GENERAL NOTES SCOPE OF WORK
E-1
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
ELECTRICAL
A. REPAIR/MAINTENANCE ( K )
2.
SCOPE OF WORK
LEGEND, GENERAL NOTES AND
SINGLE POLE TOGGLE SWITCH, 15A-125V
L E G E N D
FLEXIBLE CONDUIT W/CONNECTORS
LIGHTING
WIRING
POWER
INTERIOR
S
SYMBOL DESCRIPTION
DESCRIPTION
DESCRIPTION
J JUNCTION BOX
SYMBOL
SYMBOL
AND GOVERNMENT INSTALLED
GOVERNMENT FURNISHED
GFGI
WEATHERPROOFWP
LA LIGHTNING ARRESTER
EXPLOSIONPROOFEP
DISTRIBUTIONDIST
GROUND FAULT PROTECTIONGFP
A AMPERE
AC ALTERNATING CURRENT
AF/AT AMPERE FRAME/AMPERE TRIP
AWG AMERICAN WIRE GAUGE
BC BARE COPPER
BLDG BUILDING
BRKR BREAKER
C CONDUIT
CB CIRCUIT BREAKER
CKT CIRCUIT
CONN CONNECTION
CT CURRENT TRANSFORMER
DET(S) DETAIL(S)
DIAG DIAGRAM
DISC DISCONNECT
DWG(S) DRAWING(S)
EA EACH
EM EMERGENCY
ENCL ENCLOSURE
EXST EXISTING
F/A FIRE ALARM
FL FLOOR
FLUOR FLUORESCENT
FXTR FIXTURE
GEN GENERATOR
GND GROUND
HP HORSE POWER
HZ HERTZ
INCAND INCANDESCENT
INSTL INSTALLATION
J-BOX JUNCTION BOX
K KILO
KV KILO VOLT
KVA KILO VOLT AMPERE
LTG LIGHTING
MAG MAGNETIC
MAX MAXIMUM
MIN MINIMUM OR MINUTE
MTG MOUNTING
NO NUMBER
O/H OVER HEAD
PH PHASE
PNLBD PANELBOARD
PRIM PRIMARY
PWR POWER
Q'TY QUANTITY
RCPT RECEPTACLE
REQ'D REQUIRED
SCHED SCHEDULE
SEC SECONDARY
SPEC SPECIFICATION
STD STANDARD
SW SWITCH
TEL TELEPHONE
TYP TYPICAL
U/G UNDERGROUND
V VOLT
VA VOLT AMPERE
W WATT
W/ WITH
XFMR TRANSFORMER
& AND
PANELBOARD
HOMERUN CIRCUIT TO PANELBOARD
TYPE
DUPLEX RECEPTACLE, 2P-3W-20A-125V, GROUNDING
ABBREVIATION
AUXILIARY
DESCRIPTIONSYMBOL
BRANCH CIRCUIT, EXPOSED ON CEILING OR WALL
1.
3.
4.
5.
ANY CIRCUIT WITHOUT FURTHER DESIGNATION INDICATES 2-#12AWG
WIRES IN 16C CONDUIT UNLESS OTHERWISE INDICATED.
THE GROUNDING CONDUCTORS SHALL BE SEPARATELY PROVIDED FOR
ELECTRICAL EQUIPMENT UNLESS OTHERWISE INDICATED ON THE DRAWING.
CATV BEFORE CONSTRUCTION.
CONTRACTOR SHALL COORDINATE WITH AREA MP, DO IMO, SIGNAL BRIGADE,
FIRE CODE AND SPECIFICATIONS.
OF THE NATIONAL ELECTRICAL CODE, NATIONAL ELECTRICAL SAFETY CODE,
ALL ELECTRICAL WORK SHALL CONFORM TO THE CURRENT REQUIREMENTS
OR RENOVATION.
CONDITION AND DIMENSIONS PRIOR TO COMMENCING ANY CONSTRUCTION
THE CONTRACTOR SHALL BE RESPONSIBLE IN VERIFING ALL EXISTING
UNITS.
CERTIFICATE FROM MANUFACTURER FOR LED LIGHTING FIXTURES AND POWER
CONTRACTOR SHALL BE RESPONSIBLE TO PROVIDE 10YEARS WARRANTY
THE GRADING LINE OF NEW DUCTS WILL BE LIMITED TO THE
WIDTH OF DUCT EXCAVATION.
AND AFTER INSTALLATION OF ELECTRICAL SYSTEM.
TO THEIR ORIGINAL CONDITION AND OPERATION DURING
ALL DAMAGED AREA INCLUDING SODDING, UTILITIES, STRUCTURES
THE CONTRACTOR SHALL BE RESPONSIBLE FOR RESTORING
6.
7.
1.
T TELEPHONE LINE
3.
ACCESSARIES WITH NEW.
EXTERIOR LIGHT, TOGGLE SWITCHES AND MOUNTING
REPLACE DETERIORATED EXISTING LIGHTING FIXTURES,
REPLACE EXISTING RECEPTACLES W/COVER WITH NEW.
2.L
ON ELECTRICAL PLAN
LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG
L
ON ELECTRICAL PLAN
LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG
4.
S-250.
LIGHTNING PROTECTION SYSTEM OF BUILDING S-249 AND
INCLUDING GROUNDING TEST, ANALYSYS FOR EXISTING
PROVIDE LIGHTNING PROTECTION SYSTEM REPORT
WITH NEW.
REPLACE DETERIORATED EXISTING TELEPHONE OUTLETS
CAMP CASEY
(BLDG# S-249 & S-250)
REPAIR EARTH COVERED MAGAZINES, AHA 25
TAK, YS
190901
SCALE:
1/25
L
J
L
J
L
J
SS
WALL MOUNTED LIGHT EMITTING DIODE(LED) LIGHT
EXPLOSION PROOF TYPE LIGHT EMITTING DIODE(LED) LIGHT
OUTPUT:8,400lm,SURGE PROTECTION:15kV, CONVERTER AND
FIXTURE, 1PH, 120/277V, 80 WATT, EFFICACY:105lm/W, LUMEN
ACCESSORIES, HAZARDOUS LOCATIONS(CLASS I&II, DIVISION 2),
LUMIDAS-EX-80W OR APPROVED EQUAL.
UL LISTED, MANUFACTURED BY "DONGBU LIGHTEC" MODEL:
WET LOCATIONS TYPE(IP66), UL LISTED POWER
NS-2NS-1
FIXTURE, 1PH, 120V, 60 WATTS, CONVERTER AND ACCESSORIES
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
ELECTRICAL
TYPE "NS-1"
LED LIGHT, "EXPLOSION PROOF"
NEW CEILING SURFACE MOUNTED
"WP""WP""WP"
LOCATION, TYPE "NS-2"
NEW WALL MOUNTED LED LIGHT, WET
& COVER PLATE
WITH "WEATHER PROOF" TYPE ENCLOSURE
NEW DUPLEX GFCI POWER RECEPTACLE
EXIST/NEW ELECTRICAL PLAN FOR S-249 & S-250
E-2
& S-250, LIGHTING FIXTURE DETAILS
EXIST/NEW ELECTRICAL PLAN FOR S-249
EXIST PANELBOARD
TYPE ENCLOSURE AND COVER PLATE
NEW TELEPHONE SINGLE OUTLET WITH WEATHER PROOF
& S-259)
(TYPICAL OF 2EA FOR S-258
ENCLOSURE & COVER PLATE
WITH "WEATHER PROOF" TYPE
NEW LIGHT TOGGLE SWITCH
CAMP CASEY
(BLDG# S-249 & S-250)
REPAIR EARTH COVERED MAGAZINES, AHA 25
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
ELECTRICAL
A. REPAIR/MAINTENANCE ( K )
SCOPE OF WORK
LEGEND, GENERAL NOTES AND
L E G E N D
FLEXIBLE CONDUIT W/CONNECTORS
LIGHTING
WIRING
POWER
INTERIOR
SYMBOL DESCRIPTION
DESCRIPTION
DESCRIPTIONSYMBOL
SYMBOL
AND GOVERNMENT INSTALLED
GOVERNMENT FURNISHED
GFGI
WEATHERPROOFWP
LA LIGHTNING ARRESTER
EXPLOSIONPROOFEP
DISTRIBUTIONDIST
GROUND FAULT PROTECTIONGFP
A AMPERE
AC ALTERNATING CURRENT
AF/AT AMPERE FRAME/AMPERE TRIP
AWG AMERICAN WIRE GAUGE
BC BARE COPPER
BLDG BUILDING
BRKR BREAKER
C CONDUIT
CB CIRCUIT BREAKER
CKT CIRCUIT
CONN CONNECTION
CT CURRENT TRANSFORMER
DET(S) DETAIL(S)
DIAG DIAGRAM
DISC DISCONNECT
DWG(S) DRAWING(S)
EA EACH
EM EMERGENCY
ENCL ENCLOSURE
EXST EXISTING
F/A FIRE ALARM
FL FLOOR
FLUOR FLUORESCENT
FXTR FIXTURE
GEN GENERATOR
GND GROUND
HP HORSE POWER
HZ HERTZ
INCAND INCANDESCENT
INSTL INSTALLATION
J-BOX JUNCTION BOX
K KILO
KV KILO VOLT
KVA KILO VOLT AMPERE
LTG LIGHTING
MAG MAGNETIC
MAX MAXIMUM
MIN MINIMUM OR MINUTE
MTG MOUNTING
NO NUMBER
O/H OVER HEAD
PH PHASE
PNLBD PANELBOARD
PRIM PRIMARY
PWR POWER
Q'TY QUANTITY
RCPT RECEPTACLE
REQ'D REQUIRED
SCHED SCHEDULE
SEC SECONDARY
SPEC SPECIFICATION
STD STANDARD
SW SWITCH
TEL TELEPHONE
TYP TYPICAL
U/G UNDERGROUND
V VOLT
VA VOLT AMPERE
W WATT
W/ WITH
XFMR TRANSFORMER
& AND
HOMERUN CIRCUIT TO PANELBOARD
ABBREVIATION
AUXILIARY
DESCRIPTIONSYMBOL
BRANCH CIRCUIT, EXPOSED ON CEILING OR WALL
T TELEPHONE LINE
2.
1.
3.
ACCESSARIES WITH NEW.
EXTERIOR LIGHT, TOGGLE SWITCHES AND MOUNTING
REPLACE DETERIORATED EXISTING LIGHTING FIXTURES,
REPLACE EXISTING RECEPTACLES W/COVER WITH NEW.
1.
3.
4.
5.
ANY CIRCUIT WITHOUT FURTHER DESIGNATION INDICATES 2-#12AWG
WIRES IN 16C CONDUIT UNLESS OTHERWISE INDICATED.
THE GROUNDING CONDUCTORS SHALL BE SEPARATELY PROVIDED FOR
ELECTRICAL EQUIPMENT UNLESS OTHERWISE INDICATED ON THE DRAWING.
CATV BEFORE CONSTRUCTION.
CONTRACTOR SHALL COORDINATE WITH AREA MP, DO IMO, SIGNAL BRIGADE,
FIRE CODE AND SPECIFICATIONS.
OF THE NATIONAL ELECTRICAL CODE, NATIONAL ELECTRICAL SAFETY CODE,
ALL ELECTRICAL WORK SHALL CONFORM TO THE CURRENT REQUIREMENTS
OR RENOVATION.
CONDITION AND DIMENSIONS PRIOR TO COMMENCING ANY CONSTRUCTION
THE CONTRACTOR SHALL BE RESPONSIBLE IN VERIFING ALL EXISTING
UNITS.
CERTIFICATE FROM MANUFACTURER FOR LED LIGHTING FIXTURES AND POWER
CONTRACTOR SHALL BE RESPONSIBLE TO PROVIDE 10YEARS WARRANTY
THE GRADING LINE OF NEW DUCTS WILL BE LIMITED TO THE
WIDTH OF DUCT EXCAVATION.
AND AFTER INSTALLATION OF ELECTRICAL SYSTEM.
TO THEIR ORIGINAL CONDITION AND OPERATION DURING
ALL DAMAGED AREA INCLUDING SODDING, UTILITIES, STRUCTURES
THE CONTRACTOR SHALL BE RESPONSIBLE FOR RESTORING
6.
7.
2.
4.
SINGLE POLE TOGGLE SWITCH, 15A-125VS
J JUNCTION BOX
PANELBOARD
TYPE
DUPLEX RECEPTACLE, 2P-3W-20A-125V, GROUNDING
L
ON ELECTRICAL PLAN
LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG
L
ON ELECTRICAL PLAN
LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG
5.
S-252.
LIGHTNING PROTECTION SYSTEM OF BUILDING S-251 AND
INCLUDING GROUNDING TEST, ANALYSYS FOR EXISTING
PROVIDE LIGHTNING PROTECTION SYSTEM REPORT
CAMP CASEY
(BLDG# S-251 & S-252)
REPAIR EARTH COVERED MAGAZINES, AHA 25
TAK, YS
190901
WITH NEW.
REPLACE DETERIORATED EXISTING TELEPHONE OUTLETS
PANELBOARD.
DISTRIBUTION PANEL, SAFETY SWITCHES AND NEW A
POWER LINE AND A NEW CIRCUIT BREAKER IN MAIN
CONNECT POWER TO DEHUMIDIFIERS WITH NEW EXTERIOR
"LC2"
"PPA"
"MTS"
EH-2
EH-3
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
ELECTRICAL
E-2
252 258
SCALE: 1/300
NEW PANELBOAED "NP"
J
J
(MECH ITEM) (TYPICAL OF 3EA)
NEW DEHUMIDIFIER, 3PH, 460V, 7.8KW
H
H
H
H
EXIST RACK MTD. EQUIPMENTEXIST LIGHT CONTACTOR "LC1"
EXIST "DPA"
EXIST DT "T1"
BREAKER 3P-225AF-20AT WITH NEW 3P-225AF-70AT.
EXIST "MDP"/ REPLACE EXIST CIRCUIT
CONCRETE GROUND.
IN 35mm C. W/ CONCRETE ENCASED/ RESTORE
NEW U/G ELECTRIC WIRE 4-#4 AWG & 1-#8(G)
EXIST ELECTRIC MANHOLE (TYPCAL)
E
E
E
NEMA 3R ENCL. (TYPCAL)
600V, 60A, NON-FUSIBLE,
NEW SAFETY SWITCH, 3PST,
EXIST/NEW EXTERIOR POWER DISTRIBUTION LINE PLAN FOR BUILDING S-251 AND S-252
LINE PLAN FOR BUILDING S-251 AND S-252
EXIST/NEW EXTERIOR POWER DISTRIBUTION
CAMP CASEY
(BLDG# S-251 & S-252)
REPAIR EARTH COVERED MAGAZINES, AHA 25
TAK, YS
190901
ACCESSARIES(TYPCAL)
CONCRETE WALL W/ MOUNTING
& 1-#10(G) IN 27mm C ON THE
NEW ELECTRIC WIRE, 4-#8 AWG
E-3
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
ELECTRICAL
L
L L
L
L
J
JJ
J
WALL MOUNTED LIGHT EMITTING DIODE(LED) LIGHT
EXPLOSION PROOF TYPE LIGHT EMITTING DIODE(LED) LIGHT
OUTPUT:8,400lm,SURGE PROTECTION:15kV, CONVERTER AND
FIXTURE, 1PH, 120/277V, 80 WATT, EFFICACY:105lm/W, LUMEN
ACCESSORIES, HAZARDOUS LOCATIONS(CLASS I&II, DIVISION 2),
LUMIDAS-EX-80W OR APPROVED EQUAL.
UL LISTED, MANUFACTURED BY "DONGBU LIGHTEC" MODEL:
WET LOCATIONS TYPE(IP66), UL LISTED POWER
NS-2NS-1
FIXTURE, 1PH, 120V, 60 WATTS, CONVERTER AND ACCESSORIES
SCALE:
S
1/100
TVSS
"NP"
A
T O T A L
NO.
CKT
DESCRIPTION
LOAD(VA)
TOTAL PHASE LOAD BREAKER SIZE
CONNECTION DIAGRAM
F TB C
S N
3 4
A B C
GRD
N
3 100 30
NEW PANELBOARD "NP" LOAD SCHEDULE
35400
DEHUMIDIFIER FOR BLDG S-252
DEHUMIDIFIER FOR BLDG S-253
7800 2600
4600 1533 1534
SPARE 3000W
3000WSPARE
TVSS
TVSS
SURFACE MOUNTED, NEMA 3R ENCL.
3PH-4W-277/480V-60HZ, W/ SN & GRD, 10,000AIC
100AF-70AT
MAIN CB
SJ
7.8KW
4.6KW 1533
EXIST/NEW ELECTRICAL PLAN FOR S-251 & S-252
"WP""WP" "WP""WP"
(TYPICAL FOR S-251 & S-252)
"WEATHER PROOF" TYPE ENCLOSURE & COVER PLATE
NEW DUPLEX GFCI POWER RECEPTACLE WITH
TYPE "NS-2" (TYPICAL FOR S-251 & S-252)
NEW WALL MOUNTED LED LIGHT, WET LOCATION,
TYPE "NS-1"(TYPICAL FOR S-251 & S-252)
LED LIGHT, "EXPLOSION PROOF"
NEW CEILING SURFACE MOUNTED
NEW PANELBOARD "NP" LOAD SCHEDULE
& S-252, LIGHTING FIXTURE DETAILS &
EXIST/NEW ELECTRICAL PLAN FOR S-251
DEHUMIDIFIER FOR BLDG S-254
DEHUMIDIFIER FOR BLDG S-255
4.6KW
4.6KW
DEHUMIDIFIER FOR BLDG S-251 7.8KW 2600 2600
1533 1533 1534
1533 1533 1534
2600 2600 2600
11799
1000 31000
11799 11802
3 30- - - -
(TYPICAL FOR S-251 & S-252)
TO INDICATE WHEN INTERIOR LIGHTS ARE ON(1EA)
ENCLOSURE(2EA) & WEATERPROOF RED JEWEL AND PILOT LIGHT
NEW LIGHT TOGGLE SWITCHES WITH "WEATHER PROOF" TYPE
"OAM"
PLATE (TYIPICAL FOR S-251 & S-252)
PROOF TYPE ENCLOSURE AND COVER
NEW TELEPHONE OUTLET WITH WEATHER
L L
JJ
CAMP CASEY
(BLDG# S-251 & S-252)
REPAIR EARTH COVERED MAGAZINES, AHA 25
TAK, YS
190901
(TYPICAL FOR BUILIDNG S-251 & S-252)
EXIST PANELBOARD "OAM#1" OR "OAM#2"
NEW PANEL BOARD (FOR BUILIDNG S-252)
277/480V, 40KA, UL LISTED. (FOR BUIDLIGN S-252)
NEW TRANSIENT VOLTAGE SURGE SUPPRESSOR(TVSS)
TOTAL DEMAND LOAD ; 31400 ( VA ) DEMAND FACTOR ; 88.7 ( % )
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
ELECTRICAL
A. REPAIR/MAINTENANCE ( K )
SCOPE OF WORK
LEGEND, GENERAL NOTES AND
L E G E N D
FLEXIBLE CONDUIT W/CONNECTORS
LIGHTING
WIRING
POWER
INTERIOR
SYMBOL DESCRIPTION
DESCRIPTION
DESCRIPTIONSYMBOL
SYMBOL
AND GOVERNMENT INSTALLED
GOVERNMENT FURNISHED
GFGI
WEATHERPROOFWP
LA LIGHTNING ARRESTER
EXPLOSIONPROOFEP
DISTRIBUTIONDIST
GROUND FAULT PROTECTIONGFP
A AMPERE
AC ALTERNATING CURRENT
AF/AT AMPERE FRAME/AMPERE TRIP
AWG AMERICAN WIRE GAUGE
BC BARE COPPER
BLDG BUILDING
BRKR BREAKER
C CONDUIT
CB CIRCUIT BREAKER
CKT CIRCUIT
CONN CONNECTION
CT CURRENT TRANSFORMER
DET(S) DETAIL(S)
DIAG DIAGRAM
DISC DISCONNECT
DWG(S) DRAWING(S)
EA EACH
EM EMERGENCY
ENCL ENCLOSURE
EXST EXISTING
F/A FIRE ALARM
FL FLOOR
FLUOR FLUORESCENT
FXTR FIXTURE
GEN GENERATOR
GND GROUND
HP HORSE POWER
HZ HERTZ
INCAND INCANDESCENT
INSTL INSTALLATION
J-BOX JUNCTION BOX
K KILO
KV KILO VOLT
KVA KILO VOLT AMPERE
LTG LIGHTING
MAG MAGNETIC
MAX MAXIMUM
MIN MINIMUM OR MINUTE
MTG MOUNTING
NO NUMBER
O/H OVER HEAD
PH PHASE
PNLBD PANELBOARD
PRIM PRIMARY
PWR POWER
Q'TY QUANTITY
RCPT RECEPTACLE
REQ'D REQUIRED
SCHED SCHEDULE
SEC SECONDARY
SPEC SPECIFICATION
STD STANDARD
SW SWITCH
TEL TELEPHONE
TYP TYPICAL
U/G UNDERGROUND
V VOLT
VA VOLT AMPERE
W WATT
W/ WITH
XFMR TRANSFORMER
& AND
HOMERUN CIRCUIT TO PANELBOARD
ABBREVIATION
AUXILIARY
DESCRIPTIONSYMBOL
BRANCH CIRCUIT, EXPOSED ON CEILING OR WALL
T TELEPHONE LINE
2.
1.
3.
ACCESSARIES WITH NEW.
EXTERIOR LIGHT, TOGGLE SWITCHES AND MOUNTING
REPLACE DETERIORATED EXISTING LIGHTING FIXTURES,
REPLACE EXISTING RECEPTACLES W/COVER WITH NEW.
1.
3.
4.
5.
ANY CIRCUIT WITHOUT FURTHER DESIGNATION INDICATES 2-#12AWG
WIRES IN 16C CONDUIT UNLESS OTHERWISE INDICATED.
THE GROUNDING CONDUCTORS SHALL BE SEPARATELY PROVIDED FOR
ELECTRICAL EQUIPMENT UNLESS OTHERWISE INDICATED ON THE DRAWING.
CATV BEFORE CONSTRUCTION.
CONTRACTOR SHALL COORDINATE WITH AREA MP, DO IMO, SIGNAL BRIGADE,
FIRE CODE AND SPECIFICATIONS.
OF THE NATIONAL ELECTRICAL CODE, NATIONAL ELECTRICAL SAFETY CODE,
ALL ELECTRICAL WORK SHALL CONFORM TO THE CURRENT REQUIREMENTS
OR RENOVATION.
CONDITION AND DIMENSIONS PRIOR TO COMMENCING ANY CONSTRUCTION
THE CONTRACTOR SHALL BE RESPONSIBLE IN VERIFING ALL EXISTING
UNITS.
CERTIFICATE FROM MANUFACTURER FOR LED LIGHTING FIXTURES AND POWER
CONTRACTOR SHALL BE RESPONSIBLE TO PROVIDE 10YEARS WARRANTY
THE GRADING LINE OF NEW DUCTS WILL BE LIMITED TO THE
WIDTH OF DUCT EXCAVATION.
AND AFTER INSTALLATION OF ELECTRICAL SYSTEM.
TO THEIR ORIGINAL CONDITION AND OPERATION DURING
ALL DAMAGED AREA INCLUDING SODDING, UTILITIES, STRUCTURES
THE CONTRACTOR SHALL BE RESPONSIBLE FOR RESTORING
6.
7.
2.
4.
SINGLE POLE TOGGLE SWITCH, 15A-125VS
J JUNCTION BOX
PANELBOARD
TYPE
DUPLEX RECEPTACLE, 2P-3W-20A-125V, GROUNDING
L
ON ELECTRICAL PLAN
LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG
L
ON ELECTRICAL PLAN
LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG
5.
CAMP CASEY
(BLDG# S-253, 254 & S-255)
REPAIR EARTH COVERED MAGAZINES, AHA 25
TAK, YS
190901
WITH NEW.
REPLACE DETERIORATED EXISTING TELEPHONE OUTLETS
S-254 AND S-255.
LIGHTNING PROTECTION SYSTEM OF BUILDING S-253,
INCLUDING GROUNDING TEST, ANALYSYS FOR EXISTING
PROVIDE LIGHTNING PROTECTION SYSTEM REPORT
MANHOLE.
EXTERIOR POWER LINE AND SAFETY SWITCHES, ELECTRIC
CONNECT POWER TO DEHUMIDIFIERS FOR WITH NEW
"LC2"
"PPA"
"MTS"
EH-2
EH-3
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
ELECTRICAL
E-2
252 258
SCALE: 1/300
NEW PANELBOAED "NP"
J
(MECH ITEM) (TYPICAL OF 3EA)
NEW DEHUMIDIFIER, 3PH, 460V, 4.6KW
H
H
H
H
H
EXIST RACK MTD. EQUIPMENT
J
J
EXIST LIGHT CONTACTOR "LC1"
EXIST "DPA"
EXIST DT "T1"
NEW ELECTRIC MANHOLE "1.2m(H)X1.2m(W)X1.2m(D)"
EXIST ELECTRIC MANHOLE (TYPCAL)
N
E
E
E
NEMA 3R ENCL. (TYPCAL)
600V, 60A, NON-FUSIBLE,
NEW SAFETY SWITCH, 3PST,
CAMP CASEY
(BLDG# S-253, 254 & S-255)
REPAIR EARTH COVERED MAGAZINES, AHA 25
TAK, YS
190901
EXIST/NEW EXTERIOR POWER DISTRIBUTION LINE PLAN FOR BUILDING S-253, S-254 AND S-255
AND S-255
LINE PLAN FOR BUILDING S-253, S-254
EXIST/NEW EXTERIOR POWER DISTRIBUTION
ACCESSARIES(TYPCAL)
CONCRETE WALL W/ MOUNTING
& 1-#10(G) IN 27mm C ON THE
NEW ELECTRIC WIRE, 4-#10 AWG
& 1-#10(G) IN 28mm C.
NEW U/G ELECTRIC WIRE, 3 SETS OF 4-#10 AWG
EXIST "MDP
E-3
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
ELECTRICAL
WALL MOUNTED LIGHT EMITTING DIODE(LED) LIGHT
EXPLOSION PROOF TYPE LIGHT EMITTING DIODE(LED) LIGHT
OUTPUT:8,400lm,SURGE PROTECTION:15kV, CONVERTER AND
FIXTURE, 1PH, 120/277V, 80 WATT, EFFICACY:105lm/W, LUMEN
ACCESSORIES, HAZARDOUS LOCATIONS(CLASS I&II, DIVISION 2),
LUMIDAS-EX-80W OR APPROVED EQUAL.
UL LISTED, MANUFACTURED BY "DONGBU LIGHTEC" MODEL:
WET LOCATIONS TYPE(IP66), UL LISTED POWER
NS-2NS-1
FIXTURE, 1PH, 120V, 60 WATTS, CONVERTER AND ACCESSORIES
A
T O T A L
NO.
CKT
DESCRIPTION
LOAD(VA)
TOTAL PHASE LOAD BREAKER SIZE
CONNECTION DIAGRAM
F TB C
S N
3 4
A B C
GRD
N
3 100 30
NEW PANELBOARD "NP" LOAD SCHEDULE
35400
DEHUMIDIFIER FOR BLDG S-252
DEHUMIDIFIER FOR BLDG S-253
7800 2600
4600 1533 1534
SPARE 3000W
3000WSPARE
TVSS
TVSS
SURFACE MOUNTED, NEMA 3R ENCL.
3PH-4W-277/480V-60HZ, W/ SN & GRD, 10,000AIC
100AF-70AT
MAIN CB
7.8KW
4.6KW 1533
DEHUMIDIFIER FOR BLDG S-254
DEHUMIDIFIER FOR BLDG S-255
4.6KW
4.6KW
DEHUMIDIFIER FOR BLDG S-251 7.8KW 2600 2600
1533 1533 1534
1533 1533 1534
2600 2600 2600
11799
1000 31000
11799 11802
3 30- - - -
L
L L
L
L
J
JJ
J
SCALE:
S
1/100
SJ
"WP""WP" "WP""WP" "OAM"
CAMP CASEY
(BLDG# S-253, 254 & S-255)
REPAIR EARTH COVERED MAGAZINES, AHA 25
TAK, YS
190901
EXIST/NEW ELECTRICAL PLAN FOR S-253, S-254 & S-255
& S-255)
TYPE "NS-2" (TYPICAL FOR S-253, S-254
NEW WALL MOUNTED LED LIGHT, WET LOCATION,
(TYPICAL FOR S-253, S-254 & S-255)
"WEATHER PROOF" TYPE ENCLOSURE & COVER PLATE
NEW DUPLEX GFCI POWER RECEPTACLE WITH
(TYPICAL FOR S-253, S-254 & S-255)
TO INDICATE WHEN INTERIOR LIGHTS ARE ON(1EA)
ENCLOSURE(2EA) & WEATERPROOF RED JEWEL AND PILOT LIGHT
NEW LIGHT TOGGLE SWITCHES WITH "WEATHER PROOF" TYPE
(FOR BUILIDNG S-253, S-254 & S-255)
EXIST PANELBOARD "OAM#3", "OAM#4" OR "OAM#5"
TYPE "NS-1"(TYPICAL S-253, S-254 & S-255)
LED LIGHT, "EXPLOSION PROOF"
NEW CEILING SURFACE MOUNTED
S-255)
PLATE (TYIPICAL FOR S-253, S-254 &
PROOF TYPE ENCLOSURE AND COVER
NEW TELEPHONE OUTLET WITH WEATHER
TOTAL DEMAND LOAD ; 31400 ( VA ) DEMAND FACTOR ; 88.7 ( % ) & NEW PANELBOARD "NP" LOAD SCHEDULE
,S-254 & S-255 LIGHTING FIXTURE DETAILS
EXIST/NEW ELECTRICAL PLAN FOR S-253
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
ELECTRICAL
A. REPAIR/MAINTENANCE ( K )
SCOPE OF WORK
LEGEND, GENERAL NOTES AND
L E G E N D
FLEXIBLE CONDUIT W/CONNECTORS
LIGHTING
WIRING
POWER
INTERIOR
SYMBOL DESCRIPTION
DESCRIPTION
DESCRIPTION
J JUNCTION BOX
SYMBOL
SYMBOL
F FAN MOTOR (UNDER MECH. ITEM)
C CONTROL CIRCUIT
AND GOVERNMENT INSTALLED
GOVERNMENT FURNISHED
GFGI
WEATHERPROOFWP
LA LIGHTNING ARRESTER
EXPLOSIONPROOFEP
DISTRIBUTIONDIST
GROUND FAULT PROTECTIONGFP
A AMPERE
AC ALTERNATING CURRENT
AF/AT AMPERE FRAME/AMPERE TRIP
AWG AMERICAN WIRE GAUGE
BC BARE COPPER
BLDG BUILDING
BRKR BREAKER
C CONDUIT
CB CIRCUIT BREAKER
CKT CIRCUIT
CONN CONNECTION
CT CURRENT TRANSFORMER
DET(S) DETAIL(S)
DIAG DIAGRAM
DISC DISCONNECT
DWG(S) DRAWING(S)
EA EACH
EM EMERGENCY
ENCL ENCLOSURE
EXST EXISTING
F/A FIRE ALARM
FL FLOOR
FLUOR FLUORESCENT
FXTR FIXTURE
GEN GENERATOR
GND GROUND
HP HORSE POWER
HZ HERTZ
INCAND INCANDESCENT
INSTL INSTALLATION
J-BOX JUNCTION BOX
K KILO
KV KILO VOLT
KVA KILO VOLT AMPERE
LTG LIGHTING
MAG MAGNETIC
MAX MAXIMUM
MIN MINIMUM OR MINUTE
MTG MOUNTING
NO NUMBER
O/H OVER HEAD
PH PHASE
PNLBD PANELBOARD
PRIM PRIMARY
PWR POWER
Q'TY QUANTITY
RCPT RECEPTACLE
REQ'D REQUIRED
SCHED SCHEDULE
SEC SECONDARY
SPEC SPECIFICATION
STD STANDARD
SW SWITCH
TEL TELEPHONE
TYP TYPICAL
U/G UNDERGROUND
V VOLT
VA VOLT AMPERE
W WATT
W/ WITH
XFMR TRANSFORMER
& AND
PANELBOARD
HOMERUN CIRCUIT TO PANELBOARD
TYPE
DUPLEX RECEPTACLE, 2P-3W-20A-125V, GROUNDING
ABBREVIATION
AUXILIARY
DESCRIPTIONSYMBOL
BRANCH CIRCUIT, EXPOSED ON CEILING OR WALL
T TELEPHONE LINE
2.
1.
3.
4.
CIRCUIT BREAKER FOR BUILDING S-256 & S-257.
INTERIOR/EXTERIOR POWER LINE AND A NEW ENCLOSED
CONNECT POWER TO DEHUMIDIFIERS FOR WITH NEW
ACCESSARIES WITH NEW FOR BUILDING S-256 & S-257.
EXTERIOR LIGHT, TOGGLE SWITCHES AND MOUNTING
REPLACE DETERIORATED EXISTING LIGHTING FIXTURES,
5.
1.
3.
4.
5.
ANY CIRCUIT WITHOUT FURTHER DESIGNATION INDICATES 2-#12AWG
WIRES IN 16C CONDUIT UNLESS OTHERWISE INDICATED.
THE GROUNDING CONDUCTORS SHALL BE SEPARATELY PROVIDED FOR
ELECTRICAL EQUIPMENT UNLESS OTHERWISE INDICATED ON THE DRAWING.
CATV BEFORE CONSTRUCTION.
CONTRACTOR SHALL COORDINATE WITH AREA MP, DO IMO, SIGNAL BRIGADE,
FIRE CODE AND SPECIFICATIONS.
OF THE NATIONAL ELECTRICAL CODE, NATIONAL ELECTRICAL SAFETY CODE,
ALL ELECTRICAL WORK SHALL CONFORM TO THE CURRENT REQUIREMENTS
OR RENOVATION.
CONDITION AND DIMENSIONS PRIOR TO COMMENCING ANY CONSTRUCTION
THE CONTRACTOR SHALL BE RESPONSIBLE IN VERIFING ALL EXISTING
UNITS.
CERTIFICATE FROM MANUFACTURER FOR LED LIGHTING FIXTURES AND POWER
CONTRACTOR SHALL BE RESPONSIBLE TO PROVIDE 10YEARS WARRANTY
THE GRADING LINE OF NEW DUCTS WILL BE LIMITED TO THE
WIDTH OF DUCT EXCAVATION.
AND AFTER INSTALLATION OF ELECTRICAL SYSTEM.
TO THEIR ORIGINAL CONDITION AND OPERATION DURING
ALL DAMAGED AREA INCLUDING SODDING, UTILITIES, STRUCTURES
THE CONTRACTOR SHALL BE RESPONSIBLE FOR RESTORING
6.
7.
2.
SINGLE POLE TOGGLE SWITCH, 15A-125VS
L
ON ELECTRICAL PLAN
LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG
L
ON ELECTRICAL PLAN
LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG
6.
DOORS FOR BUILDING S-256 & S-257.
RE-CONNECT POWER & CONTROL SYSTEM FOR NEW BLAST
S-257.
LIGHTNING PROTECTION SYSTEM OF BUILDING S-256 AND
INCLUDING GROUNDING TEST, ANALYSYS FOR EXISTING
PROVIDE LIGHTNING PROTECTION SYSTEM REPORT
CAMP CASEY
(BLDG# S-256 & S-257)
REPAIR EARTH COVERED MAGAZINES, AHA 25
TAK, YS
190901
FOR BUILDING S-256 & S-257.
REPLACE EXISTING RECEPTACLES W/COVER WITH NEW
WITH NEW OR BUILDING S-256 & S-257.
REPLACE DETERIORATED EXISTING TELEPHONE OUTLETS
L L L L L L
LLLLLL
L L L L L L
L
L L L
L L
J J J J J J
JJJJJJ
J J J J J J
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
ELECTRICAL
WALL MOUNTED LIGHT EMITTING DIODE(LED) LIGHT
EXPLOSION PROOF TYPE LIGHT EMITTING DIODE(LED) LIGHT
OUTPUT:8,400lm,SURGE PROTECTION:15kV, CONVERTER AND
FIXTURE, 1PH, 120/277V, 80 WATT, EFFICACY:105lm/W, LUMEN
ACCESSORIES, HAZARDOUS LOCATIONS(CLASS I&II, DIVISION 2),
LUMIDAS-EX-80W OR APPROVED EQUAL.
UL LISTED, MANUFACTURED BY "DONGBU LIGHTEC" MODEL:
WET LOCATIONS TYPE(IP66), UL LISTED POWER
NS-2NS-1
FIXTURE, 1PH, 120V, 60 WATTS, CONVERTER AND ACCESSORIES
TTC
SSSSSS
"EP""EP"
SCALE: 1/100
EXIST/NEW ELECTRICAL PLAN FOR S-256 & S-257
LM
LM
LM
LM LM
LM
IN 21C.
6-AWG #12 & 1-#12(G)
IN 21 C.
2-AWG #12 & 1-#12(G)
"WP"
"WP"
TYPE "NS-2"(TYPICAL)
NEW WALL MOUNTED LED LIGHT, WET LOCATION,
(TYPICAL OF 2EA)
"EXPLOSION PROOF" TYPE ENCLOSURE & COVER PLATE
NEW DUPLEX POWER RECEPTACLE WITH
(TYPICAL OF 2EA)
"WEATHER PROOF" TYPE ENCLOSURE & COVER PLATE
NEW DUPLEX GFCI POWER RECEPTACLE WITH
LIMIT SWITCH (TYPICAL)
(ARCH ITEM)(TYPICAL)
DOOR CONTROL PUSH BUTTON SWITCH
NOTE.
1.
"EP"
"EP"
"EP"
TYPE "NS-1" (TYPICAL)
LED LIGHT, "EXPLOSION PROOF"
NEW CEILING SURFACE MOUNTED
ENCLOSURE & COVER PLATE (TYPICAL OF 6EA)
NEW LIGHT TOGGLE SWITCH WITH "EXPLOSION PROOF" TYPE
S-256 & S-257
EXIST/NEW ELECTRICAL PLAN FOR
E-2
IN NEMA 7 ENCL.(TYPICAL)
NEMA SIZE 1 RATED AT 10HP, WITH 30A FUSES
WITH DISCONNECT SWITHCH, 480V, 3P,
COMBINATION REVERSING STARTER
MM
M
(TYPICAL)
DOOR MOTOR OPERATOR
"WP"
(TYIPICAL FOR S-256 & S-257)
TYPE ENCLOSURE AND COVER PLATE
NEW TELEPHONE OUTLET WITH WEATHER PROOF
OF NEW BLAST DOORS FOR GOVERNMENT APPROVAL PRIOR TO CONSTRUCTION.
DOORS. CONTRACTOR SHALL PROVIDE SHOP DRAWING FOR ACTUAL WIRING/CONTROL DIAGRAM
SYSTEM AND PROVIDE ELECTRICAL MATERIALS TO MEET REQUIREMENTS OF NEW BLAST
CONTRACTOR SHALL BE RESPOSIBLE TO VEIRFY EXISTING CONDITION OF ELECTRICAL
WIRING AND CONTROL FOR BLAST DOOR CONTROL ARE ESTIMATED FOR BIDDING PURPOSE ONLY.
21 C.(TYPICAL)
3-AWG #12 & 1-#12(G) IN
POWER LINE TO MOTOR OPERATOR
CAMP CASEY
(BLDG# S-256 & S-257)
REPAIR EARTH COVERED MAGAZINES, AHA 25
TAK, YS
EXIST TELPHONE TERMINAL CABINET(TTC)
DH
P
P
D T R
S
N
S P
D
P
ANGLE TO ANGLE
AS REQUIRED
V A
R
200SQx8THK
BOTTOM PLATE
(TYPICAL)
100x200x8THK
GALV STL ANGLE
16dia MACHINE BOLT
#8 "BC"
GROUND WIRE
G
GROUND WIRE
GL
100x100x8THK(TYPICAL)
#8 "BC" IN 21C
SUPPORTING SADDLE(TYPICAL)
GALV STL ANGLE,
100 VAR 100
HD@16@200 O.C
BOT BARS
GALV STL CONDUIT
(TYPICAL)
G
NOT TO SCALE
FROM PULL BOX
3-AWG #8 & 1-#10(G) IN 27 dia C.
TO DEHUMIDIFIER
3-AWG #8 & 1-#10(G) IN 27 dia C.
NEW ENCLOSED CIRCUIT BREAKER
NEW ENCLOSED CIRCUIT BREAKER MOUNTING DETAIL
SCALE: 1/100
NEW POWER PLAN FOR DEHUMIDIFIER (BLSG# S-256 & S-257)
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
ELECTRICAL
3-AWG #8 & 1-#10(G) IN 27 dia C.
RA 600x400
CONC. PAD
(TYPICAL FOR BUILDING S-256 & 257)
ON EARTH COVERED MAGAZINE
3P-100AF-50AT, 600V, NEMA 3R ENCL.
ENCLOSED CIRCUIT BREAKER,
NEW STRUCTURE SUPPORT MOUNTED
(TYPICAL FOR BUILDING S-256 & 257)
ON EARTH COVERED MAGAZINE
3P-100AF-50AT, 600V, NEMA 3R ENCL.
ENCLOSED CIRCUIT BREAKER,
NEW STRUCTURE SUPPORT MOUNTED
EXIST PANELBOARD "SN"
EXIST SURGE PROTECTION DEVICE
EXIST PANELBOARD "SN"
TRANSFORMER
EXIST DRY TYPE
"P2"
EXIST PANELBOARD
E-3
(BLSG# S-242 & S-243)
NEW POWER PLAN FOR DEHUMIDIFIER
SA 400x400
CONNECT TO EXIST BUILDING GROUNDING SYSTEM
EXIST BUILDING GROUNDING SYSTEM
(MECH ITEM)
NEW DEHUMIDIFIER, 3PH, 480V, 18KW
GROUNDING WIRE, AWG#8, "BC"
PROVIDE NEW AIRTERMINAL WITH
GFROM DEHUMIDIFIER
TO EXISTING GROUNDING SYSTEM (TYPICAL)
PROVIDE NEW BONDING CONNECTION
EXIST AIR TERMINAL(TYPICAL)
SERVICE ENTRANCE
EXIST PULLBOX FOR
NEW SEALING FITTING(TYPICAL)
EXIST MAGNETIC CONECTOR
EXIST TEMP. CONTROL PANEL
CAMP CASEY
(BLDG# S-256 & S-257)
REPAIR EARTH COVERED MAGAZINES, AHA 25
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
ELECTRICAL
A. REPAIR/MAINTENANCE ( K )
SCOPE OF WORK
LEGEND, GENERAL NOTES AND
L E G E N D
FLEXIBLE CONDUIT W/CONNECTORS
LIGHTING
WIRING
POWER
INTERIOR
SYMBOL DESCRIPTION
DESCRIPTION
DESCRIPTION
J JUNCTION BOX
SYMBOL
SYMBOL
F FAN MOTOR (UNDER MECH. ITEM)
C CONTROL CIRCUIT
AND GOVERNMENT INSTALLED
GOVERNMENT FURNISHED
GFGI
WEATHERPROOFWP
LA LIGHTNING ARRESTER
EXPLOSIONPROOFEP
DISTRIBUTIONDIST
GROUND FAULT PROTECTIONGFP
A AMPERE
AC ALTERNATING CURRENT
AF/AT AMPERE FRAME/AMPERE TRIP
AWG AMERICAN WIRE GAUGE
BC BARE COPPER
BLDG BUILDING
BRKR BREAKER
C CONDUIT
CB CIRCUIT BREAKER
CKT CIRCUIT
CONN CONNECTION
CT CURRENT TRANSFORMER
DET(S) DETAIL(S)
DIAG DIAGRAM
DISC DISCONNECT
DWG(S) DRAWING(S)
EA EACH
EM EMERGENCY
ENCL ENCLOSURE
EXST EXISTING
F/A FIRE ALARM
FL FLOOR
FLUOR FLUORESCENT
FXTR FIXTURE
GEN GENERATOR
GND GROUND
HP HORSE POWER
HZ HERTZ
INCAND INCANDESCENT
INSTL INSTALLATION
J-BOX JUNCTION BOX
K KILO
KV KILO VOLT
KVA KILO VOLT AMPERE
LTG LIGHTING
MAG MAGNETIC
MAX MAXIMUM
MIN MINIMUM OR MINUTE
MTG MOUNTING
NO NUMBER
O/H OVER HEAD
PH PHASE
PNLBD PANELBOARD
PRIM PRIMARY
PWR POWER
Q'TY QUANTITY
RCPT RECEPTACLE
REQ'D REQUIRED
SCHED SCHEDULE
SEC SECONDARY
SPEC SPECIFICATION
STD STANDARD
SW SWITCH
TEL TELEPHONE
TYP TYPICAL
U/G UNDERGROUND
V VOLT
VA VOLT AMPERE
W WATT
W/ WITH
XFMR TRANSFORMER
& AND
PANELBOARD
HOMERUN CIRCUIT TO PANELBOARD
TYPE
DUPLEX RECEPTACLE, 2P-3W-20A-125V, GROUNDING
ABBREVIATION
AUXILIARY
DESCRIPTIONSYMBOL
BRANCH CIRCUIT, EXPOSED ON CEILING OR WALL
T TELEPHONE LINE
1.
1.
3.
4.
5.
ANY CIRCUIT WITHOUT FURTHER DESIGNATION INDICATES 2-#12AWG
WIRES IN 16C CONDUIT UNLESS OTHERWISE INDICATED.
THE GROUNDING CONDUCTORS SHALL BE SEPARATELY PROVIDED FOR
ELECTRICAL EQUIPMENT UNLESS OTHERWISE INDICATED ON THE DRAWING.
CATV BEFORE CONSTRUCTION.
CONTRACTOR SHALL COORDINATE WITH AREA MP, DO IMO, SIGNAL BRIGADE,
FIRE CODE AND SPECIFICATIONS.
OF THE NATIONAL ELECTRICAL CODE, NATIONAL ELECTRICAL SAFETY CODE,
ALL ELECTRICAL WORK SHALL CONFORM TO THE CURRENT REQUIREMENTS
OR RENOVATION.
CONDITION AND DIMENSIONS PRIOR TO COMMENCING ANY CONSTRUCTION
THE CONTRACTOR SHALL BE RESPONSIBLE IN VERIFING ALL EXISTING
UNITS.
CERTIFICATE FROM MANUFACTURER FOR LED LIGHTING FIXTURES AND POWER
CONTRACTOR SHALL BE RESPONSIBLE TO PROVIDE 10YEARS WARRANTY
THE GRADING LINE OF NEW DUCTS WILL BE LIMITED TO THE
WIDTH OF DUCT EXCAVATION.
AND AFTER INSTALLATION OF ELECTRICAL SYSTEM.
TO THEIR ORIGINAL CONDITION AND OPERATION DURING
ALL DAMAGED AREA INCLUDING SODDING, UTILITIES, STRUCTURES
THE CONTRACTOR SHALL BE RESPONSIBLE FOR RESTORING
6.
7.
2.
SINGLE POLE TOGGLE SWITCH, 15A-125VS
L
ON ELECTRICAL PLAN
LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG
L
ON ELECTRICAL PLAN
LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG
CAMP CASEY
(BLDG# S-258 & S-259)
REPAIR EARTH COVERED MAGAZINES, AHA 25
TAK, YS
190901
BUILDING S-258 & S-259.
EXTERIOR LIGHT, TOGGLE SWITCHES WITH NEW FOR
REPLACE DETERIORATED EXISTING LIGHTING FIXTURES,
L1
FEC
STORAGE
WALL MOUNTED LIGHT EMITTING DIODE(LED) LIGHT
EXPLOSION PROOF TYPE LIGHT EMITTING DIODE(LED) LIGHT
OUTPUT:8,400lm,SURGE PROTECTION:15kV, CONVERTER AND
FIXTURE, 1PH, 120/277V, 80 WATT, EFFICACY:105lm/W, LUMEN
ACCESSORIES, HAZARDOUS LOCATIONS(CLASS I&II, DIVISION 2),
LUMIDAS-EX-80W OR APPROVED EQUAL.
UL LISTED, MANUFACTURED BY "DONGBU LIGHTEC" MODEL:
WET LOCATIONS TYPE(IP66), UL LISTED POWER
NS-2NS-1
FIXTURE, 1PH, 120V, 60 WATTS, CONVERTER AND ACCESSORIES
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
ELECTRICAL
E-2
& S-259, LIGHTING FIXTURE DETAILS
EXIST/NEW ELECTRICAL PLAN FOR S-258
L
J
L
J
L
J
L L S
"WP"
S
"WP"
TYPE "NS-1" (TYPICAL)
LED LIGHT, "EXPLOSION PROOF"
NEW CEILING SURFACE MOUNTED
TYPE "NS-2"(TYPICAL)
NEW WALL MOUNTED LED LIGHT, WET LOCATION,
ENCLOSURE & COVER PLATE(TYPICAL FOR S-258 & S-259)
NEW LIGHT TOGGLE SWITCH WITH "WEATHER PROOF" TYPE
SCALE:
1/50
EXIST/NEW ELECTRICAL PLAN FOR S-258 & S-259
CAMP CASEY
(BLDG# S-258 & S-259)
REPAIR EARTH COVERED MAGAZINES, AHA 25
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
ELECTRICAL
A. REPAIR/MAINTENANCE ( K )
2.
SCOPE OF WORK
LEGEND, GENERAL NOTES AND
SINGLE POLE TOGGLE SWITCH, 15A-125V
L E G E N D
FLEXIBLE CONDUIT W/CONNECTORS
LIGHTING
WIRING
POWER
INTERIOR
S
SYMBOL DESCRIPTION
DESCRIPTION
DESCRIPTION
J JUNCTION BOX
SYMBOL
SYMBOL
AND GOVERNMENT INSTALLED
GOVERNMENT FURNISHED
GFGI
WEATHERPROOFWP
LA LIGHTNING ARRESTER
EXPLOSIONPROOFEP
DISTRIBUTIONDIST
GROUND FAULT PROTECTIONGFP
A AMPERE
AC ALTERNATING CURRENT
AF/AT AMPERE FRAME/AMPERE TRIP
AWG AMERICAN WIRE GAUGE
BC BARE COPPER
BLDG BUILDING
BRKR BREAKER
C CONDUIT
CB CIRCUIT BREAKER
CKT CIRCUIT
CONN CONNECTION
CT CURRENT TRANSFORMER
DET(S) DETAIL(S)
DIAG DIAGRAM
DISC DISCONNECT
DWG(S) DRAWING(S)
EA EACH
EM EMERGENCY
ENCL ENCLOSURE
EXST EXISTING
F/A FIRE ALARM
FL FLOOR
FLUOR FLUORESCENT
FXTR FIXTURE
GEN GENERATOR
GND GROUND
HP HORSE POWER
HZ HERTZ
INCAND INCANDESCENT
INSTL INSTALLATION
J-BOX JUNCTION BOX
K KILO
KV KILO VOLT
KVA KILO VOLT AMPERE
LTG LIGHTING
MAG MAGNETIC
MAX MAXIMUM
MIN MINIMUM OR MINUTE
MTG MOUNTING
NO NUMBER
O/H OVER HEAD
PH PHASE
PNLBD PANELBOARD
PRIM PRIMARY
PWR POWER
Q'TY QUANTITY
RCPT RECEPTACLE
REQ'D REQUIRED
SCHED SCHEDULE
SEC SECONDARY
SPEC SPECIFICATION
STD STANDARD
SW SWITCH
TEL TELEPHONE
TYP TYPICAL
U/G UNDERGROUND
V VOLT
VA VOLT AMPERE
W WATT
W/ WITH
XFMR TRANSFORMER
& AND
PANELBOARD
HOMERUN CIRCUIT TO PANELBOARD
TYPE
DUPLEX RECEPTACLE, 2P-3W-20A-125V, GROUNDING
ABBREVIATION
AUXILIARY
DESCRIPTIONSYMBOL
BRANCH CIRCUIT, EXPOSED ON CEILING OR WALL
1.
3.
4.
5.
ANY CIRCUIT WITHOUT FURTHER DESIGNATION INDICATES 2-#12AWG
WIRES IN 16C CONDUIT UNLESS OTHERWISE INDICATED.
THE GROUNDING CONDUCTORS SHALL BE SEPARATELY PROVIDED FOR
ELECTRICAL EQUIPMENT UNLESS OTHERWISE INDICATED ON THE DRAWING.
CATV BEFORE CONSTRUCTION.
CONTRACTOR SHALL COORDINATE WITH AREA MP, DO IMO, SIGNAL BRIGADE,
FIRE CODE AND SPECIFICATIONS.
OF THE NATIONAL ELECTRICAL CODE, NATIONAL ELECTRICAL SAFETY CODE,
ALL ELECTRICAL WORK SHALL CONFORM TO THE CURRENT REQUIREMENTS
OR RENOVATION.
CONDITION AND DIMENSIONS PRIOR TO COMMENCING ANY CONSTRUCTION
THE CONTRACTOR SHALL BE RESPONSIBLE IN VERIFING ALL EXISTING
UNITS.
CERTIFICATE FROM MANUFACTURER FOR LED LIGHTING FIXTURES AND POWER
CONTRACTOR SHALL BE RESPONSIBLE TO PROVIDE 10YEARS WARRANTY
THE GRADING LINE OF NEW DUCTS WILL BE LIMITED TO THE
WIDTH OF DUCT EXCAVATION.
AND AFTER INSTALLATION OF ELECTRICAL SYSTEM.
TO THEIR ORIGINAL CONDITION AND OPERATION DURING
ALL DAMAGED AREA INCLUDING SODDING, UTILITIES, STRUCTURES
THE CONTRACTOR SHALL BE RESPONSIBLE FOR RESTORING
6.
7.
1.
T TELEPHONE LINE
3.
REPLACE EXISTING RECEPTACLES W/COVER WITH NEW.
2.L
ON ELECTRICAL PLAN
LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG
L
ON ELECTRICAL PLAN
LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG
CAMP CASEY
(BLDG# S-262 & S-263)
REPAIR EARTH COVERED MAGAZINES, AHA 25
TAK, YS
190901
WITH NEW.
REPLACE DETERIORATED EXISTING TELEPHONE OUTLETS
TOGGLE SWITCHES WITH NEW.
REPLACE DETERIORATED EXISTING LIGHTING FIXTURES,
3.
SAFETY SWITCH AND ASSOCIATED POWER LINE.
REPLACE POWER LINE FOR HEAT PUMP UNIT WITH NEW
GUARD OFFICE
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
ELECTRICAL
E-2
SCALE:
1/25
EXIST/NEW ELECTRICAL PLAN FOR S-262 & S-263
NS-3a & 3b
CEILING RECESSED MOUNTED LIGHT EMITTING DIODE (LED)
(NS-1a) & WITH EM UNIT (NS-1b) AS REQUIRED AND
FIXTURE, 1PH, 120V, 45W, WITH CONVERTER & ACCESSORIES
OR APPROVED EQUAL.
MANUFACTURED BY "SKC LIGHTING, CO., LTD"
LL
TYPE ENCLOSURE AND COVER PLATE(FOR BUILDING S-236)
NEW TELEPHONE SINGLE OUTLET WITH WEATHER PROOF
S S
WITH COVER PLATE (TYPICAL)
NEW DUPLEX POWER RECEPTACLE
LED LIGHT,TYPE "NS-3b"
NEW CEILING RECESS MOUNTED
LED LIGHT,TYPE "NS-3a"
NEW CEILING RECESS MOUNTED
CAMP CASEY
(BLDG# S-262 & S-263)
REPAIR EARTH COVERED MAGAZINES, AHA 25
TAK, YS
190901
& S-263, LIGHTING FIXTURE DETAIL
EXIST/NEW ELECTRICAL PLAN FOR S-262
J
NON-FUSIBLE, NEMA 3R ENCL.
NEW SAFETY SWITCH, DPST, 240VAC, 30A.
TO NEW HEAT PUMP UNIT.
COVER PLATE/RECONNECT TO EXIST POWER FOR A/C UNIT
REMOVE EXIST RECEPTACLE AND BLOCK UP WITH BLANK
J
(MECH ITEM)
NEW HEAT PUMP UNIT, 1PH, 120V, 960W.
HEATER WITH BLANK COVER PLATE.
COVER PLATE FOR ELECTRIC HEATER UNIT
BLOCK UP EXIST JUCTION BOX WITH BLANK
(MECH ITEM)
NEW HEAT PUMP UNIT (INDOOR)
| 190901_ELEC(S-249 & S-250) |
| E-1 (S-249 & S-250) |
| E-2 (S-249 & S-250) |
| 190901_ELEC(S-251 & S-252) |
| E-1 (S-251 & S-252) |
| E-2 (S-251 & S-252) |
| E-3 (S-251 & S-252) |
| 190901_ELEC(S-253, S-254 & S-255) |
| E-1 (S-253, S-254 & S-255) |
| E-2 (S-253, S-254 & S-255) |
| E-3 (S-253, S-254 & S-255) |
| 190901_ELEC(S-256 & S-257) |
| E-1 (S-256 & S-257) |
| E-2 (S-256 & S-257) |
| E-3 (S-256 & S-257) |
| 190901_ELEC(S-258 & S-259) |
| E-1 (S-258 & S-259) |
| E-2 (S-258 & S-259) |
| 190901_ELEC(S-262 & S-263) |
| E-1 (S-262 & S-263) |
| E-2 (S-262 & S-263) |