A06 Drawings.pdf

PDF 6 MB Posted

Attached to
Rehab Warehouse Restrooms - Lake Mead National Rec
Solicitation number
140P8121R0001
Issued by

About this file

This package includes construction drawings and specifications for a restroom renovation project at Lake Mead National Recreation Area. The project scope involves demolishing existing restroom fixtures and installing new water closets, urinals, lavatories, a janitor's sink, and related plumbing fixtures in men's and women's restrooms. Mechanical drawings show demolition of the existing exhaust fan and installation of a new fan and roof-mounted relief hood. Electrical work includes occupancy sensors to control lighting and the new exhaust fan, as well as connections to an existing electrical panel. Bidders should examine site conditions before submitting responses for the solicitation to rehabilitate these government warehouse restrooms by the specified completion date.

View the file

Other files

Show all 14

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

RESTROOM

MEN'S

ABBREVIATIONS - MECHANICAL

ABV ABOVE

AC AIR CONDITIONING UNIT

ACC AIR COOLED CONDENSER

ACD AUTOMATIC CONTROL DAMPER

AD ACCESS DOOR

AHU AIR HANDLING UNIT

AL ACOUSTICAL LINING

ARCH ARCHITECTURAL

ATC AUTOMATIC TEMPERATURE CONTROL

BD BALANCING DAMPER

BDD BACK DRAFT DAMPER

BMS BUILDING MANAGEMENT SYSTEM

BO BLANK OFF

BHP BRAKE HORSE POWER

BTU BRITISH THERMAL UNIT

CD CEILING DIFFUSER

CFF CAP FOR FUTURE

CFM CUBIC FEET PER MINUTE

CG CEILING GRILLE

CO CLEAN OUT

CR CEILING REGISTER

DB DRY BULB

DIA DIAMETER

DN DOWN

DX DIRECT EXPANSION

(E) EXISTING TO REMAIN

EA EXHAUST AIR

EAT ENTERING AIR TEMPERATURE

EDB ENTERING DRY BULB

EF EXHAUST FAN

EFF EFFICIENCY

EWB ENTERING WET BULB

EWT ENTERING WATER TEMPERATURE

°F DEGREES FAHRENHEIT

F FILTER

FBO FURNISHED BY OTHERS

FC FLEXIBLE CONNECTION (DUCT OR PIPE)

FD FUSIBLE LINK FIRE DAMPER W/ DUCT ACCESS DOOR

FLR FLOOR

FLA FULL LOAD AMPS

FPI FINS PER INCH

FRE FIRE RATED ENCLOSURE

FSD COMBINATION FIRE AND SMOKE DAMPER

FT FEET

FTR FIN TUBE RADIATOR

GPM GALLONS PER MINUTE

GX GENERAL EXHAUST

HP HORSE POWER

HR HOUR

HW HOT WATER

ID INSIDE DIMENSION

KW KILOWATT

KWH KILOWATT HOURS

LAT LEAVING AIR TEMPERATURE

LBS POUNDS

LD LINEAR DIFFUSER (CEILING, WALL, SILL OR FLOOR)

LRA LOCK ROTOR AMPS

LWS LOUVER WITH WIRE SCREEN

LWT LEAVING WATER TEMPERATURE

MAT MIXED AIR TEMPERATURE

MAX MAXIMUM

MBH THOUSAND BTU PER HOUR

ABBREVIATIONS - MECHANICAL

MCC MOTOR CONTROL CENTER

MFG MANUFACTURER

MFS MAXIMUM FUSE SIZE

MIN MINIMUM

MUA MAKE UP AIR UNIT

MOCP MAXIMUM OVERCURRENT PROTECTION

(N) NEW

NC NORMALLY CLOSED

NFA NET FREE AREA

NIC NOT IN THIS CONTRACT

NK NECK

NO NORMALLY OPEN

NTS NOT TO SCALE

OAI OUTSIDE AIR INTAKE

OBD OPPOSED BLADE DAMPER

OD OUTSIDE DIMENSION

PD PRESSURE DROP

PRV PRESSURE REDUCING VALVE

PSI POUNDS PER SQUARE INCH (GAUGE)

PSIA POUNDS PER SQUARE INCH ABSOLUTE

(R) EXISTING TO BE RELOCATED

RA RETURN AIR

RF RETURN FAN

RH RELATIVE HUMIDITY

RPM REVOLUTIONS PER MINUTE

SA SUPPLY AIR

SAD SEE ARCHITECTURAL DRAWINGS

SF SUPPLY FAN

SED SEE ELECTRICAL DRAWINGS

SENS SENSIBLE

SM SHEET METAL

SP STATIC PRESSURE

SQFT SQUARE FEET

ST SOUND TRAP

TRD TRANSFER DUCT

TRG TRANSFER GRILLE

TX TOILET EXHAUST

TYP TYPICAL

UON UNLESS OTHERWISE NOTED

VAR VARIABLE

VD VOLUME DAMPER

VFD VARIABLE FREQUENCY DRIVE

W/ WITH

WB WET BULB

WG WATER GAUGE

WMS WIRE MESH SCREEN

WO-SIZE WALL OPENING - [SIZE]

(X) EXISTING TO BE DEMOLISHED

(300) CUBIC FEET OR AIR PER MINUTE OR GALLONS PER

MINUTE

1-WAY BLOW 3-WAY BLOW

4-WAY BLOW2-WAY BLOW

MECHANICAL LEGEND AND ABBREVIATIONS

R

D

18x12

18x12

DUCTWORK LEGEND

U

MISCELLANEOUS

LD-A,48x1,8Ø

(300) (300)

LD-A,48x1,8Ø

M3.1

CT

1-1

SR-A,12x8

M2.1

WO-SIZE

(200)

SR-A,12x8 (200)

(200) ER-C,12x8

(200) ER-C,12x8

CD-1,12x12 (550)

CD-1,12x12 (550)

DUCTWORK LEGEND (CONTINUED)

RETURN/EXHAUST REGISTER OR GRILLE

WITH FLEXIBLE DUCT CONNECTION

CEILING DIFFUSER WITH FLEXIBLE DUCT

CONNECTION

RETURN/EXHAUST REGISTER OR GRILLE

ROUND CEILING DIFFUSER WITH

FLEXIBLE DUCT CONNECTION

FLOOR SWIRL DIFFUSER

UNDERCUT DOOR

FIRE RATED ENCASED DUCT

TRANSFER GRILLES ON BOTH SIDES OF

PARTITION OR WALL (SIZE)

WALL OPENING ABOVE HUNG CEILING

(SIZE)

SUPPLY REGISTER WITH AIR OUTLET

DEVICE DESIGNATION

RETURN OR EXHAUST REGISTER OR

GRILLE WITH AIR INLET DEVICE

DESIGNATION

LINEAR DIFFUSER WITH PLENUM

LINEAR DIFFUSER

BACK DRAFT DAMPER WITH DUCT

ACCESS DOOR

VOLUME DAMPER IN DUCT

DUCT SPLIT WITH SPLIT SIZE

RADIUS ELBOW

RECTANGULAR SUPPLY DUCT UP

RECTANGULAR SUPPLY DUCT DOWN

RECTANGULAR RETURN OR EXHAUST

DUCT UP

RECTANGULAR RETURN OR EXHAUST

DUCT DOWN

ROUND DUCT,

UP

ROUND DUCT, DOWN

BEAM

PENETRATION

SLOPING RISE IN

DUCTWORK

SLOPING DROP IN DUCTWORK

DUCT SIZE (CLEAR INSIDE DIMENSION)

FIRST FIGURE INDICATES PLAN SIZE

ROUND DUCT DIAMETER SIZE (CLEAR

INSIDE DIMENSION)

OVAL DUCT SIZE

ACOUSTIC LINING IN DUCT (DUCT SIZE

NOTED INDICATES INSIDE DIMENSIONS)

FLEXIBLE CONNECTION

FLEXIBLE DUCT

DUCT COIL WITH ACCESS DOOR

NEW WORK

EXISTING WORK

EXISTING WORK TO BE REMOVED

POINT OF NEW CONNECTION TO EXISTING WORK

OVAL

DIAMETER

RISER DESIGNATION

SECTION DESIGNATION

DETAIL DESIGNATION

EQUIPMENT DESIGNATION

TERMINAL

DESIGNATION

AIR OUTLET/INLET

DEVICE

DESIGNATION

LINEAR DIFFUSER

DEVICE

DESIGNATION

RISER SERVICE

RISER NUMBER

SECTION NUMBER

DRAWING NUMBER

DETAIL NUMBER

DRAWING NUMBER

EQUIPMENT TYPE

EQUIPMENT FLOOR

AND NUMBER

3-24

THE NUMBER ON THE FLOOR

FLOOR OR LEVEL

TYPE

NECK OR FACE

SIZE

CFM

TYPE

LENGTH & SLOT

SIZE

PLENUM INLET SIZE

CFM

SIDE, TOP OR BOTTOM DUCT ACCESS

DOOR

ELBOW WITH TURNING VANES

RECTANGULAR OR SQUARE TO ROUND

OR OVAL TRANSITION

ROUND CEILING DIFFUSER

RECTANGULAR BRANCH TAKEOFF WITH

BALANCING DAMPER

3-24

HW

DUCT END/CAP8x6

8x616x6

16x6

DRAWING LIST

M0.1 MECHANICAL LEGEND AND ABBREVIATIONS

M0.2 MECHANICAL SCHEDULES AND DETAILS

M1.0 MECHANICAL FLOOR DEMOLITION PLAN

M1.2 MECHANICAL FLOOR PLAN

CEILING DIFFUSER

12/31/2019

07/19/19

NOTE 4

MAX.

1/2" CLEAR

TYPE III SEISMIC AIRCRAFT

CABLE (REFER TO

SPECIFICATION)

SPRING VIBRATION

ISOLATOR (REFER

TO SPECIFICATION)

HANGER ROD

SUSPENDED

EXHAUST FAN

DUAL U-BOLT

CABLE CLAMPS

CABLE

EYELET

LOCK NUT AND

WASHER

NOTES:

1. HANGER SPACING ALONG LENGTH OF UNIT TO BE AS FOLLOWS:

MINIMUM - 2 HANGERS MAXIMUM SPACING 6'-0".

2. PROVIDE ADEQUATE SEISMIC CABLE BRACING TO RESIST MOTION IN

ALL LATERAL DIRECTIONS.

3. REFER TO SMACNA SEISMIC RESTRAINT MANUAL GUIDELINES

(LATEST EDITION) FOR MECHANICAL SYSTEMS.

4. ATTACH TO STRUCTURE ABOVE.

SUSPENDED EXHAUST FAN WITH SEISMIC CABLES

NO SCALE

NOTES:

1. CONTROLLER INSTALLED ON TOP OF DIFFUSER AND

ADJUSTED THROUGH LAY-IN CEILING DIFFUSER

FRAME.

MAIN

DUCT

DIFFUSER

REMOTE

CONTROLLER

INACCESSIBLE

SUSPENDED CEILING

LOCKING GEAR

DRIVE CONTROLLER

KIT MOUNTED ON

TOP OF DIFFUSER

STAINLESS WIRE.

50 FEET MAXIMUM

EXTERNAL

CONTROLLED

VOLUME DAMPER

REMOTE CABLE DAMPER CONTROLLER

NO SCALE

RELIEF HOOD SUPPORT

NO SCALE

GRAVITY RELIEF HOOD

NEOPRENE GASKET

ALL AROUND

#10 SHEET METAL

SCREWS @ 6" O.C.

ROOFING

METAL ROOF

PREFABRICATED CURB

SUPPLIED BY HOOD

MFG.

NOTES:

1. SEE ARCHITECTURAL DRAWINGS FOR INSTALLATION

DETAIL TO ROOF.

FAN SCHEDULE

DESIGNATION SERVICE LOCATION

NUMBER OF

UNITS

MANUF.

MODEL

NUMBER

TYPE CFM

STATIC

PRESSURE

(IN WG)

RPM BHP

MOTOR

STANDBY

POWER

OPERATING

WEIGHT

(LBS)

VAR.

SPEED

(Y/N)

NOTES

HP

VOLTAGE/

PHASE

EF-1 RESTROOMS MEZZANINE 1

COOK 150SQN-HP

CENTRIFUGAL

INLINE

500 0.6 1079 0.12 0.25 120/1 NO 170 N

(1)(2)(3)(4)(5)

NOTES:

(1) FAN SELECTION BASED ON ELEVATION AT 2500 FT.

(2) FAN WITH 2-SPEED MOTOR (1140 RPM/860 RPM).

(3) PROVIDE DISCONNECT SWITCH.

(4) SEVEN DAY PROGRAMMABLE TIMER. (5) PROVIDE MOTOR COVER AND SPRING ISOLATORS.

AIR INLET AND OUTLET SCHEDULE

DESIGNATION

MANUFACTURER

MODEL NUMBER

SERVICE

FACE

DIMENSIONS

REMARKS

RG-A TITUS CT-700L RETURN SEE PLANS

(1)

EG-A TITUS 3FL EXHAUST SEE PLANS

(1)(2)

NOTES:

(1) COORDINATE FINAL DIFFUSER/GRILLE LOCATION, COLOR AND BORDER TYPE WITH ARCHITECT.

(2) PROVIDE YOUNG REGULATOR DAMPER FOR ACCESS TO VOLUME DAMPERS ABOVE INACCESSABLE OR HARD LID

CEILINGS.

VENTILATION CALCULATIONS - 2012 UNIFORM MECHANICAL CODE

Level

Space Info

2012 UMC Table Information 2012 UMC Calculations

Name

2012 UMC

Occ

Density

People

OA Rate

Area OA Rate Exhaust Rate

No of

Fixtures

Exhaust Rate

Pressure

Relationship

Exhaust

Rate

Room Type

(Select)

Pd

(#/1000

Sq Ft)

Rp

(CFM/P)

Ra

(CFM/SqFt)

CFM/Fixture # Fixtures

CFM/SqFt (0,P,N)

CFM

EXHAUSTED BY EF-1

FIRST FLOOR 109 WOMEN

Toilets - public

0 0 0 70 3 0 N 210

FIRST FLOOR 110 MEN

Toilets - public

0 0 0 70 4 0 N 280

TOTAL 490

RELIEF HOOD SCHEDULE

DESIGNATION

MANUF.

MODEL

NUMBER

LOCATION /

SERVICE

AIRFLOW

(CFM)

MAX AIR PD

(IN WG)

FREE AREA

(SQ. FT.)

THROAT AREA

(SQ. FT.)

THROAT

VELOCITY

(FPM)

NOTES

RH-1 COOK PR12 ROOF/RELIEF 500 0.10 2.04 0.852 1020

(1)

NOTES:

(1) ROOF CURB TO BE PROVIDED BY OTHERS.

EXHAUST FAN EF-1 CONTROL DIAGRAM

NO SCALE

EA

M

EA OS

120V/1PHM

DISCONNECT SWITCH

24V MOTORIZED

DAMPER RELAY FROM OCCUPANCY

SENSOR PROVIDED BY

ELECTRICAL CONTRACTOR

TM

RELAY FROM TIMER

FAN CONTROL PANEL

WITH TRANSFORMER TO

24V AND HAND-OFF-AUTO

SWITCH

SEQUENCE OF OPERATION OF EXHAUST FAN:

FAN RUNS AT LOW SPEED DURING OCCUPIED

HOURS AT SCHEDULE PROGRAMMED AT

TIMER.

FAN RUNS AT HIGH SPEED WHEN ACTIVATED

BY OCCUPANCY SENSOR THAT ALSO

ACTIVATES RESTROOM LIGHTING.

FAN IS NORMALLY OFF DURING BUILDING

UNOCCUPIED HOURS, UNLESS ACTIVATED BY

OCCUPANCY SENSOR THAT ALSO CONTROLS

RESTROOM LIGHTING.

GENERAL NOTES

A. FOR SYMBOLS AND ABBREVIATIONS, SEE DRAWING M0.1.

B. ALL HVAC COMPONENTS SHOWN ARE DIAGRAMMATIC. MECHANICAL CONTRACTOR

SHALL FIELD VERIFY EXISTING CONDITIONS PRIOR TO BUILDING AND START OF

CONSTRUCTION

C. COORDINATE EXACT CEILING DIFFUSER AND GRILLE LOCATIONS WITH ARCHITECTURAL

REFLECTED CEILING PLAN.

NUMBERED NOTES

1. DEMOLISH EXISTING EXHAUST FAN INCLUDING ASSOCIATED DUCTWORK, DAMPERS AND

CONTROLS.

2. DEMOLISH THE EXISTING SUPPLY AIR GRILLE, CLEAN AND SALVAGE FOR

REINSTALLATION AT NEW LOCATION.

x1 x8

EG-A,18x10 (290)

RG-A,16x16

TYP 2

10X8

10X8

M0.2

EG-A,18x10 (210)

M0.2

GENERAL NOTES

A. FOR SYMBOLS AND ABBREVIATIONS, SEE DRAWING M0.1.

B. ALL HVAC COMPONENTS SHOWN ARE DIAGRAMMATIC. MECHANICAL CONTRACTOR

SHALL FIELD VERIFY EXISTING CONDITIONS PRIOR TO BUILDING AND START OF

CONSTRUCTION

C. COORDINATE EXACT CEILING DIFFUSER AND GRILLE LOCATIONS WITH ARCHITECTURAL

REFLECTED CEILING PLAN.

NUMBERED NOTES

1. RELOCATED SUPPLY AIR GRILLE, CONNECT TO EXISTING DUCT. SEE ARCHITECTURAL

DRAWINGS FOR LOCATION.

2. DUCT UP TO MEZZANINE LEVEL, VERIFY EXACT LOCATION OF PENETRATION ON SITE.

3. PROVIDE GRILLE ON BOTH SIDES OF WALL. SEE ARCHITECTURAL DRAWINGS FOR

LOCATION.

4. VERTICALLY INSTALL EXHAUST FAN ON MEZZANINE LEVEL. COORDINATE EXACT

LOCATION WITH CONTRACTING OFFICER .

5. DUCT UP TO ROOF AND CONNECT TO ROOF RELIEF HOOD RH-1, COORDINATE EXACT

LOCATION OF PENETRATION WITH CONTRACTING OFFICER. INSTALL THE EXHAUST

DISCHARGE IN A WAY TO MAINTAIN A MINIMUM SEPARATION DISTANCE OF 10 FEET FROM

ANY OUTDOOR AIR INTAKES.

6. PROVIDE MOTORIZED DAMPER ON EXHAUST FAN DISCHARGE DUCT IN COMPLIANCE

WITH LOCAL ENERGY CONSERVATION CODE AND INTERLOCKED WITH EXHAUST FAN.

EF

4 5 6

EXISTING SUPPLY

AIR DUCT TO REMAIN

NEW FAN CONTROL

PANEL

NEW PROGRAMMABLE

TIMER

M0.2

RISER NO.

RISER

EQUIPMENT

EQUIPMENT NO.EQUIPMENT DESIGNATION

DWG. SHEET NO.

DETAIL NUMBER

REVISION NUMBER

DOMESTIC COLD WATER PIPING

NUMBERED NOTE NUMBER

DETAIL DESIGNATION

DOMESTIC HOT WATER PIPING

DOMESTIC HOT WATER RETURN PIPING

SLEEVE

PUMP

METER

FLOOR DRAIN, AREA DRAIN, PLANT DRAIN, GARAGE DRAIN

HOSE BIBB

POINT OF CONNECTION (NEW TO EXISTING)

ABBREVIATIONSABBREVIATIONS

PLUMBING LEGEND AND ABBREVIATIONS

LEGEND (CONTINUED)

WATER HAMMER ARRESTER

TOTAL DISCHARGE HEADTDH

RISE (WITH IN FLOOR)RISE

GARAGE DRAINGD

EXPANSION LOOP SIZE

FLEXIBLE CONNECTION

CUBIC FEET PER SECONDCFS

CUBIC FEET PER MINUTECFM

SOFT HOT WATER RETURNSHWR

SOFT HOT WATERSHW

SHOWERSH

TEMPERATURE MIXING VALVETMV

HD HUB DRAIN

EXPANSION TANKET

DRINKING FOUNTAINDF

ACCESS PANELAP

TRAP PRIMER VALVETPV

MH

MIN

MS

(N)

NC NORMALLY CLOSED

NEW

MOP SINK

MINIMUM

MANHOLE

OS&Y

P/FT

POC POINT OF CONNECTION

PITCH PER FOOT

OUTSIDE SCREW & YOKE GATE VALVE

NOT IN THIS CONTRACTNIC

PSI

PSIG

SK

SF

SINK

SQUARE FEET

POUNDS PER SQUARE INCH (GAUGE)

POUNDS PER SQUARE INCH

TOP

TYP

TS

UP

UR

UON

TOS TOP OF SLAB

UP (PENETRATES FLOOR SLAB)

UNLESS OTHERWISE NOTED

URINAL

TAMPER SWITCH

TYPICAL

TOP OF PIPE

VB

VTR

Z

WC WATER CLOSET

ZONE

VENT THROUGH ROOF

VACUUM BREAKER

VENTV

PRESSURE REDUCING VALVEPRV

Y STRAINER WITH BLOW OFF VALVE

LEGEND

PRESSURE REDUCING VALVE

OS&Y (OUTSIDE SCREW & YOKE) VALVE

VALVE (SPECIFICATION FOR TYPE)

CHECK VALVE

BALANCING VALVE

SOLENOID VALVE

UNION

PRESSURE GAUGE AND COCK

TEMPERATURE MIXING VALVE

VALVE WITH TAMPER SWITCH

AD

BLDG

AFF

BOB

BV

BOP

ABOVE FINISHED FLOOR

BOTTOM OF PIPE

BALANCING VALVE

BOTTOM OF THE BEAM

AREA DRAIN

BUILDING

CLG

COTG

CONN

CONT

CP

CLEANOUT TO GRADE

CONTINUATION

CIRCULATING PUMP

CEILING

CONNECTION

CV

CW

DN

DWG

DR

CHECK VALVE

COLD WATER

DOWN

DRAIN

DRAWING

EL

(E)

EWC

EWH

FCO

FD

ELEVATION

ELECTRIC WATER COOLER

FLOOR CLEANOUT

ELECTRIC WATER HEATER

FLOOR DRAIN

EXISTING

FL FLOOR

FT

FU FIXTURE UNIT

FEET

GAL

GPM

HW

GALLONS PER MINUTE

HOT WATER

GALLONS

HWR HOT WATER RETURN

CFH CUBIC FEET PER HOUR

CO CLEANOUT

FS FLOW SWITCH

BUTTERFLY VALVE (MANUAL)

GLOBE VALVE

SEISMIC JOINT

THERMOMETER

WATER FLOW SWITCH

GV GATE VALVE

DFU DRAINAGE FIXTURE UNIT

SAN SANITARY

HWCP HOT WATER CIRCULATING PUMP

RISER DESIGNATION

FLOOR NO.

(H)

(X)

(L)

M

CI CAST IRON

DIA DIAMETER

DROP (WITHIN FLOOR)DROP

EMERGENCY SHOWER/EYE WASHES

NORMALLY OPENNO

OD OUTSIDE DIAMETER

OFD OVERFLOW DRAIN

OST OVERFLOW STORM PIPING

EXISTING

RELOCATED

(R)

SHOCK ABSORBERSA

TRAP PRIMERTP

VR VENT RISE

WHA WATER HAMMER ARRESTER

WFU WATER FIXTURE UNIT

POST INDICATOR VALVE

SHOCK ABSORBER

VACUUM BREAKER

MANUAL AIR VENT

AUTOMATIC AIR VENT

RUNNING TRAP

BASKET STRAINER

CHECK VALVE WITH ABD

AUTOMATIC FLOW CONTROL VALVE

RELIEF VALVE

ANGLE RELIEF VALVE

REDUCER

ECCENTRIC REDUCER (E.R.)

PIV

M

A

X

X X-X

X

MISCELLANEOUS

INCHIN

INVERT ELEVATIONIE

IW INDIRECT WASTE

LDR

MAX MAXIMUM

LEADER

LAVATORYL

JS JANITOR SINK

kPa KILOPASCALS

LPS LITERS PER SECOND

M METERS

M² SQUARE METERS

M³ CUBIC METERS

mm MILLIMETER

ID INSIDE DIAMETER

REDUCED PRESSURE BACKFLOW PREVENTER ASSEMBLYRPBP

DOUBLE CHECK VALVE ASSEMBLY

SELF CONTAINED BREAHTING APPARATUS

DCVA

BA

VALVE IN VERTICAL

BOTTOM PIPE CONNECTION

TOP PIPE CONNECTION

V

SAN

SAN

VENT PIPING

SANITARY (ABOVE FLOOR)

SANITARY (BELOW FLOOR)

WASTE / VENT / STORM

EXISTING PIPING

CENTER LINEC

EXISTING PIPING TO BE REMOVED

PIPING LEGEND

CLEANOUT/PLUG

PIPE UP

P-TRAP

PIPE DOWN

FLOOR CLEANOUT/GRADE CLEANOUT

CHANGE IN PIPE ELEVATION

ARROW INDICATES DIRECTION OF FLOW

PITCH PIPE DOWN IN DIRECTION OF ARROW

CAP

INSULATED AND HEAT TRACED PIPING

FRESH AIR INLET

WALL HYDRANT

DRAWING LIST

P0.1 PLUMBING LEGEND AND ABBREVIATIONS

P0.2 PLUMBING SCHEDULES

P1.0 PLUMBING FLOOR DEMOLITION PLAN

P1.1 PLUMBING OVERALL FLOOR PLAN

P1.2 PLUMBING FLOOR PLAN

P4.1 PLUMBING RISER DIAGRAMS

P5.1 PLUMBING DETAILS

DOMESTIC TEMPERED WATER PIPINGTW

PLUMBING FIXTURE SCHEDULE

MARK

FIXTURE

DESCRIPTION BASIS OF DESIGN

CONNECTIONS

FLOW

RATE

GPF OR

GPM

NOTES

S V TRAP CW HW TW

WC-1 WATER CLOSET

FLOOR MOUNTED, ELONGATED

BOWL, SIPHON JET,

1.28 GPF, ADA

BRIGGS CARLTON MODEL #7790, CENTOCO

NO. 1500STSCCSS OPEN FRONT SEAL LESS

COVER, FLUSH VALVE SLOAN MODEL #

111-1.28

4" 2" 4" 1" - - 1.1

WC-2 WATER CLOSET

FLOOR MOUNTED, ELONGATED

BOWL, SIPHON JET,

1.28 GPF

BRIGGS CARLTON MODEL #7714, CENTOCO

NO. 1500STSCCSS OPEN FRONT SEAL LESS

COVER, FLUSH VALVE SLOAN MODEL #

111-1.28

4" 2" 4" 1" - - 1.1

UR-1 URINAL

WALL HUNG, HIGH EFFICIENCY, 0.125

GPF, ADA

BRIGGS LAWTON # 7552, 3/4" TOP SPUD WITH

SLOAN MODEL # 186-0.125 FLUSH VALVE,

ZURN FLOOR CARRIER Z-1218

2" 1-1/2" 2" 3/4" - - 0.125

L-1 LAVATORY

WALL HUNG, ADA

BRIGGS MILTON # 6620 WITH MOEN FAUCET

MODEL # 8420

1-1/2" 1-1/2" 1-1/4" 1/2" - 1/2" 0.35 1

MS-1 JANITOR'S SINK

FLOOR MOUNTED, TERRAZZO, 12"

DEPTH

FIAT MODEL # TSB300 WITH CHICAGO

MODEL # 897-CP FAUCET

3" 1-1/2" 3" 1/2" - 1/2" - 2

(E) DF-1

DRINK FOUNTAIN

EXISTING TO BE RELOCATED

MODEL ELKAY EZH2O

- 1-1/2" 1-1/2" 1-1/4" 1/2" - - -

(E) ES-1

EMERGENCY SHOWER/EYE WASH

EXISTING TO BE RELOCATED

MODEL BRADLEY

- - - - - - 1-1/4" 23

NOTES:

PROVIDE FLOOR CARRIER WITH CONCEALED ARMS, 1/2 GPM FLOW RESTRICTOR, INSULATE TRAP AND SUPPLIERS WITH TRUEBRO NO. 103 LAV GUARD.

PROVIDE MSG STAINLESS STEEL WALL GUARDS, STAINLESS STEEL CAPS ON ALL CURBS, 832AA HOSE & HOSE BRACKET AND 889CC MOP HANGER.

PLUMBING ELECTRIC WATER HEATER SCHEDULE

MARK FUEL SERVICE

LOCATION/

SERVICE

ELECTRICAL CHARACTERISTICS WATER CHARACTERISTICS

MANUFACTURER

BASIS OF

DESIGN

SIZE (IN) &

WEIGHT (LBS)

NOTES

AMPS KW V PH HZ

TANK

VOLUME

GAL

RECOVERY

CAPACITY GPH

EWT

DEG F

LWT

DEG F

CW CONN

IN

EWH-1 ELECTRIC

DOMESTIC HOT

WATER

FIRST

FLOOR

19 4.5 240 1 60 120 16 45 160 1-1/4"

BRADFORD

WHITE

E32-120R-3

28 1/4 DIA X 64 H

312 LBS

1,2

NOTES:

1. FACTORY INSTALLED T&P RELIEF VALVE AND DRAIN VALVE. 2. TOTAL WEIGHT WITH COMPLETELY FILLED WATER IS APPROX. 1300 LBS.

PLUMBING DRAIN SCHEDULE

TYPE DESCRIPTION OUTLET MANUFACTURER MODEL NUMBER GRATE NOTES

FD-1 FLOOR DRAIN 3" ZURN Z415S-P

5"x5" POLISHED NICKEL

BRONZE TOP

NOTES:

1. SQUARE TOP WITH TRAP PRIMER CONNECTION.

PLUMBING TEMPERATURE MIXING VALVE SCHEDULE

EQUIPMENT NUMBER EQUIPMENT DESCRIPTION

LOCATION LEVEL

& / OR ROOM

MAX

FLOW

(GPM)

PRESS

DROP

(PSI)

MANUFACTURER & MODEL NUMBER NOTES

TMV-1

DOMESTIC HOT WATER -

MIXING VALVE -

RESTROOMS

MEZZANINE 4 15 ACORN ST70-38 1

TMV-2

DOMESTIC HOT WATER

-EMERGENCY SHOWER

MEZZANINE

34 15

GUARDIAN G3700LF 1

NOTES:

1. LISTED EQUIPMENT MANUFACTURERS ARE THE BASIS OF DESIGN.

MINIMUM PLUMBING CHASE WALL WIDTH REQUIREMENTS

FIXTURE TYPE

FIXTURE MOUNTING

DESCRIPTION

DIMENSION FROM OUTER EDGE OF STUD TO OUTER EDGE OF STUD (INCHES)

SINGLE DOUBLE BACK TO BACK

DRINKING FOUNTAINS

WALL HUNG DRINKING FOUNTAIN 6" 6"

WALL HUNG WATER COOLER 12"

12", OFFSET

FLOOR DRAIN IN FLOOR 6" 6"

LAVATORY WALL HUNG 6" 6"

SERVICE SINK FLOOR MOUNT 6" 6"

WATER CLOSET

FLOOR MOUNT, FLUSH VALVE

6" 6"

FLOOR MOUNT, FLUSH VALVE

6" 6"

URINAL

WALL HUNG, FLUSH VALVE

6" 6"

NOTES:

1. FOR CONCRETE BLOCK WALLS, ALL DIMENSIONS SHOWN IN THIS TABLE ARE THE UNITERRUPTED INSIDE DIMENSIONS (NOT OUTSIDE DIMENSIONS).

2. WALL WIDTHS ARE THE MINIMUM REQUIRED FOR FIXTURE INSTALLATION. RISERS MAY REQUIRE ADDITIONAL WALL THICKNESS.

GENERAL NOTES

A. FIELD VERIFY EXISTING CONDITIONS OF PLUMBING

SYSTEMS NOT IN PLAIN VIEW. SUCH AS ABOVE

CEILINGS AND IN WALLS.

NUMBERED NOTES

1. DEMOLISH EXISTING PLUMBING FIXTURES INCLUDING

PIPING, VALVE AND ANY ACCESSORIES.

2. REMOVE AND SALVAGE EXISTING EMERGENCY

SHOWER/EYEWASH FOR REINSTALLATION AT NEW

LOCATION.

3. REMOVE AND SALVAGE EXISTING DRINKING FOUNTAIN

FOR REINSTALLATION AT NEW LOCATION.

E

S

A N

(E) CW 2"

CW 2"

P1.2

P1.2

NUMBERED NOTES

1. CONNECT TO EXITING 2" DCW STUB, FIELD VERIFY

EXACT LOCATION.

2. EXISTING 4" SANITARY WASTE PIPING, FIELD VERIFY

EXACT LOCATION.

3. INSTALL DOMESTIC COLD WATER PIPING ON

MEZZANINE LEVEL. FIELD VERIFY EXACT ROUTING.

WC-2WC-1

WC-1

WC-2

L-1

L-1

MS-1

(R) DF-1

(R) EW-1

EWH

TMV

TMV

WC-2

UR-1 UR-1

L-1 3

P5.1

P5.1

P5.1

GENERAL NOTES

A. FOR SYMBOLS AND ABBREVIATIONS, SEE DRAWING

P0.1.

B. SEE DRAWING P4.1 FOR PIPING SIZE NOT SHOWN ON

FLOOR PLANS.

NUMBERED NOTES

1. WATER HEATER P&T RELIEF VALVE DISCHARGE PIPE

ROUTED TO MOP SINK.

2. 2" CW UP, REFER TO SHEET P1.1 FOR CONTINUITY.

3. PROVIDE TRAP PRIMER VALVE AND INSTALL ON WALL.

4. CONNECT TO EXISTING PLUMBING VENT PIPING,

VERIFY EXACT LOCATION ON SITE.

WC-2WC-1

WC-1

WC-2

UR-1 L-1

L-1

MS-1

FD-1

FD-1

FD-1

(R) DF-1

(R) EW-1

CO3 4" SAN 4" SAN

V V

3" V UP 4

(E) 4"

SAN

WC-2

UR-1

L-1

FD-1

CONNECT TO EXISTING 2" DCW STUB-OUT.

CONNECT TO EXISTING 4" SANITARY WASTE PIPING.

CONNECT TO EXISTING PLUMBING VENT PIPING.

NUMBERED NOTES

FIRST LEVEL

MEZZANINE

EWH

WC-1 WC-1 WC-2 WC-2

UR-1

L-1 L-1L-1 MS-1 DF-1 ES-1

RESTROOMS

FIRST LEVEL

MEZZANINE

L-1 L-1

WC-1 WC-1 WC-2 WC-2

UR-1

L-1

FD-1

DF-1

VTR

V V

EWH

1RESTROOMS

CO

TW

TMV

TMV

TW

MS-1

SAN

2"

3"

(E) 4" 3"3"

2"2"3"

2"

3/4"3/4"

1-1/4" 1-1/4"

1-1/2"

FD-1

WC-2

UR-1

2" 2"

WC-2

FD-1

3"

4"4"

FD-1

SEE FLOOR PLANS

FOR CONTINUATION

(NORMALLY CLOSED)

TANK DRAIN VALVE

UNION (TYPICAL)

GATE VALVE (TYPICAL)

DRAIN

SPILL TO FLOOR

RELIEF VALVE

PRESSURE & TEMP.

FLOOR

S

STORAGE HEATER

VERTICAL ELECTRIC

ELECTRIC ELEMENT

GAUGE COCK (TYPICAL)

THERMOMETER WITH

CHECK VALVE

ELECTRIC DOMESTIC WATER HEATER

NO SCALE

AMTROL THERM-X-TROL

NO. ST-12 EXPANSION TANK

TP

TP8"x 1"

AIRGAP

45° BEVEL CUT

8"

1"

8"

CONNECT TRAP PRIMER INLET

TO FIXTURE

OUTLET TAILPIECE SIDE OF

TRAP

INSTALL TRAP PRIMER PIPING AND UNIT PER

MANUFACTURER'S RECOMMENDATIONS. PIPING

MUST SLOPE TO POINT OF CONNECTION TO

DRAIN WITHOUT TRAPS IN PIPING

3.

TRAP PRIMER VALVE SHALL BE MOUNTED ONE

FOOT ABOVE THE FINISHED FLOOR FOR EVERY 20

FEET OF PRIMER LINE.

2.

NOTES:

1. PROVIDE ACCESS PANEL IN WALLS AT TRAP

PRIMER UNIT LOCATIONS.

DISTRIBUTION UNIT(S)

(WHERE REQUIRED)

VACUUM BREAKER PORT

TRAP PRIMER VALVE

SHUT-OFF VALVE

COLD WATER LINE

8"

FLOOR SINK, FLOOR DRAIN OR

HUB DRAIN

~8"

TRAP PRIME INSTALLATION

NO SCALE

HC

CW

NOTE:

SEE PLUMBING TEMPERATURE MIXING VALVE SCHEDULE FOR SIZE

AND MAXIMUM FLOW.

TEMPERED WATER

UNION

BALL VALVE TO BALANCE SYSTEM

THERMOMETER

MIXING VALVE

NO SCALE

HW

DRAIN PAN

ELECTRICAL LEGEND AND ABBREVIATIONS

WIRING DEVICE SUBSCRIPT LEGEND

AC = ABOVE COUNTER

GFI = GROUND FAULT INTERRUPTER

IG = ISOLATED GROUND

WP = WEATHERPROOF

a = LOWER CASE LETTER INDICATES SWITCH

CONTROL

6 = NUMBER INDICATES CIRCUIT NUMBER

IG = ISOLATED GROUND (ONE OF DOUBLE DUPLEX)

a = LOWER CASE INDICATES SWITCH CONTROL

AC

GFI

IG

WP

a

IG

S a

WIRING DEVICE LEGEND

DUPLEX RECEPTACLE OUTLET: 125V; WALL MOUNTED

LOW VOLTAGE SWITCH

OCCUPANCY SENSOR; CEILING MOUNTEDOS

RACEWAY LEGEND

CONDUIT HOMERUN, MAXIMUM OF (3) BRANCH

CIRCUITS, UON

NOTE: MAXIMUM OF THREE BRANCH CIRCUITS FOR

EACH HOMERUN, UON

GROUNDING CONDUCTOR

PHASE CONDUCTOR(S)

ISOLATED GROUNDING CONDUCTOR

NEUTRAL CONDUCTOR

POWER LEGEND

MOTOR RATED SWITCH

MOTOR CONNECTION

JUNCTION BOX, CEILING MOUNTED

JUNCTION BOX, WALL MOUNTED

S M

M

J

J

LIGHTING LEGEND

LIGHTING FIXTURE DESIGNATIONS:

NUMBER (2) INDICATES CIRCUIT,

UPPERCASE LETTER (A) INDICATES RELAY,

LOWERCASE LETTER (a) INDICATES SWITCH CONTROL, F-XX INDICATES FIXTURE TYPE

LINEAR FLUORESCENT FIXTURE, SIZE

APPROXIMATELY AS SHOWN; CEILING RECESSED

LINEAR FLUORESCENT FIXTURE, SIZE

APPROXIMATELY AS SHOWN; RECESSED OR

CEILING MOUNTED

DOWNLIGHT FIXTURE, SIZE APPROXIMATELY AS

SHOWN; RECESSED OR CEILING MOUNTED

INTERIOR LIGHTING

LIGHTING NAMING LEGEND

2A a

F-XX

DRAWING LIST

E0.1 ELECTRICAL LEGEND & ABBREVIATIONS

E1.2 ELECTRICAL FLOOR PLANS

E4.1 ELECTRICAL SCHEDULES

E5.1 ELECTRICAL DETAILS

ABBREVIATIONS

CKT CIRCUIT

(E) EXISTING TO REMAIN

EMT ELECTRICAL METALLIC TUBING

GFI GROUND FAULT INTERRUPTOR

GND GROUND

MCP MOTOR CIRCUIT PROTECTOR

(N) NEW

NTS NOT TO SCALE

PVC POLYVINYL CHLORIDE CONDUIT

TYP TYPICAL

UON UNLESS OTHERWISE NOTED

UPS UNINTERRUPTIBLE POWER SUPPLY

WP WEATHERPROOF

(X) EXISTING TO BE REMOVED

FIRE ALARM LEGEND

VISUAL ALARM; WALL MOUNTED

E0.1

215790

LAKE MEAD NATIONAL RECREATION AREA

07/31/19

MMS

MAA

ARG

154865

ELECTRICAL LEGENDS

AND ABBREVIATIONS

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

DESIGNED:

AutoCAD SHX Text

TECH. REVIEW:

AutoCAD SHX Text

SUB SHEET NO.

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

SHEET

AutoCAD SHX Text

OF

AutoCAD SHX Text

TITLE OF SHEET

AutoCAD SHX Text

PMIS/PKG NO.

AutoCAD SHX Text

REHAB WAREHOUSE RESTROOMS

shaung Stamp

POWER FIRST FLOOR DEMOLITION PLAN

E1.1

SHEET NOTES

A. EXISTING RECEPTACLES AND POWER CONNECTIONS ARE SHOWN IN

APPROXIMATE LOCATIONS AND ARE BASED ON AVAILABLE

INFORMATION

B. EXAMINE THE SITE AND VERIFY ALL EXISTING CONDITIONS PRIOR TO

WORK. COORDINATE AREAS OF DEMOLITION WITH CONTRACTING

OFFICER IN FIELD PRIOR TO ACTUAL DEMOLITION

C. WHERE AN EXISTING CIRCUIT IS INTERRUPTED BY REMOVAL OF A

DEVICE OR FIXTURE FROM THAT CIRCUIT, PROVIDE ADDITIONAL

CONDUIT AND WIRE TO RESTORE SERVICE TO THE REMAINING

DEVICES AND FIXTURES ON THAT CIRCUIT.

D. WHERE DEVICES OR EQUIPMENT IS TO BE REMOVED, REMOVE ALL

CONDUITS, CONDUCTORS, J-BOXES AND SUPPORT ASSOCIATED

WITH DEVICES AND EQUIPMENT IN DEMOLITION SCOPE, UON.

E. ALL REUSED BRANCH CIRCUIT CONDUCTORS, CONDUITS AND J

BOXES SHALL REMAIN AS IS, EXTEND CIRCUIT TO NEW DEVICES

LOCATION IF NECESSARY.

F. EXISTING LIGHT FIXTURES AND CONTROLS SHOWN ARE BASED ON

AVAILABLE INFORMATION.

NUMBERED NOTES

UON, DEMOLISH ALL EXISTING POWER AND LIGHTING CIRCUITS BACK TO

SOURCE.

E1.1

215790

LAKE MEAD NATIONAL RECREATION AREA

07/31/19

MMS

MAA

ARG

154865

ELECTRICAL FLOOR

DEMOLITION PLAN

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

DESIGNED:

AutoCAD SHX Text

TECH. REVIEW:

AutoCAD SHX Text

SUB SHEET NO.

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

SHEET

AutoCAD SHX Text

OF

AutoCAD SHX Text

TITLE OF SHEET

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

SCALE OF FEET

AutoCAD SHX Text

PMIS/PKG NO.

AutoCAD SHX Text

REHAB WAREHOUSE RESTROOMS

POWER FIRST FLOOR PLAN

E1.2

GFI +42"

GFI

+42"

GFI

M

EF - 1

M

J

EWH - 1

J

PANEL # 4/13

PANEL # 4/15

PANEL #4

LT - 3

LT - 3

LT - 3

LT - 1 LT - 2

LT - 1

OS

OS

OS

OS

J

PANEL # 4/1

EM

EM

LT - 3

LT - 3

LT - 3

LT - 3

LT - 3

LT - 2

LT - 2

LIGHTING FIRST FLOOR PLAN

E1.2

SHEET NOTES

A. DRAWINGS ARE INTENDED TO SHOW GENERAL ARRANGEMENT,

DESIGN, AND EXTENT OF WORK AND ARE MORE OR LESS

DIAGRAMMATIC. DRAWINGS ARE NOT INTENDED TO SHOW

EXACT LOCATIONS EXCEPT WHERE DIMENSIONS ARE SHOWN.

ELECTRICAL WORK IS SHOWN ON PLANS USING STANDARD

INDUSTRY SYMBOLS. BEFORE ORDERING MATERIALS OR DOING

WORK, THE CONTRACTOR SHALL VERIFY ALL MEASUREMENTS

PERTAINING THERETO AND ASSUME RESPONSIBILITY

THEREFORE. ANY SUBSTANTIAL DIFFERENCES BETWEEN

DRAWINGS AND CONDITIONS IN THE FIELD SHALL BE SUBMITTED

TO THE CONSTRUCTION MANAGER FOR CONSIDERATION

BEFORE PROCEEDING WITH WORK.

B. WORK PERFORMED INCLUDES ALL LABOR, MATERIALS, AND

EQUIPMENT REQUIRED TO INSTALL A COMPLETE ELECTRICAL

SYSTEM AS INDICATED ON THESE DRAWINGS AND AS SPECIFIED.

C. REFER TO MECHANICAL EQUIPMENT WIRING SCHEDULE FOR

WIRING DISCONNECTS REQUIREMENTS.

D. CONTRACTOR SHALL VERIFY ALL EQUIPMENT SIZES AND POWER

REQUIREMENTS FOR EQUIPMENT PROVIDED BY OTHERS.

E. ALL ELECTRICAL CONDUITS AND JUNCTION BOXES IN FINISHED

SPACES SHALL BE CONCEALED. CONTRACTOR SHALL

COORDINATE WITH OTHER TRADES AND USE CHASES AND

CEILING SPACES PROVIDED.

F. CONTRACTOR, AT HIS/HER OPTION, MAY COMBINE CONDUIT

RUNS FOR FEEDERS PROVIDED THAT THE AMPERE RATING OF

THE CONDUCTORS AND ASSOCIATED CONDUIT ARE SIZED PER

NEC ARTICLE 310.

G. REFER TO ARCHITECTURAL, MECHANICAL AND PLUMBING PLANS

FOR EXACT LOCATION OF HVAC/PLUMBING EQUIPMENT.

H. PROVIDE CONDUIT, WIRE AND J-BOXES FOR CIRCUITING SHOWN.

QUANTITY AND SIZE OF J-BOXES TO BE DETERMINED BY

CONTRACTOR.

I. CONTRACTOR SHALL BE RESPONSIBLE FOR REPAIR OF ANY

ELECTRICAL AND DATA CIRCUITS AFFECTED BY CONSTRUCTION.

SUCH CIRCUITS WILL BE REPAIRED IMMEDIATELY. THERE WILL

BE NO DISRUPTION OF SERVICE OUTSIDE OF CONSTRUCTION

ZONE.

J. CONTRACTOR SHALL VERIFY ALL FIXTURE CATALOG NUMBERS

FOR ACCURACY. FIXTURE CATALOG NUMBERS ARE SUBJECT TO

CHANGE BY MANUFACTURER.

K. MOUNTING HEIGHTS SHOWN ARE FROM ABOVE FINISHED FLOOR

TO BOTTOM OF FIXTURE FOR PENDANT MOUNT FIXTURES AND

TO CENTER OF FIXTURE FOR WALL MOUNT FIXTURES UNLESS

OTHERWISE NOTED.

L. VERIFY CEILING TYPE BEFORE ORDERING LIGHTING FIXTURES.

NUMBERED NOTES

PROVIDE OCCUPANCY SENSOR WITH TWO(2) RELAYS. CONNECT RELAY #

1 TO LIGHTS IN THE ROOM AND RELAY # 2 TO EF-1.

FAN LOCATED AT MEZZANINE FLOOR ABOVE AND CONTROLLED BY

OCCUPANCY SENSORS IN MEN'S AND WOMEN'S RESTROOMS.

CONNECT EMERGENCY LIGHTS TO BUILDING EMERGENCY POWER.

CONNECT STROBE TO NEAREST FIRE ALARM CIRCUIT.

PANEL #4 IS LOCATED APPROXIMATELY 80' AWAY TO THE SOUTH ON

COLUMN. SEE DRAWING G1 FOR LOCATION.

SEE ARCHITECTURAL INTERIOR ELEVATIONS FOR LOCATION OF OUTLET.

E1.2

215790

LAKE MEAD NATIONAL RECREATION AREA

07/31/19

MMS

MAA

ARG

154865

ELECTRICAL FLOOR

PLANS

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

WOMEN

AutoCAD SHX Text

AutoCAD SHX Text

WOMEN VESTIBULE

AutoCAD SHX Text 109A

AutoCAD SHX Text

MEN

AutoCAD SHX Text

AutoCAD SHX Text

MEN VESTIBULE

AutoCAD SHX Text 110A

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text

WOMEN

AutoCAD SHX Text

AutoCAD SHX Text

WOMEN VESTIBULE

AutoCAD SHX Text 109A

AutoCAD SHX Text

MEN

AutoCAD SHX Text

AutoCAD SHX Text

MEN VESTIBULE

AutoCAD SHX Text 110A

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

DESIGNED:

AutoCAD SHX Text

TECH. REVIEW:

AutoCAD SHX Text

SUB SHEET NO.

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

SHEET

AutoCAD SHX Text

OF

AutoCAD SHX Text

TITLE OF SHEET

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

SCALE OF FEET

AutoCAD SHX Text

PMIS/PKG NO.

AutoCAD SHX Text

REHAB WAREHOUSE RESTROOMS

NUMBERED NOTES

METER PANEL FOR 30 DAYS WITH A MINIMUM OF 1 DATA POINT PER 15

MINUTES. PROVIDE ENGINEER WITH 7-DAYS AND 30-DAYS DATA FOR

VERIFICATION OF PANEL LOADING.

EQUIPMENT CONNECTION SCHEDULE

DESIGNATION HP FLA KVA

VOLT-

AGE

PH POWER SOURCE

CONNECTION

TYPE

BRANCH CIRCUIT WIRING REMARKS

EF-1 1/4 120 1 PANEL #4

SINGLE

CONNECTION

3/4"C - 2#10+1#10GND

EQUIPED WITH 2-SPEED CONTROLLER AND

TIMER.

EWH-1 4.50 240 1 PANEL #4

SINGLE

CONNECTION

3/4"C - 2#10+1#10GND

BUSSING:

100A, 10,000 AIC SYMMETRICAL

PANEL #4

LOCATION:

MAIN: 100A/3P MCB MOUNTING: SURFACE

T

Y

P

E

120/240V, 1 PHASE,

3 WIRE

T

Y

P

E

100% RATED NEUTRAL + GROUND

DESCRIPTION LOAD DEVICE CKT A B CKT DEVICE LOAD DESCRIPTION

L

RESTRM LGTS (N)

750 20/1 1

2 20/1 800

MAIN OFC RECEPS (E)

R

R

EXISTING LOAD (E)

800 20/1 3

4 20/1 800

BU MGR RECEPTS (E)

R

R

EXISTING LOAD (E)

800 20/1 5

6 20/1 696 EF-1 M

R

EXISTING LOAD (E)

800 20/1 7

8 20/1 800

RECEPTS AND LIGHTS (E)

L

R

EXISTING LOAD (E)

800 20/1 9

10 20/1 800

RECEPTS AND LIGHTS (E)

L

R

EXISTING LOAD (E)

800 20/1 11

12 20/1 800

MAIN OFC RECEP/NORTH (E)

R

R

RESTRM RECPTACLES (N)

360 20/1 13

25/2

WATER HEATER (N)

E

E

WATER COOLER (N)

600 20/1 15

16 2250 E

MAIN BREAKER 100/2

20/2

WATER HEATER (E)

E

20 1500 E

TOTAL ALL PHASES (VA) PHASE A (VA) PHASE B (VA) TOTAL ALL PHASES (AMPS)

17906 8756 9150 75

LOAD SUMMARY BY TYPE

CONN.

LOAD

DEMAND

FACTOR

NEC LOAD CONNECTED LOAD SUMMARY

E = EQUIPMENT 8100 VA 1.00 8100 VA 17906 VA

H = ELECTRIC HEAT 0 VA 1.00 0 VA 75 AMPS

K = KITCHEN EQUIPMENT 0 VA 1.00 0 VA

L = LIGHTING 2350 VA 1.25 2938 VA

M = MOTOR 696 VA 1.00 696 VA

M = LARGEST MOTOR 1.25 0 VA NEC LOAD SUMMARY

R = RECEPTACLE 6760 VA

NEC

DEMAND

6760 VA 18494 VA

77 AMPS

LUMINAIRE SCHEDULE

FIXTURE

TYPE

MANUFACTURER /

PRODUCT

DESCRIPTION

LAMP TYPE /

WATTAGE

BALLAST / DRIVER

CONNECTED LOAD /

VOLTAGE

MOUNTING NOTES/APPLICATION

LT-1

PHILIPS LEDALITE

3901-L-A-D-Q-S-3-XX-N-1

RECESSED MOUNT FIXTURE WITH FLUSH MESO OPTIC LENS. 41.8W/4 FT

0-10V, 1-100% DIMMING

120V

RECESSED

G.C. TO COORD. REQ'D

ACCESSORIES

LT-2

REMI LED BATH BAR

HINKLEY LIGHTING

SINGLE LED LIGHT SOURCE WITHIN AN ETCHED GLASS DIFFUSER WITH ALUMINUM

BACKPLATE AND MATCHING ENDCAPS. UL LISTED FOR DAMP APPLICATION.

36W, 3000 LM

LED, 3000k

INTEGRATED LED DRIVER 120V WALL MOUNTED

G.C. TO COORD. REQ'D

ACCESSORIES

LT-3

PHILIPS LIGHTOLIER

C4RN-

C4L30935MZ10U-C4RDL-XX

4” APERTURE LED DOWNLIGHT, SPECULAR CLEAR WITH FLANGE, MEDIUM BEAM

DISTRIBUTION.

31W, 3000LM

LED, 3500K

0-10V 1% DIMMING 120V RECESSED

G.C. TO COORD. REQ'D

ACCESSORIES

E4.1

215790

LAKE MEAD NATIONAL RECREATION AREA

07/31/19

MMS

MAA

ARG

154865

ELECTRICAL SCHEDULES

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

DESIGNED:

AutoCAD SHX Text

TECH. REVIEW:

AutoCAD SHX Text

SUB SHEET NO.

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

SHEET

AutoCAD SHX Text

OF

AutoCAD SHX Text

TITLE OF SHEET

AutoCAD SHX Text

PMIS/PKG NO.

AutoCAD SHX Text

REHAB WAREHOUSE RESTROOMS

+24 VDC

COMMON

CONTROL

OUTPUT

B L U

B L K

R E

D

POWER PACK

L

O

A

D

RED (LOAD)

WHITE/NEUTRAL

N

HOT

RED (LINE)

WHT

BLK

OFF SWITCH

Any 24VDC Sensor

Ceiling or Wall Mounted

LIGHTING CONTROL SCHEMATIC

NO SCALE

LV

b

LV

a

ON/OFF LOW VOTAGE SWITCH

ON/OFF LOW VOTAGE SWITCH

SWITCH OR RELAY

CONTROLLED

LINE VOLTAGE BALLAST

LIGHTS

LIGHTS

SWITCHED OR RELAY

CONTROLLED LINE

VOLTAGE

BALLAST

LIGHTING ROOM

CONTROLLER

LIGHTING ROOM

CONTROLLER

NORMAL

POWER

CIRCUIT (HOT)

NORMAL

POWER.

(NEUTRAL)

OCCUPANCY SENSOR

DETAIL

NO SCALE

E5.1

215790

LAKE MEAD NATIONAL RECREATION AREA

07/31/19

MMS

MAA

ARG

154865

ELECTRICAL DETAILS

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

DESIGNED:

AutoCAD SHX Text

TECH. REVIEW:

AutoCAD SHX Text

SUB SHEET NO.

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

SHEET

AutoCAD SHX Text

OF

AutoCAD SHX Text

TITLE OF SHEET

AutoCAD SHX Text

PMIS/PKG NO.

AutoCAD SHX Text

REHAB WAREHOUSE RESTROOMS

215790 LAKE Rehab Restrooms_100% Final Construction Drawings
G0_Cover
G1 BUILDING PLAN
A0.1 ABRV SYMB NOTES
A0.2 ASSEMBLIES
AD1.1 DEMO FLOOR PLAN/RCP
A1.1 FLOOR PLAN/RCP
A4.2 INTERIOR ELEVATIONS
A5.1 INTERIOR DETAILS
A5.2 INTERIOR DETAILS
MECH 100% CD
M0.1 MECHANICAL LEGENDS AND ABBREVIATIONS
M0.2 MECHANICAL SCHEDULES AND DETAILS
M1.0 MECHANICAL FLOOR DEMOLITION PLAN
M1.2 MECHANICAL FLOOR PLAN
PLUMBING 100% CD
P0.1 PLUMBING LEGENDS AND ABBREVIATIONS
P0.2 PLUMBING SCHEDULES
P1.0 PLUMBING FLOOR DEMOLITION PLAN
P1.1 PLUMBING OVERALL FLOOR PLAN
P1.2 PLUMBING FLOOR PLAN
P4.1 PLUMBING RISER DIAGRAMS
P5.1 PLUMBING DETAILS
ELECTRICAL 100% CD
E0.1 ELECTRICAL LEGENDS AND ABBREVIATIONS
E1.1 ELECTRICAL FLOOR DEMOLITION PLAN
E1.2 ELECTRICAL FLOOR PLANS
E4.1 ELECTRICAL SCHEDULES
E5.1 ELECTRICAL DETAILS

File details come from the government source that posted it. Updated .