Addendum_1_-_2501901.pdf
PDF 4 MB Posted
- Attached to
- Venetian Cove Marina Dock Improvement Project
- Solicitation number
- 2501901
- Issued by
- Lake County, Florida
About this file
This document is an Invitation for Bid (IFB) for the Construction of Venetian Cove Marina Dock Improvement Project issued by the City of Leesburg, Florida. Addendum No. 1, dated July 10, 2025, provides updates to the original bid documents and includes Venetian Cove Electrical Upgrade Drawings. The project encompasses electrical and marina infrastructure upgrades, specifically focusing on electrical system improvements for the marina facilities. Bidders are required to acknowledge receipt of this addendum by indicating it on their Proposal Bid Form, and if they have already submitted their form, they must revise their electronic submission to include the addendum.
The electrical upgrades include detailed specifications for branch circuit and feeder installations, with comprehensive documentation of wire sizes, conduit specifications, and equipment requirements. The drawings provide technical details for electrical systems, including panel schedules, wiring color codes, and installation guidelines. The project appears to be funded through municipal channels, with specific technical requirements for marina electrical infrastructure, including ground fault monitoring, equipment mounting, and compliance with national electrical codes. The technical specifications suggest a comprehensive approach to upgrading the marina's electrical systems to meet current safety and performance standards.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DATE: July 10, 2025 TO: All Interested Bidders and Other Interested Parties FROM: Hosea Goodwyn, Senior Buyer
The City makes the following changes, additions, deletions, information, and/or clarifications and now considers the addendum a part of the Invitation for Bid (IFB) Document. Bidders must acknowledge receipt of this addendum by indicating receipt in the space provided on the Proposal Bid Form. If the bidder has already submitted the Proposal Bid Form to the City’s Purchasing Division, the Bidder should revise their electronic submission to include this addendum. In any case, the submission of a bid is an acknowledgment of receipt of the addendum. The City will construe all bids received as though the Bidder has received and acknowledged the addendum.
The following document is hereby made part of the solicitation.
1. Venetian Cove Electrical Upgrade Drawings
ACKNOWLEDGMENT - Addendum #1
Company Name
Signature of Officer
Type/Print Officer's Name & Title
IFB 2501901
Construction of Venetian Cove Marina Dock Improvement Project
Addendum No. 1
A20 1/2"
LABEL
(2) #12 & (1) #12 GND. 20
CONDUCTOR
AMPACITY 75 °C
VOLTAGE
RANGE
120 OR 277
208 - 480
MINIMUM
CONDUITCONDUCTORS PER CONDUIT
3/4" 30(2) #10 & (1) #10 GND.
50(2) #8 & (1) #10 GND.
20(3) #12 & (1) #12 GND. 1/2"
A30
A50
B20
30(3) #10 & (1) #10 GND. 3/4"B30
50(3) #8 & (1) #10 GND.B50
65(3) #6 & (1) #10 GND.B60
85(3) #4 & (1) #8 GND.B80 1"
100(3) #3 & (1) #8 GND.B100
130(3) #1 & (1) #6 GND.B125 1-1/2"
150(3) #1/0 & (1) #6 GND.B150 2"
175(3) #2/0 & (1) #6 GND.B175
200(3) #3/0 & (1) #6 GND.B200
230(3) #4/0 & (1) #4 GND.B225 2-1/2"
255(3) #250 KCM & (1) #4 GND.B250
310(3) #350 KCM & (1) #4 GND.B300
380(3) #500 KCM & (1) #3 GND.B350 3"
400(3) #3/0 & (1) #3 GND.B400 2"2
510(3) #250 KCM & (1) #2 GND.B500 2-1/2"
620(3) #350 KCM & (1) #1 GND.B600 3"
855(3) #300 KCM & (1) #1/0 GND. 2-1/2"3B800
1020(3) #250 KCM & (1) #2/0 GND. 4B1000
1240(3) #350 KCM & (1) #3/0 GND.B1200 3"
20(4) #12 & (1) #12 GND.C20 1/2"1
30(4) #10 & (1) #10 GND. 3/4"C30
50(4) #8 & (1) #10 GND.C50
65(4) #6 & (1) #10 GND.C60
85(4) #4 & (1) #8 GND.C80 1-1/2"
100(4) #3 & (1) #8 GND.C100
130(4) #1 & (1) #6 GND.C125 1-1/2"
150(4) #1/0 & (1) #6 GND.C150 2"
175(4) #2/0 & (1) #6 GND.C175
200(4) #3/0 & (1) #6 GND.C200
230(4) #4/0 & (1) #4 GND.C225 3"
255(4) #250 KCM & (1) #4 GND.C250
310(4) #350 KCM & (1) #4 GND.C300
380(4) #500 KCM & (1) #3 GND.C350
400(4) #3/0 & (1) #3 GND.C400 2"2
510(4) #250 KCM & (1) #2 GND.C500 3"
620(4) #350 KCM & (1) #1 GND.C600 3"
855(4) #300 KCM & (1) #1/0 GND.C800 3"3
1020(4) #250 KCM & (1) #2/0 GND. 4C1000
1240(4) #350 KCM & (1) #3/0 GND.C1200 3"
1520(4) #500 KCM & (1) #4/0 GND.C1400
1675(4) #400 KCM & (1) #4/0 GND. 5C1600
2100(4) #600 KCM & (1) #250 KCM GND.C2000 4"
BRANCH CIRCUIT AND FEEDER LEGEND W/ EQUIP. GND.
ALL WIRE SIZED FOR THWN COPPER
ALL CONDUIT SIZED FOR RIGID PVC, SCHEDULE 40; RESIZE FOR DIFFERENT CONDUIT AS REQUIRED
FEEDER LABEL WITH * IN THE PLANS INDICATES NEUTRAL IS NOT REQUIRED
NUMBER
OF RUNS
115(3) #2 & (1) #6 GND.B110 1-1/2"
(3) #300 KCM & (1) #4 GND.B275
2-1/2"
2-1/2"
3"
3/4"
3/4"
3/4"
1-1/2"
2"
2"
(3) #4/0 & (1) #2 GND.B450 2-1/2" 4602
(4) #2 & (1) #6 GND.C110 1-1/2"
1-1/2"
3/4"
1"
(4) #4/0 & (1) #2 GND. 4603"2C450
3"
3-1/2"
3"
3-1/2"
3"
3"
2"
2"
2-1/2"
Φ
120 OR 277
120 OR 277
208 - 480
208 - 480
208 - 480
208 - 480
208 - 480
208 - 480
208 - 480
208 - 480
208 - 480
208 - 480
208 - 480
208 - 480
208 - 480
208 - 480
208 - 480
208 - 480
208 - 480
208 - 480
208 - 480
208 - 480
208 - 480
208 - 480
208 - 480
208 - 480
208 - 480
208 - 480
208 - 480
208 - 480
208 - 480
208 - 480
208 - 480
208 - 480
208 - 480
208 - 480
208 - 480
208 - 480
208 - 480
208 - 480
208 - 480
208 - 480
208 - 480
208 - 480
208 - 480
208 - 480
208 - 480
208 - 480
208 - 480
OFTIS
AFFETTAFFETT
1 S JEFFERSON AVE, STE 101
COOKEVILLE, TN 38501
TEL: (931) 526-5143
www.maffett-loftis.com
ENGINEERING, LLC
P R
O J E
C T
T
IT
L E
S H
E E
T T
IT
L E
REVISIONDATE
ISSUED FOR:
DATE:
PROJ NO.:
DESIGNED BY:
DRAWN BY:
REVIEWED BY:
SHEET NUMBER:
THE REPRODUCTION, COPYING
OR OTHER USE OF THIS DRAWING
WITHOUT WRITTEN CONSENT IS
PROHIBITED. © 2020 EDGEWATER
RESOURCES, LLC.
MLE PROJ NO.:
20-040
V E
N E
T
IA
N C
O V
E M
A R
IN
A
E L
E C
T R
IC
A
L U
P G
R A
D E
S L
E E
S B
U R
G
F L
NORTH
24024
E0.1
JLC
Issue Date
E L E
C T
R
IC
A L
N O
T E
S A
N D
L E
G E
N D
S
Project Status www.call811.com
CALL BEFORE YOU DIG
THE CONTRACTOR SHALL
NOTIFY ALL UTILITIES INCLUDING AND
NOT LIMITED TO GAS, WATER,
ELECTRIC, CABLE, AND TELEPHONE
COMPANIES PRIOR TO ANY
EXCAVATION. THE CONTRACTOR
SHALL NOTIFY ONE-CALL SERVICE
(CALL 811) SEVENTY-TWO (72) HOURS
AS REQUIRED BY LAW BEFORE ANY
EXCAVATION, AT ANY LOCATION.
ELECTRICAL ABBREVIATIONS
ABOVEA / AB
AMPERE FRAMEAF
ABOVE FINISHED FLOORAFF
ABOVE FINISHED GRADEAFG
ARC FAULT INTERRUPTERAFI
AUTHORITY HAVING JURISDICTIONAHJ
AVAILABLE FAULT CURRENTAIC
AMPEREAMP
ANNUNCIATOR PANELAP
AMPERE TRIPAT
AUTOMATIC TRANSFER SWITCHATS
AUTOMATICAUTO
BELOW FINISHED GRADEBFG
BASIS OF DESIGNBOD
CONTACTORC
CIRCUITCKT
COMMUNICATIONCOM
CURRENT TRANSFORMERCT
DIGITAL ALARM COMMUNICATION RECEIVERDACR
DIGITAL ALARM COMMUNICATION TRANSMITTERDACT
DUAL ELEMENT TIME DELAYDETD
DOWNDN
DRAWINGDWG
ELECTRICAL CONTRACTOREC
ENCLOSED CIRCUIT BREAKERECB
ELECTRICAL DATUM PLANEEDP
EMERGENCYEMG
EQUIPMENTEQUIP
ELECTRONIC TRIP BREAKERETB
FIRE ALARM CONTROL PANELFACP
FIRE ALARM PANELFAP
FIRE ALARM SYSTEMFAS
GALLONGAL
GENERATOR ANNUNICATOR PANELGAP
GARBAGE DISPOSALGD
GROUND FAULT CIRCUIT INTERRUPTERGFCI
GROUND FAULT INTERRUPTERGFI
GROUND FAULT MONITORGFM
GROUND FAULT PROTECTION OF EQUIPMENTGFPE
GALLONS PER HOURGPH
HEATING, AIR CONDITIONING, REFRIGERATIONHACR
HORSEPOWERHP
HERTZHZ
INTEGRATED POWER CENTERIPC
KILOVOLT-AMPEREKVA
KILOWATTKW
LIGHTING CONTACTORLC
LOCAL ELECTRICAL AND UTILITY DEPARTMENTLEUD
MAXIMUMMAX
MAIN CIRCUIT BREAKERMCB
MOLDED CASE SWITCHMCS
MAIN DISTRIBUTION PANELMDP
MANUFACTURINGMFG
MANUFACTURERMFR
MINIMUMMIN
MICROLOGIC BREAKERMLB
MAIN LUG ONLYMLO
MAIN OVERCURRENT PROTECTIONMOCP
NORMALLY CLOSEDN.C.
NORMALLY OPENN.O.
OVERCURRENT PROTECTIONOCP
OVERHEADOH
PUSH BUTTONPB
PHASEPH / Φ
PANELPNL
PORTABLE POWER CABLEPPC
RECIRCULATING / RECIRCULATIONRECIRC
RECEPTACLERECPT
SCHEDULESCH
SERVICE ENTRANCE CONDUCTORSER
SURGE PROTECTIVE DEVICESPD
SHUNT TRIPST
TELEPHONETEL
THERMAL MAGNETIC BREAKERTMB
TYPICALTYP
UNDER / UNDER CABINETU / UC
UNDERGROUNDUG
UNLESS OTHERWISE NOTEDUON
UNINTERRUPTIBLE POWER SUPPLYUPS
UNDERSLABUS
UNDERWATERUW
VOLTV
VOLT-AMPEREVA
WATTW
WEATHER-RESISTANTWR
WEATHER-RESISTANT, IN-USEWRI
ELECTRICAL LEGEND
GENERAL
PANEL
HOT LEG
HOT LEG WITH NEUTRAL
HOT LEG WITH GROUND
SWITCH LEG
THREE-WAY CIRCUIT
CIRCUIT HOME RUN
POWER
NON-FUSED DISCONNECT
TRANSFORMER
120V DUPLEX RECEPTACLE
120V QUAD RECEPTACLE
240V RECEPTACLE
RECEPTACLE WITH GROUND FAULT CIRCUIT INTERRUPTER
RECEPTACLE, IN-FLOOR BOX & COVER
WEATHER-RESISTANT RECEPTACLE, IN-USE, METAL,
HEAVY-DUTY, WITH GROUND FAULT CIRCUIT INTERRUPTER
ABOVE COUNTER RECEPTACLE, COORDINATE WITH
ARCHITECTURE
UNDER COUNTER RECEPTACLE, COORDINATE WITH
ARCHITECTURE
DATA / TELEPHONE - STUB UP CONDUIT ABOVE WALL
TELEPHONE - STUB UP CONDUIT ABOVE WALL
JUNCTION BOX
NORMALLY CLOSED CONTACT
NORMALLY OPEN CONTACT
CONTACT
DELAY OFF
THERMOSTAT
TIMER
FUSE
LIGHTING
SWITCH
3 - 4 WAY SWITCH
DIMMER SWITCH
OCCUPANCY SENSOR SWITCH, TIME SETTING OF 30 MIN. UON
CEILING-MOUNTED OCCUPANCY SENSOR, TIME SETTING OF 30
MIN. UON - HATCHING ON PLANS INDICATES AIMING OF SENSOR
EXTERIOR PHOTO-ELECTRIC CELL SWITCH
WIRING COLOR CODE
COLORCONDUCTOR
120/208 (240)
BLACKPHASE A
REDPHASE B
BLUEPHASE C (3Φ ONLY)
WHITENEUTRAL
GREENGROUND
277/480
BROWNPHASE A
ORANGEPHASE B
YELLOWPHASE C (3Φ ONLY)
GRAYNEUTRAL
GREENGROUND
NOTES:
A. HATCHING ON PLANS INDICATES 24/7 LIGHT WIRED HOT TO CIRCUIT INDICATED ON PLANS B. HATCHING ON PLANS INDICATES ILLUMINATED SIDES OF LIGHT - SEE PLANS FOR CHEVRONS
LIGHTING FIXTURE SCHEDULE
VOLTNOTES WATTSDESCRIPTIONLAMPMODELMANUFACTURERLABEL S
1SBP3040L8CS-4-UNV-DIM-FSSIGNIFYA
F14
1'x4' LINEAR FIXTURE W/ SURFACELED
MOUNT KIT
12033
12010CAN LIGHTLEDSD7RSLMZ10SCTUWSIGNIFYB
CEILING FAN W/ LIGHT KIT COORDINATELEDC
WITH OWNER
12030
EXIT/ EMERGENCY W/ BATTERYLEDCLR2WSIGNIFYE
BACKUP
1200UP/DOWN WALL SCONCELEDW
EXIT LIGHT W/ BATTERY BACKUPLEDOL2-SA-LR-WSIGNIFYX
COORDINATE SIDES AND CHAMFERS
WITH PLANS
ELECTRICAL NOTES
APPLICABLE CODES INCLUDE, BUT ARE NOT RESTRICTED T1 O, THE LATEST ADOPTED VERSIONS OF THE FOLLOWING CODES AT THE TIME OF THE
PLAN DATE:
- NFPA 70 NATIONAL ELECTRIC CODE
- INTERNATIONAL BUILDING CODE
- UL UNDERWRITERS LABORATORY
- NEMA
ELECTRICAL SYSTEM(S) SHALL BE INSTALLED COMPLETE W2 ITH ALL WORK, MATERIALS, AND EQUIPMENT CUSTOMARILY CONSIDERED PART OF
SUCH WORK FOR A FULLY OPERATIONAL, COMPLETE, AND CODE COMPLIANT SYSTEM.
PLANS ARE DIAGRAMMATIC AND ARE PROVIDED ONLY TO SH3 OW GENERAL SYSTEM. CONTRACTOR SHALL CONSIDER ACTUAL FIELD CONDITIONS DURING INSTALLATION. ANY GROSS INTERFERENCE SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER BEFORE CONTINUING.
ALL ELECTRICAL CONNECTIONS SHALL BE MOUNTED ABOVE4 ELECTRICAL DATUM PLANE.
COORDINATE FINAL LOCATIONS OF ALL SWITCHES AND OUT5 LETS WITH OWNER. OWNER SHALL RETAIN RIGHT TO MAKE MINOR LOCATION
ADJUSTMENTS PRIOR TO EQUIPMENT INSTALLATION WITHOUT ADDITIONAL COST.
ALL 3Φ CIRCUITS SHALL HAVE A-B-C PHASE ROTATION. A6 LL 3Φ ELECTRICAL SWITCHGEAR, SWITCHBOARDS, MCC’S, AND SIMILAR EQUIPMENT SHALL HAVE A-B-C PHASE ROTATION FROM LEFT TO RIGHT. REFER TO THE POWER WIRING COLOR CODE ON THIS SHEET.
VERIFY AVAILABLE CIRCUIT CURRENT WITH ELECTRICAL P7 OWER SUPPLIER.
PROVIDE COMPLETE AND COMPLIANT EQUIPMENT AND SYSTE8 M GROUNDING THROUGHOUT ELECTRICAL INSTALLATION. INSTALL BONDING
JUMPERS TO OUTLET BOXES IN METALLIC CONDUIT SYSTEMS.
UNLESS OTHERWISE NOTED, EACH CONDUIT OR RACEWAY SH9 ALL CONTAIN ONLY A SINGLE CIRCUIT.
ALL EXTERIOR EQUIPMENT SHALL BE NEMA 3R RAINTIGHT10 .
WITH ALL LIGHTING AND MOTOR LOADS OPERATING, CONT11 RACTOR SHALL VERIFY THAT THE PHASE BALANCE IN EACH PANEL IS WITHIN 5%.
COMPLETE ELECTRICAL SYSTEMS SHALL BE TESTED FOR C12 OMPLIANCE AND FUNCTION IN ACCORDANCE WITH LOCAL INSPECTIONS AND
NATIONAL CODES.
CONTRACTOR SHALL INSTALL EXPANSION AND DEFLECTION13 CONDUIT FITTINGS PER NEC 300.7(B), PLANS, AND SPECIFICATIONS.
THE AMPACITY, VOLTAGE, AND PHASE OF ALL DISCONNEC14 TS SHALL BE RATED PER THE SPECIFIED CIRCUIT AND UPSTREAM OVERCURRENT PROTECTION UON. THE ENCLOSURE NEMA RATING SHALL BE COORDINATED AS REQUIRED BY THE ENVIRONMENT.
IF DISCREPANCIES EXIST WITHIN THE PLANS AND/OR SP15 ECIFICATIONS, THE MOST STRINGENT SHALL APPLY AND SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO BRING IT TO THE ATTENTION OF THE ENGINEER BEFORE WORK IS STARTED OR MATERIAL/EQUIPMENT IS ORDERED.
THE PLANS AND SPECIFICATIONS FOR THIS WORK HAVE B16 EEN PREPARED WITH THE INTENT TO BE AS ACCURATE AND COMPLETE AS PRACTICAL, BUT ERRORS, OMISSIONS, AND CONFLICTS MAY EXIST. PRIOR TO SUBMITTING A BID FOR CONSTRUCTING THE WORK, THE CONTRACTOR SHALL REVIEW THE PLANS AND SPECIFICATIONS IN DETAIL. ANY QUESTIONS OR COMMENTS SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER PRIOR TO SUBMITTING A BID. BY SUBMITTING A BID FOR THE WORK, THE CONTRACTOR ACKNOWLEDGES THAT HE HAS REVIEWED THE PLANS AND SPECIFICATIONS, UNDERSTANDS THE DESIGN INTENT, AND DOES NOT HAVE ANY FURTHER QUESTIONS OR COMMENTS.
CONTRACTOR SHALL FIELD VERIFY THAT ALL PARALLEL C17 ONDUCTOR RUNS OF SERVICE ENTRANCE OR FEEDER CONDUCTORS FOR EACH
CIRCUIT FOLLOW THE SAME PATH AND ARE OF EQUAL LENGTH.
CONTRACTOR SHALL BE RESPONSIBLE FOR ALL UTILITY F18 EES AND CHARGES FOR INSTALLATION AND UTILITY UPGRADES FOR PROJECT.
CONTRACTOR SHALL COORDINATE AND PAY FOR ALL PERMI19 TS, INSPECTION FEES, UTILITY FEES, AND UTILITY CHARGES FOR THIS PROJECT.
CONTRACTOR SHALL WARRANTY ALL SYSTEMS FOR PARTS,20 EQUIPMENT, MATERIAL, AND LABOR FOR A PERIOD OF ONE YEAR FROM THE DATE
OF SUBSTANTIAL COMPLETION.
THE OWNER AND/OR OWNER'S REPRESENTATIVE SHALL INS21 PECT THE INSTALLATION AT SUBSTANTIAL COMPLETION AND AT ONE YEAR FROM SUBSTANTIAL COMPLETION. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CORRECTIONS THAT DO NOT CONFORM TO THE CODE AND/OR
THE CONTRACT DOCUMENTS.
KELLEMS GRIPS SHALL BE INSTALLED SO THE GRIP IS A22 LIGNED WITH THE CABLE TO AVOID ANY PRESSURE POINTS ANYWHERE ALONG THE LENGTH OF THE GRIP. THIS INCLUDES INSTALLATION PROJECTS WHERE TIDAL ACTION MAY CHANGE THE ANGLE OF THE CABLE IN REFERENCE TO THE GRIP POSITION. THE CONTRACTOR SHALL BE RESPONSIBLE FOR OBSERVING AND MAKING ANY ADJUSTMENTS TO THE GRIP MOUNTING POSITION AND CABLE LENGTHS AS REQUIRED TO MITIGATE PRESSURE POINTS AT LOW AND HIGH TIDES. REFER TO PLANS AND DETAILS WHERE THE GRIPS ARE INDENDED TO BE INSTALLED. ALL KELLEMS GRIPS, SUPPORT CABLE, AND MOUNTING HARDWARE SHALL BE STAINLESS STEEL.
LABEL REQUIREMENTS:23
A. ALL ELECTRICAL EQUIPMENT SHALL BE AFFIXED WITH A PERMANENT LABEL STATING THE EQUIPMENT NAME, VOLTAGE AND PHASE CLASS, AMPACITY, AND WHERE THE EQUIPMENT IS FED FROM.
B. PANEL DIRECTORIES SHALL BE TYPED SHOWING EACH BRANCH BREAKER LOAD AS SHOWN IN THE PANEL SCHEDULES.
C. EACH SHORE POWER PEDESTAL SHALL BE LABELED WITH THE UPSTREAM CIRCUIT AND PANEL.
CONTRACTOR SHALL CARRY CONTINGENCY IN THE AMOUNT24 OF 10% OF BID.
SUBMITTAL REQUIREMENTS: CONTRACTOR SHALL PREPARE25 AND SUBMIT TO THE ENGINEER FOR REVIEW AND APPROVAL DETAILED PRODUCT INFORMATION ON ALL EQUIPMENT INCORPORATED IN THE PROJECT RELATED TO THE SPECIFIC CONTRACTOR TRADE. SUBMITTAL SHALL BE PROVIDED, AND ENGINEER SHALL REVIEW AND APPROVE, PRIOR TO EQUIPMENT PURCHASE. FOUR COPIES OF SUBMITTALS SHALL BE PROVIDED TO THE ENGINEER. TWO COPIES SHALL BE RETURNED TO THE CONTRACTOR. PRIOR TO SUBMITTAL, CONTRACTOR SHALL REVIEW AND CERTIFY BY SIGNATURE THE SUBMITTED EQUIPMENT MEETS SPECIFICATION. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL DIMENSIONS, FITTINGS, AND CONSTRUCTION FEATURES RELATIVE TO EQUIPMENT. APPROVAL OF SUBMITTAL INFORMATION BY THE ENGINEER ONLY REFERS TO MATERIALS, DESIGN, AND ADHERENCE TO SPECIFICATIONS.
• ALL NONMETALLIC MATERIAL SHALL BE UV-RESISTANT
ELECTRICAL MATERIALS SCHEDULE - MARINA
REMARKSSTANDARDSMATERIALDESCRIPTION
WIRE / CABLE
600-VOLT#10 & SMALLER
THWN
THWN-2 AS NOTED
• SOLID OR STRANDED AS REQUIRED BY EQUIPMENTUL 83
MANUFACTURER
• TINNED SOFT
• DRAWN COPPER
• NOT FOR SUBMERSION
600-VOLT#8 & LARGER
THWN
THWN-2 AS NOTED
• STRANDEDUL 83
• TINNED SOFT
• DRAWN COPPER
105°CTYPE "W" / "G" / "G-GC" MARINE CABLE
2000-VOLT
• USE FOR UNDERWATER AND UNDERDECK FEEDERSUL 83
• STRANDED
• TINNED SOFT
• DRAWN COPPER
• EXTRA HARD USE
• SUN LIGHT RESISTANT
• OIL, GAS, AND CHEMICAL RESISTANT
• PVC JACKET600-VOLTWET-LISTED MC CABLE
CONDUIT
• NOT FOR SUBMERSIONHH 9359GALVANIZED STEELRIGID
• USE SCHEDULE 40 INEMA TC-2SCHEDULE 40 / 80 PVCPVC N PROTECTED DOCK STRUCTURE OR
UNDERGROUND / UNDERWATER / UNDERDECK
• USE SCHEDULE 80 ABOVE THE DECK AND ABOVE GROUND UP
TO 8' AND ABOVE
• ELECTRIC METALLHE 8141GALVANIZED DUCTILE STEELEMT IC TUBING - USE IN DRY LOCATIONS WITHIN
FLOATING BUILDINGS
LIQUIDTIGHT FLEXIBLELFNC
NONMETALLIC CONDUIT
• LISTED FOR DIRECT BURIAL - INSTALL WHERE NOT SUBJECT
TO PHYSICAL DAMAGE AND NOT ABOVE THE DECK
HIGH-DENSITYHDPE
POLYETHYLENE
• INSTALL UNDERGROUND FOR SERVICE AND FEEDER
CONDUCTORS WHERE NOT SUBJECT TO PHYSICAL DAMAGE
CONDUIT HANGERS / STRAPS
• 4'-0" O/C MAXIMUMGALVANIZED STEELUP TO 3/4"
• 6'-0" O/C MAXIMUM1" TO 1-1/4"
• 8'-0" O/C MAXIMUM1-1/2" & UP
CABLE SUPPORT
• COORDINATE SISTAINLESS STEEL"KELLEMS" CABLE GRIPS ZE AND STYLE FOR PROPER CABLE OR
CONDUIT
- ALL PARAMETERS SHALL BE PROGRAMMED PER THE DESIGN
- SEE CIRCUIT SCHEDULES FOR TRIP SETTINGS
- CT SENSORS SHALL BE SOLID CORE, AND THE CIRCULAR OPENING SHALL BE COORDINATED WITH THE SPECIFIED CONDUCTOR SIZE
- SHUNT TRIP OUTPUT CONTROL SHALL BE 120VAC
- EXTERNAL STROBE LIGHT TO FLASH UPON A GROUND FAULT ALARM
- SHALL BE UL 1053-LISTED
- TIME AND DATE SHALL BE SET FOR THE PROJECT LOCATION TIME ZONE
- SPARE CHANNELS SHALL BE DISABLED
- SHALL HAVE LOCKABLE DOOR
- USE SPECIFIED EQUIPMENT OR APPROVED EQUAL
- SEE GROUND FAULT MONITOR WIRING DETAIL
GROUND FAULT MONITOR SCHEDULE
NOTEENCLOSUREINPUTS / OUTPUTSMODELMANUFACTURERLABEL S
LISTED ASSEMBLYNEMA 4X1RCM420BENDERG1
LISTED ASSEMBLYNEMA 4X1RCM420BENDERG2
ROCK BOTTOM
GROUNDING ELECTRODE
CONDUCTORS
ALL CLAMPS
SUITABLE FOR
DIRECT BURIAL
OR EXOTHERMIC
WELD
-1
/2 F
T
-1
/2 F
T
MAXIMUM 45° ANGLE
EXOTHERMIC WELD,
TYPICAL
MACHINE-COMPACTED
SOIL 1
/1 E0.2
111213
/2 E0.2
EXIT
EXIT
5' MAX
4' 6" MIN
O R
A S
N O
T E
D
M A
X
M
IN
M
IN
M
IN
M A
X
M A
X
M
IN
M A
X
F I R E
F I R E
/4 E0.2
VARIES
AS
NEEDED
LIGHT BANK 2
LIGHT BANK 1
GND
COMMON
GND
GND
COMMON
OUT OUT
IN IN
HOT
GND
N
C1
R
LIGHTING
GND
GND
COMMON
GND
GND
COMMON
OUT OUT
IN IN
N
HOT
120V
CKT
GND
N
HOT
NO CONTACTOR
4-WAY
SWITCH
ADDITIONAL
4-WAYS
3-WAY
SWITCH
3-WAY
SWITCH
4-WAY
SWITCH
3-WAY
SWITCH
3-WAY
SWITCH
WITH CONTACTOR
ADDITIONAL
4-WAYS
120V
CKT 1
120V
CKT 2
OFTIS
AFFETTAFFETT
1 S JEFFERSON AVE, STE 101
COOKEVILLE, TN 38501
TEL: (931) 526-5143
www.maffett-loftis.com
ENGINEERING, LLC
P R
O J E
C T
T
IT
L E
S H
E E
T T
IT
L E
DATE REVISION
ISSUED FOR:
DATE:
PROJ NO.:
DESIGNED BY:
DRAWN BY:
REVIEWED BY:
SHEET NUMBER:
THE REPRODUCTION, COPYING
OR OTHER USE OF THIS DRAWING
WITHOUT WRITTEN CONSENT IS
PROHIBITED. © 2020 EDGEWATER
RESOURCES, LLC.
MLE PROJ NO.:
20-040
V E
N E
T
IA
N C
O V
E M
A R
IN
A
E L
E C
T R
IC
A
L U
P G
R A
D E
S L
E E
S B
U R
G
F L
NORTH
24024
E0.2
JLC
Issue Date
E L E
C T
R
IC
A L
D E
T A
IL
S
Project Status
NOT TO SCALEE0.2
1 GND ROD INSTALL. DTL
NOT TO SCALEE0.2
2 GROUND ROD DTL
NOT TO SCALEE0.2
3 GROUNDING DTL
NOT TO SCALEE0.2
5 DEVICE MOUNTING DTL
NOT TO SCALEE0.2
POWER/DATA
OUTLET DTL
NOT TO SCALEE0.2
3 & 4-WAY
LGT SWITCH WIRING DTL
NOT TO SCALEE0.2
7 BONDING DTL
NOT TO SCALEE0.2
8 GFM WIRING DTL
ELECTRICAL NOTES
NUMBERED NOTES
1 INSTALL GROUND ROD BELOW GROUND
FREEZING DEPTH. COORDINATE DEPTH
WITH AREA OF INSTALLATION.
2 GROUND ROD TO HAVE A MINIMUM OF 8'
IN CONTACT WITH UNDISTURBED EARTH.
3 UL LISTED UNDERGROUND EXOTHERMIC
WELD OR APPROVED CLAMP, TYP.
4 UL LISTED 5/8" Ø x 10' DRIVEN GROUND
ROD, TYP. COORDINATE LOCATION WITH
SITE. SEE REFERENCED DETAIL.
5 GROUNDING CONDUCTOR, TYP. SAME
SIZE AS GROUNDING ELECTRODE
CONDUCTOR.
6 GROUNDING ELECTRODE CONDUCTOR.
7 GROUND RODS TO BE INSTALLED IN A
TRIANGULAR PATTERN WITH MIN. 6'
APART, TYP.
8 VIRGIN EARTH.
9 FINISHED GRADE.
ELECTRICAL NOTES
NUMBERED NOTES
1 METAL FRAME OF BUILDING OR
MOUNTING STRUCTURE.
2 MAIN DISCONNECT.
3 SERVICE EQUIPMENT.
4 NEUTRAL BAR.
5 GROUNDING BAR.
6 GROUNDING PLATE OR BONDING POINT
AS REQUIRED.
7 WATER PIPING ON LOAD SIDE OF METER.
8 GAS PIPING ON LOAD SIDE OF METER.
9 FINISHED FLOOR.
10 FILL GRAVEL.
11 CONCRETE FOOTER.
12 CONCRETE-ENCASED ELECTRODE, 1/2" x
20' FOR NEW CONSTRUCTION.
13 GROUND ROD, SEE REFERENCED
DETAIL.
14 BONDING POINT.
15 GROUND BAR FOR LOW VOLTAGE
UTILITIES.
16 FINISHED GRADE.
17 GROUNDING ELECTRODE CONDUCTOR.
GENERAL NOTES
A SHALL BE PER NEC ARTICLE 250.
B ALL PROJECTS MAY NOT INCLUDE METAL
WATER PIPE, GAS LINE, OR METAL
CONSTRUCTION.
C CONFIGURATION OF SERVICE MAY
DIFFER, COORDINATE INSTALLATION.
ELECTRICAL NOTES
GENERAL NOTES
A WALL AND CEILING CONSTRUCTION DETAILS MAY
VARY, COORDINATE OUTLET INSTALLATION
REQUIREMENTS AT EACH LOCATION.
NUMBERED NOTES
1 2-1/2" DEEP BOX, THOMAS & BETTS OR EQUAL.
VERIFY SCREW HOLES OF COVERPLATE PRIOR TO
ORDERING.
2 COORDINATE WITH PLANS AND/OR OWNER FOR
QUANTITY AND SIZE OF CONDUITS.
3 RECEPTACLE WALL BOX WITH CONDUIT AS
REQUIRED.
4 FINISHED CEILING, COORDINATE WITH
ARCHITECTURAL REFLECTIVE CEILING PLAN.
5 WALL STUD.
6 COORDINATE THICKNESS OF WALL COVERING AT
EACH BOX LOCATION. EXTEND BOX FROM STUD TO
ACCOMMODATE THICKNESS OR USE APPROPRIATE
PLASTER RING.
7 COORDINATE POWER, PHONE, DATA, AND TV
COVERPLATES WITH OWNER.
8 DUPLEX RECEPTACLES SHALL BE BRYANT OR
HUBBEL NO. 56252, OR APPROVED EQUAL, RATED 20
AMP, 125 VOLTS, GROUNDING TYPE AS REQUIRED.
9 CAULK FIRE RATED CEILING AS NEEDED.
10 STUB CONDUIT ABOVE ACCESSIBLE CEILING 4" OR
ROUTE CONDUIT TO COMMUNICATION PANEL.
COORDINATE WITH ARCHITECT AND OWNER.
11 PULL STRING IN CONDUIT.
12 SCUFF GUARD.
ELECTRICAL NOTES
GENERAL NOTES
A MOUNTING HEIGHTS OF DEVICE BOXES MAY BE ADJUSTED IN MASONRY WALLS TO HAVE
TOP OR BOTTOM EDGE OF DEVICE TO LINE UP WITH A JOINT.
B SEE FLOOR PLANS FOR LOCATION OF DEVICES.
C FOR REFERENCE ONLY. NOT ALL DEVICES INCLUDED IN THIS PROJECT. COORDINATE WITH
PLANS.
NUMBERED NOTES
1 120V RECEPTACLE, TELEVISION OUTLET.
2 CLOCK, COORDINATE WITH ARCHITECTURAL AND POWER REQUIREMENTS.
3 EXIT AND/OR EMERGENCY LIGHTING.
4 SIDE APPROACH THERMOSTAT, COORDINATE WITH MECHANICAL.
5 LIGHT CONTROL DEVICES, SHALL BE MOUNTED 12" MAX FROM DOOR FRAME OR DOOR
SWING, COORDINATE WITH PLANS.
6 PULL STATION.
7 120V RECEPTACLES OR PHONE/DATA/TV OUTLET. REFER TO PLANS FOR ADJUSTED
HEIGHT AFF.
8 FIRE ALARM NOTIFICATION DEVICES MOUNTED 90" AFF OR BELOW 6" BELOW CEILING,
WHICHEVER IS LOWER.
9 DEVICES ABOVE COUNTERTOPS OR BACKSPLASHES, LABELED "A" ON PLAN VIEW.
10 COORDINATE CABINETRY WITH ARCHITECTURAL.
11 DEVICES UNDER CABINETS, LABELED "U" ON PLAN VIEW.
12 TYPICAL PANELBOARD.
13 NIGHT LIGHT.
14 NURSE CALL LIGHT.
15 NURSE CALL PULL CORD.
16 CEILING, COORDINATE HEIGHT WITH ARCHITECTURAL.
17 EQUIPMENT WORKSPACE.
18 HIGHEST BREAKER.
19 CONDUITS STUBBED ABOVE ACCESSIBLE CEILING OR ROUTE CONDUIT TO
COMMUNICATION PANEL, SEE REFERENCED DETAIL.
20 BATTERY PACK.
ELECTRICAL NOTES
NUMBERED NOTES
1 BONDING CONDUCTOR #3/0 GREEN
INSULATION COPPER CABLE, MSHA
ACCEPTED, WET LOCATIONS, RESISTANT
TO OILS, ACIDS, ALKALINES, AND
ABRASION-RESISTANT, OR 12" OF GREEN
TAPE AT EACH END. CONDUCTOR
STRAND SHALL BE MINIMUM OF 448/24
STRANDS. ALLOW ENOUGH SLACK IN
WIRE FOR STRUCTURE MOVEMENT AS
PRACTICAL. INSTALLATION LOCATION
SHALL BE SUCH THAT NO DAMAGE WILL
OCCUR TO CONDUCTOR DURING
STRUCTURE MOVEMENT.
2 (2) STAINLESS STEEL HEX BOLTS 5/16 - 18
MIN.
3 HEX STYLE CRIMP OR EQUAL, USING A
MINIMUM OF 14 TON CRIMP TOOL.
4 CLEAN STRUCTURE METAL BEHIND
CLAMP.
ELECTRICAL NOTES
NUMBERED NOTES
1 ELECTRICAL PANEL.
2 MAIN CIRCUIT BREAKER.
3 GROUND FAULT MONITOR (GFM),
COORDINATE WITH MANUFACTURER FOR
WIRING AND INSTALLATION
REQUIREMENTS. RED BEACON SHALL
FLASH UPON ALL CIRCUIT TRIPS DUE TO
GROUND FAULT ALARMS.
4 SHUNT TRIP BRANCH BREAKER, TYPICAL.
SEE PANEL SCHEDULE FOR SIZE.
5 GFM CURRENT SENSOR, TYPICAL. SIZE
PER WIRE AS SHOWN IN PANEL
SCHEDULE. HOT AND NEUTRAL
CONDUCTORS ROUTED THROUGH CT.
6 CURRENT SENSOR CONTROL WIRE,
TYIPCAL.
7 SHUNT TRIP CONTROL WIRE, TYPICAL.
8 TAP BUS ON LOAD SIDE OF THE MAIN
BREAKER AND RUN TO GFM. UTILIZE A
SUB-FEED LUG BLOCK OR SIMILAR
MEANS TO MAKE TAP. TERMINATE
CIRCUIT ON MANUFACTURER'S SUPPLIED
OVERCURRENT DEVICE. CIRCUIT
CONDUCTORS SHALL NOT EXTEND
LONGER THAN 10 FEET.
9 BRANCH CIRCUIT TO MARINA PEDESTAL,
TYPICAL.
GENERAL NOTES
A REFER TO GROUND FAULT MONITOR
SCHEDULE.
M
IN
M
IN
M
IN
ELECTRICAL
DATUM PLANE
WATER LEVEL NORMAL
POOL
HIGHEST WATER LEVEL
UNDER NORMAL
CIRCUMSTANCES
DOCK
ELECTRICAL
DATUM PLANE
DECK STRUCTURE
FLOATING FIXED
M
IN
HIGHEST WATER LEVEL
UNDER NORMAL CIRCUMSTANCES
ELECTRICAL
DATUM PLANE
LAND NOT SUBJECT TO TIDES
LAND
ELECTRICAL EQUIPMENT
ELECTRICAL EQUIPMENT
ELECTRICAL EQUIPMENT
/1 E0.3
PANEL
3" METAL ANGLE
ALUMINUM OR HOT DIPPED
GALVANIZED HOS, OR STAINLESS
STEEL WELDMENT
BOLTED TO DECK WITH
STAINLESS STEEL HARDWARE
CONDUIT
STRAP
DECK
CONDUIT
WORK
SPACE AS
REQUIRED
BY NEC
OFTIS
AFFETTAFFETT
1 S JEFFERSON AVE, STE 101
COOKEVILLE, TN 38501
TEL: (931) 526-5143
www.maffett-loftis.com
ENGINEERING, LLC
P R
O J E
C T
T
IT
L E
S H
E E
T T
IT
L E
DATE REVISION
ISSUED FOR:
DATE:
PROJ NO.:
DESIGNED BY:
DRAWN BY:
REVIEWED BY:
SHEET NUMBER:
THE REPRODUCTION, COPYING
OR OTHER USE OF THIS DRAWING
WITHOUT WRITTEN CONSENT IS
PROHIBITED. © 2020 EDGEWATER
RESOURCES, LLC.
MLE PROJ NO.:
20-040
V E
N E
T
IA
N C
O V
E M
A R
IN
A
E L
E C
T R
IC
A
L U
P G
R A
D E
S L
E E
S B
U R
G
F L
NORTH
24024
E0.3
JLC
Issue Date
E L E
C T
R
IC
A L
D E
T A
IL
S
Project Status
NOT TO SCALEE0.3
ELECTRICAL
DATUM PLANE DTL
NOT TO SCALEE0.3
EQUIPMENT
BONDING DTL
NOT TO SCALEE0.3
MARINA
POST MOUNT DTL
ELECTRICAL NOTES
GENERAL NOTES
A ALL ELECTRICAL CONNECTIONS (WITH
EXCEPTION TO GROUND BONDING TO
DOCK STRUCTURE), ON FLOATING OR
FIXED PIERS, SHALL BE ABOVE THE
ELECTRICAL DATUM PLANE. BOTTOMS
OF TRANSFORMERS SHALL NOT BE
BELOW THE ELECTRICAL DATUM PLANE.
ELECTRICAL NOTES
NUMBERED NOTES
1 BOND METAL DOCK STRUCTURE TO
GROUND BUS OF EQUIPMENT.
2 ELECTRICAL EQUIPMENT.
3 SUPPORT STRUCTURE.
4 DECK.
5 DOCK STRUCTURE.
6 WATER LEVEL.
7 ELECTRICAL DATUM PLANE, SEE
REFERENCED DETAIL.
E1.2
E1.2
E1.3
E1.3
OFTIS
AFFETTAFFETT
1 S JEFFERSON AVE, STE 101
COOKEVILLE, TN 38501
TEL: (931) 526-5143
www.maffett-loftis.com
ENGINEERING, LLC
P R
O J E
C T
T
IT
L E
S H
E E
T T
IT
L E
DATE REVISION
ISSUED FOR:
DATE:
PROJ NO.:
DESIGNED BY:
DRAWN BY:
REVIEWED BY:
SHEET NUMBER:
THE REPRODUCTION, COPYING
OR OTHER USE OF THIS DRAWING
WITHOUT WRITTEN CONSENT IS
PROHIBITED. © 2020 EDGEWATER
RESOURCES, LLC.
MLE PROJ NO.:
20-040
V E
N E
T
IA
N C
O V
E M
A R
IN
A
E L
E C
T R
IC
A
L U
P G
R A
D E
S L
E E
S B
U R
G
F L
NORTH
24024
E1.0
JLC
Issue Date
E L
E C
T R
IC
A
L S
IT
E
P L A
N
Project Status
SCALE: 1" = 30'-0" (WHEN PRINTED FULL SCALE ON 24"X36")E1.0
1 ELECTRICAL SITE PLAN
0' 10' 20' 40' 80'
ELECTRICAL NOTES
A
A
T
B F
P
OS
OS
O S
O S
O S
O S
OS
OS
OS
W W
W W
W
B F
P
P1
G1
P1-6
P1-11
P1-13,15
P1-14
P1-16
P1-8
P1-9
HP-1
P1-10,12 P1-17,19
WH
AA
AA
BBB
B B
B
B B
B B
B B
B
B B
B
B
B B
B
B B
BB
B
E
E
X
X
X
P1-2
P1-4
E
E
E
OFTIS
AFFETTAFFETT
1 S JEFFERSON AVE, STE 101
COOKEVILLE, TN 38501
TEL: (931) 526-5143
www.maffett-loftis.com
ENGINEERING, LLC
P R
O J E
C T
T
IT
L E
S H
E E
T T
IT
L E
DATE REVISION
ISSUED FOR:
DATE:
PROJ NO.:
DESIGNED BY:
DRAWN BY:
REVIEWED BY:
SHEET NUMBER:
THE REPRODUCTION, COPYING
OR OTHER USE OF THIS DRAWING
WITHOUT WRITTEN CONSENT IS
PROHIBITED. © 2020 EDGEWATER
RESOURCES, LLC.
MLE PROJ NO.:
20-040
V E
N E
T
IA
N C
O V
E M
A R
IN
A
E L
E C
T R
IC
A
L U
P G
R A
D E
S L
E E
S B
U R
G
F L
NORTH
24024
E1.1
JLC
Issue Date
S H
IP
S
T O
R E
E L
E C
T R
IC
A
L P
L A
N S
Project Status
SCALE: 1/4" = 1'-0" (WHEN PRINTED FULL SCALE ON 24"X36")E1.1
1 ELECTRICAL POWER PLAN
ELECTRICAL NOTES
NORTH0' 2' 4' 8' 16' 0' 2' 4' 8' 16' NORTH
SCALE: 1/4" = 1'-0" (WHEN PRINTED FULL SCALE ON 24"X36")E1.1
2 ELECTRICAL LIGHTING PLAN
gary Arrow gary Cloud gary Text Box Seem to be dark in most spaces gary Cloud gary Cloud gary Length Measurement 3'-3" gary Length Measurement 3'-7 1/2" gary Callout Lights need to be centered in room gary Text Box This stall is dark gary Callout shadow at sink gary Text Box same comments gary Callout hide gary Callout hide gary Arrow gary Cloud gary Cloud gary Cloud
P2P2-1,3 P2-5,7
P2-6,8 P2-2,4
G2
POST
MOUNT
SEE DTL
3 / E0.3
P2-9,11 P2-10,12 P2-13,15
P2-17,19 P2-14,16P2-18,20
OFTIS
AFFETTAFFETT
1 S JEFFERSON AVE, STE 101
COOKEVILLE, TN 38501
TEL: (931) 526-5143
www.maffett-loftis.com
ENGINEERING, LLC
P R
O J E
C T
T
IT
L E
S H
E E
T T
IT
L E
DATE REVISION
ISSUED FOR:
DATE:
PROJ NO.:
DESIGNED BY:
DRAWN BY:
REVIEWED BY:
SHEET NUMBER:
THE REPRODUCTION, COPYING
OR OTHER USE OF THIS DRAWING
WITHOUT WRITTEN CONSENT IS
PROHIBITED. © 2020 EDGEWATER
RESOURCES, LLC.
MLE PROJ NO.:
20-040
V E
N E
T
IA
N C
O V
E M
A R
IN
A
E L
E C
T R
IC
A
L U
P G
R A
D E
S L
E E
S B
U R
G
F L
NORTH
24024
E1.2
JLC
Issue Date
M A
R
IN
A P
O W
E R
P L A
N A
B
Project Status
SCALE: 1" = 10'-0" (WHEN PRINTED FULL SCALE ON 24"X36")E1.2
1 PART A POWER PLAN
SCALE: 1" = 10'-0" (WHEN PRINTED FULL SCALE ON 24"X36")E1.2
2 PART B POWER PLAN
0' 5' 10' 20' 40'
0' 5' 10' 20' 40'
ELECTRICAL NOTES
gary Cloud gary Callout Hide waterline gary Callout Hide waterline
PC
PC-5,7
PC-2,4
PC-6,8
PC-1,3
POST MOUNT
SEE DTL
3 / E0.3
PD
PD-9,11PD-5,7
PD-6,8
PD-1,3
PD-2,4
POST MOUNT
SEE DETAIL
3 / E0.3
OFTIS
AFFETTAFFETT
1 S JEFFERSON AVE, STE 101
COOKEVILLE, TN 38501
TEL: (931) 526-5143
www.maffett-loftis.com
ENGINEERING, LLC
P R
O J E
C T
T
IT
L E
S H
E E
T T
IT
L E
DATE REVISION
ISSUED FOR:
DATE:
PROJ NO.:
DESIGNED BY:
DRAWN BY:
REVIEWED BY:
SHEET NUMBER:
THE REPRODUCTION, COPYING
OR OTHER USE OF THIS DRAWING
WITHOUT WRITTEN CONSENT IS
PROHIBITED. © 2020 EDGEWATER
RESOURCES, LLC.
MLE PROJ NO.:
20-040
V E
N E
T
IA
N C
O V
E M
A R
IN
A
E L
E C
T R
IC
A
L U
P G
R A
D E
S L
E E
S B
U R
G
F L
NORTH
24024
E1.3
JLC
Issue Date
M A
R
IN
A P
O W
E R
P L A
N C
D
Project Status
0' 5' 10' 20' 40'
0' 5' 10' 20' 40'
ELECTRICAL NOTES
SCALE: 1" = 10'-0" (WHEN PRINTED FULL SCALE ON 24"X36")E1.3
1 PART C POWER PLAN
SCALE: 1" = 10'-0" (WHEN PRINTED FULL SCALE ON 24"X36")E1.3
2 PART D POWER PLAN
gary Cloud gary Callout Ped's shifted gary Cloud
OFTIS
AFFETTAFFETT
1 S JEFFERSON AVE, STE 101
COOKEVILLE, TN 38501
TEL: (931) 526-5143
www.maffett-loftis.com
ENGINEERING, LLC
P R
O J E
C T
T
IT
L E
S H
E E
T T
IT
L E
DATE REVISION
ISSUED FOR:
DATE:
PROJ NO.:
DESIGNED BY:
DRAWN BY:
REVIEWED BY:
SHEET NUMBER:
THE REPRODUCTION, COPYING
OR OTHER USE OF THIS DRAWING
WITHOUT WRITTEN CONSENT IS
PROHIBITED. © 2020 EDGEWATER
RESOURCES, LLC.
MLE PROJ NO.:
20-040
V E
N E
T
IA
N C
O V
E M
A R
IN
A
E L
E C
T R
IC
A
L U
P G
R A
D E
S L
E E
S B
U R
G
F L
NORTH
24024
E3.1
JLC
Issue Date
E L
E C
T R
IC
A
L R
IS
E
R A
N D
P A
N E
L S
C H
E D
U L
E S
Project Status
5. TAP BLOCK
4. 30mA GFPE
3. SHUNT TRIP - REFER TO GFM WIRING DETAIL
2. COMBINATION AFCI
1. GFCI BREAKER A. CONTINUOUS METAL RACEWAY
BREAKER NOTES (REFERENCED IN NOTES COLUMN): CIRCUIT NOTES (REFERENCED IN NOTES COLUMN):
TOTAL EST. DEMAND: 192 A
Maint. Recpt. 13.7 kVA 86.55% 11.8 kVA TOTAL CONN.: 199 A
Non-Continuous 29.5 kVA 100.00% 29.5 kVA TOTAL EST. DEMAND (kVA): 46.1 kVA
Continuous 0.6 kVA 125.00% 0.8 kVA TOTAL CONN. LOAD (kVA): 47.8 kVA
Receptacle 4.0 kVA 100.00% 4.0 kVA
LOAD CLASSIFICATION CONNECTED (kVA) DEMAND FACTOR EST. DEMAND (kVA) PANEL TOTALS
TOTAL LOAD: 23.8 kVA 24.1 kVA
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
25 26
23 24
21 22
19 12.0 20
0 A 2 WATER HEATER
17 12.0 0.1 18 G1 5 A20 1 0 A
15 2.2 1.1 16 RECEPTION RECPTS A20 1 20 A
30 A 2 B30 AHU-1
13 2.2 0.5 14 EXTERIOR RECPT A20 1 20 A
20 A 1 A20 OFFICE RECPTS 11 0.7 0.6 12
20 A 1 A20 CORRIDOR RECPTS 9 0.5 0.6 10
MINI-SPLIT B20 2 15 A
7 0.4 8 MEN'S RESTROOM RECPT A20 1 20 A
-- 1 - EXTRA POLE FOR SHUNT TRIP - 5 -- 0.7 6 OFFICE RECPTS A20 1 20 A
3 6.9 0.3 4 RESTROOMS & JANOTOR LIGHTING A20 1 20 A
200 A 2 B200 3 P2
1 6.9 0.2 2 OFFICES & STORAGE LIGHTING A20 1 20 A
TRIP
AMPS POLES FEED NOTES CIRCUIT DESCRIPTION CKT A B CKT CIRCUIT DESCRIPTION NOTES FEED POLES
TRIP
AMPS
ENCLOSURE: TYPE 1 VOLTS: 120/240 1Φ,3-WIRE MCB RATING: 400 A
MOUNTING: SURFACE PANEL NOTES: MAINS RATING: 400 A
SUPPLY FROM: MODEL: NQ MAINS TYPE: MCB
LOCATION: MANUFACTURER: SQUARE D A.I.C. RATING: COORDINATE
BRANCH PANEL: P1
5. TAP BLOCK
4. 30mA GFPE
3. SHUNT TRIP - REFER TO GFM WIRING DETAIL
2. COMBINATION AFCI
1. GFCI A. CONTINUOUS METAL RACEWAY
BREAKER NOTES (REFERENCED IN NOTES COLUMN): CIRCUIT NOTES (REFERENCED IN NOTES COLUMN):
TOTAL EST. DEMAND: 50 A
TOTAL CONN.: 58 A
TOTAL EST. DEMAND (kVA): 12.1 kVA
Maint. Recpt. 13.7 kVA 86.55% 11.8 kVA TOTAL CONN. LOAD (kVA): 13.9 kVA
Continuous 0.2 kVA 125.00% 0.2 kVA
LOAD CLASSIFICATION CONNECTED (kVA) DEMAND FACTOR EST. DEMAND (kVA) PANEL TOTALS
TOTAL LOAD: 6.9 kVA 6.9 kVA
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
-- 1 - EXTRA POLE FOR SHUNT TRIP - 25 -- -- 26 - EXTRA POLE FOR SHUNT TRIP - 1 --
23 1.5 1.8 24
100 A 2 B100 5 PC
21 1.5 1.8 22
PD 5 B100 2 100 A
19 0.4 0.4 20
20 A 2 B20 4 RECEPTACLES
17 0.4 0.4 18
RECEPTACLES 4 B20 2 20 A
15 0.4 0.4 16
20 A 2 B20 4 RECEPTACLES
13 0.4 0.4 14
RECEPTACLES 4 B20 2 20 A
11 0.4 0.4 12
20 A 2 B20 4 RECEPTACLES
9 0.4 0.4 10
RECEPTACLES 4 B20 2 20 A
7 0.4 0.4 8
20 A 2 B20 4 RECEPTACLES
5 0.4 0.4 6
RECEPTACLES 4 B20 2 20 A
3 0.4 0.4 4
20 A 2 B20 4 RECEPTACLES
1 0.4 0.4 2
RECEPTACLES 4 B20 2 20 A
TRIP
AMPS POLES FEED NOTES CIRCUIT DESCRIPTION CKT A B CKT CIRCUIT DESCRIPTION NOTES FEED POLES
TRIP
AMPS
ENCLOSURE: NEMA 3R VOLTS: 120/240 1Φ,3-WIRE MCB RATING: 200 A
MOUNTING: SURFACE PANEL NOTES: MAINS RATING: 200 A
SUPPLY FROM: P1 MODEL: NQ MAINS TYPE: MCB
LOCATION: MANUFACTURER: SQUARE D A.I.C. RATING: COORDINATE
BRANCH PANEL: P2
CIRCUIT SCHEDULE
CKT # DESCRIPTION VD %
GFPE
TRIP (mA)
GFPE
TIME (ms)
1,3 P2 0.60% 90-100 400
2 OFFICES & STORAGE
LIGHTING
0.21% N/A N/A
4 RESTROOMS & JANOTOR
LIGHTING
0.51% N/A N/A
6 OFFICE RECPTS 0.94% N/A N/A
8 MEN'S RESTROOM RECPT 0.55% N/A N/A
9 CORRIDOR RECPTS 0.73% N/A N/A
10,12 MINI-SPLIT 0.55%
11 OFFICE RECPTS 0.67% N/A N/A
13,15 AHU-1 1.00% N/A N/A
14 EXTERIOR RECPT 0.91% N/A N/A
16 RECEPTION RECPTS 1.21% N/A N/A
17,19 WATER HEATER 1.94%
18 G1 0.07% N/A N/A
CIRCUIT SCHEDULE
CKT # DESCRIPTION VD %
GFPE
TRIP (mA)
GFPE
TIME (ms)
1,3 RECEPTACLES 0.79% 30 N/A
2,4 RECEPTACLES 0.81% 30 N/A
5,7 RECEPTACLES 0.40% 30 N/A
6,8 RECEPTACLES 0.44% 30 N/A
9,11 RECEPTACLES 0.85% 30 N/A
10,12 RECEPTACLES 1.22% 30 N/A
13,15 RECEPTACLES 1.58% 30 N/A
14,16 RECEPTACLES 1.55% 30 N/A
17,19 RECEPTACLES 1.18% 30 N/A
18,20 RECEPTACLES 0.84% 30 N/A
21,23 PC 0.87% 90-100 400
22,24 PD 1.55% 90-100 400
5. TAP BLOCK
4. 30mA GFPE
3. SHUNT TRIP - REFER TO GFM WIRING DETAIL
2. COMBINATION AFCI
1. GFCI A. CONTINUOUS METAL RACEWAY
BREAKER NOTES (REFERENCED IN NOTES COLUMN): CIRCUIT NOTES (REFERENCED IN NOTES COLUMN):
TOTAL EST. DEMAND: 12 A
TOTAL CONN.: 12 A
TOTAL EST. DEMAND (kVA): 2.9 kVA
Maint. Recpt. 2.9 kVA 100.00% 2.9 kVA TOTAL CONN. LOAD (kVA): 2.9 kVA
Continuous 0.0 kVA 125.00% 0.1 kVA
LOAD CLASSIFICATION CONNECTED (kVA) DEMAND FACTOR EST. DEMAND (kVA) PANEL TOTALS
TOTAL LOAD: 1.5 kVA 1.5 kVA
23 24
21 22
19 20
17 18
15 16
13 14
11 12
9 10
7 0.4 0.4 8
20 A 2 A20 4 RECEPTACLES
5 0.4 0.4 6
RECEPTACLES 4 A20 2 20 A
3 0.4 0.4 4
20 A 2 A20 4 RECEPTACLES
1 0.4 0.4 2
RECEPTACLES 4 A20 2 20 A
TRIP
AMPS POLES FEED NOTES CIRCUIT DESCRIPTION CKT A B CKT CIRCUIT DESCRIPTION NOTES FEED POLES
TRIP
AMPS
ENCLOSURE: NEMA 3R VOLTS: 120/240 1Φ,3-WIRE MCB RATING: 100 A
MOUNTING: SURFACE PANEL NOTES: MAINS RATING: 100 A
SUPPLY FROM: P2 MODEL: NQ MAINS TYPE: MCB
LOCATION: MANUFACTURER: SQUARE D A.I.C. RATING: COORDINATE
BRANCH PANEL: PC
5. TAP BLOCK
4. 30mA GFPE
3. SHUNT TRIP - REFER TO GFM WIRING DETAIL
2. COMBINATION AFCI
1. GFCI A. CONTINUOUS METAL RACEWAY
BREAKER NOTES (REFERENCED IN NOTES COLUMN): CIRCUIT NOTES (REFERENCED IN NOTES COLUMN):
TOTAL EST. DEMAND: 15 A
TOTAL CONN.: 15 A
TOTAL EST. DEMAND (kVA): 3.7 kVA
Maint. Recpt. 3.6 kVA 100.00% 3.6 kVA TOTAL CONN. LOAD (kVA): 3.7 kVA
Continuous 0.1 kVA 125.00% 0.1 kVA
LOAD CLASSIFICATION CONNECTED (kVA) DEMAND FACTOR EST. DEMAND (kVA) PANEL TOTALS
TOTAL LOAD: 1.8 kVA 1.8 kVA
23 24
21 22
19 20
17 18
15 16
13 14
11 0.4 12
20 A 2 A20 4 RECEPTACLES
9 0.4 10
7 0.4 0.4 8
20 A 2 A20 4 RECEPTACLES
5 0.4 0.4 6
RECEPTACLES 4 A20 2 20 A
3 0.4 0.4 4
20 A 2 A20 4 RECEPTACLES
1 0.4 0.4 2
RECEPTACLES 4 A20 2 20 A
TRIP
AMPS POLES FEED NOTES CIRCUIT DESCRIPTION CKT A B CKT CIRCUIT DESCRIPTION NOTES FEED POLES
TRIP
AMPS
ENCLOSURE: NEMA 3R VOLTS: 120/240 1Φ,3-WIRE MCB RATING: 100 A
MOUNTING: SURFACE PANEL NOTES: MAINS RATING: 100 A
SUPPLY FROM: P2 MODEL: NQ MAINS TYPE: MCB
LOCATION: MANUFACTURER: SQUARE D A.I.C. RATING: COORDINATE
BRANCH PANEL: PD
CIRCUIT SCHEDULE
CKT # DESCRIPTION VD %
GFPE
TRIP (mA)
GFPE
TIME (ms)
1,3 RECEPTACLES 0.36% 30 N/A
2,4 RECEPTACLES 0.32% 30 N/A
5,7 RECEPTACLES 0.35% 30 N/A
6,8 RECEPTACLES 0.39% 30 N/A
CIRCUIT SCHEDULE
CKT # DESCRIPTION VD %
GFPE
TRIP (mA)
GFPE
TIME (ms)
1,3 RECEPTACLES 0.39% 30 N/A
2,4 RECEPTACLES 0.36% 30 N/A
5,7 RECEPTACLES 0.32% 30 N/A
6,8 RECEPTACLES 0.33% 30 N/A
9,11 RECEPTACLES 0.65% 30 N/A
MECHANICAL LEGEND
SUPPLY DIFFUSER
RETURN AIR GRILLE
SUPPLY / RETURN SIDEWALL GRILLE
X" x X"
XXX CFM
A
DIFFUSER / GRILLE CALLOUT
CONNECTION SIZE
AIRFLOW IN CFM
FD FIRE DAMPER - FUSABLE LINK @ 165°F
XX-1 SCHEDULED ITEM LABEL
T THERMOSTAT
SUPPLY DUCT
FLEX DUCT
RETURN DUCT
MANUAL DAMPER
OUTSIDE AIR DUCT
EXHAUST DUCT
NUMBERED NOTES
GROUND MOUNTED CONDENSING UNIT
CONCRETE EQUIPMENT PAD. MIN. 4"
ABOVE FINISH GRADE.
MOUNT DISCONNECT SWITCH ON
EXTERIOR WALL OF BUILDING
INSULATED REFRIGERANT SUCTION
PIPING. ROUTE IN PLUMB AND SQUARE
FASHION. CONFIGURE SO TO MINIMIZE
LENGTH EXTERIOR TO BUILDING.
INSULATED REFRIGERANT LIQUID
PIPING. ROUTE IN PLUMB AND SQUARE
FASHION. CONFIGURE SO TO MINIMIZE
LENGTH EXTERIOR TO BUILDING.
UNIT ELECTRICAL FEEDER PER NEC.
ROUTE IN PLUMB AND SQUARE
FASHION. CONFIGURED SO TO
MINIMIZE LENGTH EXTERIOR TO
BUILDING. FEEDER BY MECH.
CONTRACTOR.
STRAPPING PER NEC.
SEAL PENETRATION THROUGH
BUILDING EXTERIOR.
COVER REFRIGERANT PIPING WITH
18GA GALVANIZED COVER.
UNIT ELECTRICAL CONNECTION BOX.
VERTICAL SPLIT SYSTEM AIR HANDLER.
SUPPLY DUCT
RETURN DUCT
OUTSIDE AIR DUCT WITH BALANCING
DAMPER.
RETURN PLENUM BOX.
CONDENSATE TRAP AND DRAIN.
FLEXIBLE DUCT CONNECTION.
FILTER RACK WITH AIR TIGHT, HINGED
ACCESS DOOR. SUPPORT CHANNELS
MUST BE WITHIN 1/4" OF FILTER SIZE
AND PROVIDE CONTINUOUS SUPPORT.
FILTER SHALL BE ACCESSIBLE
WITHOUT THE USE OF TOOLS. SIZE
FILTER FOR A MAXIMUM AIR VELOCITY
OF 400 FPM.
DRIP PAN WITH FLOAT SWITCH TO
SHUT-DOWN UNIT.
REFRIGERANT LINES.
SMOKE DETECTOR
SLEEVE FOR EQUIPMENT LITERATURE.
NUMBERED NOTES
S
OFTIS
AFFETTAFFETT
1 S JEFFERSON AVE, STE 101
COOKEVILLE, TN 38501
TEL: (931) 526-5143
www.maffett-loftis.com
ENGINEERING, LLC
P R
O J E
C T
T
IT
L E
S H
E E
T T
IT
L E
DATE REVISION
ISSUED FOR:
DATE:
PROJ NO.:
DESIGNED BY:
DRAWN BY:
REVIEWED BY:
SHEET NUMBER:
THE REPRODUCTION, COPYING
OR OTHER USE OF THIS DRAWING
WITHOUT WRITTEN CONSENT IS
PROHIBITED. © 2020 EDGEWATER
RESOURCES, LLC.
MLE PROJ NO.:
20-040
V E
N E
T
IA
N C
O V
E M
A R
IN
A
E L
E C
T R
IC
A
L U
P G
R A
D E
S L
E E
S B
U R
G
F L
NORTH
24024
M0.1
JBN
Issue Date
M E
C H
A N
IC
A
L N
O T
E S
A N
D S
C H
E D
U L E
S
Project Status
SPECIFIC HVAC NOTES:
1. INDOOR SUMMER DESIGN TEMPERATURE - 72°F
INDOOR WINTER DESIGN TEMPERATURE - 68°F
OUTDOOR SUMMER DESIGN TEMPERATURE - 95°F DB / 78°F WB
OUTDOOR WINTER DESIGN TEMPERATURE - 0°F
VENTILATION PER ASHRAE 62
2. A SMOKE DETECTOR DESIGNED TO SHUT DOWN THE SUPPLY FAN
IN CASE OF FIRE SHALL BE INSTALLED IN EACH AIR HANDLER
RETURN DUCT. UNITS OVER 2,000 CFM SHALL HAVE SUPPLY DUCT
DETECTORS.
3. DUCT SMOKE DETECTORS SHALL BE SUPPLIED BY THE FIRE
ALARM CONTRACTOR AND INSTALLED BY THE MECHANICAL
CONTRACTOR. IF THE BUILDING DOES NOT HAVE A CENTRAL FIRE
ALARM SYSTEM, AND THE DUCT SMOKE DETECTORS ARE STAND
ALONE UNITS FOR FAN SHUT DOWN ONLY, THE MECHANICAL
CONTRACTOR SHALL PROVIDE AND INSTALL THE DETECTORS.
4. ALL EXPOSED REFRIGERATION PIPING SHALL BE COVERED AND
PROTECTED WITH ALUMINUM OR GALV SHEET METAL CLADDING.
5. ROUTE REFRIGERANT PIPING CONCEALED AS PRACTICAL. WHEN
EXPOSED, ROUTE PIPING IN A NEAT, SQUARE, AND TRUE FASHION.
6. INSTALL REFRIGERATION PIPING CONSIDERING MANUFACTURERS
RECOMMENDATIONS. SIZE AND DEVELOPED LENGTH OF PIPING
SHALL BE CONSISTENT WITH MANUFACTURERS ALLOWANCE.
TAKE HEIGHT AND RELATIONSHIP OF INDOOR AND OUTDOOR
UNITS INTO CONSIDERATION.
AIR BALANCE NOTES:
1. PRIOR TO FINAL ACCEPTANCE, THE CONTRACTOR SHALL
MEASURE AIR FLOW AT EACH LOUVER, REGISTER, AND GRILLE.
2. THE CONTRACTOR SHALL BALANCE EACH DUCT SYSTEM AND
MAKE ADJUSTMENTS AS NECESSARY SO THAT THE AIR FLOWS
ARE CONSISTENT WITH THAT NOTED ON THE PLANS AND WITH THE
OVERALL DESIGN INTENT. ADJUSTMENTS SHALL INCLUDE DAMPER
SETTINGS AND FAN SPEEDS.
3. CONTRACTOR SHALL PRODUCE A RECORD DOCUMENT THAT
IDENTIFIES ALL MEASURED AIR FLOWS, FANS SPEEDS, AND
DAMPER SETTINGS. TWO COPIES OF THE RECORD DOCUMENT
SHALL BE PROVIDED - ONE FOR THE OWNER AND ONE FOR THE
DESIGNER.
4. AIR FLOWS THAT DEVIATE FROM THE DESIGN INTENT MORE THAN
10% SHALL BE HIGHLIGHTED AND BROUGHT TO SPECIAL
ATTENTION OF THE DESIGNER FOR FURTHER INVESTIGATION.
HVAC MATERIALS SCHEDULE
DESCRIPTION
CONCEALED
RECTANGULAR
METAL DUCT
EXPOSED
RECTANGULAR
METAL DUCT
CONCEALED
ROUND
METAL DUCT
EXPOSED
ROUND
METAL DUCT
EXTERIOR TO BUILDING
RECTANGULAR
METAL DUCT
FLEXIBLE AIR DUCT
FLEXIBLE EXHAUST DUCT
DUCT SEALANT
DUCT JOINT TAPE
DUCT INSULATION
EXTERNAL WRAP
DUCT INSULATION
INTERNALLY LINED
REFRIGERANT PIPING
THERMOSTAT AND
CONTROL WIRING
EXHAUST HOOD MATERIALS
MATERIAL
24 GAUGE MINIMUM
GALVANIZED STEEL
SHEET METAL
24 GAUGE MINIMUM
GALVANIZED STEEL
SHEET METAL
26 GAUGE MINIMUM
GALVANIZED STEEL
LONGITUDAL SEAM
28 GAUGE MINIMUM
GALVANIZED STEEL
SPIRAL SEAM
24 GAUGE MINIMUM
GALVANIZED STEEL
SHEET METAL
TYPE NM-IL
TYPE M-UN
CORRUGATED
ALUMINUM
SURE-GRIP 404
ECO-DUCT SEAL
2" THICK FIBERGLASS
BLANKET
1" THICK
ELASTOMERIC DUCT
LINER
COPPER
COPPER
REFER TO PLANS
STANDARDS
G-60 GALV
ASTM A653 & A924
G-60 GALV
ASTM A653 & A924
G-60 GALV
ASTM A653 & A924
G-60 GALV
ASTM A653 & A924
G-60 GALV
ASTM A653 & A924
CLASS 1
ASTM B209
CLASS 1
ASTM D-2202
ASTM C 553-92
ASTM C 1290
ASTM C 411
ASTM C 1071
TYPE ACR
ASTM B280
18 GA. SHIELDED
REMARKS
PRESSURE CLASS - 1" WG
SEAL - CLASS A
EXTERNALLY INSULATED
PRESSURE CLASS - 1" WG
SEAL - CLASS A
UNINSULATED UNLESS OTHERWISE NOTED
PRESSURE CLASS - 2" WG
SEAL - CLASS A
EXTERNALLY INSULATED
PRESSURE CLASS - 2" WG
SEAL - CLASS A
UNINSULATED
PRESSURE CLASS - 1" WG
SEAL - CLASS A
RIGID INSULATION, VENTURE CLAD WEATHER TIGHT WRAP
8' MAXIMUM LENGTH
INSULATION R-VALUE =
R-4.2 WHERE ROUTED WITHIN THERMAL ENVELOPE
R-8 WHERE ROUTED OUTSIDE THERMAL ENVELOPE
8' MAXIMUM
LENGTH
UNINSULATED
GRAY, SOLVENT BASED, SYNTHETIC RUBBER RESIN,
SMACNA PRESSURE CLASSES 1/2 - 10" WG SMACNA SEAL
CLASSES A, B, C,
FOIL SCRIM KRAFT FACED, VAPOR SEAL
R= 5.6 HR FT² °F / BTU
R=4.3 HR FT² °F / BTU
CLOSED CELL ELASTOMERIC INSULATION
ARMAFLEX OR EQUAL.
SIZE PER MANUFACTURER WITH 1/2" MINIMUM
ARMAFLEX INSULATION. INSULATE LIQUID AND VAPOR
LINES SEPARATELY. ALL EXTERIOR LINES SHALL BE
ROUTED CONCEALED AND / OR COVERED WITH 26 GA
GALVANIZED SHEET METAL.
ROUTE REMOTE FROM LINE VOLTAGE WIRING
3" MINIMUM FOIL FACED
NOTES:
1) ALL MATERIALS AND CONSTRUCTION SHALL COMPLY WITH NFPA STANDARDS 90A AND 90B AND SMACNA.
2) ALL METALLIC MATERIALS SHALL BE UL 181 CLASS 0 (NO FLAME SPREAD OR SMOKE DEVELOPMENT)
3) ALL NON-METALLIC MATERIALS SHALL BE UL 181 CLASS 1 (25 FLAME SPREAD AND 50 SMOKE DEVELOPMENT)
4) DUCTING NOTED TO BE INTERNALLY INSULATED SHALL NOT REQUIRE EXTERNAL INSULATION
5) ALL DIMENSIONS NOTED ARE INSIDE CLEAR DIMENSIONS. SIZE INTERNALLY LINED DUCTS ACCORDINGLY
SPLIT SYSTEM HEAT-PUMP SCHEDULE
SYSTEM
NOMINAL PERFORMANCE
MINIMUM SEER / EER
MANUFACTURER
OUTDOOR VENT. AIR (CFM)
INDOOR UNIT MODEL NO.
CONFIGURATION
HEATING CAPACITY - HEAT PUMP (BTUH)
AUX. HEAT - KW
FAN - CFM / EXTERNAL STATIC PRESS.
FAN - HP
VOLTAGE
MINIMUM CIRCUIT AMPS (MCA)
MAXIMUM OVERCURRENT (MOCP)
COOLING CAPACITY TOTAL (BTUH)
COOLING CAPACITY SENSIBLE (BTUH)
ENTERING AIR DB / WB
NOMINAL UNIT DIMENSIONS (L-W-H)
OUTDOOR UNIT
MODEL NO.
REFRIGERANT
VOLTAGE
MINIMUM CIRCUIT AMPS (MCA)
MAXIMUM OVERCURRENT (MOCP)
NOMINAL UNIT DIMENSIONS (L-W-H)
NOMINAL UNIT WEIGHT (LB)
ACCESSORIES (SEE BELOW)
TEM4B0C37M31
AHU-1
3 TONS
TRANE
VERTICAL
31,800
1,200 / 0.5"
1/2
240/1/60
35,317
25,999
80 / 67
21"x24"x52"
HP-1
4TWR4036N1
R-410A
35"x38"x37"
1,2,3,4,5,6
240/1/60
REMARKS:
1. AMBIENT OUTDOOR AIR CONDITIONS - 95° DB / 78° WB
2. AIR HANDLER - SINGLE POINT POWER CONNECTION
ACCESSORIES:
1. THROWAWAY FILTER - MERV 8
2. PROGRAMMABLE THERMOSTAT - HONEYWELL SERIES 8000 OR EQUAL
3. OVERFLOW DRAIN PAN WITH AUTOMATIC SHUT-OFF FLOAT SWITCH AND
DRAIN VALVE
4. VIBRATION ISOLATION
5. COIL HAIL GUARDS
EXHAUST FAN SCHEDULE
IDENTIFICATION
TYPE
MANUFACTURER
MODEL
CFM
STATIC PRESSURE
MOTOR HP / WATTS
VOLTAGE
ACCESSORIES
0.2"
EF-1,2
CEILING
GREENHECK
CSP-A250
-- / 62
120/1/60
1,2,3,4
ACCESSORIES:
1. FACTORY MOUNTED DISCONNECT SWITCH
2. BACKDRAFT DAMPER
3. SPEED CONTROL, CHASSIS MOUNTED, FOR BALANCING
4. POWERED WITH LIGHTS
MECHANICAL MAINTENANCE
CONTRACT NOTE:
1. FOR THE PERIOD OF ONE-YEAR AFTER SUBSTANTIAL
COMPLETION, THE MECHANICAL CONTRACTOR SHALL
PROVIDE MAINTENANCE SERVICES AS NEEDED TO ENSURE
OPTIMUM PERFORMANCE OF THE MECHANICAL SYSTEMS.
THESE SERVICES SHALL BE IN ADDITION TO ANY WARRANTIES
SPECIFIED ELSEWHERE. MAINTENANCE SERVICES SHALL
INCLUDE BUT ARE NOT LIMITED TO:
A. PROVIDING AND CHANGING FILTERS EVERY THREE
MONTHS (MINIMUM)
B. CLEAN ALL AIR COILS EVERY SIX MONTHS (MINIMUM)
C. BALANCING OF AIRFLOWS AS PRACTICAL TO MATCH
OWNER'S NEEDS
D. VERIFYING OPERATION OF VENTILATION AIR EQUIPMENT
(ERVs, OA DAMPERS)
E. MAINTAINING REFRIGERANT CHARGE PER
MANUFACTURER'S RECOMMENDATIONS
F. PROGRAMMING OF THERMOSTATS AND CONTROLS
G. SEASONAL CHANGEOVERS
H. MAKING CONTROL ADJUSTMENTS AS PRACTICAL TO
ADDRESS HUMIDITY CONCERNS
I. CLEANING CONDENSATE TRAPS
J. TESTING OF ALL SENSORS AND SWITCHES (SMOKE
DETECTOR, OVERFLOW PAN FLOAT SWITCH, ETC.)
2. ALL SERVICES SHALL BE COORDINATED WITH THE OWNER SO
TO MAXIMIZE TRAINING OPPORTUNITIES.
3. ALL WORK SHALL BE PERFORMED BY PERSONNEL WHO ARE
FACTORY AUTHORIZED BY THE MANUFACTURER OF THE
EQUIPMENT BEING SERVICED.
BASIS OF DESIGN NOTES:
1. MANUFACTURERS AND EQUIPMENT MODEL NUMBERS ARE
SCHEDULED TO SPECIFY DESIGN INTENT AND BASIS OF DESIGN.
2. REQUESTS FOR ALTERNATE MANUFACTURERS AND EQUIPMENT
SHALL BE CONSIDERED.
3. REQUESTS SHALL UTILIZE SUBSTITUTION REQUEST FORMS AND
PROCEDURES PROVIDED IN THE PROJECT MANUAL.
4. REQUESTED ALTERNATE EQUIPMENT SHALL BE EQUAL OR BETTER
THAN SCHEDULED EQUIPMENT.
5. APPROVAL OF SUBSTITUTION REQUEST IS NOT GUARANTEED BUT
IS THE RIGHT OF THE OWNER AND DESIGNER.
6. CONTRACTOR IS RESPONSIBLE TO COORDINATE ALL TRADES
AFFECTED BY AND ASSOCIATED WITH SUBSTITUTION INCLUDING
ELECTRICAL SERVICES.
7. CONTRACTOR IS RESPONSIBLE TO ENSURE SUBSTITUTION WILL
FIT IN AVAILABLE SPACE INCLUDING SERVICE ACCESS
REQUIREMENTS.
1. INSTALLATION SHALL COMPLY WITH ALL APPLICABLE CURRENTLY
ADOPTED CODES AT THE TIME OF THE PLAN DATE, INCLUDING (BUT NOT
LIMITED TO) THE FOLLOWING:
IBC INTERNATIONAL BUILDING CODE
IFC INTERNATIONAL FIRE CODE
IMC INTERNATIONAL MECHANICAL CODE
NFPA 90A AIR CONDITIONING AND VENTILATION CODE
NFPA 90B AIR CONDITIONING AND VENTILATION CODE
SMACNA HVAC DUCT CONSTRUCTION MATERIALS
IECC INTERNATIONAL ENERGY CONSERVATION CODE
2. HVAC SYSTEM SHALL BE INSTALLED COMPLETE WITH ALL WORK,
MATERIALS, AND EQUIPMENT CUSTOMARILY CONSIDERED PART OF
SUCH WORK FOR FULLY OPERATIONAL, COMPLETE AND CODE
COMPLIANT SYSTEMS. PROVIDE AND INSTALL ALL EQUIPMENT, DUCTING,
DAMPERS, DIFFUSERS, LOUVERS, GRILLES, ETC. AS REQUIRED.
3. PLANS ARE DIAGRAMMATIC AND ARE PROVIDED ONLY TO SHOW
GENERAL SYSTEMS. CONTRACTOR SHALL CONSIDER ACTUAL FIELD
CONDITIONS DURING INSTALLATION ANY GROSS INTERFERENCE SHALL
BE BROUGHT TO THE ATTENTION OF THE ENGINEER BEFORE
CONTINUING.
4. PLAN SCALES NOTED, IF ANY, ARE ONLY APPLICABLE TO PLANS
PLOTTED AT FULL SIZE. CONTRACTOR IS CAUTIONED WHEN USING
PLANS PLOTTED AT REDUCED SIZES. REGARDLESS, CONTRACTOR
SHALL NOT SCALE PLANS, BUT SHALL REFER TO NOTED DIMENSIONS.
FOR DIMENSIONS NOT NOTED, CONTRACTOR SHALL REFER TO ACTUAL
FIELD CONDITIONS AND/OR DIMENSIONED ARCHITECTURAL,
STRUCTURAL, OR CIVIL PLANS.
5. SUBMITTAL REQUIREMENTS: CONTRACTORS SHALL PREPARE AND
SUBMIT TO THE ENGINEER FOR REVIEW AND APPROVAL DETAILED
PRODUCT INFORMATION ON ALL EQUIPMENT PROPOSED FOR USE.
SUBMITTAL SHALL BE PROVIDED AND ENGINEER SHALL REVIEW AND
APPROVE, PRIOR TO EQUIPMENT PURCHASE. SUBMITTALS SHALL BE
SUBMITTED IN ELECTRONIC (PDF) FORMAT. PRIOR TO SUBMITTAL
CONTRACTOR SHALL REVIEW AND CERTIFY BY SIGNATURE THAT
SUBMITTED EQUIPMENT MEETS SPECIFICATION. CONTRACTOR SHALL
BE RESPONSIBLE FOR ALL DIMENSIONS, FITTING, AND CONSTRUCTION
FEATURES RELATIVE TO EQUIPMENT. APPROVAL OF SUBMITTAL
INFORMATION BY THE ENGINEER DOES NOT RELIEVE THE
CONTRACTOR'S OBLIGATION TO PROVIDE CODE COMPLIANT SYSTEMS.
6. ALL SERVICEABLE EQUIPMENT, VALVES, UNIONS, FIRE DAMPERS,
CONTROLS, ETC. SHALL BE INSTALLED IN ACCESSIBLE LOCATIONS.
7. LOCATE AND INSTALL ALL EQUIPMENT CONSIDERING MANUFACTURERS
CLEARANCES, MANUFACTURERS INSTALLATION INSTRUCTIONS, AND
LISTING AGENCY CERTIFICATIONS.
8. VERIFY ALL ELECTRICAL REQUIREMENTS WITH EQUIPMENT
MANUFACTURERS. COORDINATE WITH ELECTRICAL CONTRACTOR.
9. FIRE STOPPING SYSTEM SHALL BE INSTALLED AT ALL PENETRATIONS
THROUGH FIRE RATED WALLS, CEILINGS OR CONSTRUCTION.
10. A FIRE DAMPER SHALL BE INSTALLED IN EACH AIR DUCT AS IT
PENETRATES FIRE RATED WALLS OR FLOORS.
11. PROVIDE AND INSTALL ALL HANGERS AND SUPPORTS PER CODE AND
SMACNA RECOMMENDATIONS.
12. THERMOSTATS SHALL BE PROGRAMMABLE TYPE COMPATIBLE WITH
MECHANICAL EQUIPMENT SERVED.
13. ALL DUCT WORK DIMENSIONS SHOWN ARE INSIDE CLEAR. FABRICATE
DUCT SO TO MAINTAIN CLEARANCE SPECIFIED. INTERNALLY LINED
DUCTS SHALL BE OVERSIZED SO TO ACCOMMODATE THICKNESS OF
INSULATION.
14. SUPPLY, RETURN, AND OUTSIDE AIR DUCTWORK SHALL BE GALVANIZED
SHEET METAL WITH INSULATION AS NOTED ON THE PLANS AND
MATERIALS SCHEDULES.
15. LOCATE ALL CEILING MOUNTED REGISTERS, GRILLES, DIFFUSERS, FANS,
ETC. PER REFLECTED CEILING PLAN. COORDINATE WITH ELECTRICAL
AND FINISH CEILING INSTALLATION.
16. ALL TRANSVERSE JOINTS TO BE SEALED WITH APPROVED DUCTSEALER.
17. TURNS IN DUCTWORK SHALL HAVE 1.5 MINIMUM RADIUS RATIO
WHENEVER POSSIBLE, OTHERWISE TURNING VANES SHALL BE
INSTALLED WITHIN DUCT.
18. EVERY SUPPLY DIFFUSER SHALL BE INDIVIDUALLY CONTROLLED BY A
DAMPER PLACED AT THAT DIFFUSER'S SUPPLY DUCT TAKEOFF.
19. INSTALL FLEXIBLE VIBRATION ISOLATION DUCT SECTIONS AT BOTH
SUPPLY AND RETURN DUCT CONNECTIONS TO THE FURNACE / AIR
HANDLER.
20. ALL OUTDOOR AIR INTAKE LOUVERS SHALL BE 10'-0" MINIMUM DISTANCE
AWAY FROM SEWER OR COMBUSTION EXHAUST VENTS.
21. THE PLANS AND SPECIFICATIONS FOR THIS WORK HAVE BEEN
PREPARED WITH THE INTENT TO BE AS ACCURATE AND COMPLETE AS
PRACTICAL, BUT ERRORS, OMISSIONS, AND CONFLICTS MAY EXIST.
PRIOR TO SUBMITTING A BID FOR CONSTRUCTING THE WORK, THE
CONTRACTOR SHALL REVIEW THE PLANS AND SPECIFICATIONS IN
DETAIL. ANY QUESTIONS OR COMMENTS SHALL BE BROUGHT TO THE
ATTENTION OF THE ENGINEER PRIOR TO SUBMITTING A BID. BY
SUBMITTING A BID FOR THE WORK, THE CONTRACTOR ACKNOWLEDGES
THAT HE HAS REVIEWED THE PLANS AND SPECIFICATIONS,
UNDERSTANDS THE DESIGN INTENT, AND DOES NOT HAVE ANY
FURTHER QUESTIONS OR COMMENTS.
NOTES:
1. DIFFUSER OR GRILLE NECK SIZE TO MATCH OR EXCEED FLEX CONNECTOR SIZE AS NOTED IN THE PLANS.
2. AIR VOLUME TO ALL SUPPLY DIFFUSERS SHALL BE CONTROLLABLE BY EITHER MANUAL DAMPER IN CONNECTOR TO
MAIN DUCT OR INTEGRAL DAMPER IN DIFFUSER UNLESS OTHERWISE NOTED.
3. ALL CEILING DIFFUSERS AND GRILLES SHALL INCLUDE MOLDED FIBERGLASS BACK PANELS.
4. INCLUDE FILTERS WITH ALL FILTER GRILLES. FILTERS SHALL BE REPLACED WITH NEW AT SUBSTANTIAL COMPLETION
OF PROJECT.
5. INCLUDE MOUNTING FRAMES FOR ALL GRILLES INSTALLED IN GYP. BOARD CEILINGS.
LOUVER, DIFFUSER AND GRILLE SCHEDULE
MARK TYPE MANUFACTURER MODEL COMMENTS
B CEILING
RETURN
GRILLE
HART & COOLEY,
METALAIRE
RE5-T,
CC5-6
2' x 2' LAY-IN CEILING RETURN AIR GRILLE, EXTRUDED ALUMINUM, 1/2X1/2X1/2 GRID CORE, WHITE ENAMEL FINISH, WITH SQUARE TO ROUND ADAPTER
FOR NOTED CONNECTOR SIZE
L INTAKE /
EXHAUST AIR
LOUVER
GREENHECK, UNITED
ENERTECH
FSJ-402,
FL-D-4
FABRICATED STATIONARY BLADE LOUVER. J-STYLE, 4"
X16GA BLADES, MECHANICALLY FASTENED WITH 1/2" X1/2"
ALUMINUM MESH BIRDSCREEN, 2 COAT KYNAR FINISH,
COLOR AS SELECTED BY ARCHITECTURAL
S CEILING
SUPPLY
GRILLE
PRICE 600 LOUVERED FACE SIDE WALL DIFFUSER, ALL ALUMINUM
CONSTRUCTION, WITH OPPOSED BLADE DAMPER, WHITE
ENEAMEL FINISH, SIZE PER FLOOR PLAN
GENERAL HVAC NOTES:
NOT TO SCALEM0.1
1 GROUND MOUNTED CONDENSING UNIT DETAIL
NOT TO SCALEM0.1
2 SPLIT SYSTEM AIR HANDLER DETAIL
T
D
C
B
3 42
A
HP-1
"x
"x
14"x12" 14"x10"
"x
10"x10"
12"x6"
50 CFM
S
12"x6"
150 CFM
S 12"x6"
150 CFM
S
12"x6"
75 CFM
S 12"x6"
75 CFM
S
12"x6"
75 CFM
S
12"x6"
75 CFM
S 12"x6"
150 CFM
S 12"x6"
150 CFM
S
12"x6"
150 CFM
S14"ø
1250 CFM
B
AHU-1
12"x6"
150 CFM
S
EF-2
EF-1
8"ø
18"x18"
250 CFM
L
3AHU-1
RD
NUMBER NOTES:
RETURN OR EXHAUST REGISTER
RETURN OR EXHAUST DUCT UP TO ABOVE
SUPPLY DUCT UP TO ABOVE
RATED WALL - SEE PLANS FOR TYPE
FIRE DAMPER - SEE PLANS FOR TYPE
FIRE DAMPER ACCESS DOOR IN ACCESSIBLE
LOCATION
SUPPLY AIR DIFFUSER
INSULATED FLEX DUCT
BELL MOUTH FITTING OR SPIN-IN, WITH MANUAL
VOLUME DAMPER
FULL RADIUS ELL OR SQUARE ELL WITH TURNING
VANES
TRANSITION
RISE OR DROP
OPPOSED BLADE MANUAL BALANCING DAMPER -
TYPICAL EACH BRANCE TAKE-OFF OR RUN OUT
45 DEGREE TEE FITTING - "SHOE" TYPE
SUPPLY DUCT DOWN TO BELOW
RETURN DUCT OR EXHAUST DUCT DOWN TO
BELOW
15 16
X
2X
BA
2" (51mm)
PLUS X
UNIT TYPE
DRAW THRU
FAN
BLOW THRU
FAN
1" (25mm)
MINIMUM
WHERE X = STATIC PRESSURE IN PAN
A B
M
IN
NUMBER NOTES:
1 DRAIN LINE SHALL BE AT
LEAST THE SAME SIZE AS THE
NIPPLE ON THE DRAIN PAN
PITCH DOWN TOWARD DRAIN
CLEAN OUT
DRAIN PAN
OPEN DRAIN - COORDINATE
WITH PLUMBING
OPEN VENT ABOVE RIM
HEIGHT OF DRAIN
NUMBERED NOTES:
1 CEILING EXHAUST FAN
PROVIDE SQUARE TO ROUND
TRANSITION AS REQUIRED
CEILING PAD OR HARD CEILING
ROUTE DUCT TO WALL CAP OR ROOF
CAP AS REQUIRED
SUPPORT DUCT TO PREVENT SAG OR
SWAY
SUPPORT FAN FROM CEILING
OFTIS