING CONDUIT AND WIRE FOR NEW
EQUIPMENT.
CONTRACTOR SHALL REUSE EXISTING CONDUIT AND WIRE FOR NEW
EQUIPMENT. CONTRACTOR SHALL REMOVE PHASE WIRE FROM PANEL
CONNECTION, FOR USE ON 2-POLE UNIT.
CONTRACTOR SHALL PROVIDE AND INSTALL NEW CONDUIT AND WIRE FOR
NEW EQUIPMENT.
EXHAUST FAN SHALL BE CONTROLLED BY NEW TIMECLOCK. CONFIRM TIME
SCHEDULING WITH OWNER.
REMOVE EXISTING PNEUMATIC INTERLOCK WITHIN STARTER, AND CONNECT
TO NEW CONTROL PANEL FOR CONTROLS.
CONTRACTOR SHALL PROVIDE CIRCUIT TO TRANSFORMER, FOR CONTROL
VALVE POWER.
1. CONTRACTOR SHALL PROVIDE AND INSTALL 4-11/16" DEEP SQUARE BOX WITH 1" CND
AND SINGLE GANG PLASTER RING, STUBBED TO NEAREST CIRCULATION CEILING OR
CABLE TRAY FOR ALL DATA DEVICES.
GENERAL ELECTRICAL NOTES
SCALE: 1/8" = 1'-0"
0 1 5 10 20
N PARTIAL FLOOR PLAN - NEW POWER - AREA "D"
J C
IS
D
T O
R R
A N
T C
E N
T E R
A D
D
IT
IO
N
S
R E N
O V A T
IO
N S
M A
T R
I X
E30
P A R
T
IA
L F
L O
O R
N KEY PLAN
NOT TO SCALE
P L A N
N
E W
P O
W E R
A
R E A D
PTAC
PTAC
PTAC
PTAC
CONV
PTAC
PTAC
CONV
EF
CONV
CONV
CONV
CONV
ECH-1
208V-1Ø, 3.0KW
RTU-6
208V-1Ø, 17.0A
F-24,26
J
J
CR
CR
DOOR OPERATOR
(TYP.)
J-26,28
J-15
J-15
J-17
J
J-15
J
WP
J-19
WP
EXIST. PNL
"L"
EXIST. PNL
"X"
EXIST. PNL
"K"
EXIST. PNL
"J"
NEW PNL
"MDP"
EXIST. PNL
"G"
EXIST. PNL
"H"
NEW PNL
"DP2"
EXIST. PNL
"F"
WP
GFI
J-12
ELECTRICAL KEY NOTES
RELOCATED EQUIPMENT. CONTRACTOR SHALL EXTEND ASSOCIATED
BRANCH CIRCUIT CONDUIT AND WIRE TO NEW LOCATION.
CONTRACTOR SHALL PROVIDE AND INSTALL POWER FOR OWNER PROVIDED
SIGNAGE. VERIFY LOCATION WITH OWNER, PRIOR TO ROUGH-IN.
CONTRACTOR SHALL REUSE EXISTING CONDUIT AND WIRE FOR NEW
EQUIPMENT.
CONTRACTOR SHALL REUSE EXISTING CONDUIT AND WIRE FOR NEW
EQUIPMENT. CONTRACTOR SHALL REMOVE PHASE WIRE FROM PANEL
CONNECTION, FOR USE ON 2-POLE UNIT.
CONTRACTOR SHALL PROVIDE AND INSTALL NEW CONDUIT AND WIRE FOR
NEW EQUIPMENT.
EXHAUST FAN SHALL BE CONTROLLED BY NEW TIMECLOCK. CONFIRM TIME
SCHEDULING WITH OWNER.
REMOVE EXISTING PNEUMATIC INTERLOCK WITHIN STARTER, AND CONNECT
TO NEW CONTROL PANEL FOR CONTROLS.
CONTRACTOR SHALL PROVIDE CIRCUIT TO TRANSFORMER, FOR CONTROL
VALVE POWER.
1. CONTRACTOR SHALL PROVIDE AND INSTALL 4-11/16" DEEP SQUARE BOX WITH 1" CND
AND SINGLE GANG PLASTER RING, STUBBED TO NEAREST CIRCULATION CEILING OR
CABLE TRAY FOR ALL DATA DEVICES.
GENERAL ELECTRICAL NOTES
SCALE: 1/8" = 1'-0"
0 1 5 10 20
N PARTIAL FLOOR PLAN - NEW POWER - AREA "E"
J C
IS
D
T O
R R
A N
T C
E N
T E R
A D
D
IT
IO
N
S
R E N
O V A T
IO
N S
M A
T R
I X
E31
P A R
T
IA
L F
L O
O R
N KEY PLAN
NOT TO SCALE
P L A N
N
E W
P O
W E R
A
R E A E
CONVCONVCONVCONV
CU-3A
208V-1Ø, 13.6A
CU-2A
208V-1Ø, 16.5ACU-1A
208V-1Ø, 16.5A
F-1 120V-1Ø, 11.0A
F-2 120V-1Ø, 11.0A
F-3 120V-1Ø, 8.2A
B2-8,10
B2-2
B1-7,9 B1-8,10
B1-4B1-2
WPWPWP
EXIST. PNL
"B"
EXIST.
PNL
"DP1A"
EXIST. PNL
"B1"
EXIST. PNL
"B2"
EXIST. PNL
"DP1"
3 3
WP
GFI
B1-11
J
W-35
SCALE: 1/8" = 1'-0"
0 1 5 10 20
N PARTIAL FLOOR PLAN - NEW POWER - AREA "F"
J C
IS
D
T O
R R
A N
T C
E N
T E R
A D
D
IT
IO
N
S
R E N
O V A T
IO
N S
M A
T R
I X
E32
P A R
T
IA
L F
L O
O R
N KEY PLAN
NOT TO SCALE
P L A N
N
E W
P O
W E R
A
R E A F
CONV
CONV
CU-5A
208V-1Ø, 17.6A
CU-4A
208V-1Ø, 17.6A
F-5 120V-1Ø, 11.0A
F-4 120V-1Ø, 11.0A
C1-8,10
C1-2
C2-8,10
C2-2
CU-11B
208V-1Ø, 15.1MCA
WP
WP
W-38,40
EXIST. PNL
"C1"
EXIST. PNL
"C2"
EXIST. PNL
"C"
WP
GFI
C2-4
CONV
CONV
CONV
CONV
F-7 120V-1Ø, 11.0A
F-6 120V-1Ø, 11.0A
CU-7A
208V-1Ø, 17.6A
CU-6A
208V-1Ø, 17.6A
D1-2
D2-2 D2-8,10
D1-8,10
WP
WP
EXIST. PNL
"D"
EXIST. PNL
"D1"
EXIST. PNL
"D2"
WP
GFI
WP
GFI
D2-4
D1-4
ELECTRICAL KEY NOTES
RELOCATED EQUIPMENT. CONTRACTOR SHALL EXTEND ASSOCIATED
BRANCH CIRCUIT CONDUIT AND WIRE TO NEW LOCATION.
CONTRACTOR SHALL PROVIDE AND INSTALL POWER FOR OWNER PROVIDED
SIGNAGE. VERIFY LOCATION WITH OWNER, PRIOR TO ROUGH-IN.
CONTRACTOR SHALL REUSE EXISTING CONDUIT AND WIRE FOR NEW
EQUIPMENT.
CONTRACTOR SHALL REUSE EXISTING CONDUIT AND WIRE FOR NEW
EQUIPMENT. CONTRACTOR SHALL REMOVE PHASE WIRE FROM PANEL
CONNECTION, FOR USE ON 2-POLE UNIT.
CONTRACTOR SHALL PROVIDE AND INSTALL NEW CONDUIT AND WIRE FOR
NEW EQUIPMENT.
EXHAUST FAN SHALL BE CONTROLLED BY NEW TIMECLOCK. CONFIRM TIME
SCHEDULING WITH OWNER.
REMOVE EXISTING PNEUMATIC INTERLOCK WITHIN STARTER, AND CONNECT
TO NEW CONTROL PANEL FOR CONTROLS.
CONTRACTOR SHALL PROVIDE CIRCUIT TO TRANSFORMER, FOR CONTROL
VALVE POWER.
1. CONTRACTOR SHALL PROVIDE AND INSTALL 4-11/16" DEEP SQUARE BOX WITH 1" CND
AND SINGLE GANG PLASTER RING, STUBBED TO NEAREST CIRCULATION CEILING OR
CABLE TRAY FOR ALL DATA DEVICES.
GENERAL ELECTRICAL NOTES
SCALE: 1/8" = 1'-0"
0 1 5 10 20
N PARTIAL FLOOR PLAN - NEW POWER - AREA "G"
J C
IS
D
T O
R R
A N
T C
E N
T E R
A D
D
IT
IO
N
S
R E N
O V A T
IO
N S
M A
T R
I X
E33
P A R
T
IA
L F
L O
O R
N KEY PLAN
NOT TO SCALE
P L A N
N
E W
P O
W E R
A
R E A G
CUH
CONV CONV CONV CONV CONV CONV
CONVCONV
CONV
RTU-7
208V-3Ø, 43.0A
ECH-4
208V-1Ø, 1.5KW
ECH-3
208V-1Ø, 3.0KW
ECH-1
208V-1Ø, 3.0KW
ECH-2
208V-1Ø, 1.5KW
DP2-20,22,24
F-24,26
F-28,30
E-30,32
E-38,40
WP
EXIST. PNL
"F"
EXIST. PNL
"E"
WP
GFIE-5
SCALE: 1/8" = 1'-0"
0 1 5 10 20
N
PARTIAL FLOOR PLAN - NEW POWER - AREA "H" (ALTERNATE)
J C
IS
D
T O
R R
A N
T C
E N
T E R
A D
D
IT
IO
N
S
R E N
O V A T
IO
N S
M A
T R
I X
E34
P A R
T
IA
L F
L O
O R
N KEY PLAN
NOT TO SCALE
P L A N
N
E W
P O
W E R
A
R E A H
CU-11B
208V-1Ø, 15.1MCA
CU-10B
208V-1Ø, 15.1MCA
CU-8B
208V-1Ø, 15.1MCA
CU-9B
208V-1Ø, 15.1MCA
UV-8
120V-1Ø, 6.3MCA
UV-9
120V-1Ø, 6.3MCA
UV-10
120V-1Ø, 6.3MCA
UV-11
120V-1Ø, 6.3MCA
120V-1Ø, 6.3MCA
WP
WP
W-22
W-20
W-16
W-18
WP
W-32,34
WP
W-38,40
W-31,33
W-37,39
EXIST. PNL
"W"
EXIST. PNL
"V"
WP
GFI
W-41
WP
GFI
W-42
J
W-35
EWC
W-36
ELECTRICAL KEY NOTES
RELOCATED EQUIPMENT. CONTRACTOR SHALL EXTEND ASSOCIATED
BRANCH CIRCUIT CONDUIT AND WIRE TO NEW LOCATION.
CONTRACTOR SHALL PROVIDE AND INSTALL POWER FOR OWNER PROVIDED
SIGNAGE. VERIFY LOCATION WITH OWNER, PRIOR TO ROUGH-IN.
CONTRACTOR SHALL REUSE EXISTING CONDUIT AND WIRE FOR NEW
EQUIPMENT.
CONTRACTOR SHALL REUSE EXISTING CONDUIT AND WIRE FOR NEW
EQUIPMENT. CONTRACTOR SHALL REMOVE PHASE WIRE FROM PANEL
CONNECTION, FOR USE ON 2-POLE UNIT.
CONTRACTOR SHALL PROVIDE AND INSTALL NEW CONDUIT AND WIRE FOR
NEW EQUIPMENT.
EXHAUST FAN SHALL BE CONTROLLED BY NEW TIMECLOCK. CONFIRM TIME
SCHEDULING WITH OWNER.
REMOVE EXISTING PNEUMATIC INTERLOCK WITHIN STARTER, AND CONNECT
TO NEW CONTROL PANEL FOR CONTROLS.
CONTRACTOR SHALL PROVIDE CIRCUIT TO TRANSFORMER, FOR CONTROL
VALVE POWER.
1. CONTRACTOR SHALL PROVIDE AND INSTALL 4-11/16" DEEP SQUARE BOX WITH 1" CND
AND SINGLE GANG PLASTER RING, STUBBED TO NEAREST CIRCULATION CEILING OR
CABLE TRAY FOR ALL DATA DEVICES.
GENERAL ELECTRICAL NOTES
SCALE: 1/8" = 1'-0"
0 1 5 10 20
N PARTIAL FLOOR PLAN - NEW POWER - AREA "I"
J C
IS
D
T O
R R
A N
T C
E N
T E R
A D
D
IT
IO
N
S
R E N
O V A T
IO
N S
M A
T R
I X
E35
P A R
T
IA
L F
L O
O R
N KEY PLAN
NOT TO SCALE
P L A N
N
E W
P O
W E R
A
R E A
I"
CU-11B
208V-1Ø, 15.1MCA
CU-10B
208V-1Ø, 15.1MCA
CU-12B
208V-1Ø, 15.1MCA
UV-10
120V-1Ø, 6.3MCA
UV-11
120V-1Ø, 6.3MCA
UV-13
120V-1Ø, 6.3MCA
UV-12
120V-1Ø, 6.3MCA
WP
W-16
W-18
WP
W-32,34
WP
W-38,40
V-26,28
V-10
V-20
EXIST. PNL
"V"
EXIST. PNL
"RP-AA"
WP
GFI
V-30
WP
GFI
W-42
EWC
W-36
ELECTRICAL KEY NOTES
RELOCATED EQUIPMENT. CONTRACTOR SHALL EXTEND ASSOCIATED
BRANCH CIRCUIT CONDUIT AND WIRE TO NEW LOCATION.
CONTRACTOR SHALL PROVIDE AND INSTALL POWER FOR OWNER PROVIDED
SIGNAGE. VERIFY LOCATION WITH OWNER, PRIOR TO ROUGH-IN.
CONTRACTOR SHALL REUSE EXISTING CONDUIT AND WIRE FOR NEW
EQUIPMENT.
CONTRACTOR SHALL REUSE EXISTING CONDUIT AND WIRE FOR NEW
EQUIPMENT. CONTRACTOR SHALL REMOVE PHASE WIRE FROM PANEL
CONNECTION, FOR USE ON 2-POLE UNIT.
CONTRACTOR SHALL PROVIDE AND INSTALL NEW CONDUIT AND WIRE FOR
NEW EQUIPMENT.
EXHAUST FAN SHALL BE CONTROLLED BY NEW TIMECLOCK. CONFIRM TIME
SCHEDULING WITH OWNER.
REMOVE EXISTING PNEUMATIC INTERLOCK WITHIN STARTER, AND CONNECT
TO NEW CONTROL PANEL FOR CONTROLS.
CONTRACTOR SHALL PROVIDE CIRCUIT TO TRANSFORMER, FOR CONTROL
VALVE POWER.
1. CONTRACTOR SHALL PROVIDE AND INSTALL 4-11/16" DEEP SQUARE BOX WITH 1" CND
AND SINGLE GANG PLASTER RING, STUBBED TO NEAREST CIRCULATION CEILING OR
CABLE TRAY FOR ALL DATA DEVICES.
GENERAL ELECTRICAL NOTES
SCALE: 1/8" = 1'-0"
0 1 5 10 20
N PARTIAL FLOOR PLAN - NEW POWER - AREA "J"
J C
IS
D
T O
R R
A N
T C
E N
T E R
A D
D
IT
IO
N
S
R E N
O V A T
IO
N S
M A
T R
I X
E36
P A R
T
IA
L F
L O
O R
N KEY PLAN
NOT TO SCALE
P L A N
N
E W
P O
W E R
A
R E A J
A2-31,33,35
CU-9B
208V-1Ø, 15.1MCA
CU-14B
208V-1Ø, 17.5MCA
CU-13B
208V-1Ø, 15.1MCA
UV-9
120V-1Ø, 6.3MCA
UV-14
120V-1Ø, 6.3MCA
UV-13
120V-1Ø, 6.3MCA
WP
WP
WP
W-22
W-37,39
V-31,33
V-25,27
V-8
V-10
EPO
EXIST. PNL
"V"
EXIST. PNL
"S"
EXIST. PNL
"T"
EXIST.
POOL "PNL
#1"
WP
WP
GFI
V-29
WP
GFI
W-41
J
S-15
ELECTRICAL KEY NOTES
RELOCATED EQUIPMENT. CONTRACTOR SHALL EXTEND ASSOCIATED
BRANCH CIRCUIT CONDUIT AND WIRE TO NEW LOCATION.
CONTRACTOR SHALL PROVIDE AND INSTALL POWER FOR OWNER PROVIDED
SIGNAGE. VERIFY LOCATION WITH OWNER, PRIOR TO ROUGH-IN.
CONTRACTOR SHALL REUSE EXISTING CONDUIT AND WIRE FOR NEW
EQUIPMENT.
CONTRACTOR SHALL REUSE EXISTING CONDUIT AND WIRE FOR NEW
EQUIPMENT. CONTRACTOR SHALL REMOVE PHASE WIRE FROM PANEL
CONNECTION, FOR USE ON 2-POLE UNIT.
CONTRACTOR SHALL PROVIDE AND INSTALL NEW CONDUIT AND WIRE FOR
NEW EQUIPMENT.
EXHAUST FAN SHALL BE CONTROLLED BY NEW TIMECLOCK. CONFIRM TIME
SCHEDULING WITH OWNER.
REMOVE EXISTING PNEUMATIC INTERLOCK WITHIN STARTER, AND CONNECT
TO NEW CONTROL PANEL FOR CONTROLS.
CONTRACTOR SHALL PROVIDE CIRCUIT TO TRANSFORMER, FOR CONTROL
VALVE POWER.
1. CONTRACTOR SHALL PROVIDE AND INSTALL 4-11/16" DEEP SQUARE BOX WITH 1" CND
AND SINGLE GANG PLASTER RING, STUBBED TO NEAREST CIRCULATION CEILING OR
CABLE TRAY FOR ALL DATA DEVICES.
GENERAL ELECTRICAL NOTES
SCALE: 1/8" = 1'-0"
0 1 5 10 20
N PARTIAL FLOOR PLAN - NEW POWER - AREA "K"
J C
IS
D
T O
R R
A N
T C
E N
T E R
A D
D
IT
IO
N
S
R E N
O V A T
IO
N S
M A
T R
I X
E37
P A R
T
IA
L F
L O
O R
N KEY PLAN
NOT TO SCALE
P L A N
N
E W
P O
W E R
A
R E A K
RTU-10
208V-3Ø, 31.0A
RTU-8
208V-3Ø, 31.0A
RTU-9
208V-3Ø, 31.0A
RTU-11
208V-3Ø, 31.0A
RTU-12
208V-3Ø, 31.0A
RTU-13
208V-3Ø, 26.0A
A2-31,33,35
A2-32,34,36
A2-37,39,41
A2-38,40,42
A2-43,45,47
A2-44,46,48
CONTROL PANEL (TYP.)
CU-14B
208V-1Ø, 17.5MCA
CU-13B
208V-1Ø, 15.1MCA
CU-12B
208V-1Ø, 15.1MCA
UV-13
120V-1Ø, 6.3MCA
WP
WP
WP
V-31,33
V-25,27
V-26,28
V-10
EXIST. PNL
"A1"
EXIST. PNL
"A2"
WP
WP
WP
WP
WP
WP
WP
GFI
A2-54
WP
GFI
WP
GFI
V-30
V-29
EWC
A2-55
ELECTRICAL KEY NOTES
RELOCATED EQUIPMENT. CONTRACTOR SHALL EXTEND ASSOCIATED
BRANCH CIRCUIT CONDUIT AND WIRE TO NEW LOCATION.
CONTRACTOR SHALL PROVIDE AND INSTALL POWER FOR OWNER PROVIDED
SIGNAGE. VERIFY LOCATION WITH OWNER, PRIOR TO ROUGH-IN.
CONTRACTOR SHALL REUSE EXISTING CONDUIT AND WIRE FOR NEW
EQUIPMENT.
CONTRACTOR SHALL REUSE EXISTING CONDUIT AND WIRE FOR NEW
EQUIPMENT. CONTRACTOR SHALL REMOVE PHASE WIRE FROM PANEL
CONNECTION, FOR USE ON 2-POLE UNIT.
CONTRACTOR SHALL PROVIDE AND INSTALL NEW CONDUIT AND WIRE FOR
NEW EQUIPMENT.
EXHAUST FAN SHALL BE CONTROLLED BY NEW TIMECLOCK. CONFIRM TIME
SCHEDULING WITH OWNER.
REMOVE EXISTING PNEUMATIC INTERLOCK WITHIN STARTER, AND CONNECT
TO NEW CONTROL PANEL FOR CONTROLS.
CONTRACTOR SHALL PROVIDE CIRCUIT TO TRANSFORMER, FOR CONTROL
VALVE POWER.
1. CONTRACTOR SHALL PROVIDE AND INSTALL 4-11/16" DEEP SQUARE BOX WITH 1" CND
AND SINGLE GANG PLASTER RING, STUBBED TO NEAREST CIRCULATION CEILING OR
CABLE TRAY FOR ALL DATA DEVICES.
GENERAL ELECTRICAL NOTES
SCALE: 1/8" = 1'-0"
0 1 5 10 20
N PARTIAL FLOOR PLAN - NEW POWER - AREA "L"
J C
IS
D
T O
R R
A N
T C
E N
T E R
A D
D
IT
IO
N
S
R E N
O V A T
IO
N S
M A
T R
I X
E38
P A R
T
IA
L F
L O
O R
N KEY PLAN
NOT TO SCALE
P L A N
N
E W
P O
W E R
A
R E A L
120V-1Ø, 1/15HP
120V-1Ø, 1/15HP
CONTROL PANEL (TYP.)
T-12 T-32 T-34 T-36
CU-14B
208V-1Ø, 17.5MCAUV-14
120V-1Ø, 6.3MCA
CH-2
120V-1Ø, 17.5MCA
R-37
WP
V-8
B-2 120V-1Ø, 12.0A
B-1 120V-1Ø, 12.0A
P-1
208V-3Ø, 1.5HP
P-2
208V-3Ø, 1.5HP
J J
J J
T-14,16,18
T-19,21,23
T-33
T-35
P-3 120V-1Ø, 3.0A
P-4 120V-1Ø, 3.0A
EPO
EXIST. PNL
"S"
EXIST. PNL
"T"
EXIST.
POOL "PNL
#1"
EX
EX
J
S-15
J
S-15
J
S-15J
S-15
J
S-15
ELECTRICAL KEY NOTES
RELOCATED EQUIPMENT. CONTRACTOR SHALL EXTEND ASSOCIATED
BRANCH CIRCUIT CONDUIT AND WIRE TO NEW LOCATION.
CONTRACTOR SHALL PROVIDE AND INSTALL POWER FOR OWNER PROVIDED
SIGNAGE. VERIFY LOCATION WITH OWNER, PRIOR TO ROUGH-IN.
CONTRACTOR SHALL REUSE EXISTING CONDUIT AND WIRE FOR NEW
EQUIPMENT.
CONTRACTOR SHALL REUSE EXISTING CONDUIT AND WIRE FOR NEW
EQUIPMENT. CONTRACTOR SHALL REMOVE PHASE WIRE FROM PANEL
CONNECTION, FOR USE ON 2-POLE UNIT.
CONTRACTOR SHALL PROVIDE AND INSTALL NEW CONDUIT AND WIRE FOR
NEW EQUIPMENT.
EXHAUST FAN SHALL BE CONTROLLED BY NEW TIMECLOCK. CONFIRM TIME
SCHEDULING WITH OWNER.
REMOVE EXISTING PNEUMATIC INTERLOCK WITHIN STARTER, AND CONNECT
TO NEW CONTROL PANEL FOR CONTROLS.
CONTRACTOR SHALL PROVIDE CIRCUIT TO TRANSFORMER, FOR CONTROL
VALVE POWER.
1. CONTRACTOR SHALL PROVIDE AND INSTALL 4-11/16" DEEP SQUARE BOX WITH 1" CND
AND SINGLE GANG PLASTER RING, STUBBED TO NEAREST CIRCULATION CEILING OR
CABLE TRAY FOR ALL DATA DEVICES.
GENERAL ELECTRICAL NOTES
SCALE: 1/8" = 1'-0"
0 1 5 10 20
N PARTIAL FLOOR PLAN - NEW POWER - AREA "M"
J C
IS
D
T O
R R
A N
T C
E N
T E R
A D
D
IT
IO
N
S
R E N
O V A T
IO
N S
M A
T R
I X
E39
P A R
T
IA
L F
L O
O R
N KEY PLAN
NOT TO SCALE
P L A N
N
E W
P O
W E R
A
R E A M
PANEL
EXISTING
"L" 120/208V 3Ø, 4W
400A, MLO
CUSTOMER OWNED
TR-1
400A/3P
GROUND BUS
EXISTING "MDP"
1600A, 120/208V, 3Ø-4W
800A/3P
1600A/3P
800A/3P
#6BUILDING
STEEL
COLD WATER
PIPING
GROUND
ROD #6
CONCRETE
ENCASED
EXEX
1000A BUS RATING 1200A BUS RATING
225A/3P
PANEL
EXISTING
"M" 120/208V 3Ø, 4W
225A, MLO
200A/3P
PANEL
EXISTING
"J" 120/208V 3Ø, 4W
225A, MLO
200A/3P
SPARE
FORMER PANEL "L"
SHORT NOTED ON BREAKER
200A/3P
PANEL
EXISTING
"K" 120/208V 3Ø, 4W
225A, MLO
SPACE
150A/3P
PANEL
EXISTING
"A" 120/208V 3Ø, 4W
225A, MLO
100A/3P
SPARE
FORMER UV CORP 23
SPACE
SHORT NOTED ON BREAKER
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
EXISTING CABINET
100A/3P
GROUND BUS
EXISTING "DP-3"
600A, 120/208V, 3Ø-4W
100A/3P
600A/3P
1000A BUS RATING
CUSTOMER OWNED
TR-2
EXISTING PRIMARY
SWITCHGEAREXISTING PRIMARY
METERING CABINET
FROM UTILITY COMPANY
PANEL
EXISTING
"R" 120/208V 3Ø, 4W
225A, MCB
PANEL
EXISTING
"Q" 120/208V 3Ø, 4W
100A, MCB
PANEL
EXISTING
"S" 120/208V 3Ø, 4W
100A, MCB
PANEL
EXISTING
"T" 120/208V 3Ø, 4W
100A, MCB
PANEL
EXISTING
"POOL"
120/208V 3Ø, 4W
100A, MLO
PANEL
EXISTING
"V" 120/208V 3Ø, 4W
225A, MCB
PANEL
EXISTING
"A1" 120/208V 3Ø, 4W
300A, MCB
PANEL
EXISTING
"A2" 120/208V 3Ø, 4W
300A, MLO
PANEL
EXISTING
"RP-AA"
120/208V 3Ø, 4W
225A, MCB
PANEL
EXISTING
"W" 120/208V 3Ø, 4W
225A, MCB
PANEL
EXISTING
"HOME LAB"
120/208V 3Ø, 4W
100A, MCB
PANEL
EXISTING
"C" 120/208V 3Ø, 4W
225A, MLO
100A/3P
3PH 3W
NEMA 3R
FUSED
CAFETERIA
RTU
PANEL
EXISTING
"B" 120/208V 3Ø, 4W
225A, MLO
PANEL
EXISTING
"D" 120/208V 3Ø, 4W
225A, MLO
PANEL
EXISTING
"Z" 120/208V 1Ø, 3W
100A, MCB
M
PANEL
EXISTING
"C1" 120/208V 3Ø, 4W
60A, MCB
PANEL
EXISTING
"C2" 120/208V 3Ø, 4W
60A, MCB
PANEL
EXISTING
"D1" 120/208V 3Ø, 4W
60A, MCB
PANEL
EXISTING
"D2" 120/208V 3Ø, 4W
60A, MCB
PANEL
EXISTING
"E" 120/208V 3Ø, 4W
225A, MLO
PANEL
EXISTING
"F" 120/208V 3Ø, 4W
225A, MLO
300A/3P
GROUND BUS
EXISTING "DP1"
800A, 120/208V, 3Ø-4W
800A BUS RATING
SPACE
SPACE
100A/2P
100A/3P
100A/3P
225A/3P
100A/3P
225A/3P
225A/3P
SPACE
225A/3P
225A/3P
PANEL
EXISTING
"G" 120/208V 3Ø, 4W
225A, MLO
PANEL
EXISTING
"H" 120/208V 3Ø, 4W
225A, MLO
150A/3P
GROUND BUS
EXISTING "DP2"
800A, 120/208V, 3Ø-4W
800A BUS RATING
150A/3P
200A/3P
200A/3P
225A/3P
225A/3P
100A/3P
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPARE
FORMER UVSPARESPARE
PANEL
EXISTING
"X" 120/208V 1Ø, 3W
100A, MCB
PANEL
EXISTING
"B1" 120/208V 3Ø, 4W
60A, MCB
PANEL
EXISTING
"B2" 120/208V 3Ø, 4W
60A, MCB
PANEL
EXISTING
"N" 120/208V 3Ø, 4W
125A, MCB
PANEL
EXISTING
"P" 120/208V 3Ø, 4W
225A, MLO
100A/3P
100A/3P
125A/3P
100A/3P
225A/3P
225A/3P
SPARE
DEFECTIVE BREAKER
100A/3P
3PH 3W
NEMA 3R
FUSED
RTU
SPARE
#6BUILDING
STEEL
COLD WATER
PIPING
GROUND
ROD #6
CONCRETE
ENCASED
EXEX
EXISTING EQUIPMENT TO REMAIN.
DISCONNECT & REMOVE EXISTING EQUIPMENT. REMOVE ASSOCIATED
CONDUIT & WIRE.
DISCONNECT & REMOVE EXISTING EQUIPMENT. ASSOCIATED CONDUIT &
WIRE TO REMAIN FOR NEW EQUIPMENT.
DISCONNECT & REMOVE EXISTING EQUIPMENT. MODIFY ASSOCIATED
FEEDER CONDUIT & WIRE FOR NEW FEED SOURCE.
DEMOLITION NOTES
1 1
1 1
4 4
4 2 4 4
4 4 4 4
4 4 4 4
1 1 1 1 1 1 1 1 1 1
1 1 1 1 1 1
J C
IS
D
T O
R R
A N
T C
E N
T E R
A D
D
IT
IO
N
S
R E N
O V A T
IO
N S
M A
T R
I X
E X
IS
T
IN
G E L E C
T R
IC
A L R
IS
E R
D
IA
G R
A
E40
PANEL
EXISTING
"L" 120/208V 3Ø, 4W
400A, MLO
CUSTOMER OWNED
TR-1
400A/3P
GROUND BUS
NEW "MDP"
1600A, 120/208V, 3Ø-4W
800A/3P
1600A/3P
800A/3P
#6BUILDING
STEEL
COLD WATER
PIPING
GROUND
ROD #6
CONCRETE
ENCASED
225A/3P
PANEL
EXISTING
"M" 120/208V 3Ø, 4W
225A, MLO
200A/3P
PANEL
EXISTING
"J" 120/208V 3Ø, 4W
225A, MLO
200A/3P
200A/3P
PANEL
EXISTING
"K" 120/208V 3Ø, 4W
225A, MLO
150A/3P
PANEL
EXISTING
"A" 120/208V 3Ø, 4W
225A, MLO
100A/3P
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
EXISTING CABINET
100A/3P
GROUND BUS
EXISTING "DP-3"
600A, 120/208V, 3Ø-4W
100A/3P
600A/3P
1000A BUS RATING
CUSTOMER OWNED
TR-2
EXISTING PRIMARY
SWITCHGEAREXISTING PRIMARY
METERING CABINET
FROM UTILITY COMPANY
PANEL
NEW
"R" 120/208V 3Ø, 4W
225A, MCB
PANEL
NEW
"Q" 120/208V 3Ø, 4W
100A, MCB
PANEL
EXISTING
"S" 120/208V 3Ø, 4W
100A, MCB
PANEL
EXISTING
"T" 120/208V 3Ø, 4W
100A, MCB
PANEL
EXISTING
"POOL"
120/208V 3Ø, 4W
100A, MLO
PANEL
EXISTING
"E" 120/208V 3Ø, 4W
225A, MLO
PANEL
EXISTING
"F" 120/208V 3Ø, 4W
225A, MLO
PANEL
EXISTING
"G" 120/208V 3Ø, 4W
225A, MLO
PANEL
EXISTING
"H" 120/208V 3Ø, 4W
225A, MLO
150A/3P
GROUND BUS
NEW "DP2"
800A, 120/208V, 3Ø-4W
800A BUS RATING
150A/3P
200A/3P
200A/3P
225A/3P
225A/3P
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
PANEL
EXISTING
"X" 120/208V 1Ø, 3W
100A, MCB
PANEL
EXISTING
"N" 120/208V 3Ø, 4W
125A, MCB
PANEL
NEW
"P" 120/208V 3Ø, 4W
225A, MLO
100A/3P
100A/3P
125A/3P
100A/3P
225A/3P
225A/3P
#6BUILDING
STEEL
COLD WATER
PIPING
GROUND
ROD #6
CONCRETE
ENCASED
#3/0#3/0
ELECTRICAL KEY NOTES
MAIN BREAKER SHALL HAVE INTEGRAL ERMS.
CONTRACTOR SHALL PROVIDE AND INSTALL OWNER PROVIDED DIGITAL
METER.
CONNECT EXISTING EQUIPMENT TO NEW DISTRIBUTION PANEL.
#4/0#4/0
SPARE
DEFECTIVE BREAKER SPARE
1. CONTRACTOR'S SCOPE OF WORK SHALL INCLUDE PROVIDING ARC-FLASH STUDY, AS
REQUIRED BY NEC. AVAILABLE FAULT CURRENT RATINGS SHALL BE LISTED ON ALL
PANELS LOCATED THROUGHOUT THE BUILDING. STUDY SHALL BE TURNED OVER TO
OWNER, WITHIN PROJECT CLOSEOUT PACKAGE.
GENERAL ELECTRICAL NOTES
1600A BUS RATING
GFI
100A/3P
TVSS
80A/3P
TVSS
80A/3P
TVSS
3 3 3 3 3 3
(3) #3
(1) #8 GND
1-1/4" CND
(3) #3
(1) #8 GND
1-1/4" CND
(3) #3
(1) #8 GND
1-1/4" CND
(4) #4/0
(1) #4 GND
2-1/2" CND
(4) #4/0
(1) #4 GND
2-1/2" CND
(4) #1
(1) #8 GND
1-1/2" CND
(5) SETS OF
(4) #400KCMIL
(1) #4/0 GND
3-1/2" CND
PANEL
EXISTING
"V" 120/208V 3Ø, 4W
225A, MCB
PANEL
EXISTING
"A1" 120/208V 3Ø, 4W
300A, MCB
PANEL
EXISTING
"A2" 120/208V 3Ø, 4W
300A, MLO
PANEL
EXISTING
"RP-AA"
120/208V 3Ø, 4W
225A, MCB
PANEL
EXISTING
"W" 120/208V 3Ø, 4W
225A, MCB
PANEL
EXISTING
"HOME LAB"
120/208V 3Ø, 4W
100A, MCB
PANEL
EXISTING
"C" 120/208V 3Ø, 4W
225A, MLO
100A/3P
3PH 3W
NEMA 3R
FUSED
CAFETERIA
RTU
PANEL
EXISTING
"B" 120/208V 3Ø, 4W
225A, MLO
PANEL
EXISTING
"D" 120/208V 3Ø, 4W
225A, MLO
PANEL
EXISTING
"Z" 120/208V 1Ø, 3W
100A, MCB
PANEL
EXISTING
"C1" 120/208V 3Ø, 4W
60A, MCB
PANEL
EXISTING
"C2" 120/208V 3Ø, 4W
60A, MCB
PANEL
EXISTING
"D1" 120/208V 3Ø, 4W
60A, MCB
PANEL
EXISTING
"D2" 120/208V 3Ø, 4W
60A, MCB
300A/3P
GROUND BUS
EXISTING "DP1"
800A, 120/208V, 3Ø-4W
800A BUS RATING
SPACE
SPACE
100A/2P
100A/3P
100A/3P
225A/3P
100A/3P
225A/3P
225A/3P
225A/3P
225A/3P
PANEL
EXISTING
"B1" 120/208V 3Ø, 4W
60A, MCB
PANEL
EXISTING
"B2" 120/208V 3Ø, 4W
60A, MCB
80A/3P
TVSS
(3) #3
(1) #8 GND
1-1/4" CND
J C
IS
D
T O
R R
A N
T C
E N
T E R
A D
D
IT
IO
N
S
R E N
O V A T
IO
N S
M A
T R
I X
R E V
IS
E D
E L E C
T R
IC
A L R
IS
E R
D
IA
G R
A
E41
PHOTO CONTROL,
INTERMATIC
NOTE:
-MOUNT PHOTO EYE FACING NORTH ON NORTH SIDE OF BUILDING.
WITH CLOCK MOTOR, 7-DAY
TIME SWITCH CONTROL
INTERMATIC #T7402BC
CONTROL AND 40 AMP 4 POLE CONTACTS,
N
AREA LIGHTS
2 EXTERIOR LIGHTING CONTROL DETAIL
SCALE: N.T.S.
BUILDING LIGHTSLINE
NEUTRAL
PLAN
ELECTRICAL
COMPOSITE GASKETED BOX,
QUAZITE OR EQUAL
HEAVY DUTY, SKID-RESISTANT COVER,
BOLT-DOWN TYPE, TAMPER RESISTANT
HARDWARE
3" MIN. SAND OR
GRANULAR BACKFILL
1 ELECTRICAL HANDHOLE DETAIL
SCALE:NTS
LIFTING EYE
FINISHED GRADE
UNDISTURBED EARTH
CONDUIT
SECTION
24"
13"
OPEN BOTTOM
BOX EXTENSION
DIVIDER
24" DIAMETER
SONOTUBE
6 LIGHT POLE DETAIL
SCALE: N.T.S.
24"60"
36"
CURB & ROADWAY
SEAL TIGHT HOLE
LIGHT POLE:
ULS POLES #RPSQ-20-5-11-AB-MODBASE/MODAB-DD1-XHH
(20' POLE WITH 2 HH 1-3/8" HOLE) WITH ANCHOR BOLTS
· STEEL POLE: 20' POLE x 5" SQ x 11 GAUGE
· MODBASE/MODAB: 10.5"-11.5" BOLT CIRCLE WITH 3/4"
O.D. ANCHOR BOLTS
· XHH: 15' ABOVE BASE AT 90°
HAND HOLE ON SIDE
OPPOSITE OF ROADWAY
216"
48"
12"
18"
24" DIAMETER GRAY
"CEMETUBE" HDPE WITH BELLED
END
1.75'
(TYP. U.N.O.)
1" CONDUIT OUT OF BOX
INTO POLE BASE
2" CONDUIT IN
12"x12" QUAZITE BOX
(COMMUNICATION)
2" CONDUIT
2" CONDUIT
LIGHT POLE
1.75'
(TYP. U.N.O.)
CURB & GUTTER
PLAN VIEW
24" DIAMETER BASE
1" CONDUIT
FOR COMMUNICATIONS
1" CONDUIT
FOR ELECTRIC
1" SEAL TIGHT WITH 90°
FITTING AT TOP
FOR COMMUNICATIONS
HAND HOLE: QUAZITE #PC1212BA12, 12"x12", 12" DEEP OPEN BOTTOM. PROVIDE
#PC1212CA0012 "COMMUNICATIONS" COVER. INSTALL ENCLOSURE ON 6" GRAVEL BASE.
INSTALL 1" PVC CONDUIT FROM HAND HOLE THROUGH CONCRETE POLE BASE AND
INTO POLE. COMMUNICATION CONDUIT SHALL EXTEND UNINTERRUPTED FROM PVC
CONDUIT TO 90° FITTING AT 17' ABOVE POLE BASE BY MEANS OF SEAL TIGHT FLEXIBLE
CONDUIT. ELECTRICIAN SHALL DRILL HOLE IN 11 GAUGE STEEL FOR FITTING. PAINT
METAL TO PREVENT RUSTING.
HAND HOLE: QUAZITE #PC1212BA12, 12"x12", 12" DEEP OPEN
BOTTOM. PROVIDE #PC1212CA0017 "ELECTRIC" COVER.
INSTALL ENCLOSURE ON 6" GRAVEL BASE. INSTALL POWER IN
1" PVC CONDUIT FROM HAND HOLE THROUGH CONCRETE POLE
BASE AND INTO POLE.
FIXTURE(S) PER SCHEDULE
BASE COVER
GROUND LUG
#6 TW GREEN GRD. WIRE
GROUND ROD/CADWELD
8'-0" x 5/8" GROUND ROD.
PROVIDE IN-LINE WATERPROOF FUSES AS
RECOMMENDED BY LUMINAR MANUFACTURER.
INSTALL NEAR HANDHOLE.
ANCHOR BOLTS FURNISHED
BY MANUFACTURER
RIGID STEEL CONDUIT
STUB-OUT MIN. DEPTH PER
N.E.C. OR SPECS.
PROVIDE DOUBLE NUTS FOR LEVELING OF UNIT (ONE ABOVE,
ONE BELOW BASE FLANGE) GROUT BETWEEN BASE AND
FLANGE. SLOPE TOP TO PREVENT WATER ACCUMULATION.
2'-0"
5' -0
3'
-0
'-0
4 AREA LIGHT - POLE BASE DETAIL
SCALE: N.T.S.
PROVIDE IN-LINE WATER
BY MANUFACTURER
CONNECT GRD. TO POLE
BASE WITH BURNDY #GB4C
HANDHOLE
SIZE AS RECOMMENDED
PROOF FUSES IN CIRCUIT
POLE MANUFACTURER
REBAR (TYP.)
BASE BY E.C.
GRD. ROD CLAMP
8'-0" x 5/8" DIA.
#6 TW GREEN GRD. WIRE
RIGID CONDUIT
GROUND ROD
COPPER CLAD
BASE COVER
LEVELING OF UNIT (ONE ABV. & ONE
TO PREVENT WATER ACCUMULATION.
ANCHOR BOLTS FURNISHED BY
ANCHOR BOLTS TO PROJECT ABOVE TOP
OF BASE. PROVIDE DOUBLE NUTS FOR
BELOW BASE FLANGE). GROUT BETWEEN
CONCRETE BASE & FLANGE. SLOPE TOP
CONDUIT & WIRE AS SPECIFIED
2'-0" 3'
-0
'-0
INSTALL NEAR HANDHOLE
5 PEDESTRIAN LIGHT - POLE BASE DETAIL
SCALE: N.T.S.
CONCRETE SLAB
3" MIN. BELOW SLAB
OR AS REQUIRED FOR
SWEEPS
SCHEDULE 40 PVC CONDUIT
REFER TO SPECS FOR CONDUIT REQUIREMENTS
PVC TO RIGID ADAPTOR
TO TRANSITION FROM UNDERFLOOR
PROVIDE RGC WITH SWEEP
PVC CONDUIT.
COMPACTED
UNDERFLOOR CONDUITS IN
SLAB ON GRADE INSTALLATION
SCALE: N.T.S.
FIXTURE
MOUNTING
HEIGHT
LIGHT ENGINEDESCRIPTION AND COMMENTSTYPE MANUFACTURER CATALOG NO.
LIGHTING FIXTURE SCHEDULE
T5W
2T4W
T4W
T4FT
T2-HSS
T2
SL2
DIMMING INFO
1. ALTERNATE LIGHTING NOT ALLOWED FOR THE FIXTURES LISTED.
FIXTURE SCHEDULE NOTES
GALN-SA2C-740-U-T2-BZMCGRAW EDISON AS SHOWN ON
DRAWINGS
EXTERIOR SITE LIGHT WITH 2 LIGHT SQUARES, TYPE 2 OPTICS, INTEGRAL
PHOTOCELL, AND BRONZE FINISH. 0-10V
14219 LUMENS
108W, 4000K
LED
GPC-SA1C-740-U-SL2-BZMCGRAW EDISON AS SHOWN ON
DRAWINGS
EXTERIOR SITE LIGHT WITH 1 LIGHT SQUARE, TYPE 2 SPILL-CONTROL OPTICS,
INTEGRAL PHOTOCELL, AND BRONZE FINISH. 0-10V
7399 LUMENS
59W, 4000K
LED
GALN-SA2C-740-U-T2-BZ-HSSMCGRAW EDISON AS SHOWN ON
DRAWINGS
EXTERIOR SITE LIGHT WITH 2 LIGHT SQUARES, TYPE 2 OPTICS, HOUSE SIDE
SHIELD, INTEGRAL PHOTOCELL, AND BRONZE FINISH. 0-10V
14219 LUMENS
108W, 4000K
LED
GALN-SA6C-740-U-T4FT-BZMCGRAW EDISON AS SHOWN ON
DRAWINGS
EXTERIOR SITE LIGHT WITH 6 LIGHT SQUARES, TYPE 4 FORWARD OPTICS,
INTEGRAL PHOTOCELL, AND BRONZE FINISH. 0-10V
42558 LUMENS
321W, 4000K
LED
GALN-SA6C-740-U-5WQ-BZMCGRAW EDISON AS SHOWN ON
DRAWINGS
EXTERIOR SITE LIGHT WITH 6 LIGHT SQUARES, TYPE 5 WIDE OPTICS, INTEGRAL
PHOTOCELL, AND BRONZE FINISH. 0-10V
44560 LUMENS
321W, 4000K
LED
GALN-SA4C-740-U-T4W-BZMCGRAW EDISON AS SHOWN ON
DRAWINGS
EXTERIOR SITE LIGHT WITH 4 LIGHT SQUARES, TYPE 4 WIDE OPTICS, INTEGRAL
PHOTOCELL, AND BRONZE FINISH. 0-10V
28333 LUMENS
213W, 4000K
LED
(2): GALN-SA6C-740-U-T4FT-BZMCGRAW EDISON AS SHOWN ON
DRAWINGS
DOUBLE HEAD EXTERIOR SITE LIGHT WITH 6 LIGHT SQUARES, TYPE 4 FORWARD
OPTICS, INTEGRAL PHOTOCELL, AND BRONZE FINISH. 0-10V
85116 LUMENS
642W, 4000K
LED
-PROVIDE ADEQUATE COMPONENTS FOR CIRCUITING SHOWN ON SITE PLAN
J C
IS
D
T O
R R
A N
T C
E N
T E R
A D
D
IT
IO
N
S
R E N
O V A T
IO
N S
M A
T R
I X
E42
E L E C
T R
IC
A L
S
IT
E D
E T A
IL
S
QUANTITY AS SHOWN ON PLANS.
LIGHTING LOAD
(TYPICAL)
POWER PACK
(TYP.)
CAT 5e CABLE (TYP.)
OCCUPANCY/PHOTOCELL
SENSORS (TYPICAL)
TOP CONTROL
BOTTOM CONTROL
S
ON/OFF
DOS
TOP CONTROL
BOTTOM CONTROL
120V IN0
10V
POWER CIRCUIT
QUANTITY AS SHOWN ON PLANS.
LIGHTING LOAD
(TYPICAL)
POWER PACK
(TYP.)
CAT 5e CABLE (TYP.)
OCCUPANCY/PHOTOCELL
SENSORS (TYPICAL)
TOP CONTROLED
BOTTOM NOT
CONTROLED
D
POWER PACK
(TYP.) TOP CONTROLED
BOTTOM NOT
CONTROLED
CAT 5e
CABLE
(TYP.)
POWER PACK
(TYP.) TOP CONTROLED
BOTTOM NOT
CONTROLED
POWER PACK
(TYP.) TOP CONTROLED
BOTTOM NOT
CONTROLED
SINGLE VOLTAGE, MULTI-CIRCUIT RECEPTACLE AND
LIGHTING CONTROL
SCALE: N.T.S.
POWER CIRCUIT
POWER CIRCUIT
POWER CIRCUIT
277V POWER CIRCUIT
QUANTITY AS SHOWN ON PLANS.
LIGHTING LOAD
(TYPICAL)
POWER PACK
(TYP.)
CAT 5e CABLE (TYP.)
OCCUPANCY/PHOTOCELL
SENSORS (TYPICAL)
D
POWER PACK
(TYP.) TOP CONTROLED
BOTTOM NOT
CONTROLED
CAT 5e
CABLE
(TYP.)
POWER PACK
(TYP.) TOP CONTROLED
BOTTOM NOT
CONTROLED
POWER PACK
(TYP.) TOP CONTROLED
BOTTOM NOT
CONTROLED
DUAL VOLTAGE, MULTI-CIRCUIT RECEPTACLE AND
LIGHTING CONTROL
SCALE: N.T.S.
120V POWER CIRCUIT
120V POWER CIRCUIT
120V POWER CIRCUIT
CEILING OCC SENSOR RECEPTACLE AND LIGHTING
CONTROL
SCALE: N.T.S.
WALL OCC SENSOR RECEPTACLE AND LIGHTING
CONTROL
SCALE: N.T.S.
POWER CIRCUIT
QUANTITY AS SHOWN ON PLANS.
LIGHTING LOAD
(TYPICAL)
POWER PACK
(TYP.)
CAT 5e CABLE (TYP.)
S K
TYPICAL DIMMING LAYOUTS
ON/OFF
S D
OCCUPANCY/PHOTOCELL
SENSORS (TYPICAL)
1.
2.
3.
4.
SEQUENCE OF OPERATION:
ALL CONTROLS TO BE COMPLIANT WITH MICHIGAN
ENERGY CODE, BASED UPON ASHRAE 90.1, 2013.
MANUAL ON, LOCAL DIMMING AND ON/OFF OVERRIDE,
AUTOMATIC OFF.
PROVIDE SINGLE (1) COVERPLATE. SIZE BASED ON
SWITCHES REQUIRED.
SEE PLANS FOR SPECIFIC QUANTITY AND LOCATION OF
SWITCH TYPES.
S K
TURN TO RIGHT
FOR ON/UP
LEFT FOR
OFF/DOWN
POWER CIRCUIT
QUANTITY AS SHOWN ON PLANS.
LIGHTING LOAD
(TYPICAL)
POWER PACK
(TYP.)
CAT 5e CABLE (TYP.)
S D
S D
TYPICAL DIMMING LAYOUTS
ON/OFF
S D
POWER PACK
(TYP.)
LIGHTING LOAD
(TYPICAL)
OCCUPANCY/PHOTOCELL
SENSORS (TYPICAL)
1.
2.
3.
4.
SEQUENCE OF OPERATION:
ALL CONTROLS TO BE COMPLIANT WITH MICHIGAN
ENERGY CODE, BASED UPON ASHRAE 90.1, 2013.
MANUAL ON, LOCAL DIMMING AND ON/OFF OVERRIDE,
AUTOMATIC OFF.
PROVIDE SINGLE (1) COVERPLATE. SIZE BASED ON
SWITCHES REQUIRED.
SEE PLANS FOR SPECIFIC QUANTITY AND LOCATION OF
SWITCH TYPES.
ON/OFF
S
ON/OFF
DOS
1.
BASIS OF DESIGN:
PROVIDE ACUITY #WSX-PDT-D-SA
1.
2.
SEQUENCE OF OPERATION:
ALL CONTROLS TO BE COMPLIANT WITH MICHIGAN
ENERGY CODE, BASED UPON ASHRAE 90.1, 2013.
MANUAL ON, LOCAL DIMMING AND ON/OFF OVERRIDE,
AUTOMATIC OFF.
APPROVED ALTERNATES:
S
1.
BASIS OF DESIGN:
PROVIDE ACUITY #WSX-PDT
OS
1.
2.
3.
SEQUENCE OF OPERATION:
ALL CONTROLS TO BE COMPLIANT WITH MICHIGAN
ENERGY CODE, BASED UPON ASHRAE 90.1, 2013.
MANUAL ON, ON/OFF OVERRIDE, AUTOMATIC OFF.
TOILETS AND STORAGE CLOSETS SHALL BE
AUTOMATIC ON/OFF.
APPROVED ALTERNATES:
1.
2.
3.
4.
APPROVED ALTERNATES:
HUBBELL
LUTRON
LEGRAND
LEVITON
S
ON/OFF
S
ON
OFF
STANDARD
SWITCH
D
DIMMER
SWITCH
ON/OFF ON/OFF
S D S D
DUAL DIMMER
SWITCH
ALL ON ON/OFF
S D S D
TRIPLE DIMMER
SWITCH
S D
ON/OFF ON/OFF
ALL OFF
1.
2.
3.
BASIS OF DESIGN:
ACUITY NLIGHT.
PROVIDE WIRED OR WIRELESS VERSIONS
BASED ON SPACE CONTROL SYSTEM.
PROVIDE WITH SINGLE COVERPLATE BASED
UPON SWITCH CONFIGURATION AND
EXISTING JUNCTION BOX SIZE.
D
CAT 5e
CABLE
(TYP.)
LIGHTING LOAD
(TYPICAL)
5 WALL OCC SENSOR DETAIL
SCALE: N.T.S.
6 DIMMABLE WALL OCC SENSOR DETAIL
SCALE: N.T.S.
1.
2.
3.
4.
HUBBELL
LUTRON
LEGRAND
LEVITON
1.
2.
3.
4.
HUBBELL
LUTRON
LEGRAND
LEVITON
1.
BASIS OF DESIGN:
PROVIDE ACUITY #WSX-PDT
APPROVED ALTERNATES:
1.
2.
3.
4.
HUBBELL
LUTRON
LEGRAND
LEVITON
1.
BASIS OF DESIGN:
PROVIDE ACUITY #WSX-PDT
APPROVED ALTERNATES:
1.
2.
3.
4.
HUBBELL
LUTRON
LEGRAND
LEVITON
7 SINGLE ZONE CEILING MOUNTED OCC SENSOR DETAIL
SCALE: N.T.S.
9 TYPICAL LIGHTING CONTROL LAYOUTS
SCALE: N.T.S.
8 DUAL ZONE CEILING MOUNTED OCC SENSOR DETAIL
SCALE: N.T.S.
POWER CIRCUIT
ROOM CONTROLLER POWER
PACKS (TYP. OF ALL)
ROOM CONTROLLER POWER
PACKS (TYP. OF ALL)
ROOM CONTROLLER POWER
PACKS (TYP. OF ALL)
ROOM CONTROLLER STYLE
CONTROLS (TYP. OF ALL)
ROOM CONTROLLER POWER
PACKS (TYP. OF ALL)
ROOM CONTROLLER POWER
PACKS (TYP. OF ALL)
J C
IS
D
T O
R R
A N
T C
E N
T E R
A D
D
IT
IO
N
S
R E N
O V A T
IO
N S
M A
T R
I X
E44
L
IG
H T
IN
G C
O N
T R
O L
D E T A
IL
S
ELECTRICAL KEY NOTES
CONTRACTOR SHALL REPLACE EXISTING 30A 3P BREAKER WITH NEW 50A 3P
BREAKER TO SERVE NEW ROOFTOP UNIT.
CONTRACTOR SHALL REPLACE EXISTING 50A 3P BREAKER WITH NEW 40A 3P
BREAKER TO SERVE NEW ROOFTOP UNIT.
LOAD SUMMARY
REMOVED LOAD: 14411W
ADDED LOAD: 6778W
NET LOAD: (7633)W
LOAD SUMMARY
REMOVED LOAD: 62623W
ADDED LOAD: 63342W
NET LOAD: 719W
J C
IS
D
T O
R R
A N
T C
E N
T E R
A D
D
IT
IO
N
S
R E N
O V A T
IO
N S
M A
T R
I X
E45
P A N
E L S
C H
E D
U L E S
E L E C
T R
IC
A
CONTRACTOR SHALL REPLACE EXISTING 20A 1P BREAKER WITH NEW 15A 1P
BREAKER TO SERVE NEW FURNACE.
CONTRACTOR SHALL REPLACE EXISTING 30A 3P BREAKER WITH (1) NEW 25A
2P BREAKER AND (1) NEW 20A 1P BREAKER TO SERVE NEW CONDENSING
UNIT.
2 2
LOAD SUMMARY
REMOVED LOAD: 21133W
ADDED LOAD: 7604W
NET LOAD: (135293)W
J C
IS
D
T O
R R
A N
T C
E N
T E R
A D
D
IT
IO
N
S
R E N
O V A T
IO
N S
M A
T R
I X
E46
P A N
E L S
C H
E D
U L E S
E L E C
T R
IC
BREAKER TO SERVE NEW FURNACE.
CONTRACTOR SHALL REPLACE EXISTING 30A 2P BREAKER WITH NEW 20A 2P
BREAKER TO SERVE NEW CONDENSING UNIT.
LOAD SUMMARY
REMOVED LOAD: 10566W
ADDED LOAD: 3052W
NET LOAD: (7514)W
J C
IS
D
T O
R R
A N
T C
E N
T E R
A D
D
IT
IO
N
S
R E N
O V A T
IO
N S
M A
T R
I X
E47
P A N
E L S
C H
E D
U L E S
E L E C
T R
IC
BREAKER TO SERVE NEW FURNACE.
LOAD SUMMARY
REMOVED LOAD: 6912W
ADDED LOAD: 3986W
NET LOAD: (2926)W
LOAD SUMMARY
REMOVED LOAD: 6912W
ADDED LOAD: 3986W
NET LOAD: (2926)W
J C
IS
D
T O
R R
A N
T C
E N
T E R
A D
D
IT
IO
N
S
R E N
O V A T
IO
N S
M A
T R
I X
E48
P A N
E L S
C H
E D
U L E S
E L E C
T R
IC
BREAKER TO SERVE NEW FURNACE.
LOAD SUMMARY
REMOVED LOAD: 6912W
ADDED LOAD: 3986W
NET LOAD: (2926)W
LOAD SUMMARY
REMOVED LOAD: 6912W
ADDED LOAD: 3986W
NET LOAD: (2926)W
J C
IS
D
T O
R R
A N
T C
E N
T E R
A D
D
IT
IO
N
S
R E N
O V A T
IO
N S
M A
T R
I X
E49
P A N
E L S
C H
E D
U L E S
E L E C
T R
IC
CONTRACTOR SHALL RELOCATE EXISTING BRANCH CIRCUIT TO NEW PANEL.
FORMER BREAKER LISTED ON EXISTING PANEL SCHEDULE. EXTEND
ASSOCIATED CONDUIT AND WIRE AS NEEDED.
CONTRACTOR SHALL INSTALL NEW 50A 3P BREAKER TO SERVE NEW
ROOFTOP UNIT.
CONTRACTOR SHALL INSTALL NEW 80A 3P BREAKER TO SERVE NEW TVSS.
J C
IS
D
T O
R R
A N
T C
E N
T E R
A D
D
IT
IO
N
S
R E N
O V A T
IO
N S
M A
T R
I X
E50
P A N
E L S
C H
E D
U L E S
E L E C
T R
IC
CONTRACTOR SHALL RELOCATE EXISTING BRANCH CIRCUIT TO NEW PANEL.
FORMER BREAKER LISTED ON EXISTING PANEL SCHEDULE. EXTEND
ASSOCIATED CONDUIT AND WIRE AS NEEDED.
J C
IS
D
T O
R R
A N
T C
E N
T E R
A D
D
IT
IO
N
S
R E N
O V A T
IO
N S
M A
T R
I X
E51
P A N
E L S
C H
E D
U L E S
E L E C
T R
IC
CONTRACTOR SHALL REPLACE EXISTING 30A 2P BREAKER WITH NEW 20A 2P
BREAKER TO SERVE NEW ELECTRIC CABINET UNIT HEATER.
CONTRACTOR SHALL INSTALL WITH NEW 20A 2P BREAKER TO SERVE NEW
ELECTRIC CABINET UNIT HEATER.
J C
IS
D
T O
R R
A N
T C
E N
T E R
A D
D
IT
IO
N
S
R E N
O V A T
IO
N S
M A
T R
I X
E52
P A N
E L S
C H
E D
U L E S
E L E C
T R
IC
CONTRACTOR TO VERIFY EXISTING BREAKER SIZE. SERVE NEW ROOFTOP
UNIT WITH 25A 2P BREAKER.
J C
IS
D
T O
R R
A N
T C
E N
T E R
A D
D
IT
IO
N
S
R E N
O V A T
IO
N S
M A
T R
I X
E53
P A N
E L S
C H
E D
U L E S
E L E C
T R
IC
CONTRACTOR SHALL REPLACE EXISTING 30A 2P BREAKER WITH NEW 20A 2P
BREAKER TO SERVE NEW MINI-SPLIT HEAT PUMP.
CONTRACTOR SHALL REPLACE EXISTING 20A 1P BREAKER WITH NEW 15A 1P
BREAKER TO SERVE NEW UNIT VENTILATOR.
CONTRACTOR SHALL REPLACE EXISTING 30A 3P BREAKER WITH (1) NEW 25A
2P BREAKER AND (1) NEW 20A 1P BREAKER TO SERVE NEW CONDENSING
UNIT..
4 CONTRACTOR SHALL REPLACE EXISTING 30A 3P BREAKER WITH (1) NEW 30A
2P BREAKER AND (1) NEW 20A 1P BREAKER TO SERVE NEW CONDENSING
UNIT.
J C
IS
D
T O
R R
A N
T C
E N
T E R
A D
D
IT
IO
N
S
R E N
O V A T
IO
N S
M A
T R
I X
E55
P A N
E L S
C H
E D
U L E S
E L E C
T R
IC
CONTRACTOR SHALL RELOCATE EXISTING BRANCH CIRCUIT FROM EXISTING
PANEL Q TO NEW PANEL R. FORMER BREAKER LISTED ON EXISTING PANEL
SCHEDULE. EXTEND ASSOCIATED CONDUIT AND WIRE AS NEEDED.
J C
IS
D
T O
R R
A N
T C
E N
T E R
A D
D
IT
IO
N
S
R E N
O V A T
IO
N S
M A
T R
I X
E56
P A N
E L S
C H
E D
U L E S
E L E C
T R
IC
BREAKER TO SERVE NEW UNIT VENTILATOR.
CONTRACTOR SHALL REPLACE EXISTING 30A 3P BREAKER WITH (1) NEW 25A
2P BREAKER AND (1) NEW 20A 1P BREAKER TO SERVE NEW CONDENSING
UNIT.
LOAD SUMMARY
REMOVED LOAD: 23057W
ADDED LOAD: 9357W
NET LOAD: (13700)W
LOAD SUMMARY
REMOVED LOAD: 21616W
ADDED LOAD: 12874W
NET LOAD: (8742)W
CONTRACTOR SHALL REPLACE EXISTING 20A 3P BREAKER WITH NEW 15A 3P
BREAKER TO SERVE NEW PUMP.
J C
IS
D
T O
R R
A N
T C
E N
T E R
A D
D
IT
IO
N
S
R E N
O V A T
IO
N S
M A
T R
I X
E57
P A N
E L S
C H
E D
U L E S
E L E C
T R
IC
J C
IS
D
T O
R R
A N
T C
E N
T E R
A D
D
IT
IO
N
S
R E N
O V A T
IO
N S
M A
T R
I X
E58
P A N
E L S
C H
E D
U L E S
E L E C
T R
IC
File details come from the government source that posted it. Updated .