The load bank must meet the following specifications: 230VAC L-N and 400VAC L-L, three-phase, 400 Hz power configuration; a 6-pin aircraft power receptacle with shield compliant with Drawing LE409-0001 (with suggested suppliers Anderson Airmotive part number 3-498501 or ITT Cannon EA376); minimum load capacity of 100 kW with incremental load switching of 10 kW or less; a meter displaying input frequency, volts, amps, and watts; E/F interlock protection; four BNC female connectors for oscilloscope monitoring of voltage, current, and frequency per phase; thermal protection; casters for transport; lifting pockets for forklift loading/unloading; and noise levels not exceeding 85 dB(A) in accordance with OSHA standard 29 CFR 1910.95.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DEPARTMENT OF THE AIR FORCE

OKLAHOMA CITY AIR LOGISTICS COMPLEX (AFMC)

TINKER AIR FORCE BASE, OKLAHOMA

21 January 2026

ITEM DESCRIPTION

1. The 76th AMXG/567th is requesting utilization of funds for the purchase of one (1) Portable Resistive Load Bank.

2. The requested equipment item description / Specifications are outlined below.

a. Quantity of one (1) Portable Resistive Load Bank.

(1) 230VAC L-N, 400VAC L-L, 3-Phase, 400 Hz

(2) 6-Pin Aircraft Power Receptacle with Shield

(a) Must be supplied in accordance with (IAW) the requirements specified in Drawing

LE409-0001.

(b) Suggested sources of supply (Anderson Airmotive part no. 3-498501 OR ITT Cannon EA376 IAW dwg. LE409-0001).

(3) Load capacity of 100 kW or more.

(4) Switch to load in increments of 10 kW or less.

(5) Meter to display input frequency, volts, amps, watts.

(6) E/F interlock.

(7) 4x BNC female connectors for monitoring of input power voltage, current, and frequency per phase with oscilloscope.

(8) Thermal Protection.

(9) Casters for ease of transport.

(10) Lifting pockets for loading/unloading with forklift.

(11) Noise level not to exceed 85 dB (A) IAW OSHA standard 29 CFR 1910.95.