A06_SOW_Enclosures.pdf
PDF 11 MB Posted
- Attached to
- BRS CHECK VALVE INSTALLATION
- Solicitation number
- 140L3925Q0075
About this file
This document is a comprehensive 5-Year Sprinkler System Inspection Report for the Bureau of Land Management's Black Rock Station located at 200 Transfer Station Rd, Gerlach, Nevada. The inspection was conducted on 01/05/2022 by Scott Summitt, covering the entire facility's fire protection systems. Key findings include a booster pump that was non-operational with a low flowing pressure of only 18 psi (versus the required 57.6 psi), and the inspection was performed in accordance with NFPA 25 version 2017 standards. The report meticulously documents the status of various fire protection system components, including wet sprinklers, control valves, fire department connections, pipes, fittings, and sprinklers, with most items requiring further attention or repair.
The related federal contract opportunity (Solicitation Number: 140L3925Q0075) specifically seeks a contractor for BRS Check Valve Installation, which involves installing a backflow preventer device on the existing fire riser and completing the five-year NFPA 25 inspection of the fire sprinkler system. The project is governed by Nevada Administrative Code (NAC) and Nevada Revised Statutes (NRS) fire protection requirements, and requires contractor certification with the Nevada State Fire Marshall. The project is being managed by the Department of the Interior's Bureau of Land Management's Nevada Region, located at the Black Rock Station in Gerlach, Nevada.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| B03_Wage_Determination_SCA_2015-5601_Rv__26.pdf | ||
| A04_20250519_SOW_BRAC-BF.docx | DOCX document | |
| Sol_140L3925Q0075.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BUREAU OF LAND MANAGEMENT
5100 EAST WINNEMUCCA BLVD.
WINNEMUCCA, NV 89445
PROJECT
LOCATION
WELLS
Austin
Tonopah
LAS VEGAS
WENDOVERELKO
RENO
WINNEMUCCA
GERLACH
FLAP: COUNTY ROAD 34
RECONSTRUCTION
VICINTY MAP
VICINITY MAP
1.0
Vicinty Map
BRS BACKFLOW PREVENTION VALVES
BLACK ROCK
DESERT
LOCATION:
0 Transfer Rd, Washoe County, Nevada, 89412
Project Location: 40.659000°° N, - -119.370000° W
A
P
P
R
O
X
M
I
T
O
C
E
D
A
R
V
I
L
L
E
A P
P R
O X
M
I
U
S
I
G
R
A
N
I
R
A
N
G
E
U
N
I
N
P
C
I
F
I
L
R
O
A
D
EMPIRE
S
E
L E
N
I
N
G
E
B
L
A
K
OC
K
T
Y
A P
P R
O X
M
I
V
Y A
FLY GEYSER
SOLDIER MEADOWS RD
EMPIRE MINING
CORPORATION
PROJECT LOCATION
AutoCAD SHX Text Title
AutoCAD SHX Text Figure No.
AutoCAD SHX Text Project Title
AutoCAD SHX Text
NTS
AutoCAD SHX Text
ORIGINAL SHEET - ANSI A
AutoCAD SHX Text
APRIL 2025
AutoCAD SHX Text
U.S. DEPARTMENT OF THE INTERIOR
AutoCAD SHX Text
BUREAU OF LAND MANAGEMENT
AutoCAD SHX Text S:\ENG\Buildings&Assets\CASHE&security\BlackRock Site Visit\Standpipe\2025 BFlow Only\Attachments\parts\Vicinity Map BRock.dwg; SCOTT, THOMAS ; SCOTT, THOMAS SCOTT, THOMAS A;4/29/2025 4:18 PM;4/29/2025 4:18 PM4/29/2025 4:18 PM
AutoCAD SHX Text 1"= 4 Miles
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 93A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 95A
AutoCAD SHX Text
AutoCAD SHX Text
ELKO
AutoCAD SHX Text
IDAHO
AutoCAD SHX Text
LANDER
AutoCAD SHX Text
EUREKA
AutoCAD SHX Text
PERSHING
AutoCAD SHX Text
WASHOE
AutoCAD SHX Text
OREGON
AutoCAD SHX Text
HUMBOLDT
AutoCAD SHX Text
UTAH
AutoCAD SHX Text
ARIZONA
AutoCAD SHX Text
WHITE PINE
AutoCAD SHX Text
LINCOLN
AutoCAD SHX Text
CLARK
AutoCAD SHX Text
NYE
AutoCAD SHX Text
CALIFORNIA
AutoCAD SHX Text
MINERAL
AutoCAD SHX Text
ST
AutoCAD SHX Text
LYON
AutoCAD SHX Text
CC
AutoCAD SHX Text
DOUG
AutoCAD SHX Text
ESMERALDA
AutoCAD SHX Text
CHURCHILL
AutoCAD SHX Text
CALIFORNIA
Provided for contractor's reference and convenience. Contractor to verify all measurements and existing conditions.
AutoCAD SHX Text Gonewell Fire Control
AutoCAD SHX Text Gonewell Fire Control
AutoCAD SHX Text 3.6"
AutoCAD SHX Text
POTTER THE SYMBOL OF PROTECTION ST. LOUIS MO. MODEL NUMBER (ALL ELSE ILLEGIBLE)
AutoCAD SHX Text
ALL TEES ARE LABELED AS 1- "12"
AutoCAD SHX Text
PRESSURE GAUGE
AutoCAD SHX Text
1/2" DRAINLINE
AutoCAD SHX Text
TEST STANDARD STOC 1 IN MODEL M1000
AutoCAD SHX Text
LABELED "TEST" "OFF" "DRAIN"
AutoCAD SHX Text
FLOOR
AutoCAD SHX Text
CEILING
Owner/Agent Property BLM Black Rock Station 200 Transfer Station Rd, Gerlach, NV, 89412
BLM Black Rock Station 200 Transfer Station Rd, Gerlach, NV, 89412
Date: 01/05/2022
Inspection and Testing Report 5 Year Sprinkler System
Inspected by: Scott Summitt Start time 01/05/2022 09:46 am
Finish time 01/05/2022 09:51 am
Systems / Devices Summary Page
System / Device Quantity in the building
Quantity tested this inspection
Quantity tested this year Failed items
Wet Sprinkler 0 1 2
Butterfly Valve 0 1 2
Bell 0 1 2
Water Flow Alarm 0 1 2
Booster Pump 0 1 2 Booster pump non operational. Flowing pressure only 18psi. 57.6 at base of required per calculation sticker
Percentage of equipment tested in this inspection 100 Percentage of equipment tested so far 100
What area of the building was tested today? Entire
Tag Color? Red: Impairments found
Date and time system was restored? 01/05/2022 01:44 am
200 Transfer Station Rd, Gerlach, NV, 89412
BLM Black Rock Station 200 Transfer Station Rd, Gerlach, NV, 89412
Date: 01/05/2022
Inspection and Testing Report 5 Year Sprinkler System
Inspected by: Scott Summitt Start time 01/05/2022 09:46 am
Finish time 01/05/2022 09:51 am
This fire sprinkler report is in accordance with NFPA 25 version 2017
Monitoring Information Name of the monitoring company? : DC Specialise Phone number? : 8002867731 Account #? : A70149
System Information Flow Test Pressure
Type Location Make Model Size Static Flow Static
Wet Sprinkler #1 South center Straight Shotgun CPVC 1½" 40 18 40
Wet Sprinkler #1
Yes No N/A Frequency Description Notes
Q Was a main drain test performed? (only if the sole supply is through a backflow preventer or pressure reducing valve)
Q Are the main drain test results within 10% from previous test? 13.2.5.3 Booster pump non op
Q Were the alarm devices tested? 5.3.2.1
Q Is the hydraulic design sign attached and legible? 5.2.5
Q Location of Inspectors Test Connection? Riser
Q Was the Inspectors Test Connection or bypass opened and observed flow? 5.3.2.3
Q Did the Inspectors Test Connection trip the alarms? 5.3.2.3
Q How many seconds did it take for the Inspectors Test Connection to trip the alarms? NFPA 72-17.13.2 : 34
Status?
NFPA Questions
Yes No N/A Frequency Description Notes
Backflow
Is there a Backflow assembly or assemblies on site? 13.7.1.1
Master Pressure Regulating Device
Is there a master pressure regulating device? 13.5.4
Control Valves
W Are control valves in the correct open or closed position? 13.3.2.2
200 Transfer Station Rd, Gerlach, NV, 89412
BLM Black Rock Station 200 Transfer Station Rd, Gerlach, NV, 89412
Date: 01/05/2022
Inspection and Testing Report 5 Year Sprinkler System
Inspected by: Scott Summitt Start time 01/05/2022 09:46 am
Finish time 01/05/2022 09:51 am
NFPA Questions
Yes No N/A Frequency Description Notes
W Are the control valves sealed? 13.3.2.2
M Are the control valves locked or supervised? 13.3.2.2
M Are the control valves accessible? 13.3.2.2
M Are the control valves free of damage or leaks? 13.3.2.2
M Do the control valves have proper signage? 13.3.2.2
S Did the supervisory switches function properly? 13.3.3.5.2
A Were all control valves operated through their full range of motion and returned to normal position? 13.3.3.1
Fire Department Connections
Q Are the FDC's visible and accessible? 13.8.1
Q Do the FDC couplings/swivels operate correctly? 13.8.1
Q Are the FDC plugs/caps in place? 13.8.1
Q Are the FDC gaskets free from damage? 13.8.1
Q Are the FDC ball drip valves functional? 13.8.1
Q Are the FDC identification signs in place? 13.8.1
Q Are the FDC's interior clear of obstructions? 13.8.1
Q Do the FDC clappers operate correctly? 13.8.1
Q Are the FDC check valves free from leaks? 13.8.1
Pressure Reducing Valves
Q Are there pressure reducing valves on site? 13.5.1
Pipe and Fittings
A Are hangers and seismic bracing tight and free from damage? 10.2.3.2
A Are the pipes and fittings in good condition with no external corrosion? 10.2.3.1
A Are the pipes and fittings free of leaks and mechanical damage? 10.2.3.1
A Do pipes and fittings have correct alignment and no external loads? 10.2.3.1
200 Transfer Station Rd, Gerlach, NV, 89412
BLM Black Rock Station 200 Transfer Station Rd, Gerlach, NV, 89412
Date: 01/05/2022
Inspection and Testing Report 5 Year Sprinkler System
Inspected by: Scott Summitt Start time 01/05/2022 09:46 am
Finish time 01/05/2022 09:51 am
NFPA Questions
Yes No N/A Frequency Description Notes
A Do pipes and fittings have heat trace per manufacturer's requirements? 5.2.6
A Is wet piping free from exposure to freezing temperatures? 10.2.3.1
Sprinklers
A Are the sprinklers free from damage or leaks? 5.2.1.1.1
A Are sprinklers free of corrosion, foreign material or paint? 5.2.1.1.1
A Are sprinklers installed in proper orientation? 5.2.1.1.2
A Do sprinklers have fluid in the glass bulbs? 5.2.1.1.1
A Are proper number and type of spare sprinklers on site including an installation wrench? 5.4.1.5
A Are sprinklers free of loading? 5.2.1.1.1
A Are the escutcheons/cover plates present and installed correctly? 5.2.1.1.5
A Is there minimum clearance between sprinklers and storage? 5.2.1.2
Alarm Valves Riser Check Valves
M Are the gauges on the alarm valves/riser check valves showing normal water pressure is maintained? 13.4.1.1
Q Are the gauges in good operating condition? 13.2.7.1.1
M Are the alarm valves/riser check valves free of damage? 13.4.1.1
M Are the alarm valves/riser check valves accessible? 13.2.3
M Are the alarm valves/riser check valves retard chambers/alarm drains free from leaks? 13.4.1.1
A Was a valve status test performed? 13.3.3.4
5 Alarm valve interior was inspected including strainers,filters and restriction orifice? 13.4.3.1.5
5 Check valve internally moves freely and is in good condition? 13.4.2.1
5 Were the gauges tested or replaced? 13.2.7.2
5 Was an obstruction inspection performed? 14.2.1.1
Q Are there Antifreeze loops on site? 4.1.9.1
Pneumatic Valves
200 Transfer Station Rd, Gerlach, NV, 89412
BLM Black Rock Station 200 Transfer Station Rd, Gerlach, NV, 89412
Date: 01/05/2022
Inspection and Testing Report 5 Year Sprinkler System
Inspected by: Scott Summitt Start time 01/05/2022 09:46 am
Finish time 01/05/2022 09:51 am
NFPA Questions
Yes No N/A Frequency Description Notes
Has the 5 year obstruction teat been performed
Additional Questions
Pass Fail N/A Description Notes
Date of last 5 year inspection current
Were any adjustments, corrections or repairs made? N/A
BLM
Sign Print Scott Summitt
Sign License#
Owner/Agent Owner/Agent Inspector Inspector Inspector
WASHOE COUNTY BUILDING PERMIT FILES
10-2589
• 10-2589 MISC: Building Permit Application
• 10-2589 ECALC: Automatic Fire Sprinkler Submittals and Calculations.
• 10-2589 PLAN: Fire Sprinkler Plans
• 10-2589 PERMIT: Building Permit (Fire Sprinkler)
11-0459
• 11-0459 ECALC: Fire Alarm Submittal
• 11-0459 MISC: Building Permit Application
• 1-0459 PLAN: Fire Alarm Planset
• 11-0459 PERMIT: Building Permit
10-2589
• 10-2589 MISC: Building Permit Application
• 10-2589 ECALC: Automatic Fire Sprinkler Submittals and Calculations.
• 10-2589 PLAN: Fire Sprinkler Plans
• 10-2589 PERMIT: Building Permit (Fire Sprinkler)
11-0459
• 11-0459 ECALC: Fire Alarm Submittal
• 11-0459 MISC: Building Permit Application
• 1-0459 PLAN: Fire Alarm Planset
• 11-0459 PERMIT: Building Permit
| Sheets and Views |
| AREAMap |
| 2 20220823_StandpipeMes.pdf |
| Sheets and Views |
| Model |
| 6 WashoeCountyBuildingPermits.pdf |
| 10-2589 |
| 10-2589 MISC: Building Permit Application |
| 10-2589 ECALC: Automatic Fire Sprinkler Submittals and Calculations. |
| 10-2589 PLAN: Fire Sprinkler Plans |
| 10-2589 PERMIT: Building Permit (Fire Sprinkler) |
| 11-0459 |
| 11-0459 ECALC: Fire Alarm Submittal |
| 11-0459 MISC: Building Permit Application |
| 1-0459 PLAN: Fire Alarm Planset |
| 11-0459 PERMIT: Building Permit |
| 10-2589 MISC: Building Permit Application |
| 10-2589 ECALC: Automatic Fire Sprinkler Submittals and Calculations. |
| 10-2589 PLAN: Fire Sprinkler Plans |
| 10-2589 PERMIT: Building Permit (Fire Sprinkler) |
| 11-0459 ECALC: Fire Alarm Submittal |
| 11-0459 MISC: Building Permit Application |
| 1-0459 PLAN: Fire Alarm Planset |
| 11-0459 PERMIT: Building Permit |
File details come from the government source that posted it. Updated .