The document provided is an Addendum No. 2 related to Invitation for Bid (IFB) #25-0501 for Renwick Bell Tower Repairs issued by the City of Fredericksburg, Virginia. The addendum addresses various questions from vendors regarding the repair work, including the use of helical anchors, removal and resetting of existing brick masonry, the type of mortar to be used, and the coating of the stone elements. The responses clarify the intended use of the specified materials and the overall approach to the repairs. The IFB due date is August 19, 2024, at 2:00 PM EST.

The addendum indicates that the repair work is expected to involve patching of spalled brick and stone, repointing of mortar joints, and potential removal and resetting of loose brick masonry. The City has provided a Dropbox folder with photographs to assist contractors in understanding the existing conditions. The contract will be awarded for the "Renwick Bell Tower Repair" project, which is located within the jurisdiction of Stafford County, Virginia.

View the file

Other files

Show all 16

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

City of Fredericksburg Telephone: 540.372.1017 P.O. Box 7447 Fax: 540.372.12.15 Fredericksburg, VA 22404-7447

August 12, 2024

ADDENDUM NO.2 TO ALL OFFERORS:

Reference –IFB # 25-0501 Commodity: Renwick Bell Tower Repairs DUE DATE: August 19th, 2024 – 2:00 P.M. EST

The following is a general summary of questions that have been submitted by various vendors, edited for clarity, along with the City’s responses.

1. Stainless steel, self-cutting, helical anchors are discussed, where in the brick or stone masonry repairs are these expected to be used? Is there a spacing that is required (18” o.c. for example)? (Section 0400120.6, 2.7A).

A. It is not anticipated that these types of anchors will be necessary for the specified repairs; however, in instances where the Engineer determines that reinforcement of the brick/stone masonry is warranted, the Contractor may be directed to install helical anchors. Reimbursement for this work would be in accordance with Workcode G1MR for “General Maintenance and Repair”

2. Where in the drawings does it discuss removing and resetting existing brick masonry veneer? There doesn’t appear to be a work code for this work. If that is the case, how should it be billed if we bill per work code? (Section 040120.6, 1.2.A.1, “Remove and reset existing brick masonry veneer as designated in contract drawings.”).

A. There is not a specific detail which shows removing and resetting of the brick; and, specific locations where this type of repair might occur are not shown on the Drawings. A minimal allowance (20 brick) has been included in the contract to cover situations where existing brick are loose and/or dislocated and the Contractor must remove the brick, clean excess mortar and then reset the same brick. Exact locations where this will be performed will be determined during the Contractor’s preliminary survey with the Engineer.

3. It is discussed to use Cathedral Stone pointing mortar to repair the brickwork joints. Cathedral Stone is a reputable brand that describes their pointing mortar in their data sheet as “These single – component, cementitious, mineral based pointing mortar are specifically formulated for the restoration of mortar joints in all types of masonry.” Based on the drawings, it is specified to use a lime based mortar. Please advise if this is the only product that is requested in this application. (Section 040120.6, Products).

A. Please see comments from Addendum 1. The Jahn mortar referenced above is for patching of spalled portions of existing brick or stone units. All repointing work should be performed using Cathedral Stone Product’s “Historic Pointing Mortar” (or approved equal) as referenced in Paragraph 2.3.B.1. Alternate manufacturers/products are acceptable provided they meet specified requirements.

4. In the product list, nothing is discussed about the “setting” material. Materials that are mentioned include jahn pointing mortar, portland cement, hydrated lime type s or sa, and lime putty. Is there an idea of what is expected to be used for the setting mortar and how you want it to be different than the pointing mortar? In some situations, it is advisable for them to be different. In this proposed work, is there a reason why they can’t be the same? (Section 040120.6, Products).

A. We do not anticipate that a separate setting mortar will be required. The Contractor should disregard references to setting mortar and should anticipate using the same historic pointing mortar for all applications.

5. Products that could save on cost and or might be more appropriate in some ways could be Natural Hydraulic lime (NHL) or Pozzolanic Hydraulic Lime (PHL). Even though it isn’t mentioned in the document, are these appropriate materials to be used in the bedding and repointing? It does mention lime putty but based on experience and research, one might want to add an approved pozzolan in given situations. The material list doesn’t discuss the possible use of pozzolans. Can you please elaborate on this topic and what is expected? (Section 040120.6, Products).

A. The intent of this project is to use a repair mortar that closely resembles the original mortar. Consequently, the Contractor is required to obtain samples of the original mortar for laboratory analyses. If it is determined that the use of NHL or PHL are consistent with the qualities of the original mortar, we are not opposed to their use, following submittal review and approval; and, following approval of mock-ups.

6. It appears the stone has a coating overtop of it. Is this coating expected to be removed to properly assess and patch each stone? (Section 040120.6).

A. We believe that the original architectural stone elements were covered with a thin layer of cement/stucco when the remainder of façade was covered with stucco in the early 20th century. This cement/stucco “coating” only needs to be removed slightly beyond the extents spalled areas of the existing stone, to facilitate patching of the underlying stone. Once patching is complete, the Contractor should reapply the veneer layer of cement/stucco to resemble pre-construction conditions. It is anticipated that the “coating” material will be similar to the stucco patching material.

7. It would be appropriate to match the stone color not the coating color. If this is the case, the stone would need to be coated after the patches are completed. Is there any documentation on what type of coating is applied to the stone currently? What would be an approved coating to put back after the stone patches are complete? (Section 040120.6).

A. See commentary on Question 6 above.

8. Please advise is this is to be colored to match the current stucco finish. There is no paint or mineral coating applied on top of the stucco finish? (Section 092400, Acrylic-based finish coatings).

A. It is our understanding that some type of acrylic-based coating was applied to the stucco on the bell tower when repairs were performed approximately 20 to 25 years ago. The intent is to match existing materials as much as possible.

9. The materials in this section don’t specify a sealant to be used to patch cracks. Is there a recommended product? (Section 092400, 3.5.B).

A. See Specification Section 040120.6, Paragraph 2.4.A for approved sealants. The Contractor may use other sealants, if properties are consistent with specified requirements and upon review and approval by the Engineer; and, following approval of mock-ups.

10. If it is patched with a sealant with sand applied to create the texture, the color may not be a complete match. If the wall isn’t to be coated after the repairs, is it up to the contractor to find a sealant that is colored to match the current wall? (Section 092400, 3.5.B).

A. It is understood that the sealant repairs will not be an exact match to the existing stucco; however, the intent is to closely replicate the color/texture of the existing stucco. The Contractor should submit multiple samples and prepare multiple mock-ups so that a closely matching finish can be obtained.

11. The materials in this section don’t specify a sealant to be used for the control joint. Is there a recommended product for the control joints? Please advise again how the control joint should be coated to match the color of the building? Is the sealant colored or is the repair going to be coated after installation? If so what product is requested to coat the repair? (Section 092400, 3.6).

A. See responses to Questions 9 and 10 above.

12. A Dropbox folder has been created with hundreds of photographs for the Contractors’ https://www.dropbox.com/scl/fo/bgrlipm4c266eqrlkvdkj/ACVolfoaCE2pVQjogrhCRP4?rlkey=3h2ncfe9kku2mo34jt32fn0dv&e=1&st=ap64vuv9&dl=0 image1.png

File details come from the government source that posted it. Updated .