A2 Drawing files - Mech.pdf

PDF 11 MB Posted

Attached to
Repair Earth Covered Magazines (ECMs) in Ammunition Holding Area (AHA) No. 25 Camp Casey
Solicitation number
W91QVN-20-R-0115
Issued by

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

AS SHOWN

M-1

MECHANICAL

BELL AND SPIGOT

TRAP, ELECTRIC (INDICATE TYPE)

SOLVENT CEMENT

REDUCER, ECCENTRIC (STRAIGHT, INVERT)

REDUCER, ECCENTRIC (STRAIGHT, DOWN)

FIRE DEPARTMENT CONNECTION

M E C H A N I C A L M A T E R I A L I N D I C A T I O N S & S Y M B O L S

TEE, OUTLET DOWN

ANCHOR, MAIN

BUTTERFLY

AIR LINE

valves : (for selective actuators)

GATE, ANGLE

PLUG VALVE

GATE, GLOBE

THREE WAY

CONTROL

DPT DEWPOINT TEMPERATUREAMERICAN WIRE GAUGEAWG

CENTIGRADE

CAPACITY

BRAKE HORSEPOWER

BAROMETER(-TRIC)

BOILING POINT

PRESSURE, BAROMETRIC

COOLING LOAD

COEFFICIENT

CUBIC METER PER HOUR

COUNTER CLOCKWISE

CLASSIFICATION

CAST IRON PIPE

CHILLED WATER

CIRCUIT

CUBIC METER

COMPRESSOR

CONTINUE

CONNECTIONCONN

CONT

CU M

CPRSR

CLASS

CLG LOAD

COEF

CMH

CKT

CIP

CHW

CCW

C

CAP

BP

BARO PR

BARO

BHP

FA FACE AREA OR FRESH AIR

FHC

FLA

FHY FIRE HYDRANT

FULL LOAD AMPERES

FIRE HOSE CABINET

EFF

EWT

EXPJT

EVAP

EP

EQPT

ESP

ENT

ECON

EDR

EAT

ECC

DX

DPDT

DPV

EFFICIENCY

EXPANSION JOINT

EXTERNAL STATIC PRESSURE

EVAPORAT (-E,-ING,-ED,-OR)

ENTERING WATER TEMP

EXPLOSION PROOF

ENTERING

EQUIPMENT

DRY PIPE VALVE

DOUBLE POLE DOUBLE THROW

ENTERING AIR TEMPERATURE

EQUIVALENT DIRECT RADIATION

DIRECT EXPANSION

ECONOMIZER

ECCENTRIC

air conditioning and refrigeration

AIR COOLED

ALARM CHECK VALVE

AIR CONDITION UNIT (S)

AVERAGE

APPROXIMATE

AMPERE(AMP, AMPS)

AIR HANDLING UNIT

ALTITUDE

AMBIENT

ALUMINUM

APPARATUS DEW POINT

AIR CONDITION (-ING,-ED)

AIR COOLED CONDENSING UNIT

APPROX

AVG

AMP

AMB

AIR COND

ALT

AL

AHU

ACCU

ACLD

ACU

ACV

ADP

C/HWS

C/HWR

CHS

CHR

D

RS

RL

RD

(NAME)

M

CU MM

DIAG

DO

DIV

DIFF

DB

DIA or

DBT

CW

Cv

CWP

DECIBEL OR DRY BULB

DRY BULB TEMPERATURE

DIAGRAM

DIVISION

DIESEL OIL

DIFFERENCE

DIAMETER

DEGREE

o

CUBIC MILLIMETER

COEFFICIENT, VALVE FLOW

CLOCKWISE OR COLD WATER

CIRCULATING WATER PUMP

HOT/CHILLED WATER SUPPLY

HOT CHILLED WATER RETURN

CHILLED WATER RETURN

CHILLED WATER SUPPLY

DRAIN

REFRIGERANT SUCTION

REFRIGERANT LIQUID

CONTROL AIR MAIN

PIPE TO BE REMOVED

REFRIGERANT DISCHARGE

GLOBE

GATE

A

BALL

SQ

PLUMBING

LIQUID LINELL

PLMB

LINEAR METER

LITERS PER DAY

LITERS PER HOUR

LAUNDRY TRAY

LITERS PER SECOND

LEAVING WATER TEMPERATURE

NOT APPLICABLE

NOISE CRITERIA

NORMALLY CLOSED

METERS PER SECOND

METERS PER HOUR

MINIMUM OR MINUTE

NORMALLY OPEN

NATIONAL TAPER PIPE (THREAD)

NOT IN CONTRACTNICKG KILOGRAM

KILOGRAM PER SQ. CENTIMETER (ABSOLUTE)

KILOGRAM PER SQ. CENTIMETER

KILOGRAM PER SQ. CENTIMETER (GAUGE)KG/SQ CM G

KG/SQ CM A

KG/SQ CM

NO

N.O.

NPT

NUMBER

KILOCALORIE PER HOUR

THERMAL CONDUCTIVITY

JOULE

IRON PIPE SIZE

ISOMETRIC

DIAMETER, INSIDE

KCAL/HR

K

J

ISO

ID

IPS

HEAD

HERTZ

HORIZONTAL

HORSEPOWER

HOT WATER

HOT WATER HEATER

HOUR(S)

MERCURY

HORIZ

HZ

HW

HWH

HP

HR

HD

HG

MAX MAXIMUM

NC

N/A

N.C.

MM

MPH

MPS

MIN

MILLIMETER

M

LT

LWT

LM

LPH

LPS

LPD

METERS

SUPPLY AIRSA

SANITARY

SUBMERSIBLE

SCHEDULE

SAN

SCH

SBM

UH

UR

U

QUART

QUANTITY

PERCENT

PETROLEUM, OIL AND LUBRICANTS

POINT OF CONNECTION

PARTS PER MILLION

PRESSURE REDUCING VALVE

RADIATOR

REFRIGERANT (12, 22, ETC)

REVOLUTIONS PER MINUTE

REFRIGERATION TON

THERMAL RESISTANCE

RETURN AIR

RELATIVE HUMIDITY

RT

RH

RPM

R12, R22

R

RA

RDTR

QT

QTY

PPM

PRV

POC

POL

THERM

TONS

TYP

THK

TSTAT

TD

TEMP

SYM

STOR

SUCT

STD

STL

SSU

SSF

SST

ST

FLEXIBLE CONNECTOR

EXPANSION JOINT

EXPANSION LOOP

FLOWMETER, ORIFICE

KILOGRAM PER SQ. METER (GAUGE)

KILOGRAM PER SQ. METER (ABSOLUTE)

KILOGRAM PER SQ. METER

STRAINER, BLOW OFF

PUMP (INDICATE USE)

PRESSURE GAUGE AND COCK

PRESSURE SWITCH

KILOWATT HOUR

LATENT HEAT

LEAVING AIR TEMPERATURE

FLOWMETER, VENTURI

A B B R E V I A T I O N S

FIBERGLASS REINFORCED PLASTIC

FEMALE PIPE THREAD

GRAMS

HOSE BIBB

FACE VELOCITY

FEED WATER PUMP

GAGE OR GAUGE

GALVANIZED STEEL

FIXTURE

GA

GALVS

HB

GR

FXTR

FVEL

FWP

FLUSH VALVE

FREQUENCY

FUEL OILFO

FREQ

FRP

FPT

FV

LAT

LH

LG

LBS

L

LAV

KWH

LENGTH

POUNDS

LITERS

LAVATORY

KG/SM G

KG/SM A

KG/SM

KJ

KW

KILOJOULE

KILOWATT

P

PS

FS

STRAINER

FLOW SWITCH

OFM

VFM

EJ

BALL JOINT

(2-WAY SHOWN)

OUTSIDE AIR

NOT TO SCALE

OUTSIDE AIR INTAKE LOUVER

POLE

OXYGEN

PASCAL

PRESSURE DROP OR DIFFERENCE

PHASE (ELECTRIC)

PRESSURE GAGE

OUTSIDE SCREW & YOKE

DIAMETER, OUTSIDE

PH

PG

Pa

PD

P

OXY

OS&Y

NTS

OA

OD

OAIL

SPR

SP

SPEC

SPDT

SM

SLPD

SLPS

SLPH

SEC

SF

SG

SH

SL

sprinkler

DRY-PIPE VALVE

PRE-ACTION VALVE

SIDEWALL SPRINKLER

ALARM CHECK VALVE

PENDENT SPRINKLER

UNION, SCREWED

UNION, FLANGED

TEE, SINGLE SWEEP

UPRIGHT SPRINKLER

COLD WATER

HOT WATER SUPPLY

HOT WATER RETURN

CONDENSATE DRAIN ABOVE

SANITARY DRAIN

ACID WASTE

CHEMICAL SUPPLY PIPES

FLOOR DRAIN

CONDENSATE DRAIN BELOW

FLOOR OR GRADE

FUNNEL DRAIN, OPEN

SURFACE CLEANOUT

VENT THRU ROOF

FLOOR CLEANOUT

PIPE SLEEVE

HOSE BIBB

BACKFLOW PREVENTER

PIPE SLEEVE WITH FIRE STOPPING

FLOOR SINK (200mm x 200mm)

PITCH OR PIPE, UP(U), DOWN(D)

FLOOR OR GRADE

(NAME)E

VAC

A

HWS

MTWR

HWR

MTWS

CR

CS

FOG

FOR

FOS

FOV

FOD

MU

VPD

PC

BBD

MPC

LPC

LPS

MPS

JWS

JWR

FCO

LOW TEMPERATURE HOT WATER RETURN

LOW TEMPERATURE HOT WATER SUPPLY

MEDIUM TEMPERATURE HOT WATER RETURN

MEDIUM TEMPERATURE HOT WATER SUPPLY

VACUUM (AIR)

COMPRESSED AIR

EXISTING PIPE

FUEL OIL RETURN

FUEL OIL SUPPLY

CONDENSATE WATER RETURN

CONDENSATE WATER SUPPLY

FUEL OIL GAUGE

PLAN ELEV.

BFP

200mm x 200mm

SCO

FUEL OIL TANK VENT

PUMPED CONDENSATE

BOILER BLOW DOWN

VACUUM PUMP DISCHARGE

FUEL OIL DRAIN

MAKE UP WATER

LOW PRESSURE STEAM

JACKET WATER SUPPLY

JACKET WATER RETURN

LOW PRESSURE CONDENSATE

MEDIUM PRESSURE CONDENSATE

MEDIUM PRESSURE STEAM

ACID

(NAME)

FD

CD

G GAS

CD

VENT

PIPING

heating plumbing

MOTOR ELECTRIC

CHECK, NON-SLAM

QUICK CLOSING, FUSIBLE LINK

SQUARE HEAD BALANCING COCK

PRESSURE REDUCING

SQUARE HEAD BALANCING COCK

HOSE END DRAIN

CONTROL, PNEUMATIC-ELECTRIC

CONTROL, ELECTRIC-PNEUMATIC

ALIGNMENT GUIDE

ANCHOR, INTERMEDIATE

AIR VENT, AUTOMATIC

AIR VENT, MANUAL

W/ MEASURING TAP

MV

AVV

S AIR SEPARATOR

S

R

SAFETY

QUICK OPENING

RELIEF

PE

LOCK SHIELD

NEEDLE

valves, special duty :

EP

M

S

CHECK, SWING

SOLENOID

DIAPHRAGM

LATERAL

TEE, OUTLET UP

REDUCER, CONCENTRIC

TEE

CONNECTION, TOP

ELBOW, TURNED UP

CONNECTION, BOTTOM

ELBOW, TURNED DOWN

fitting :

FLANGED

WELDED

R

SOLDERED

CAP

BUSHING

THERMOMETER

SCREWED

THERMOSTAT, ELECTRIC

valve actuators dampers

SQUARE

WATTHOUR OR WATER HEATER

HEAT TRANSFER COEFFICIENT

UNIT HEATER

URINAL

TEMPERATURE DIFFERENCE

TONS OF REFRIGERATION

THERMOMETER

THERMOSTAT

TYPICAL

THICKNESS

TEMPERATURE

SYMBOL

STAINLESS STEEL

SAYBOLT SECONDS FUROL

SAYBOLT SECONDS UNIVERSAL

STORAGE

SUCTION

STANDARD

STEEL

STEAM

WIDTH

WEIGHT

WASHER

WATERPROOF

WATER CLOSET

WATER-COOLED

W/

WT

WTRPRF

WSHR

WITH

WD

WH

WC

WCLD

FIRE DAMPER (PROVIDE ACCESS DOOR)

ELECTRIC MOTOR OPERATED DAMPER

SMOKE DAMPER (PROVIDE ACCESS DOOR)

PRESSURE, DYNAMIC(VELOCITY)

WET BULB TEMPERATURE

STATIC PRESSURE

LPD, STANDARD CONDITIONS

LPS, STANDARD CONDITIONS

LPH, STANDARD CONDITIONS

SINGLE POLE DOUBLE THROW

SPECIFICATION

SPRINKLER

SQUARE METER

SPECIFIC GRAVITY

SECOND

SAFETY FACTOR

SENSIBLE HEAT

SENSIBLE LOAD

VOLUME

VERTICAL

VISCOSITY

WET BULB

VENTILATION

WB

WBT

W

VP

WATT

VOL

VISC

VENT

VERT

VACUUM

VALVE

VARIABLE AIR VOLUME

VELOCITY

VOLTV

VAC

VLV

VAV

VEL

SD

AD

M

VD

AD FD

S

BDD

PNEUMATIC OPERATED DAMPER

SPLITTER DAMPER

BACKDRAFT DAMPER

MANUAL VOLUME DAMPER

DUCT SECTION, POSITIVE PRESS., FIRST

EXHAUST AIR GRILLE OR REGISTER, CEILING

DUCT SECTION, NEGATIVE PRESS., FIRST

ACCESS DOOR, VERTICAL OR HORIZONTAL

CHANGE OF ELEVATION, RISE(R), DOWN(D)

COWL, (GOOSENECK) AND FLASHING

F S

FC

TRANSITION

DETECTORS, FIRE AND/OR SMOKE

TURNING VANES

FLEXIBLE CONNECTION

SOUND ATTENUATOR

FLEXIBLE DUCT

AD

R

810mm x 400mm

810mm x 400mm

810mm x 400mm

FIGURE IS ON TOP

ACOUSTICAL LINING

DIRECTION OF FLOW

FIGURE IS ON TOP

(600mm x 300mmH, 472 LPS)

TG 600/300

NECK DIAMETER)

DIFFUSER, LINEAR

CEILING DIFFUSER, ROUND TYPE (200mm

CEILING DIFFUSER, SQUARE TYPE

EXISTING WORK TO BE REMOVED

200mm NCD

SUPPLY AIR GRILLE OR REGISTER, CEILING

EXHAUST AIR GRILLE OR REGISTER, CEILING

SUPPLY AIR GRILLE OR REGISTER, SIDEWALL

RETURN AIR GRILLE OR REGISTER, CEILING

TRANSFER GRILLE ASSEMBLY

LOUVER, DOOR OR WALL

UNDERCUT DOOR (13mm, 47.2 LPS)

DOOR GRILLE (300mmx150mmH)

(500mmWx300mmH, 94.4 LPS)

500/300L

47.2

UC 13mm

300x150

DG

94.4

SR

RR

RG

SG

EG

ER

SR

SG

DUCT WORK

grilles, registers and diffusers :

RLA

LRA

RATED LOAD AMPS

LOCKED ROTOR AMPS

REMOVE EXIST WORK(R)

(E) EXISTING WORK TO REMAIN.

OR END OF DEMOLITION WORK

POINT OF CONNECTION NEW TO EXISTING

SYMBOLS AND ABBREVIATIONS

MECHANICAL MATERIAL INDICATIONS &

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

DATE

CHIEF, ENGR'G DIV

FORCE PROTECTION

CHK'D

REVISIONS

IMCOM

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

FIRE & EMERGENCY SVC

SAFETY

190901

CHONG, ST

( BLDG S-251 & 252)

REPAIR EARTH COVERED MAGAZINES, AHA 25

CAMP CASEY

5. CONCRETE REMOVAL AND RESTORATION SHALL CONFORM TO SPECIFICATION.

NECESSARY DUCT CONNECTION(S) TO FUNCTION AS ORIGINALLY INTENDED.

12. PRIOR TO INSTALLING NEW HVAC AND PLUMBING PIPING CONTRACTOR MUST

COORDINATE WITH EXISTING DUCTWORK AND PIPING ELEVATION/LOCATION.

IF EXISTING DUCT ELEVATION IS CONFLICTED WITH NEW PIPING INSTALLATION,

REMOVE EXISTING DUCTWORK AND INSTALL NEW DUCTWORK AND MAKE ALL

CONTRACTING OFFICER FOR APPROVAL.

CONTRACTOR ACCORDING TO ACTUAL FIELD CONDITIONS AND SUBMITTED TO THE

FIELD CONDITIONS. SUCH DETAILS SHALL BE PREPARED IN THE FIELD BY THE

11. SOME DETAILS SHOWN ON THIS CONTRACT DRAWINGS MAY NOT MATCH EXACT

SUCH AS ANCHORS, HANGERS/SUPPORT, ETC.

10. ALL HVAC PIPING/DUCTWORK TO BE REMOVED SHALL INCLUDE ALL IT'S ACCESSORIES

9. ANY OPENING RESULT FROM THE REMOVAL WORK THAT'S NOT TO BE RE-USED

SHALL BE PATCHED OR RESTORED TO MATCH ADJACENT SURFACE OR AREA.

PER SPEC.

THIS CONTRACTOR.

AND SHALL BE VERIFIED AT THE JOB SITE.

CORRECTIONS FOR CONTRACTING OFFICER'S APPROVAL.

7. ALL WALL/FLOOR/ROOF OPENINGS RESULTED FROM THE REMOVAL OF PIPING AND

4. ANY PIPES THAT PENETRATE FIRE RATED WALL (EXISTING/ NEW) SHALL BE SEALED

6. NO MECHANICAL WORK CAN BE STARTED WITHOUT AN APPROVED SHOP DRAWINGS.

SHOP DRAWING SHALL NOT BE THE EXACT DUPLICATION OF THE CONTRACT DRAWING.

2. LOCATION AND SIZES OF EXISTING EQUIPMENT, DUCTWORK, PIPING, ETC. APPROXIMATE

OFFICER'S REPRESENTATIVE ATTENTION WITH RECOMMENDATIONS FOR PROPER

IF ANY DISCREPANCY IS DETECTED, IT SHOULD BE BROUGHT TO THE CONTRACTING

THE EXISTING CONDITIONS, EQUIPMENT, FINISHES, ETC., PRIOR TO START OF WORK.

1. THE CONTRACTOR SHALL VISIT THE SITE AND SHALL FAMILIARIZE HIMSELF WITH

THE WORK PERFORMED UNDER THIS CONTRACT SHALL BE REPAIRED OR REPLACED BY

THE EXISTING EQUIPMENT ANY EQUIPMENT, DUCT WORK, PIPING ETC. DAMAGED DUE TO

3. CONNECT TO EXISTING SYSTEM SHALL BE DONE IN SUCH A MANNER AS NOT DAMAGE

THE REQUIREMENTS OF SEAL CLASS C.

8. ALL SUPPLY, RETURN AND EXHAUST AIR DUCTWORK SHALL BE CONSTRUCTED

ACCORDING TO SMACNA STATIC PRESSURE CALSS 500PA AND DUCTWORK SHALL MEET

DUCTWORK SHALL BE PATCHED OR RESTORED TO MATCH ADJACENT SURFACE OR AREAS.

13.

CHANGES REQUIRED TO MAKE THIS

CONTRACTOR SHALL PROVIDE NECESSARY SHOP DRAWINGS FOR ANY

REQUIREMENT FOR GAS ONLY BURNERS MAY BE JUSTIFIABLE. THE

PACKAGE, PRIOR TO THE START OF CONSTRUCTION, THEREFORE THE

PROVIDE NATURAL GAS ACCESS TO THE BUILDING UNDER THIS DESIGN

CONCURRENT NATURAL GAS CONVERSION PROJECT PACKAGES MAY

HEATING SYSTEMS WITH DPW PRIOR TO THE START OF CONSTRUCTION.

AND OIL) BURNERS FOR HEATING HOT WATER AND DOMESTIC HOT WATER

THE CONTRACTOR SHALL COORDINATE THE USAGE OF DUAL FUEL (GAS

GENERAL NOTES

14.

TO RECOGNIZED COMMERICAL STANDARDS.

INSTALL ALL EQUIPMENT AND MATERIALS IN A FIRST CLASS MANNER CONFORMING

15.

AND OPERATION OF THE EQUIPMENT.

OR CONDITIONS THAT WILL PREVENT THE PROPER INSTALLATION, MAINTENANCE

OF EQUIPMENT AND NOYIFY THE ENGINEER OF ANY INADEQUATE CLEARANCES

REVIEW ALL SPACES WHERE EQUIPMENT IS TO BE INSTALLED PRIOR TO ORDERING

WHILE MEETING THE MANUFACTURER'S RECOMMENDED ACCESS REQUIREMENTS.

ALL EQUIPMENT SHALL BE CAPABLE OF FITTING INTO THE SPACES ALLOCATED

16.

FIRESTOP ALL PENETRATIONS BETWEEN FLOORS.

WITH A UL APPROVED SYSTEM APPROPRIATE FOR THE PENETRATION TYPE AND FIRE RATING,

PROPERLY FIRESTOP ALL PENETRATIONS THROUGH FIRE RATED WALL, FLOORS, OR PARTITIONS

17.

PROVIDE REMOTELY ACTUATED DAMPERS IN AREA WITH GYPBOARD OR CONCEALED CEILINGS.

THAT THE EQUIPMENT CAN BE MAINTAINED ADEQUATELY.

FOR TWO VALVES. COORDINATE THE LOCATION OF ACCESS PANELS TO INSURE

ITEM INDISE DUCTS REQUIRING SERVICING OR INSPECTION 12"x12" ACCESS PANELS

FIRE/SMOKE DAMPERS, DUCT SMOKE DETECTOR, BACKDRAFT DAMPERS AND FOR ANY

PROVIDE ACCESS DOORS IN DUCTS AT ALL AUTOMATIC CONTROL DAMPERS, FIRE DAMPERS,

PROVIDE ACCESS PANELS TO ALL CONCEALED VALVES, DAMPERS, AND EQUIPMENT.

18.

WITH THE CURRENT CITY AND COUNTRY.

SEISMICALLY BRACE ALL EQUIPMENT, PIPING AND DUCTWORK IN ACCORDANCE

19.

OR CONCEALED CEILINGS.

DRAWINGS OR NOT. PROVIDE REMOTELY ACTUATED DAMPERS IN AREAS WITH GYPBOARD

PROVIDE VOLUME DAMPERS ON DUCTWORK BRANCH LINES WHETHER SHOWN ON THE

OR CONCEALED CEILINGS.

DRAWINGS OR NOT. PROVIDE REMOTELY ACTUATED DAMPERS IN AREAS WITH GYPBOARD

PROVIDE VOLUME DAMPERS ON DUCTWORK BRANCH LINES WHETHER SHOWN ON THE19.

20.

OR EXTERIOR DUCT INSULATION AS REQUIRED PER SPECIFICATION.

DUCT SIZES SHOWN ARE NET SIZES INSIDE DUCTWORK. MAKE ALLOWANCES FOR INTERIOR

21.

THE FIRE WALL OR FLOOR. FIRE DAMPERS SHALL BE UL LISTED.

WALLS AND FLOORS. FIRE DAMPER RATINGS SHALL BE COMPATIBLE WITH

PROVIDE FIRE DAMPERS AT ALL DUCT PENETRATIONS THROUGH FIRE RATED

22.

TAKE-OFFS FROM SQUARE OR RECTANGULAR MAINS.

TAKE-OFFS FROM THE MAIN DUCT. PROVIDE SPIN-IN TYPE FITTINGS AT ALL ROUND DUCT

30 DEGREES OR USE RADIUS ELBOWS. PROVIDE AIR SPLITTER DAMPERS AT ALL BRANCH

PROVIDE TURNING VANES IN ALL ELBOWS THAT CHANGE AIR DIRECTION MORE THAN

23. PROVIDE VENTS AT ALL HIGH POINTS AND DRAINS AT ALL LOW POINTS OF WATER PIPING.

24.

AND FLOORS.

PROVIDE SLEEVES AND ESCUTCHEONS AT PIPE PENETRATIONS THROUGH CONCRETED WALL

25.

BODIES EXPOSED TO AIR BELOW THE FLOOR.

OR ANY OTHER COLD LIQUID WHICH MAY CREATE CONDENSATION, FROM SINK

INSULATE ALL SEWER PIPING RECEIVING AIR CONDITIONING CONDENSATE DRAINS,

INSTALL CONDENSATE DRAINS AT A MINIMUM SLOPE OF 1 / 4 INCH PER 1 FOOT.

26.

OTHERWISE INDICATED.

MOUNT ALL ROOM THERMOSTATS AT 4'-0" ABOVE FINISHED FLOOR UNLESS

27.

TO SUPPORT THE CONTROL REQUIREMENTS.

PROVIDE STEP DOWN TRANSFORMERS, AUXILARY RELAYS AND WIRING AS NECESSARY

AS SHOWN

M-2

MECHANICAL

SCOPE OF WORK

WORK CLASS "K" (REPAIR / MAINTENANCE WORK)

GENERAL NOTES AND SCOPE OF WORK

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

DATE

CHIEF, ENGR'G DIV

FORCE PROTECTION

CHK'D

REVISIONS

IMCOM

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

FIRE & EMERGENCY SVC

SAFETY

BLDG# S-251 AND S-252

1.

2.

BLDG# S-251 AND S-252, CP CASEY WITH NEW.

3.

AS INDICATED ON THE DRAWING.

REPLACE EXISTING DETERIORATED HUMIDITY SENSOR AND HUMIDITY LEVEL ALARM, BLDG# S-251 AND S-252, CP CASEY

REPLACE EXISTING DETERIORATED BLAST VALVES, BLDG# S-251 AND S-252, CP CASEY AS INDICATED ON THE DRAWING.

REPLACE EXISTING DETERIORATED PACKAGED DEHUMIDIFIER(2SETS), ANGLE IRON SUPPORT ASSOCIATED DUCTWORK, CHONG, ST

190901

( BLDG S-251 & 252)

M-3

DESICCANT DEHUMIDIFIER

TYPE

KG/H

CAPACITY

ITEM NO. QTY. SERVICE

PROCESS&REACTIVATION FAN

REMARK

5.0 Bldg# S-251

& S-252

PACKAGED DEHUMIDIFIER-1

DEHUMI-

LPS

192/70

DESICCANT WHEEL

HPS

TYPE

SIZE

(mm)

445x300t

KW

MOTOR

0.56

(PROCESS/

REACTIVATION)

REACTIVATION HEATER

ELEC.

TYPE

KW

CAPACITY

6.9

ELECTRIC SOURCE

V/PH/HZ

480/3/60

KW

TOTAL

POWER

7.8

(PROCESS)DIFICATION E.S.P.

(Pa)

DH

CE MARK, BACTERIOSTATIC ROTOR, SIEMENS CLIMATIX PLC CONTROL SYSTEM.2

REFER TO "MUNTERS, MODEL : ML690 CLIMATIX OR APPROVED EQUAL"

( BLDG S-251 & 252)

REPAIR EARTH COVERED MAGAZINES, AHA 25

CAMP CASEY

CHONG, ST

M E C H A N I C A L E Q U I P M E N T S C H E D U L E - 2

MECHANICAL EQIPMENT SCHEDULE - 2

190901

A

B C D

E F G HA

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

DATE

CHIEF, ENGR'G DIV

FORCE PROTECTION

CHK'D

REVISIONS

IMCOM

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

FIRE & EMERGENCY SVC

SAFETY

M-4

MECHANICAL

1.

NOTES:

CONTRACTOR SHALL VERIFY EXACT LOCATION, SIZE AND DIRECTION

2.

OF HVAC DUCT IN FIELD(TYP)

CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR HVAC DUCT SYSTEM.

DEHUMIDIFIER AND DUCT FLOOR PLAN

SCALE : 1 / 50-

1 DEHUMIDIFIER AND DUCT FLOOR PLAN (BLDG# S-251 & S-252)

SPECIFIC NOTES

BLAST VALVE, FUCARE FC-RBV-11-OW-2X1, 13BAR REFLECTED 70MS, SINGLE BLOCK 600CMH@100PA.

BLAST VALVE, FUCARE FC-RBV-11-OW-1X2, 13BAR REFLECTED 70MS, SINGLE BLOCK 600CMH@100PA.

ROOF COVER DETAIL

CONC. PAD

BLOCK-UP

BLOCK-UP

S A ø

0.3

HUMIDITY SENSOR

HUMIDITY LEVEL ALARM

W/ HORN STROBE SET @

60% RH

H

COVER DETAIL

SEE ROOF

DH

100 x 100 (TYP OF 10)

SA GRILL 140CMH

( BLDG S-251 & 252)

REPAIR EARTH COVERED MAGAZINES, AHA 25

CAMP CASEY

CHONG, ST

M7

(BLDG# S-251 & S-252), NOTES, SPECIFIC

NOTES AND ROOF COVER DETAIL

190901

DUCT OPENING

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

DATE

CHIEF, ENGR'G DIV

FORCE PROTECTION

CHK'D

REVISIONS

IMCOM

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

MECHANICAL

BELL AND SPIGOT

TRAP, ELECTRIC (INDICATE TYPE)

SOLVENT CEMENT

REDUCER, ECCENTRIC (STRAIGHT, INVERT)

REDUCER, ECCENTRIC (STRAIGHT, DOWN)

FIRE DEPARTMENT CONNECTION

M E C H A N I C A L M A T E R I A L I N D I C A T I O N S & S Y M B O L S

TEE, OUTLET DOWN

ANCHOR, MAIN

BUTTERFLY

AIR LINE

valves : (for selective actuators)

GATE, ANGLE

PLUG VALVE

GATE, GLOBE

THREE WAY

CONTROL

DPT DEWPOINT TEMPERATUREAMERICAN WIRE GAUGEAWG

CENTIGRADE

CAPACITY

BRAKE HORSEPOWER

BAROMETER(-TRIC)

BOILING POINT

PRESSURE, BAROMETRIC

COOLING LOAD

COEFFICIENT

CUBIC METER PER HOUR

COUNTER CLOCKWISE

CLASSIFICATION

CAST IRON PIPE

CHILLED WATER

CIRCUIT

CUBIC METER

COMPRESSOR

CONTINUE

CONNECTIONCONN

CONT

CU M

CPRSR

CLASS

CLG LOAD

COEF

CMH

CKT

CIP

CHW

CCW

C

CAP

BP

BARO PR

BARO

BHP

FA FACE AREA OR FRESH AIR

FHC

FLA

FHY FIRE HYDRANT

FULL LOAD AMPERES

FIRE HOSE CABINET

EFF

EWT

EXPJT

EVAP

EP

EQPT

ESP

ENT

ECON

EDR

EAT

ECC

DX

DPDT

DPV

EFFICIENCY

EXPANSION JOINT

EXTERNAL STATIC PRESSURE

EVAPORAT (-E,-ING,-ED,-OR)

ENTERING WATER TEMP

EXPLOSION PROOF

ENTERING

EQUIPMENT

DRY PIPE VALVE

DOUBLE POLE DOUBLE THROW

ENTERING AIR TEMPERATURE

EQUIVALENT DIRECT RADIATION

DIRECT EXPANSION

ECONOMIZER

ECCENTRIC

air conditioning and refrigeration

AIR COOLED

ALARM CHECK VALVE

AIR CONDITION UNIT (S)

AVERAGE

APPROXIMATE

AMPERE(AMP, AMPS)

AIR HANDLING UNIT

ALTITUDE

AMBIENT

ALUMINUM

APPARATUS DEW POINT

AIR CONDITION (-ING,-ED)

AIR COOLED CONDENSING UNIT

APPROX

AVG

AMP

AMB

AIR COND

ALT

AL

AHU

ACCU

ACLD

ACU

ACV

ADP

C/HWS

C/HWR

CHS

CHR

D

RS

RL

RD

(NAME)

M

CU MM

DIAG

DO

DIV

DIFF

DB

DIA or

DBT

CW

Cv

CWP

DECIBEL OR DRY BULB

DRY BULB TEMPERATURE

DIAGRAM

DIVISION

DIESEL OIL

DIFFERENCE

DIAMETER

DEGREE

o

CUBIC MILLIMETER

COEFFICIENT, VALVE FLOW

CLOCKWISE OR COLD WATER

CIRCULATING WATER PUMP

HOT/CHILLED WATER SUPPLY

HOT CHILLED WATER RETURN

CHILLED WATER RETURN

CHILLED WATER SUPPLY

DRAIN

REFRIGERANT SUCTION

REFRIGERANT LIQUID

CONTROL AIR MAIN

PIPE TO BE REMOVED

REFRIGERANT DISCHARGE

GLOBE

GATE

A

BALL

SQ

PLUMBING

LIQUID LINELL

PLMB

LINEAR METER

LITERS PER DAY

LITERS PER HOUR

LAUNDRY TRAY

LITERS PER SECOND

LEAVING WATER TEMPERATURE

NOT APPLICABLE

NOISE CRITERIA

NORMALLY CLOSED

METERS PER SECOND

METERS PER HOUR

MINIMUM OR MINUTE

NORMALLY OPEN

NATIONAL TAPER PIPE (THREAD)

NOT IN CONTRACTNICKG KILOGRAM

KILOGRAM PER SQ. CENTIMETER (ABSOLUTE)

KILOGRAM PER SQ. CENTIMETER

KILOGRAM PER SQ. CENTIMETER (GAUGE)KG/SQ CM G

KG/SQ CM A

KG/SQ CM

NO

N.O.

NPT

NUMBER

KILOCALORIE PER HOUR

THERMAL CONDUCTIVITY

JOULE

IRON PIPE SIZE

ISOMETRIC

DIAMETER, INSIDE

KCAL/HR

K

J

ISO

ID

IPS

HEAD

HERTZ

HORIZONTAL

HORSEPOWER

HOT WATER

HOT WATER HEATER

HOUR(S)

MERCURY

HORIZ

HZ

HW

HWH

HP

HR

HD

HG

MAX MAXIMUM

NC

N/A

N.C.

MM

MPH

MPS

MIN

MILLIMETER

M

LT

LWT

LM

LPH

LPS

LPD

METERS

SUPPLY AIRSA

SANITARY

SUBMERSIBLE

SCHEDULE

SAN

SCH

SBM

UH

UR

U

QUART

QUANTITY

PERCENT

PETROLEUM, OIL AND LUBRICANTS

POINT OF CONNECTION

PARTS PER MILLION

PRESSURE REDUCING VALVE

RADIATOR

REFRIGERANT (12, 22, ETC)

REVOLUTIONS PER MINUTE

REFRIGERATION TON

THERMAL RESISTANCE

RETURN AIR

RELATIVE HUMIDITY

RT

RH

RPM

R12, R22

R

RA

RDTR

QT

QTY

PPM

PRV

POC

POL

THERM

TONS

TYP

THK

TSTAT

TD

TEMP

SYM

STOR

SUCT

STD

STL

SSU

SSF

SST

ST

FLEXIBLE CONNECTOR

EXPANSION JOINT

EXPANSION LOOP

FLOWMETER, ORIFICE

KILOGRAM PER SQ. METER (GAUGE)

KILOGRAM PER SQ. METER (ABSOLUTE)

KILOGRAM PER SQ. METER

STRAINER, BLOW OFF

PUMP (INDICATE USE)

PRESSURE GAUGE AND COCK

PRESSURE SWITCH

KILOWATT HOUR

LATENT HEAT

LEAVING AIR TEMPERATURE

FLOWMETER, VENTURI

A B B R E V I A T I O N S

FIBERGLASS REINFORCED PLASTIC

FEMALE PIPE THREAD

GRAMS

HOSE BIBB

FACE VELOCITY

FEED WATER PUMP

GAGE OR GAUGE

GALVANIZED STEEL

FIXTURE

GA

GALVS

HB

GR

FXTR

FVEL

FWP

FLUSH VALVE

FREQUENCY

FUEL OILFO

FREQ

FRP

FPT

FV

LAT

LH

LG

LBS

L

LAV

KWH

LENGTH

POUNDS

LITERS

LAVATORY

KG/SM G

KG/SM A

KG/SM

KJ

KW

KILOJOULE

KILOWATT

P

PS

FS

STRAINER

FLOW SWITCH

OFM

VFM

EJ

BALL JOINT

(2-WAY SHOWN)

OUTSIDE AIR

NOT TO SCALE

OUTSIDE AIR INTAKE LOUVER

POLE

OXYGEN

PASCAL

PRESSURE DROP OR DIFFERENCE

PHASE (ELECTRIC)

PRESSURE GAGE

OUTSIDE SCREW & YOKE

DIAMETER, OUTSIDE

PH

PG

Pa

PD

P

OXY

OS&Y

NTS

OA

OD

OAIL

SPR

SP

SPEC

SPDT

SM

SLPD

SLPS

SLPH

SEC

SF

SG

SH

SL

sprinkler

DRY-PIPE VALVE

PRE-ACTION VALVE

SIDEWALL SPRINKLER

ALARM CHECK VALVE

PENDENT SPRINKLER

UNION, SCREWED

UNION, FLANGED

TEE, SINGLE SWEEP

UPRIGHT SPRINKLER

COLD WATER

HOT WATER SUPPLY

HOT WATER RETURN

CONDENSATE DRAIN ABOVE

SANITARY DRAIN

ACID WASTE

CHEMICAL SUPPLY PIPES

FLOOR DRAIN

CONDENSATE DRAIN BELOW

FLOOR OR GRADE

FUNNEL DRAIN, OPEN

SURFACE CLEANOUT

VENT THRU ROOF

FLOOR CLEANOUT

PIPE SLEEVE

HOSE BIBB

BACKFLOW PREVENTER

PIPE SLEEVE WITH FIRE STOPPING

FLOOR SINK (200mm x 200mm)

PITCH OR PIPE, UP(U), DOWN(D)

FLOOR OR GRADE

(NAME)E

VAC

A

HWS

MTWR

HWR

MTWS

CR

CS

FOG

FOR

FOS

FOV

FOD

MU

VPD

PC

BBD

MPC

LPC

LPS

MPS

JWS

JWR

FCO

LOW TEMPERATURE HOT WATER RETURN

LOW TEMPERATURE HOT WATER SUPPLY

MEDIUM TEMPERATURE HOT WATER RETURN

MEDIUM TEMPERATURE HOT WATER SUPPLY

VACUUM (AIR)

COMPRESSED AIR

EXISTING PIPE

FUEL OIL RETURN

FUEL OIL SUPPLY

CONDENSATE WATER RETURN

CONDENSATE WATER SUPPLY

FUEL OIL GAUGE

PLAN ELEV.

BFP

200mm x 200mm

SCO

FUEL OIL TANK VENT

PUMPED CONDENSATE

BOILER BLOW DOWN

VACUUM PUMP DISCHARGE

FUEL OIL DRAIN

MAKE UP WATER

LOW PRESSURE STEAM

JACKET WATER SUPPLY

JACKET WATER RETURN

LOW PRESSURE CONDENSATE

MEDIUM PRESSURE CONDENSATE

MEDIUM PRESSURE STEAM

ACID

(NAME)

FD

CD

G GAS

CD

VENT

PIPING

heating plumbing

MOTOR ELECTRIC

CHECK, NON-SLAM

QUICK CLOSING, FUSIBLE LINK

SQUARE HEAD BALANCING COCK

PRESSURE REDUCING

SQUARE HEAD BALANCING COCK

HOSE END DRAIN

CONTROL, PNEUMATIC-ELECTRIC

CONTROL, ELECTRIC-PNEUMATIC

ALIGNMENT GUIDE

ANCHOR, INTERMEDIATE

AIR VENT, AUTOMATIC

AIR VENT, MANUAL

W/ MEASURING TAP

MV

AVV

S AIR SEPARATOR

S

R

SAFETY

QUICK OPENING

RELIEF

PE

LOCK SHIELD

NEEDLE

valves, special duty :

EP

M

S

CHECK, SWING

SOLENOID

DIAPHRAGM

LATERAL

TEE, OUTLET UP

REDUCER, CONCENTRIC

TEE

CONNECTION, TOP

ELBOW, TURNED UP

CONNECTION, BOTTOM

ELBOW, TURNED DOWN

fitting :

FLANGED

WELDED

R

SOLDERED

CAP

BUSHING

THERMOMETER

SCREWED

THERMOSTAT, ELECTRIC

valve actuators dampers

SQUARE

WATTHOUR OR WATER HEATER

HEAT TRANSFER COEFFICIENT

UNIT HEATER

URINAL

TEMPERATURE DIFFERENCE

TONS OF REFRIGERATION

THERMOMETER

THERMOSTAT

TYPICAL

THICKNESS

TEMPERATURE

SYMBOL

STAINLESS STEEL

SAYBOLT SECONDS FUROL

SAYBOLT SECONDS UNIVERSAL

STORAGE

SUCTION

STANDARD

STEEL

STEAM

WIDTH

WEIGHT

WASHER

WATERPROOF

WATER CLOSET

WATER-COOLED

W/

WT

WTRPRF

WSHR

WITH

WD

WH

WC

WCLD

FIRE DAMPER (PROVIDE ACCESS DOOR)

ELECTRIC MOTOR OPERATED DAMPER

SMOKE DAMPER (PROVIDE ACCESS DOOR)

PRESSURE, DYNAMIC(VELOCITY)

WET BULB TEMPERATURE

STATIC PRESSURE

LPD, STANDARD CONDITIONS

LPS, STANDARD CONDITIONS

LPH, STANDARD CONDITIONS

SINGLE POLE DOUBLE THROW

SPECIFICATION

SPRINKLER

SQUARE METER

SPECIFIC GRAVITY

SECOND

SAFETY FACTOR

SENSIBLE HEAT

SENSIBLE LOAD

VOLUME

VERTICAL

VISCOSITY

WET BULB

VENTILATION

WB

WBT

W

VP

WATT

VOL

VISC

VENT

VERT

VACUUM

VALVE

VARIABLE AIR VOLUME

VELOCITY

VOLTV

VAC

VLV

VAV

VEL

SD

AD

M

VD

AD FD

S

BDD

PNEUMATIC OPERATED DAMPER

SPLITTER DAMPER

BACKDRAFT DAMPER

MANUAL VOLUME DAMPER

DUCT SECTION, POSITIVE PRESS., FIRST

EXHAUST AIR GRILLE OR REGISTER, CEILING

DUCT SECTION, NEGATIVE PRESS., FIRST

ACCESS DOOR, VERTICAL OR HORIZONTAL

CHANGE OF ELEVATION, RISE(R), DOWN(D)

COWL, (GOOSENECK) AND FLASHING

F S

FC

TRANSITION

DETECTORS, FIRE AND/OR SMOKE

TURNING VANES

FLEXIBLE CONNECTION

SOUND ATTENUATOR

FLEXIBLE DUCT

AD

R

810mm x 400mm

810mm x 400mm

810mm x 400mm

FIGURE IS ON TOP

ACOUSTICAL LINING

DIRECTION OF FLOW

FIGURE IS ON TOP

(600mm x 300mmH, 472 LPS)

TG 600/300

NECK DIAMETER)

DIFFUSER, LINEAR

CEILING DIFFUSER, ROUND TYPE (200mm

CEILING DIFFUSER, SQUARE TYPE

EXISTING WORK TO BE REMOVED

200mm NCD

SUPPLY AIR GRILLE OR REGISTER, CEILING

EXHAUST AIR GRILLE OR REGISTER, CEILING

SUPPLY AIR GRILLE OR REGISTER, SIDEWALL

RETURN AIR GRILLE OR REGISTER, CEILING

TRANSFER GRILLE ASSEMBLY

LOUVER, DOOR OR WALL

UNDERCUT DOOR (13mm, 47.2 LPS)

DOOR GRILLE (300mmx150mmH)

(500mmWx300mmH, 94.4 LPS)

500/300L

47.2

UC 13mm

300x150

DG

94.4

SR

RR

RG

SG

EG

ER

SR

SG

DUCT WORK

grilles, registers and diffusers :

RLA

LRA

RATED LOAD AMPS

LOCKED ROTOR AMPS

REMOVE EXIST WORK(R)

(E) EXISTING WORK TO REMAIN.

OR END OF DEMOLITION WORK

POINT OF CONNECTION NEW TO EXISTING

SYMBOLS AND ABBREVIATIONS

MECHANICAL MATERIAL INDICATIONS &

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

DATE

CHIEF, ENGR'G DIV

FORCE PROTECTION

CHK'D

REVISIONS

IMCOM

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

FIRE & EMERGENCY SVC

SAFETY

190901

CHONG, ST

( BLDG S-253, S-254 & 255)

12. PRIOR TO INSTALLING NEW HVAC AND PLUMBING PIPING CONTRACTOR MUST

COORDINATE WITH EXISTING DUCTWORK AND PIPING ELEVATION/LOCATION.

IF EXISTING DUCT ELEVATION IS CONFLICTED WITH NEW PIPING INSTALLATION,

REMOVE EXISTING DUCTWORK AND INSTALL NEW DUCTWORK AND MAKE ALL

CONTRACTING OFFICER FOR APPROVAL.

CONTRACTOR ACCORDING TO ACTUAL FIELD CONDITIONS AND SUBMITTED TO THE

FIELD CONDITIONS. SUCH DETAILS SHALL BE PREPARED IN THE FIELD BY THE

11. SOME DETAILS SHOWN ON THIS CONTRACT DRAWINGS MAY NOT MATCH EXACT

SUCH AS ANCHORS, HANGERS/SUPPORT, ETC.

10. ALL HVAC PIPING/DUCTWORK TO BE REMOVED SHALL INCLUDE ALL IT'S ACCESSORIES

9. ANY OPENING RESULT FROM THE REMOVAL WORK THAT'S NOT TO BE RE-USED

SHALL BE PATCHED OR RESTORED TO MATCH ADJACENT SURFACE OR AREA.

PER SPEC.

THIS CONTRACTOR.

AND SHALL BE VERIFIED AT THE JOB SITE.

CORRECTIONS FOR CONTRACTING OFFICER'S APPROVAL.

7. ALL WALL/FLOOR/ROOF OPENINGS RESULTED FROM THE REMOVAL OF PIPING AND

4. ANY PIPES THAT PENETRATE FIRE RATED WALL (EXISTING/ NEW) SHALL BE SEALED

6. NO MECHANICAL WORK CAN BE STARTED WITHOUT AN APPROVED SHOP DRAWINGS.

SHOP DRAWING SHALL NOT BE THE EXACT DUPLICATION OF THE CONTRACT DRAWING.

2. LOCATION AND SIZES OF EXISTING EQUIPMENT, DUCTWORK, PIPING, ETC. APPROXIMATE

OFFICER'S REPRESENTATIVE ATTENTION WITH RECOMMENDATIONS FOR PROPER

IF ANY DISCREPANCY IS DETECTED, IT SHOULD BE BROUGHT TO THE CONTRACTING

THE EXISTING CONDITIONS, EQUIPMENT, FINISHES, ETC., PRIOR TO START OF WORK.

1. THE CONTRACTOR SHALL VISIT THE SITE AND SHALL FAMILIARIZE HIMSELF WITH

THE WORK PERFORMED UNDER THIS CONTRACT SHALL BE REPAIRED OR REPLACED BY

THE EXISTING EQUIPMENT ANY EQUIPMENT, DUCT WORK, PIPING ETC. DAMAGED DUE TO

3. CONNECT TO EXISTING SYSTEM SHALL BE DONE IN SUCH A MANNER AS NOT DAMAGE

THE REQUIREMENTS OF SEAL CLASS C.

8. ALL SUPPLY, RETURN AND EXHAUST AIR DUCTWORK SHALL BE CONSTRUCTED

ACCORDING TO SMACNA STATIC PRESSURE CALSS 500PA AND DUCTWORK SHALL MEET

DUCTWORK SHALL BE PATCHED OR RESTORED TO MATCH ADJACENT SURFACE OR AREAS.

13.

CHANGES REQUIRED TO MAKE THIS

CONTRACTOR SHALL PROVIDE NECESSARY SHOP DRAWINGS FOR ANY

REQUIREMENT FOR GAS ONLY BURNERS MAY BE JUSTIFIABLE. THE

PACKAGE, PRIOR TO THE START OF CONSTRUCTION, THEREFORE THE

PROVIDE NATURAL GAS ACCESS TO THE BUILDING UNDER THIS DESIGN

CONCURRENT NATURAL GAS CONVERSION PROJECT PACKAGES MAY

HEATING SYSTEMS WITH DPW PRIOR TO THE START OF CONSTRUCTION.

AND OIL) BURNERS FOR HEATING HOT WATER AND DOMESTIC HOT WATER

THE CONTRACTOR SHALL COORDINATE THE USAGE OF DUAL FUEL (GAS

GENERAL NOTES

14.

TO RECOGNIZED COMMERICAL STANDARDS.

INSTALL ALL EQUIPMENT AND MATERIALS IN A FIRST CLASS MANNER CONFORMING

15.

AND OPERATION OF THE EQUIPMENT.

OR CONDITIONS THAT WILL PREVENT THE PROPER INSTALLATION, MAINTENANCE

OF EQUIPMENT AND NOYIFY THE ENGINEER OF ANY INADEQUATE CLEARANCES

REVIEW ALL SPACES WHERE EQUIPMENT IS TO BE INSTALLED PRIOR TO ORDERING

WHILE MEETING THE MANUFACTURER'S RECOMMENDED ACCESS REQUIREMENTS.

ALL EQUIPMENT SHALL BE CAPABLE OF FITTING INTO THE SPACES ALLOCATED

16.

FIRESTOP ALL PENETRATIONS BETWEEN FLOORS.

WITH A UL APPROVED SYSTEM APPROPRIATE FOR THE PENETRATION TYPE AND FIRE RATING,

PROPERLY FIRESTOP ALL PENETRATIONS THROUGH FIRE RATED WALL, FLOORS, OR PARTITIONS

17.

PROVIDE REMOTELY ACTUATED DAMPERS IN AREA WITH GYPBOARD OR CONCEALED CEILINGS.

THAT THE EQUIPMENT CAN BE MAINTAINED ADEQUATELY.

FOR TWO VALVES. COORDINATE THE LOCATION OF ACCESS PANELS TO INSURE

ITEM INDISE DUCTS REQUIRING SERVICING OR INSPECTION 12"x12" ACCESS PANELS

FIRE/SMOKE DAMPERS, DUCT SMOKE DETECTOR, BACKDRAFT DAMPERS AND FOR ANY

PROVIDE ACCESS DOORS IN DUCTS AT ALL AUTOMATIC CONTROL DAMPERS, FIRE DAMPERS,

PROVIDE ACCESS PANELS TO ALL CONCEALED VALVES, DAMPERS, AND EQUIPMENT.

18.

WITH THE CURRENT CITY AND COUNTRY.

SEISMICALLY BRACE ALL EQUIPMENT, PIPING AND DUCTWORK IN ACCORDANCE

19.

OR CONCEALED CEILINGS.

DRAWINGS OR NOT. PROVIDE REMOTELY ACTUATED DAMPERS IN AREAS WITH GYPBOARD

PROVIDE VOLUME DAMPERS ON DUCTWORK BRANCH LINES WHETHER SHOWN ON THE

OR CONCEALED CEILINGS.

DRAWINGS OR NOT. PROVIDE REMOTELY ACTUATED DAMPERS IN AREAS WITH GYPBOARD

PROVIDE VOLUME DAMPERS ON DUCTWORK BRANCH LINES WHETHER SHOWN ON THE19.

20.

OR EXTERIOR DUCT INSULATION AS REQUIRED PER SPECIFICATION.

DUCT SIZES SHOWN ARE NET SIZES INSIDE DUCTWORK. MAKE ALLOWANCES FOR INTERIOR

21.

THE FIRE WALL OR FLOOR. FIRE DAMPERS SHALL BE UL LISTED.

WALLS AND FLOORS. FIRE DAMPER RATINGS SHALL BE COMPATIBLE WITH

PROVIDE FIRE DAMPERS AT ALL DUCT PENETRATIONS THROUGH FIRE RATED

22.

TAKE-OFFS FROM SQUARE OR RECTANGULAR MAINS.

TAKE-OFFS FROM THE MAIN DUCT. PROVIDE SPIN-IN TYPE FITTINGS AT ALL ROUND DUCT

30 DEGREES OR USE RADIUS ELBOWS. PROVIDE AIR SPLITTER DAMPERS AT ALL BRANCH

PROVIDE TURNING VANES IN ALL ELBOWS THAT CHANGE AIR DIRECTION MORE THAN

23. PROVIDE VENTS AT ALL HIGH POINTS AND DRAINS AT ALL LOW POINTS OF WATER PIPING.

24.

AND FLOORS.

PROVIDE SLEEVES AND ESCUTCHEONS AT PIPE PENETRATIONS THROUGH CONCRETED WALL

25.

BODIES EXPOSED TO AIR BELOW THE FLOOR.

OR ANY OTHER COLD LIQUID WHICH MAY CREATE CONDENSATION, FROM SINK

INSULATE ALL SEWER PIPING RECEIVING AIR CONDITIONING CONDENSATE DRAINS,

INSTALL CONDENSATE DRAINS AT A MINIMUM SLOPE OF 1 / 4 INCH PER 1 FOOT.

26.

OTHERWISE INDICATED.

MOUNT ALL ROOM THERMOSTATS AT 4'-0" ABOVE FINISHED FLOOR UNLESS

27.

TO SUPPORT THE CONTROL REQUIREMENTS.

PROVIDE STEP DOWN TRANSFORMERS, AUXILARY RELAYS AND WIRING AS NECESSARY

AS SHOWN

M-2

MECHANICAL

SCOPE OF WORK

WORK CLASS "K" (REPAIR / MAINTENANCE WORK)

GENERAL NOTES AND SCOPE OF WORK

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

DATE

CHIEF, ENGR'G DIV

FORCE PROTECTION

CHK'D

REVISIONS

IMCOM

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

FIRE & EMERGENCY SVC

SAFETY

1.

2.

3.

AS INDICATED ON THE DRAWING.

REPLACE EXISTING DETERIORATED PACKAGED DEHUMIDIFIER(3SETS), ANGLE IRON SUPPORT ASSOCIATED DUCTWORK, BLDG# S-253, S-254 AND S-255

BLDG# S-253, S-254 AND S-255, CP CASEY WITH NEW.

REPLACE EXISTING DETERIORATED BLAST VALVES, BLDG# S-253, S-254 AND S-255, CP CASEY AS INDICATED ON THE DRAWING.

REPLACE EXISTING DETERIORATED HUMIDITY SENSOR AND HUMIDITY LEVEL ALARM, BLDG# S-253, S-254 AND S-255, CP CASEY

CHONG, ST

190901

( BLDG S-253, S-254 & 255)

DESICCANT DEHUMIDIFIER

TYPE

KG/H

CAPACITY

ITEM NO. QTY. SERVICE

PROCESS&REACTIVATION FAN

REMARK

3.1 Bldg# S-253, PACKAGED DEHUMIDIFIER-1

DEHUMI-

LPS

117/43

DESICCANT WHEEL

HPS

TYPE

SIZE

(mm)

445x200t

KW

MOTOR

0.38

(PROCESS/

REACTIVATION)

REACTIVATION HEATER

ELEC.

TYPE

KW

CAPACITY

4.2

ELECTRIC SOURCE

V/PH/HZ

480/3/60

KW

TOTAL

POWER

4.6

(PROCESS)DIFICATION E.S.P.

(Pa)

DH

CE MARK, BACTERIOSTATIC ROTOR, SIEMENS CLIMATIX PLC CONTROL SYSTEM.3 S-254 & S-255

REFER TO "MUNTERS, MODEL : ML420 CLIMATIX OR APPROVED EQUAL"

CAMP CASEY

CHONG, ST

( BLDG S-253, S-254 & 255)

REPAIR EARTH COVERED MAGAZINES, AHA 25

M E C H A N I C A L E Q U I P M E N T S C H E D U L E - 3

MECHANICAL EQIPMENT SCHEDULE - 3

190901

A

B C D

E F G HA

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

DATE

CHIEF, ENGR'G DIV

FORCE PROTECTION

CHK'D

REVISIONS

IMCOM

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

MECHANICAL

1.

NOTES:

CONTRACTOR SHALL VERIFY EXACT LOCATION, SIZE AND DIRECTION

2.

OF HVAC DUCT IN FIELD(TYP)

CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR HVAC DUCT SYSTEM.

DEHUMIDIFIER AND DUCT FLOOR PLAN

SCALE : 1 / 50-

DH

0.3

S A ø

H

HUMIDITY SENSOR

HUMIDITY LEVEL ALARM

W/ HORN STROBE SET @

60% RH

100 x 100 (TYP OF 5)

SA GRILL 140CMH

SPECIFIC NOTES

BLAST VALVE, FUCARE FC-RBV-11-OW-2X1, 13BAR REFLECTED 70MS, SINGLE BLOCK 600CMH@100PA.

BLAST VALVE, FUCARE FC-RBV-11-OW-1X2, 13BAR REFLECTED 70MS, SINGLE BLOCK 600CMH@100PA.

BLOCK-UP

BLOCK-UP

ROOF COVER DETAIL

CONC. PAD

SEE ROOF

COVER DETAIL

DEHUMIDIFIER AND DUCT FLOOR PLAN (BLDG# S-253, S-254 & S-255)

CAMP CASEY

CHONG, ST

M9

( BLDG S-253, S-254 & 255)

REPAIR EARTH COVERED MAGAZINES, AHA 25

(BLDG# S-253, S-254 & S-255), NOTES,

SPECIFIC NOTES AND ROOF COVER DETAIL

190901

DUCT OPENING

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

DATE

CHIEF, ENGR'G DIV

FORCE PROTECTION

CHK'D

REVISIONS

IMCOM

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

MECHANICAL

BELL AND SPIGOT

TRAP, ELECTRIC (INDICATE TYPE)

SOLVENT CEMENT

REDUCER, ECCENTRIC (STRAIGHT, INVERT)

REDUCER, ECCENTRIC (STRAIGHT, DOWN)

FIRE DEPARTMENT CONNECTION

M E C H A N I C A L M A T E R I A L I N D I C A T I O N S & S Y M B O L S

TEE, OUTLET DOWN

ANCHOR, MAIN

BUTTERFLY

AIR LINE

valves : (for selective actuators)

GATE, ANGLE

PLUG VALVE

GATE, GLOBE

THREE WAY

CONTROL

DPT DEWPOINT TEMPERATUREAMERICAN WIRE GAUGEAWG

CENTIGRADE

CAPACITY

BRAKE HORSEPOWER

BAROMETER(-TRIC)

BOILING POINT

PRESSURE, BAROMETRIC

COOLING LOAD

COEFFICIENT

CUBIC METER PER HOUR

COUNTER CLOCKWISE

CLASSIFICATION

CAST IRON PIPE

CHILLED WATER

CIRCUIT

CUBIC METER

COMPRESSOR

CONTINUE

CONNECTIONCONN

CONT

CU M

CPRSR

CLASS

CLG LOAD

COEF

CMH

CKT

CIP

CHW

CCW

C

CAP

BP

BARO PR

BARO

BHP

FA FACE AREA OR FRESH AIR

FHC

FLA

FHY FIRE HYDRANT

FULL LOAD AMPERES

FIRE HOSE CABINET

EFF

EWT

EXPJT

EVAP

EP

EQPT

ESP

ENT

ECON

EDR

EAT

ECC

DX

DPDT

DPV

EFFICIENCY

EXPANSION JOINT

EXTERNAL STATIC PRESSURE

EVAPORAT (-E,-ING,-ED,-OR)

ENTERING WATER TEMP

EXPLOSION PROOF

ENTERING

EQUIPMENT

DRY PIPE VALVE

DOUBLE POLE DOUBLE THROW

ENTERING AIR TEMPERATURE

EQUIVALENT DIRECT RADIATION

DIRECT EXPANSION

ECONOMIZER

ECCENTRIC

air conditioning and refrigeration

AIR COOLED

ALARM CHECK VALVE

AIR CONDITION UNIT (S)

AVERAGE

APPROXIMATE

AMPERE(AMP, AMPS)

AIR HANDLING UNIT

ALTITUDE

AMBIENT

ALUMINUM

APPARATUS DEW POINT

AIR CONDITION (-ING,-ED)

AIR COOLED CONDENSING UNIT

APPROX

AVG

AMP

AMB

AIR COND

ALT

AL

AHU

ACCU

ACLD

ACU

ACV

ADP

C/HWS

C/HWR

CHS

CHR

D

RS

RL

RD

(NAME)

M

CU MM

DIAG

DO

DIV

DIFF

DB

DIA or

DBT

CW

Cv

CWP

DECIBEL OR DRY BULB

DRY BULB TEMPERATURE

DIAGRAM

DIVISION

DIESEL OIL

DIFFERENCE

DIAMETER

DEGREE

o

CUBIC MILLIMETER

COEFFICIENT, VALVE FLOW

CLOCKWISE OR COLD WATER

CIRCULATING WATER PUMP

HOT/CHILLED WATER SUPPLY

HOT CHILLED WATER RETURN

CHILLED WATER RETURN

CHILLED WATER SUPPLY

DRAIN

REFRIGERANT SUCTION

REFRIGERANT LIQUID

CONTROL AIR MAIN

PIPE TO BE REMOVED

REFRIGERANT DISCHARGE

GLOBE

GATE

A

BALL

SQ

PLUMBING

LIQUID LINELL

PLMB

LINEAR METER

LITERS PER DAY

LITERS PER HOUR

LAUNDRY TRAY

LITERS PER SECOND

LEAVING WATER TEMPERATURE

NOT APPLICABLE

NOISE CRITERIA

NORMALLY CLOSED

METERS PER SECOND

METERS PER HOUR

MINIMUM OR MINUTE

NORMALLY OPEN

NATIONAL TAPER PIPE (THREAD)

NOT IN CONTRACTNICKG KILOGRAM

KILOGRAM PER SQ. CENTIMETER (ABSOLUTE)

KILOGRAM PER SQ. CENTIMETER

KILOGRAM PER SQ. CENTIMETER (GAUGE)KG/SQ CM G

KG/SQ CM A

KG/SQ CM

NO

N.O.

NPT

NUMBER

KILOCALORIE PER HOUR

THERMAL CONDUCTIVITY

JOULE

IRON PIPE SIZE

ISOMETRIC

DIAMETER, INSIDE

KCAL/HR

K

J

ISO

ID

IPS

HEAD

HERTZ

HORIZONTAL

HORSEPOWER

HOT WATER

HOT WATER HEATER

HOUR(S)

MERCURY

HORIZ

HZ

HW

HWH

HP

HR

HD

HG

MAX MAXIMUM

NC

N/A

N.C.

MM

MPH

MPS

MIN

MILLIMETER

M

LT

LWT

LM

LPH

LPS

LPD

METERS

SUPPLY AIRSA

SANITARY

SUBMERSIBLE

SCHEDULE

SAN

SCH

SBM

UH

UR

U

QUART

QUANTITY

PERCENT

PETROLEUM, OIL AND LUBRICANTS

POINT OF CONNECTION

PARTS PER MILLION

PRESSURE REDUCING VALVE

RADIATOR

REFRIGERANT (12, 22, ETC)

REVOLUTIONS PER MINUTE

REFRIGERATION TON

THERMAL RESISTANCE

RETURN AIR

RELATIVE HUMIDITY

RT

RH

RPM

R12, R22

R

RA

RDTR

QT

QTY

PPM

PRV

POC

POL

THERM

TONS

TYP

THK

TSTAT

TD

TEMP

SYM

STOR

SUCT

STD

STL

SSU

SSF

SST

ST

FLEXIBLE CONNECTOR

EXPANSION JOINT

EXPANSION LOOP

FLOWMETER, ORIFICE

KILOGRAM PER SQ. METER (GAUGE)

KILOGRAM PER SQ. METER (ABSOLUTE)

KILOGRAM PER SQ. METER

STRAINER, BLOW OFF

PUMP (INDICATE USE)

PRESSURE GAUGE AND COCK

PRESSURE SWITCH

KILOWATT HOUR

LATENT HEAT

LEAVING AIR TEMPERATURE

FLOWMETER, VENTURI

A B B R E V I A T I O N S

FIBERGLASS REINFORCED PLASTIC

FEMALE PIPE THREAD

GRAMS

HOSE BIBB

FACE VELOCITY

FEED WATER PUMP

GAGE OR GAUGE

GALVANIZED STEEL

FIXTURE

GA

GALVS

HB

GR

FXTR

FVEL

FWP

FLUSH VALVE

FREQUENCY

FUEL OILFO

FREQ

FRP

FPT

FV

LAT

LH

LG

LBS

L

LAV

KWH

LENGTH

POUNDS

LITERS

LAVATORY

KG/SM G

KG/SM A

KG/SM

KJ

KW

KILOJOULE

KILOWATT

P

PS

FS

STRAINER

FLOW SWITCH

OFM

VFM

EJ

BALL JOINT

(2-WAY SHOWN)

OUTSIDE AIR

NOT TO SCALE

OUTSIDE AIR INTAKE LOUVER

POLE

OXYGEN

PASCAL

PRESSURE DROP OR DIFFERENCE

PHASE (ELECTRIC)

PRESSURE GAGE

OUTSIDE SCREW & YOKE

DIAMETER, OUTSIDE

PH

PG

Pa

PD

P

OXY

OS&Y

NTS

OA

OD

OAIL

SPR

SP

SPEC

SPDT

SM

SLPD

SLPS

SLPH

SEC

SF

SG

SH

SL

sprinkler

DRY-PIPE VALVE

PRE-ACTION VALVE

SIDEWALL SPRINKLER

ALARM CHECK VALVE

PENDENT SPRINKLER

UNION, SCREWED

UNION, FLANGED

TEE, SINGLE SWEEP

UPRIGHT SPRINKLER

COLD WATER

HOT WATER SUPPLY

HOT WATER RETURN

CONDENSATE DRAIN ABOVE

SANITARY DRAIN

ACID WASTE

CHEMICAL SUPPLY PIPES

FLOOR DRAIN

CONDENSATE DRAIN BELOW

FLOOR OR GRADE

FUNNEL DRAIN, OPEN

SURFACE CLEANOUT

VENT THRU ROOF

FLOOR CLEANOUT

PIPE SLEEVE

HOSE BIBB

BACKFLOW PREVENTER

PIPE SLEEVE WITH FIRE STOPPING

FLOOR SINK (200mm x 200mm)

PITCH OR PIPE, UP(U), DOWN(D)

FLOOR OR GRADE

(NAME)E

VAC

A

HWS

MTWR

HWR

MTWS

CR

CS

FOG

FOR

FOS

FOV

FOD

MU

VPD

PC

BBD

MPC

LPC

LPS

MPS

JWS

JWR

FCO

LOW TEMPERATURE HOT WATER RETURN

LOW TEMPERATURE HOT WATER SUPPLY

MEDIUM TEMPERATURE HOT WATER RETURN

MEDIUM TEMPERATURE HOT WATER SUPPLY

VACUUM (AIR)

COMPRESSED AIR

EXISTING PIPE

FUEL OIL RETURN

FUEL OIL SUPPLY

CONDENSATE WATER RETURN

CONDENSATE WATER SUPPLY

FUEL OIL GAUGE

PLAN ELEV.

BFP

200mm x 200mm

SCO

FUEL OIL TANK VENT

PUMPED CONDENSATE

BOILER BLOW DOWN

VACUUM PUMP DISCHARGE

FUEL OIL DRAIN

MAKE UP WATER

LOW PRESSURE STEAM

JACKET WATER SUPPLY

JACKET WATER RETURN

LOW PRESSURE CONDENSATE

MEDIUM PRESSURE CONDENSATE

MEDIUM PRESSURE STEAM

ACID

(NAME)

FD

CD

G GAS

CD

VENT

PIPING

heating plumbing

MOTOR ELECTRIC

CHECK, NON-SLAM

QUICK CLOSING, FUSIBLE LINK

SQUARE HEAD BALANCING COCK

PRESSURE REDUCING

SQUARE HEAD BALANCING COCK

HOSE END DRAIN

CONTROL, PNEUMATIC-ELECTRIC

CONTROL, ELECTRIC-PNEUMATIC

ALIGNMENT GUIDE

ANCHOR, INTERMEDIATE

AIR VENT, AUTOMATIC

AIR VENT, MANUAL

W/ MEASURING TAP

MV

AVV

S AIR SEPARATOR

S

R

SAFETY

QUICK OPENING

RELIEF

PE

LOCK SHIELD

NEEDLE

valves, special duty :

EP

M

S

CHECK, SWING

SOLENOID

DIAPHRAGM

LATERAL

TEE, OUTLET UP

REDUCER, CONCENTRIC

TEE

CONNECTION, TOP

ELBOW, TURNED UP

CONNECTION, BOTTOM

ELBOW, TURNED DOWN

fitting :

FLANGED

WELDED

R

SOLDERED

CAP

BUSHING

THERMOMETER

SCREWED

THERMOSTAT, ELECTRIC

valve actuators dampers

SQUARE

WATTHOUR OR WATER HEATER

HEAT TRANSFER COEFFICIENT

UNIT HEATER

URINAL

TEMPERATURE DIFFERENCE

TONS OF REFRIGERATION

THERMOMETER

THERMOSTAT

TYPICAL

THICKNESS

TEMPERATURE

SYMBOL

STAINLESS STEEL

SAYBOLT SECONDS FUROL

SAYBOLT SECONDS UNIVERSAL

STORAGE

SUCTION

STANDARD

STEEL

STEAM

WIDTH

WEIGHT

WASHER

WATERPROOF

WATER CLOSET

WATER-COOLED

W/

WT

WTRPRF

WSHR

WITH

WD

WH

WC

WCLD

FIRE DAMPER (PROVIDE ACCESS DOOR)

ELECTRIC MOTOR OPERATED DAMPER

SMOKE DAMPER (PROVIDE ACCESS DOOR)

PRESSURE, DYNAMIC(VELOCITY)

WET BULB TEMPERATURE

STATIC PRESSURE

LPD, STANDARD CONDITIONS

LPS, STANDARD CONDITIONS

LPH, STANDARD CONDITIONS

SINGLE POLE DOUBLE THROW

SPECIFICATION

SPRINKLER

SQUARE METER

SPECIFIC GRAVITY

SECOND

SAFETY FACTOR

SENSIBLE HEAT

SENSIBLE LOAD

VOLUME

VERTICAL

VISCOSITY

WET BULB

VENTILATION

WB

WBT

W

VP

WATT

VOL

VISC

VENT

VERT

VACUUM

VALVE

VARIABLE AIR VOLUME

VELOCITY

VOLTV

VAC

VLV

VAV

VEL

SD

AD

M

VD

AD FD

S

BDD

PNEUMATIC OPERATED DAMPER

SPLITTER DAMPER

BACKDRAFT DAMPER

MANUAL VOLUME DAMPER

DUCT SECTION, POSITIVE PRESS., FIRST

EXHAUST AIR GRILLE OR REGISTER, CEILING

DUCT SECTION, NEGATIVE PRESS., FIRST

ACCESS DOOR, VERTICAL OR HORIZONTAL

CHANGE OF ELEVATION, RISE(R), DOWN(D)

COWL, (GOOSENECK) AND FLASHING

F S

FC

TRANSITION

DETECTORS, FIRE AND/OR SMOKE

TURNING VANES

FLEXIBLE CONNECTION

SOUND ATTENUATOR

FLEXIBLE DUCT

AD

R

810mm x 400mm

810mm x 400mm

810mm x 400mm

FIGURE IS ON TOP

ACOUSTICAL LINING

DIRECTION OF FLOW

FIGURE IS ON TOP

(600mm x 300mmH, 472 LPS)

TG 600/300

NECK DIAMETER)

DIFFUSER, LINEAR

CEILING DIFFUSER, ROUND TYPE (200mm

CEILING DIFFUSER, SQUARE TYPE

EXISTING WORK TO BE REMOVED

200mm NCD

SUPPLY AIR GRILLE OR REGISTER, CEILING

EXHAUST AIR GRILLE OR REGISTER, CEILING

SUPPLY AIR GRILLE OR REGISTER, SIDEWALL

RETURN AIR GRILLE OR REGISTER, CEILING

TRANSFER GRILLE ASSEMBLY

LOUVER, DOOR OR WALL

UNDERCUT DOOR (13mm, 47.2 LPS)

DOOR GRILLE (300mmx150mmH)

(500mmWx300mmH, 94.4 LPS)

500/300L

47.2

UC 13mm

300x150

DG

94.4

SR

RR

RG

SG

EG

ER

SR

SG

DUCT WORK

grilles, registers and diffusers :

RLA

LRA

RATED LOAD AMPS

LOCKED ROTOR AMPS

REMOVE EXIST WORK(R)

(E) EXISTING WORK TO REMAIN.

OR END OF DEMOLITION WORK

POINT OF CONNECTION NEW TO EXISTING

SYMBOLS AND ABBREVIATIONS

MECHANICAL MATERIAL INDICATIONS &

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

DATE

CHIEF, ENGR'G DIV

FORCE PROTECTION

CHK'D

REVISIONS

IMCOM

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

FIRE & EMERGENCY SVC

SAFETY

190901

CHONG, ST

( BLDG S-256 & 257)

12. PRIOR TO INSTALLING NEW HVAC AND PLUMBING PIPING CONTRACTOR MUST

COORDINATE WITH EXISTING DUCTWORK AND PIPING ELEVATION/LOCATION.

IF EXISTING DUCT ELEVATION IS CONFLICTED WITH NEW PIPING INSTALLATION,

REMOVE EXISTING DUCTWORK AND INSTALL NEW DUCTWORK AND MAKE ALL

CONTRACTING OFFICER FOR APPROVAL.

CONTRACTOR ACCORDING TO ACTUAL FIELD CONDITIONS AND SUBMITTED TO THE

FIELD CONDITIONS. SUCH DETAILS SHALL BE PREPARED IN THE FIELD BY THE

11. SOME DETAILS SHOWN ON THIS CONTRACT DRAWINGS MAY NOT MATCH EXACT

SUCH AS ANCHORS, HANGERS/SUPPORT, ETC.

10. ALL HVAC PIPING/DUCTWORK TO BE REMOVED SHALL INCLUDE ALL IT'S ACCESSORIES

9. ANY OPENING RESULT FROM THE REMOVAL WORK THAT'S NOT TO BE RE-USED

SHALL BE PATCHED OR RESTORED TO MATCH ADJACENT SURFACE OR AREA.

PER SPEC.

THIS CONTRACTOR.

AND SHALL BE VERIFIED AT THE JOB SITE.

CORRECTIONS FOR CONTRACTING OFFICER'S APPROVAL.

7. ALL WALL/FLOOR/ROOF OPENINGS RESULTED FROM THE REMOVAL OF PIPING AND

4. ANY PIPES THAT PENETRATE FIRE RATED WALL (EXISTING/ NEW) SHALL BE SEALED

6. NO MECHANICAL WORK CAN BE STARTED WITHOUT AN APPROVED SHOP DRAWINGS.

SHOP DRAWING SHALL NOT BE THE EXACT DUPLICATION OF THE CONTRACT DRAWING.

2. LOCATION AND SIZES OF EXISTING EQUIPMENT, DUCTWORK, PIPING, ETC. APPROXIMATE

OFFICER'S REPRESENTATIVE ATTENTION WITH RECOMMENDATIONS FOR PROPER

IF ANY DISCREPANCY IS DETECTED, IT SHOULD BE BROUGHT TO THE CONTRACTING

THE EXISTING CONDITIONS, EQUIPMENT, FINISHES, ETC., PRIOR TO START OF WORK.

1. THE CONTRACTOR SHALL VISIT THE SITE AND SHALL FAMILIARIZE HIMSELF WITH

THE WORK PERFORMED UNDER THIS CONTRACT SHALL BE REPAIRED OR REPLACED BY

THE EXISTING EQUIPMENT ANY EQUIPMENT, DUCT WORK, PIPING ETC. DAMAGED DUE TO

3. CONNECT TO EXISTING SYSTEM SHALL BE DONE IN SUCH A MANNER AS NOT DAMAGE

THE REQUIREMENTS OF SEAL CLASS C.

8. ALL SUPPLY, RETURN AND EXHAUST AIR DUCTWORK SHALL BE CONSTRUCTED

ACCORDING TO SMACNA STATIC PRESSURE CALSS 500PA AND DUCTWORK SHALL MEET

DUCTWORK SHALL BE PATCHED OR RESTORED TO MATCH ADJACENT SURFACE OR AREAS.

13.

CHANGES REQUIRED TO MAKE THIS

CONTRACTOR SHALL PROVIDE NECESSARY SHOP DRAWINGS FOR ANY

REQUIREMENT FOR GAS ONLY BURNERS MAY BE JUSTIFIABLE. THE

PACKAGE, PRIOR TO THE START OF CONSTRUCTION, THEREFORE THE

PROVIDE NATURAL GAS ACCESS TO THE BUILDING UNDER THIS DESIGN

CONCURRENT NATURAL GAS CONVERSION PROJECT PACKAGES MAY

HEATING SYSTEMS WITH DPW PRIOR TO THE START OF CONSTRUCTION.

AND OIL) BURNERS FOR HEATING HOT WATER AND DOMESTIC HOT WATER

THE CONTRACTOR SHALL COORDINATE THE USAGE OF DUAL FUEL (GAS

GENERAL NOTES

14.

TO RECOGNIZED COMMERICAL STANDARDS.

INSTALL ALL EQUIPMENT AND MATERIALS IN A FIRST CLASS MANNER CONFORMING

15.

AND OPERATION OF THE EQUIPMENT.

OR CONDITIONS THAT WILL PREVENT THE PROPER INSTALLATION, MAINTENANCE

OF EQUIPMENT AND NOYIFY THE ENGINEER OF ANY INADEQUATE CLEARANCES

REVIEW ALL SPACES WHERE EQUIPMENT IS TO BE INSTALLED PRIOR TO ORDERING

WHILE MEETING THE MANUFACTURER'S RECOMMENDED ACCESS REQUIREMENTS.

ALL EQUIPMENT SHALL BE CAPABLE OF FITTING INTO THE SPACES ALLOCATED

16.

FIRESTOP ALL PENETRATIONS BETWEEN FLOORS.

WITH A UL APPROVED SYSTEM APPROPRIATE FOR THE PENETRATION TYPE AND FIRE RATING,

PROPERLY FIRESTOP ALL PENETRATIONS THROUGH FIRE RATED WALL, FLOORS, OR PARTITIONS

17.

PROVIDE REMOTELY ACTUATED DAMPERS IN AREA WITH GYPBOARD OR CONCEALED CEILINGS.

THAT THE EQUIPMENT CAN BE MAINTAINED ADEQUATELY.

FOR TWO VALVES. COORDINATE THE LOCATION OF ACCESS PANELS TO INSURE

ITEM INDISE DUCTS REQUIRING SERVICING OR INSPECTION 12"x12" ACCESS PANELS

FIRE/SMOKE DAMPERS, DUCT SMOKE DETECTOR, BACKDRAFT DAMPERS AND FOR ANY

PROVIDE ACCESS DOORS IN DUCTS AT ALL AUTOMATIC CONTROL DAMPERS, FIRE DAMPERS,

PROVIDE ACCESS PANELS TO ALL CONCEALED VALVES, DAMPERS, AND EQUIPMENT.

18.

WITH THE CURRENT CITY AND COUNTRY.

SEISMICALLY BRACE ALL EQUIPMENT, PIPING AND DUCTWORK IN ACCORDANCE

19.

OR CONCEALED CEILINGS.

DRAWINGS OR NOT. PROVIDE REMOTELY ACTUATED DAMPERS IN AREAS WITH GYPBOARD

PROVIDE VOLUME DAMPERS ON DUCTWORK BRANCH LINES WHETHER SHOWN ON THE

OR CONCEALED CEILINGS.

DRAWINGS OR NOT. PROVIDE REMOTELY ACTUATED DAMPERS IN AREAS WITH GYPBOARD

PROVIDE VOLUME DAMPERS ON DUCTWORK BRANCH LINES WHETHER SHOWN ON THE19.

20.

OR EXTERIOR DUCT INSULATION AS REQUIRED PER SPECIFICATION.

DUCT SIZES SHOWN ARE NET SIZES INSIDE DUCTWORK. MAKE ALLOWANCES FOR INTERIOR

21.

THE FIRE WALL OR FLOOR. FIRE DAMPERS SHALL BE UL LISTED.

WALLS AND FLOORS. FIRE DAMPER RATINGS SHALL BE COMPATIBLE WITH

PROVIDE FIRE DAMPERS AT ALL DUCT PENETRATIONS THROUGH FIRE RATED

22.

TAKE-OFFS FROM SQUARE OR RECTANGULAR MAINS.

TAKE-OFFS FROM THE MAIN DUCT. PROVIDE SPIN-IN TYPE FITTINGS AT ALL ROUND DUCT

30 DEGREES OR USE RADIUS ELBOWS. PROVIDE AIR SPLITTER DAMPERS AT ALL BRANCH

PROVIDE TURNING VANES IN ALL ELBOWS THAT CHANGE AIR DIRECTION MORE THAN

23. PROVIDE VENTS AT ALL HIGH POINTS AND DRAINS AT ALL LOW POINTS OF WATER PIPING.

24.

AND FLOORS.

PROVIDE SLEEVES AND ESCUTCHEONS AT PIPE PENETRATIONS THROUGH CONCRETED WALL

25.

BODIES EXPOSED TO AIR BELOW THE FLOOR.

OR ANY OTHER COLD LIQUID WHICH MAY CREATE CONDENSATION, FROM SINK

INSULATE ALL SEWER PIPING RECEIVING AIR CONDITIONING CONDENSATE DRAINS,

INSTALL CONDENSATE DRAINS AT A MINIMUM SLOPE OF 1 / 4 INCH PER 1 FOOT.

26.

OTHERWISE INDICATED.

MOUNT ALL ROOM THERMOSTATS AT 4'-0" ABOVE FINISHED FLOOR UNLESS

27.

TO SUPPORT THE CONTROL REQUIREMENTS.

PROVIDE STEP DOWN TRANSFORMERS, AUXILARY RELAYS AND WIRING AS NECESSARY

AS SHOWN

M-2

MECHANICAL

SCOPE OF WORK

WORK CLASS "K" (REPAIR / MAINTENANCE WORK)

1.

2.

GENERAL NOTES AND SCOPE OF WORK

BLDG# S-256 AND S-257, CP CASEY WITH NEW.

3.

AS INDICATED ON THE DRAWING.

REPLACE EXISTING DETERIORATED BLAST VALVES, BLDG# S-256 AND S-257, CP CASEY AS INDICATED ON THE DRAWING.

REPLACE EXISTING DETERIORATED PACKAGED DEHUMIDIFIER(2SETS), CONC PADS ASSOCIATED DUCTWORK, A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

DATE

CHIEF, ENGR'G DIV

FORCE PROTECTION

CHK'D

REVISIONS

IMCOM

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

FIRE & EMERGENCY SVC

SAFETY

4. REPLACE EXISTING DETERIORATED FABRIC DUCTS WITH ACCESSORIES, BLDG# S-256 AND S-257 AS INDICATED ON THE DRAWING.

REPLACE EXISTING DETERIORATED HUMIDITY SENSOR AND HUMIDITY LEVEL ALARM, BLDG# S-256 AND S-257

BLDG# S-256 AND S-257

CHONG, ST

190901

( BLDG S-256 & 257)

TYPE

CAPACITY

ITEM NO. QTY. SERVICE

SUPPLY FAN

RPMLPS

KW

E.S.P.

(Pa)

MOTOR

REACTIVATION FAN

REMARK

41.9 1,389 300 3.71,330Bldg# S-256

& S-257

PACKAGED DEHUMIDIFIER-2

CONDENSER FAN

REFRIGERANT

R410APROPELLER FAN

TYPE

KW

MOTOR

1.5

KW

MOTOR

0.75

ELECTRIC SOURCE

V/PH/HZ

460/3/60

COMPRESSOR

TON

CAPACITY

STAGE

12 4

FOR CIRCUIT

REFRIGERANT CHARGE

2.7/3.9/3.9/3.9

LPS

1,416

DESICCANT WHEEL

TiGEL

TYPE

SIZE

(mm)

1,000x100t

KW

TOTAL

POWER

DEHUMI-

DIFICATION

KG/H

DX AIR COOLED

PACKAGED CONDENSING

OUTDOOR

DH

ETL LISTED, CAREL PLC CONTROL SYSTEM

A

B C D

E F G HA

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

DATE

CHIEF, ENGR'G DIV

FORCE PROTECTION

CHK'D

REVISIONS

IMCOM

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

FIRE & EMERGENCY SVC

SAFETY

REQUIREMENT

1. CONTRACTOR SHALL USE AIR FRIGHT TO DELIVERY OFF-MATERIALS FOR THE FAST TRACT SCHEDULING.

REFER TO "MUNTERS, MODEL : DRYCOOL3412 OR APPROVED EQUAL"

( BLDG S-256 & 257)

REPAIR EARTH COVERED MAGAZINES, AHA 25

CAMP CASEY

CHONG, ST

M E C H A N I C A L E Q U I P M E N T S C H E D U L E - 1

MECHANICAL EQIPMENT SCHEDULE - 1

190901

MECHANICAL

1.

NOTES:

CONTRACTOR SHALL VERIFY EXACT LOCATION, SIZE AND DIRECTION

2.

OF HVAC DUCT IN FIELD(TYP)

CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR HVAC DUCT SYSTEM.

SCALE : 1 / 100-

SPECIFIC NOTES

4 REMOVE EXISTING DETERIORATED VENTILATOR(3SETS) AND BLOCK-UP(3SETS)

(BLDG# S-256 & S-257), NOTES AND

SPECIFIC NOTES

BLAST VALVE, FUCARE FC-RBV-11-OW-2X2, 13BAR REFLECTED 70MS, SINGLE BLOCK 620CMH@100PA.

BLAST VALVE, FUCARE FC-RBV-11-OW-2X3, 13BAR REFLECTED 70MS, SINGLE BLOCK 600CMH@100PA.

BLAST VALVE, FUCARE FC-RBV-11-OW-2X2, 13BAR REFLECTED 70MS, SINGLE BLOCK 620CMH@100PA.

DEHUMIDIFIER AND DUCT FLOOR PLAN - 1 (BLSG# S-256 & S-257)

DEHUMIDIFIER AND DUCT FLOOR PLAN-1

BLOCK UP (TYP OF 2)

DH

CONC. PAD

H

HUMIDITY SENSOR

RA 400 x 400

ACESS PANEL

DUCTS.A.

750x200 (30x8)

EQUALL

Q-SOX OR APPROVED

FABRIC DUCT

550 (22IN) SEMICIRCLE

APPROVED EQUAL

BY FABRIC DUCT Q-SOX OR

SEMI-ROUND ADAPTER

ROUND…