Addendum 2 ITB-22-023-06 Telecommunications Wiring Belle Isle Library.pdf
PDF 48 KB Posted
- Attached to
- Telecommunications Wiring - Belle Isle Library
- Solicitation number
- 22-023-06
- Issued by
- Oklahoma County, Oklahoma City, Oklahoma
About this file
This document is Addendum Two to Invitation to Bid (ITB) 22-023-06 for Telecommunications Wiring at Belle Isle Library, issued by a local government entity in Oklahoma on October 11, 2021. The addendum corrects and clarifies specific requirements for fiber optic cabling installation, specifically noting that fiber needs to be 12-strand with 6 strands terminated and 6 strands left dark, to be pulled from the first floor data closet to the basement data closet using a provided 3-inch conduit.
The technical specifications for the fiber installation include requirements that the fiber be 50 micron, OM3 or OM4, with LC connections, and vendors must use UniCam connectors or fuse on a pigtail for termination. The addendum also specifies that while fiber is not required to be run in innerduct within the conduit, it must be protected by innerduct from the conduit to the rack. Vendors are required to sign, date, and return a copy of the addendum with their solicitation response to acknowledge receipt of these updated specifications.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Addendum to ITB 22-023-06 Telecommunications Wiring Belle Isle Library
Addendum Two (2) - Issued October 11, 2021
This addendum is a correction to Requirement a of Addendum 1. The fiber needs to be 12-strand (instead of 12-pair) with 6-strand terminated and 6 strand left dark. See below for correct requirements.
1. The library is adding to the project that fiber needs to be pulled from the data closet on the 1st floor to the data closet in the Basement using the 3” conduit provided as part of construction.
CORRECTED Requirements:
a) CORRECTION: Fiber needs to be 12-strand with 6-strand terminated and 6-strand left dark
b) Fiber is not required to be run in innerduct in the conduit but should be in innerduct from the conduit to the rack for protection.
c) Fiber is required to be 50 micron, OM3 or OM4, LC connection
d) Vendor must use UniCam connectors or fuse on a pigtail for termination
Sign, date, and return a copy of this addendum with your solicitation response to acknowledge receipt.
Vendor Company Name (Print)
Authorized Representative Name (Print)
Title
Authorized Representative Signature
Date
| Addendum to ITB 22-023-06 |
| Addendum Two (2) - Issued October 11, 2021 |
| CORRECTED Requirements: |
File details come from the government source that posted it. Updated .