ADDENDUM 1_REVISED SPECS_BANCROFT AE.pdf
PDF 1009 KB Posted
- Attached to
- Y1AZ--PROJECT 526-15-112 Renovate and Modernize E. R. Federal contract opportunity
- Solicitation number
- 36C242
About this file
This is an amendment to a solicitation for the renovation and modernization of the emergency room at the James J. Peters VA Medical Center in Bronx, New York under project number 526-15-112. The amendment provides clarifications to the scope of work, responses to requests for information, additional drawings for Arjo lifts, and a revised statement of work and bid pricing sheet that includes an add alternate for exterior canopy work. The bid date is extended to August 10, 2022 at 2:00 PM, with bids to be hand delivered and the bid opening held in person. Interested bidders must acknowledge this amendment and the revised documents and attachments in their submitted bids to be deemed responsive.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| RENOVATE AND MODERNIZE E.R._REVISED SOW AND BID PRICING SHEET WITH DRAWINGS AND PHOTOS.pdf | ||
| RENOVATE AND MODERNIZE E.R._SITE VISIT SIGN IN SHEET_7.7.2022.pdf | ||
| RENOVATE AND MODERNIZE E.R._COMPILED LIST OF RFI AND VA RESPONSES_REV 2 7.27.22.pdf | ||
| ADDENDUM 1_BAE_Arjo Installation Drawing.pdf | ||
| AMENDMENT 1_CANOPY SCOPE AND DRAWING.pdf | ||
| RENOVATE AND MODERNIZE ER_IFB 36C24222B0004_AMENDMENT 0001.docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
RENOVATE EMERGENCY ROOM JAMES J. PETERS VA MEDICAL CENTER
526-15-112 ADDENDUM NO. ONE/1
July 19, 2022
ADDENDUM NO. ONE TO THE BIDDING DOCUMENTS FOR:
Renovate Emergency Room
James J. Peters VA Medical Center 130 W Kingsbridge Road Bronx, NY 10468
TO ALL BIDDERS OF RECORD:
This addendum shall be a part of the Contract Documents and modifies the original Bidding Documents dated June 3, 2020 as follows. Acknowledge receipt of this addendum in the space provided on the Bid Form. Failure to acknowledge receipt of Addendum may subject Bidder to disqualification.
ITEM NO.
CHANGES TO PROJECT MANUAL
Section 13 05 41 Seismic Restraint Requirements for Non-Structural Components
1.1 Added section.
CHANGES TO DRAWINGS
Drawing AS101
1.2 Revised drawing to clarify scope of work for the replacement of the existing concrete walk.
ADDENDUM NO. ONE consists of <10 > pages and drawings.
END OF ADDENDUM NO. ONE
BANCROFT ARCHITECTS + ENGINEERS
3300 Dundee Road Northbrook, IL 60062
(847) 952-9362
Document1-BN
James J. Peters VA Medical Center
Bronx, New York
RENOVATE EMERGENCY ROOM
Bancroft Architects + Engineers
01-01-21
Contract No. VA242-17-C-0070
Station Project No. 526-15-112
Bancroft-AE Project No. 17-102 07/19/2022
13 05 41 - 1
SECTION 13 05 41
SEISMIC RESTRAINT REQUIREMENTS FOR NON-STRUCTURAL COMPONENTS
PART 1 - GENERAL
1.1 DESCRIPTION:
A. Provide seismic restraint in accordance with the requirements of the drawings, VA Handbook H18-8: Seismic Design Requirements and this specification in order to maintain the integrity of non-structural components and equipment of the building so that they remain safe and functional in case of seismic event.
B. The design of seismic restraints of non-structural components to resist seismic load shall be based on Seismic Design parameters indicated below in accordance with VA H-18-8 in conjunction with ASCE 7, as specified in H-18-8 Section 4.0, for existing building retrofit projects. Specific requirements for Critical and Essential facilities are covered in Section 4.0 of H-18-8, including applying Ip = 1.5 for all nonstructural components in Critical facilities.
1. International Building Code 2018 Edition
2. American Society of Civil Engineers Seismic Evaluation and Retrofit of Existing Buildings ASCE 41-17.
3. American Society of Civil Engineers Minimum Design Loads and
Associated Criteria for Buildings and Other Structures (ASCE 7).
4. Facility Occupancy Category per VA H-18-8: Essential Facility
5. Site Class: D
6. Building Risk Category: IV
7. Mapped MCER 0.2 s period Spectral Response Acceleration Parameter
(Ss): .362
8. Mapped MCER 1.0 s period Spectral Response Acceleration Parameter
(S1): .007
9. Short period Spectral Response Acceleration Parameter (Sds): .364
10. Short period Spectral Response Acceleration Parameter (Sd1): .113
11. Building Seismic Design Category: D
12. Component Importance Factor (Ip): 1.25
13. Component Response Modification Factor (Rp):
14. Component Overstrength Factor:
Station Project No. 526-15-112
Bancroft-AE Project No. 17-102 07/19/2022
13 05 41 - 2
C. Definitions: Non-structural building components are components or systems that are not part of the building’s structural system whether inside or outside, above or below grade. Non-structural components of buildings include but are not limited to (Refer to VA H-18-8, ASCE 7 and ASCE 41 for additional examples):
1. Architectural Elements: Facades that are not part of the structural system and its shear resistant elements; cornices and other architectural projections and parapets that do not function structurally; glazing; nonbearing partitions; suspended ceilings;
stairs isolated from the basic structure; cabinets; bookshelves;
medical equipment; and storage racks, etc.
2. Electrical Elements: Power and lighting systems; substations;
switchgear and switchboards; auxiliary engine-generator sets;
transfer switches; motor control centers; motor generators; selector and controller panels; fire protection and alarm systems; special life support systems; and telephone and communication systems, etc.
3. Mechanical Elements: Heating, ventilating, and air-conditioning systems; medical gas systems; plumbing systems; sprinkler systems;
pneumatic systems; boiler/chiller/utility plant/other equipment and components, etc.
4. Transportation Elements: Mechanical, electrical and structural elements for transport systems, i.e., elevators and dumbwaiters, including hoisting equipment and counterweights.
1.2 RELATED WORK:
Related specifications include but are not limited to those shown below.
Coordinate all work with the applicable specification for that work.
A. Cast-In-Place Concrete: Section 03 30 53, CAST-IN-PLACE CONCRETE
B. Structural Steel Framing: Section 05 12 00, STRUCTURAL STEEL FRAMING
C. Metal Fabrication: Section 05 50 00, METAL FABRICATIONS
D. Acoustical Ceilings: Section 09 51 00 ACOUSTICAL CEILINGS
E. Interior Lighting: Section 26 51 00, INTERIOR LIGHTING
1.3 QUALITY CONTROL:
A. Shop-Drawing Preparation:
1. Non-structural seismic restraint systems shop drawings and delegated design calculations shall be prepared by a professional structural
Station Project No. 526-15-112
Bancroft-AE Project No. 17-102 07/19/2022
13 05 41 - 3 engineer with a minimum of 5 years’ experience in the design and detailing of seismic force restraints. The professional structural engineer shall be registered in the state where the project is located and submit qualifications with list of projects illustrating compliance with the experience requirement of this section.
2. Submit design tables and information used for the design-force levels, stamped and signed by a professional structural engineer registered in the State where project is located.
B. Coordination:
1. Do not install seismic restraints until seismic restraint submittals are approved by the Contracting Officers Representative (COR).
2. Coordinate trapezes or other multi-pipe hanger systems prior to submission of shop drawings for review.
C. Seismic Certification:
In structures assigned to Seismic Design Category C, D, E, or F, permanent equipment and components are to have Special Seismic
Certification in accordance with requirements of section 13.2.2 of ASCE
7, including those required in existing buildings within Section
13.7.1.3.3, 13.7.7.3.3 and 13.7.8.3.3 of ASCE 41, except for equipment and components that are considered inherently rugged as listed in
Section 4.2.2 of VA H18-8, and shall comply with section 13.2.6 of ASCE
7.
1.4 SUBMITTALS:
A. Submit a complete and coordinated set of bracing and signed and sealed anchorage drawings and calculations for all non-structural elements requiring seismic restraint by the delegated professional structural engineer mentioned in Section 1.3.A.1 for review prior to installation including:
1. Description, layout, and location of all items to be anchored or braced with anchorage or brace points noted and dimensioned.
2. Details of all anchorage and bracing at large scale with all members, parts brackets shown, together with all connections, bolts, welds etc. clearly identified and specified. Details shall be coordinated with all project conditions and trades prior to shop drawing submission for review.
Station Project No. 526-15-112
Bancroft-AE Project No. 17-102 07/19/2022
13 05 41 - 4
3. Complete calculations including but not limited to seismic design criteria, computer model input and output, seismic design forces and capacities, design tables and information used for all proprietary design elements such as post installed anchors, stamped and signed by a professional structural engineer specified in section 1.3 A.1.
4. For all post installed anchorages submit the appropriate
International Code Council Engineering Service (ICC-ES) evaluation reports, California’s Office of Statewide Health Planning and
Development(OSHPD) pre-approvals, or lab test reports verifying compliance with OSHPD Interpretation of Regulations 28-6.
5. Delegated professional structural engineer qualifications.
B. Submit for review prior to installation, the following for seismic protection of piping in addition to items noted in Section 1.4.A:
1. Single-line piping diagrams on a floor-by-floor basis. Show all suspended piping for a given floor on the same plain.
2. Type of pipe (Copper, steel, cast iron, insulated, non-insulated, etc.).
3. Pipe contents.
4. Structural framing for the seismic and gravity support and the main superstructure for which the bracing and or anchorage is attached.
5. Location of all gravity load pipe supports and spacing requirements.
6. Numerical value of gravity load reactions.
7. Location of all seismic bracing.
8. Numerical value of applied seismic brace loads.
9. Type of connection (Vertical support, vertical support with seismic brace etc.).
10. Seismic brace reaction type (tension or compression): Details illustrating all support and bracing components, methods of connections, and specific anchors to be used.
C. Submit for review prior to installation, the following items for seismic protection of suspended ductwork and suspended electrical and communication cables, in addition to items noted in Section 1.4.A:
1. Details illustrating all support and bracing components, methods of connection, and specific anchors to be used.
2. Numerical value of applied gravity and seismic loads and seismic loads acting on support and bracing components.
Station Project No. 526-15-112
Bancroft-AE Project No. 17-102 07/19/2022
13 05 41 - 5
3. Maximum spacing of hangers and bracing.
1.5 APPLICABLE PUBLICATIONS:
A. The Publications listed below (including amendments, addenda revisions, supplements and errata) form a part of this specification to the extent referenced. The publications are referenced in text by basic designation only.
B. American Concrete Institute (ACI):
355.2-19................Qualification for Post-Installed Mechanical
Anchors in Concrete and Commentary
C. American Institute of Steel Construction (AISC):
Load and Resistance Factor Design, Volume 1, Second Edition
D. ASTM International (ASTM):
A36/A36M-19.............Standard Specification for Carbon Structural
Steel
A53/A53M-18.............Standard Specification for Pipe, Steel, Black and Hot-Dipped, Zinc-Coated, Welded and
Seamless
A307-14e1...............Standard Specifications for Carbon Steel Bolts, Studs, and Threaded Rod 60,000 PSI Tensile
Strength
A325-14.................Standard Specification for Structural Bolts, Steel, Heat Treated, 120/105 ksi Minimum
Tensile Strength
A325M-14................Standard Specification for High-Strength Bolts for Structural Steel Joints [Metric]
A490-14a................Standard Specification for Heat-Treated Steel
Structural Bolts, 150 ksi Minimum Tensile
Strength
A490M-14a...............Standard Specification for High-Strength Steel
Bolts, Classes 10.9 and 10.9.3, for Structural
Steel Joints [Metric]
A500/A500M-18...........Standard Specification for Cold-Formed Welded and Seamless Carbon Steel Structural Tubing in
Rounds and Shapes
Station Project No. 526-15-112
Bancroft-AE Project No. 17-102 07/19/2022
13 05 41 - 6
A501/A501M-14...........Standard Specification for Hot-Formed Welded and Seamless Carbon Steel Structural Tubing
A615/A615M-20...........Standard Specification for Deformed and Plain
Carbon Steel Bars for Concrete Reinforcement
A992/A992M-11(2015).....Standard Specification for Steel for Structural
Shapes for Use in Building Framing
A996/A996M-16...........Standard Specification for Rail Steel and Axle
Steel Deformed Bars for Concrete Reinforcement
E488/E488M-18...........Standard Test Methods for Strength of Anchors in Concrete Elements
E. American Society of Civil Engineers
1. Minimum Design Loads and Associated Criteria for Buildings and Other
Structures (ASCE 7) Edition as indicated in section 1.1 B of this specification. Associated Criteria for Buildings and Other
Structures (ASCE 7).
F. International Building Code (IBC) Edition as indicated in Section 1.1 B of this specification.
G. VA Handbook H18-8 Seismic Design Requirements, VA H-18-8, November
2019(REVISED MAY 1,2020)
H. National Uniform Seismic Installation Guidelines (NUSIG)
I. Sheet Metal and Air Conditioning Contractors National Association
J. (SMACNA): Seismic Restraint Manual - Guidelines for Mechanical Systems, 3RD EDITION 2008 and Addendum
1.6 REGULATORY REQUIREMENT:
A. IBC as shown in Section 1.1 B of this specification.
B. Exceptions: The omission of seismic restraints shall be allowed only in accordance with VA H18-8, ASCE 7.
PART 2 - PRODUCTS
2.1 STEEL:
A. Structural Steel: ASTM A36, A992.
B. Structural Tubing: ASTM A500, Grade B.
C. Structural Tubing: ASTM A501.
D. Steel Pipe: ASTM A53/A53M, Grade B.
E. Bolts & Nuts: ASTM A325 OR A490.
Station Project No. 526-15-112
Bancroft-AE Project No. 17-102 07/19/2022
13 05 41 - 7
2.2 CAST-IN-PLACE CONCRETE:
A. Concrete: 28 day strength, f’c = 27.5 MPa (4,000 psi)
B. Reinforcing Steel: ASTM A615/615M or ASTM A996/A996M deformed.
PART 3 - EXECUTION
3.1 CONSTRUCTION, GENERAL:
A. Provide equipment supports and anchoring devices to withstand the seismic design forces, so that when seismic design forces are applied, the equipment cannot displace, overturn, or become inoperable.
B. Provide anchorages in conformance with recommendations of the equipment manufacturer and as shown on approved shop drawings and calculations.
C. Construct seismic restraints and anchorage to allow for thermal expansion.
D. Testing Before Final Inspection:
1. Test 10-percent of anchors in masonry and concrete per ASTM E488, and ACI 355.2 to determine that they meet the required load capacity. If any anchor fails to meet the required load, test the next 20 consecutive anchors, which are required to have zero failure, before resuming the 10-percent testing frequency.
2. Before scheduling Final Inspection, submit a report on this testing indicating the number and location of testing, and what anchor-loads were obtained.
3. Construct seismic restraints and anchorages to not interfere with other trades or damage existing or in-situ elements of the constructed building.
3.2 EQUIPMENT RESTRAINT AND BRACING:
A. See drawings for equipment to be restrained or braced.
3.3 MECHANICAL DUCTWORK AND PIPING; ELECTRICAL BUSWAYS, CONDUITS, AND CABLE
TRAYS; AND TELECOMMUNICATION WIRES AND CABLE TRAYS
A. Support and brace mechanical ductwork and piping; electrical busways, conduits and cable trays; and telecommunication wires and cable trays including boiler plant stacks and breeching to resist directional forces (lateral, longitudinal and vertical).
B. Brace duct and breeching branches with a minimum of 1 brace per branch.
C. Provide supports and anchoring so that, upon application of seismic forces, piping remains fully connected as operable systems which will
Station Project No. 526-15-112
Bancroft-AE Project No. 17-102 07/19/2022
13 05 41 - 8 not displace sufficiently to damage adjacent or connecting equipment, or building members.
D. Piping Connections: Provide flexible connections where pipes connect to equipment. Make the connections capable of accommodating relative differential movements between the pipe and equipment under conditions of earthquake shaking.
3.4 PARTITIONS
A. In buildings with flexible structural frames, anchor partitions to only structural element, such as a floor slab, and separate such partition by a physical gap from all other structural elements.
B. Properly anchor masonry walls to the structure for restraint, so as to carry lateral loads imposed due to earthquake along with their own weight and other lateral forces.
3.5 CEILINGS AND LIGHTING FIXTURES
A. At intervals required to meet the seismic demand forces, laterally brace suspended ceilings against lateral and vertical movements, and provide with a physical separation at the walls.
B. Independently support and laterally brace all lighting fixtures. Refer to applicable portion of lighting specification, Section 26 51 00, INTERIOR LIGHTING.
3.6 FACADES AND GLAZING
A. Do not install concrete masonry unit filler walls in a manner that can restrain the lateral deflection of the building frame. Provide a gap with adequately sized resilient filler to separate the structural frame from the non-structural filler wall.
B. Tie brick veneers to a separate wall that is independent of the steel frame as shown on construction drawings to ensure strength against applicable seismic forces at the project location.
C. Install attachments to structure for all façade materials as shown on construction drawings to ensure strength against applicable seismic forces at the project location.
3.7 STORAGE RACKS, CABINETS, AND BOOKCASES
A. Install storage racks to withstand earthquake forces and anchored to the floor or laterally braced from the top to the structural elements.
B. Anchor medical supply cabinets to the floor or walls and equip them with properly engaged, lockable latches.
Station Project No. 526-15-112
Bancroft-AE Project No. 17-102 07/19/2022
13 05 41 - 9
C. Anchor filing cabinets that are more than 2 drawers high to the floor or walls, and equip all drawers with properly engaged, lockable latches.
D. Anchor bookcases that are more than 30 inches high to the floor or walls, and equip any doors with properly engaged, lockable latches.
- - - E N D - - -
36 32333435 31.9
E
31.832.5
E7
EXISTING CORRIDOR
EXISTING CONCRETE
CURB TO REMAIN
AMBULANCE
DROP OFF AREA
RAMP
RAMP
EXISTING TUNNEL BELOW
TOP OF TUNNEL = 171'-0"
1" SCORED OR
SAWCUT
CONTRACTION JOINT
CLASS B CONCRETE
1/4" RADIUS
FORMED JOINTS
ONLY
1/4" DEEP
SCORED JOINTS
EXPANSION JOINT WITH 1/4"
BITUMINOUS JOINT FILLER.
60' MAX. EXPANSION JOINT
TO EXPANSION JOINT.
4'
- 0
1' - 5" 4' - 0" 1' - 6"
1/2" EXPANSION JOINT. SEE
DETAIL THIS SHEET.
CONCRETE
SIDEWALK
CONCRETE CURB
TOP OF
CONCRETE
CURB
TOP OF EXISTING PAVEMENT
6"
TOP OF
PAVEMENT
SEAL WITH BEAD OF SILICONE SEALER
1/2" PREMOLDED JOINT FILLER ADJACENT TO
CONCRETE PAVEMENT OR SIDEWALK ONLY
6" X 6" W2.9 X W2.9
WELDED WIRE
FABRIC
6" AGGREGATE SUBBASE
SIDEWALK. CLASS B CONCRETE. F'c = 4,000 PSI
SLOPE 1% MIN. / 2% MAX.
EXISTING CURB
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
A
B
C
D
E
F
CONSULTANTS ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Drawing Title
Approved: Project Director
Phase Project Title Project Number
Building Number
Drawing Number
Location
Issue Date Checked Drawn
VA FORM 08-6231
CONSTRUCTION
DOCUMENTS / BID SET
VA CONTRACT NO: BAE PROJECT NO:
Revisions: Date: Page of
FULLY SPRINKLERED
C U s e rs \d b ib b s \D o c u m e n ts \5
-1 -1
J J P
V A
M C
E D
A
R C
H E
L E
C d e ta c h e d d b ib b s
X
R
.r v t
/1
/2
:1
:4
A
M
FLOOR AND CEILING PLAN - FIRST FLOOR
EXTERIOR
RENOVATE EMERGENCY ROOM
130 W KINGSBRIDGE ROAD, BRONX, NY 10468
6/3/2020 RR DTB
526-15-112
AS101
VA242-17-C-0070 17-102 127
N
1/4" = 1'-0"
FLOOR PLAN AT EXTERIOR CANOPY
SITE PLAN KEYNOTES
1 EXISTING 6" STEEL COLUMN TO REMAIN. PROTECT FOUNDATION.
2 REPLACE CONCRETE WALK AND RAMPS. PROVIDE EXPANSION AND CONTRACTION JOINTS AS
REQUIRED.
3 OUTLINE OF EXISTING CANOPY ABOVE TO REMAIN.
4 REPAIR HOLE IN CONCRETE.
0 2' 4' 8'
GENERAL NOTES
1. EXPANSION JOINTS SHALL BE LOCATED WHERE SIDEWALK ABUTS CONCRETE
DRIVEWAYS, CURB OR OTHER ADJACENT STRUCTURES.
2. ONE-HALF INCH BITUMINOUS JOINT FILLER SHALL BE INSTALLED AT EXPANSION JOINT
LOCATIONS AND SHALL EXTEND THE FULL DEPTH OF THE CONCRETE.
3. 1" DEEP CONTRACTION JOINTS SHALL BE PLACED AT INTERVALS OF APPROXIMATELY
15' OR AT A SPACING THAT MATCHES THE ADJACENT CURB.
4. FORMED CONTRACTION JOINTS SHALL BE FINISHED WITH A TOOL HAVING A 1/4"
RADIUS.
5. CONCRETE SHALL BE FINISHED BY MEANS OF A FLOAT, STEEL TROWELLED AND
BROOMED WITH A FINE BRUSH IN A TRANSVERSE DIRECTION.
6. 1/4" DEEP SCORED JOINTS (TYP) SPACED AT 6' OR EQUAL TO SIDEWALK WIDTH.
65% DESIGN DEVELOPMENT SUBMISSION AUG. 16, 2018
95% CONSTRUCTION DOCUMENTS SUBMISSION NOV. 18, 2018
100% CONSTRUCTION DOCUMENTS SUBMISSION JUNE 7, 2019
CONSTRUCTION DOCUMENTS / BID SET JUNE 3, 2020
ADDENDUM 1 JULY 19, 2022
3" = 1'-0"
DETAIL - EXPANSION AND CONTRACTION JOINTS
1/2" = 1'-0"
DETAIL - SIDEWALK RAMP
1 1/2" = 1'-0"
DETAIL - CONCRETE WALK
0 6" 9"3" 0 1' 2' 4' 0 1' 1 1/2'1/2'
File details come from the government source that posted it. Updated .