LAKE – 254113B SOW

LAKE MEAD NATIONAL RECREATION AREA

BOULDER CITY, NEVADA

PMIS NO. 254113B

GFM ELECTRICAL CABLE FOR ECHO BAY WATER INTAKE BARGE

STATEMENT OF WORK

APRIL 22, 2022

1.1 REQUIREMENTS

A. Determine, purchase, and deliver 2,300 linear feet of new electrical cable for an existing pump that is on a barge. About 2,000 linear feet of the electrical cable will be underwater.

Determine that the proper electrical cable is purchased and delivered to start-up and operate the existing pump.

Electrical Cable: The two (2) attachments for electrical cables is an example of an acceptable brand. But the attachments do not imply brand name, supplier, or manufacturer.

Specifications:

o 250 Kcmil o 3 copper conductor, submersible power cable.

o ASTM B3 Standard Specification for Soft or Annealed Copper Wire o ASTM B172 Standard Specification for Rope-Lay-Stranded Copper Conductors

Having Bunch-Stranded Copper Conductors.

o UL 1650 Standard for Portable Power Cable o MSHA Approved o RoHS-2

Existing Pump: See below for data plate.

B. Point of Contact(s):

Contracting Officer’s Representative - Sam Luke, 702-293-8721, sam_luke@nps.gov.

C. Delivery To:

Attn: Sam Luke/EB Barge Lake Mead National Recreation Area Echo Bay Maintenance Compound (No address)

D. Delivery: 140 calendar days after receipt of order. Delivery will be Monday thru Thursday, 9:00 am to 4:00 pm. Delivery will be coordinated 48 hours before arrival. Electrical cable will be delivered on spool(s).

LAKE – 254113B SOW

Data Plate for Existing Pump

3/C CU 2000V EPDM/CPE Type G-GC Industrial Grade Cable 90°C Flexible Copper conductors, Ethylene Propylene Diene Monomer (EPDM) insulation, Single Layer Chlorinated Polyethylene (CPE) Jacket

Image not to scale. See Table 1 for dimensions.

CONSTRUCTION:

1. Conductor: Bare, soft drawn, annealed, flexible, rope-lay stranded copper per ASTM B3/B172

2. Separator Tape: Non-conducting tape applied between the conductor and insulation to facilitate stripping

3. Insulation: Ethylene Propylene Diene Monomer (EPDM). Color coded black, white, red

4. Ground Check: One insulated, bare, soft drawn, annealed, rope stranded, flexible lay copper per ASTM B3/B172

5. Ground Conductors: Two insulated, bare, soft drawn, annealed, rope stranded, flexible lay copper per ASTM B3/B172

6. Fillers: Paper fillers applied as needed to round the cable core

7. Reinforcement Binder: Reinforcing binder with twine applied over the core

8. Jacket: Black, flame resistant, thermosetting Chlorinated Polyethylene (CPE)

APPLICATIONS AND FEATURES:

Southwire Type G-GC cable is a heavy-duty industrial cable for use in flexible, portable, and extra-hard usage applications where equipment grounding is required per NEC Article 400. Suitable for continuous submersion in water – ideal for submersible pumps, marine application. Also suitable for use in light to medium-duty mining applications. Sunlight and oil resistant. Highly flexible and easy to work with in cold conditions. Not for use as permanent building wiring. Meets FT-5 Flame Test. cUL Listed.

SPECIFICATIONS:

• ASTM B3 Standard Specification for Soft or Annealed Copper Wire

• ASTM B172 Standard Specification for Rope-Lay-Stranded Copper Conductors Having Bunch-Stranded Copper Conductors

• UL 1650 Standard for Portable Power Cable

• MSHA Approved

• RoHS-2 (European Directive 2011/65/EU)

SAMPLE PRINT LEGEND:

XXX AWG 3/C TYPE G-GC PORTABLE POWER CABLE 90{D}C - WET OR DRY 2000V OIL RESISTANT 60{D}C SUN RES. {UL} P-136-35-MSHA - AIW{TM} E172226 MASTER-DESIGN --- c{UL} FT1/FT5 (-40{D}C)

Copyright © 2022 Southwire Company, LLC. All Rights Reserved SPEC 44140 DATE: 03/30/2022 20:34 UTC Rev: 3.0.00M

Southwire Company, LLC | One Southwire Drive, Carrollton, GA 30119 | www.southwire.com

Stock # : 570239 SPEC 44140

Table 1 – Weights and Measurements

Stock Number

Cond.

Size

Cond.

Number

Cond.

Strands

Diameter Over

Conductor

Insul.

Thickness

Diameter Over

Insulation

Ground Size

Ground Strands

Ground Check Size

Ground Check

Strands

Jacket Thickness

Approx.

OD

Approx.

Weight

AWG/

Kcmil

No. No. inch mil inch AWG No. AWG No. mil inch lb/1000ft

570239 250 3 608 0.605 95 0.83 2 259 8 71 240 2.29 4460

All dimensions are nominal and subject to normal manufacturing tolerances ◊ Cable marked with this symbol is a standard stock item

Table 2 – Electrical and Engineering Data

Stock Number

Cond.

Size

Cond.

Number

DC Resistance @ 25°C

AC Resistance @ 90°C

Inductive Reactance

Min Bending Radius

Allowable Ampacity In Air

60°C†

Allowable Ampacity In Air

75°C†

Allowable Ampacity In Air

90°C†

AWG/

Kcmil

No. Ω/1000ft Ω/1000ft MΩ/1000ft inch Amp Amp Amp

570239 250 3 0.0448 0.056 0.029 14 259 310 352

† Ampacity based on NEC 400.5(A)(2) and is for a single isolated cable in air operated at an ambient temperature of 30°C connected to utilization equipment so that only three conductors are current-carrying.

Copyright © 2022 Southwire Company, LLC. All Rights Reserved SPEC 44140 DATE: 03/30/2022 20:34 UTC Rev: 3.0.00M

Southwire Company, LLC | One Southwire Drive, Carrollton, GA 30119 | www.southwire.com

Stock # : 570239 SPEC 44140

Pa ig e Ele ctr ic

LP

Two, three or four conductors having XHHW-2 conductors with PVC jacket conforming to Article 318 “Cable Trays” and Article 340 “Power and Control Cable Type TC”. Direct Burial, Passes 210,000 BTU flame test and suitable for use as submersible cable.

Conductors:

Conductors consist of uncoated soft, copper strands meeting the requirements of ASTM B3. Unless otherwise specified, the conductor shall be supplied as Class B compressed per ASTM B8.

Insulation:

The insulation is flame-retardant cross-linked polyethylene (XHHW-2) extruded concentrically over the conductor to the wall thickness for Type XHHW-2 as specified.

Conductor Coding:

Phase identification is provided by number code on each insulated con-ductor.

Ground Wire:

One stranded bare copper ground wire will be located in one of the outer interstices

APPLICATIONS:

1.1

CONSTRUCTION:

2.1

2.2

2.3

2.4

1.0

2.0

Assembly:

Conductors and ground wire are cabled together, “Filled” cables include suitable fill-ers with a binder to develop a round cable cross section.

Jacket:

A protective sunlight and ozone resistant jacket of Polyvinyl Chloride (PVC) or chlo-rinated polyethylene (CPE) is extruded overall.

• Listed by UL as Type TC per Standard

1277 & IEEE 1202.

• Listed by UL as Type TC per Standard 1277 (4 AWG & larger, PVC jacketed only).

• Conforms to ICEA S-95-658/NEMA WC70 Non-shielded 0-2KV Cables

• Listed by UL as Sunlight Resistant

• Listed by UL as Direct Burial

2.5

2.6

STANDARDS & RATINGS:

600V SUBMERSIBLE POWER CABLE

WITH GROUND

TYPE TC-ER

2, 3 AND 4 CONDUCTOR

INSULATION: XLPE - Cross-Linked Polyethlene JACKET: PVC Polyvinyl Chloride

SIZES: 8 - 750 MCM

90°C DRY, 90°C WET

P7267-SPA

We’re Big in Big pump cable. 6/16/20 spec 9O4-543-1223, 8OO-997-2443, Fax: 9O4-543-133O, www.paigeelectric.com

3.0 www.paigeelectric.com

Pa ig e Ele ctr ic

LP

We’re Big in Big pump cable. page 2 6/16/20

Paige Part Numbers

Conductor Insulation Thickness

Overall Jacket

Size AWG Cooper Ground

Wire

Approximate O.D.

Cable Weight

Ampacity

Size No. of Insulated Conductos

No. of Strands

Nominal O.D.

mils mils inches lbs/ mft* ft

90°C (1)

90°C (2)

7267SPA1 8 3 7 0.14 45 60 8 0.68 330 55 48

7267SPA2 6 3 7 0.18 45 60 8 0.75 445 75 65

7267SPA3 4 3 7 0.23 45 80 8 0.89 650 95 89

7267SPA4 2 3 7 0.28 45 80 6 1.02 955 130 119

7267SPA5 1 3 19 0.32 55 80 6 1.15 1180 150 137

7267SPA6 1/0 3 19 0.36 55 80 6 1.24 1415 170 163

7267SPA7 2/0 3 19 0.41 55 80 6 1.33 1710 195 186

7267SPA8 3/0 3 19 0.46 55 80 4 1.44 2130 225 214

7267SPA9 4/0 3 19 0.51 55 80 4 1.56 2595 260 253

7267SPA10 250 3 37 0.56 65 110 4 1.77 3140 290 276

7267SPA11 300 3 37 0.61 65 110 3 1.88 3700 320 317

7267SPA12 350 3 37 0.66 65 110 3 1.99 4235 350 345

7267SPA13 400 3 37 0.71 65 110 3 2.09 4760 380 371

7267SPA14 500 3 37 0.79 65 110 2 2.26 5840 430 427

7267SPA15 600 3 61 0.87 80 110 2 2.50 6975 475 468

7267SPA16 750 3 61 0.97 80 110 1 2.72 8595 535 529

7267SPA17 8 4 7 0.14 45 60 8 0.74 400 44 38

7267SPA18 6 4 7 0.18 45 60 8 0.82 550 60 52

7267SPA19 4 4 7 0.23 45 80 8 0.98 815 76 71

7267SPA20 2 4 7 0.28 45 80 6 1.12 1200 104 95

7267SPA21 1 4 19 0.32 55 80 6 1.27 1490 120 110

7267SPA22 1/0 4 19 0.36 55 80 6 1.36 1805 136 130

7267SPA23 2/0 4 19 0.41 55 80 6 1.47 2190 156 149

7267SPA24 3/0 4 19 0.46 55 80 4 1.59 2725 180 171

7267SPA25 4/0 4 19 0.51 55 80 4 1.78 3430 208 202

7267SPA26 250 4 37 0.56 65 110 4 1.95 4030 232 221

7267SPA27 300 4 37 0.61 65 110 3 2.08 4755 256 254

7267SPA28 350 4 37 0.66 65 110 3 2.20 5450 280 276

7267SPA29 400 4 37 0.71 65 110 3 2.31 6145 304 297

7267SPA30 500 4 37 0.79 65 110 2 2.51 75454 344 342

7267SPA31 600 4 61 0.87 80 140 2 2.83 9190 380 374

7267SPA32 750 4 61 0.97 80 140 1 3.08 11315 428 423

(1) Based on cables installed in uncovered cable tray at the conductor temperature indicated, 30˚C ambient temperature per NEC.

(2) Based on cables in raceway in free air, 30˚C ambient temperature per NEC.

4.0 DIMENSIONS: