A06-DrawingsFINAL.pdf
PDF 6 MB Posted
- Attached to
- WI FWS TREMPEALEAU NWR GARAGE ADDITION
- Solicitation number
- 140F0222R0024
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Attachment__1Trempealeau_0005.pdf | ||
| Sol_140F0222R0024_Amd_0005.pdf | ||
| Attachment__3Trempealeau_0005.pdf | ||
| Attachment__2_(1)Trempealeau_0005.pdf | ||
| Sol_140F0222R0024_Amd_0004.pdf | ||
| Sol_140F0222R0024_Amd_0003.pdf | ||
| Sol_140F0222R0024_Amd_0002.pdf | ||
| Sol_140F0222R0024_Amd_0001.pdf | ||
| Safety_Checklist.pdf | ||
| A04-Specs_FINAL.pdf | ||
| B03-WageDetermination.pdf | ||
| 17-RF-007_Bid_Schedule.pdf | ||
| BidBond__Form_SF24.pdf | ||
| Sol_140F0222R0024.pdf | ||
| PPQ.docx | DOCX document | |
| CPARS_Notice.pdf |
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BDD
S
F/S
M
EXHAUST AIR INLET
RETURN AIR INLET
SUPPLY AIR OUTLET
BACK DRAFT DAMPER
MOTORIZED DAMPER
SMOKE DAMPER
MANUAL/VOLUME DAMPER
VERTICAL FIRE DAMPER
FIRE/SMOKE DAMPER
CFM-TYPE
AIRSIDE SYMBOLS
RECTANGLE TO ROUND
TRANSITION
STRAIGHT TAP
45° ENTRY TAP
HIGH EFFICIENCY
TAP, RECTANGLE
TO ROUND
SUPPLY DUCT TOWARD VIEWER
SUPPLY DUCT AWAY FROM VIEWER
RETURN DUCT TOWARD VIEWER
RETURN DUCT AWAY FROM VIEWER
EXHAUST DUCT TOWARD VIEWER
EXHAUST DUCT AWAY FROM VIEWER
CHANGE IN DUCT ELEVATION -
RISE INDICATED BY "R"
R
CHANGE IN DUCT ELEVATION -
DROP INDICATED BY "D"
D
FLEXIBLE CONNECTION
FC
DUCT LINING
OVAL SPIRAL DUCT
(WIDTH/HEIGHT IN INCHES)
ROUND SPIRAL DUCT
(DIAMETER IN INCHES)
RECTANGULAR DUCT
(WIDTHxHEIGHT IN INCHES)
12/10
12Ø
12x10
SIDEWALL DIFFUSER
SIDEWALL GRILLE
TRANSFER GRILLES
UNDERCUT DOOR (H=CLEARANCE)
UC, H
SIZE
AIR INLET/OUTLET TAG
RA
S
THERMOSTAT WITH
LOCKING SECURITY
COVER
HUMIDISTAT
THERMOSTAT REVERSE ACTING
THERMOSTAT
CONTROL SYMBOLS
XXX
TEMPERATURE SENSOR
HUMIDITY SENSOR
SENSOR (OTHER)
(REFER TO GEN ABBREV
FOR SENSOR TYPE)
T
T
T
H
H
T
S
EQUIPMENT ABBREVIATIONS
ACC AIR COOLED CONDENSER
ACCU AIR COOLING CONDENSING
UNIT
ACP AIR COMPRESSOR
AF AIR FILTER
AFMS AIR FLOW MEASURING
STATION
AHU AIR HANDLING UNIT
AS AIR SEPARATOR
B BOILER
CC COOLING COIL
CF CABINET FAN
CF CHEMICAL FEEDER
CFP CHEMICAL FEED PUMP
CH CHILLER
CP CONDENSATE PUMP
CRAC COMPUTER ROOM AIR
CONDITIONER
CRU CONDENSATE RETURN UNIT
CSG CLEAN STEAM GENERATOR
CT COOLING TOWER
CUH CABINET UNIT HEATER
CWP CONDENSER WATER PUMP
DBP DOMESTIC WATER BOOSTER
PUMP
EAV EXHAUST AIR VALVE
EF EXHAUST FAN
ERU ENERGY RECOVERY UNIT
ET EXPANSION TANK
FCU FAN COIL UNIT
FP FIRE PUMP
FUR FURNACE
GEN GENERATOR
HUM HUMIDIFIER
HC HEATING COIL
HRU HEAT RECOVERY UNIT
HTR HEATER
HX HEAT EXCHANGE
HPU HEAT PUMP UNIT
OBD OPPOSED BLADE DAMPER
OWS OIL WATER SEPARATOR
P PUMP
PRV POWER ROOF VENTILATOR
RF RETURN FAN
RHC REHEAT COIL
RMB RADIANT MIXING BLOCK
RTU ROOF TOP UNIT
SAT SOUND ATTENUATOR
SEP SEWAGE EJECTOR PUMP
SF SUPPLY FAN
TMV THERMOSTATIC MIXING
VALVE
UH UNIT HEATER
US UTILITY SET
UV UNIT VENTILATOR
VAV VARIABLE AIR VOLUME BOX
WF WATER FILTER
WFMS WATER FLOW MEASURING
STATION
WH WATER HEATER
WHD WALL HYDRANT
FIXTURE ABBREVIATIONS
BT BATH TUB
CO CLEAN OUT
DF DRINKING FOUNTAIN
DISP GARBAGE DISPOSAL
DW DISHWASHER CONNECTION
EWC ELECTRIC WATER COOLER
EWS EMERGENCY EYE
WASH/SHOWER
EW EYE WASH
FD FLOOR DRAIN
HB HOSE BIB
HY HYDRANT
LT LAUNDRY TUB
LV LAVATORY
MB MOP BASIN
OB WASHING MACHINE
OUTLET BOX
SH SHOWER
SK SINK
SS SERVICE SINK
TD TRENCH DRAIN
UR URINAL
WB WASH BASIN
WC WATER CLOSET
WCO WALL CLEAN OUT
WHD WALL HYDRANT
MECHANICAL SHEET INDEX
PLUMBING AND PIPING SYMBOLS
CA
3" FD
A
M
DOMESTIC COLD WATER
RPZ BACK FLOW PREVENTER
FLOOR DRAIN
(SIZE AS INDICATED)
FIN-TUBE RADIATION ELEMENT
HOSE BIB OR WALL HYDRANT
AUTO AIR VENT
RELIEF VALVE
MANUAL AIR VENT
DROP IN PIPE
RISE IN PIPE
PIPE CONNECTION
FLOW DIRECTION ARROW
METER
PRESSURE REDUCING VALVE
PRESSURE GAUGE
TRIPLE DUTY VALVE
UNION
STRAINER
SHUT-OFF VALVE
TWO-WAY CONTROL VALVE
THREE-WAY CONTROL VALVE
CHECK VALVE
CIRCUIT BALANCING VALVE
PUMP
OR
THERMOMETER
DOMESTIC HOT WATER
COMPRESSED AIR
CWR
CONDENSER WATER RETURN
CWS
CONDENSER WATER SUPPLY
D
INDIRECT DRAIN
GAS
GAS
GR
GLYCOL RETURN
GS
GLYCOL SUPPLY
HPWR
HEAT PUMP WATER RETURN
HPWS
HEAT PUMP WATER SUPPLY
HRR
HEAT RECOVERY WATER RETURN
HRS
HEAT RECOVERY WATER SUPPLY
HWR
HEATING WATER RETURN
HWS
HEATING WATER SUPPLY
LPC
LOW PRESSURE STEAM CONDENSATE
LPG
LIQUID PETROLEUM GAS
LPS
LOW PRESSURE STEAM
MPC
MEDIUM PRESSURE STEAM
CONDENSATE
MPS
MEDIUM PRESSURE STEAM
N2
NITROGEN
NG
NATURAL GAS
N2O
NITROUS OXIDE
NPW
NON-POTABLE WATER
OVFL
OVERFLOW STORM DRAIN
OW
OIL WASTE
PC
PUMPED CONDENSATE
RD
REFRIGERANT DISCHARGE (HOT GAS)
RL
REFRIGERANT LIQUID
RS
REFRIGERANT SUCTION
SW
SOFTENED WATER
SD
STORM DRAIN
SDBS
STORM DRAIN, BELOW SLAB
TWR
TEMPERED WATER RETURN
TWS
TEMPERED WATER SUPPLY
WAGD
WASTE ANESTHETIC GAS DISPOSAL
VENT
WASTE/SANITARY
WASTE/SANITARY, BELOW SLAB
WASTE CONDENSATE (COLD COND.)
WC
MED VAC
MEDICAL VACUUM
MED AIR
MEDICAL AIR
V
W
WBS
CW
HW
GENERAL SYMBOLS
Y.Z
X
NUMBER OF SHEET WHERE
DETAIL APPEARS.
NO. OF DETAIL
REVISION NUMBER, SHOWN
ON PLAN
TIE IN POINT
KEYED NOTE
GENERAL MECHANICAL NOTES
1. REFER TO "DIVISION 1 - GENERAL REQUIREMENTS" IN THE
PROJECT MANUAL FOR WORK THAT IS THE RESPONSIBILITY
OF ALL CONTRACTORS.
2. IT IS THE RESPONSIBILITY OF THE MECHANICAL
CONTRACTORS TO COORDINATE THE WORK OF THEIR
TRADE WITH ALL OTHER TRADES PRIOR TO PROCEEDING
WITH THEIR WORK. ANY WORK REQUIRING REMOVAL AND
REINSTALLATION DUE TO LACK OF COORDINATION SHALL BE
THE RESPONSIBILITY OF THE CONTRACTORS.
3. PRIOR TO PERFORMING WORK REQUIRED, INSPECT ALL
EXISTING CONDITIONS AND INSTALLED WORK OF OTHER
TRADES AND VERIFY THAT ALL CONDITIONS AND ALL SUCH
WORK IS COMPLETE TO THE POINT WHERE MECHANICAL
WORK CAN PROPERLY COMMENCE.
4. PERFORM CUTTING, FITTING, AND PATCHING OF MECHANICAL
EQUIPMENT AND MATERIALS REQUIRED TO REMOVE
EXISTING WORK AND TO INSTALL EQUIPMENT AND
MATERIALS IN EXISTING STRUCTURES.
5. PROTECT NEW WORK AND EXISTING WORK TO REMAIN.
6. THE CONTRACTOR IS REQUIRED TO FIELD VERIFY
LOCATIONS OF EXISTING WORK TO REMAIN.
7. ALL EQUIPMENT SHALL BE INSTALLED TRUE, LEVEL, AND IN THE
LOCATION SHOWN ON THE DRAWINGS.
8. ALL EQUIPMENT SHALL BE INSTALLED IN A MANNER THAT
PROVIDES ADEQUATE MAINTENANCE ACCESS.
9. PROTECT EQUIPMENT AND MATERIALS FROM THE
WEATHER AND CONSTRUCTION DUST DURING
CONSTRUCTION AND LEAVE ALL EQUIPMENT AND DUCT
INTERIORS CLEAN.
10. INSTALL DUCT AND PIPING AS HIGH AS POSSIBLE WITHIN THE
ROOMS THAT THEY ARE SHOWN UNLESS OTHERWISE NOTED.
GENERAL ABBREVIATIONS
DB
ELEC
EXH
EX
F or °F
ELEV
EQUIP
EWT
DN
DWG
EA
EAT
EL
DIA
DISCH
COORD
CTR
CUFT
CV
CW
CONTR
COND
CONN
CONST
CONT
CI
CLG
CLG
CO
CFM
CHW
BTUH
CAP
CB
BTU
AUTO
BLDG
BOT
APPROX
ARCH
ALT
ALUM
AP
AFF
AG
AC
Ø
A
TEMPERATURE
POUNDS PER SQUARE INCH GAUGE
HEATING, VENTILATION,
AIR CONDITIONING
GALLONS PER MINUTE
NORMALLY CLOSED
NOT IN CONTRACT
ONE THOUSAND CUBIC FEET
MOTORIZED DAMPER
LEAVING AIR TEMPERATURE
LIQUEFIED PETROLEUM GAS
LEAVING WATER TEMPERATURE
POUNDS PER HOUR
INCHES WATER GAUGE
ONE THOUSAND BTU PER HOUR
DRY BULB
LVR LOUVER
ELECTRICAL
ENTERING WATER TEMPERATURE
EXHAUST AIR
DEGREES FAHRENHEIT
EXISTING
ELEVATION
EQUIPMENT
ENTERING AIR TEMPERATURE
DOWN
DRAWING
EACH
ELBOW
DIAMETER
DISCHARGE
MH MANHOLE
NC
NIC
NO
NOM
MIN
MISC
MTR
MUA
NC
NORMALLY OPEN
NOMINAL
MISCELLANEOUS
MAKE-UP AIR
NOISE CRITERIA
MINIMUM
MOTOR
MAX
MFR
MCF
MD
MECH
LWT
MAN
MATL
M/A
MAXIMUM
MANUFACTURER
MECHANICAL
MANUAL
MATERIAL
MIXED AIR
CONTINUE, CONTINUATION
COORDINATE
CHECK VALVE
DOMESTIC COLD WATER
DEGREE
CENTER
CUBIC FEET
CONDENSATE
CONSTRUCT
CONTRACTOR
CONNECT
BRITISH THERMAL UNITS PER HOUR
DOMESTIC CIRCULATING HOT
CUBIC FEET PER MINUTE
CAST IRON
CEILING
COOLING
CLEAN OUT
CATCH BASIN
CAPACITY
LB/HR
LPG
LAT
LF
INV
LB
INWG
KBTU
LINEAL FEET
INVERT
POUND
HW
IN
INSUL
HTG
HVAC
HD
HORZ
HP
GPM
DOMESTIC HOT WATER
INSULATION
HEATING
INCH/INCHES
HEAD
HORIZONTAL
HORSE POWER
SQ SQUARE
VENT
VERT
TEMP
TSP
STRUCT
SUSP
TYP
WB
VOL
VTR
W
VEL
UG
V
TCP
TEFC
SS
STD
TYPICAL
VELOCITY
WET BULB
VENTILATION
VENT THROUGH ROOF
VERTICAL
UNDERGROUND
VOLUME
WASTE
VENT
TEMPERATURE CONTROL PANEL
TOTAL STATIC PRESSURE
STRUCTURAL
SUSPENDED
TOTALLY ENCLOSED FAN COOLED
STAINLESS STEEL
STANDARD
SECT
SPEC
REQD
SA
SHT
SP
SPS
SIM
SLV
SF
SD
SAN
RM
RPM
RH
RLA
RED
REC
RD
RA
RCP
SUPPLY AIR
STATIC PRESSURE STATION
STATIC PRESSURE
SPECIFICATION
SQUARE FEET
SMOKE DAMPER
SANITARY
SHEET
SIMILAR
SLEEVE
SECTION
REVOLUTIONS PER MINUTE
RELATIVE HUMIDITY
RECESSED
REQUIRED
RELIEF AIR
RADIANT CEILING PANEL
RETURN AIR
ROOF DRAIN
ROOM
REDUCER
FIBERGLASS REINFORCED PIPE
GENERAL CONTRACTOR
GALLONS PER HOUR
FUEL OIL SUPPLY
FEET PER MINUTE
FIN TUBE RADIATION
BRITISH THERMAL UNITS
ARCHITECT/ARCHITECTURAL
AUTOMATIC
BUILDING
BOTTOM
ACCESS PANEL
APPROXIMATE
ALTERNATE
ALUMINUM
ABOVE FINISHED FLOOR
ABOVE GROUND
AIR CONDITIONING
DIAMETER
AIR
GAL
GALV
GC
GPH
FTR
GA
FPM
FRP
FT
FTG
FOS
GALLON
GALVANIZED
GAUGE
FOOT (FEET)
FOOTING
FLEX FLEXIBLE
PRESS
PLBG
PSI
PSIG
PWR
PRV
PIV
PD
ORD
OXY
OC
OA
OF
NTS
POST INDICATOR VALVE
PRESSURE REDUCING VALVE
POUNDS PER SQUARE INCH
PLUMBING
PRESSURE
OVERFLOW ROOF DRAIN
PRESSURE DROP
POWER
OUTSIDE AIR
ON CENTER
OVERFLOW
NOT TO SCALE
OXYGEN
AD ACCESS DOOR
BOD BOTTOM OF DUCT
CAV CONSTANT AIR VOLUME
CO CARBON MONOXIDE
CO2 CARBON DIOXIDE
DAT DISCHARGE AIR TEMPERATURE
DIM DIMENSION
ESP EXTERNAL STATIC PRESSURE
FA FRESH AIR
FOB FLAT ON BOTTOM
FOT FLAT ON TOP
HHW HEATING HOT WATER
MAD MIXED AIR DAMPER
MAT MIXED AIR TEMPERATURE
MBH ONE THOUSAND BTU PER HOUR
MMBH ONE MILLION BTU PER HOUR
OAD
OUTSIDE AIR DAMPER
OAT
OUTSIDE AIR TEMPERATURE
PG
PROPYLENE GLYCOL
PRS
RAD RETURN AIR DAMPER
RAT RETURN AIR TEMPERATURE
RECT RECTANGULAR
RLD
RND ROUND
RELIEF AIR DAMPER
SRV
SAFETY RELIEF VALVE
VFD VARIABLE FREQUENCY DRIVE
RPZ REDUCED PRESSURE ZONE
WC WATER COLUMN
PRESSURE REDUCING STATION
APD AIR PRESSURE DROP
WCO WALL CLEAN OUT
WPD WATER PRESSURE DROP
INTEGRATED PART LOAD VALUEIPLV
NPLV NOMINAL PART LOAD VALUE
WATER
F
IN
A L P
LO
T
D R A W
IN
G
S
TA
TU
S
P
LO
T D A
TE
P R O
JE
C T
LO
C A
TI
O N
D W G
N A M E
TREMPEALEAU COUNTY WISCONSIN
17-RF-007
05/22 AJM
3R-WI-162- 33
TREMPEALEAU NATIONAL WILDLIFE REFUGE
ADDITION TO 3 STALL GARAGE
REVISION DATE DESCRIPTION BY
DESIGNED DRAWN: DATE: CHECKED:
SHEET_____OF_____DRAWING NO:CADD:
PROJECT NUMBER
TPL .DWG
GENERAL DRAWING NOTE:
THE U.S. FISH AND WILDLIFE SERVICE, REGION 3 CADD DRAWINGS
ARE DRAWN ON A 22" X 34" STANDARD "D" SIZE SHEET (FULL
SIZE) 100%. WHEN PLOTTING DRAWINGS AT DIFFERENT
PERCENTAGES BAR SCALES ON DRAWINGS SHALL BE USED FOR
MEASURING.
B I M
U S F W
T r e m p e a l e a u
M a i n t
G a r a g e
A d d i t i o n
F W S
T r e m p e a u l e a u
M E P
C e n t r a l r v t
A M
AWLSDC
M1
MECHANICAL SYMBOLS AND ABBREVIATIONS
C h e c k e r
M1 16116 116
1-1/2" CW
FROM WELL
1-1/2" CW UP
LPG FROM TANK,
REFER TO
DETAIL 2/M5
1" LPG UP
4" W TO
SEPTIC
SYSTEM
UP TO CO
2" W UP TO MB-1
2" W/V UP TO LV-1
4" W
UP TO CO
4" W
2" W UP
TO EW-1
2" V UP
4" W UP
TO WC-1
4" W
2" W UP
TO UR-1
2" W UP
TO FD-2
2" W UP
TO SH-1
1-1/2"
V UP
2" W UP
TO OB-1
3" W UP
4" W
UP TO CO
2" W UP TO SK-1
2" W UP
TO FD-1
1-1/2" V UP
UP TO CO
P F
VEHICLE
MAINTENANCE
OFFICE
RESTROOM
MECH
SH-1
UR-1
WC-1
LV-1
FD-2
EW-1
MB-1
FD-1
OB-1
1" CW & HW
UP TO WH-1
1/2" CW & HW,
1-1/2" V DN
3/4" CW &
HW DN
CO
CO
1-1/2" CW DN
3/4" CW & HW,
1-1/2" V DN
1/2" HW DN
1/2" CW,
(2) 1-1/2" V DN
1-1/2"
V DN
CO
SK-1
CO
3" W DN,
2" V UP
3" W UP
TO FD-3
WCO
HB-1
HB-1
HB-2
SHUTOFF VALVE
ON RISER
SHUTOFF VALVE
ON RISER
1-1/2"
V DN
1-1/2" V
1/2" CW
1/2" CW
1-1/2" V DN
1/2" CW, 2" V DN
1/2" CW & HW,
1-1/2" V DN
3/4" CA TO OWNER
PROVIDED AIR
COMPRESSOR
CA HOSE REEL
1" LPG DN
1" LPG UP
TMV IN CABINET
FOR EW-1
CO
SH-1
SK-1
FD-2
UR-1
FD-1
CO
EW-1
CO
WC-1
MB-1
LV-1
CO
OB-1
FD-3
WCO
2" V
4" VTR
3" W
(6 DFU)
3" W
(6 DFU)
2" W
(2 DFU)
3" W
(8 DFU)
2" W
(2 DFU)
2" W
(4 DFU)
2" W
(2 DFU)
3" W
(4 DFU)
3" W
(6 DFU)
3" W
(12 DFU)
2" W
(2 DFU)
4" W
(22 DFU)
2" W
(2 DFU)
3" W
(6 DFU)
2" W
(1 DFU)
3" W
(7 DFU)
2" W
(2 DFU)
4" W
(29 DFU)
4" W
(33 DFU)
1-1/2" V
1-1/2" V
1-1/2" V
1-1/2" V
1-1/2" V
2" V
2" V
2" V
1-1/2" V
2" V
1-1/2" V
P
3/4" BALL
VALVE (TYP)
T HANDLE REGULATOR
WITH GAUGE
3/8" QUICK
CONNECT
SOCKET
HOSE REEL
CA MAIN
FILTER
F
IN
A L P
LO
T
D R A W
IN
G
S
TA
TU
S
P
LO
T D A
TE
P R O
JE
C T
LO
C A
TI
O N
D W G
N A M E
TREMPEALEAU COUNTY WISCONSIN
17-RF-007
05/22 AJM
3R-WI-162- 33
TREMPEALEAU NATIONAL WILDLIFE REFUGE
ADDITION TO 3 STALL GARAGE
REVISION DATE DESCRIPTION BY
DESIGNED DRAWN: DATE: CHECKED:
SHEET_____OF_____DRAWING NO:CADD:
PROJECT NUMBER
TPL .DWG
GENERAL DRAWING NOTE:
THE U.S. FISH AND WILDLIFE SERVICE, REGION 3 CADD DRAWINGS
ARE DRAWN ON A 22" X 34" STANDARD "D" SIZE SHEET (FULL
SIZE) 100%. WHEN PLOTTING DRAWINGS AT DIFFERENT
PERCENTAGES BAR SCALES ON DRAWINGS SHALL BE USED FOR
MEASURING.
B I M
U S F W
T r e m p e a l e a u
M a i n t
G a r a g e
A d d i t i o n
F W S
T r e m p e a u l e a u
M E P
C e n t r a l r v t
A M
AWLSDC
M2
PLUMBING PLANS AND WASTE RISER
C h e c k e r
M2
SCALE:
1/4" = 1'-0"
M2
1 UNDERSLAB PLUMBING PLAN
SCALE:
1/4" = 1'-0"
M2
2 LEVEL 1 PLUMBING PLAN
1 0 4 8 12
SCALE: 1/4" = 1'-0"
SCALE: NO SCALE
M2
3 SANITARY RISER DIAGRAM
SCALE:
NO SCALE
M2
4 COMPRESSED AIR OUTLET DETAIL
17117 117
WH-1
1" CW &
HW DN
WH-1 COMBUSTION AIR
AND EXHAUST
FD-3
WS-1
1" LPG DN
3/4" LPG
KEYED SHEET NOTES
INSTALL WATER HEATER ON A 6" HIGH
SUPPORT STAND FABRICATED FROM
GALVANIZED OR CADMIUM PLATED
CHANNELS OR ANGLES. PROVIDE A
30x30X2 INCH DEEP STAINLESS STEEL
DRAIN PAN BENEATH THE WATER
HEATER AND STAND WITH A 3/4" OUTLET
PIPED TO THE FLOOR DRAIN. PIPE THE
RELIEF VALVE TO THE FLOOR DRAIN
FUNNEL. PIPE EXHAUST CONDENSATE
TO FD-3.
PIPE WS-1 DISCHARGE TO FD-3 FUNNEL.
2" V DN AND UP, TRANSITION TO
4" V PRIOR TO PENETRATING ROOF
HB-1
OB-1
WH-1
WS-1
UR-1
SH-1
HB-2
WC-1
EW-1
TMV
MB-1
LV-1
SK-1
HB-1
1/2" CW
(5 FU)
1/2" CW & HW
(2 FU EA)
3/4" CW & HW
(6 FU EA)
3/4" CW
(7 FU)
3/4" CW
(13 FU)
1/2" CW
(4 FU)
1/2" HW
(5 FU)
1/2" CW & HW
(4 FU EA)
1" CW
(21 FU)
1" HW
(15 FU)
3/4" CW & HW
(4 FU EA)
1" CW
(25 FU)
1" HW
(21 FU)
1/2" CW
(4 FU)
1-1/4" CW
(29 FU)
1/2" CW
(5 FU)
1/2" CW & HW
(4 FU EA)
1" CW & HW
(25 FU EA)
1" CW
(29 FU)
1-1/4" CW
(34 FU)
1-1/2" CW
(63 FU)
1" HW
(17 FU)
F
IN
A L P
LO
T
D R A W
IN
G
S
TA
TU
S
P
LO
T D A
TE
P R O
JE
C T
LO
C A
TI
O N
D W G
N A M E
TREMPEALEAU COUNTY WISCONSIN
17-RF-007
05/22 AJM
3R-WI-162- 33
TREMPEALEAU NATIONAL WILDLIFE REFUGE
ADDITION TO 3 STALL GARAGE
REVISION DATE DESCRIPTION BY
DESIGNED DRAWN: DATE: CHECKED:
SHEET_____OF_____DRAWING NO:CADD:
PROJECT NUMBER
TPL .DWG
GENERAL DRAWING NOTE:
THE U.S. FISH AND WILDLIFE SERVICE, REGION 3 CADD DRAWINGS
ARE DRAWN ON A 22" X 34" STANDARD "D" SIZE SHEET (FULL
SIZE) 100%. WHEN PLOTTING DRAWINGS AT DIFFERENT
PERCENTAGES BAR SCALES ON DRAWINGS SHALL BE USED FOR
MEASURING.
B I M
U S F W
T r e m p e a l e a u
M a i n t
G a r a g e
A d d i t i o n
F W S
T r e m p e a u l e a u
M E P
C e n t r a l r v t
A M
AWLSDC
M3
MEZZANINE PLUMBING PLAN, PLUMBING SCHEDULES, WATER RISER
C h e c k e r
M3 1 0 4 8 12
SCALE: 1/4" = 1'-0"
SCALE:
1/4" = 1'-0"
M3
1 MEZZANINE LEVEL PLUMBING PLAN
WATER HEATER (GAS) SCHEDULE
UNIT NO. MANUFACTURER MODEL LOCATION
STORAGE
CAPACITY
WATER
STORAGE TEMP.
WATER
DISCHARGE TEMP.
TEMP.
RISE
RECOVERY
RATE
INPUT
MBH
EFFICIENCY
ELECTRICAL REQUIREMENTS
NOTESVOLTAGE PHASE AMPS
WH-1 A.O. SMITH BTX 100 200 50 GAL. 120 °F 120 °F 100 °f 116 gph 100 96 120 V 1 5 1
PLUMBING FIXTURE SCHEDULE
UNIT NO. DESCRIPTION
DOMESTIC WATER SANITARY
NOTES
COLD WATER HOT WATER
DFU
DRAIN
SIZE
VENT SIZEFU SIZE FU SIZE
EW-1 WALL MOUNTED EYEWASH 4 1/2" 4 1/2" 2 2" 1 1/2"
FD-1 2" FLOOR DRAIN 0 0" 0 0" 2 2" 1 1/2"
FD-2 LINEAR SHOWER DRAIN 0 0" 0 0" 2 2" 1 1/2"
FD-3 3" FLOOR DRAIN W/ FUNNEL 0 0" 0 0" 6 3" 2" 7" GRATE W/ 4" ROUND FUNNEL
HB-1 HOSE BIBB 5 1/2" 0 0" 0 0" 0"
HB-2 HOT WATER HOSE BIBB 0 0" 5 1/2" 0 0" 0"
LV-1 LAVATORY 2 1/2" 2 1/2" 1 2" 1 1/2"
MB-1 MOP BASIN (36x24) 4 3/4" 4 3/4" 6 3" 2"
OB-1 WASHING MACHINE OUTLET BOX 4 1/2" 4 1/2" 2 2" 1 1/2"
SH-1 SHOWER 4 3/4" 4 3/4" 2 2" 1 1/2"
SK-1 SINK 2 1/2" 2 1/2" 2 2" 1 1/2"
UR-1 URINAL 4 1/2" 0 0" 4 2" 1 1/2"
WC-1 FLOOR MOUNTED TANK TOILET 4 1/2" 0 0" 4 3" 2"
WATER SOFTENER SCHEDULE
UNIT NO. MANUFACTURER MODEL LOCATION
OPERATING
RANGE BRINE TANK RESIN TANK NOTES
WS-1 CULLIGAN 12" AQUA SENSOR 200 10 GPM @ 10 PSI 18" DIA. x 43" TALL 12" DIA. x 52" TALL PROVIDE WITH 120V TO 24V TRANSFORMER, 21.6 WATTS
NOTES:
1. PROPANE FIRED, CONCENTRIC VENT KIT, CONDENSATE NEUTRALIZATION KIT, 8.00" MINIMUM GAS PRESSURE
SCALE:
NO SCALE
M3
2 DOMESTIC WATER RISER DIAGRAM
18118 118
M
MECH
VEHICLE
MAINTENANCE
RESTROOM
OFFICE
UH-1
CO
NO2
L-1
EF-1
10x24 EXHAUST
DN TO 12" A.F.F.
8Ø SUPPLY
UP TO ERV-1
75-A
75-B
6ø ø
FCU-1
FCU-2
ROUTE CONDENSATE
FROM FCU-1 & FCU-2
TO MOP SINK
8Ø EXH UP
TO ERV-1
ø
150-C
DRYER
EXHAUST
HOOD
4ø
4Ø COMBUSTION AIR
AND EXHAUST HOODS
x
BOTTOM OF LOUVER
AND MOTORIZED
DAMPER AT 8'-0" A.F.F.
(2) 1/4" RL & (2) 3/8" RS
LINESETS FROM ACCU-1
TO FCU-1 & FCU-2
(2) 1/4" RL &
(2) 3/8" RS UP
ERV-1
8Ø SUPPLY DN
8Ø OA
INTAKE
8Ø RELIEF
ACCU-1
MEZZANINE
8Ø EXH DN
EF-2
TO L-1
(2) 1/4" RL
& (2) 3/8" RS DN
F
IN
A L P
LO
T
D R A W
IN
G
S
TA
TU
S
P
LO
T D A
TE
P R O
JE
C T
LO
C A
TI
O N
D W G
N A M E
TREMPEALEAU COUNTY WISCONSIN
17-RF-007
05/22 AJM
3R-WI-162- 33
TREMPEALEAU NATIONAL WILDLIFE REFUGE
ADDITION TO 3 STALL GARAGE
REVISION DATE DESCRIPTION BY
DESIGNED DRAWN: DATE: CHECKED:
SHEET_____OF_____DRAWING NO:CADD:
PROJECT NUMBER
TPL .DWG
GENERAL DRAWING NOTE:
THE U.S. FISH AND WILDLIFE SERVICE, REGION 3 CADD DRAWINGS
ARE DRAWN ON A 22" X 34" STANDARD "D" SIZE SHEET (FULL
SIZE) 100%. WHEN PLOTTING DRAWINGS AT DIFFERENT
PERCENTAGES BAR SCALES ON DRAWINGS SHALL BE USED FOR
MEASURING.
B I M
U S F W
T r e m p e a l e a u
M a i n t
G a r a g e
A d d i t i o n
F W S
T r e m p e a u l e a u
M E P
C e n t r a l r v t
A M
AWLSDC
M4
VENTILATION PLANS
C h e c k e r
M4
SCALE: 1/4" = 1'-0"
M4
1 LEVEL 1 VENTILATION PLAN
SCALE: 1/4" = 1'-0"
M4
2 MEZZANINE LEVEL VENTILATION PLAN
1 0 4 8 12
SCALE: 1/4" = 1'-0"
19119 119
GRADE
ANODE-LESS RISER
BELOW GRADE PE PIPE
EXTERIOR WALL
1 INCH STEEL LPG
@ 11" WC
REGULATOR
300 MBH
1 INCH STEEL
2 PSI LPG
HW CW
TMV
W
V
F
IN
A L P
LO
T
D R A W
IN
G
S
TA
TU
S
P
LO
T D A
TE
P R O
JE
C T
LO
C A
TI
O N
D W G
N A M E
TREMPEALEAU COUNTY WISCONSIN
17-RF-007
05/22 AJM
3R-WI-162- 33
TREMPEALEAU NATIONAL WILDLIFE REFUGE
ADDITION TO 3 STALL GARAGE
REVISION DATE DESCRIPTION BY
DESIGNED DRAWN: DATE: CHECKED:
SHEET_____OF_____DRAWING NO:CADD:
PROJECT NUMBER
TPL .DWG
GENERAL DRAWING NOTE:
THE U.S. FISH AND WILDLIFE SERVICE, REGION 3 CADD DRAWINGS
ARE DRAWN ON A 22" X 34" STANDARD "D" SIZE SHEET (FULL
SIZE) 100%. WHEN PLOTTING DRAWINGS AT DIFFERENT
PERCENTAGES BAR SCALES ON DRAWINGS SHALL BE USED FOR
MEASURING.
B I M
U S F W
T r e m p e a l e a u
M a i n t
G a r a g e
A d d i t i o n
F W S
T r e m p e a u l e a u
M E P
C e n t r a l r v t
A M
AWLSDC
M5
MECHANICAL SCHEDULES, DETAILS, & SITE PLAN
C h e c k e r
M5
FAN SCHEDULE
UNIT NO. MANUFACTURER MODEL LOCATION SERVES DUTY CFM
TSP (IN.
OF W.C.)
FAN RPM FINISH WEIGHT VIB. ISO.
ELECTRICAL REQUIREMENTS
NOTESFLA OPERATING POWER HP VOLTAGE PHASE
EF-1 GREENHECK CUE-121-A SIDEWALL VEHICLE MAINTENANCE 101 GENERAL EXHAUST 1500 CFM 0.25 1393 ALUMINUM 67 SHOCK MOUNTS 0.21 1/2 120 V 1 1
EF-2 GREENHECK CUE-095-G SIDEWALL VEHICLE MAINTENANCE 101 GENERAL EXHAUST 555 CFM 0.31 1300 ALUMINUM 40 SHOCK MOUNTS 0.07 1/12 120 V 1 2
NOTES:
1. PSC MOTOR, NEMA-1 TOGGLE SWITCH, MOUNTED AND WIRED JUNCTION BOX, BD-330-PB-12X12 DAMPER, SOLID STATE SPEED CONTROL, ALUMINUM BIRDSCREEN
2. NEMA-1 TOGGLE SWITCH, MOUNTED AND WIRED JUNCTION BOX, GRAVITY BACKDRAFT DAMPER, ALUMINUM BIRDSCREEN. ALUMINUM CURB FOR WALL MOUNTING
LOUVER SCHEDULE
UNIT NO. SERVES CFM WIDTH HEIGHT
FREE AREA
(SQ. FT.)
MAX. FREE
AREA VELOCITY
APD (IN.
OF W.C.) NOTES
L-1 VEHICLE MAINTENANCE 101 1500 CFM 2' - 7" 4' - 9" 4.26 345 FPM 0.01 1
AIR TO AIR HEAT EXCHANGER SCHEDULE
UNIT NO. MANUFACTURER MODEL LOCATION CFM
ESP (IN OF W.C.) SUMMER CONDITIONS WINTER CONDITIONS ELECTRICAL REQUIREMENTS
SUPPLY AIR EXHAUST AIR
OUTDOOR AIR ROOM AIR FRESH AIR OUTDOOR AIR ROOM AIR FRESH AIR
VOLTAGE PHASE MCADB WB DB WB DB WB DB WB DB WB DB WB
ERV-1 RENEWAIRE EV200 200 150 CFM 0.35 0.35 87 °F 72 °F 75 °F 63 °F 78 °F 67 °F -17 °F -18 °F 70 °F 49 °F 52 °F 38 °F 120 V 1 10
SPLIT AC SYSTEM FAN COIL UNIT SCHEDULE
UNIT NO. MANUFACTURER MODEL LOCATION SERVES TYPE
CAPACITY ELECTRICAL REQUIREMENTS
NOTES
COOLING
MBH
HEATING
MBH
VOLTAGE PHASE MCA
FCU-1 FUJITSU ASU7RLF1 102 OFFICE 102 HIGH WALL 7 7 240 V 1
FCU-2 FUJITSU ASU7RLF1 103 RESTROOM 103 HIGH WALL 7 7 240 V 1
SPLIT AC SYSTEM AIR COOLED CONDENSING UNIT SCHEDULE
UNIT NO. MANUFACTURER MODEL LOCATION REFRIGERANT
CAPACITIES ELECTRICAL REQUIREMENTS
NOTES
COOLING HEATING
VOLTAGE PHASE MCA
OUTSIDE
AIR
RATED CAPACITY
(MBH)
RATED CAPACITY
(MBH)
ACCU-1 FUJITSU AOU18RLXFZH 200 R410A 95 °F 18 22 240 V 1 19.7
GRILLE, REGISTER, AND DIFFUSER SCHEDULE
UNIT NO. MANUFACTURER MODEL DUTY SIZE
VOLUME
CONTROL MATERIAL FRAME TYPE
NOISE
CRITERIA FINISH NOTES
A TITUS OMNI SUPPLY 12x12 DUCT MOUNTED STEEL LAY-IN LESS THAN 30 WHITE
B TITUS OMNI SUPPLY 12x12 DUCT MOUNTED STEEL SURFACE MOUNTED LESS THAN 30 WHITE
C TITUS 350FL RETURN 12x12 NONE ALUMINUM SURFACE MOUNTED LESS THAN 30 WHITE
UNIT HEATER (GAS) SCHEDULE
UNIT NO. MANUFACTURER MODEL LOCATION
MECHANICAL REQUIREMENTS ELECTRICAL REQUIREMENTS
NOTESCFM INPUT MBH OUTPUT MBH FUEL TYPE FUEL PRESSURE ARRANGEMENT FAN RPM HP VOLTAGE PHASE
UH-1 REZNOR UDAS 200 101 2562 CFM 200 166 PROPANE 11" W.C. HORIZONTAL 1050 1/6 120 V 1 1
NOTES:
1. PROVIDE 24 VOLT ACTUATED MOTORIZED DAMPER ATTACHED TO INTERIOR FACE OF LOUVER.
SCALE:
NO SCALE
M5
1 PROPANE SERVICE DETAIL
NOTES:
1. PROVIDE PROPANE GAS REGULATOR IF INLET PRESSURE IS REQUIRED TO BE LESS THAN FUEL PRESSURE LISTED.
SCALE:
NO SCALE
M5
3 EYEWASH DETAIL
120 120
ELECTRICAL DRAWINGS
SYSTEM DESIGNATION
EQUIPMENT DESIGNATION
LOS-1-1
(BLANK)
LS
LR
OS
SE
D
PANEL NO.
FLOOR OF STRUCTURE
HIGH VOLTAGE 277/480
LOW VOLTAGE 120/208
EQUIPMENT DESIGNATION
SYSTEMS DESIGNATION
H
L
CODE
CODE
PANELBOARD IDENTIFICATION
ELECTRICAL ABBREVIATIONS LIST
#P QUANTITY OF POLES (2P, 3P, ETC)
A AMPERE
AF AMP (FRAME)
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AFCI ARC FAULT CIRCUIT
INTERRUPTER
AL ALUMINUM
ALT ALTERNATE
ARCH ARCHITECT, ARCHITECTURAL
AS AMP (SWITCH)
AT AMP (TRIP)
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AUX AUXILIARY
AV AUDIO VISUAL
AWG AMERICAN WIRE GAUGE
BLDG BUILDING
BMS BUILDING MANAGEMENT
SYSTEM
C CONDUIT
CAB CABINET
CATV CABLE TELEVISION
CB CIRCUIT BREAKER
CCTV CLOSED CIRCUIT TELEVISION
CKT CIRCUIT
CLG CEILING
COMB COMBINATION
CONST CONSTRUCTION
CONTR CONTRACTOR
CT CURRENT TRANSFORMER
CTL CONTROLLED
CTR CENTER
CU COPPER
DIA DIAMETER
DIST DISTRIBUTION
DN DOWN
DS DISCONNECT SWITCH
DT DOUBLE THROW
DWG DRAWING
ELEC ELECTRIC, ELECTRICAL
ELEV ELEVATOR
EM EMERGENCY
EMS ENERGY MANAGEMENT SYSTEM
EMT ELECTRICAL METALLIC TUBING
EQUIP EQUIPMENT
EWC ELECTRIC WATER COOLER
EXIST EXISTING
FA FIRE ALARM
FACP FIRE ALARM CONTROL PANEL
FLR FLOOR
FU FUSE
FDS FUSED DISCONNECT SWITCH
GA GAUGE
GALV GALVANIZED
GC GENERAL CONTRACTOR
GEN GENERATOR
GFCI GROUND FAULT CIRCUIT
INTERRUPTER
GFP GROUND FAULT PROTECTOR
GND GROUND
GRS GALVANIZED RIGID STEEL
(CONDUIT)
GYP GYPSUM BOARD
HH HANDHOLE
HOA HAND-OFF-AUTOMATIC SWITCH
HP HORSEPOWER
HTR HEATER
HV HIGH VOLTAGE
IG ISOLATED GROUND
IMC INTERMEDIATE METAL CONDUIT
IR INFRARED
JBOX JUNCTION BOX
KV KILOVOLT
KVA KILOVOLT-AMPERE
KVAR KILOVOLT-AMPERE REACTIVE
KW KILOWATT
KWH KILOWATT HOUR
LTG LIGHTING
LV LOW VOLTAGE
MAX MAXIMUM
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDP MAIN DISTRIBUTION PANEL
MFR MANUFACTURER
MH MANHOLE
MIC MICROPHONE
MIN MINIMUM
MISC MISCELLANEOUS
MLO MAIN LUGS ONLY
MOA MULTIOUTLET ASSEMBLY
MSBD MAIN SWITCHBOARD
MTS MANUAL TRANSFER SWITCH
MTR MOTOR, MOTORIZED
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURER'S
ASSOCIATION
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO NORMALLY OPEN
OH OVERHEAD
PA PUBLIC ADDRESS
PF POWER FACTOR
PH PHASE
PIV POST INDICATING VALVE
PNL PANEL
PP POWER POLE
PRJ PROJECTOR
PRV POWER ROOF VENTILATOR
PT POTENTIAL TRANSFORMER
PVC POLYVINYL CHLORIDE
(CONDUIT)
PWR POWER
QTY QUANTITY
RCPT RECEPTACLE
REQ REQUIRED
RM ROOM
RSC RIGID STEEL CONDUIT
SIM SIMILAR
SCCR SHORT CIRCUIT CURRENT RATING
SPEC SPECIFICATION
SPKR SPEAKER
SP SPARE
SS STAINLESS STEEL
STD STANDARD
SURF SURFACE MOUNTED
SW SWITCH
SWBD SWITCHBOARD
SYM SYMMETRICAL
TL TWIST LOCK
TR TAMPER RESISTANT
TV TELEVISION
TYP TYPICAL
UC UNDER COUNTER
UE UNDERGROUND ELECTRICAL
UG UNDERGROUND
UT UNDERGROUND TELEPHONE
UTIL UTILITY
UV ULTRAVIOLET
V VOLT
VA VOLT-AMPERES
VFD VARIABLE FREQUENCY DRIVE
W WATT
WR WEATHER RESISTANT
XFMR TRANSFORMER
@ AT
DELTA
' FEET
" INCHES
# NUMBER
Ø PHASE
℄ CENTER LINE
A2 12b
16c d
L-1-1
ELECTRICAL SYMBOL LEGEND NOTATION
THE LIGHTING FIXTURE TYPE IS INDICATED BY AN UPPER CASE LETTER.
THE CIRCUIT DESIGNATION IS INDICATED BY A NUMBER.
THE SWITCH DESIGNATION IS INDICATED BY A LOWER CASE LETTER.
EXAMPLE 1: LIGHTING FIXTURE TYPE "A" IS CONNECTED TO CIRCUIT 12 AND
CONTROLLED BY SWITCH "b".
EXAMPLE 2: THE FIXTURE TYPE SHOWN AS A NUMERATOR INDICATES ALL LIGHTING
FIXTURES IN THE ROOM OR SPACE ARE THE SAME TYPE. THE CIRCUIT NUMBER AND
SWITCH DESIGNATION SHOWN AS A DENOMINATOR INDICATES ALL LIGHTING FIXTURES
IN THE ROOM OR SPACE ARE CONNECTED TO THE SAME CIRCUIT, CONTROLLED BY
THE SAME SWITCHES, CENTER / OUTBOARD MULTILEVEL SWITCHING.
EXIT LIGHTS. SHADED AREA INDICATES ILLUMINATED FACE(S). ARROW INDICATES
DIRECTIONAL ARROW ON ILLUMINATED FACE(S). EXAMPLE: THE EXIT LIGHT TYPE
"E" WITH SINGLE FACE AND DIRECTIONAL ARROW IS CONNECTED TO CIRCUIT 14.
DEVICES. THE CIRCUIT DESIGNATION IS INDICATED BY A NUMBER. THE SWITCH
DESIGNATION IS INDICATED BY A LOWER CASE LETTER. EXAMPLE: SPLIT DUPLEX
RECEPTACLE IS CONNECTED TO CIRCUIT 16 AND ONE RECEPTACLE OUTLET IS
CONTROLLED BY SWITCH "c".
THE LINE VOLTAGE ZONE DESIGNATION IS INDICATED BY A LOWER CASE LETTER.
EXAMPLE: SINGLE POLE SWITCH "d" TO CONTROL LIGHTING FIXTURES INDICATED BY
"d".
PANELBOARDS. PANELBOARD DOORS MAY BE SHOWN TO INDICATE OPENING SIDE
OF RECESSED PANELBOARDS. SEE PANELBOARD IDENTIFICATION FOR
DESIGNATION CODES.
CONDUIT SHOWN SHALL CONTAIN 2 # 12 CONDUCTORS IN 3/4" CONDUIT UNLESS
SPECIFIC EQUIPMENT REQUIRES A DIFFERENT SIZE.
HOME RUN TO BRANCH CIRCUIT PANELBOARD. THE PANELBOARD DESIGNATION IS
SHOWN ADJACENT TO THE HOME RUN ARROW AS A NUMERATOR AND THE CIRCUIT
DESIGNATION IS SHOWN AS THE DENOMINATOR. CIRCUIT BREAKER SIZES
(AMPS/NUMBER OF POLES) ARE SHOWN IN THE PANELBOARD SCHEDULE WITH THE
CORRESPONDING PANELBOARD AND CIRCUIT DESIGNATION. EXAMPLE: HOME RUN TO
PANELBOARD L-1-1; CIRCUITS 1, 3, 5.
A2
2ab
L-1-1
1,3,5
FIRST
SECOND
MEZZANINE
M
FLOOR OF STRUCTURE CODE
NORMAL
LIFE SAFETY
LEGALLY REQUIRED
OPTIONAL STANDBY
SERVICE ENTRANCE
DISTRIBUTION
E
ALL DEVICES THAT CAN BE EITHER WALL, SURFACE OR SUSPENDED MOUNTED
SHALL UTILIZE THE FOLLOWING NOTATION FOR THE MOUNTING REQUIREMENTS:
1. A LEG OFF THE DEVICE SYMBOL IS FOR THE WALL MOUNTED CONDITION.
2. MULTIPOINT DOTS ON DEVICE SYMBOL IS FOR THE SUSPENDED
CONDITION.
3. DEVICE SYMBOL WITH NO ADDITIONAL ITEMS SHALL BE SURFACE /
CEILING MOUNTED CONDITION.
F
IN
A L P
LO
T
D R A W
IN
G
S
TA
TU
S
P
LO
T D A
TE
P R O
JE
C T
LO
C A
TI
O N
D W G
N A M E
TREMPEALEAU COUNTY WISCONSIN
17-RF-007
05/22 AJM
3R-WI-162- 33
TREMPEALEAU NATIONAL WILDLIFE REFUGE
ADDITION TO 3 STALL GARAGE
REVISION DATE DESCRIPTION BY
DESIGNED DRAWN: DATE: CHECKED:
SHEET_____OF_____DRAWING NO:CADD:
PROJECT NUMBER
TPL .DWG
GENERAL DRAWING NOTE:
THE U.S. FISH AND WILDLIFE SERVICE, REGION 3 CADD DRAWINGS
ARE DRAWN ON A 22" X 34" STANDARD "D" SIZE SHEET (FULL
SIZE) 100%. WHEN PLOTTING DRAWINGS AT DIFFERENT
PERCENTAGES BAR SCALES ON DRAWINGS SHALL BE USED FOR
MEASURING.
B I M
U S F W
T r e m p e a l e a u
M a i n t
G a r a g e
A d d i t i o n
F W S
T r e m p e a u l e a u
M E P
C e n t r a l r v t
P M
AMLMJV
E1
ELECTRICAL NOTES AND ABBREVIATIONS
M
JV
E1
E1 ELECTRICAL NOTES AND ABBREVIATIONS
E2 ELECTRICAL SYMBOL LEGEND
E3 ELECTRICAL SITE PLAN
E4 LEVEL 1 ELECTRICAL DEMOLITION PLAN
E5 LEVEL 1 LIGHTING PLAN
E6 MEZZANINE LIGHTING PLAN
E7 LEVEL 1 POWER PLAN
E8 MEZZANINE POWER PLAN
E9 ELECTRICAL DETAILS AND DIAGRAMS
E10 ELECTRICAL SCHEDULES
E11 ELECTRICAL SCHEDULES
T1 LEVEL 1 TECHNOLOGY PLAN
T2 MEZZANINE TECHNOLOGY PLAN
21121 121
PANELBOARD (TYPE DENOTED)
FOURPLEX RECEPT. (CONTROLLED, GFCI, USB)
DUPLEX RECEPT. (CONTROLLED, GFCI, USB)
CORD REEL
1. ALL DISTANCES ARE TO CENTER OF DEVICE OR EQUIPMENT UNLESS OTHERWISE NOTED. DEVICES INDICATED AT 48" MAY NOT BE INSTALLED WITH ANY OPERABLE PART HIGHER THAN 48".
DEVICES MAY BE INSTALLED IN CONCRETE MASONRY UNITS WITH THE TOP OF THE DEVICE AT 48".
2. NOT ALL SYMBOLS SHOWN ARE UTILIZED IN THE PROJECT.
DASHED SYMBOL INDICATES REMOVED
HALFTONE SYMBOL INDICATES EXISTING
X
MOTOR CONNECTION (TYPE DENOTED)
SPECIAL CABINET (TYPE DENOTED)
J
SPECIAL RECEPT. OR CONN. (SEE SCHEDULE)
JUNCTION BOX
COMMUNICATION OUTLET (# - CABLE QUANTITY; "0" - ROUGH-IN ONLY)
ANALOG COMMUNICATION OUTLET (# - CABLE QUANTITY; "0" - ROUGH-IN ONLY)
DOOR CONTACTS
CARD READER
CONDUIT TRANSITION DOWN
CONDUIT TRANSITION UP
BRANCH CIRCUIT HOME RUN
CONDUIT EXPOSED
CONDUIT STUBBED OUT
CONDUIT CONCEALED BELOW FLOOR
CONDUIT CONCEALED IN WALL OR OVERHEAD
ELECTRICAL SYMBOL LEGEND
AS NOTED
DC
CR
CONDUIT SLEEVE (SIZE DENOTED)
XX
TECHNOLOGY
POWER
CONDUIT
GENERAL
AS NOTED
HEIGHT SYMBOL TAGS DESCRIPTION
HEIGHT SYMBOL TAGS DESCRIPTION
HEIGHT SYMBOL TAGS DESCRIPTION
SECURITY
HEIGHT SYMBOL TAGS DESCRIPTION
HEIGHT SYMBOL TAGS DESCRIPTION
SWITCH (2 POLE, 3-WAY, 4-WAY, KEYED, DIMMER,
OCCUPANCY SENSOR, MOMENTARY CONTACT,
TIME CONTROL AND TIMER)
PUSH BUTTON
X
OS
DISCONNECT SWITCH (FUSED)
DISCONNECT SWITCH (NON-FUSED)
OCCUPANCY SENSOR - TYPE DENOTED
CONTROLS
HEIGHT SYMBOL TAGS DESCRIPTION
RECESSED LIGHT (TYPE DENOTED)
SURFACE LIGHT (TYPE DENOTED)
EXIT SIGN (TYPE DENOTED)
STRIP LIGHT (TYPE DENOTED)
EMERGENCY BATTERY LIGHT (TYPE DENOTED)
SEE E002
96"
X
X
X
X
X
X
AS NOTED
X
LIGHTING
HEIGHT SYMBOL TAGS DESCRIPTION
48" AFF TO
TOP OF BOX
48" AFF TO
TOP OF BOX
36" AFF TO
BOTTOM OF
BOX
36" AFF TO
BOTTOM OF
BOX
FIRE ALARM
FIRE ALARM PULLSTATION
F
HEAT DETECTOR
SMOKE DETECTOR
FIRE ALARM STROBE (CANDELAS)
FIRE ALARM SPEAKER W/STROBE (CANDELAS)
F
FIRE ALARM REMOTE ANNUNCIATOR
FAA
F S
HEIGHT SYMBOL TAGS DESCRIPTION
FIRE ALARM SPEAKER
F S
90" AFF TO
TOP OF BOX
90" AFF TO
TOP OF BOX
90" AFF TO
TOP OF BOX
48" AFF TO
TOP OF BOX
48" AFF TO
TOP OF BOX
MOTION DETECTOR
MD
F
IN
A L P
LO
T
D R A W
IN
G
S
TA
TU
S
P
LO
T D A
TE
P R O
JE
C T
LO
C A
TI
O N
D W G
N A M E
TREMPEALEAU COUNTY WISCONSIN
17-RF-007
05/22 AJM
3R-WI-162- 33
TREMPEALEAU NATIONAL WILDLIFE REFUGE
ADDITION TO 3 STALL GARAGE
REVISION DATE DESCRIPTION BY
DESIGNED DRAWN: DATE: CHECKED:
SHEET_____OF_____DRAWING NO:CADD:
PROJECT NUMBER
TPL .DWG
GENERAL DRAWING NOTE:
THE U.S. FISH AND WILDLIFE SERVICE, REGION 3 CADD DRAWINGS
ARE DRAWN ON A 22" X 34" STANDARD "D" SIZE SHEET (FULL
SIZE) 100%. WHEN PLOTTING DRAWINGS AT DIFFERENT
PERCENTAGES BAR SCALES ON DRAWINGS SHALL BE USED FOR
MEASURING.
B I M
U S F W
T r e m p e a l e a u
M a i n t
G a r a g e
A d d i t i o n
F W S
T r e m p e a u l e a u
M E P
C e n t r a l r v t
P M
AMLMJV
E2
ELECTRICAL SYMBOL LEGEND
M
JV
E2 22122 122
KEYED SHEET NOTES
1. EC SHALL REMOVE EXISTING LIGHT
FIXTURES IN GARAGE AREA. RETAIN
EXISTING LIGHTING CIRCUITS FOR
RECONNECTION. REMOVE EXISTING LIGHT
SWITCHES CONTROLLING EXISTING
LIGHTS.
2. REMOVE EXISTING WALL PACK. SALVAGE
CONDUIT AND CONDUCTORS FOR
REINSTALLATION OF NEW FIXTURE.
GENERAL SHEET NOTES
A. REFER TO ARCHITECTURAL DRAWINGS AND
SPECIFICATIONS FOR PHASES OF
DEMOLITION. COORDINATE WITH GENERAL
CONSTRUCTION.
B. EXISTING LIGHTING FIXTURES AND
DEVICES SHOWN ON THIS DRAWING ARE
BASED ON CASUAL FIELD OBSERVATION
AND EXISTING DRAWINGS (IF AVAILABLE).
IT IS THE ELECTRICAL CONTRACTOR'S
RESPONSIBILITY, PRIOR TO BIDDING, TO
FIELD VERIFY EXISTING CONDITIONS TO
DETERMINE THE EXTENT OF THE
ELECTRICAL DEMOLITION WORK REQUIRED.
C. DISCONNECT AND REMOVE ALL LIGHTING
FIXTURES AND DEVICES, UNLESS NOTED
OTHERWISE. REMOVE ASSOCIATED
CONDUIT AND WIRING BACK TO SOURCE.
D. PROVIDE CONDUIT AND ELECTRICAL
WIRING AS NECESSARY FOR CONTINUITY
OF FEEDERS / BRANCH CIRCUITS
ORIGINATING OUTSIDE THE DEMOLITION
AREA THAT SERVE ANY LIGHTING FIXTURES
AND / OR DEVICES TO REMAIN.
E. PROVIDE BLANK COVERPLATES FOR
EXISTING UNUSED JUNCTION BOX
OPENINGS TO REMAIN.
F. DISCONNECT AND REMOVE WALL-
MOUNTED LIGHTING SWITCHES /
CONTROLS TO ACCOMMODATE NEW DOOR
CONFIGURATIONS.
EXISTING
VEHICLE
STORAGE
2 2
F
IN
A L P
LO
T
D R A W
IN
G
S
TA
TU
S
P
LO
T D A
TE
P R O
JE
C T
LO
C A
TI
O N
D W G
N A M E
TREMPEALEAU COUNTY WISCONSIN
17-RF-007
05/22 AJM
3R-WI-162- 33
TREMPEALEAU NATIONAL WILDLIFE REFUGE
ADDITION TO 3 STALL GARAGE
REVISION DATE DESCRIPTION BY
DESIGNED DRAWN: DATE: CHECKED:
SHEET_____OF_____DRAWING NO:CADD:
PROJECT NUMBER
TPL .DWG
GENERAL DRAWING NOTE:
THE U.S. FISH AND WILDLIFE SERVICE, REGION 3 CADD DRAWINGS
ARE DRAWN ON A 22" X 34" STANDARD "D" SIZE SHEET (FULL
SIZE) 100%. WHEN PLOTTING DRAWINGS AT DIFFERENT
PERCENTAGES BAR SCALES ON DRAWINGS SHALL BE USED FOR
MEASURING.
B I M
U S F W
T r e m p e a l e a u
M a i n t
G a r a g e
A d d i t i o n
F W S
T r e m p e a u l e a u
M E P
C e n t r a l r v t
P M
AMLMJV
E4
LEVEL 1 ELECTRICAL DEMOLITION PLAN
C h e c k e r
E4
SCALE: 1/4" = 1'-0"
E4
1 LEVEL 1 ELECTRICAL DEMOLITION PLAN
1 0 4 8 12
24124 124
1. REFER TO MEZZANINE LIGHTING PLAN FOR
FIXTURES IN THIS ROOM / AREA.
2. SUSPEND FIXTURES IN THIS ROOM / AREA
AT 8'-0" AFF TO BOTTOM OF FIXTURE.
3. CONNECT FIXTURE TO EXISTING EXTERIOR
LIGHTING CIRCUIT "EXIST-1" SALVAGED
DURING DEMOLITION. CONTROL ALL
EXTERIOR FIXTURES BY SWITCHES
INDICATED.
4. PROVIDE NEW 3-WAY SWITCH SURFACE
MOUNTED 48" AFF TO TOP OF BOX ON
EXISTING WALL TO CONTROL ALL
EXTERIOR WALL PACKS (CIRCUIT EXIST-1).
5. PROVIDE (2) NEW LOW VOLTAGE DIMMER
SWITCHES IN THREE LOCATIONS
INDICATED TO CONTROL NEW LED LIGHTS
INSTALLED IN THE EXISTING GARAGE. IN
EACH LOCATION, ONE SWITCH SHALL
CONTROL THE NORTH ROW OF LIGHTS AND
ONE SWITCH SHALL CONTROL THE SOUTH
ROW OF LIGHTS.
GENERAL SHEET NOTES
A. REFER TO ARCHITECTURAL REFLECTED
CEILING PLANS FOR EXACT LIGHTING
FIXTURE LOCATIONS WITHIN CEILING.
B. REFER TO ARCHITECTURAL ELEVATIONS
FOR EXACT BUILDING / WALL-MOUNTED
LIGHTING FIXTURE AND CONTROLS
LOCATIONS.
C. REFER TO LIGHTING SCHEDULES FOR
SPECIFIC FIXTURE AND CONTROLS
INFORMATION.
D. REFER TO SPECIFICATION SECTION 26 0519
FOR REQUIRED CONDUCTOR SIZE
ADJUSTMENTS FOR VOLTAGE DROP.
E. PROVIDE 6' FLEXIBLE METAL CONDUIT FOR
RECESSED LIGHTING FIXTURES INSTALLED
IN ACCESSIBLE LAY-IN CEILINGS.
F. PROVIDE LIGHTING CONTROL DEVICES PER
MANUFACTURER'S RECOMMENDATIONS
(CATALOG NUMBER, LOCATION AND
QUANTITY); REFER TO SPECIFICATION
SECTION 26 0943. DEVICES SHOWN ARE
FOR GENERAL DESIGN INTENT ONLY.
G. PROVIDE WALL-MOUNTED LIGHTING
SWITCHES / CONTROLS TO ACCOMMODATE
NEW DOOR CONFIGURATIONS.
H. PROVIDE WORK FOR ALL ALTERNATE ITEMS
(IF ANY). REFER TO NOTES ON DRAWINGS
AND SPECIFICATIONS FOR ALTERNATE
DESCRIPTIONS.
I. WALL MOUNTED DEVICES LOCATED ON
CMU OR CONCRETE WALLS SHALL BE
SURFACE MOUNTED.
LVD
LV
LV
OS
OS
LVD
LVD
LVD
LV
LVD
LVD LVD
LVDLVD
VEHICLE
MAINTENANCE
MECH
RESTROOM
OFFICE
EXISTING
VEHICLE
STORAGE
A22A A22A
A22A A22A
A22B
A22B
D1
DT2
DT2
S1 S1
EM2
EM2
EM2
EM2
EM2
EM2
EM2 EM2 EM2
EM2
EM2EM2EM2
E1
E1
E1
E1
TO LIGHTS IN
ROOM 200
BB-E
EXIST
BB-E
BB
BB
BB
BB-E
3 3
3 3
3 3
MAIN
4 4
F
IN
A L P
LO
T
D R A W
IN
G
S
TA
TU
S
P
LO
T D A
TE
P R O
JE
C T
LO
C A
TI
O N
D W G
N A M E
TREMPEALEAU COUNTY WISCONSIN
17-RF-007
05/22 AJM
3R-WI-162- 33
TREMPEALEAU NATIONAL WILDLIFE REFUGE
ADDITION TO 3 STALL GARAGE
REVISION DATE DESCRIPTION BY
DESIGNED DRAWN: DATE: CHECKED:
SHEET_____OF_____DRAWING NO:CADD:
PROJECT NUMBER
TPL .DWG
GENERAL DRAWING NOTE:
THE U.S. FISH AND WILDLIFE SERVICE, REGION 3 CADD DRAWINGS
ARE DRAWN ON A 22" X 34" STANDARD "D" SIZE SHEET (FULL
SIZE) 100%. WHEN PLOTTING DRAWINGS AT DIFFERENT
PERCENTAGES BAR SCALES ON DRAWINGS SHALL BE USED FOR
MEASURING.
B I M
U S F W
T r e m p e a l e a u
M a i n t
G a r a g e
A d d i t i o n
F W S
T r e m p e a u l e a u
M E P
C e n t r a l r v t
P M
AMLMJV
E5
LEVEL 1 LIGHTING PLAN
M
JV
E5
SCALE: 1/4" = 1'-0"
E5
1 LEVEL 1 LIGHTING PLAN
1 0 4 8 12
25125 125
1. SUSPEND FIXTURES IN THIS ROOM / AREA
AT 9'-0" AFF TO BOTTOM OF FIXTURE.
2. SUSPEND FIXTURES IN THIS ROOM / AREA
AT 12'-0" AFF TO BOTTOM OF FIXTURE.
3. SUSPEND FIXTURES IN THIS ROOM / AREA
AT 16'-0" AFF TO BOTTOM OF FIXTURE.
GENERAL SHEET NOTES
A. REFER TO ARCHITECTURAL REFLECTED
CEILING PLANS FOR EXACT LIGHTING
FIXTURE LOCATIONS WITHIN CEILING.
B. REFER TO ARCHITECTURAL ELEVATIONS
FOR EXACT BUILDING / WALL-MOUNTED
LIGHTING FIXTURE AND CONTROLS
LOCATIONS.
C. REFER TO LIGHTING SCHEDULES FOR
SPECIFIC FIXTURE AND CONTROLS
INFORMATION.
D. REFER TO SPECIFICATION SECTION 26 0519
FOR REQUIRED CONDUCTOR SIZE
ADJUSTMENTS FOR VOLTAGE DROP.
E. PROVIDE 6' FLEXIBLE METAL CONDUIT FOR
RECESSED LIGHTING FIXTURES INSTALLED
IN ACCESSIBLE LAY-IN CEILINGS.
F. PROVIDE LIGHTING CONTROL DEVICES PER
MANUFACTURER'S RECOMMENDATIONS
(CATALOG NUMBER, LOCATION AND
QUANTITY); REFER TO SPECIFICATION
SECTION 26 0943. DEVICES SHOWN ARE
FOR GENERAL DESIGN INTENT ONLY.
G. PROVIDE WALL-MOUNTED LIGHTING
SWITCHES / CONTROLS TO ACCOMMODATE
NEW DOOR CONFIGURATIONS.
H. PROVIDE WORK FOR ALL ALTERNATE ITEMS
(IF ANY). REFER TO NOTES ON DRAWINGS
AND SPECIFICATIONS FOR ALTERNATE
DESCRIPTIONS.
I. WALL MOUNTED DEVICES LOCATED ON
CMU OR CONCRETE WALLS SHALL BE
SURFACE MOUNTED.
LV
MEZZANINE
VEHICLE
MAINTENANCE
S1 S1
S1 S1
S1 S1
H1 H1 H1
H1 H1 H1
H1 H1 H1
EM2
EM2
E1
EXISTING
VEHICLE
STORAGE
H1 H1
H1
H1
H1
H1 H1
H1H1
H1
H1
H1
H1H1
1 1 1
1 1 1
MAIN
TO SWITCH AT
BOTTOM OF STAIRS
EM2
3 3
3 3
4 4
4 4
EXIST
EXIST
F
IN
A L P
LO
T
D R A W
IN
G
S
TA
TU
S
P
LO
T D A
TE
P R O
JE
C T
LO
C A
TI
O N
D W G
N A M E
TREMPEALEAU COUNTY WISCONSIN
17-RF-007
05/22 AJM
3R-WI-162- 33
TREMPEALEAU NATIONAL WILDLIFE REFUGE
ADDITION TO 3 STALL GARAGE
REVISION DATE DESCRIPTION BY
DESIGNED DRAWN: DATE: CHECKED:
SHEET_____OF_____DRAWING NO:CADD:
PROJECT NUMBER
TPL .DWG
GENERAL DRAWING NOTE:
THE U.S. FISH AND WILDLIFE SERVICE, REGION 3 CADD DRAWINGS
ARE DRAWN ON A 22" X 34" STANDARD "D" SIZE SHEET (FULL
SIZE) 100%. WHEN PLOTTING DRAWINGS AT DIFFERENT
PERCENTAGES BAR SCALES ON DRAWINGS SHALL BE USED FOR
MEASURING.
B I M
U S F W
T r e m p e a l e a u
M a i n t
G a r a g e
A d d i t i o n
F W S
T r e m p e a u l e a u
M E P
C e n t r a l r v t
P M
AMLMJV
E6
MEZZANINE LIGHTING PLAN
C h e c k e r
E6
SCALE:
1/4" = 1'-0"
E6
1 MEZZANINE LIGHTING PLAN
26126 126
1. PROVIDE NEMA 6-30R RECEPTACLE FOR
WELDER.
2. PROVIDE NEMA 6-15R RECEPTACLE FOR
AIR COMPRESSOR.
3. PROVIDE NEMA 6-50R RECEPTACLE FOR
WELDER.
4. PROVIDE DEDICATED CIRCUIT FOR
REFRIGERATOR.
5. PROVIDE NEMA 14-30R RECEPTACLE FOR
DRYER.
6. PROVIDE RECEPTACLE MOUNTED TO
STRUCTURAL CEILING. PROVIDE 12/3 50'
RETRACTABLE CORD REEL, WITH (2) NEMA
5-20 DUPLEX RECEPTACLES, WOODHEAD
#92433 OR EQUAL.
7. PROVIDE NEW 120/240V SINGLE PHASE,
400A MCB.
8. PROVIDE DEDICATED CIRCUIT FOR
MICROWAVE.
GENERAL SHEET NOTES
A. REFER TO "TYPICAL DEVICE MOUNTING
DETAIL" FOR DEVICE MOUNTING HEIGHTS
AND ADJACENCIES.
B. REFER TO ARCHITECTURAL ELEVATIONS
FOR EXACT WALL-MOUNTED DEVICE
LOCATIONS.
C. REFER TO PANEL BOUNDARIES ON PLAN
FOR PANEL CIRCUITING INFORMATION.
D. REFER TO EQUIPMENT SCHEDULES FOR
SPECIFIC EQUIPMENT CONNECTION
INFORMATION.
E. PROVIDE ROUGH-IN FOR THE FOLLOWING
SYSTEMS TO BE PROVIDED BY THE
DIVISION 27 CONTRACTOR:
1. TECHNOLOGY CABLING
2. TECHNOLOGY EQUIPMENT ROOM
COMPONENTS
3. FIRE ALARM BACKBONE CABLING
F. PROVIDE ROUGH-IN FOR THE FOLLOWING
SYSTEMS TO BE PROVIDED BY THE
DIVISION 28 CONTRACTOR:
1. FIRE ALARM SYSTEM
G. STUB TECHNOLOGY CONDUIT INTO
ACCESSIBLE CEILING SPACE, UNLESS
NOTED OTHERWISE.
H. PROVIDE WORK FOR ALL ALTERNATE ITEMS
(IF ANY). REFER TO NOTES ON DRAWINGS
AND SPECIFICATIONS FOR ALTERNATE
DESCRIPTIONS.
I. WALL MOUNTED DEVICES LOCATED ON
CMU OR CONCRETE WALLS SHALL BE
SURFACE MOUNTED.
J. UNLESS NOTED OTHERWISE, ALL WALL
MOUNTED DEVICES SHALL BE MOUNTED 36"
AFF TO BOTTOM OF BOX.
P F
MECH
VEHICLE
MAINTENANCE
RESTROOM
OFFICE
EXISTING
VEHICLE
STORAGE
FCU-1
FCU-2
UH-1
EF-1
GFCI
54"
GFCI
42"
OHD
OHD
EXIST
GFCI
48"
CTL
36"
CTL
36"
FACP
CTL
36"
AC
GFCI
48"
48"
48"
48"
48"
WP
GFCI
60"
48"
54"
OHD OHD OHD
OHD
60"
60"
60"
60"
60"
WP
GFCI
60"
60"
60"
60"
MAIN
MAIN
MAIN
9 11 13
EXIST
EXIST
EXIST
EXIST
WP
GFCI
60"
EXIST
MAIN
MAIN
MAIN
10,12
MAIN
18,20
MAIN
14,16
MAIN
30,32
MAIN
31,33
MAIN
31,33
MAIN
22,24
MAIN
22,24
34,36
MAIN
34,36
MAIN
MAIN
MAIN
26,28
MAIN
26,28
MAIN
MAIN
FAAP
11 11
MAIN
AC
GFCI
GFCI
60"
MAIN
F
IN
A L P
LO
T
D R A W
IN
G
S
TA
TU
S
P
LO
T D A
TE
P R O
JE
C T
LO
C A
TI
O N
D W G
N A M E
TREMPEALEAU COUNTY WISCONSIN
17-RF-007
05/22 AJM
3R-WI-162- 33
TREMPEALEAU NATIONAL WILDLIFE REFUGE
ADDITION TO 3 STALL GARAGE
REVISION DATE DESCRIPTION BY
DESIGNED DRAWN: DATE: CHECKED:
SHEET_____OF_____DRAWING NO:CADD:
PROJECT NUMBER
TPL .DWG
GENERAL DRAWING NOTE:
THE U.S. FISH AND WILDLIFE SERVICE, REGION 3 CADD DRAWINGS
ARE DRAWN ON A 22" X 34" STANDARD "D" SIZE SHEET (FULL
SIZE) 100%. WHEN PLOTTING DRAWINGS AT DIFFERENT
PERCENTAGES BAR SCALES ON DRAWINGS SHALL BE USED FOR
MEASURING.
B I M
U S F W
T r e m p e a l e a u
M a i n t
G a r a g e
A d d i t i o n
F W S
T r e m p e a u l e a u
M E P
C e n t r a l r v t
P M
AMLMJV
E7
LEVEL 1 POWER PLAN
M
JV
E7
SCALE:
1/4" = 1'-0"
E7
1 LEVEL 1 POWER PLAN
1 0 4 8 12
27127 127
1. PROVIDE DEDICATED CIRCUIT FOR
FREEZER.
2. PROVIDE UNISTRUT FRAME TO MOUNT
WATER SOFTENER RECEPTACLE 18" AFF.
GENERAL SHEET NOTES
A. REFER TO "TYPICAL DEVICE MOUNTING
DETAIL" FOR DEVICE MOUNTING HEIGHTS
AND ADJACENCIES.
B. REFER TO ARCHITECTURAL ELEVATIONS
FOR EXACT WALL-MOUNTED DEVICE
LOCATIONS.
C. REFER TO PANEL BOUNDARIES ON PLAN
FOR PANEL CIRCUITING INFORMATION.
D. REFER TO EQUIPMENT SCHEDULES FOR
SPECIFIC EQUIPMENT CONNECTION
INFORMATION.
E. PROVIDE ROUGH-IN FOR THE FOLLOWING
SYSTEMS TO BE PROVIDED BY THE
DIVISION 27 CONTRACTOR:
1. TECHNOLOGY CABLING
2. TECHNOLOGY EQUIPMENT ROOM
COMPONENTS
3. FIRE ALARM BACKBONE CABLING
F. PROVIDE ROUGH-IN FOR THE FOLLOWING
SYSTEMS TO BE PROVIDED BY THE
DIVISION 28 CONTRACTOR:
1. FIRE ALARM SYSTEM
G. STUB TECHNOLOGY CONDUIT INTO
ACCESSIBLE CEILING SPACE, UNLESS
NOTED OTHERWISE.
H. PROVIDE WORK FOR ALL ALTERNATE ITEMS
(IF ANY). REFER TO NOTES ON DRAWINGS
AND SPECIFICATIONS FOR ALTERNATE
DESCRIPTIONS.
I. WALL MOUNTED DEVICES LOCATED ON
CMU OR CONCRETE WALLS SHALL BE
SURFACE MOUNTED.
J. UNLESS NOTED OTHERWISE, ALL WALL
MOUNTED DEVICES SHALL BE MOUNTED 36"
AFF TO BOTTOM OF BOX.
MEZZANINE
ACCU-1
ERV-1
48"
48"
48"
WH-1
MAIN
MAIN
MAIN
VEHICLE
MAINTENANCE
EXISTING
VEHICLE
STORAGE
MAIN
26,28
MAIN
EF-2
MAIN
MAIN
WS-1
F
IN
A L P
LO
T
D R A W
IN
G
S
TA
TU
S
P
LO
T D A
TE
P R O
JE
C T
LO
C A
TI
O N
D W G
N A M E
TREMPEALEAU COUNTY WISCONSIN
17-RF-007
05/22 AJM
3R-WI-162- 33
TREMPEALEAU NATIONAL WILDLIFE REFUGE
ADDITION TO 3 STALL GARAGE
REVISION DATE DESCRIPTION BY
DESIGNED DRAWN: DATE: CHECKED:
SHEET_____OF_____DRAWING NO:CADD:
PROJECT NUMBER
TPL .DWG
GENERAL DRAWING NOTE:
THE U.S. FISH AND WILDLIFE SERVICE, REGION 3 CADD DRAWINGS
ARE DRAWN ON A 22" X 34" STANDARD "D" SIZE SHEET (FULL
SIZE) 100%. WHEN PLOTTING DRAWINGS AT DIFFERENT
PERCENTAGES BAR SCALES ON DRAWINGS SHALL BE USED FOR
MEASURING.
B I M
U S F W
T r e m p e a l e a u
M a i n t
G a r a g e
A d d i t i o n
F W S
T r e m p e a u l e a u
M E P
C e n t r a l r v t
P M
AuthorDesigner
E8
MEZZANINE POWER PLAN
C h e c k e r
E8
SCALE:
1/4" = 1'-0"
E8
1 MEZZANINE POWER PLAN
28128 128
0' - 6"
DETAIL NOTES:
1. INSTALL WALL MOUNTED
VANITY LIGHT 0' - 2"
ABOVE NEAREST MIRROR.
R E
F E
R E
N C
E
A
R C
H I T
E C
T U
R A
L
P
L A
N S
F
O R
M
I R
R O
R
M
O U
N T
I N
G
H
E I G
H T
KEYED NOTES:
1. INSTALL RECEPTACLE 0' - 6" FROM NEAREST
MIRROR EDGE. REFER TO PLAN DRAWINGS FOR
INTENDED LOCATION. CONTRACTOR SHALL
UTILIZE BACKBOX SUPPORTS TO PROVIDE
CONSISTENT SPACING OF MULTIPLE SEPARATE
BOXES IN A LINE. REFER TO SPECIFICATIONS FOR
REQUIREMENTS.
WASHING MACHINE
OUTLET BOX (BY
DIV 22)
DRYER VENT (BY DIV 23)
NEUTRAL (N)
LINE/HOT (L)
NEUTRAL (N)
SWITCHED LINE/HOT
20A
POWER
PACK
JUNCTION BOX
20A
SPLIT-WIRED
RECEPTACLE
MARK FOR AUTOMATICALLY CONTROLLED
RECEPTACLES AS REQUIRED BY NEC
KEYED SHEET NOTES
1. DISCONNECT EXISTING UTILITY SERVICE
ENTRANCE CONDUCTORS FROM PANEL
"EXIST". REMOVE CONDUCTORS TO
SOURCE. CUT CONDUIT AT SLAB AND CAP.
ABANDON UNDERGROUND CONDUIT.
2. PROVIDE NEW FEEDER FROM NEW PANEL
"MAIN" TO BACK FEED THE MAIN AT PANEL
"EXIST".
3. DISCONNECT EXISTING CONDUCTORS
FROM UTILITY TRANSFORMER.
4. TERMINATE CONDUCTORS AT UTILITY
TRANSFORMER FOR NEW SERVICE
ENTRANCE CONDUCTORS TO PANEL
"MAIN".
5. ROUTE CONDUITS UNDERGROUND AND
UNDER SLAB OF NEW ADDITION TO MAIN
PANEL LOCATION. TRANSITION FROM
BELOW SLAB PVC TO RMC FOR EXPOSED
CONDUIT.
LEVEL 1GRADE
MECH 104 EXISTING VEHICLE STORAGE 100
UTILITY
TRANSFORMER
NEW PANEL
"MAIN"
120/240V
SINGLE PHASE
400A MCB
EXISTING PANEL
"EXIST"
120/240V
SINGLE PHASE
100A MCB
(2) 2"C EACH WITH
(2) #3/0 + (1) #3 GND
(1) 1-1/4"C EACH WITH
(2) #1 + (1) #6 GND
3 1
F
IN
A L P
LO
T
D R A W
IN
G
S
TA
TU
S
P
LO
T D A
TE
P R O
JE
C T
LO
C A
TI
O N
D W G
N A M E
TREMPEALEAU COUNTY WISCONSIN
17-RF-007
05/22 AJM
3R-WI-162- 33
TREMPEALEAU NATIONAL WILDLIFE REFUGE
ADDITION TO 3 STALL GARAGE
REVISION DATE DESCRIPTION BY
DESIGNED DRAWN: DATE: CHECKED:
SHEET_____OF_____DRAWING NO:CADD:
PROJECT NUMBER
TPL .DWG
GENERAL DRAWING NOTE:
THE U.S. FISH AND WILDLIFE SERVICE, REGION 3 CADD DRAWINGS
ARE DRAWN ON A 22" X 34" STANDARD "D" SIZE SHEET (FULL
SIZE) 100%. WHEN PLOTTING DRAWINGS AT DIFFERENT
PERCENTAGES BAR SCALES ON DRAWINGS SHALL BE USED FOR
MEASURING.
B I M
U S F W
T r e m p e a l e a u
M a i n t
G a r a g e
A d d i t i o n
F W S
T r e m p e a u l e a u
M E P
C e n t r a l r v t
P M
AMLMJV
E9
ELECTRICAL DETAILS AND DIAGRAMS
M
JV
E9SCALE:
NOT TO SCALE
E9
TYPICAL BATHROOM VANITY ELEVATION
DETAIL
SCALE:
NOT TO SCALE
E9
2 TYPICAL WASHER / DRYER ELEVATION DETAIL
SCALE:
NOT TO SCALE
E9
4 SPLIT-WIRED DUPLEX RECEPTACLE DETAIL
SCALE:
NOT TO SCALE
E9
3 ELECTRICAL POWER DISTRIBUTION DIAGRAM
29129 129
A. UNIVERSAL AND MULTI-VOLT DRIVERS ACCEPTABLE.
B. WHERE "APPROVED EQUAL" IS LISTED IN THE MANUFACTURER COLUMN, FIXTURES MUST BE SUBMITTED AS A SUBSTITUTION FOR APPROVAL PRIOR TO BID SUBMISSION.
GENERAL NOTES:
1. WET LOCATION LISTED. MOUNT 96" ABOVE GRADE. PROVIDE 120V SINGLE FUSE. PROVIDE 120V BUTTON TYPE INTEGRAL PHOTOCELL.
SCHEDULE NOTES:
A. OCCUPANCY SENSOR TIME OUT IS 15 MINUTES, UNLESS OTHERWISE NOTED.
GENERAL NOTES:
F
IN
A L P
LO
T
D R A W
IN
G
S
TA
TU
S
P
LO
T D A
TE
P R O
JE
C T
LO
C A
TI
O N
D W G
N A M E
TREMPEALEAU COUNTY WISCONSIN
17-RF-007
05/22 AJM
3R-WI-162- 33
TREMPEALEAU NATIONAL WILDLIFE REFUGE
ADDITION TO 3 STALL GARAGE
REVISION DATE DESCRIPTION BY
DESIGNED DRAWN: DATE: CHECKED:
SHEET_____OF_____DRAWING NO:CADD:
PROJECT NUMBER
TPL .DWG
GENERAL DRAWING NOTE:
THE U.S. FISH AND WILDLIFE SERVICE, REGION 3 CADD DRAWINGS
ARE DRAWN ON A 22" X 34" STANDARD "D" SIZE SHEET (FULL
SIZE) 100%. WHEN PLOTTING DRAWINGS AT DIFFERENT
PERCENTAGES BAR SCALES ON DRAWINGS SHALL BE USED FOR
MEASURING.
B I M
U S F W
T r e m p e a l e a u
M a i n t
G a r a g e
A d d i t i o n
F W S
T r e m p e a u l e a u
M E P
C e n t r a l r v t
P M
AMLMJV
E10
ELECTRICAL SCHEDULES
M
JV
E10
LIGHTING CONTROL SEQUENCE OF OPERATIONS SCHEDULE
ROOM ROOM NAME
FC
TARGET
TIME
SCHEDULED OCCUPANCY SENSORS OVERRIDE
DAYLIGHT
SENSOR
POWER
PACK
(PLUG
LOAD)
PHOTO
CELL
TIME
CLOCK
AUTO
ON
MANUAL
ON
TIME
DELAY
WALL
SWITCHES
WALL
DIMMERS
MULTI-
ZONE
100 EXISTING
VEHICLE
STORAGE
50 --- --- --- --- --- --- X --- --- ---
101 VEHICLE
MAINTENANCE
50 --- --- --- --- --- --- X --- --- ---
102 OFFICE 30 --- --- X --- 15 MIN --- X --- --- X
103 RESTROOM 10 --- --- X --- 15 MIN X --- --- --- ---
104 MECH 20 --- --- --- --- --- X --- --- --- ---
200 MEZZANINE 20 --- --- --- --- --- X --- --- --- ---
LIGHTING CONTROL DEVICE SCHEDULE
TYPE DESCRIPTION MANUFACTURER
3 SINGLE GANG, SINGLE PUSHBUTTON FOR
LIGHTING CONTROL.
SEE
SPECIFICATIONS
DT2 DUAL TECHNOLOGY PASSIVE INFRARED
AND ULTRASONIC OCCUPANCY SENSOR,
STANDARD RANGE.
SEE
SPECIFICATIONS
LV SINGLE GANG, SINGLE PUSHBUTTON FOR
LIGHTING CONTROL.
SEE
SPECIFICATIONS
LVD SINGLE GANG, SINGLE PUSHBUTTON FOR
LIGHTING CONTROL.
SEE
SPECIFICATIONS
LIGHTING FIXTURE SCHEDULE
TYPE
FIXTURE HOUSING LIGHT SOURCE
DRIVER VOLT WATT
EMERGENCY
COMPONENTS
BASIS OF DESIGN APPROVED EQUALS
NOTEDESCRIPTION
LENS /
DIFFUSER
MOUNTING SOURCE
MINIMUM
LUMEN
OUTPUT
(lm)
MINIMUM
COLOR
TEMP
(KELVIN)
CRI
MINIMUM
PROJECTED
LIFE
(HOURS)
MFR CATALOG SERIES MFR CATALOG SERIES
A22A 2' X 2' FLAT PANEL FIXTURE
WITH ALUMINUM TRIM AND
STEEL BACKING.
FROSTED
ACRYLIC LENS
CEILING
RECESSED
LAY-IN
LED 2,610 3500 80 L73 60,000 DIGITAL 120 V 29 W --- METALUX 22 FP SERIES LITHONIA
COLUMBIA
CREE
PHILIPS
EPANL SERIES
CFP22 SERIES
C-TR-C-FP22 SERIES
FZP SERIES
A22B 2' X 2' FLAT PANEL FIXTURE
WITH ALUMINUM TRIM, STEEL
BACKING AND DRYWALL
FLANGE.
FROSTED
ACRYLIC LENS
CEILING
RECESSED
LED 2,610 3500 80 L73 60,000 DIGITAL 120 V 29 W --- METALUX 22 FP SERIES LITHONIA
COLUMBIA
CREE
PHILIPS
EPANL SERIES
CFP22 SERIES
C-TR-C-FP22 SERIES
FZP SERIES
D1 6" DIAMETER SHOWER
DOWNLIGHT, FLUSH LENS
WITH WHITE PAINTED TRIM,
IP65 RATED WET LOCATION.
SMOOTH
CLEAR LENS
CEILING
RECESSED
LED 750 3500 90 L70 60,000 DIGITAL 120 V 8 W --- GOTHAM EVO6SH SERIES
E1 CONTEMPORARY LED SINGLE
FACED EXIT SIGN WITH BLACK
POWDER PAINT ALUMINUM
HOUSING, BRUSHED
ALUMINUM FACE, RED
LETTERS, AND CHEVRON
ARROWS AS SHOWN ON
PLANS.
--- UNIVERSAL LED --- --- --- 50,000 --- 120 V 5 W LITHONIA LES 1 SERIES GALAXY
SURE-LITES
XD & XDN SERIES
CX61 SERIES
EM2 EMERGENCY LIGHTING UNIT
EQUIPMENT WITH WHITE
HOUSING, BATTERY AND
CHARGER, TWO LED LAMP
HEADS, WITH
SELF-DIAGNOSTICS.
--- WALL LED 536 --- --- --- 120 V 1 W SURELITES SEL25-SD SERIES CHLORIDE
LIGHT GUARD
S236LT12WIC-T
SERIES
U236LT12WSC-T
SERIES
H1 RECTANGULAR HIGH BAY,
MEDIUM DISTRIBUTION,
LIGHTWEIGHT ALUMINUM
CONSTRUCTION, PAINTED
AFTER FABRICATION.
SEMI-DIFFUSE
ACRYLIC LENS
CEILING
SUSPENDED
(AIR-CRAFT
CABLE)
LED 12,000 3500 90 L70 100,000 DIGITAL 120 V 137 W --- LITHONIA IBHST SERIES
S1 4' LONG LENSED STRIP WITH
STEEL HOUSING, BAKED
WHITE ENAMEL FINISH.
CURVED
FULL-FROST
ACRYLIC LENS
CEILING
SUSPENDED
(AIR-CRAFT
CABLE)
LED 4,214 3500 80 L87 60,000 DIGITAL 120 V 35 W --- METALUX SNLED SERIES LITHONIA
ELITE
HE WILLIAMS
LSI
ZL1N SERIES
OEC-LED SERIES
75R SERIES
SDL4 SERIES
BB LED WALL PACK. FULL CUTOFF WALL LED 3,000 3500 70 L70 100,000 DIGITAL 120 V 47 W --- LUMARK WP SERIES
BB-E LED WALL PACK, WITH -40
DEGREE EMERGENCY
BATTERY.
FULL CUTOFF WALL LED 3,000 3500 70 L70 60,000 DIGITAL 120 V 47 W -40 DEGREE
COLD
WEATHER
BATTERY
LUMARK WP SERIES 1
30130 130
1. PROVIDE CONDUIT AND CONDUCTORS SCHEDULED FROM CIRCUIT BREAKER TO ACCU-1. PROVIDE CONDUIT AND CONDUCTORS SCHEDULED FROM ACCU-1
TO FCU. ALL EQUIPMENT (ACCU-1, FCU-1 AND FCU-2) SHALL BE FED FROM SAME CIRCUIT BREAKER ROUTED THROUGH EXTERIOR ACCU-1.
2. PROVIDE NEMA 3R DISCONNECT.
3. RECEIVE PUSHBUTTON OVERHEAD DOOR OPERATOR FROM GENERAL CONTRACTOR. INSTALL OPERATOR ON WALL AS INDICATED ON DRAWINGS.
PROVIDE CONDUIT AND CONDUCTOR BETWEEN MOTOR AND OPERATOR FOR A COMPLETE AND OPERABLE SYSTEM.
SCHEDULE NOTES:
F
IN
A L P
LO
T
D R A W
IN
G
S
TA
TU
S
P
LO
T D A
TE
P R O
JE
C T
LO
C A
TI
O N
D W G
N A M E
TREMPEALEAU COUNTY WISCONSIN
17-RF-007
05/22 AJM
3R-WI-162- 33
TREMPEALEAU NATIONAL WILDLIFE REFUGE
ADDITION TO 3 STALL GARAGE
REVISION DATE DESCRIPTION BY
DESIGNED DRAWN: DATE: CHECKED:
SHEET_____OF_____DRAWING NO:CADD:
PROJECT NUMBER
TPL .DWG
GENERAL DRAWING NOTE:
THE U.S. FISH AND WILDLIFE SERVICE, REGION 3 CADD DRAWINGS
ARE DRAWN ON A 22" X 34" STANDARD "D" SIZE SHEET (FULL
SIZE) 100%. WHEN PLOTTING DRAWINGS AT DIFFERENT
PERCENTAGES BAR SCALES ON DRAWINGS SHALL BE USED FOR
MEASURING.
B I M
U S F W
T r e m p e a l e a u
M a i n t
G a r a g e
A d d i t i o n
F W S
T r e m p e a u l e a u
M E P
C e n t r a l r v t
A M
AMLMJV
E11
ELECTRICAL SCHEDULES
M
JV
E11
ELECTRICAL EQUIPMENT SCHEDULE
NO. DESCRIPTION ROOM
LOAD
VOLT PHASE SCCR
CONDUIT &
WIRE SIZE
STARTER
COMPONENT
CONTROL
DEVICE
COMPONENT
DISCONNECT
COMPONENT NOTESHP
A
WFLA MCA
ACCU-1 SPLIT AC SYSTEM CONDENSING
UNIT
200 0 20 0 240 1 2#12, 1#12G, 3/4"C
W/UNIT T-STAT NFS 1,2
EF-1 FAN SIDEWALL 1/2 0 0 0 120 1 2#12, 1#12G,
3/4"C
W/UNIT DIV 23 NFS 2
EF-2 FAN SIDEWALL 1/12 0 0 0 120 1 2#12, 1#12G,
3/4"C
W/UNIT DIV 23 NFS 2
ERV-1 AIR TO AIR HEAT EXCHANGER 200 0 10 0 120 1 38 °F 2#12, 1#12G,
3/4"C
W/UNIT DIV 23 MRS
FCU-1 SPLIT AC SYSTEM FAN COIL UNIT 102 0 1 0 240 1 2#12, 1#12G,
3/4"C
W/UNIT DIV 23 MRS 1
FCU-2 SPLIT AC SYSTEM FAN COIL UNIT 103 0 1 0 240 1 2#12, 1#12G,
3/4"C
W/UNIT DIV 23 MRS 1
OHD OVERHEAD DOOR 100, 101 6.66 0 0 120 1 2#12, 1#12G,
3/4"C
W/UNIT PUSH BUTTON MRS 3
UH-1 UNIT HEATER 101 1/6 0 0 0 120 1 2#12, 1#12G,
3/4"C
W/UNIT T-STAT W/UNIT
WH-1 WATER HEATER 200 5 0 0 120 1 2#12, 1#12G,
3/4"C
W/UNIT DIV 23 MRS
WS-1 WATER SOFTENER 200 0.08 0 0 120 1 2#12, 1#12G,
3/4"C
W/UNIT DIV 23 W/UNIT
1. LIGHT TEXT INDICATES EXISTING LOADS; DARK TEXT INDICATES NEW LOADS. PANEL TOTALS SHOWN INCLUDE NEW LOADS ONLY.
2. PROVIDE (5) SQUARE D TYPE QO, 20A/1P CIRCUIT BREAKERS IN EXISTING PANEL TO SERVE NEW LOADS INDICATED.
NOTES:
EST. DEMAND CURRENT: 26 A
CONNECTED CURRENT: 23 A
MTR 3197 VA 106.25% 3397 VA ESTIMATED DEMAND: 6192 VA
LITES 2218 VA 125.00% 2773 VA CONNECTED LOAD: 5461 VA
RCPT 180 VA 100.00% 180 VA
LOAD CLASSIFICATION CONNECTED DEMAND ESTIMATED PANEL TOTALS
TOTAL AMPS: 25 A 21 A
TOTAL LOAD: 3 kVA 3 kVA
SPACE -- -- 19 0.0 0.0 20 -- -- SPACE
SPACE -- -- 17 0.0 0.0 18 -- -- SPACE
SPACE -- -- 15 0.0 0.0 16 -- -- SPACE
OHD 100 20 A 1 13 0.8 0.0 14 -- -- SPACE
OHD 100 20 A 1 11 0.8 0.0 12 -- -- SPACE
OHD 100 20 A 1 9 0.8 0.0 10 -- -- SPACE
OHD 100 20 A 1 7 0.8 0.0 8 -- -- SPACE
ELECTRIC GATE 20 A 1 5 0.0 1.0 6 1 20 A LIGHTS
GAS PUMP 20 A 1 3 0.0 1.0 4 1 20 A LIGHTS
WALL PACKS 20 A 1 1 0.3 0.2 2 1 20 A RECEPTACLES
LOAD DESCRIPTION BKR POLES CKT A B CKT POLES BKR LOAD DESCRIPTION
BUS AMPS: 100 AMPS
MAIN DEVICE: 100 A MAIN CB SPECIAL:
MOUNTING: SURFACE NEMA 1 A.I.C. RATING: 10,000 AMPS SYMMETRICAL
LOCATION: EXISTING VEHICLE STORAGE 100 VOLTAGE: 120/240 V. 1 ø 3 W.
PANELBOARD:EXIST
NOTES:
EST. DEMAND CURRENT: 229 A
SPEC 29069 VA 100.00% 29069 VA CONNECTED CURRENT: 223 A
MTR 10514 VA 111.24% 11696 VA ESTIMATED DEMAND: 55022 VA
LITES 1718 VA 125.00% 2148 VA…