About this file

This document is an Addendum related to an Invitation for Bids for a state and local contract opportunity between the California Department of General Services Real Estate Services Division and the Department of State Hospitals for the Central Utility Plant Interconnect at the Metropolitan State Hospital in Norwalk, Los Angeles County, California (Project No. 13292).

The key details include the change in the bid due date from November 14, 2024 to November 21, 2024, and the bid opening date from November 15, 2024 to November 22, 2024. The scope of work involves the demolition of the existing 66kV outdoor substation and 12kV switchgear, and the installation of new 5kV switchgear, utility metering, battery, and other electrical equipment. The contractor must also provide a schedule for shutdowns that minimizes impacts to the hospital's operations. The project is a readvertisement of a previous project that did not receive any bids. The required contractor's license is a C-10 or B, and there are requirements for Disabled Veteran Business Enterprise (DVBE) participation.

View the file

Other files

File Type Posted
RFBI_4.pdf PDF
13292_-_RFBI_2.pdf PDF
RFBI_3.pdf PDF
13292_-_Pre_Bid_Sign_In_Sheets.pdf PDF
RFBI_5.pdf PDF
13292_-_Bid_Package_R3.pdf PDF
13292_-_Approved_Drawings_with_Issue_Date_R3.pdf PDF
13292_-_Project_Manual_Book_I.R3.pdf PDF
13292_-_RFBI_1.pdf PDF
13292_-_Project_Manual_Book_II_R3.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ADDENDUM NO. 1

RESDMSTR: 12/23/2021 00 91 13 - 1 of 2 000000000013292

STATE OF CALIFORNIA DEPARTMENT OF GENERAL SERVICES

REAL ESTATE SERVICES DIVISION

PROJECT MANAGEMENT AND DEVELOPMENT BRANCH

Date: November 8, 2024 DOCUMENT 00 91 13

ADDENDUM No. 1 TO THE CONTRACT DOCUMENTS

New Bid Due Date - November 21, 2024

CENTRAL UTILITY PLANT INTERCONNECT DSH – METROPOLITAN

DEPARTMENT OF STATE HOSPITALS

METROPOLITAN STATE HOSPITAL

11401 BLOOMFIELD AVE NORWALK, LOS ANGELES COUNTY, CALIFORNIA

PROJECT NO. 000000000013292

ACKNOWLEDGE RECEIPT OF THIS ADDENDUM ON BID FORM AND

REVISE THE CONTRACT DOCUMENTS AS FOLLOWS:

BIDDING REQUIREMENTS

1. DOCUMENT 00 11 00 - INVITATION TO BID

A. DELETE DOCUMENT 00 11 00 INVITATION TO BID AND

ADD DOCUMENT 00 11 00 Addendum 1 dated November 08, 2024 making the following changes:

CHANGE bid due date from November 14, 2024 to November 21, 2024.

CHANGE bid opening date from November 15, 2024 to November 22, 2024.

2. DOCUMENT 00 41 00 – BID FORM

A. CHANGE bid due date from November 14, 2024 to November 21, 2024.

Revised Bid Forms will not be issued to Bidders. Bidders shall change date on originally issued

Bid Forms.

DRAWINGS

ADD the following attached Addendum No. 1 Drawing Sheets, dated 11-08-24; showing revised minor scope changes.

1. SHEET T 1.0

ADD HCAI OSP NUMBBER AND HCAI/OSHPD LEVEL 5

DELETE The existing 66kV outdoor substation including all ancillaries.

ADDENDUM NO. 1

RESDMSTR: 12/23/2021 00 91 13 - 2 of 2 000000000013292

2. SHEETS T4.0

A. Updated scale.

B. Relocated manhole location.

3. SHEET E1.0

A. Overhead lines of 66kV and 12kV including poles are no longer part of this project.

It will be responsibility of SCE to demolish in separate contract.

B. Relocated manhole location

4. SHEET E1.1

DELETE Note: See E4.0, Detail 6

5. SHEET E1.2

B. Revised underground layout.

6. SHEET E1.3

B. Revised underground routing.

7. SHEETS E2.0

A. Relocated manhole location.

8. SHEET E4.0

DELETE Detail #5: 66kV/12kV Poles to be demolished by Southern California Edison DELETE Detail #5: 66kV Substation to be demolished by Southern California Edison

END OF ADDENDUM NO. 1

ATTACHMENTS:

Document 00 11 00, Invitation for Bids, pages 1 through 4.

Addendum No. 1 Drawing Sheets: T1.0, T4.0, E1.0, E1.1, E1.2, E1.3, E2.0, E4.0

INVITATION FOR BIDS

00 11 00 - 1

Addendum No. 1 – November 8, 2024

RESDMSTR: 05/01/2024 000000000013292

STATE OF CALIFORNIA

DEPARTMENT OF GENERAL SERVICES

REAL ESTATE SERVICES DIVISION

PROJECT MANAGEMENT AND DEVELOPMENT BRANCH

DOCUMENT 00 11 00

INVITATION FOR BIDS

SEALED BIDS: DGS will receive sealed bids at 707 Third Street, West Sacramento, California 95605, before 2:00 P.M., November 21, 2024. Bids received after this date/time will not be considered received on time.

A public bid opening will be held on November 22, 2024 at 2:00 P.M. at 707 Third Street, 5th floor reception area, West Sacramento, CA 95605. If bidders choose to attend the bid opening, to maintain proper social distancing, the bid opening may be held in the atrium. At the public bid opening, all bids received before 2:00 P.M., November 21, 2024 will be opened and recorded onto a Preliminary Bid Tabulation. Bidders do not need to attend the bid opening as the Preliminary Bid Tabulation will be made available immediately after the bid opening is completed and it will be emailed to invited bidders.

The bid opening may be attended virtually via the following link:

Teams Meeting Link: https://teams.microsoft.com/l/meetup-join/19%3ameeting_MzNlNTk5MTQtNDZmZC00NmQ2LTg2NTQtNTA5YzNmNjM5Yjlk%40thread.v2/0 ?context=%7b%22Tid%22%3a%22ea45f7b1-07d7-49a8-b8f5- 37136ec9382d%22%2c%22Oid%22%3a%223b64f837-4256-46bc-9349-e8174cd968a7%22%7d Teams Meeting ID: 267 375 199 918 Teams Passcode: DDNSVu

HAND DELIVERED BIDS: Shall be placed in the DGS/OBAS Bid/Proposal Drop Box located in the lobby at 707 3rd Street in West Sacramento. The Drop Box will be opened at 2:00 p.m. Tuesday through Thursday and bids/proposals in the box will be certified as being received before 2:00 p.m.

that day.

If mailing bids, ensure the outside of the mailing reads:

ATTENTION: HECTOR CAVAZOS

CENTRAL UTILITY PLANT INTERCONNECT DSH – METROPOLITAN

METROPOLITAN STATE HOSPITAL

NORWALK, LOS ANGELES COUNTY, CALIFORNIA

DO NOT OPEN

DEPARTMENT OF GENERAL SERVICES

OFFICE OF BUSINESS AND ACQUISTION SERVICES

707 3RD STREET, MS 508, WEST SACRAMENTO, CA 95605

The bids shall include all Work pursuant to the Drawings and Project Manual, and Addenda as may be issued prior to bid opening date.

Scope of Work: Major components of Project Work consist of demolition of existing 66kv outdoor substation including all ancillaries and the 12kv switchgear inside the co-generation plant. Provide new 5kv switchgear (with provision for future automation and controls) and utility metering section. Provide battery, battery charger, enclosure, and battery calculation. Provide from spare circuit breaker of new switchgear temporary power supply to feed the existing “MCC-A” located in Co-Gen Building while the new feed is in construction. Provide new equipment pad for Southern California Edison equipment and new 5kv switchgear equipment, including underground conduit. Demolish the existing Transformer “A” https://teams.microsoft.com/l/meetup-join/19%3ameeting_MzNlNTk5MTQtNDZmZC00NmQ2LTg2NTQtNTA5YzNmNjM5Yjlk%40thread.v2/0?context=%7b%22Tid%22%3a%22ea45f7b1-07d7-49a8-b8f5-37136ec9382d%22%2c%22Oid%22%3a%223b64f837-4256-46bc-9349-e8174cd968a7%22%7d https://teams.microsoft.com/l/meetup-join/19%3ameeting_MzNlNTk5MTQtNDZmZC00NmQ2LTg2NTQtNTA5YzNmNjM5Yjlk%40thread.v2/0?context=%7b%22Tid%22%3a%22ea45f7b1-07d7-49a8-b8f5-37136ec9382d%22%2c%22Oid%22%3a%223b64f837-4256-46bc-9349-e8174cd968a7%22%7d https://teams.microsoft.com/l/meetup-join/19%3ameeting_MzNlNTk5MTQtNDZmZC00NmQ2LTg2NTQtNTA5YzNmNjM5Yjlk%40thread.v2/0?context=%7b%22Tid%22%3a%22ea45f7b1-07d7-49a8-b8f5-37136ec9382d%22%2c%22Oid%22%3a%223b64f837-4256-46bc-9349-e8174cd968a7%22%7d https://teams.microsoft.com/l/meetup-join/19%3ameeting_MzNlNTk5MTQtNDZmZC00NmQ2LTg2NTQtNTA5YzNmNjM5Yjlk%40thread.v2/0?context=%7b%22Tid%22%3a%22ea45f7b1-07d7-49a8-b8f5-37136ec9382d%22%2c%22Oid%22%3a%223b64f837-4256-46bc-9349-e8174cd968a7%22%7d

00 11 00 - 2 located outdoor and intercept the pathway and provide new 5kv conductor to re-feed the existing 5kv “MCC-A”. Provide methods and schedule of shutdown to DSH – Metropolitan State Hospital (MSH) for approval. The schedule of shutdown shall have minimal impact to the operation of the facility.

Readvertisement: This is a readvertisement of a Project for which no bids were opened on September 6, 2024 and no contract was awarded. No revisions were made to scope of original work and Drawings and Project Manual, including Addenda, remain same as originally issued with exception of new bid opening date. New Bid Forms will be posted to the Event Details in the Cal eProcure website.

License: Contractors' State License Classification required to bid Project is C-10 or B.

Certificate of Reported Compliance (CRC) – Fleet Vehicles: As a condition of Contract award, prior to Contract execution, Contractor shall submit copies of the valid CRCs for any fleet retained by the Contractor or any listed Subcontractor, for which any vehicles subject to the California Air Resources Board In-Use Off-Road Diesel Fueled Fleet Regulations, Section 2449(i), Title 12, California Code of Regulations, are used in the completion of the work included in the Contract.

More information on the In-Use Off-Road Diesel-Fueled Fleets Regulation can be found at the following link: https://ww2.arb.ca.gov/our-work/programs/use-road-diesel-fueled-fleets-regulation

Generative Artificial Intelligence (GenAI) Disclosure: The State of California seeks to realize the potential benefits of Generative Artificial Intelligence through the development and deployment of GenAI tools, while balancing the risks of these new technologies. Bidders must notify the State in writing if their solution or service includes, or makes available, any GenAI technology, including GenAI from third parties or subcontractors. The State has developed a form STD 1000 GenAI Disclosure & Factsheet to be completed by the Bidder. Failure to disclose GenAI to the State and submit the form STD 1000 GenAI Disclosure & Factsheet will result in disqualification of the Bidder and may void any resulting contract. The State reserves its right to seek any and all relief it may be entitled to as a result of such non-disclosure. Upon receipt of a Bidder GenAI Disclosure & Factsheet, the State reserves the right to incorporate GenAI Special Provisions into the final contract or reject bids that present an unacceptable level of risk to the State.

Generative Artificial Intelligence (GenAI) Disclosure & Factsheet (STD 1000) can be viewed and downloaded at the following internet site: https://www.documents.dgs.ca.gov/dgs/fmc/pdf/std1000.pdf

Completed form STD 1000 Generative Artificial Intelligence (GenAI) Disclosure & Factsheet must be included in the bid submission, as part of Project Manual Document 00 41 00 “Bid Form”. If the GenAI Disclosure & Factsheet is not submitted by the bidder, the bid shall be deemed nonresponsive.

DOJ Custodian of Record (COR) Requirement: As a condition of Contract award, at the time of Contract award Contractor is required to furnish to State evidence that the Contractor’s organization has a Department of Justice (DOJ)-confirmed Custodian of Records (COR) for background checks.

Alternatively, at the time of award the Contractor may furnish to State evidence or proof of mailing (via USPS Registered Mail or tracking information) that Contractor submitted an application for processing to DOJ to obtain a COR in accordance with DOJ requirements.

For bidders without a DOJ-Confirmed Custodian of Record at the time of Contract award but who provide evidence of a submitted application at the time of Contract award, an allowance of 30 calendar days from NTP shall be included in the baseline schedule for processing of the Contractor’s Custodian of Record and completion of onsite construction staff background checks (FBI and/or DOJ). State shall not be responsible for any Contractor costs caused by any delays in establishing a Custodian of Record.

Information regarding Custodian of Records program is available at https://oag.ca.gov/fingerprints/custodian https://ww2.arb.ca.gov/our-work/programs/use-road-diesel-fueled-fleets-regulation https://www.documents.dgs.ca.gov/dgs/fmc/pdf/std1000.pdf https://oag.ca.gov/fingerprints/custodian

00 11 00 - 3

Availability of Funds: Award of this contract is subject to the availability of funds through the State’s normal budget process and/or transfer of funds to the Department of General Services through the Architecture Revolving Fund.

Pre-bid Site Inspection: Bids will only be accepted from those Contractors having attended the MANDATORY pre-bid site inspection tour on October 16, 2024, at 10:00 A.M, at which time representatives of the State and prospective bidders shall meet at Metropolitan State Hospital, 11401 Bloomfield Ave. Norwalk, CA. 90650, at area of work (East of Balsam St. and Fifth St. intersection). The State’s requirements for Disabled Veteran Business Enterprise (DVBE) participation and other Contract requirements will be presented. Prime Contractors are encouraged to have their Key Administrator and DVBE office coordinator attend to receive this information and to have their questions answered.

Attendance for the entire inspection is required in order for new bidders to be eligible to submit a bid. Previous potential bidders who attended the two previous pre-bid walks and who provide proof of attendance are not required to attend this October 16, 2024 pre-bid walk in order to bid.

Executive Order N-6-22: The Bidder must be advised of Executive Order N-6-22 Russia Sanctions. On March 4, 2022, Governor Gavin Newsom issued Executive Order (EO) N-6-22 regarding Economic Sanctions against Russia and Russian entities and individuals. “Economic Sanctions” refers to sanctions imposed by the U.S. government in response to Russia’s actions in Ukraine, as well as any sanctions imposed under state law. By submitting a bid, Bidder represents that it is not a target of Economic Sanctions. Should the State determine Bidder is a target of Economic Sanctions or is conducting prohibited transactions with sanctioned individuals or entities, that shall be grounds for rejection of the Bidder’s bid any time prior to contract execution, or, if determined after contract execution, shall be grounds for termination by the State.

Drawings and Project Manual: Bid forms, plans, specifications, and addenda will be available for download at http://www.caleprocure.ca.gov/. Click on “Start Search.” In the Event name field, enter the project number and click search. While viewing the Event Details, click on “View Event Package” to view bid forms.

It is recommended that all vendors register as a bidder through the Cal eProcure website at https://www.caleprocure.ca.gov/pages/bidder-vendor.aspx. This will allow for automatic notifications if there is any modification to the Event such as the posting of an addendum or additional documentation.

Drawings and Project Manual may also be viewed through Builders' Exchanges.

Bid: Submit on lump sum basis with Allowances as set forth in Bid Forms.

DVBE: Participation in Disabled Veterans Business Enterprises (DVBE) program may be required for this project. Refer to Project Manual Document 00 21 00, Project Manual Document 00 22 10 and Bid Forms for requirements. Bidders are advised to commence the required DVBE procedures immediately upon receipt of drawings and project manual.

DVBE Bid Incentive: The DVBE Incentive program is being applied on this project. Refer to Project Manual Document 00 21 00, Article 18.5.

Small Business Preference: Refer to Project Manual Document 00 21 00, Article 5.5

Non-Small Business Subcontractor Preference: Refer to Project Manual Document 00 21 00, Article 5.6 http://www.caleprocure.ca.gov/ https://www.caleprocure.ca.gov/pages/bidder-vendor.aspx

00 11 00 - 4

Bonds: Successful bidder shall furnish payment and performance bonds, each in the amount of 100 percent of the Contract price.

Non-Discrimination Program (Gov. Code, Section 12990): Refer to Project Manual Document 00 72 00, General Conditions of the Contract for Construction.

Labor Code: Pursuant to Labor Code, Section 1774, the Contractor to whom the contract is awarded, and any subcontractor under him, shall pay not less than the specified general prevailing rates of per diem to all workers employed in the execution of the contract. Pursuant to Labor Code, Section 1770 et seq., the Department of Industrial Relations (DIR) has ascertained general prevailing rate of per diem wages in the locality in which the work is to be performed. Copies of the general prevailing rate of per diem wages are available from the Department of Industrial Relations, Labor Statistics & Research Division, P.O. Box 420603, San Francisco, CA 94142, (415) 703-4780; or general prevailing rate of per diem may be accessed on the internet at Department of Industrial Relations website (https://www.dir.ca.gov) for the August 2024 published general prevailing rate of per diem wages for this contract. Copies of the general prevailing rate of per diem wages are on file at DGS’ principal office, which shall be made available to any interested party on request. Note that when the general prevailing rate of per diem determination shows an expiration date (noted by a double asterisk**), to expire during the term of the contract, the Contractor must call or write the DIR to obtain the new rates and incorporate them in this contract for submittal of bid. The Contractor is responsible to comply with the Labor Code Sections and general prevailing rate of per diem determinations, including all the guidelines and the fine print in the general prevailing rate of per diem determinations. Refer to Project Manual Document 00 72 00, General Conditions of the Contract for Construction.

Labor Compliance Monitoring and Enforcement: This project is subject to monitoring and enforcement by the Department of Industrial Relations (DIR), Compliance Monitoring Unit. All Contractors and subcontractors, regardless of tier, shall be required to comply with the Monitoring and Enforcement Program, including, but not limited to, contractor registration, submittal of electronic certified payroll reports directly to the DIR as applicable and cooperation with on-site monitoring by DIR personnel. Refer to Labor Code 1771.4 et seq. and the General Conditions of the Contract for Construction, Document 00 72 00, Article 3.3.3 for more information.

END OF DOCUMENT

https://www.dir.ca.gov/

11401 BLOOMFIELD AVENUE, NORWALK, CALIFORNIA 90650

PROJECT ADDRESS :

PREPARED FOR:

DEPARTMENT OF STATE HOSPITALS

DEMOLISH 12KV SWITCHGEAR INSIDE THE CO-GENERATION PLANT.

PROVIDE NEW 5KV SWITCHGEAR AND UTILITY METERING SECTION. NEW 5KV

SWITCHGEAR SHALL HAVE PROVISION FOR FUTURE AUTOMATION AND CONTROLS.

PROVIDE BATTERY, BATTERY CHARGER, ENCLOSURE, AND BATTERY

CALCULATION.

PROVIDE FROM SPARE CIRCUIT BREAKER OF NEW SWITCHGEAR TEMPORARY

POWER SUPPLY TO FEED THE EXISTING "MCC-A" LOCATED IN CO-GEN BUILDING

WHILE THE NEW FEED IS ON CONSTRUCTION.

PROVIDE EQUIPMENT PAD FOR SCE EQUIPMENT AND NEW 5KV SWITCHGEAR

EQUIPMENT, AND UNDERGROUND CONDUIT.

DEMOLISH THE EXISTING TRANSFORMER "A" LOCATED OUTDOOR AND INTERCEPT

THE EXISTING PATHWAY AND PROVIDE NEW 5KV CONDUCTOR TO RE-FEED THE

EXISTING 5KV "MCC-A".

PROVIDE METHODS AND SCHEDULE OF SHUTDOWN TO DSH- METROPOLITAN

STATE HOSPITAL (MSH) FOR APPROVAL. THE SCHEDULE OF SHUTDOWN SHALL

HAVE MINIMAL IMPACT TO THE OPERATION OF THE FACILITY.

1. 2022 BUILDING STANDARDS ADMINISTRATIVE CODE, TITLE 24 C.C.R.

2. 2022 CALIFORNIA BUILDING CODE (CBC), PART 2, TITLE 24 C.C.R.

3. 2022 CALIFORNIA ELECTRICAL CODE (CEC), PART 3, TITLE 24 C.C.R.

4. 2022 CALIFORNIA MECHANICAL CODE (CMC), PART 4, TITLE 24 C.C.R.

5. 2022 CALIFORNIA PLUMBING CODE (CPC), PART 5, TITLE 24 C.C.R.

6. 2022 CALIFORNIA ENERGY CODE (CEC), PART 6, TITLE 24 C.C.R.

7. 2022 CALIFORNIA FIRE CODE, PART 9, TITLE 24 C.C.R.

8. 2022 CALIFORNIA GREEN BUILDING STANDARDS CODE (CALGREEN), PART 11,

TITLE 24 C.C.R.

9. 2022 CALIFORNIA REFERENCED STANDARDS, PART 12, TITLE 24 C.C.R.

10. TITLE 19 C.C.R., PUBLIC SAFETY, STATE FIRE MARSHAL REGULATIONS.

11. HCAI/OSHPD LEVEL 5 - ACUTE PSYCHIATRIC HOSPITAL

N N

NOT TO SCALEN NOT TO SCALE

NOT TO SCALE

Imperial Hwy

NORWALK

Bloom field Ave

Norwalk Blvd

Telegraph Rd.

Studebaker Rd

Florence Ave. Telegraph Rd.

Rosecrans Ave.

SANTA ANA FW

Y N

Pioneer Blvd

G reenstone Ave

Firestone Blvd

NORWALK

STA FE

SPRING

WHITTIERBELL

DOWNEY

BELLFLOWER

GARDENS

PROJECT

LOCATION

PROJECT

LOCATION

SCOPE OF WORKAPPLICABLE CODES

SITE MAP

PROJECT INFORMATION

LOCATION MAP VICINITY MAP

DSH - METROPOLITAN

CUP INTERCONNECT - CENTRAL PLANT

PROJECT LOCATION

Checked

Vault File Number

Project Number

Reference North Sheet Scale

Sheet Number

Designed

Sheet Title

Supervisor

Issue Date

Drawn

Project

No.

JCCA #: 23793-5

00000000000XXXX

METROPOLITAN STATE HOSPITAL

11401 BLOOMFIELD AVENUE

NORWALK, CALIFORNIA 90650

DEPARTMENT OF

STATE HOSPITALS

(DSH)

AS SHOWN

DSA STAMP

DSH-M CUP

INTERCONNECT

DSH

01/12/2024

SA

FI

LE

: L :\2

3\

3-

C U

P In te rc on ne ct , D

SH

-M

\C

AD

\2

5_

T1

C O

VE

R

S H

EE

T

- C

EN

TR

AL

P

LA

N T

- 2

4-

-0 8.

dw g

D

AT

E/

TI

M E:

N ov

4, 3:

PM

JCCA

V2 PLAN CHECK SUBMITTAL

Client Agency

DEPARTMENT OF STATE HOSPITALS

385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501

P: 310.212.7644 F:310.212.5272I

HJL ZML RN

Issue Date Description

PROJECT SUMMARY

THE PROJECT CONSISTS OF THE INSTALLATION OF AN ELECTRICAL INTERCONNECT

TO PROVIDE POWER TO CENTRAL UTILITY PLANT (CUP). THE CUP CURRENTLY

UTILIZES A 66KV SUPPLY FROM SOUTHERN CALIFORNIA EDISON. DSH RECENTLY

ACQUIRED THE CUP FROM PREVIOUS LEASE AND IS OPERATING THE CUP ON A

LIMITED BASIS. DSH-METROPOLITAN DOES NOT PLAN TO GENERATING ELECTRICITY

NOR SEND POWER TO THE GRID, THERE IS NO LONGER ANY NEED FOR THE 66KV

SUPPLY NOR SOUTHERN CALIFORNIA EDISON SIGGEN SUBSTATION.

DEPARTMENT OF STATE HOSPITALS

11401 South Bloomfield Avenue Norwalk, California 90650

JOSHUA KAISER

Chief Construction Officer

(916) 248-0015 Email: joshua.kaiser@dsh.ca.gov.

BRIAN HUDSON

DSH Overall CM Lead

(682) 777-0906 Email: Brian.Hudson@dsh.ca.gov.

ALEX VAN ELDEN

(949) 391-5066 Email: Alexander.VanElden@dsh.ca.gov.

METROPOLITAN STATE HOSPITAL

11401 BLOOMFIELD AVENUE, NORWALK,

CALIFORNIA 90650 LOS ANGELES COUNTY

TITLE SHEET,

APPLICABLE CODES

AND SCOPE OF WORK

T1.0

OSFM PERMIT#: 23-6278

HCAI COMPLIANCE

NEW EQUIPMENT SHALL COMPLY WITH HCAI REQUIREMENT.

METAL CLAD SWITCHGEAR OSP-0046

METAL ENCLOSED SWITCHGEAR OSP-0037

BATTERY CHARGER OSP-0131

BATTERY RACK OSP-0264

PANG HER

Assoc. Construction Analyst

(916) 915-8293 Email: Pang.Her@dsh.ca.gov.

PAUL SMITH

Chief of Plant Operations

(562) 651-4376 EXT. 8094

Cell: (562) 292-4755 Email: Paul.Smith@dsh.ca.gov.

NATALIE GARCIA

Assistant Hospital Administrator

(562) 521-1417 Main Office: (562) 651-4376 Email: Natalie.Garcia@dsh.ca.gov.

J.C. Chang & Associates, Inc. Engineers, Architects and Planners 385 Van Ness Way, Suite 208 Torrance, California 90501

(310) 212-7644

PREPARED BY:

(REFER TO OSFM PERMIT#: 24-0864 FOR SWITCHGEAR BUILDING)

1 11/08/24 ADDENDUM #1

l l

EXISTING CONCRETE SLAB OVER

UNDERGROUND #2 FUEL OIL

STORAGE TANK

TRANSFORMER

PIPE

BRIDGE

(E) MANHOLE "MHAA"

(E) CHW SUPPLY AND RETURN

PIPING AND FUEL PIPE

BOLLARD

(TYP)

(E)TUNNEL EXHAUST FAN TO REMAIN

30' TYP.4.7

4.4

101F

102F

107J-A

107J-B

6J

-A

DRAINAGE

SUMP WITH

PUMP

104L A&B

104LJ2 A&B 104LJ1 A&B

112J

104F 103F

109-J

105F

105F

ADMINISTRATION,

MAINTENANCE, &

CONTROL ROOM

BLOCK

106L-B

106L-A

LUBE OIL

COOLER

6J

-B

HYDRAULIC

STARTER

SKID

110J A&B

110JD1

110JL1

TURBINE

LUBE OIL

COOLER

SKID

101L

120J-A

120J-B

119J-A 119J-B

101D

111L-C

CHILLER

WASTER WATER CLARIFIER

101J-A&B

101JD1

101JD2

111L-A

MOTOR

111L-B

MOTOR CHILLER SHELL

103J

105J-B

105J-ALUBE OIL

CONSOLE

SPACE RESERVED FOR SWITCHGEAR

101L

FLUE GAS

ANALYZER PANEL

EJECTOR, GLAND CONDENSER,

EXTRACTION VALVE PLATFORM

OIL

RETURN

101LD3

101LD2

101LD1

102D 104J-B

104J-A

105LJ1

105LF1

105LJ2

105LF2

105LJ3

105LF3

101C

BALSAM STREET

30' TYP.

' T

YP

. 1

' T

YP

105'-7"

32'-9"

35'

'-9

'-1

32'-3"

FUTURE

ABOVEGROUND

TANK

FUEL

POLISHER

FUTURE

DAYTANK

FUTURE

2,500KW

FUTURE

NGR NGR

FUTURE SWITCHGEAR

WITH MASTER

CONTROLLER

FUTURE GENERATOR

AREA NOT PART OF THIS

CONTRACT

BOLLARD

(TYP)

SCALE

CUP BUILDING CODE ANALYSES FLOOR PLAN

TRUE

NORTH

PLAN

NORTH1

Checked

Vault File Number

Project Number

Reference North Sheet Scale

Sheet Number

Designed

Sheet Title

Supervisor

Issue Date

Drawn

Project

No.

JCCA #: 23793-5

00000000000XXXX

METROPOLITAN STATE HOSPITAL

11401 BLOOMFIELD AVENUE

NORWALK, CALIFORNIA 90650

DEPARTMENT OF

STATE HOSPITALS

(DSH)

AS SHOWN

DSA STAMP

DSH-M CUP

INTERCONNECT

DSH

01/12/2024

SA

FI

LE

: L :\2

3\

3-

C U

P In te rc on ne ct , D

SH

-M

\C

AD

\2

5_

T4

C O

-G

EN

B U

IL

D

IN

G

C O

D E

AN

AL

YS

IS

.d w g D

AT

E/

TI

M

E:

N ov

4, 1:

AM

JCCA

V2 PLAN CHECK SUBMITTAL

Client Agency

DEPARTMENT OF STATE HOSPITALS

385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501

P: 310.212.7644 F:310.212.5272I

HJL ZML RN

Issue Date Description

CODE ANALYSES CUP BUILDING:

EXISTING BUILDING TYPE: II-B (8" CMU BLOCK WALLS WITH STEEL DECK/ROOF)

OCCUPANCY: F-1 OCCUPANCY

HEIGHT: EXISTING 46' AFG

SPRINKLERED: YES

NUMBER OF STORIES: 1

AREA: F-1 OCC = 19,147 SF (1ST LEVEL)

AREA: B OCC = 2,260 SF (2ND LEVEL)

PER CHAPTER 5 CBC

II-B/F-1 OCC SPRINKLERED 62,000 SF ALLOWED > 19,147 SF OK

II-B/F-1 OCC SPRINKLERED 92,000 SF ALLOWED > 2,260 SF OK

II-B/B AND F-1 OCC SPRINKLERED 3 STORIES (75 FEET) ALLOWED > 1 STORY (46 FEET) OK

PER CHAPTER 6 CBC

II-B BEARING WALL: 0 RATING REQUIRED = OK

II-B INTERIOR WALLS AND, ROOF 0 RATING REQUIRED = OK

II-B/F-1 OCCUPANCY DISTANCE TO FIRE SEPARATION BETWEEN 10 FEET AND

30 FEET = 0 RATING = OK

1. CLOSEST IMAGINARY PL IS 15 FT.

CODE ANALYSES CONT:

PER CHAPTER 10 CBC

FUNCTION OF SPACE: MECH/ELECTRICAL ROOM OL = 78

1. OCCUPANCY F-1 = 19147/300 = 63 PER PLAN. B OCCUPANCY = 2260/150 = 15 OCC

2. 63 > 49 OCC. TWO EXIT DOOR REQUIRED WITH PANIC HARDWARE (5 DOORS PROVIDED)

3. 15 OCC < 49 HOWEVER, OFFICE ON 2ND FLOOR THEREFORE TWO EXITS REQUIRED (2 EXITS PROVIDED)

4. F-1 OCC W/ SPRINKLER SYSTEM MAX.100 FT TO EXIT ACCESS. EXIT ACCESS < 250 FT = OK

5. B OCC W/ SPRINKLER SYSTEM 30 FT TO EXIT ACCESS. EXIT ACCESS < 300 FT = OK.

FIRE SEPERATION DISTANCE LINE

CODE ANALYSIS NOTES:

30 FEET FIRE SEPARATION DISTANCE UNLESS NOTED

OTHERWISE.

IM

P

E R

IA

L

H W

Y

BLOOMFIELD AVENUEBLOOMFIELD AVENUE

10,274 10,274

9,0009,000

9,371 9,371

2,695 2,439

10,501

8,200

7,933

8,977

8,977

7,933

8,200

10,501

10,501

8,200

7,933

8,97710,501

8,200

7,933

8,977

17,235

17,235 17,235

17,235

NORWALK BOULEVARD

80 Stalls

St al ls

18 Stalls

58 Stalls

S ta lls

S ta lls

101102

408/416

406/414

402/410

417 419

418 420

CTW

BLDG.

A

A

BLDG.

S.N.F.

404/412

KEY PLAN

SCALE:N.T.S.

EXIT PATH < 250'

NOTE:

THIS IS SHOWN FOR REFERENCE ONLY. NO

CHANGE IS PROPOSED FOR BUILDING LOCATION OR

EXISTING FIRE SEPARATION DISTANCE.

LEGEND:

CUP BUILDING

CODE ANALYSES

FLOOR PLAN

T4.0

0 5 10 15 FEET 30

1" = 15'

OH OH OH OH OH OH

OH

O H

66KV 66KV 66KV 66KV 66KV 66KV

12KV

66KV

12KV

12KV

TO BE DEMOLISHED BY SOUTHERN CALIFORNIA

EDISON (SCE) INCLUDING POLES.

(E) 12KV OVERHEAD LINE

TO REMAIN

(D)66KV POLE

O H

OH

O H

OH

O H

O H

OH

IM

P

E R

IA

L

H W

Y

BLOOMFIELD AVENUEBLOOMFIELD AVENUE

COGENERATIONCO-GEN.

TRANSPORTATIONTRANS.

VOCATIONAL REHABILITATION

HOUSEKEEPING

ADMINISTRATION

OFFICE OF STATE ARCHITECT

GARAGE

RESIDENCE NUMBER

EMPLOYEE

BUILDING

OCCUPATIONAL THERAPY

WAREHOUSE

SHELTER

VOC. REHAB.

HSEKP.

ADMIN.

OSA

G R#

EMP.

BLDG.

O.T.

W S

ABBREVIATIONS & SYMBOLS

PATIENT SUPPORT MODULESP.S.M.

10,274 10,274

9,0009,000

9,371 9,371

2,695 2,439

10,501

8,200

7,933

8,977

8,977

7,933

8,200

10,501

10,501

8,200

7,933

8,97710,501

8,200

7,933

8,977

17,235

17,235 17,235

17,235

(Lower)

WATER TANKS

IRRIGATION PUMP HOUSE

WATER SOFTENER BUILDING DOMESTIC PUMP HOUSE

DEVICE

BACKFLOW

COMMINUTOR

BUILDING

CTE CHILLER

P.S.M.

COURT

TENNIS

DOM.IRR.

M

ET

AL

PRO

PERTY LIN

E

PR

O

PE

RT

Y

LI

N E

PROPERTY LINE

FD. SERV. WHSE.

LUMBER SHED

GAS PUMP

EN

GI

N.

S

SS

S

S

S

DC

U

TRANS.

GA

RA

GE

PLUMBER

OFFICES

PLANT OP'S.

RECEIVING

STORES /

CAR PORT

CARPENTER

PA

IN

T

MASON

ST

OR

SH

EE

T

EL

EC

T.

W

EL

D.

O .T

O .T

O.T. SOUTH

O.T. NORTH

EM

P.

B

LD

G.

EMP. BLDG. 3

RE

CY

CL

IN

G

S

S

G

#18

G

#19

#16

G

#14

#13

313/315

G

G

EM

P.

B

LD

G.

EMP. BLDG. 1

#1

#15S

LA

UN

DR

Y

KITCHEN

OFFICE

TRUST

S

201/203

2/2

5/2

0/2

9/2

3/2

STORAGE

CHILL WATERBARBER/

W3

COOLING TOWER

#6

#8#7

HSEKP.WHSE 1

PROPERTY

HALL

JAMES

306-308

HOUSE

BOILER

E1

309-311 (CPS)

W2NORTH YARD

PCB SHED

HOMES

#10

G

G

G

#11

#12

#20

PUMP HOUSE

(ABANDONED)

CO

ND

OM

IN

IU

M

CO

M

PL

EX

FASHION CNT.

STORAGE

PROPERTY LINE

PROPERTY LINE

PR

O

PE

RT

Y

LI

N E

PROPERTY LINE

PR

O

PE

RT

Y

LI

N E

OASIS

P.S.M.

#17

VOLLEYBALL

BASKETBALL

GR

AS

S

AR

EA

SALLYPORT

VISITOR CENTER

ADMIN.

CLINICAL

BLDG.

CE

NT

ER

STUDIO

ART

WAREHOUSE

REHAB.

HOMES

HOMES

CENTER

305/307

BIRCH GROVE

CEDAR STREET

ELM STREET

POST

WELLNESS

GR

ND

LOCK

WASH.

WAREHOUSE

KITCHEN

CENTRAL

(Omitted)

CLINIC

D-57 (Upper)

BEAUTY SHOP

CE

NT

ER

FA

SH

IO

N

FSHN. CNT.

STORE

RELIGIOUS

CENTER

NORWALK BOULEVARD

80 Stalls

St al ls

18 Stalls

58 Stalls

S ta lls

S ta lls

#5

BUILDING

CO-GEN.

S.N.F.

TRAILER

101102

HOSP.

OFFICE

POLICE

407/415

405/413

CTE

BLDG.

401/409

408/416

406/414

402/410

417 419

418 420

YOUTH

ADMINISTRATION

BUILDING

CTW

BLDG.

A

A

A

BLDG.

S.N.F.

TRUST

OFFICE

BLDG.

LIBRARY

404/412

403/411

6/

P.S.M.

(D)12KV POLE

OVERALL ELECTRICAL SITE PLAN

TRUE

NORTH

PLAN

NORTH1

Checked

Vault File Number

Project Number

Reference North Sheet Scale

Sheet Number

Designed

Sheet Title

Supervisor

Issue Date

Drawn

Project

No.

JCCA #: 23793-5

00000000000XXXX

METROPOLITAN STATE HOSPITAL

11401 BLOOMFIELD AVENUE

NORWALK, CALIFORNIA 90650

DEPARTMENT OF

STATE HOSPITALS

(DSH)

AS SHOWN

DSA STAMP

DSH-M CUP

INTERCONNECT

DSH

01/12/2024

SA

FI

LE

: L :\2

3\

3-

C U

P In te rc on ne ct , D

SH

-M

\C

AD

\2

5_

E1

O

VE

R

AL

L

SI

TE

P

LA

N

-1

1-

.d w g D

AT

E/

TI

M

E:

N ov

4, 3:

PM

JCCA

V2 PLAN CHECK SUBMITTAL

Client Agency

DEPARTMENT OF STATE HOSPITALS

385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501

P: 310.212.7644 F:310.212.5272I

HJL ZML RN

Issue Date Description

KEYNOTES:

SEE E1.1, E1.2, & E1.3 FOR BUILDING & SUBSTATION LAYOUT SCOPE

OF WORK.

OVERALL

ELECTRICAL

SITE PLAN

E1.0

SCALE: 0 40020 FEET200

1" = 200'

1 11/08/24 ADDENDUM #1

TR-A

66/12KV ELECTRICAL SUBSTATION

TO BE DEMOLISHED BY SOUTHERN

CALIFORNIA EDISON (SCE)

(E)

COGENERATION

BUILDING

TRANSFORMER

PIPE

BRIDGE

BALSAM STREET

(E) UNDERGROUND

CONDUIT BETWEEN

12KV SWITCHGEAR

AND OUTDOOR

SUB-STATION

PROTECT (E)GROUND

OF TRANSFORMER "A"

FOR FUTURE USE

(E) UNDERGROUND

GROUNDING

(E) CHW SUPPLY AND RETURN

PIPING AND FUEL PIPE

UNDERGROUND

TUNNEL

(D)SCE TRANSFORMER

(E) SS

(D)BUILDING

(ELECTRIC

GEAR)

EXISTING CONCRETE SLAB

OVER UNDERGROUND #2 FUEL

OIL STORAGE TANK

(E) MANHOLE "MHAA"

(E)12KV OVERHEAD LINE

(D)12KV POLE WITH AIR

BREAK SWITCH, REFER

TO SCE DRAWING

(D)SCE PAD-MOUNTED

GEAR, PMU-5

(E) HV2-1, HV1-1, HV3-1, HV4-1

(E) HV1-15, CK-2, HV2-2, HV1-2,

HV3-2, HV4-2

(E) CK-3, F4-2

(E)CK-1 AND FUTURE CONDUITS

PROTECT IN PLACE

(E)

MANHOLE

"MHA"

(E)CUP 200KW EMERGENCY

GENERATOR LOCATION

(E)A/G PULLBOX2

TR-3TR-2

(E)GROUNDING

CONNECTION NOT

VERIFIED (TYP)

SCALE

ELECTRICAL SITE PLAN - DEMOLITION PLAN

TRUE

NORTH

PLAN

NORTH1

Checked

Vault File Number

Project Number

Reference North Sheet Scale

Sheet Number

Designed

Sheet Title

Supervisor

Issue Date

Drawn

Project

No.

JCCA #: 23793-5

00000000000XXXX

METROPOLITAN STATE HOSPITAL

11401 BLOOMFIELD AVENUE

NORWALK, CALIFORNIA 90650

DEPARTMENT OF

STATE HOSPITALS

(DSH)

AS SHOWN

DSA STAMP

DSH-M CUP

INTERCONNECT

DSH

01/12/2024

SA

FI

LE

: L :\2

3\

3-

C U

P In te rc on ne ct , D

SH

-M

\C

AD

\2

5_

E1

EL

EC

TR

IC

AL

S

IT

E

PL

AN

-1

1-

.d w g D

AT

E/

TI

M

E:

N ov

4, 3:

PM

JCCA

V2 PLAN CHECK SUBMITTAL

Client Agency

DEPARTMENT OF STATE HOSPITALS

385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501

P: 310.212.7644 F:310.212.5272I

HJL ZML RN

Issue Date Description

SEE ENLARGED PLAN ON

SHEET E2.0 DETAIL 1 & 2

COORDINATE WITH SCE FOR THE DEMOLITION OF EXISTING GUY.

COORDINATE WITH SCE FOR THE DEMOLITION OF (E) SCE

EQUIPMENT. REFER TO SCE DRAWING. PROVIDE COVER PLATE

ON THE OPENINGS AFTER THE REMOVAL OF EQUIPMENT.

DEMOLISHED EXISTING SWITCHGEAR BUILDING INCLUDING THE

ABANDONED SWITCHGEAR EQUIPMENT.

(E)MV PULLBOX TO PROTECT AND REMAIN IN PLACE.

DEMO WORK KEYNOTES:

ELECTRICAL

SITE PLAN

DEMOTION PLAN

E1.1

1 11/08/24 ADDENDUM #1

0 5 10 15 FEET 30

1" = 15' l

(E) SS

EXISTING CONCRETE SLAB OVER

UNDERGROUND #2 FUEL OIL

STORAGE TANK

BALSAM STREET

G

(E) MANHOLE "MHAA"

12KV OVERHEAD LINE

(E)UNDERGROUND CONDUIT

BETWEEN 12KV SWITCHGEAR

AND OUTDOOR SUB-STATION

(E) UNDERGROUND CONDUIT(E) HV1-15, CK-2, HV2-2, HV1-2, HV3-2, HV4-2

(E) CK-3, F4-2

(E)CK-1 AND SPARE CONDUITS.

ROUTING ARE NOT VERIFIED.

(E)MANHOLE "MHA"

(E) CHW SUPPLY AND RETURN

PIPING AND FUEL PIPE

UNDERGROUND

TUNNEL

(TYP)

(E) TUNNEL EXHAUST FAN TO REMAIN

(E) 5KV, NEMA 3R

SPLICE BOX TO

REMAIN

(E) UNDERGROUND

CONDUIT

(N)(4)4"C - ABOVEGROUND CONDUITS

5 6

"MHAA-1"

4'x6'-6"x5'-6"

13 14

(8)5"C

(E)75KVA TRANSFORMER

(E)MV PB

(E)MCC

(E)MV DISCONNECT SWITCHES

(E)TRANSFORMER "TGB"

(E)45KVA TRANSFORMER

(E)LIGHTING PANEL "A"

(E)PANEL "B"

(E)BATTERY &

BATTERY CHARGER

(E)LOCAL DIST. PANEL (LDP)

(E)ALARMTRONICS

FUTURE PARALLELING

SWITCHGEAR WITH MASTER

CONTROLLER

(4) 5"C

(4)2"C (2)2"C

(2)2"C3

3 3

Checked

Vault File Number

Project Number

Reference North Sheet Scale

Sheet Number

Designed

Sheet Title

Supervisor

Issue Date

Drawn

Project

No.

JCCA #: 23793-5

00000000000XXXX

METROPOLITAN STATE HOSPITAL

11401 BLOOMFIELD AVENUE

NORWALK, CALIFORNIA 90650

DEPARTMENT OF

STATE HOSPITALS

(DSH)

AS SHOWN

DSA STAMP

DSH-M CUP

INTERCONNECT

DSH

01/12/2024

SA

FI

LE

: L :\2

3\

3-

C U

P In te rc on ne ct , D

SH

-M

\C

AD

\2

5_

E1

EL

EC

TR

IC

AL

S

IT

E

PL

AN

N

EW

W

O R

K_

EN

LA

R

G

ED

-1

1-

.d w g D

AT

E/

TI

M

E:

N ov

4, 3:

PM

JCCA

V2 PLAN CHECK SUBMITTAL

Client Agency

DEPARTMENT OF STATE HOSPITALS

385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501

P: 310.212.7644 F:310.212.5272I

HJL ZML RN

Issue Date Description

KEYNOTES:

GENERAL NOTES: (APPLICABLE TO EXTERIOR WORK)

1. THE EXISTING CONDITIONS OF BELOW GROUND PIPING AND UTILITIES SUCH AS GAS

MAINS, WATER MAINS, SANITARY SEWERS, POWER AND COMMUNICATIONS CONDUITS

AND OTHER UTILITIES ARE TAKEN FROM EXISTING RECORD DRAWINGS AND VERIFIED

BY FIELD OBSERVATION. THE LOCATION OF THESE UTILITIES IS APPROXIMATE ONLY.

IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO FIELD VERIFY THE EXACT

LOCATION AND DEPTH OF BELOW GROUND PIPING AND UTILITIES IN THE IMMEDIATE

VICINITY OF SUBSURFACE WORK, WHETHER SHOWN ON THE DRAWING OR NOT.

CONTRACTOR SHALL RETAIN THE SERVICES OF AN UNDERGROUND UTILITY

LOCATING COMPANY. UTILIZE GROUND PENETRATING RADAR AND OTHER UTILITY

LOCATING DEVICES TO DETERMINE THE LOCATION AND DEPTH OF ALL

UNDERGROUND IMPROVEMENTS WITHIN APPROXIMATELY 20' OF ALL NEW WORK.

PAINT MARK ALL UTILITY LOCATIONS ON THE PAVEMENT SURFACE. THIS TASK SHALL

BE COMPLETED PRIOR TO ANY EXCAVATING.

2. PRIOR TO STARTING TRENCHING, POTHOLE TO VERIFY THE DEPTH OF EXISTING

PIPES WHICH ARE TO JOIN OR CROSS NEW PIPING OR CONDUITS. ADJUST DEPTH OF

NEW PIPE CONDUIT AS REQUIRED TO CROSS EXISTING UTILITIES. NOTIFY ENGINEER

OF ANY DISCREPANCIES OR INTERFERENCES PRIOR TO LAYING ANY PIPE.

3. PRIOR TO STARTING TRENCHING, VERIFY LOCATION AND WORKING CONDITION OF

THE ASSOCIATED WATER VALVES WHICH NEED TO BE EXERCISED DUE TO THE

WATER SHUTDOWN ASSOCIATED WITH THE SCOPE OF WORK. NOTIFY ENGINEER IF

THERE ARE ANY DISCREPANCIES WITH THE VALVES.

4. EXISTING UNDERGROUND UTILITIES SHOWN HEREIN HAVE BEEN LOCATED FROM

VARIOUS SOURCES OF VARYING RELIABILITY, INCLUDING SURFACE EVIDENCE AND

AVAILABLE RECORDS, AND ARE SHOWN FOR INFORMATION ONLY. THE CONTRACTOR

IS RESPONSIBLE FOR DETERMINING THE EXACT LOCATION OF ALL EXISTING UTILITIES

AND FOR THE PROTECTION OF AND REPAIR OF DAMAGE TO THEM.

5. ALL WORK RELATED TO SCE EQUIPMENT AND UNDERGROUND WORK SHALL BE

INSTALLED IN ACCORDANCE WITH SCE ESR AND UGS MANUAL. IT SHOULD BE

ACCEPTED BY SCE INSPECTION TEAM. SEE ATTACHED SCE DRAWING FOR

ADDITIONAL INFORMATION.

6. CONTACT DIG ALERT (811) 48 HOURS PRIOR TO EXCAVATION.

SCALE

TRUE

NORTH

PLAN

NORTH1

3,750KVA TRANSFORMER PAD, SEE DETAIL 6/E4.1

PROVIDE ONE ROUND OF SLACK CONDUCTOR.

REMOVE AND REPLACE AC PAVING FOR ELECTRICAL CONDUIT TRENCH.

SEE DETAIL 2/E4.0, 2/E4.1

VACUUM FAULT INTERRUPTER (VFI) EQUIPMENT PAD, SEE DETAIL 7/E4.1.

BYPASS EQUIPMENT PAD, SEE DETAIL 5/E4.1.

3-WAY RAG EQUIPMENT PAD, SEE DETAIL 5/E4.1.

CAPACITOR EQUIPMENT PAD, SEE DETAIL 8/E4.1.

(E) EQUIPMENT PAD TO REMAIN. COVER TRENCH SIMILAR TO EXISTING

COVER PLATE ONCE THE REMOVAL OF (E)EQUIPMENT IS COMPLETED.

(E)SCE 12KV UNDERGROUND CONDUIT NOT VERIFIED. CONDUIT SHALL

BE ABANDONED IN PLACE ONCE THE UPGRADE IS COMPLETED.

NEW 5KV, 1200A, 3Ø, SCE METERING EQUIPMENT SHALL BE IN

COMPLIANCE WITH ESR REQUIREMENT. SUBMIT SHOP DRAWING TO SCE

FOR APPROVAL. SEE DETAIL #2, E4.2 FOR EQUIPMENT PAD DETAIL.

18" X 18" X 6" NEMA 3R PULL BOX (LOW VOLTAGE - POWER).

18" X 18" X 6" NEMA 3R PULL BOX (SIGNAL).

1 1/2"Ø AND 2"Ø PVC (POWER), SEE DETAIL 5/E4.2.

(2)2"Ø PVC (SIGNAL), SEE DETAIL 5/E4.2.

SEE DETAIL 2/E4.2 EXCEPT CONDUIT IS 4" DIAMETER.

(E)SCE 5KV UNDERGROUND CONDUITS AND THE ROUTING ARE NOT

VERIFIED. CONDUITS SHALL BE PLUG AND ABANDONED IN PLACE ONCE

THE UPGRADE IS COMPLETED.

(1)5"C, SEE DETAIL 4/E4.2

(2)5"C, SEE DETAIL 9/E4.2

(4)5"C, SEE DETAIL 8/E4.2

24"D X 36"W X 48"H HV PULL BOX

REPAIR DAMAGE ASPHALT WALKWAY DUE TO NEW UNDERGROUND

CONDUIT. EXTEND WIDTH OF ASPHALT WALKWAY FOR 48".

REFER WITH SCE DRAWING FOR ADDITIONAL INFORMATION ON POLE

RISER REQUIREMENT.

12" X 22" UNDERGROUND PULLBOX, SEE DETAIL 4/E4.3. PROVISION FOR

FUTURE GENERATOR AREA INTERFACE.

REMOVE AND REPLACE AC PAVING FOR ELECTRICAL CONDUIT TRENCH.

SEE DETAIL 2/E4.0 BUT 8 CONDUITS.

SEE DETAIL 8/E4.2 BUT 10 CONDUITS

REMOVABLE BOLLARD, TYPICAL OF 2, SEE DETAIL 2/E4.3

FIXED BOLLARD, DETAIL 4/E4.1, NOT TO EXCEED 4'-6" APART, TYPICAL.

REMOVE AND REPLACE AC PAVING FOR ELECTRICAL CONDUIT TRENCH.

FUTURE GENERATOR POWER CONDUITS, SEE DETAIL 2/E4.0.

0 FEET8

1" = 8'-0"

4 16

ELECTRICAL SITE

PLAN - ENLARGED

E1.2

ELECTRICAL SITE PLAN - ENLARGED

(E) SS

(E)

COGENERATION

BUILDING

EXISTING CONCRETE SLAB OVER

UNDERGROUND #2 FUEL OIL

STORAGE TANK

TRANSFORMER

PIPE

BRIDGE

BALSAM STREET

G

(E) MANHOLE "MHAA"

R=5'-0"

(TYP)

"MHAA-2"

DETAIL#1/E4.0

12KV OVERHEAD LINE

G10D

(E)UNDERGROUND CONDUIT

BETWEEN 12KV

SWITCHGEAR AND OUTDOOR

SUB-STATION

VERIFY ON SITE THE DEPTH

AND ROUTING

(E) GROUND OF

TRANSFORMER "A"

TO RE-USE

(E)UNDERGROUND

GROUNDING

(E) UNDERGROUND CONDUIT(E)HV1-15, CK-2, HV2-2,

HV1-2, HV3-2, HV4-2

(E)CK-3, F4-2

(E)MV PB

(E)MANHOLE "MHA"

(E) CHW SUPPLY AND RETURN

PIPING AND FUEL PIPE

UNDERGROUND

TUNNEL

1' -6

5' -0

(E)TUNNEL EXHAUST FAN TO REMAIN

(E)5KV, NEMA

3R SPLICE

BOX TO

REMAIN

(E)UNDERGROUND

CONDUIT

"MHAA-1"

DETAIL#5/E4.3

3'-0"

4' -0

2'

-6

(8)5"C

5 6

1 8

4'-0"

29 (TYP.)

FUTURE

ABOVEGROUND

TANK

FUEL

POLISHER

FUTURE

FUTURE

DAYTANK

NGR NGR

FUTURE PARALLELING

SWITCHGEAR WITH MASTER

CONTROLLER

2,500KW

FUTURE

2,500KW

FUTURE

(4)5"C

FUTURE GENERATOR

AREA NOT PART OF THIS

CONTRACT

11'-8"

6' -0

5'-9"

4'-7"

4' -6

4'-0"

'-0

(4)5"C

SCALE

ELECTRICAL SITE PLAN - UNDERGROUND NEW WORK

TRUE

NORTH

PLAN

NORTH1

Checked

Vault File Number

Project Number

Reference North Sheet Scale

Sheet Number

Designed

Sheet Title

Supervisor

Issue Date

Drawn

Project

No.

JCCA #: 23793-5

00000000000XXXX

METROPOLITAN STATE HOSPITAL

11401 BLOOMFIELD AVENUE

NORWALK, CALIFORNIA 90650

DEPARTMENT OF

STATE HOSPITALS

(DSH)

AS SHOWN

DSA STAMP

DSH-M CUP

INTERCONNECT

DSH

01/12/2024

SA

FI

LE

: L :\2

3\

3-

C U

P In te rc on ne ct , D

SH

-M

\C

AD

\2

5_

E1

EL

EC

TR

IC

AL

S

IT

E

PL

AN

N

EW

W

O R

K

- 2

4-

-0

8.

dw g D

AT

E/

TI

M

E:

N ov

4, 3:

PM

JCCA

V2 PLAN CHECK SUBMITTAL

Client Agency

DEPARTMENT OF STATE HOSPITALS

385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501

P: 310.212.7644 F:310.212.5272I

HJL ZML RN

Issue Date Description

SEE ENLARGED PLAN ON

SHEET DETAIL 1 & 2/E2.0

KEYNOTES:

3,750KVA TRANSFORMER PAD, SEE DETAIL 6/E4.1.

PROVIDE ONE ROUND OF SLACK CONDUCTOR.

REMOVE AND REPLACE AC PAVING FOR ELECTRICAL

CONDUIT TRENCH. SEE DETAIL 2/E4.0, 2/E4.1.

VACUUM FAULT INTERRUPTER EQUIPMENT PAD, SEE DETAIL

7/E4.1

BYPASS EQUIPMENT PAD, SEE DETAIL 5/E4.1

3-WAY RAG EQUIPMENT PAD, SEE DETAIL 5/E4.1

CAPACITOR EQUIPMENT PAD, SEE DETAIL 8/E4.1

(E)EQUIPMENT PAD TO REMAIN. COVER TRENCH SIMILAR TO

EXISTING COVER PLATE ONCE THE REMOVAL OF

(E)EQUIPMENT IS COMPLETED.

GROUNDING TEST WELL, SEE DETAIL 4/E4.0.

#4/0 BARE COPPER CONDUCTOR BURIED 48" BELOW FINISH

GRADE.

5/8"Ø X 8' GROUNDING ROD, SEE DETAIL 4/E4.0 WITHOUT TEST

WELL

CONNECTION TO REBARS AND MAIN GROUNDING SHALL BE

BY EXOTHERMIC WELDING, USE #2/0 BARE COPPER WIRE

E1.3

ELECTRICAL

SITE PLAN -

UNDERGROUND

NEW WORK

1 11/08/24 ADDENDUM #1

(4)5"C

SEE ENLARGED PLAN ON

SHEET E2.0 DETAIL 4 & 5.

0 5 10 15 FEET 30

1" = 15'

SEE ENLARGED PLAN ON

SHEET DETAIL 3/E2.0

DEMOLISH POWER AND CONTROL CONDUCTOR

FROM 12KV SWITCHGEAR. CONDUIT SHALL BE

PLUG & FLUSH IN CONCRETE PAD.

(E) GROUNDING

DEMOLISH TRANSFORMER

TR-A AND PAD

DEMO OR SECURE BELOW GRADE GROUNDING

CONDUCTOR NO LONGER REQUIRED

(E) CONDUIT TO INTERCEPT AND RE-USE.

PROTECT

(E) GROUND

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

(E) PULL BOX

(E) ELECTRIC EQUIPMENT

TO REMAIN (TYP)

1 1/2"C -2#8+2#10+

2#10 GND

(4)4"C ABOVE GROUND

(E) PANEL "A"

(E) 5KV SWITCHGEAR

4.5

3.7

SWITCHGEAR

ROOM

STAIR #2

12KV SWITCHGEAR TO BE

DEMOLISHED INCLUDING

ASSOCIATED EQUIPMENT

SUCH AS BATTERY,

BATTERY CHARGER, ETC.

(E) MCC-A

STAIR #1

U.P.S. ROOM

PARTS/TOOLS

STORAGE

STORAGE

ROOM

REPAIR

SHOP

DEMOLISH (E) UNDERGROUND

CONDUIT AND CONDUCTOR.

CONDUIT SHALL BE CUT 6"

MINIMUM BELOW FINISH FLOOR.

G G G G G G

STUB-UP GROUNDING

TO BE DEMOLISHED

(TYP)

(E)GROUND RING TO

REMAIN AND PROTECT

IN PLACE.

SLURRY SEAL ABOVE DUCTBANK WHEN

ROUTING UNDER RETAINING WALL

FOOTING. SEE E4.1 DETAIL 1.

TO MANHOLE

"MHAA-1"

SEE E1.2

5' -0

" 7'-2"

INTERCEPT (E) CONDUIT AND PROVIDE

NEW CONDUCTOR, SEE SLD.

EQUIPMENT

GROUNDING

(E)LPA. PROVIDE 20A, 1P

CB KAIC RATING SHALL

MATCH EXISTING

3/4"C-3#12 CUPSW-1 HEATER

WEATHERPROOF SEAL THE PENETRATION

GROUND REBARS

TERMINATE CONDUIT 2' FROM

EQUIPMENT PAD, CAP & SECURE

(E) GROUNDING NEW LOAD INTERRUPTING

SWITCH "CUPSW-1"

PROVIDE #2/0 BARE COPPER GROUND

CONDUCTOR AND EXOTHERMICALLY

WELD WITH THE MAIN GROUNDING RING

ED.6D

ED.6D

ED.6D

4.5

3.7

ED.6D

SWITCHGEAR

ROOM

STAIR #2

(E) MCC-A

STAIR #1

U.P.S. ROOM

PARTS/TOOLS

STORAGE

STORAGE

ROOM

REPAIR

SHOP

(E) CONDUIT TO

BE RE-USED

Checked

Vault File Number

Project Number

Reference North Sheet Scale

Sheet Number

Designed

Sheet Title

Supervisor

Issue Date

Drawn

Project

No.

JCCA #: 23793-5

00000000000XXXX

METROPOLITAN STATE HOSPITAL

11401 BLOOMFIELD AVENUE

NORWALK, CALIFORNIA 90650

DEPARTMENT OF

STATE HOSPITALS

(DSH)

AS SHOWN

DSA STAMP

DSH-M CUP

INTERCONNECT

DSH

01/12/2024

SA

FI

LE

: L :\2

3\

3-

C U

P In te rc on ne ct , D

SH

-M

\C

AD

\2

5_

E2

EN

LA

R G

ED

P

LA

N

-1

1-

.d w g D

AT

E/

TI

M

E:

N ov

4, 3:

PM

JCCA

V2 PLAN CHECK SUBMITTAL

Client Agency

DEPARTMENT OF STATE HOSPITALS

385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501

P: 310.212.7644 F:310.212.5272I

HJL ZML RN

Issue Date Description

NEW WORK KEYNOTES:

1 PROVIDE (1)2P, 40A (BATTERY CHARGER) AND (1)1P, 20A

(HEATER) FOR NEW OUTDOOR SWITCHGEAR.

MAIN SWITCHGEAR BUILDING

TRUE

NORTH

PLAN

NORTH3 SCALE: 0 FEET8

1/8" = 1'-0"

4 16

TRANSFORMER AREA - DEMOLITION PLAN

TRUE

NORTH

PLAN

NORTH1 SCALE: 0 FEET8

1/8" = 1'-0"

4 16

UNDERGROUND PULL SECTION (UGPS)

MAIN BREAKER

SCE METERING

HV1

HV2

CENTRAL KITCHEN BREAKER

HV3

HV4

TRANSITION SECTION

KEYNOTES:

SWITCHGEAR ROOM - DEMOLITION PLAN

TRUE

NORTH

PLAN

NORTH4 SCALE: 0 FEET8

1/8" = 1'-0"

4 16

TRANSFORMER AREA - NEW WORK PLAN

TRUE

NORTH

PLAN

NORTH2 SCALE: 0 FEET8

1/8" = 1'-0"

4 16

SWITCHGEAR ROOM - NEW WORK PLAN

TRUE

NORTH

PLAN

NORTH5 SCALE: 0 FEET8

1/8" = 1'-0"

4 16

GM BREAKER

HV4 AT BREAKER

SPARE

CIRCUIT BREAKER G-3 (FUTURE)

GEN #2 CONTROL SECTION

CIRCUIT BREAKER G-2

CIRCUIT BREAKER G-1

MASTER CONTROL PANEL

GEN #1 CONTROL SECTION

ENLARGED PLAN

E2.0

Checked

Vault File Number

Project Number

Reference North Sheet Scale

Sheet Number

Designed

Sheet Title

Supervisor

Issue Date

Drawn

Project

No.

JCCA #: 23793-5

00000000000XXXX

METROPOLITAN STATE HOSPITAL

11401 BLOOMFIELD AVENUE

NORWALK, CALIFORNIA 90650

DEPARTMENT OF

STATE HOSPITALS

(DSH)

AS SHOWN

DSA STAMP

DSH-M CUP

INTERCONNECT

DSH

01/12/2024

SA

FI

LE

: L :\2

3\

3-

C U

P In te rc on ne ct , D

SH

-M

\C

AD

\2

5_

E4

D

ET

AI

LS

-1

1-

.d w g D

AT

E/

TI

M

E:

N ov

4, 1:

AM

JCCA

V2 PLAN CHECK SUBMITTAL

Client Agency

DEPARTMENT OF STATE HOSPITALS

385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501

P: 310.212.7644 F:310.212.5272I

HJL ZML RN

Issue Date Description

RESERVED

NOT TO SCALE

NOT TO SCALE

WARNING

TAPE

3"

NATIVE BACKFILL

MATERIAL SHALL BE 90%

COMPACTION

CARLON

SNAP-N-STAC

SPACER LOCATED

EVERY 10'

CONDUIT

TYPE EB 35

PVC (TYP)

3' -6

3" 3"

REPAIR ASPHALT PAVEMENT.

SEE E4.1 DETAIL 2.

CAST IN PLACE

CONCRETE

ENCASEMENT

(2000) PSI) 12

2 NTS

UNDERGROUND ELECTRICAL CONDUIT

6"

6"6"

6' -8

5'-0"5'-0"

6"

5' -6

8" 6"

8"

REVERSABLE

FRAME

1" PICK HOLE

3'-1 3/4"

1/

8" 5"

3'-2"

1"

3'-0" 3'-9 1/4"

GENERAL INFORMATION

· ALL MATERIALS USED IN MANUFACTURING

SHALL CONFORM TO ASTM A48-83 CLASS

· 30. FRAME & COVER BEARING SURFACES

MACHINED TO ASSURE CLOSE, QUIET FIT.

· STANDARD COVER MEETS H-20 WHEEL

LOADING. STANDARD COVER MARKINGS

· LABEL:"ELECTRIC"

DESIGN FOR H-20-44 BRIDGE LOADING.

ASSEMBLY TO BE PLACED ON A 6" BASE OF

CRUSHER RUN FOR EASE OF INSTALLATION

AND EVEN LOAD DISTRIBUTION.

1 NTS

4'-0"x4'-0"x5'-6" MANHOLE DETAIL - JENSEN PRECAST

12"Ø SUMP KNOCKOUT

GROUNDING TEST WELL

NOT TO SCALE4

CL

5/8"Øx8' LENGTH COPPER

GROUND ROD

GROUND LEVEL

UNDERGROUND PULLBOX

DRAINAGE STEEL FRAME

1'x1'x2' DEEP DRAINAGE SUMP WITH 3/4" DIA.

PEA GRAVEL WRAPPED IN FILTER FABRIC

CABLE SUPPORT

5kV CONDUCTOR

CABLE CLEAT

EPVRT-04 OR

AS REQUIRED

HILTI KB-3 EXPANSION

ANCHOR 3/8"Ø x 4-1/2" WITH

MINIMUM EMBEDMENT OF

3-1/2".

12" DIA.

SUMP

CONDUCTOR

IN

PLAN

OUT

UNISTRUT SUPPORT

AND UNISTRUT FITTINGS

COMPLETE WITH BOLTS

WASHER AND WING NUT

36" CLEAR OPENING

FRAME & COVER MODEL

B-5520

5'-6" 4'-0"

4'-0"

#2 (TYP. FOR 8

EQUALLY SPACED)

(N) MANHOLE COVER

ASSEMBLY SEE DETAILS

FOR SPECIFICATIONS

AND DIMENSIONS

12"

MIN

12"

MIN (N) EXTERNAL

CONC. COLLAR

SLOPE TO DRAIN

MIN 2% ALL AROUND

SAWCUT (E) AC

FULL DEPTH

(E) AC (WHERE OCCURS)

#4 (TYP. FOR 4)

ADJOINED TO EXIST ASPHALT

NOT TO SCALE3

AND COVER ASSEMBLY

MANHOLE FRAME

RESERVED

6" BASE OF CRUSHER RUN

(E) SOIL

PREVENT LOSS OF

DENSITY ON (E) BASE

AND SUBGRADE

ERITECH INSPECTION WELLS

PART NUMBER T416B OR EQUAL

GROUND LEVEL

GROUNDING

ELECTRODE

CONDUCTOR

EXOTHERMIC

WELDING (TYP.)

5/8"Ø x 8' COPPER

GROUND ROD

10"Ø

/4

13"Ø

TO GROUNDING GRID/

GROUNDING ROD

TO EQUIPMENT

GROUND BUS

MECHANICALLY

CONNECTED

ELECTRICAL

DETAILS

E4.0

5" 5"

5"5"

1 1