This package includes construction drawings and specifications for a restroom renovation project at Lake Mead National Recreation Area. The project scope involves demolishing existing restroom fixtures and installing new water closets, urinals, lavatories, a janitor's sink, and related plumbing fixtures in men's and women's restrooms. Mechanical drawings show demolition of the existing exhaust fan and installation of a new fan and roof-mounted relief hood. Electrical work includes occupancy sensors to control lighting and the new exhaust fan, as well as connections to an existing electrical panel. Bidders should examine site conditions before submitting responses for the solicitation to rehabilitate these government warehouse restrooms by the specified completion date.
View the file
Other files
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
RESTROOM
MEN'S
ABBREVIATIONS - MECHANICAL
ABV ABOVE
AC AIR CONDITIONING UNIT
ACC AIR COOLED CONDENSER
ACD AUTOMATIC CONTROL DAMPER
AD ACCESS DOOR
AHU AIR HANDLING UNIT
AL ACOUSTICAL LINING
ARCH ARCHITECTURAL
ATC AUTOMATIC TEMPERATURE CONTROL
BD BALANCING DAMPER
BDD BACK DRAFT DAMPER
BMS BUILDING MANAGEMENT SYSTEM
BO BLANK OFF
BHP BRAKE HORSE POWER
BTU BRITISH THERMAL UNIT
CD CEILING DIFFUSER
CFF CAP FOR FUTURE
CFM CUBIC FEET PER MINUTE
CG CEILING GRILLE
CO CLEAN OUT
CR CEILING REGISTER
DB DRY BULB
DIA DIAMETER
DN DOWN
DX DIRECT EXPANSION
(E) EXISTING TO REMAIN
EA EXHAUST AIR
EAT ENTERING AIR TEMPERATURE
EDB ENTERING DRY BULB
EF EXHAUST FAN
EFF EFFICIENCY
EWB ENTERING WET BULB
EWT ENTERING WATER TEMPERATURE
°F DEGREES FAHRENHEIT
F FILTER
FBO FURNISHED BY OTHERS
FC FLEXIBLE CONNECTION (DUCT OR PIPE)
FD FUSIBLE LINK FIRE DAMPER W/ DUCT ACCESS DOOR
FLR FLOOR
FLA FULL LOAD AMPS
FPI FINS PER INCH
FRE FIRE RATED ENCLOSURE
FSD COMBINATION FIRE AND SMOKE DAMPER
FT FEET
FTR FIN TUBE RADIATOR
GPM GALLONS PER MINUTE
GX GENERAL EXHAUST
HP HORSE POWER
HR HOUR
HW HOT WATER
ID INSIDE DIMENSION
KW KILOWATT
KWH KILOWATT HOURS
LAT LEAVING AIR TEMPERATURE
LBS POUNDS
LD LINEAR DIFFUSER (CEILING, WALL, SILL OR FLOOR)
LRA LOCK ROTOR AMPS
LWS LOUVER WITH WIRE SCREEN
LWT LEAVING WATER TEMPERATURE
MAT MIXED AIR TEMPERATURE
MAX MAXIMUM
MBH THOUSAND BTU PER HOUR
ABBREVIATIONS - MECHANICAL
MCC MOTOR CONTROL CENTER
MFG MANUFACTURER
MFS MAXIMUM FUSE SIZE
MIN MINIMUM
MUA MAKE UP AIR UNIT
MOCP MAXIMUM OVERCURRENT PROTECTION
(N) NEW
NC NORMALLY CLOSED
NFA NET FREE AREA
NIC NOT IN THIS CONTRACT
NK NECK
NO NORMALLY OPEN
NTS NOT TO SCALE
OAI OUTSIDE AIR INTAKE
OBD OPPOSED BLADE DAMPER
OD OUTSIDE DIMENSION
PD PRESSURE DROP
PRV PRESSURE REDUCING VALVE
PSI POUNDS PER SQUARE INCH (GAUGE)
PSIA POUNDS PER SQUARE INCH ABSOLUTE
(R) EXISTING TO BE RELOCATED
RA RETURN AIR
RF RETURN FAN
RH RELATIVE HUMIDITY
RPM REVOLUTIONS PER MINUTE
SA SUPPLY AIR
SAD SEE ARCHITECTURAL DRAWINGS
SF SUPPLY FAN
SED SEE ELECTRICAL DRAWINGS
SENS SENSIBLE
SM SHEET METAL
SP STATIC PRESSURE
SQFT SQUARE FEET
ST SOUND TRAP
TRD TRANSFER DUCT
TRG TRANSFER GRILLE
TX TOILET EXHAUST
TYP TYPICAL
UON UNLESS OTHERWISE NOTED
VAR VARIABLE
VD VOLUME DAMPER
VFD VARIABLE FREQUENCY DRIVE
W/ WITH
WB WET BULB
WG WATER GAUGE
WMS WIRE MESH SCREEN
WO-SIZE WALL OPENING - [SIZE]
(X) EXISTING TO BE DEMOLISHED
(300) CUBIC FEET OR AIR PER MINUTE OR GALLONS PER
MINUTE
1-WAY BLOW 3-WAY BLOW
4-WAY BLOW2-WAY BLOW
MECHANICAL LEGEND AND ABBREVIATIONS
R
D
18x12
18x12
DUCTWORK LEGEND
U
MISCELLANEOUS
LD-A,48x1,8Ø
(300) (300)
LD-A,48x1,8Ø
M3.1
CT
1-1
SR-A,12x8
M2.1
WO-SIZE
(200)
SR-A,12x8 (200)
(200) ER-C,12x8
(200) ER-C,12x8
CD-1,12x12 (550)
CD-1,12x12 (550)
DUCTWORK LEGEND (CONTINUED)
RETURN/EXHAUST REGISTER OR GRILLE
WITH FLEXIBLE DUCT CONNECTION
CEILING DIFFUSER WITH FLEXIBLE DUCT
CONNECTION
RETURN/EXHAUST REGISTER OR GRILLE
ROUND CEILING DIFFUSER WITH
FLEXIBLE DUCT CONNECTION
FLOOR SWIRL DIFFUSER
UNDERCUT DOOR
FIRE RATED ENCASED DUCT
TRANSFER GRILLES ON BOTH SIDES OF
PARTITION OR WALL (SIZE)
WALL OPENING ABOVE HUNG CEILING
(SIZE)
SUPPLY REGISTER WITH AIR OUTLET
DEVICE DESIGNATION
RETURN OR EXHAUST REGISTER OR
GRILLE WITH AIR INLET DEVICE
DESIGNATION
LINEAR DIFFUSER WITH PLENUM
LINEAR DIFFUSER
BACK DRAFT DAMPER WITH DUCT
ACCESS DOOR
VOLUME DAMPER IN DUCT
DUCT SPLIT WITH SPLIT SIZE
RADIUS ELBOW
RECTANGULAR SUPPLY DUCT UP
RECTANGULAR SUPPLY DUCT DOWN
RECTANGULAR RETURN OR EXHAUST
DUCT UP
RECTANGULAR RETURN OR EXHAUST
DUCT DOWN
ROUND DUCT,
UP
ROUND DUCT, DOWN
BEAM
PENETRATION
SLOPING RISE IN
DUCTWORK
SLOPING DROP IN DUCTWORK
DUCT SIZE (CLEAR INSIDE DIMENSION)
FIRST FIGURE INDICATES PLAN SIZE
ROUND DUCT DIAMETER SIZE (CLEAR
INSIDE DIMENSION)
OVAL DUCT SIZE
ACOUSTIC LINING IN DUCT (DUCT SIZE
NOTED INDICATES INSIDE DIMENSIONS)
FLEXIBLE CONNECTION
FLEXIBLE DUCT
DUCT COIL WITH ACCESS DOOR
NEW WORK
EXISTING WORK
EXISTING WORK TO BE REMOVED
POINT OF NEW CONNECTION TO EXISTING WORK
OVAL
DIAMETER
RISER DESIGNATION
SECTION DESIGNATION
DETAIL DESIGNATION
EQUIPMENT DESIGNATION
TERMINAL
DESIGNATION
AIR OUTLET/INLET
DEVICE
DESIGNATION
LINEAR DIFFUSER
DEVICE
DESIGNATION
RISER SERVICE
RISER NUMBER
SECTION NUMBER
DRAWING NUMBER
DETAIL NUMBER
DRAWING NUMBER
EQUIPMENT TYPE
EQUIPMENT FLOOR
AND NUMBER
3-24
THE NUMBER ON THE FLOOR
FLOOR OR LEVEL
TYPE
NECK OR FACE
SIZE
CFM
TYPE
LENGTH & SLOT
SIZE
PLENUM INLET SIZE
CFM
SIDE, TOP OR BOTTOM DUCT ACCESS
DOOR
ELBOW WITH TURNING VANES
RECTANGULAR OR SQUARE TO ROUND
OR OVAL TRANSITION
ROUND CEILING DIFFUSER
RECTANGULAR BRANCH TAKEOFF WITH
BALANCING DAMPER
3-24
HW
DUCT END/CAP8x6
8x616x6
16x6
DRAWING LIST
M0.1 MECHANICAL LEGEND AND ABBREVIATIONS
M0.2 MECHANICAL SCHEDULES AND DETAILS
M1.0 MECHANICAL FLOOR DEMOLITION PLAN
M1.2 MECHANICAL FLOOR PLAN
CEILING DIFFUSER
12/31/2019
07/19/19
NOTE 4
MAX.
1/2" CLEAR
TYPE III SEISMIC AIRCRAFT
CABLE (REFER TO
SPECIFICATION)
SPRING VIBRATION
ISOLATOR (REFER
TO SPECIFICATION)
HANGER ROD
SUSPENDED
EXHAUST FAN
DUAL U-BOLT
CABLE CLAMPS
CABLE
EYELET
LOCK NUT AND
WASHER
NOTES:
1. HANGER SPACING ALONG LENGTH OF UNIT TO BE AS FOLLOWS:
MINIMUM - 2 HANGERS MAXIMUM SPACING 6'-0".
2. PROVIDE ADEQUATE SEISMIC CABLE BRACING TO RESIST MOTION IN
ALL LATERAL DIRECTIONS.
3. REFER TO SMACNA SEISMIC RESTRAINT MANUAL GUIDELINES
(LATEST EDITION) FOR MECHANICAL SYSTEMS.
4. ATTACH TO STRUCTURE ABOVE.
SUSPENDED EXHAUST FAN WITH SEISMIC CABLES
NO SCALE
NOTES:
1. CONTROLLER INSTALLED ON TOP OF DIFFUSER AND
ADJUSTED THROUGH LAY-IN CEILING DIFFUSER
FRAME.
MAIN
DUCT
DIFFUSER
REMOTE
CONTROLLER
INACCESSIBLE
SUSPENDED CEILING
LOCKING GEAR
DRIVE CONTROLLER
KIT MOUNTED ON
TOP OF DIFFUSER
STAINLESS WIRE.
50 FEET MAXIMUM
EXTERNAL
CONTROLLED
VOLUME DAMPER
REMOTE CABLE DAMPER CONTROLLER
NO SCALE
RELIEF HOOD SUPPORT
NO SCALE
GRAVITY RELIEF HOOD
NEOPRENE GASKET
ALL AROUND
#10 SHEET METAL
SCREWS @ 6" O.C.
ROOFING
METAL ROOF
PREFABRICATED CURB
SUPPLIED BY HOOD
MFG.
NOTES:
1. SEE ARCHITECTURAL DRAWINGS FOR INSTALLATION
DETAIL TO ROOF.
FAN SCHEDULE
DESIGNATION SERVICE LOCATION
NUMBER OF
UNITS
MANUF.
MODEL
NUMBER
TYPE CFM
STATIC
PRESSURE
(IN WG)
RPM BHP
MOTOR
STANDBY
POWER
OPERATING
WEIGHT
(LBS)
VAR.
SPEED
(Y/N)
NOTES
HP
VOLTAGE/
PHASE
EF-1 RESTROOMS MEZZANINE 1
COOK 150SQN-HP
CENTRIFUGAL
INLINE
500 0.6 1079 0.12 0.25 120/1 NO 170 N
(1)(2)(3)(4)(5)
NOTES:
(1) FAN SELECTION BASED ON ELEVATION AT 2500 FT.
(2) FAN WITH 2-SPEED MOTOR (1140 RPM/860 RPM).
(3) PROVIDE DISCONNECT SWITCH.
(4) SEVEN DAY PROGRAMMABLE TIMER. (5) PROVIDE MOTOR COVER AND SPRING ISOLATORS.
AIR INLET AND OUTLET SCHEDULE
DESIGNATION
MANUFACTURER
MODEL NUMBER
SERVICE
FACE
DIMENSIONS
REMARKS
RG-A TITUS CT-700L RETURN SEE PLANS
(1)
EG-A TITUS 3FL EXHAUST SEE PLANS
(1)(2)
NOTES:
(1) COORDINATE FINAL DIFFUSER/GRILLE LOCATION, COLOR AND BORDER TYPE WITH ARCHITECT.
(2) PROVIDE YOUNG REGULATOR DAMPER FOR ACCESS TO VOLUME DAMPERS ABOVE INACCESSABLE OR HARD LID
CEILINGS.
VENTILATION CALCULATIONS - 2012 UNIFORM MECHANICAL CODE
Level
Space Info
2012 UMC Table Information 2012 UMC Calculations
Name
2012 UMC
Occ
Density
People
OA Rate
Area OA Rate Exhaust Rate
No of
Fixtures
Exhaust Rate
Pressure
Relationship
Exhaust
Rate
Room Type
(Select)
Pd
(#/1000
Sq Ft)
Rp
(CFM/P)
Ra
(CFM/SqFt)
CFM/Fixture # Fixtures
CFM/SqFt (0,P,N)
CFM
EXHAUSTED BY EF-1
FIRST FLOOR 109 WOMEN
Toilets - public
0 0 0 70 3 0 N 210
FIRST FLOOR 110 MEN
Toilets - public
0 0 0 70 4 0 N 280
TOTAL 490
RELIEF HOOD SCHEDULE
DESIGNATION
MANUF.
MODEL
NUMBER
LOCATION /
SERVICE
AIRFLOW
(CFM)
MAX AIR PD
(IN WG)
FREE AREA
(SQ. FT.)
THROAT AREA
(SQ. FT.)
THROAT
VELOCITY
(FPM)
NOTES
RH-1 COOK PR12 ROOF/RELIEF 500 0.10 2.04 0.852 1020
(1)
NOTES:
(1) ROOF CURB TO BE PROVIDED BY OTHERS.
EXHAUST FAN EF-1 CONTROL DIAGRAM
NO SCALE
EA
M
EA OS
120V/1PHM
DISCONNECT SWITCH
24V MOTORIZED
DAMPER RELAY FROM OCCUPANCY
SENSOR PROVIDED BY
ELECTRICAL CONTRACTOR
TM
RELAY FROM TIMER
FAN CONTROL PANEL
WITH TRANSFORMER TO
24V AND HAND-OFF-AUTO
SWITCH
SEQUENCE OF OPERATION OF EXHAUST FAN:
FAN RUNS AT LOW SPEED DURING OCCUPIED
HOURS AT SCHEDULE PROGRAMMED AT
TIMER.
FAN RUNS AT HIGH SPEED WHEN ACTIVATED
BY OCCUPANCY SENSOR THAT ALSO
ACTIVATES RESTROOM LIGHTING.
FAN IS NORMALLY OFF DURING BUILDING
UNOCCUPIED HOURS, UNLESS ACTIVATED BY
OCCUPANCY SENSOR THAT ALSO CONTROLS
RESTROOM LIGHTING.
GENERAL NOTES
A. FOR SYMBOLS AND ABBREVIATIONS, SEE DRAWING M0.1.
B. ALL HVAC COMPONENTS SHOWN ARE DIAGRAMMATIC. MECHANICAL CONTRACTOR
SHALL FIELD VERIFY EXISTING CONDITIONS PRIOR TO BUILDING AND START OF
CONSTRUCTION
C. COORDINATE EXACT CEILING DIFFUSER AND GRILLE LOCATIONS WITH ARCHITECTURAL
REFLECTED CEILING PLAN.
NUMBERED NOTES
1. DEMOLISH EXISTING EXHAUST FAN INCLUDING ASSOCIATED DUCTWORK, DAMPERS AND
CONTROLS.
2. DEMOLISH THE EXISTING SUPPLY AIR GRILLE, CLEAN AND SALVAGE FOR
REINSTALLATION AT NEW LOCATION.
x1 x8
EG-A,18x10 (290)
RG-A,16x16
TYP 2
10X8
10X8
M0.2
EG-A,18x10 (210)
M0.2
GENERAL NOTES
A. FOR SYMBOLS AND ABBREVIATIONS, SEE DRAWING M0.1.
B. ALL HVAC COMPONENTS SHOWN ARE DIAGRAMMATIC. MECHANICAL CONTRACTOR
SHALL FIELD VERIFY EXISTING CONDITIONS PRIOR TO BUILDING AND START OF
CONSTRUCTION
C. COORDINATE EXACT CEILING DIFFUSER AND GRILLE LOCATIONS WITH ARCHITECTURAL
REFLECTED CEILING PLAN.
NUMBERED NOTES
1. RELOCATED SUPPLY AIR GRILLE, CONNECT TO EXISTING DUCT. SEE ARCHITECTURAL
DRAWINGS FOR LOCATION.
2. DUCT UP TO MEZZANINE LEVEL, VERIFY EXACT LOCATION OF PENETRATION ON SITE.
3. PROVIDE GRILLE ON BOTH SIDES OF WALL. SEE ARCHITECTURAL DRAWINGS FOR
LOCATION.
4. VERTICALLY INSTALL EXHAUST FAN ON MEZZANINE LEVEL. COORDINATE EXACT
LOCATION WITH CONTRACTING OFFICER .
5. DUCT UP TO ROOF AND CONNECT TO ROOF RELIEF HOOD RH-1, COORDINATE EXACT
LOCATION OF PENETRATION WITH CONTRACTING OFFICER. INSTALL THE EXHAUST
DISCHARGE IN A WAY TO MAINTAIN A MINIMUM SEPARATION DISTANCE OF 10 FEET FROM
ANY OUTDOOR AIR INTAKES.
6. PROVIDE MOTORIZED DAMPER ON EXHAUST FAN DISCHARGE DUCT IN COMPLIANCE
WITH LOCAL ENERGY CONSERVATION CODE AND INTERLOCKED WITH EXHAUST FAN.
EF
4 5 6
EXISTING SUPPLY
AIR DUCT TO REMAIN
NEW FAN CONTROL
PANEL
NEW PROGRAMMABLE
TIMER
M0.2
RISER NO.
RISER
EQUIPMENT
EQUIPMENT NO.EQUIPMENT DESIGNATION
DWG. SHEET NO.
DETAIL NUMBER
REVISION NUMBER
DOMESTIC COLD WATER PIPING
NUMBERED NOTE NUMBER
DETAIL DESIGNATION
DOMESTIC HOT WATER PIPING
DOMESTIC HOT WATER RETURN PIPING
SLEEVE
PUMP
METER
FLOOR DRAIN, AREA DRAIN, PLANT DRAIN, GARAGE DRAIN
HOSE BIBB
POINT OF CONNECTION (NEW TO EXISTING)
ABBREVIATIONSABBREVIATIONS
PLUMBING LEGEND AND ABBREVIATIONS
LEGEND (CONTINUED)
WATER HAMMER ARRESTER
TOTAL DISCHARGE HEADTDH
RISE (WITH IN FLOOR)RISE
GARAGE DRAINGD
EXPANSION LOOP SIZE
FLEXIBLE CONNECTION
CUBIC FEET PER SECONDCFS
CUBIC FEET PER MINUTECFM
SOFT HOT WATER RETURNSHWR
SOFT HOT WATERSHW
SHOWERSH
TEMPERATURE MIXING VALVETMV
HD HUB DRAIN
EXPANSION TANKET
DRINKING FOUNTAINDF
ACCESS PANELAP
TRAP PRIMER VALVETPV
MH
MIN
MS
(N)
NC NORMALLY CLOSED
NEW
MOP SINK
MINIMUM
MANHOLE
OS&Y
P/FT
POC POINT OF CONNECTION
PITCH PER FOOT
OUTSIDE SCREW & YOKE GATE VALVE
NOT IN THIS CONTRACTNIC
PSI
PSIG
SK
SF
SINK
SQUARE FEET
POUNDS PER SQUARE INCH (GAUGE)
POUNDS PER SQUARE INCH
TOP
TYP
TS
UP
UR
UON
TOS TOP OF SLAB
UP (PENETRATES FLOOR SLAB)
UNLESS OTHERWISE NOTED
URINAL
TAMPER SWITCH
TYPICAL
TOP OF PIPE
VB
VTR
Z
WC WATER CLOSET
ZONE
VENT THROUGH ROOF
VACUUM BREAKER
VENTV
PRESSURE REDUCING VALVEPRV
Y STRAINER WITH BLOW OFF VALVE
LEGEND
PRESSURE REDUCING VALVE
OS&Y (OUTSIDE SCREW & YOKE) VALVE
VALVE (SPECIFICATION FOR TYPE)
CHECK VALVE
BALANCING VALVE
SOLENOID VALVE
UNION
PRESSURE GAUGE AND COCK
TEMPERATURE MIXING VALVE
VALVE WITH TAMPER SWITCH
AD
BLDG
AFF
BOB
BV
BOP
ABOVE FINISHED FLOOR
BOTTOM OF PIPE
BALANCING VALVE
BOTTOM OF THE BEAM
AREA DRAIN
BUILDING
CLG
COTG
CONN
CONT
CP
CLEANOUT TO GRADE
CONTINUATION
CIRCULATING PUMP
CEILING
CONNECTION
CV
CW
DN
DWG
DR
CHECK VALVE
COLD WATER
DOWN
DRAIN
DRAWING
EL
(E)
EWC
EWH
FCO
FD
ELEVATION
ELECTRIC WATER COOLER
FLOOR CLEANOUT
ELECTRIC WATER HEATER
FLOOR DRAIN
EXISTING
FL FLOOR
FT
FU FIXTURE UNIT
FEET
GAL
GPM
HW
GALLONS PER MINUTE
HOT WATER
GALLONS
HWR HOT WATER RETURN
CFH CUBIC FEET PER HOUR
CO CLEANOUT
FS FLOW SWITCH
BUTTERFLY VALVE (MANUAL)
GLOBE VALVE
SEISMIC JOINT
THERMOMETER
WATER FLOW SWITCH
GV GATE VALVE
DFU DRAINAGE FIXTURE UNIT
SAN SANITARY
HWCP HOT WATER CIRCULATING PUMP
RISER DESIGNATION
FLOOR NO.
(H)
(X)
(L)
M
CI CAST IRON
DIA DIAMETER
DROP (WITHIN FLOOR)DROP
EMERGENCY SHOWER/EYE WASHES
NORMALLY OPENNO
OD OUTSIDE DIAMETER
OFD OVERFLOW DRAIN
OST OVERFLOW STORM PIPING
EXISTING
RELOCATED
(R)
SHOCK ABSORBERSA
TRAP PRIMERTP
VR VENT RISE
WHA WATER HAMMER ARRESTER
WFU WATER FIXTURE UNIT
POST INDICATOR VALVE
SHOCK ABSORBER
VACUUM BREAKER
MANUAL AIR VENT
AUTOMATIC AIR VENT
RUNNING TRAP
BASKET STRAINER
CHECK VALVE WITH ABD
AUTOMATIC FLOW CONTROL VALVE
RELIEF VALVE
ANGLE RELIEF VALVE
REDUCER
ECCENTRIC REDUCER (E.R.)
PIV
M
A
X
X X-X
X
MISCELLANEOUS
INCHIN
INVERT ELEVATIONIE
IW INDIRECT WASTE
LDR
MAX MAXIMUM
LEADER
LAVATORYL
JS JANITOR SINK
kPa KILOPASCALS
LPS LITERS PER SECOND
M METERS
M² SQUARE METERS
M³ CUBIC METERS
mm MILLIMETER
ID INSIDE DIAMETER
REDUCED PRESSURE BACKFLOW PREVENTER ASSEMBLYRPBP
DOUBLE CHECK VALVE ASSEMBLY
SELF CONTAINED BREAHTING APPARATUS
DCVA
BA
VALVE IN VERTICAL
BOTTOM PIPE CONNECTION
TOP PIPE CONNECTION
V
SAN
SAN
VENT PIPING
SANITARY (ABOVE FLOOR)
SANITARY (BELOW FLOOR)
WASTE / VENT / STORM
EXISTING PIPING
CENTER LINEC
EXISTING PIPING TO BE REMOVED
PIPING LEGEND
CLEANOUT/PLUG
PIPE UP
P-TRAP
PIPE DOWN
FLOOR CLEANOUT/GRADE CLEANOUT
CHANGE IN PIPE ELEVATION
ARROW INDICATES DIRECTION OF FLOW
PITCH PIPE DOWN IN DIRECTION OF ARROW
CAP
INSULATED AND HEAT TRACED PIPING
FRESH AIR INLET
WALL HYDRANT
DRAWING LIST
P0.1 PLUMBING LEGEND AND ABBREVIATIONS
P0.2 PLUMBING SCHEDULES
P1.0 PLUMBING FLOOR DEMOLITION PLAN
P1.1 PLUMBING OVERALL FLOOR PLAN
P1.2 PLUMBING FLOOR PLAN
P4.1 PLUMBING RISER DIAGRAMS
P5.1 PLUMBING DETAILS
DOMESTIC TEMPERED WATER PIPINGTW
PLUMBING FIXTURE SCHEDULE
MARK
FIXTURE
DESCRIPTION BASIS OF DESIGN
CONNECTIONS
FLOW
RATE
GPF OR
GPM
NOTES
S V TRAP CW HW TW
WC-1 WATER CLOSET
FLOOR MOUNTED, ELONGATED
BOWL, SIPHON JET,
1.28 GPF, ADA
BRIGGS CARLTON MODEL #7790, CENTOCO
NO. 1500STSCCSS OPEN FRONT SEAL LESS
COVER, FLUSH VALVE SLOAN MODEL #
111-1.28
4" 2" 4" 1" - - 1.1
WC-2 WATER CLOSET
FLOOR MOUNTED, ELONGATED
BOWL, SIPHON JET,
1.28 GPF
BRIGGS CARLTON MODEL #7714, CENTOCO
NO. 1500STSCCSS OPEN FRONT SEAL LESS
COVER, FLUSH VALVE SLOAN MODEL #
111-1.28
4" 2" 4" 1" - - 1.1
UR-1 URINAL
WALL HUNG, HIGH EFFICIENCY, 0.125
GPF, ADA
BRIGGS LAWTON # 7552, 3/4" TOP SPUD WITH
SLOAN MODEL # 186-0.125 FLUSH VALVE,
ZURN FLOOR CARRIER Z-1218
2" 1-1/2" 2" 3/4" - - 0.125
L-1 LAVATORY
WALL HUNG, ADA
BRIGGS MILTON # 6620 WITH MOEN FAUCET
MODEL # 8420
1-1/2" 1-1/2" 1-1/4" 1/2" - 1/2" 0.35 1
MS-1 JANITOR'S SINK
FLOOR MOUNTED, TERRAZZO, 12"
DEPTH
FIAT MODEL # TSB300 WITH CHICAGO
MODEL # 897-CP FAUCET
3" 1-1/2" 3" 1/2" - 1/2" - 2
(E) DF-1
DRINK FOUNTAIN
EXISTING TO BE RELOCATED
MODEL ELKAY EZH2O
- 1-1/2" 1-1/2" 1-1/4" 1/2" - - -
(E) ES-1
EMERGENCY SHOWER/EYE WASH
EXISTING TO BE RELOCATED
MODEL BRADLEY
- - - - - - 1-1/4" 23
NOTES:
PROVIDE FLOOR CARRIER WITH CONCEALED ARMS, 1/2 GPM FLOW RESTRICTOR, INSULATE TRAP AND SUPPLIERS WITH TRUEBRO NO. 103 LAV GUARD.
PROVIDE MSG STAINLESS STEEL WALL GUARDS, STAINLESS STEEL CAPS ON ALL CURBS, 832AA HOSE & HOSE BRACKET AND 889CC MOP HANGER.
PLUMBING ELECTRIC WATER HEATER SCHEDULE
MARK FUEL SERVICE
LOCATION/
SERVICE
ELECTRICAL CHARACTERISTICS WATER CHARACTERISTICS
MANUFACTURER
BASIS OF
DESIGN
SIZE (IN) &
WEIGHT (LBS)
NOTES
AMPS KW V PH HZ
TANK
VOLUME
GAL
RECOVERY
CAPACITY GPH
EWT
DEG F
LWT
DEG F
CW CONN
IN
EWH-1 ELECTRIC
DOMESTIC HOT
WATER
FIRST
FLOOR
19 4.5 240 1 60 120 16 45 160 1-1/4"
BRADFORD
WHITE
E32-120R-3
28 1/4 DIA X 64 H
312 LBS
1,2
NOTES:
1. FACTORY INSTALLED T&P RELIEF VALVE AND DRAIN VALVE. 2. TOTAL WEIGHT WITH COMPLETELY FILLED WATER IS APPROX. 1300 LBS.
PLUMBING DRAIN SCHEDULE
TYPE DESCRIPTION OUTLET MANUFACTURER MODEL NUMBER GRATE NOTES
FD-1 FLOOR DRAIN 3" ZURN Z415S-P
5"x5" POLISHED NICKEL
BRONZE TOP
NOTES:
1. SQUARE TOP WITH TRAP PRIMER CONNECTION.
PLUMBING TEMPERATURE MIXING VALVE SCHEDULE
EQUIPMENT NUMBER EQUIPMENT DESCRIPTION
LOCATION LEVEL
& / OR ROOM
MAX
FLOW
(GPM)
PRESS
DROP
(PSI)
MANUFACTURER & MODEL NUMBER NOTES
TMV-1
DOMESTIC HOT WATER -
MIXING VALVE -
RESTROOMS
MEZZANINE 4 15 ACORN ST70-38 1
TMV-2
DOMESTIC HOT WATER
-EMERGENCY SHOWER
MEZZANINE
34 15
GUARDIAN G3700LF 1
NOTES:
1. LISTED EQUIPMENT MANUFACTURERS ARE THE BASIS OF DESIGN.
MINIMUM PLUMBING CHASE WALL WIDTH REQUIREMENTS
FIXTURE TYPE
FIXTURE MOUNTING
DESCRIPTION
DIMENSION FROM OUTER EDGE OF STUD TO OUTER EDGE OF STUD (INCHES)
SINGLE DOUBLE BACK TO BACK
DRINKING FOUNTAINS
WALL HUNG DRINKING FOUNTAIN 6" 6"
WALL HUNG WATER COOLER 12"
12", OFFSET
FLOOR DRAIN IN FLOOR 6" 6"
LAVATORY WALL HUNG 6" 6"
SERVICE SINK FLOOR MOUNT 6" 6"
WATER CLOSET
FLOOR MOUNT, FLUSH VALVE
6" 6"
FLOOR MOUNT, FLUSH VALVE
6" 6"
URINAL
WALL HUNG, FLUSH VALVE
6" 6"
NOTES:
1. FOR CONCRETE BLOCK WALLS, ALL DIMENSIONS SHOWN IN THIS TABLE ARE THE UNITERRUPTED INSIDE DIMENSIONS (NOT OUTSIDE DIMENSIONS).
2. WALL WIDTHS ARE THE MINIMUM REQUIRED FOR FIXTURE INSTALLATION. RISERS MAY REQUIRE ADDITIONAL WALL THICKNESS.
GENERAL NOTES
A. FIELD VERIFY EXISTING CONDITIONS OF PLUMBING
SYSTEMS NOT IN PLAIN VIEW. SUCH AS ABOVE
CEILINGS AND IN WALLS.
NUMBERED NOTES
1. DEMOLISH EXISTING PLUMBING FIXTURES INCLUDING
PIPING, VALVE AND ANY ACCESSORIES.
2. REMOVE AND SALVAGE EXISTING EMERGENCY
SHOWER/EYEWASH FOR REINSTALLATION AT NEW
LOCATION.
3. REMOVE AND SALVAGE EXISTING DRINKING FOUNTAIN
FOR REINSTALLATION AT NEW LOCATION.
E
S
A N
(E) CW 2"
CW 2"
P1.2
P1.2
NUMBERED NOTES
1. CONNECT TO EXITING 2" DCW STUB, FIELD VERIFY
EXACT LOCATION.
2. EXISTING 4" SANITARY WASTE PIPING, FIELD VERIFY
EXACT LOCATION.
3. INSTALL DOMESTIC COLD WATER PIPING ON
MEZZANINE LEVEL. FIELD VERIFY EXACT ROUTING.
WC-2WC-1
WC-1
WC-2
L-1
L-1
MS-1
(R) DF-1
(R) EW-1
EWH
TMV
TMV
WC-2
UR-1 UR-1
L-1 3
P5.1
P5.1
P5.1
GENERAL NOTES
A. FOR SYMBOLS AND ABBREVIATIONS, SEE DRAWING
P0.1.
B. SEE DRAWING P4.1 FOR PIPING SIZE NOT SHOWN ON
FLOOR PLANS.
NUMBERED NOTES
1. WATER HEATER P&T RELIEF VALVE DISCHARGE PIPE
ROUTED TO MOP SINK.
2. 2" CW UP, REFER TO SHEET P1.1 FOR CONTINUITY.
3. PROVIDE TRAP PRIMER VALVE AND INSTALL ON WALL.
4. CONNECT TO EXISTING PLUMBING VENT PIPING,
VERIFY EXACT LOCATION ON SITE.
WC-2WC-1
WC-1
WC-2
UR-1 L-1
L-1
MS-1
FD-1
FD-1
FD-1
(R) DF-1
(R) EW-1
CO3 4" SAN 4" SAN
V V
3" V UP 4
(E) 4"
SAN
WC-2
UR-1
L-1
FD-1
CONNECT TO EXISTING 2" DCW STUB-OUT.
CONNECT TO EXISTING 4" SANITARY WASTE PIPING.
CONNECT TO EXISTING PLUMBING VENT PIPING.
NUMBERED NOTES
FIRST LEVEL
MEZZANINE
EWH
WC-1 WC-1 WC-2 WC-2
UR-1
L-1 L-1L-1 MS-1 DF-1 ES-1
RESTROOMS
FIRST LEVEL
MEZZANINE
L-1 L-1
WC-1 WC-1 WC-2 WC-2
UR-1
L-1
FD-1
DF-1
VTR
V V
EWH
1RESTROOMS
CO
TW
TMV
TMV
TW
MS-1
SAN
2"
3"
(E) 4" 3"3"
2"2"3"
2"
3/4"3/4"
1-1/4" 1-1/4"
1-1/2"
FD-1
WC-2
UR-1
2" 2"
WC-2
FD-1
3"
4"4"
FD-1
SEE FLOOR PLANS
FOR CONTINUATION
(NORMALLY CLOSED)
TANK DRAIN VALVE
UNION (TYPICAL)
GATE VALVE (TYPICAL)
DRAIN
SPILL TO FLOOR
RELIEF VALVE
PRESSURE & TEMP.
FLOOR
S
STORAGE HEATER
VERTICAL ELECTRIC
ELECTRIC ELEMENT
GAUGE COCK (TYPICAL)
THERMOMETER WITH
CHECK VALVE
ELECTRIC DOMESTIC WATER HEATER
NO SCALE
AMTROL THERM-X-TROL
NO. ST-12 EXPANSION TANK
TP
TP8"x 1"
AIRGAP
45° BEVEL CUT
8"
1"
8"
CONNECT TRAP PRIMER INLET
TO FIXTURE
OUTLET TAILPIECE SIDE OF
TRAP
INSTALL TRAP PRIMER PIPING AND UNIT PER
MANUFACTURER'S RECOMMENDATIONS. PIPING
MUST SLOPE TO POINT OF CONNECTION TO
DRAIN WITHOUT TRAPS IN PIPING
3.
TRAP PRIMER VALVE SHALL BE MOUNTED ONE
FOOT ABOVE THE FINISHED FLOOR FOR EVERY 20
FEET OF PRIMER LINE.
2.
NOTES:
1. PROVIDE ACCESS PANEL IN WALLS AT TRAP
PRIMER UNIT LOCATIONS.
DISTRIBUTION UNIT(S)
(WHERE REQUIRED)
VACUUM BREAKER PORT
TRAP PRIMER VALVE
SHUT-OFF VALVE
COLD WATER LINE
8"
FLOOR SINK, FLOOR DRAIN OR
HUB DRAIN
~8"
TRAP PRIME INSTALLATION
NO SCALE
HC
CW
NOTE:
SEE PLUMBING TEMPERATURE MIXING VALVE SCHEDULE FOR SIZE
AND MAXIMUM FLOW.
TEMPERED WATER
UNION
BALL VALVE TO BALANCE SYSTEM
THERMOMETER
MIXING VALVE
NO SCALE
HW
DRAIN PAN
ELECTRICAL LEGEND AND ABBREVIATIONS
WIRING DEVICE SUBSCRIPT LEGEND
AC = ABOVE COUNTER
GFI = GROUND FAULT INTERRUPTER
IG = ISOLATED GROUND
WP = WEATHERPROOF
a = LOWER CASE LETTER INDICATES SWITCH
CONTROL
6 = NUMBER INDICATES CIRCUIT NUMBER
IG = ISOLATED GROUND (ONE OF DOUBLE DUPLEX)
a = LOWER CASE INDICATES SWITCH CONTROL
AC
GFI
IG
WP
a
IG
S a
WIRING DEVICE LEGEND
DUPLEX RECEPTACLE OUTLET: 125V; WALL MOUNTED
LOW VOLTAGE SWITCH
OCCUPANCY SENSOR; CEILING MOUNTEDOS
RACEWAY LEGEND
CONDUIT HOMERUN, MAXIMUM OF (3) BRANCH
CIRCUITS, UON
NOTE: MAXIMUM OF THREE BRANCH CIRCUITS FOR
EACH HOMERUN, UON
GROUNDING CONDUCTOR
PHASE CONDUCTOR(S)
ISOLATED GROUNDING CONDUCTOR
NEUTRAL CONDUCTOR
POWER LEGEND
MOTOR RATED SWITCH
MOTOR CONNECTION
JUNCTION BOX, CEILING MOUNTED
JUNCTION BOX, WALL MOUNTED
S M
M
J
J
LIGHTING LEGEND
LIGHTING FIXTURE DESIGNATIONS:
NUMBER (2) INDICATES CIRCUIT,
UPPERCASE LETTER (A) INDICATES RELAY,
LOWERCASE LETTER (a) INDICATES SWITCH CONTROL, F-XX INDICATES FIXTURE TYPE
LINEAR FLUORESCENT FIXTURE, SIZE
APPROXIMATELY AS SHOWN; CEILING RECESSED
LINEAR FLUORESCENT FIXTURE, SIZE
APPROXIMATELY AS SHOWN; RECESSED OR
CEILING MOUNTED
DOWNLIGHT FIXTURE, SIZE APPROXIMATELY AS
SHOWN; RECESSED OR CEILING MOUNTED
INTERIOR LIGHTING
LIGHTING NAMING LEGEND
2A a
F-XX
DRAWING LIST
E0.1 ELECTRICAL LEGEND & ABBREVIATIONS
E1.2 ELECTRICAL FLOOR PLANS
E4.1 ELECTRICAL SCHEDULES
E5.1 ELECTRICAL DETAILS
ABBREVIATIONS
CKT CIRCUIT
(E) EXISTING TO REMAIN
EMT ELECTRICAL METALLIC TUBING
GFI GROUND FAULT INTERRUPTOR
GND GROUND
MCP MOTOR CIRCUIT PROTECTOR
(N) NEW
NTS NOT TO SCALE
PVC POLYVINYL CHLORIDE CONDUIT
TYP TYPICAL
UON UNLESS OTHERWISE NOTED
UPS UNINTERRUPTIBLE POWER SUPPLY
WP WEATHERPROOF
(X) EXISTING TO BE REMOVED
FIRE ALARM LEGEND
VISUAL ALARM; WALL MOUNTED
E0.1
215790
LAKE MEAD NATIONAL RECREATION AREA
07/31/19
MMS
MAA
ARG
154865
ELECTRICAL LEGENDS
AND ABBREVIATIONS
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
DESIGNED:
AutoCAD SHX Text
TECH. REVIEW:
AutoCAD SHX Text
SUB SHEET NO.
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
OF
AutoCAD SHX Text
TITLE OF SHEET
AutoCAD SHX Text
PMIS/PKG NO.
AutoCAD SHX Text
REHAB WAREHOUSE RESTROOMS
shaung Stamp
POWER FIRST FLOOR DEMOLITION PLAN
E1.1
SHEET NOTES
A. EXISTING RECEPTACLES AND POWER CONNECTIONS ARE SHOWN IN
APPROXIMATE LOCATIONS AND ARE BASED ON AVAILABLE
INFORMATION
B. EXAMINE THE SITE AND VERIFY ALL EXISTING CONDITIONS PRIOR TO
WORK. COORDINATE AREAS OF DEMOLITION WITH CONTRACTING
OFFICER IN FIELD PRIOR TO ACTUAL DEMOLITION
C. WHERE AN EXISTING CIRCUIT IS INTERRUPTED BY REMOVAL OF A
DEVICE OR FIXTURE FROM THAT CIRCUIT, PROVIDE ADDITIONAL
CONDUIT AND WIRE TO RESTORE SERVICE TO THE REMAINING
DEVICES AND FIXTURES ON THAT CIRCUIT.
D. WHERE DEVICES OR EQUIPMENT IS TO BE REMOVED, REMOVE ALL
CONDUITS, CONDUCTORS, J-BOXES AND SUPPORT ASSOCIATED
WITH DEVICES AND EQUIPMENT IN DEMOLITION SCOPE, UON.
E. ALL REUSED BRANCH CIRCUIT CONDUCTORS, CONDUITS AND J
BOXES SHALL REMAIN AS IS, EXTEND CIRCUIT TO NEW DEVICES
LOCATION IF NECESSARY.
F. EXISTING LIGHT FIXTURES AND CONTROLS SHOWN ARE BASED ON
AVAILABLE INFORMATION.
NUMBERED NOTES
UON, DEMOLISH ALL EXISTING POWER AND LIGHTING CIRCUITS BACK TO
SOURCE.
E1.1
215790
LAKE MEAD NATIONAL RECREATION AREA
07/31/19
MMS
MAA
ARG
154865
ELECTRICAL FLOOR
DEMOLITION PLAN
AutoCAD SHX Text A
AutoCAD SHX Text B
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
DESIGNED:
AutoCAD SHX Text
TECH. REVIEW:
AutoCAD SHX Text
SUB SHEET NO.
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
OF
AutoCAD SHX Text
TITLE OF SHEET
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
SCALE OF FEET
AutoCAD SHX Text
PMIS/PKG NO.
AutoCAD SHX Text
REHAB WAREHOUSE RESTROOMS
POWER FIRST FLOOR PLAN
E1.2
GFI +42"
GFI
+42"
GFI
M
EF - 1
M
J
EWH - 1
J
PANEL # 4/13
PANEL # 4/15
PANEL #4
LT - 3
LT - 3
LT - 3
LT - 1 LT - 2
LT - 1
OS
OS
OS
OS
J
PANEL # 4/1
EM
EM
LT - 3
LT - 3
LT - 3
LT - 3
LT - 3
LT - 2
LT - 2
LIGHTING FIRST FLOOR PLAN
E1.2
SHEET NOTES
A. DRAWINGS ARE INTENDED TO SHOW GENERAL ARRANGEMENT,
DESIGN, AND EXTENT OF WORK AND ARE MORE OR LESS
DIAGRAMMATIC. DRAWINGS ARE NOT INTENDED TO SHOW
EXACT LOCATIONS EXCEPT WHERE DIMENSIONS ARE SHOWN.
ELECTRICAL WORK IS SHOWN ON PLANS USING STANDARD
INDUSTRY SYMBOLS. BEFORE ORDERING MATERIALS OR DOING
WORK, THE CONTRACTOR SHALL VERIFY ALL MEASUREMENTS
PERTAINING THERETO AND ASSUME RESPONSIBILITY
THEREFORE. ANY SUBSTANTIAL DIFFERENCES BETWEEN
DRAWINGS AND CONDITIONS IN THE FIELD SHALL BE SUBMITTED
TO THE CONSTRUCTION MANAGER FOR CONSIDERATION
BEFORE PROCEEDING WITH WORK.
B. WORK PERFORMED INCLUDES ALL LABOR, MATERIALS, AND
EQUIPMENT REQUIRED TO INSTALL A COMPLETE ELECTRICAL
SYSTEM AS INDICATED ON THESE DRAWINGS AND AS SPECIFIED.
C. REFER TO MECHANICAL EQUIPMENT WIRING SCHEDULE FOR
WIRING DISCONNECTS REQUIREMENTS.
D. CONTRACTOR SHALL VERIFY ALL EQUIPMENT SIZES AND POWER
REQUIREMENTS FOR EQUIPMENT PROVIDED BY OTHERS.
E. ALL ELECTRICAL CONDUITS AND JUNCTION BOXES IN FINISHED
SPACES SHALL BE CONCEALED. CONTRACTOR SHALL
COORDINATE WITH OTHER TRADES AND USE CHASES AND
CEILING SPACES PROVIDED.
F. CONTRACTOR, AT HIS/HER OPTION, MAY COMBINE CONDUIT
RUNS FOR FEEDERS PROVIDED THAT THE AMPERE RATING OF
THE CONDUCTORS AND ASSOCIATED CONDUIT ARE SIZED PER
NEC ARTICLE 310.
G. REFER TO ARCHITECTURAL, MECHANICAL AND PLUMBING PLANS
FOR EXACT LOCATION OF HVAC/PLUMBING EQUIPMENT.
H. PROVIDE CONDUIT, WIRE AND J-BOXES FOR CIRCUITING SHOWN.
QUANTITY AND SIZE OF J-BOXES TO BE DETERMINED BY
CONTRACTOR.
I. CONTRACTOR SHALL BE RESPONSIBLE FOR REPAIR OF ANY
ELECTRICAL AND DATA CIRCUITS AFFECTED BY CONSTRUCTION.
SUCH CIRCUITS WILL BE REPAIRED IMMEDIATELY. THERE WILL
BE NO DISRUPTION OF SERVICE OUTSIDE OF CONSTRUCTION
ZONE.
J. CONTRACTOR SHALL VERIFY ALL FIXTURE CATALOG NUMBERS
FOR ACCURACY. FIXTURE CATALOG NUMBERS ARE SUBJECT TO
CHANGE BY MANUFACTURER.
K. MOUNTING HEIGHTS SHOWN ARE FROM ABOVE FINISHED FLOOR
TO BOTTOM OF FIXTURE FOR PENDANT MOUNT FIXTURES AND
TO CENTER OF FIXTURE FOR WALL MOUNT FIXTURES UNLESS
OTHERWISE NOTED.
L. VERIFY CEILING TYPE BEFORE ORDERING LIGHTING FIXTURES.
NUMBERED NOTES
PROVIDE OCCUPANCY SENSOR WITH TWO(2) RELAYS. CONNECT RELAY #
1 TO LIGHTS IN THE ROOM AND RELAY # 2 TO EF-1.
FAN LOCATED AT MEZZANINE FLOOR ABOVE AND CONTROLLED BY
OCCUPANCY SENSORS IN MEN'S AND WOMEN'S RESTROOMS.
CONNECT EMERGENCY LIGHTS TO BUILDING EMERGENCY POWER.
CONNECT STROBE TO NEAREST FIRE ALARM CIRCUIT.
PANEL #4 IS LOCATED APPROXIMATELY 80' AWAY TO THE SOUTH ON
COLUMN. SEE DRAWING G1 FOR LOCATION.
SEE ARCHITECTURAL INTERIOR ELEVATIONS FOR LOCATION OF OUTLET.
E1.2
215790
LAKE MEAD NATIONAL RECREATION AREA
07/31/19
MMS
MAA
ARG
154865
ELECTRICAL FLOOR
PLANS
AutoCAD SHX Text A
AutoCAD SHX Text B
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
WOMEN
AutoCAD SHX Text
AutoCAD SHX Text
WOMEN VESTIBULE
AutoCAD SHX Text 109A
AutoCAD SHX Text
MEN
AutoCAD SHX Text
AutoCAD SHX Text
MEN VESTIBULE
AutoCAD SHX Text 110A
AutoCAD SHX Text A
AutoCAD SHX Text B
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text
WOMEN
AutoCAD SHX Text
AutoCAD SHX Text
WOMEN VESTIBULE
AutoCAD SHX Text 109A
AutoCAD SHX Text
MEN
AutoCAD SHX Text
AutoCAD SHX Text
MEN VESTIBULE
AutoCAD SHX Text 110A
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
DESIGNED:
AutoCAD SHX Text
TECH. REVIEW:
AutoCAD SHX Text
SUB SHEET NO.
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
OF
AutoCAD SHX Text
TITLE OF SHEET
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
SCALE OF FEET
AutoCAD SHX Text
PMIS/PKG NO.
AutoCAD SHX Text
REHAB WAREHOUSE RESTROOMS
NUMBERED NOTES
METER PANEL FOR 30 DAYS WITH A MINIMUM OF 1 DATA POINT PER 15
MINUTES. PROVIDE ENGINEER WITH 7-DAYS AND 30-DAYS DATA FOR
VERIFICATION OF PANEL LOADING.
EQUIPMENT CONNECTION SCHEDULE
DESIGNATION HP FLA KVA
VOLT-
AGE
PH POWER SOURCE
CONNECTION
TYPE
BRANCH CIRCUIT WIRING REMARKS
EF-1 1/4 120 1 PANEL #4
SINGLE
CONNECTION
3/4"C - 2#10+1#10GND
EQUIPED WITH 2-SPEED CONTROLLER AND
TIMER.
EWH-1 4.50 240 1 PANEL #4
SINGLE
CONNECTION
3/4"C - 2#10+1#10GND
BUSSING:
100A, 10,000 AIC SYMMETRICAL
PANEL #4
LOCATION:
MAIN: 100A/3P MCB MOUNTING: SURFACE
T
Y
P
E
120/240V, 1 PHASE,
3 WIRE
T
Y
P
E
100% RATED NEUTRAL + GROUND
DESCRIPTION LOAD DEVICE CKT A B CKT DEVICE LOAD DESCRIPTION
L
RESTRM LGTS (N)
750 20/1 1
2 20/1 800
MAIN OFC RECEPS (E)
R
R
EXISTING LOAD (E)
800 20/1 3
4 20/1 800
BU MGR RECEPTS (E)
R
R
EXISTING LOAD (E)
800 20/1 5
6 20/1 696 EF-1 M
R
EXISTING LOAD (E)
800 20/1 7
8 20/1 800
RECEPTS AND LIGHTS (E)
L
R
EXISTING LOAD (E)
800 20/1 9
10 20/1 800
RECEPTS AND LIGHTS (E)
L
R
EXISTING LOAD (E)
800 20/1 11
12 20/1 800
MAIN OFC RECEP/NORTH (E)
R
R
RESTRM RECPTACLES (N)
360 20/1 13
25/2
WATER HEATER (N)
E
E
WATER COOLER (N)
600 20/1 15
16 2250 E
MAIN BREAKER 100/2
20/2
WATER HEATER (E)
E
20 1500 E
TOTAL ALL PHASES (VA) PHASE A (VA) PHASE B (VA) TOTAL ALL PHASES (AMPS)
17906 8756 9150 75
LOAD SUMMARY BY TYPE
CONN.
LOAD
DEMAND
FACTOR
NEC LOAD CONNECTED LOAD SUMMARY
E = EQUIPMENT 8100 VA 1.00 8100 VA 17906 VA
H = ELECTRIC HEAT 0 VA 1.00 0 VA 75 AMPS
K = KITCHEN EQUIPMENT 0 VA 1.00 0 VA
L = LIGHTING 2350 VA 1.25 2938 VA
M = MOTOR 696 VA 1.00 696 VA
M = LARGEST MOTOR 1.25 0 VA NEC LOAD SUMMARY
R = RECEPTACLE 6760 VA
NEC
DEMAND
6760 VA 18494 VA
77 AMPS
LUMINAIRE SCHEDULE
FIXTURE
TYPE
MANUFACTURER /
PRODUCT
DESCRIPTION
LAMP TYPE /
WATTAGE
BALLAST / DRIVER
CONNECTED LOAD /
VOLTAGE
MOUNTING NOTES/APPLICATION
LT-1
PHILIPS LEDALITE
3901-L-A-D-Q-S-3-XX-N-1
RECESSED MOUNT FIXTURE WITH FLUSH MESO OPTIC LENS. 41.8W/4 FT
0-10V, 1-100% DIMMING
120V
RECESSED
G.C. TO COORD. REQ'D
ACCESSORIES
LT-2
REMI LED BATH BAR
HINKLEY LIGHTING
SINGLE LED LIGHT SOURCE WITHIN AN ETCHED GLASS DIFFUSER WITH ALUMINUM
BACKPLATE AND MATCHING ENDCAPS. UL LISTED FOR DAMP APPLICATION.
36W, 3000 LM
LED, 3000k
INTEGRATED LED DRIVER 120V WALL MOUNTED
G.C. TO COORD. REQ'D
ACCESSORIES
LT-3
PHILIPS LIGHTOLIER
C4RN-
C4L30935MZ10U-C4RDL-XX
4” APERTURE LED DOWNLIGHT, SPECULAR CLEAR WITH FLANGE, MEDIUM BEAM
DISTRIBUTION.
31W, 3000LM
LED, 3500K
0-10V 1% DIMMING 120V RECESSED
G.C. TO COORD. REQ'D
ACCESSORIES
E4.1
215790
LAKE MEAD NATIONAL RECREATION AREA
07/31/19
MMS
MAA
ARG
154865
ELECTRICAL SCHEDULES
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
DESIGNED:
AutoCAD SHX Text
TECH. REVIEW:
AutoCAD SHX Text
SUB SHEET NO.
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
OF
AutoCAD SHX Text
TITLE OF SHEET
AutoCAD SHX Text
PMIS/PKG NO.
AutoCAD SHX Text
REHAB WAREHOUSE RESTROOMS
+24 VDC
COMMON
CONTROL
OUTPUT
B L U
B L K
R E
D
POWER PACK
L
O
A
D
RED (LOAD)
WHITE/NEUTRAL
N
HOT
RED (LINE)
WHT
BLK
OFF SWITCH
Any 24VDC Sensor
Ceiling or Wall Mounted
LIGHTING CONTROL SCHEMATIC
NO SCALE
LV
b
LV
a
ON/OFF LOW VOTAGE SWITCH
ON/OFF LOW VOTAGE SWITCH
SWITCH OR RELAY
CONTROLLED
LINE VOLTAGE BALLAST
LIGHTS
LIGHTS
SWITCHED OR RELAY
CONTROLLED LINE
VOLTAGE
BALLAST
LIGHTING ROOM
CONTROLLER
LIGHTING ROOM
CONTROLLER
NORMAL
POWER
CIRCUIT (HOT)
NORMAL
POWER.
(NEUTRAL)
OCCUPANCY SENSOR
DETAIL
NO SCALE
E5.1
215790
LAKE MEAD NATIONAL RECREATION AREA
07/31/19
MMS
MAA
ARG
154865
ELECTRICAL DETAILS
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
DESIGNED:
AutoCAD SHX Text
TECH. REVIEW:
AutoCAD SHX Text
SUB SHEET NO.
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
OF
AutoCAD SHX Text
TITLE OF SHEET
AutoCAD SHX Text
PMIS/PKG NO.
AutoCAD SHX Text
REHAB WAREHOUSE RESTROOMS
| 215790 LAKE Rehab Restrooms_100% Final Construction Drawings |
| G0_Cover |
| G1 BUILDING PLAN |
| A0.1 ABRV SYMB NOTES |
| A0.2 ASSEMBLIES |
| AD1.1 DEMO FLOOR PLAN/RCP |
| A1.1 FLOOR PLAN/RCP |
| A4.2 INTERIOR ELEVATIONS |
| A5.1 INTERIOR DETAILS |
| A5.2 INTERIOR DETAILS |
| MECH 100% CD |
| M0.1 MECHANICAL LEGENDS AND ABBREVIATIONS |
| M0.2 MECHANICAL SCHEDULES AND DETAILS |
| M1.0 MECHANICAL FLOOR DEMOLITION PLAN |
| M1.2 MECHANICAL FLOOR PLAN |
| PLUMBING 100% CD |
| P0.1 PLUMBING LEGENDS AND ABBREVIATIONS |
| P0.2 PLUMBING SCHEDULES |
| P1.0 PLUMBING FLOOR DEMOLITION PLAN |
| P1.1 PLUMBING OVERALL FLOOR PLAN |
| P1.2 PLUMBING FLOOR PLAN |
| P4.1 PLUMBING RISER DIAGRAMS |
| P5.1 PLUMBING DETAILS |
| ELECTRICAL 100% CD |
| E0.1 ELECTRICAL LEGENDS AND ABBREVIATIONS |
| E1.1 ELECTRICAL FLOOR DEMOLITION PLAN |
| E1.2 ELECTRICAL FLOOR PLANS |
| E4.1 ELECTRICAL SCHEDULES |
| E5.1 ELECTRICAL DETAILS |