LAKE – 254113B SOW
LAKE MEAD NATIONAL RECREATION AREA
BOULDER CITY, NEVADA
PMIS NO. 254113B
GFM ELECTRICAL CABLE FOR ECHO BAY WATER INTAKE BARGE
STATEMENT OF WORK
APRIL 21, 2022
1.1 REQUIREMENTS
A. Determine, purchase, and deliver 2,300 linear feet of new electrical cable for an existing pump that is on a barge. About 2,000 linear feet of the electrical cable will be underwater.
Determine that the proper electrical cable is purchased and delivered to start-up and operate the existing pump.
Electrical Cable: The two (2) attachments for electrical cables is an example of an acceptable brand. But the attachments do not imply brand name, supplier, or manufacturer.
• Specifications:
o 3 copper conductor, submersible power cable.
o ASTM B3 Standard Specification for Soft or Annealed Copper Wire o ASTM B172 Standard Specification for Rope-Lay-Stranded Copper Conductors
Having Bunch-Stranded Copper Conductors.
o UL 1650 Standard for Portable Power Cable o MSHA Approved o RoHS-2
Existing Pump: See below for data plate.
B. Point of Contact(s):
Contracting Officer’s Representative - Sam Luke, 702-293-8721, sam_luke@nps.gov.
C. Delivery To:
Attn: Sam Luke/EB Barge Lake Mead National Recreation Area 101 Katzenbach Dr Boulder City, NV 89005
D. Delivery: 140 calendar days after receipt of order. Delivery will be Monday thru Thursday, 9:00 am to 4:00 pm. Delivery will be coordinated 48 hours before arrival. Electrical cable will be delivered on spool(s).
mailto:sam_luke@nps.gov
LAKE – 254113B SOW
Data Plate for Existing Pump
3/C CU 2000V EPDM/CPE Type G-GC Industrial Grade Cable 90°C Flexible Copper conductors, Ethylene Propylene Diene Monomer (EPDM) insulation, Single Layer Chlorinated Polyethylene (CPE) Jacket
Image not to scale. See Table 1 for dimensions.
CONSTRUCTION:
1. Conductor: Bare, soft drawn, annealed, flexible, rope-lay stranded copper per ASTM B3/B172
2. Separator Tape: Non-conducting tape applied between the conductor and insulation to facilitate stripping
3. Insulation: Ethylene Propylene Diene Monomer (EPDM). Color coded black, white, red
4. Ground Check: One insulated, bare, soft drawn, annealed, rope stranded, flexible lay copper per ASTM B3/B172
5. Ground Conductors: Two insulated, bare, soft drawn, annealed, rope stranded, flexible lay copper per ASTM B3/B172
6. Fillers: Paper fillers applied as needed to round the cable core
7. Reinforcement Binder: Reinforcing binder with twine applied over the core
8. Jacket: Black, flame resistant, thermosetting Chlorinated Polyethylene (CPE)
APPLICATIONS AND FEATURES:
Southwire Type G-GC cable is a heavy-duty industrial cable for use in flexible, portable, and extra-hard usage applications where equipment grounding is required per NEC Article 400. Suitable for continuous submersion in water – ideal for submersible pumps, marine application. Also suitable for use in light to medium-duty mining applications. Sunlight and oil resistant. Highly flexible and easy to work with in cold conditions. Not for use as permanent building wiring. Meets FT-5 Flame Test. cUL Listed.
SPECIFICATIONS:
• ASTM B3 Standard Specification for Soft or Annealed Copper Wire
• ASTM B172 Standard Specification for Rope-Lay-Stranded Copper Conductors Having Bunch-Stranded Copper Conductors
• UL 1650 Standard for Portable Power Cable
• MSHA Approved
• RoHS-2 (European Directive 2011/65/EU)
SAMPLE PRINT LEGEND:
XXX AWG 3/C TYPE G-GC PORTABLE POWER CABLE 90{D}C - WET OR DRY 2000V OIL RESISTANT 60{D}C SUN RES. {UL} P-136-35-MSHA - AIW{TM} E172226 MASTER-DESIGN --- c{UL} FT1/FT5 (-40{D}C)
Copyright © 2022 Southwire Company, LLC. All Rights Reserved SPEC 44140 DATE: 03/30/2022 20:34 UTC Rev: 3.0.00M
Southwire Company, LLC | One Southwire Drive, Carrollton, GA 30119 | www.southwire.com
Stock # : 570239 SPEC 44140
Table 1 – Weights and Measurements
Stock Number
Cond.
Size
Cond.
Number
Cond.
Strands
Diameter Over
Conductor
Insul.
Thickness
Diameter Over
Insulation
Ground Size
Ground Strands
Ground Check Size
Ground Check
Strands
Jacket Thickness
Approx.
OD
Approx.
Weight
AWG/
Kcmil
No. No. inch mil inch AWG No. AWG No. mil inch lb/1000ft
570239 250 3 608 0.605 95 0.83 2 259 8 71 240 2.29 4460
All dimensions are nominal and subject to normal manufacturing tolerances ◊ Cable marked with this symbol is a standard stock item
Table 2 – Electrical and Engineering Data
Stock Number
Cond.
Size
Cond.
Number
DC Resistance @ 25°C
AC Resistance @ 90°C
Inductive Reactance
Min Bending Radius
Allowable Ampacity In Air
60°C†
Allowable Ampacity In Air
75°C†
Allowable Ampacity In Air
90°C†
AWG/
Kcmil
No. Ω/1000ft Ω/1000ft MΩ/1000ft inch Amp Amp Amp
570239 250 3 0.0448 0.056 0.029 14 259 310 352
† Ampacity based on NEC 400.5(A)(2) and is for a single isolated cable in air operated at an ambient temperature of 30°C connected to utilization equipment so that only three conductors are current-carrying.
Copyright © 2022 Southwire Company, LLC. All Rights Reserved SPEC 44140 DATE: 03/30/2022 20:34 UTC Rev: 3.0.00M
Southwire Company, LLC | One Southwire Drive, Carrollton, GA 30119 | www.southwire.com
Stock # : 570239 SPEC 44140
Pa ig e Ele ctr ic
LP
Two, three or four conductors having XHHW-2 conductors with PVC jacket conforming to Article 318 “Cable Trays” and Article 340 “Power and Control Cable Type TC”. Direct Burial, Passes 210,000 BTU flame test and suitable for use as submersible cable.
Conductors:
Conductors consist of uncoated soft, copper strands meeting the requirements of ASTM B3. Unless otherwise specified, the conductor shall be supplied as Class B compressed per ASTM B8.
Insulation:
The insulation is flame-retardant cross-linked polyethylene (XHHW-2) extruded concentrically over the conductor to the wall thickness for Type XHHW-2 as specified.
Conductor Coding:
Phase identification is provided by number code on each insulated con-ductor.
Ground Wire:
One stranded bare copper ground wire will be located in one of the outer interstices
APPLICATIONS:
1.1
CONSTRUCTION:
2.1
2.2
2.3
2.4
1.0
2.0
Assembly:
Conductors and ground wire are cabled together, “Filled” cables include suitable fill-ers with a binder to develop a round cable cross section.
Jacket:
A protective sunlight and ozone resistant jacket of Polyvinyl Chloride (PVC) or chlo-rinated polyethylene (CPE) is extruded overall.
• Listed by UL as Type TC per Standard
1277 & IEEE 1202.
• Listed by UL as Type TC per Standard 1277 (4 AWG & larger, PVC jacketed only).
• Conforms to ICEA S-95-658/NEMA WC70 Non-shielded 0-2KV Cables
• Listed by UL as Sunlight Resistant
• Listed by UL as Direct Burial
2.5
2.6
STANDARDS & RATINGS:
600V SUBMERSIBLE POWER CABLE
WITH GROUND
TYPE TC-ER
2, 3 AND 4 CONDUCTOR
INSULATION: XLPE - Cross-Linked Polyethlene JACKET: PVC Polyvinyl Chloride
SIZES: 8 - 750 MCM
90°C DRY, 90°C WET
P7267-SPA
We’re Big in Big pump cable. 6/16/20 spec 9O4-543-1223, 8OO-997-2443, Fax: 9O4-543-133O, www.paigeelectric.com
3.0 www.paigeelectric.com
Pa ig e Ele ctr ic
LP
We’re Big in Big pump cable. page 2 6/16/20
Paige Part Numbers
Conductor Insulation Thickness
Overall Jacket
Size AWG Cooper Ground
Wire
Approximate O.D.
Cable Weight
Ampacity
Size No. of Insulated Conductos
No. of Strands
Nominal O.D.
mils mils inches lbs/ mft* ft
90°C (1)
90°C (2)
7267SPA1 8 3 7 0.14 45 60 8 0.68 330 55 48
7267SPA2 6 3 7 0.18 45 60 8 0.75 445 75 65
7267SPA3 4 3 7 0.23 45 80 8 0.89 650 95 89
7267SPA4 2 3 7 0.28 45 80 6 1.02 955 130 119
7267SPA5 1 3 19 0.32 55 80 6 1.15 1180 150 137
7267SPA6 1/0 3 19 0.36 55 80 6 1.24 1415 170 163
7267SPA7 2/0 3 19 0.41 55 80 6 1.33 1710 195 186
7267SPA8 3/0 3 19 0.46 55 80 4 1.44 2130 225 214
7267SPA9 4/0 3 19 0.51 55 80 4 1.56 2595 260 253
7267SPA10 250 3 37 0.56 65 110 4 1.77 3140 290 276
7267SPA11 300 3 37 0.61 65 110 3 1.88 3700 320 317
7267SPA12 350 3 37 0.66 65 110 3 1.99 4235 350 345
7267SPA13 400 3 37 0.71 65 110 3 2.09 4760 380 371
7267SPA14 500 3 37 0.79 65 110 2 2.26 5840 430 427
7267SPA15 600 3 61 0.87 80 110 2 2.50 6975 475 468
7267SPA16 750 3 61 0.97 80 110 1 2.72 8595 535 529
7267SPA17 8 4 7 0.14 45 60 8 0.74 400 44 38
7267SPA18 6 4 7 0.18 45 60 8 0.82 550 60 52
7267SPA19 4 4 7 0.23 45 80 8 0.98 815 76 71
7267SPA20 2 4 7 0.28 45 80 6 1.12 1200 104 95
7267SPA21 1 4 19 0.32 55 80 6 1.27 1490 120 110
7267SPA22 1/0 4 19 0.36 55 80 6 1.36 1805 136 130
7267SPA23 2/0 4 19 0.41 55 80 6 1.47 2190 156 149
7267SPA24 3/0 4 19 0.46 55 80 4 1.59 2725 180 171
7267SPA25 4/0 4 19 0.51 55 80 4 1.78 3430 208 202
7267SPA26 250 4 37 0.56 65 110 4 1.95 4030 232 221
7267SPA27 300 4 37 0.61 65 110 3 2.08 4755 256 254
7267SPA28 350 4 37 0.66 65 110 3 2.20 5450 280 276
7267SPA29 400 4 37 0.71 65 110 3 2.31 6145 304 297
7267SPA30 500 4 37 0.79 65 110 2 2.51 75454 344 342
7267SPA31 600 4 61 0.87 80 140 2 2.83 9190 380 374
7267SPA32 750 4 61 0.97 80 140 1 3.08 11315 428 423
(1) Based on cables installed in uncovered cable tray at the conductor temperature indicated, 30˚C ambient temperature per NEC.
(2) Based on cables in raceway in free air, 30˚C ambient temperature per NEC.
4.0 DIMENSIONS:
File details come from the government source that posted it. Updated .