Adams_Annex_CMU_repair_set.pdf

PDF 1 MB Posted

Attached to
Adams Annex Façade Repair
Solicitation number
2026.083-ITB
Issued by
Washington County, Oregon

About this file

This is a permit set of construction documents for the Adams Annex Building located at 235 W. Main Street in Hillsboro, Oregon, prepared for Washington County. The project scope involves repair of vehicular damage to an existing concrete masonry unit (CMU) building, including replacement of the exterior CMU wall construction and replacement of a door. The work includes demolition of damaged masonry, installation of new reinforced CMU walls with specified reinforcing bars, installation of a new hollow metal door and frame, electrical work for a new light switch with surface-mounted conduit, ceiling repairs, soffit patching, and interior and exterior painting to match existing conditions. The project is classified as Construction Type III-B with one story and includes coordination with existing structural systems, roof connections, and specialized masonry reinforcement requirements. The structural design complies with the 2025 Oregon Structural Specialty Code based on the 2024 International Building Code, with a seismic design category of D and business occupancy classification.

The permit set specifies detailed construction requirements including nominal 8-inch CMU walls with minimum 2,000 PSI compressive strength, Type M or S mortar conforming to ASTM C270, ASTM A615 Grade 60 reinforcing steel, and complete grouting of all structural masonry walls. Special inspections and testing are required throughout construction in accordance with OSSC requirements, including verification of masonry unit strength, mortar and grout compressive strength, and post-installed anchor installations. The project documentation includes design criteria for snow loads (25 PSF roof design load), wind criteria (107 MPH ultimate wind speed), and specific requirements for reinforcing bar placement, lap splices, and connections to existing roof structure. The permit set was issued May 14, 2026, with an expiration date of June 30, 2027, and includes four drawing sheets addressing general structural notes, special inspections, elevations, and construction details.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FE

FE

ADAMS ANNEX BUILDING

235 W MAIN ST. HILLSBORO, OR 97124

AREA OF WORK

REINFORCING BAR WHERE OCCURS,

SEE STRUCTURAL DRAWINGS

PER ASSEMBLY TAG

SEE STRUCTURAL DRAWINGS FOR

ADDITIONAL INFORMATION

ALIGN TO FACE OF EXISTING CMU,

PAINT TO MATCH

NOTES:

1. SEE STRUCTURAL FOR SIZES AND REINFORCEMENT

REVISIONS

SE

RA

D es ign an d A rch ite ctu re , In c.

ARCHITECTURE

URBAN DESIGN + PLANNING

INTERIOR DESIGN

PORTLAND|OAKLAND

SERADESIGN.COM

CHECKED BY:

ISSUE DATE:

PROJECT NO:

7/

/2

4:

:1

PM

A D

A M

S A

N N

EX

C

M U

R

EP

A

IR

W

AS

H

IN

G

TO

N C

O U

N

TY

W . M ai n

St

H ills bo ro

, O R

, 9

G

C

O

VE

R S

H

EE

T

C O

D E

C O

M

PL

IA

N

C E

ADAMS ANNEX CMU REPAIR

WASHINGTON COUNTY

PE

RM

IT

S

ET

G001

AM

14 MAY 2026

2503066

COVER SHEET +

CODE

COMPLIANCE

SHEET INDEX

SHEET NUMBER SHEET NAME PERMIT

GENERAL

G001 COVER SHEET + CODE COMPLIANCE ■

ARCHITECTURE

A101 PLANS, ELEVATIONS & DETAILS ■

STRUCTURAL

S-001 GENERAL STRUCTURAL NOTES AND SPECIAL INSPECTIONS ■

S-002 ELEVATION AND DETAILS ■

1/16" = 1'-0"

SITE PLAN1

A.

B.

C.

D.

ALL WORK SHOWN ON THIS SHEET IS INCLUDED IN THE CONTRACT FOR CONSTRUCTION,

WHETHER SHOWN ELSEWHERE OR NOT. CONTRACTOR SHALL MAKE ALLOWANCES FOR

CONNECTION, HOOK UP, ETC. AS REQUIRED SO THAT ITEMS, EQUIPMENT, ETC. ARE FIT

FOR INTENDED PURPOSE.

PROVIDE LISTED FIRESTOP, CONTINUOUS AT PERIMETER GAPS OF ALL RATED

CONSTRUCTION AS REQUIRED TO MAINTAIN THE SPECIFIED RATING.

DOCUMENTATION OF EXISTING CONDITIONS BASED ON 2026 CONSTRUCTION

DOCUMENTS PERMIT SET.

CONTRACTOR SHALL COORDINATE EXISTING LIGHT SWITCH WITHDING ANY NEW OR

RELOCATED EQUIPMENT.

GENERAL NOTES

THIS PROJECT IS AN ALTERATION TO REPAIR VEHICULAR DAMAGE TO AN EXISTING CMU BUILDING BY

REPLACING THE EXTERIOR CMU WALL CONSTRUCTION AND REPLACING A DOOR.

BUILDING NARRATIVE

2025 OREGON STRUCTURAL SPECIALTY CODE (OSSC) BASED ON THE 2024 INTERNATIONAL BUILDING CODE

WITH OREGON AMENDMENTS

2023 OREGON ELECTRICAL SPECIALTY CODE (OESC) BASED ON 2023 NFPA 70 NATIONAL ELECTRIC CODE

2021 INTERNATIONAL EXISTING BUILDING CODE (IEBC) WITH OSSC CH 34 AMENDMENTS

APPLICABLE BUILDING REGULATIONS

A.

B.

REFER TO SPECIFICATION SECTION 02 41 00 - DEMOLITION AND 01 70 00 - EXECUTION

AND CLOSEOUT REQUIREMENTS FOR ADDITIONAL INFORMATION.

COORDINATE DEMO WORK WITH NEW CONSTRUCTION. DEMOLITION AND REMOVAL

WORK SHALL BE DONE AS NEATLY AND CAREFULLY AS POSSIBLE TO PREVENT DAMAGE

TO ADJACENT SURFACES AND/OR EQUIPMENT. CUTTING SHALL BE DONE IN NEAT,

STRAIGHT, TRUE LINES USING THE PROPER CUTTING TOOLS WITH MINIMAL OR NO

DAMAGE TO REMAINING MATERIAL. PRIOR TO CUTTING STRUCTURAL ITEMS THE

CONTRACTOR SHALL HAVE THE STRUCTURAL ENGINEER REVIEW REMOVAL METHODS.

GENERAL NOTES - DEMOLITION

A. REFERENCE STRUCTURAL FOR CONCRETE MASONRY UNIT, BEARING AND SHEAR WALL

REQUIREMENTS.

123C

FRAMING MEMBER MATERIAL

AND SIZE (WALL ONLY)

NOMINAL 8" CMU

CEMENTITIOUS WALLS**

A

*REFERENCE STRUCTURAL DOCUMENTS FOR BEARING AND SHEAR WALL REQUIREMENTS

**REFERENCE STRUCTURAL DOCUMENTS FOR BEARING AND REINFORCING REQUIREMENTS

ASSEMBLY NUMBER

GENERAL NOTES - WALL ASSEMBLIES

ASSEMBLY TAG - KEY

FRAMING MEMBER SIZE DESIGNATION

PERMIT APPLICANT: SERA DESIGN AND ARCHITECTURE, INC. 503.445.7372

ON BEHALF OF WASHINGTON COUNTY

LEGAL DESCRIPTION:

GARDEN TRACT ADDITION, BLOCK 1, LOT 26 AND PTS 23-25, ACRES .39 IN THE CITY OF HILLSBORO, COUNTY OF WASHINGTON AND STATE OF OREGON. TAX ID #: 1N336DA12600.

SEISMIC ZONE:

DESIGN CATEGORY D

OCCUPANCY CLASSIFICATION:

BUSINESS GROUP B - CIVIC ADMINISTRATION

PROJECT ADDRESS: 235 W. MAIN ST, HILLSBORO, OR 97124

GENERAL INFORMATION

CONSTRUCTION TYPE: III-B

CHAPTER 5

BUILDING HEIGHT (PER TABLE 504.3) 55' 30' - NO CHANGE

ALLOWABLE EXISTING

NUMBER OF STORIES (PER TABLE 504.4) 3 STORIES 1 STORY - NO CHANGE

EXISTING BUILDING CONSTRUCTION

SITE

VICINITY MAP

WASHINGTON COUNTY

169 NORTH FIRST AVENUE, MS-42

HILLSBORO, OR 97124

TEL: (503) 846-8715

ATTN:

TRACY ORVIS, PROJECT MANAGER

TRACY_ORVIS@WASHINGTONCOUNTYOR.GOV

SERA DESIGN AND ARCHITECTURE, INC

600 SW 10TH AVE #500

PORTLAND, OR 97205

TEL: (503) 445-7372

ATTN: GEORGE HAGER, PRINCIPAL

GEORGEH@SERADESIGN.COM

KPFF

111 SW 5TH AVE #2600

PORTLAND, OR 97204

TEL: (503) 227-3251

ATTN: ERIK KABUSTREITER, PROJECT MANAGER

ERIK.KABUSREITER@KPFF.COM

OWNER:

ARCHITECT OF

RECORD:

STRUCTURAL

ENGINEER:

PROJECT DIRECTORY

DISCLAIMER

THE WRITTEN AGREEMENT, DRAWINGS, SPECIFICATIONS AND ANY ADDENDA COMPRISE

THE CONTRACT FOR THIS PROJECT. THEY SHALL BE TREATED AS ONE ENTITY, EQUALLY,

WITHOUT PRIORITY. ITEMS, ELEMENTS, FIXTURES, SYSTEMS AND EQUIPMENT SHOWN

SHALL BE FURNISHED AND INSTALLED EVEN THOUGH TYPICALLY SHOWN ELSEWHERE.

THEREFORE IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO READ AND COMPREHEND

ALL THESE DOCUMENTS IN ORDER TO COMPLETE THE WORK. IF A CONTRACTOR CHOOSES

TO NOT THOROUGHLY REVIEW THE ENTIRE SET OF CONTRACT DOCUMENTS, THEY DO SO

AT THEIR OWN RISK AND AGREE TO FURNISH & INSTALL ALL ITEMS NOTED ABOVE AT NO

ADDITIONAL COST OR DELAY TO THE OWNER. (THE ONLY EXCEPTION TO THIS IS THAT THE

SPECIFICATIONS SHALL TAKE PRECEDENCE OVER GENERAL NOTES ON THIS SHEET.)

CMU WALL

A CITY REVIEW

RESPONSE

7.31.26

A

3/32" = 1'-0"

EXISTING FLOOR PLAN2

A

A

" C

R

2'- 0"

6'- 4"

4'- 8" A1013

A101 4

401A0

LEVEL 01

100'-0"

6"

SURFACE MOUNTED CONDUIT TO BE RUN

ALONG THE CEILING AND DOWN THE WALL

FOR EXISTING LIGHT FIXTURE CONTROL,

PAINT TO MATCH WALL

RB-1

P-1

LEVEL 01

100'-0"

SPECIALITY SHAPED CMU BLOCK

TO MATCH EXISTING PATTERN, VIF

P-2

EXTENTS OF NEW CMU

WALL CONSTRUCTION

REMOVE CEILING WHERE NECESSARY FOR NEW

CMU WALL AND CONNECTIONS TO ROOF

STRUCTURE. REPAIR ANY DAMAGE TO CEILING

AND INSTALL NEW ELECTRICAL WIRING FOR

SWITCH, PAINT TO MATCH EXISTING.

6"

REMOVE PORTION OF EXISTING SOFFIT

SHEATHING TO ALLOW FOR THE NEW CMU

WALL TO BE CONSTRUCTED, PATCH BACK

SOFFIT SHEATHING AND PAINT TO MATCH

EXISTING.

MAX

1'-0"

OPENING WIDTH

OP

EN

IN

G

HE

IG

HT

F-2 = PAIR

SEE

SCHED

SEE

SCHED

WIDTH

OPENING

OP

EN

IN

G

HE

IG

HT

SEE ASSEMBLIES

08 11 13 - HOLLOW METAL FRAME

08 11 13 - HM DOOR

07 92 00 - JOINT SEALANT

SEE ASSEMBLIES

2"

VA

RI

ES

2"

07 92 00 - JOINT SEALANT

08 11 13 - HOLLOW METAL FRAME

DI

M

PO

IN

T

2"

DIM POINT

EXTERIOR

EXTERIOR

4"

7 5/8"

10 74 49 - RUBBER WEDGE RAMP

FULL WIDTH OF DOOR OPENING

08 11 13 - HM DOOR AND FRAME

BED OF SEALANT

08 11 13 - THRESHOLD

EXISTING SIDEWALK

04 20 00 UNIT MASONRY

NAME DESCRIPTION PRODUCT COMMENTS

CMU-1 16x8x8 VIF PAINTED TO MATCH EXISTING SPECIALITY BLOCK SHAPE TO MATCH EXISTING PATTERN ON THE BUILDING

09 65 00 RESILIENT FLOORING

NAME DESCRIPTION PRODUCT COMMENTS

RB-1 RUBBER BASE MFG: MATCH EXISTING

COLOR: MATCH EXISTING

SIZE: MATCH EXISTING

RF-1 LVT FLOORING MFG: PATCRAFT

STYLE: LOCAL RESERVE I592V

COLOR: FOG 00560

SIZE: 7" X 48"

COUNTY TO PROVIDE ATTIC STOCK FOR

MINOR REPAIRS

09 91 13 & 09 91 23 PAINT & COATING

NAME DESCRIPTION PRODUCT COMMENTS

P-1 GENERAL INTERIOR PAINT MFG: MATCH EXISTING

COLOR: MATCH EXISTING

FINISH: EGGSHELL AT WALLS AND FLAT AT CEILINGS

P-2 EXTERIOR PAINT MFG: MATCH EXISTING

COLOR: MATCH EXISTING

FINISH: MATCH EXISTING

REVISIONS

SE

RA

D es ign an d A rch ite ctu re , In c.

ARCHITECTURE

URBAN DESIGN + PLANNING

INTERIOR DESIGN

PORTLAND|OAKLAND

SERADESIGN.COM

CHECKED BY:

ISSUE DATE:

PROJECT NO:

6/ 3/

:2

2:

P M

A D

A M

S A

N N

EX

C

M U

R

EP

A

IR

W

AS

H

IN

G

TO

N C

O U

N

TY

W . M ai n

St

H ills bo ro

, O R

, 9

A1

P

LA

N S, E

LE

VA

TI

O N

S

D

ET

AI

LS

PE

RM

IT

S

ET

A101

AM

14 MAY 2026

2503066

PLANS,

ELEVATIONS &

DETAILS

A. FLOOR PLAN KEYED NOTES APPLY TO A100 SERIES SHEETS. ALL KEYED NOTES MAY

NOT OCCUR ON THIS SHEET AND DO NOT APPLY TO ANY OTHER SHEETS EXCEPT THOSE

NOTED.

DOOR OPENING SCHEDULE

NO

OPENING RATING

(HOURS)

DOOR FRAME DETAIL

COMMENTSW H TYPE MATL FIN HDWR TYPE MATL FIN HEAD JAMB SILL

LEVEL 01

01 6'-0" 7'-0" --- F : F2 HM P-2 01 01 HM P-2 7/A101 7/A101 8/A101 ---

GENERAL NOTES - FLOOR PLAN

1/4" = 1'-0"

DOOR TYPE5 1/4" = 1'-0"

FRAME TYPE6

KEYED NOTES - FLOOR PLAN

1 ALIGN

2 PROVIDE NEW LIGHT SWITCH WITH SURFACE MOUNTED CONDUIT TYING INTO EXISTING

WIRING.

3 REMOVE REMAINING DAMAGED CMU FULL HEIGHT FROM DOOR OPENING TO EDGE OF

DAMAGED WINDOW OPENING

1/4" = 1'-0"

FLOOR PLAN1

1/4" = 1'-0"

INTERIOR ELEVATION4 1/4" = 1'-0"

EAST ELEVATION3

1/4" = 1'-0"

REFLECTED CEILING PLAN2

3" = 1'-0"

HM DOOR HEAD/ JAMB7

3" = 1'-0"

HM THRESHOLD8

DESIGN CRITERIA

DESIGN WAS BASED ON THE STRENGTH AND DEFLECTION CRITERIA OF THE OSSC. IN ADDITION TO THE DEAD LOADS, THE FOLLOWING LOADS AND ALLOWABLES WERE USED FOR DESIGN, WITH LIVE LOADS (L.L.) REDUCED PER OSSC:

SNOW CRITERIA

DESIGN ROOF SNOW LOAD 25 PSF MINIMUM IN ACCORDANCE WITH OSSC

GROUND SNOW LOAD

Pg= 15 PSF

IN ACCORDANCE WITH: snowload.seao.org

FLAT ROOF SNOW LOAD Pf = 14 PSF

SNOW EXPOSURE FACTOR Ce = 0.9

SNOW LOAD IMPORTANCE FACTOR Is = 1.0

THERMAL FACTOR Ct = 1.0

WIND CRITERIA

RISK CATEGORY II

BASIC WIND SPEED VULT = 107 MPH (3-SECOND GUST) VASD = 83 MPH (3-SECOND GUST)

SURFACE ROUGHNESS CATEGORY C

EXPOSURE CATEGORY C

GUST / INTERNAL PRESSURE GCpi = +/- 0.18

POST-INSTALLED CONCRETE ANCHORS

POST-INSTALLED CONCRETE ANCHORS SHALL BE THE FOLLOWING PRODUCTS, U.N.O.:

TYPE APPROVED ANCHORS

ADHESIVE ANCHORS SIMPSON SET-3G (ICC ESR-4057)

ANCHORS SHALL BE INSTALLED IN STRICT CONFORMANCE WITH THE MANUFACTURER'S RECOMMENDATIONS AND PRODUCT EVALUATION REPORTS. EMBEDMENTS SPECIFIED ON DRAWINGS ARE "EFFECTIVE" EMBEDMENTS.

REFERENCE MANUFACTURER LITERATURE FOR CORRESPONDING ACTUAL EMBEDMENT DEPTHS. DO NOT CUT

REINFORCING IN NEW OR EXISTING CONCRETE DURING INSTALLATION.

REQUESTS FOR ANCHOR SUBSTITUTIONS SHALL BE SUBMITTED TO THE SEOR IN WRITING ALONG WITH EVIDENCE OF

EQUAL OR GREATER CAPACITY TO THE SPECIFIED CONNECTION.

REINFORCED CONCRETE MASONRY

CONCRETE MASONRY UNITS SHALL COMPLY WITH ASTM C90, MEDIUM WEIGHT, SAMPLED AND TESTED IN ACCORDANCE w/ ASTM C140. LINEAL SHRINKAGE FOR UNITS SHALL NOT EXCEED 0.065%. BLOCK COMPRESSIVE STRENGTH SHALL BE AS INDICATED IN BELOW TABLE. ASSEMBLIES SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH ( f 'm) AS INDICATED IN BELOW TABLE AS VERIFIED BY THE UNIT STRENGTH METHOD CONFORMING TO OSSC CHAPTER

17 AND TMS 602-16. WALLS SHALL BE REINFORCED AS SHOWN ON THE ELEVATION.

ASSEMBLY STRENGTH

f'm (PSI)

BLOCK UNIT STRENGTH

(PSI)

GROUT STRENGTH (PSI) MORTAR

2,000 2,000 2,000 TYPE M OR S

MORTAR

MORTAR SHALL BE OF THE TYPE INDICATED IN THE PRECEDING TABLE, WITH A MINIMUM COMPRESSIVE STRENGTH AT 28 DAYS OF 1,800 PSI FOR TYPE S MORTAR OR 2,500 PSI FOR TYPE M MORTAR AND SHALL CONFORM WITH ASTM C270

AND OSSC SECTION 2103.

REINFORCING SHALL CONFORM TO OSSC SECTION 2103.4 AND TMS 602-16 ARTICLE 2.4. DEFORMED BARS SHALL BE ASTM A615 GRADE 60, AND SHALL BE SECURELY PLACED IN ACCORDANCE WITH TMS 602-16 SPECIFICATION SECTION 3.4.

REINFORCING STEEL SHALL BE DETAILED IN ACCORDANCE WITH THE "ACI MANUAL OF STANDARD PRACTICE FOR DETAILING REINFORCED CONCRETE STRUCTURES," ACI 315. SHOP DRAWINGS SHALL INCLUDE ELEVATIONS OF ALL STRUCTURAL CMU WALLS SHOWING LOCATIONS OF BOND BEAMS, BARS, AND OTHER SPECIAL REINFORCEMENT.

MASONRY REINFORCING STEEL

GROUT SHALL HAVE COMPRESSIVE STRENGTH AS INDICATED IN THE PRECEDING TABLE AND SHALL CONFORM TO OSSC SECTION 2103. GROUT SHALL CONSIST OF A MIXTURE OF CEMENTITIOUS MATERIALS AND AGGREGATE TO WHICH SUFFICIENT WATER HAS BEEN ADDED TO CAUSE THE MIXTURE TO FLOW WITHOUT SEGREGATION OF THE CONSTITUENTS. ALL CELLS CONTAINING VERTICAL BARS AND ALL BOND BEAMS SHALL BE FILLED WITH GROUT. FULLY

GROUT ALL STRUCTURAL MASONRY WALLS UNLESS NOTED OTHERWISE.

MASONRY GROUT

THE MAXIMUM GROUT POUR HEIGHT SHALL BE 12'-8". CLEAN-OUTS ARE REQUIRED FOR ANY POUR HEIGHT GREATER THAN 5'-4". WHERE REQUIRED, CLEAN-OUTS SHALL BE LOCATED AT ALL CORES CONTAINING VERTICAL REINFORCEMENT AND AT A MAXIMUM OF 32" O.C. GROUT LIFTS GREATER THAN 5'-4" ARE LIMITED IN HEIGHT TO THE BOTTOM OF THE LOWEST BOND BEAM THAT IS MORE THAN 5'-4" ABOVE THE BOTTOM OF THE LIFT, PROVIDED THAT:

1) THE MASONRY HAS CURED FOR AT LEAST 4 HOURS, AND 2) THE GROUT SLUMP IS MAINTAINED BETWEEN 10 AND 11 INCHES. IF EITHER OF THESE TWO CONDITIONS ARE NOT MET, THEN THE MAXIMUM LIFT HEIGHT SHALL BE 5'-4".

SPECIAL INSPECTIONS AND TESTING

SPECIAL INSPECTION WILL BE PROVIDED BY THE OWNER BASED ON THE REQUIREMENTS OF THE OSSC AS SUMMARIZED IN THE SPECIAL INSPECTION AND TESTING PROGRAM BELOW. CONTRACTOR SHALL PROVIDE SUFFICIENT NOTICE AND ACCESS FOR

THE SPECIAL INSPECTOR TO PERFORM THESE INSPECTIONS.

MASONRY MINIMUM VERIFICATION REQUIREMENTS

MINIMUM VERIFICATION

PRIOR TO CONSTRUCTION,

VERIFICATION OF COMPLIANCE

OF SUBMITTALS.

REQUIRED FOR QUALITY ASSURANCE LEVEL

QUALITY

ASSURANCE

LEVEL 1

QUALITY

ASSURANCE

LEVEL 2

QUALITY

ASSURANCE

LEVEL 3

TMS 602-16

Table 3 (S-25)

CODE REFERENCE

REQUIRED - - -ART. 1.5

REMARKS

SYSTEM OR MATERIAL

UNIT STRENGTH METHOD-MASONRY UNIT

MASONRY- REQUIRED TESTING

OSSC CODE REFERENCE OR

REFERENCED STANDARD

REMARKS

OSSC 1705.4 , TMS 602 1.4.B, TMS

602.2.3, TMS 602 2.3 E, ASTM

REFERENCES PER REMARKS

CONCRETE MASONRY (ASTM C90)

CONCRETE MASONRY UNIT MATERIALS TO

CONFORM TO

ASTM C55, C73, C90, C129, C744, OR C1634 AS

SPECIFIED.

UNIT STRENGTH METHOD-COMPRESSIVE

STRENGTH OF MORTAR

OSSC 1705.4, TMS 602 2.1 , ASTM C270 MORTAR SHALL COMPLY WITH ASTM C270 .

UNIT STRENGTH METHOD-COMPRESSIVE

STRENGTH OF GROUT

OSSC 1705.4, TMS 602 2.2, ASTM C476

GROUT SHALL COMPLY WITH ASTM C476.

WHEN f'm EXCEEDS 2,000 PSI PROVIDE

COMPRESSIVE STRENGTH THAT EQUALS OR

EXCEEDS f'm. DETERMINE COMPRESSIVE

STRENGTH OF GROUT IN ACCORDANCE

WITH ASTM C1019. DO NOT USE

ADMIXTURES UNLESS ACCEPTABLE. FIELD

ADDITION OF ADMIXTURES IS NOT

PERMITTED IN SELF-CONSOLIDATING

GROUT.

GENERAL NOTES:

1.4 B.1 OR 1.4 B.2 EITHER THE UNIT STRENGTH METHOD OR THE PRISM TEST METHOD MAY BE CHOSEN TO SATISFY SPECIAL INSPECTIONS

COMPRESSIVE STRENGTH FOR EACH WYTHE.

PROVIDE CLEAR COVER TO MASONRY REINFORCING AS FOLLOWS:

REINFORCING STEEL COVER

USE

MASONRY FACE NOT EXPOSED TO EARTH OR WEATHER

MINIMUM COVER

(TO OUTSIDE FACE OF MASONRY)

1 1/2"

MASONRY FACE EXPOSED TO EARTH OR WEATHER

1 1/2" (#5 AND SMALLER)

2" (#6 AND LARGER)

MASONRY ACCESSORIES

POST INSTALLED ANCHORS SHALL BE INSTALLED IN STRICT CONFORMANCE WITH MANUFACTURER'S PRINTED INSTALLATION INSTRUCTIONS AND PRODUCT EVALUATION REPORTS. REINFORCING IN NEW OR EXISTING MASONRY SHALL NOT BE CUT DURING INSTALLATION. ALL ANCHORS EXPOSED TO EARTH OR WEATHER SHALL BE PROTECTED FROM CORROSION BY HOT-DIP GALVANIZING OR USE OF STAINLESS STEEL. ALL THREAD ROD FOR ADHESIVE ANCHORS

SHALL CONFORM TO ASTM F1554 GRADE 55, U.N.O.

LOADS SHALL NOT BE PLACED ON ADHESIVE ANCHORS UNTIL ADHESIVE IS FULLY CURED. MASONRY SUBSTRATE SHALL BE DRY, WITHIN THE ALLOWABLE TEMPERATURE RANGE, HOLES SHALL BE MADE WITH A HAMMER DRILL USING A CARBIDE TIPPED DRILL BIT, AND CLEANED IN ACCORDANCE WITH THE MANUFACTURER'S PRINTED INSTALLATION

INSTRUCTIONS.

POST-INSTALLED MASONRY ANCHORS

TYPE APPROVED ANCHOR

ADHESIVE SIMPSON SET - 3G (ICC EST-4844)

TABLE NOTE:

MINIMUM GROUT COVER BETWEEN REINFORCEMENT AND INSIDE FACE OF CELL SHALL BE 1/4" FOR FINE

GROUT AND 1/2" FOR COURSE GROUT.

ANCHORS - SPECIAL INSPECTIONS

SYSTEM OR MATERIAL

OSSC CODE

REFERENCE

CODE OR

STANDARD

REFERENCE

FREQUENCY (NOTE 6)

REMARKSCONTINUOUS PERIODIC

ACI 318: 17.2.5 SEE NOTES

BELOW

POST INSTALLED ADHESIVE ANCHORS

IN HARDENED CONCRETE AND

COMPLETED MASONRY

SPECIAL INSPECTION OF MECHANICAL POST INSTALLED ANCHORS SHALL BE IN STRICT CONFORMANCE WITH THE ICC REPORT AND MANUFACTURER'S INSTALLATION REQUIREMENTS. ANCHOR INSTALLERS SHALL BE QUALIFIED AS REQUIRED BY JURISDICTION

REQUIREMENTS.

INSPECTION REPORTS SHALL IDENTIFY NAMES OF INSTALLERS.

SPECIAL INSPECTOR SHALL PROVIDE DOCUMENTATION AT THE END OF ANCHOR INSTALLATIONS STATING THAT THE ANCHORS WERE

INSPECTED PER APPROVED ANCHOR EVALUATION REPORT.

GENERAL

STRUCTURAL DRAWINGS ARE A PART OF THE CONTRACT DOCUMENTS AND ARE COMPLEMENTARY TO THE ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING DRAWINGS, THE SPECIFICATIONS AND OTHER CONTRACT DOCUMENTS. THE CONTRACTOR IS RESPONSIBLE FOR COORDINATING THE REQUIREMENTS FROM THE CONTRACT DOCUMENTS INTO THEIR SHOP DRAWINGS AND WORK. AS REQUIRED BY THE GENERAL

CONDITIONS, THE CONTRACTOR SHALL PROMPTLY REPORT TO THE ARCHITECT ANY ERRORS,

INCONSISTENCIES, OR OMISSIONS IN THE CONTRACT DOCUMENTS DISCOVERED BY OR MADE KNOWN TO THE

CONTRACTOR.

THE GENERAL STRUCTURAL NOTES SUPPLEMENT THE PROJECT SPECIFICATIONS. REFER TO THE PROJECT SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS. NOTES AND DETAILS ON THE STRUCTURAL DRAWINGS SHALL TAKE PRECEDENCE OVER THE GENERAL STRUCTURAL NOTES AND TYPICAL DETAILS. WHERE NO DETAILS ARE GIVEN, CONSTRUCTION SHALL BE AS SHOWN FOR SIMILAR WORK. WHERE CONFLICT EXISTS, THE MORE STRINGENT OR RESTRICTIVE REQUIREMENT SHALL GOVERN UNTIL CLARIFICATION IS REQUESTED.

CODE REQUIREMENTS:

CONFORM TO THE 2025 OREGON STRUCTURAL SPECIALTY CODE (OSSC), BASED ON THE 2024 INTERNATIONAL

BUILDING CODE (IBC).

TEMPORARY CONDITIONS:

THE STRUCTURE IS DESIGNED TO FUNCTION AS A UNIT UPON COMPLETION. THE CONTRACTOR IS RESPONSIBLE FOR FURNISHING ALL TEMPORARY BRACING AND/OR SUPPORT THAT MAY BE REQUIRED AS THE RESULT OF THE

CONTRACTOR'S CONSTRUCTION METHODS AND/OR SEQUENCES UNTIL COMPLETION.

CONTRACTOR'S CONSTRUCTION AND/OR ERECTION SEQUENCES SHALL RECOGNIZE AND CONSIDER THE EFFECTS OF THERMAL MOVEMENTS OF STRUCTURAL ELEMENTS DURING THE CONSTRUCTION PERIOD.

EXISTING CONDITIONS:

ALL EXISTING CONDITIONS, DIMENSIONS AND ELEVATIONS SHALL BE FIELD VERIFIED. THE CONTRACTOR SHALL NOTIFY THE ARCHITECT OF ANY SIGNIFICANT DISCREPANCIES FROM CONDITIONS SHOWN ON THE DRAWINGS.

ASSUMED FUTURE CONSTRUCTION:

VERTICAL: NONE

HORIZONTAL: NONE

111 SW Fifth Ave., Suite 2600

Portland, OR 97204

O: 503.227.3251

F: 503.227.7980 www.kpff.com

CHECKED BY:

ISSUE DATE:

PROJECT NO:

REVISIONS

ARCHITECTURE

URBAN DESIGN + PLANNING

INTERIOR DESIGN

PORTLAND|OAKLAND

SERADESIGN.COM

10022300225 R25 Kpff

P E

R M

IT

A D

A M

S A

N N

E X

C M

U R

E P

A

IR

W A

S H

IN

G

T O

N C

O U

N T

Y

W

M a in

S tr e e t, H ill s b o ro

O

R

S-001

PB, EK

05.14.2026

10022300225

GENERAL

STRUCTURAL NOTES

AND SPECIAL

INSPECTIONS

S-001 GENERAL STRUCTURAL NOTES AND SPECIAL

INSPECTIONS

S-002 ELEVATION AND DETAILS

DRAWING INDEX

ISSUE LOG

D R

D A

T E

ISSUE LOG KEY:

' X ' ISSUED AS PART OF A SET

' - ' NOT A PART OF ISSUED SET

' * ' FOR INFORMATION ONLY

/2

/2

EXPIRES 06/30/2027

(E) ROOF

(E) 8" CMU WALL

CMU WALL

PLAN NOTES:

1. INDICATES EXISTING STRUCTURE.

2. FIELD VERIFY EXISTING DIMENSIONS AND ELEVATIONS.

3. INDICATES CMU WALL.

S-002

S-002

#4 EPOXY ANCHOR

MATCHING

SPACING OF

HORIZONTAL REINF. AT

CL OF WALL w/ 6" MIN.

EMBED

(2) #4 @ 48" o.c.

HORIZONTAL

BARS

S-002

#4 EPOXY ANCHOR

MATCHING SPACING OF

VERT. REINF. AT CL OF

WALL w/ 6" MIN. EMBED

TYP.

12" LAP SPLICE

L A

P S

P L

IC

E T

Y P

#6 @ 48" o.c.

VERTICAL BARS

TYP.

12" LAP SPLICE

REF. ARCH. FOR SHAPED

DECORATIVE BLOCK

AS OCCURS

(E) ROOF

(E) FOOTING

TO REMAIN

TOP OF FOOTING

8" CMU WALL

REF. ELEVATION

SHORE ROOF

UNTIL MASONRY

HAS CURED

SIMPSON LTA2

CONNECTOR REF.

3/S-001

CAPILLARY BREAK

BETWEEN WOOD

RAFTER AND CMU BLOCK

TYP.

REMOVE AND REPLACE

AS REQUIRED FOR

MASONRY REPAIR

(E) ROOF

8" THICK SOLDIER

COURSE BEAM LINTEL

(2) #4

HORIZONTAL BARS

SHORE ROOF

UNTIL MASONRY

HAS CURED

SIMPSON LTA2

CONNECTOR FROM

EXISTING RAFTER

EMBEDED INTO TOP OF

CMU BLOCK AT EACH

RAFTER

CAPILLARY BREAK

BETWEEN WOOD

RAFTER AND CMU

BLOCK TYP.

REMOVE AND REPLACE

AS REQUIRED FOR

MASONRY REPAIR

HAIRPIN BAR TO

MATCH HORIZ. REINF.

SIZE AND SPACING. LAP

w/ BOND BEAM REINF.

PER LAP SPLICE

SCHEDULE ON

GENERAL STRUCTURAL

NOTES

VERTICAL

REINFORCING

END OF WALL

T Y

P

/2

M

IN

C

O V

E R

T Y

P

/2

M

IN

C L R

8" NOM. MIN. SOLID

GROUTED CMU(2) 1" O.D. VERT. CONDUITS OR

(1) 1 1/2" O.D. VERT. CONDUIT

IN CELL NOT CONTAINING

REINFORCING.

MIN.

(3) O.D.

SPACING

NOTES:

1. ALUMINUM CONDUITS ARE NOT PERMITTED.

2. PIPES CONTAINING LIQUID, GAS OR VAPORS AT

TEMPERATURES HIGHER THAN 150 ° F ARE NOT

PERMITTED TO BE EMBEDDED INTO CMU WALLS.

3. PIPES UNDER PRESSURE IN EXCESS OF 55 PSI

ARE NOT PERMITTED TO BE EMBEDDED IN CMU WALLS.

4. PIPES CONTAINING WATER OR OTHER LIQUIDS

SUBJECT TO FREEZING ARE NOT PERMITTED TO BE

EMBEDDED IN CMU WALLS.

5. A MAXIMUM OF (2) CELLS PER 48" OF CMU WALL IS

PERMITTED TO CONTAIN CONDUITS.

6. HORIZ. RUNS MUST BE LESS THAN 4'-0".

7. CONDUITS MAY BE INSTALLED IN CMU AT CONTRACTOR'S OPTION.

4' - 0"

111 SW Fifth Ave., Suite 2600

Portland, OR 97204

O: 503.227.3251

F: 503.227.7980 www.kpff.com

CHECKED BY:

ISSUE DATE:

PROJECT NO:

REVISIONS

ARCHITECTURE

URBAN DESIGN + PLANNING

INTERIOR DESIGN

PORTLAND|OAKLAND

SERADESIGN.COM

10022300225 R25 Kpff

P E

R M

IT

A D

A M

S A

N N

E X

C M

U R

E P

A

IR

W A

S H

IN

G

T O

N C

O U

N T

Y

W

M a in

S tr e e t, H ill s b o ro

O

R

S-002

PB, EK

05.14.2026

10022300225

ELEVATION AND

DETAILS

1" = 1'-0"1

CMU WALL ELEVATION

1" = 1'-0"2

TYP. WALL SECTION

1" = 1'-0"3

HEADER BEAM ABOVE

NEW DOOR OPENING

1" = 1'-0"4

CMU PIER/ END OF WALL DETAIL

1" = 1'-0"5

CONDUITS EMEDDED IN CMU WALL

EXPIRES 06/30/2027

001 G001 COVER SHEET AND CODE COMPLIANCE
002 A101 PLANS ELEVATIONS AND DETAILS
003 S-001 GENERAL STRUCTURAL NOTES
004 S-002 ELEVATION AND DETAILS
S-002 - ELEVATION AND DETAILS