This is an Addendum 3 to bid specification BL073-23 for the Gwinnett County Gateway Monuments Project, issued by Gwinnett County on August 22, 2023. The project involves the installation of two gateway sign monuments at specified locations in Gwinnett County: one at the intersection of State Route 124 and Riverlake Way (26'-6" tall) and another at the I-85 Interchange at Jimmy Carter Boulevard. The work includes sign fabrication and installation, with fabricated aluminum components, site preparation including 350 square feet of Bermuda sod placement, and coordination with Georgia Department of Transportation under an encroachment permit. The addendum clarifies that existing guardrail at the State Route 124 location shall remain undamaged, and no guardrail installation is required at the I-85 location. Special inspection requirements are outlined in accordance with the 2018 International Building Code, addressing structural steel construction, concrete construction, masonry construction, and soils verification, with monthly interim reporting and final completion documentation required.
The contractor bears responsibility for utility company coordination and primary service installation to the utility meter, with the Owner only responsible for establishing the utility account. All materials testing and additional soil testing beyond the included Geotechnical Exploration Report shall be paid by the Owner as specified in the Project Manual Section 01 12 00 Part 3 Execution. County permits are not required on Gwinnett County property, though the awarded contractor must be licensed to conduct business in Georgia; no county business license is required. Working hours are restricted per drawings A1.1A and A1.0B and specification section 01 14 00. Warranty requirements are outlined in specification section 01 78 40, with liquidated damages referenced in specification section 01 30 10. Gwinnett County is exempt from federal excise tax and Georgia sales tax; vendors are responsible for all applicable taxes on materials and services, with no cost-plus markup paid on taxes. All bidders must acknowledge receipt of Addendum 3 in the Bid Form or face potential disqualification.
Text of this file
BL073-23 Addendum 3 Page 1 of 3
August 22, 2023
Addendum 3
BL073-23, Gwinnett County Gateway Monuments Project
Q1. Please confirm the County has/shall obtain(ed) all rights of way and easements required for all sign locations.
A1. The locations are within existing GDOT/ State DOT right of way; DOT will be working under an encroachment permit with the Georgia Department of Transportation. The vendor does not need to acquire the permit for the work.
Q2. Is the contractor responsible for any guardrail installation if required?
A2. PPI does not foresee a requirement to install guardrail. Refer to the attached site location plan and guardrail drawing for additional information about existing guardrail at site location -
State Route 124 and Riverlake Way.
Q3. If yes, will both sign locations need guardrail installation?
A3. Existing guardrail to remain at site location - State Route 124 and Riverlake Way. There is no guardrail installation required at site location - I-85 Interchange at Jimmy Carter Boulevard.
Q4. Electrical/Utility Clarification: Electrical plans (Detail 3) states utility company coordination by Contractor, but the Project Manual (Section 01 12 00 Part 3 Execution) states utility company coordination by Owner. Please clarify.
A4. The Owner is only responsible for setting up the account with the utility company. The contractor is responsible for coordination as per detail 1/E2.1A and detail 1/2.1B.
Q5. Can Owner be responsible for utility power primary service to the utility meter?
A5. No. The contractor is responsible for the utility power primary service as per keynote 3 detail
1/E2.1A and keynote 3 detail 1/2.1B.
BL073-23 Addendum 3 Page 2 of 3
Q6. Please confirm any materials testing and/or any additional soil testing beyond the included
Geotechnical Exploration Report will be paid for by the Owner as stated in the Project Manual
(Section 01 12 00 Part 3 Execution).
A6. Please see attached special inspection requirements. Refer to statement and schedule of special inspections for additional testing requirements for the project. Refer to project manual
(Section 01 12 00 Part 3 Execution) for Contractor and Owner responsibilities related to soil and materials testing.
Q7. Are any county permits required for these signs?
A7. Permitting is not required on Gwinnett County property.
Q8. Is a county business license required for these signs?
A8. No. However, the awarded contractor must be licensed to business in Georgia.
Q9. Will working hours be restricted at any time?
A9. Yes. There is information about restrictions, refer to drawings A1.1A and A1.0B and specification section 01 14 00.
Q10. Are there any special warranties/guarantees?
A10. All bidders are expected to meet the specifications outlines in the bid document. Please refer to the section 01 78 40 regarding warranties.
Q11. Are there any liquidated damages? Amounts not specified in Sample Contract.
A11. References to liquidated damages are in specification section 01 30 10.
Q12. Is sales tax to be included in bid?
A12. Per the Instructions to Vendors, Section IV, Item H;
Gwinnett County is exempt from federal excise tax and Georgia sales tax regarding goods and services purchased directly by Gwinnett County. Vendors are responsible for federal excise tax and sales tax, including taxes for materials incorporated in county construction projects. Vendors should contact the State of Georgia Sales Tax Division for additional information. Agreements were there is a cost-plus mark-up, mark-up will not be paid on taxes.
BL073-23 Addendum 3 Page 3 of 3
Q13. Do these signs include fabricated aluminum?
A13. Yes.
All bidders shall acknowledge receipt of this addendum by inserting its number and date in the
Bid Form. Failure to do so may subject the bidder to disqualification. This addendum forms a part of the Contract Documents.
Thank you.
Olivia Graves
Purchasing Associate II
33'-0"
20'-6"
FACE OF SIGN
FA
C
E O
F
SI
G N
ED
G
E O
F
TR
AV
EL
L
AN
E
EDGE OF TRAVEL LANE
THE CONTRACTOR SHALL CLEAR ONLY THE AREAS
REQUIRED FOR SIGN AND GUARDRAIL INSTALLATION.
ALL EXCAVATED SOILS SHALL BE REMOVED FROM
THE SITE AND PROPERLY DISPOSED.
SITE LOCATION: APPROXIMATE COORDINATES
33° 46' 21" N 84° 03' 24" W
INTERSECTION OF 124 AND RIVERLAKE WAY
PROPOSED GATEWAY
SIGN LOCATION - 26'-6" TALL
PROVIDE 350 SQUARE FEET
OF BERMUDA SOD AT
NEW SIGN LOCATION
EXISTING GUARDRAIL TO REMAIN.
CONTRACTOR SHALL NOT DAMAGE.
GEORGIA STATE ROUTE 124
RIGHT OF WAY VARIES
ASPHALT PAVING
SPEED LIMIT 45MPH
R
IV
ER
LA
KE
W
AY
AS
PH
AL
T
PA
VI
N
G
SCALE 1:16
N
AutoCAD SHX Text State Route 124 and Riverlake Way
AutoCAD SHX Text Site Location Plan -
SCALE: NTS
EXISTING GUARDRAIL TO REMAIN.
CONTRACTOR SHALL NOT DAMAGE
AutoCAD SHX Text State Route 124 and Riverlake Way
AutoCAD SHX Text Guardrail -
ACEC/SEAOG SI GL 01 –19 page A1
STATEMENT OF SPECIAL INSPECTIONS
PROJECT: Gwinnett County Transportation Gateway Signs
LOCATION: Gwinnett County
PERMIT APPLICANT:
APPLICANT’S ADDRESS:
ARCHITECT OF RECORD:
STRUCTURAL ENGINEER OF RECORD: William J. Peltier, P.E., S.E.
MECHANICAL ENGINEER OF RECORD:
ELECTRICAL ENGINEER OF RECORD:
REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE: William J. Peltier, P.E.,S.E.
This Statement of Special Inspections is submitted in accordance with Section 1704.3 of the 2018 International Building Code. It includes a Schedule of Special Inspection Services applicable to the above-referenced Project as well as the identity of the individuals, agencies, or firms intended to be retained for conducting these inspections. If applicable, it includes Special Inspections for Seismic Resistance and/or Special Inspections for Wind Resistance.
Are Special Inspections for Seismic Resistance included in the Statement of Special Inspections?
Yes No
Are Special Inspections for Wind Resistance included in the Statement of Special Inspections?
Yes No
The Special Inspector(s) shall keep records of all inspections and shall furnish interim inspection reports to the Building Official and to the Registered Design Professional in Responsible Charge at a frequency agreed upon by the Design Professional and the Building Official prior to the start of work. Discrepancies shall be brought to the immediate attention of the Contractor for correction. If the discrepancies are not corrected, the discrepancies shall be brought to the attention of the Building Official and the Registered Design Professional in Responsible Charge prior to completion of that phase of work. A Final Report of Special Inspections documenting required special inspections and corrections of any discrepancies noted in the inspections shall be submitted to the Building Official and the Registered Design Professional in Responsible Charge at the conclusion of the project.
Frequency of interim report submittals to the Registered Design Professional in Responsible Charge:
Weekly Bi-Weekly X Monthly Other; specify:
The Special Inspection program does not relieve the Contractor of the responsibility to comply with the Contract Documents. Jobsite safety and means and methods of construction are solely the responsibility of the Contractor.
Statement of Special Inspections Prepared by:
William J Peltier Type or print name
08/11/2023 Signature Date
Building Official’s Acceptance:
Signature Date
Permit Number:
Frequency of interim report submittals to the Building Official:
X Monthly Bi- Monthly Upon Completion Other; specify:
Preparer’s Seal
PROJECT
APPLICABLE TO THIS PROJECT
MATERIAL / ACTIVITY SERVICE Y/N EXTENT AGENT* DATE COMPLETED
1. Fabricator and erector documents
(Verify reports and certificates as listed in AISC 360, Section N 3.2 for compliance with construction documents)
Submittal Review Y Each submittal TA
2. Material verification of structural steel Shop (3) and field inspection Y Periodic TA
3. Structural steel welding:
a. Inspection tasks Prior to Welding
(Observe, or perform for each welded joint or member, the QA tasks listed in AISC 360, Table
N5.4-1)
Shop (3) and field inspection Y Observe or Perform as noted (4)
TA
b. Inspection tasks During Welding
(Observe, or perform for each welded joint or member, the QA tasks listed in AISC 360, Table
N5.4-2)
Shop (3) and field inspection Y Observe (4) TA
c. Inspection tasks After Welding
(Observe, or perform for each welded joint or member, the QA tasks listed in AISC 360, Table
N5.4-3)
Shop (3) and field inspection Y Observe or Perform as noted (4)
TA
d. Nondestructive testing (NDT) of welded joints: see Commentary
1) Complete penetration groove welds 5/16" or greater in risk category III or IV
Shop (3) or field ultrasonic testing - 100% N Periodic TA
2) Complete penetration groove welds 5/16" or greater in risk category II
Shop (3) or field ultrasonic testing - 10% of welds minimum
N Periodic TA
3) Welded joints subject to fatigue when required by AISC 360, Appendix 3, Table A-3.1
Shop (3) or field radiographic or
Ultrasonic testing N Periodic TA
4) Fabricator's NDT reports when fabricator performs NDT Verify reports N Each submittal (5) EOR1
4. Structural steel bolting: Shop (3) and field inspection
a. Inspection tasks Prior to Bolting
(Observe, or perform tasks for each bolted connection, in accordance with QA tasks listed in AISC 360, Table N5.6-1)
Y Observe or Perform as noted (4)
TA
b. Inspection tasks During Bolting
(Observe the QA tasks listed in
AISC 360, Table N5.6-2)
Y Observe (4) TA
1) Pre-tensioned and slip-critical joints
a) Turn-of-nut with matching markings N Periodic TA
NOT PERMITTED
b) Direct tension indicator Y Periodic TA
c) Twist-off type tension control bolt Y Periodic TA
d) Turn-of-nut without matching markings N Continuous TA
NOT PERMITTED
e) Calibrated wrench Y Continuous NA
2) Snug-tight joints Y Periodic TA
c. Inspection tasks After Bolting
(Perform tasks for each bolted connection in accordance with QA tasks listed in AISC 360, Table
N5.6-3)
Y Perform (4) TA
5. Visual inspection of exposed cut surfaces of galvanized structural steel main members and exposed corners of the rectangular HSS for cracks subsequent to galvanizing
Shop (3) or field inspection N Periodic
SCHEDULE OF SPECIAL INSPECTIONS SERVICES
1705.2.1 Structural Steel Construction
ACEC/SEAOG SI GL 01 – 19 B1 of B4
MATERIAL / ACTIVITY SERVICE Y/N EXTENT AGENT* DATE COMPLETED
SCHEDULE OF SPECIAL INSPECTIONS SERVICES
1705.2.1 Structural Steel Construction6. Embedments (Verify diameter, grade, type, length, embedment. See
1705.3 for anchors)
Field inspection Y Periodic TA
7. Verify member locations, braces, stiffeners, and application of joint details at each connection comply with construction documents
Field inspection Y Periodic TA
1. Inspection and placement verification of reinforcing steel and prestressing tendons.
Shop (3) and field inspection Y Periodic TA
2. Reinforcing bar welding: N NOT PERMITTED
a. Verification of weldability of bars other than ASTM A706.
N Periodic
b. Inspection of single-pass fillet welds 5/16 or less in size.
N Periodic
c. Inspection of all other welds. N Continuous
3. Inspection of anchors cast in concrete.
Shop (3) and field inspection Y Periodic TA
4. Inspection of anchors post-installed in hardened concrete members per research reports, or, if no specific requirements are provided, requirements shall be provided by the registered design professional and approved by the building official, including verification of anchor type, anchor dimensions, hole dimensions, hole cleaning procedures, anchor spacing, edge distances, concrete minimum thickness, anchor embedment and tightening torque
Field inspection N Periodic TA
a. Adhesive anchors installed in horizontal or upward-inclined orientation that resist sustained tension loads.
N Continuous
b. Mechanical and adhesive anchors not defined in 4a.
N Periodic TA
5. Verify use of approved design mix Shop (3) and field inspection Y Periodic TA
6. Prior to placement, fresh concrete sampling, perform slump and air content tests and determine temperature of concrete and perform any other tests as specified in construction documents.
Shop (3) and field inspection Y Continuous TA
7. Inspection of concrete and shotcrete placement for proper application techniques
Shop (3) and field inspection Y Continuous TA
8. Verify maintenance of specified curing temperature and techniques Shop (3) and field inspection Y Periodic TA
9. Inspection of prestressed concrete: Shop (3) and field inspection N
a. Application of prestressing force N Continuous
b. Grouting of bonded prestressing tendons N Continuous
10. Inspect erection of precast concrete members N Periodic
11. Verification of in-situ concrete strength, prior to stressing of tendons in post tensioned concrete and prior to removal of shores and forms from beams and structural slabs
Review field testing and laboratory reports N Periodic EOR1
12. Inspection of formwork for shape, lines, location and dimensions Field inspection N Periodic TA
1705.3 Concrete Construction
ACEC/SEAOG SI GL 01 – 19 B2 of B4
MATERIAL / ACTIVITY SERVICE Y/N EXTENT AGENT* DATE COMPLETED
SCHEDULE OF SPECIAL INSPECTIONS SERVICES
1705.2.1 Structural Steel Construction13. Concrete strength testing and verification of compliance with construction documents
Field testing and review of laboratory reports Y Periodic TA
1. Prior to construction, verification of compliance of submittals
Submittal Review Y Prior to Construction TA
1. Prior to construction verification of f'm and f'AAC except where specifically required by the code
Testing by unit strength method or prism test method Y Prior to Construction TA
2. During construction, verification of Slump Flow and Visual Stability
Index (VSI) when self-consolidating grout is delivered to project site.
Testing by unit strength method or prism test method Y Periodic TA
1. During construction, verification of f'm and f'AAC for every 5,000 SF
Testing by unit strength method or prism test method NA Periodic
2. During construction, verification of proportions of materials as delivered to the project site for premixed or preblended mortar, prestressing grout, and grout other than self-consolidating grout.
Field inspection NA Periodic
a. Proportions of the site-prepared mortar Field inspection Y Periodic TA
b. Grade and size of prestressing tendons and anchorages Field Inspection NA Periodic TA
c. Grade, type, and size of reinforcement, anchor bolts, and prestressing tendons and anchorages
Field Inspection Y Periodic TA
d. Prestressing technique Field Inspection NA Periodic
e. Properties of thin-bed mortar for
AAC masonry
NA
Level 2 - Continuous (b)
Level 2 - Periodic (c)
TA
(b) Required for the first 5,000 square feet
(c) Required after the first 5,000 square feet Level 3 - Continuous
Y Level 2 - Periodic TA
Level 3 - Continuous
Y Level 2 - Periodic TA
Level 3 - Continuous
b. Placement of prestressing tendons and anchorages Field Inspection NA Periodic TA
Y Level 2 - Periodic TA
Level 3 - Continuous
d. Proportions of site-prepared grout and prestresssing grout for bonded tendons
Field Inspection Y Periodic TA
a. Materials and procedures with the approved submittals Field inspection Y Periodic TA
b. Placement of masonry units and mortar joint construction Field Inspection Y Periodic TA
c. Size and location of structural members Field inspection Y Periodic TA
(D) Levels 2 and 3 Quality Assurance:
Field Inspection
f. Sample panel construction Field Inspection
Field inspection
3. Verify compliance of the following during construction:
1. As masonry construction begins, verify that the following are
1705.4 Masonry Construction
(A) Level 1, 2 and 3 Quality Assurance:
(B) Level 2 & 3 Quality Assurance:
(C) Level 3 Quality Assurance:
2. Prior to grouting, verify that the following are in compliance:
a. Grout space Field Inspection
c. Placement of reinforcement, connectors, and anchor bolts
MINIMUM VERIFICATION REQUIREMENTS
MINIMUM SPECIAL INSPECTION REQUIREMENTS
ACEC/SEAOG SI GL 01 – 19 B3 of B4
MATERIAL / ACTIVITY SERVICE Y/N EXTENT AGENT* DATE COMPLETED
SCHEDULE OF SPECIAL INSPECTIONS SERVICES
1705.2.1 Structural Steel Construction Y Level 2 - Periodic TA
Level 3 - Continuous
i. Placement of AAC masonry units and construction of thin-bed mortar joints
NA
Level 2 - Continuous (b)
Level 2 - Periodic (c)
(b) Required for the first 5,000 square feet
(c) Required after the first 5,000 square feet Level 3 - Continuous
Y Level 2 - Periodic TA
Level 3 - Continuous
1. Verify materials below shallow foundations are adequate to achieve the design bearing capacity.
Field inspection Y Periodic TA
2. Verify excavations are extended to proper depth and have reached proper material.
Field inspection Y Periodic TA
3. Perform classification and testing of compacted fill materials.
Field inspection Y Periodic TA
4. Verify use of proper materials, densities, and lift thicknesses during placement and compaction of controlled fill
Field inspection Y Continuous TA
5. Prior to placement of controlled fill, inspect subgrade and verify that site has been prepared properly
Field inspection Y Periodic TA
* INSPECTION AGENTS
FIRM ADDRESS TELEPHONE NO.
1. INSPECTIONS & TESTING AGENCY (TA) TO BE DETERMINED AT A LATER DATE
270 Langley Dr 770-963-0654
Lawrenceville, GA 30046
3.
4.
Notes: 1. The inspection and testing agent(s) shall be engaged by the Owner or the Owner's Agent, and not by the Contractor or Subcontractor whose work is to be inspected or tested. Any conflict of interest must be disclosed to the Building Official prior to commencing work. The qualifications of the Special Inspector(s) and/or testing agencies may be subject to the approval of the Building Official and/or the Design Professional.
2. The list of Special Inspectors may be submitted as a separate document, if noted so above.
3. Shop Inspections of fabricated items are not required where the fabricator is approved in accordance with IBC Section 1704.2.5.1 and listed in activity 1709.2.
4. Observe: Observe on a random basis, operations need not be delayed pending these inspections. Perform: These tasks shall be performed for each welded joint, bolted connection, or steel element.
5. NDT of welds completed in an approved fabricator's shop may be performed by that fabricator when approved by the AHJ. Refer to AISC 360, N6.
Are Special Inspections for Seismic Resistance included in the Statement of Special Inspections ? No Are Special Inspections for Wind Resistance included in the Statement of Special Inspections ? No
DATE: 8/11/2023
h. Placement of grout and prestressing grout for bonded tendons is in compliance
Field inspection NA Continuous
NA Continuous
NOT PERMITTED
f. Preparation, construction, and protection of masonry during cold weather (temperature below 40 o F) or hot weather (temperature above o F)
Field inspection Y Periodic TA
NA Continuous
Field inspection
e. Welding of reinforcement Field inspection
2. William J Peltier and Associates (EOR)
Field inspection
4. Observe preparation of grout specimens, mortar specimens, and/or prisms
Field inspection
1705.6 Soils
g. Application and measurement of prestressing force Field testing
d. Type, size, location of anchors, including other details of anchorage of masonry to structural members, frames, or other construction
ACEC/SEAOG SI GL 01 – 19 B4 of B4
| BL073-23 ADD 3 |
| Guardrail Drawing Question 2 |
| Gwinnett County Monument Sign Statement of Special Inspections & Schedule |
| 2019 Statement Special Inspections |
| 2019_schedule_of_special_inspections_services |
Other files
| File | Type | Posted |
|---|---|---|
| Award Information | — | |
| ADD 1 | — | |
| ADD 2 | — | |
| ADD 4 | — | |
| NOT | — |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
File details come from the government source that posted it. Updated .