963-48_OCFS_48_-_Spec._Volume_2.pdf

PDF 11 MB Posted

Attached to
Fire Station #48
Solicitation number
Y25-766
Issued by
Orange County, Orlando City, Florida

About this file

The document is a comprehensive project manual for the Orange County Fire Rescue Fire Station #48 project located in Winter Garden, Florida. The bid solicitation is for a new fire station construction project with an estimated cost of $9,750,000, with sealed electronic bids to be accepted through the OpenGov e-Procurement Platform until 4:00 pm EST on Tuesday, May 13, 2025. Prospective bidders are required to submit responses electronically and create a free account on the OpenGov platform. The project involves detailed technical specifications for HVAC, plumbing, fire protection, and building automation systems, with specific requirements for equipment, materials, installation, and performance standards.

The project documents provide extensive technical specifications covering multiple building systems, including detailed requirements for mechanical, electrical, and control systems. The specifications outline precise installation guidelines, performance expectations, and technical standards for components such as ductwork, piping, valves, sensors, and building automation systems. Bidders must adhere to specific local and national codes, including NFPA, ASHRAE, and Florida Building Code requirements. The project includes provisions for comprehensive system testing, commissioning, and training, with specific requirements for documentation, warranties, and post-installation support. Technical submissions must include detailed shop drawings, product data, and compliance documentation, with a focus on open-protocol building automation systems and energy-efficient design.

View the file

Other files

File Type Posted
Fire_Station_#48_(Addendum_#3_Revision).pdf PDF
963-48_OCFS_48_-_Spec._Volume_1.pdf PDF
963-48_OCFS_48_-_DRWG.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ORANGE COUNTY FIRE STATION #48

6963 Avalon Road, Winter Garden, FL 34787

PERMIT DOCUMENTS

ADG # 963-48 | January 17, 2025

A R C H I T E C T :

C O N S U L T A N T S :

ARCHITECTS DESIGN GROUP, Inc.

I.S.K. Reeves V, F.A.I.A.

Ian A. Reeves, A.I.A.

333 N. Knowles Ave.

Winter Park, FL 32789 T: 407-647-1706 F: 407-645-5525 email : adg@adgusa.org

CIVIL

AVCON. Inc.

5555 E. Michigan St., Suite 200 Orlando, FL 32822-2779 T: (407) 599-1122

M.E.P / F.P SGM Engineering, Inc.

935 Lake Baldwin Lane Orlando, FL 32814 T: (407) 767-5188

LANDSCAPE

CASTLE BAY DESIGN + STUDIO

3000 N Ponce De Leon Blvd., Suite C St. Augustine, FL 32084 T: (386) 747-1370

STRUCTURAL

BASE Consultants 1214 East Concord Street Orlando, FL 32803 T: (407) 377-7227

FUELING CONSULTANT

Stillwater Technologies 2101 W. State Rd. 434, Suite 135 Orlando, FL 32779 T: (407) 206-7222

VOLUME 2

akeillor Image

ADG No. 963-48 Table of Contents

Orange County Fire Rescue

Fire Station 48

Bid Documents

January 17, 2025

TABLE OF CONTENTS

Volume 2

ORANGE COUNTY FIRE RESCUE

STATION NO. 48

ADG PROJECT No. 963-48

SECTION

NO. SECTION TITLE SECTION DESCRIPTION

DIVISION 13 - SPECIAL CONSTRUCTION

NOT USED

DIVISION 14 - CONVEYING EQUIPMENT

NOT USED

DIVISION 21 - FIRE PROTECTION

210500 COMMON WORK RESULTS FOR FIRE SUPPRESSION

211100 FACILITY FIRE-SUPPRESSION WATER-SERVICE PIPING

211313 WET-PIPE SPRINKLER SYSTEM

DIVISION 22 - PLUMBING

220500 COMMON WORK RESULTS FOR PLUMBING

220519 METERS AND GAGES FOR PLUMBING PIPING

220523 GENERAL-DUTY VALVES FOR PLUMBING PIPING

220529 HANGERS & SUPPORTS FOR PLUMBING PIPING & EQUIPMENT

220553 IDENTIFICATIONS FOR PLUMBING PIPING & EQUIPMENT

220700 PLUMBING INSULATION

221116 DOMESTIC WATER PIPING

221119 DOMESTIC WATER PIPING SPECIALTIES

221316 SANITARY WASTE & VENT PIPING

221319 SANITARY WASTE PIPING SPECIALTIES

221323 SANITARY WASTER INTERCEPTORS

223300 ELECTRIC, DOMESTIC WATER HEATERS

224000 PLUMBING FIXTURES

224700 DRINKING FOUNTAINS & WATER COOLERS

DIVISION 23 - HEATING VENTILATING AND AIR CONDITIONING

230500 COMMON WORK RESULTS FOR HVAC

230513 COMMON MOTOR REQUIREMENTS FOR HVAC EQUIPMENT

230517 SLEEVES & SLEEVE SEALS FOR HVAC PIPING

230529 HANGERS & SUPPORTS FOR HVAC PIPING & EQUIPMENT

230548 VIBRATION CONTROLS FOR HVAC EQUIPMENT

230553 IDENTIFICATION FOR HVAC PIPING & EQUIPMENT

230593 TESTING, ADJUSTING, & BALANCING

230713 DUCT INSULATION

Fire Station 48

Bid Documents

January 17, 2025

230719 HVAC PIPING INSULATION

230800 COMMISSIONING OF HVAC SYSTEMS

230900 INSTRUMENTATION & CONTROL FOR HVAC

231126 FACILITY LIQUIFIED-PETROLEUM GAS PIPING

233113 METAL DUCTS

233300 AIR DUCT ACCESSORIES

233423 HVAC POWER VENTILATORS

233600 AIR TERMINALS

233713 DIFFUSERS, REGISTERS & GRILLES

237313 MODULAR INDOOR CENTRAL-STATION AIR-HANDLING UNITS

238126 SPLIT-SYSTEM AIR-CONDITIONERS

DIVISION 26 – ELECTRICAL

260500 COMMON WORK RESULTS FOR ELECTRICAL

260519 LOW VOLTAGE CONDUCTORS & CABLES

260526 GROUNDING & BONDING FOR ELECTRICAL SYSTEMS

260529 HANGERS & SUPPORTS FOR ELECTRICAL SYSTEMS

260533 RACEWAYS & BOXES FOR ELECTRICAL SYSTEMS

260536 CABLE TRAYS FOR ELECTRICAL SYSTEMS

260553 IDENTIFICATION FOR ELECTRICAL SYSTEMS

260573 OVERCURRENT DEVICE COORDINATION STUDY WITH ARC FLASH ANALYSIS

260923 STAND ALONE LIGHTING CONTROL DEVICES

262416 PANELBOARDS

262726 WIRING DEVICES

262813 FUSES

262816 ENCLOSED SWITCHES & CIRCUIT BOARDS

263213 DIESEL GENERATOR

263600 TRANSFER SWITCHES

264313 SURGE PROTECTION DEVICES

265100 INTERIOR LIGHTING

265600 EXTERIOR LIGHTING

DIVISION 27 – TECHNOLOGY

272626 DATA COMMUNICATIONS INTEGRATION

274133 TELEVISION SYSTEM

275116 FIRE STATION ALERTING SYSTEM

*Note: This is a proprietary system and is included for contractor information and coordination purposes.

DIVISION 28 - ELECTRONIC SAFETY AND SECURITY

283111 ADDRESSABLE FIRE-ALARM SYSTEM

DIVISION 31 - EARTHWORK

311100 CLEARING & GRUBBING

312300 EXCAVATION & FILL

312319 DEWATERING

Fire Station 48

Bid Documents

313116 TERMITE CONTROL

DIVISION 32 - EXTERIOR IMPROVEMENTS

321216 ASPHALTIC CONCRETE PAVING

321313 CONCRETE PAVING

311713 PARKING BUMPERS

323000 SITE IMPROVEMENTS

323116 DECORATIVE METAL SECURITY FENCES & GATES

323121 ALUMINUM LOUVER GATES

DIVISION 33 – UTILITIES

331100 WATER DISTRIBUTION SYSTEMS

333000 SANITARY SEWAGE SYSTEM

333100 SANITARY UTILITY SEWAGE PIPING

334100 STORM DRAINAGE PIPING

335000 FUEL DISTRIBUTION UTILITIES

DIVISION 48 – PHOTOVOLTAIC SOLAR PANELS

481400 PHOTOVOLTAIC SOLAR PANELS

APPENDIX

FR00 FURNITURE SPECIFICATIONS

TP603 SIGNALIZATION

TP783 ITS FIBER OPTIC CABLE AND INTERCONNECT

END OF TABLE OF CONTENTS

ADG No. 963-48 210500-1 Common Work Results for

Orange County Fire Rescue Fire Suppression

Fire Station 48

Bid Documents

January 17, 2025

SECTION 21 05 00

COMMON WORK RESULTS FOR FIRE SUPPRESSION

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including Division 01 General

Requirements Specification Sections, apply to this Section.

1.2 SUMMARY

A. This Section includes the following:

1. Piping materials and installation instructions common to most piping systems.

2. Fire-suppression equipment and piping demolition.

3. Equipment installation requirements common to equipment sections.

4. Painting and finishing.

5. Supports and anchorages.

1.3 DEFINITIONS

A. Finished Spaces: Spaces other than mechanical and electrical equipment rooms, furred spaces, pipe chases, unheated spaces immediately below roof, spaces above ceilings, unexcavated spaces, crawlspaces, and tunnels.

B. Exposed, Interior Installations: Exposed to view indoors. Examples include finished occupied spaces and mechanical equipment rooms.

C. Exposed, Exterior Installations: Exposed to view outdoors or subject to outdoor ambient temperatures and weather conditions. Examples include rooftop locations.

D. Concealed, Interior Installations: Concealed from view and protected from physical contact by building occupants. Examples include above ceilings and in chases.

E. Concealed, Exterior Installations: Concealed from view and protected from weather conditions and physical contact by building occupants but subject to outdoor ambient temperatures. Examples include installations within unheated shelters.

ADG No. 963-48 210500-2 Common Work Results for

Fire Station 48

Bid Documents

January 17, 2025

1.4 SUBMITTALS

A. Welding certificates.

1.5 QUALITY ASSURANCE

A. Steel Support Welding: Qualify processes and operators according to AWS

D1.1, "Structural Welding Code--Steel."

B. Steel Pipe Welding: Qualify processes and operators according to ASME Boiler and Pressure Vessel Code: Section IX, "Welding and Brazing Qualifications."

1. Comply with provisions in ASME B31 Series, "Code for Pressure Piping."

2. Certify that each welder has passed AWS qualification tests for welding processes involved and that certification is current.

C. Electrical Characteristics for Fire-Suppression Equipment: Equipment of higher electrical characteristics may be furnished provided such proposed equipment is approved in writing and connecting electrical services, circuit breakers, and conduit sizes are appropriately modified. If minimum energy ratings or efficiencies are specified, equipment shall comply with requirements.

1.6 DELIVERY, STORAGE, AND HANDLING

A. Deliver pipes and tubes with factory-applied end caps. Maintain end caps through shipping, storage, and handling to prevent pipe end damage and to prevent entrance of dirt, debris, and moisture.

B. Store plastic pipes protected from direct sunlight. Support to prevent sagging and bending.

1.7 COORDINATION

A. Arrange for pipe spaces, chases, slots, and openings in building structure during progress of construction, to allow for fire-suppression installations.

B. Coordinate installation of required supporting devices and set sleeves in poured-in-place concrete and other structural components as they are constructed.

C. Coordinate requirements for access panels and doors for fire-suppression items requiring access that are concealed behind finished surfaces. Access panels and doors are specified in Division 08 Section "Access Doors and Frames."

PART 2 - PRODUCTS

ADG No. 963-48 210500-3 Common Work Results for

Fire Station 48

Bid Documents

January 17, 2025

2.1 PIPE, TUBE, AND FITTINGS

A. Refer to individual Division 21 piping Sections for pipe, tube, and fitting materials and joining methods.

B. Pipe Threads: ASME B1.20.1 for factory-threaded pipe and pipe fittings.

2.2 JOINING MATERIALS

A. Refer to individual Division 21 piping Sections for special joining materials not listed below.

B. Pipe-Flange Gasket Materials: Suitable for chemical and thermal conditions of piping system contents.

1. ASME B16.21, nonmetallic, flat, asbestos-free, 1/8-inch maximum thickness unless thickness or specific material is indicated.

a. Full-Face Type: For flat-face, Class 125, cast-iron and cast-bronze flanges.

b. Narrow-Face Type: For raised-face, Class 250, cast-iron and steel flanges.

2. AWWA C110, rubber, flat face, 1/8 inch thick, unless otherwise indicated; and full-face or ring type, unless otherwise indicated.

C. Flange Bolts and Nuts: ASME B18.2.1, carbon steel, unless otherwise indicated.

D. Plastic, Pipe-Flange Gasket, Bolts, and Nuts: Type and material recommended by piping system manufacturer, unless otherwise indicated.

E. Welding Filler Metals: Comply with AWS D10.12 for welding materials appropriate for wall thickness and chemical analysis of steel pipe being welded.

PART 3 - EXECUTION

3.1 PIPING SYSTEMS - COMMON REQUIREMENTS

A. Install piping according to the following requirements and Division 21 Sections specifying piping systems.

B. Drawing plans, schematics, and diagrams indicate general location and arrangement of piping systems. Indicated locations and arrangements were used to size pipe and calculate friction loss, expansion, pump sizing, and other

ADG No. 963-48 210500-4 Common Work Results for

Fire Station 48

Bid Documents

January 17, 2025 design considerations. Install piping as indicated unless deviations to layout are approved on Coordination Drawings.

C. Install piping in concealed locations, unless otherwise indicated and except in equipment rooms and service areas.

D. Install piping indicated to be exposed and piping in equipment rooms and service areas at right angles or parallel to building walls. Diagonal runs are prohibited unless specifically indicated otherwise. Refer to architectural plans for additional installation requirements.

E. Install inspector test drains and auxiliary drains lines to empty into the site storm sewer system. Route discharge piping underground to connect to nearby storm inlet.

F. Install piping above accessible ceilings to allow sufficient space for ceiling panel removal.

G. Install piping to permit valve servicing.

H. Install piping at indicated slopes.

I. Install piping free of sags and bends.

J. Install fittings for changes in direction and branch connections.

K. Install piping to allow application of insulation.

L. Select system components with pressure rating equal to or greater than system operating pressure.

M. Verify final equipment locations for roughing-in.

N. Refer to equipment specifications in other Sections of these Specifications for roughing-in requirements.

3.2 PIPING JOINT CONSTRUCTION

A. Join pipe and fittings according to the following requirements and Division 21

Sections specifying piping systems.

B. Ream ends of pipes and tubes and remove burrs. Bevel plain ends of steel pipe.

C. Remove scale, slag, dirt, and debris from inside and outside of pipe and fittings before assembly.

ADG No. 963-48 210500-5 Common Work Results for

Fire Station 48

Bid Documents

January 17, 2025

D. Threaded Joints: Thread pipe with tapered pipe threads according to ASME

B1.20.1. Cut threads full and clean using sharp dies. Ream threaded pipe ends to remove burrs and restore full ID. Join pipe fittings and valves as follows:

1. Apply appropriate tape or thread compound to external pipe threads unless dry seal threading is specified.

2. Damaged Threads: Do not use pipe or pipe fittings with threads that are corroded or damaged. Do not use pipe sections that have cracked or open welds.

E. Welded Joints: Construct joints according to AWS D10.12, using qualified processes and welding operators according to Part 1 "Quality Assurance"

Article.

F. Flanged Joints: Select appropriate gasket material, size, type, and thickness for service application. Install gasket concentrically positioned. Use suitable lubricants on bolt threads.

3.3 PAINTING

A. Painting of fire-suppression systems, equipment, and components is specified in

Division 09 Sections "Painting & Special Coatings".

B. Damage and Touchup: Repair marred and damaged factory-painted finishes with materials and procedures to match original factory finish.

3.4 ERECTION OF METAL SUPPORTS AND ANCHORAGES

A. Refer to Division 05 Section "Metal Fabrications" for structural steel.

B. Cut, fit, and place miscellaneous metal supports accurately in location, alignment, and elevation to support and anchor fire-suppression materials and equipment.

C. Field Welding: Comply with AWS D1.1.

END OF SECTION 21 05 00

THIS PAGE INTENTIONALLY LEFT BLANK

ADG No. 963-48 211100-1 Facility Fire-Suppression

Orange County Fire Rescue Water-Service Piping

Fire Station 48

Bid Documents

January 17, 2025

SECTION 21 11 00

FACILITY FIRE-SUPPRESSION WATER-SERVICE PIPING

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including Division 01 General

Requirements Specification Sections, apply to this Section.

1.2 SUMMARY

A. Section includes fire-suppression water-service piping and related components outside the building and service entrance piping through wall into the building.

B. Utility-furnished products include water meters that will be furnished to the site, ready for installation.

C. Related Sections:

1. Division 21 Section "Wet-Pipe Sprinkler Systems" for wet-pipe firesuppression sprinkler systems inside the building.

1.3 SUBMITTALS

A. Product Data: For each type of product indicated.

B. Shop Drawings:

1. Detail precast concrete vault assemblies and indicate dimensions, method of field assembly, and components.

2. Wiring Diagrams: For power, signal, and control wiring.

1.4 QUALITY ASSURANCE

A. Regulatory Requirements:

1. Comply with requirements of utility company supplying water. Include tapping of water mains and backflow prevention.

2. Comply with standards of authorities having jurisdiction for fire-suppression water-service piping, including materials, hose threads, installation, and testing.

ADG No. 963-48 211100-2 Facility Fire-Suppression

Fire Station 48

Bid Documents

January 17, 2025

B. Piping materials shall bear label, stamp, or other markings of specified testing agency.

C. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.

D. Comply with the "Approval Guide," published by FM Global, or UL's "Fire

Protection Equipment Directory" for fire-service-main products.

E. NFPA Compliance: Comply with NFPA 24 for materials, installations, tests, flushing, and valve and hydrant supervision for fire-suppression water-service piping.

1.5 DELIVERY, STORAGE, AND HANDLING

A. Preparation for Transport: Prepare valves, including fire hydrants, according to the following:

1. Ensure that valves are dry and internally protected against rust and corrosion.

2. Protect valves against damage to threaded ends and flange faces.

3. Set valves in best position for handling. Set valves closed to prevent rattling.

B. During Storage: Use precautions for valves, including fire hydrants, according to the following:

1. Do not remove end protectors unless necessary for inspection; then reinstall for storage.

2. Protect from weather. Store indoors and maintain temperature higher than ambient dew point temperature. Support off the ground or pavement in watertight enclosures when outdoor storage is necessary.

C. Handling: Use sling to handle valves and fire hydrants if size requires handling by crane or lift. Rig valves to avoid damage to exposed parts. Do not use handwheels or stems as lifting or rigging points.

D. Deliver piping with factory-applied end caps. Maintain end caps through shipping, storage, and handling to prevent pipe-end damage and to prevent entrance of dirt, debris, and moisture.

E. Protect stored piping from moisture and dirt. Elevate above grade. Do not exceed structural capacity of floor when storing inside.

F. Protect flanges, fittings, and specialties from moisture and dirt.

G. Store plastic piping protected from direct sunlight. Support to prevent sagging and bending.

ADG No. 963-48 211100-3 Facility Fire-Suppression

Fire Station 48

Bid Documents

January 17, 2025

1.6 PROJECT CONDITIONS

A. Interruption of Fire-Suppression Water-Service Piping: Do not interrupt service to facilities occupied by Owner or others unless permitted under the following conditions and then only after arranging to provide temporary waterdistribution service according to requirements indicated:

1. Notify Owner no fewer than five days in advance of proposed interruption of service.

2. Do not proceed with interruption of service without Owner's written permission.

1.7 COORDINATION

A. Coordinate connection to water main with utility company.

PART 2 - PRODUCTS

2.1 DUCTILE-IRON PIPE AND FITTINGS

A. Mechanical-Joint, Ductile-Iron Pipe: AWWA C151, with mechanical-joint bell and plain spigot end.

B. Mechanical-Joint, Ductile-Iron Fittings: AWWA C110, ductile- or gray-iron standard pattern or AWWA C153, ductile-iron compact pattern.

1. Glands, Gaskets, and Bolts: AWWA C111, ductile- or gray-iron glands, rubber gaskets, and steel bolts.

C. Flanges: ASME B16.1, Class 125, cast iron.

2.2 BACKFLOW PREVENTERS

A. Double-Check, Detector-Assembly Backflow Preventers:

1. Manufacturers: Subject to compliance with requirements:

a. Ames Fire & Waterworks; a division of Watts Water Technologies, Inc.

b. FEBCO; SPX Valves & Controls.

c. Watts Water Technologies, Inc.

d. Zurn Plumbing Products Group; Wilkins Water Control Products

Division.

2. Standards: ASSE 1048 and UL's "Fire Protection Equipment Directory" listing or "Approval Guide," published by FM Global, listing.

3. Operation: Continuous-pressure applications.

ADG No. 963-48 211100-4 Facility Fire-Suppression

Fire Station 48

Bid Documents

January 17, 2025

4. Body Material: Cast iron with interior lining complying with AWWA C550 or that is FDA approved.

5. End Connections: Flanged.

6. Configuration: Designed for horizontal, straight through flow.

7. Accessories:

a. Valves: UL 262, "Approval Guide," published by FM Global, listing, approved; OS&Y gate type with flanged ends on inlet and outlet.

b. Bypass: With displacement-type water meter, shutoff valves, and reduced-pressure backflow preventer.

2.3 FIRE HYDRANTS

A. AWWA Wet-Barrel Fire Hydrants:

1. Manufacturers: Subject to compliance with requirements:

a. American AVK Company; Valves & Fittings Division.

b. Clow Valve Company; a division of McWane, Inc.

c. Jones, James Company.

d. Mueller Co.; Water Products Division.

2. Description: Post type, with one NPS 4-1/2 and two NPS 2-1/2 outlets and with NPS 6 threaded or flanged inlet, and base section with NPS 6 mechanical-joint inlet. Include interior coating according to AWWA C550.

3. Standard: AWWA C503.

4. Pressure Rating: 200 psig minimum.

B. UL-Listed, Wet-Barrel Fire Hydrants:

1. Manufacturers: Subject to compliance with requirements:

a. American AVK Company; Valves & Fittings Division.

b. Clow Valve Company; a division of McWane, Inc.

c. Jones, James Company.

d. Mueller Co.; Water Products Division.

2. Description: Freestanding, with one NPS 4-1/2 and two NPS 2-1/2 outlets and with NPS 6 threaded or flanged inlet, and base section with NPS 6 mechanical-joint inlet.

3. Standards: UL 246 and "Approval Guide," published by FM Global, listing.

4. Design: Wet barrel.

5. Pressure Rating: 200 psig.

6. Outlet Threads: NFPA 1963, with external hose thread used by local fire department. Include cast-iron caps with steel chains.

7. Operating and Cap Nuts: Pentagon, 1-1/2 inches point to flat.

8. Direction of Opening: Hydrant valves open by turning operating nut to left or counterclockwise.

9. Exterior Finish: Red alkyd-gloss enamel paint unless otherwise indicated.

ADG No. 963-48 211100-5 Facility Fire-Suppression

Fire Station 48

Bid Documents

January 17, 2025

2.4 FIRE-DEPARTMENT CONNECTIONS

A. Manufacturers: Subject to compliance with requirements:

1. Elkhart Brass Mfg. Company, Inc.

2. Guardian Fire Equipment, Inc.

3. Potter Roemer.

4. Reliable Automatic Sprinkler Co., Inc.

B. Description: Freestanding, with cast-bronze body, thread inlets according to

NFPA 1963 and matching local fire-department hose threads, and threaded bottom outlet. Include lugged caps, gaskets, and chains; lugged swivel connection and drop clapper for each hose-connection inlet; 18-inch- high brass sleeve; and round escutcheon plate. C. Standard: UL 405.

D. Connections: Three NPS 2-1/2 inlets and one NPS 6 outlet.

E. Inlet Alignment: Inline, horizontal.

F. Finish Including Sleeve: Polished chrome plated.

G. Escutcheon Plate Marking: "AUTO SPKR & STANDPIPE."

2.5 GROUT

A. Standard: ASTM C 1107, Grade B, post-hardening and volume adjusting, dry, hydraulic-cement grout.

B. Characteristics: Nonshrink; recommended for interior and exterior applications.

C. Design Mix: 5000-psi, 28-day compressive strength.

D. Packaging: Premixed and factory packaged.

PART 3 - EXECUTION

3.1 EARTHWORK

A. Comply with excavating, trenching, and backfilling requirements in Division 31

Section "Earth Moving."

3.2 PIPING INSTALLATION

ADG No. 963-48 211100-6 Facility Fire-Suppression

Fire Station 48

Bid Documents

January 17, 2025

A. Water-Main Connection: Arrange with water utility company for tap of size and in location indicated in water main.

B. Water-Main Connection: Tap water main according to requirements of water utility company and of size and in location indicated.

C. Make connections larger than NPS 2 with tapping machine according to the following:

1. Install tapping sleeve and tapping valve according to MSS SP-60.

2. Install tapping sleeve on pipe to be tapped. Position flanged outlet for gate valve.

3. Use tapping machine compatible with valve and tapping sleeve; cut hole in main. Remove tapping machine and connect water-service piping.

4. Install gate valve onto tapping sleeve. Comply with MSS SP-60. Install valve with stem pointing up and with valve box.

D. Make connections NPS 2 and smaller with drilling machine according to the following:

1. Install service-saddle assemblies and corporation valves in size, quantity, and arrangement required by utility company's standards.

2. Install service-saddle assemblies on water-service pipe to be tapped.

Position outlets for corporation valves.

3. Use drilling machine compatible with service-saddle assemblies and corporation valves. Drill hole in main. Remove drilling machine and connect water-service piping.

4. Install corporation valves into service-saddle assemblies.

5. Install manifold for multiple taps in water main.

6. Install curb valve in water-service piping with head pointing up and with service box.

E. Comply with NFPA 24 for fire-service-main piping materials and installation.

F. Install ductile-iron, water-service piping according to AWWA C600 and AWWA

M41.

1. Install encasement for piping according to ASTM A 674 or AWWA C105.

G. Bury piping with depth of cover over top at least 30 inches, with top at least 12 inches below level of maximum frost penetration, and according to the following:

1. Under Driveways: With at least 36 inches of cover over top.

2. In Loose Gravelly Soil and Rock: With at least 12 inches of additional cover.

H. Install piping by tunneling or jacking, or combination of both, under streets and other obstructions that cannot be disturbed.

ADG No. 963-48 211100-7 Facility Fire-Suppression

Fire Station 48

Bid Documents

January 17, 2025

I. Extend fire-suppression water-service piping and connect to water-supply source and building fire-suppression water-service piping systems at locations and pipe sizes indicated.

1. Terminate fire-suppression water-service piping at building wall until building-water-piping systems are installed. Terminate piping with caps, plugs, or flanges as required for piping material. Make connections to building's fire-suppression water-service piping systems when those systems are installed.

J. Install underground piping with restrained joints at horizontal and vertical changes in direction. Use restrained-joint piping, thrust blocks, anchors, tie-rods and clamps, and other supports.

K. Comply with requirements in Division 21 Sections for fire-suppression-water piping inside the building.

L. Comply with requirements in Division 22 Section "Domestic Water Piping" for potable-water piping inside the building.

3.3 JOINT CONSTRUCTION

A. Install couplings, flanges, flanged fittings, unions, nipples, and transition and special fittings that have finish and pressure rating same as or higher than systems pressure rating for aboveground applications unless otherwise indicated.

B. Install unions adjacent to each valve in tubing NPS 2 and smaller.

C. Install flanges, flange adaptors, or couplings for grooved-end piping on valves, apparatus, and equipment having NPS 2-1/2 and larger end connections. D.

Ream ends of tubes and remove burrs.

E. Remove scale, slag, dirt, and debris from outside and inside of pipes, tubes, and fittings before assembly.

F. Copper-Tubing, Brazed Joints: Join copper tube and fittings according to CDA's

"Copper Tube Handbook," "Brazed Joints" Chapter.

G. Copper-Tubing, Pressure-Sealed Joints: Use proprietary crimping tool and procedure recommended by copper, pressure-seal-fitting manufacturer. H.

Ductile-Iron Piping, Gasketed Joints for Fire-Service-Main Piping: UL 194.

I. Ductile-Iron Piping, Grooved Joints: Cut-groove pipe. Assemble joints with grooved-end, ductile-iron-piping couplings, gaskets, lubricant, and bolts.

ADG No. 963-48 211100-8 Facility Fire-Suppression

Fire Station 48

Bid Documents

January 17, 2025

J. Flanged Joints: Select appropriate gasket material in size, type, and thickness suitable for water service. Join flanges with bolts according to ASME B31.9.

K. PE Piping Heat-Fusion Joints: Clean and dry joining surfaces by wiping with clean cloth or paper towels. Join according to ASTM D 2657.

L. PVC Piping Gasketed Joints: Use joining materials according to AWWA C900.

Construct joints with elastomeric seals and lubricant according to ASTM D 2774 or ASTM D 3139.

M. Fiberglass Piping Bonded Joints: Use adhesive and procedure recommended by piping manufacturer.

N. Dissimilar Materials Piping Joints: Use adapters compatible with both piping materials, with OD, and with system working pressure. O. Do not use flanges or unions for underground piping.

3.4 ANCHORAGE INSTALLATION

A. Anchorage, General: Install water-distribution piping with restrained joints.

Anchorages and restrained-joint types that may be used include the following:

1. Concrete thrust blocks.

2. Locking mechanical joints.

3. Set-screw mechanical retainer glands.

4. Bolted flanged joints.

5. Heat-fused joints.

6. Pipe clamps and tie rods.

B. Install anchorages for tees, plugs and caps, bends, crosses, valves, and hydrant branches in fire-suppression water-service piping according to NFPA 24 and the following:

1. Gasketed-Joint, Ductile-Iron, Water-Service Piping: According to

AWWA C600.

2. Gasketed-Joint, PVC Water-Service Piping: According to AWWA M23.

3. Bonded-Joint Fiberglass, Water-Service Piping: According to AWWA M45.

C. Apply full coat of asphalt or other acceptable corrosion-resistant material to surfaces of installed ferrous anchorage devices.

3.5 VALVE INSTALLATION

A. MSS Valves: Install as component of connected piping system.

ADG No. 963-48 211100-9 Facility Fire-Suppression

Fire Station 48

Bid Documents

January 17, 2025

B. Support valves and piping, not direct buried, on concrete piers. Comply with requirements for concrete piers in Division 03 Section "Cast-in-Place Concrete."

3.6 BACKFLOW PREVENTER INSTALLATION

A. Install backflow preventers of type, size, and capacity indicated. Include valves and test cocks. Install according to requirements of plumbing and health department and authorities having jurisdiction.

B. Do not install backflow preventers that have relief drain in vault or in other spaces subject to flooding.

C. Do not install bypass piping around backflow preventers.

D. Support NPS 2-1/2 and larger backflow preventers and piping on concrete piers.

Comply with requirements for concrete piers in Division 03 Section "Castin-Place

Concrete."

E. Install protective pipe bollards on two sides of each fire-department connection.

3.7 FIRE HYDRANT INSTALLATION

A. General: Install each fire hydrant with separate gate valve in supply pipe, anchor with restrained joints or thrust blocks, and support in upright position.

B. Wet-Barrel Fire Hydrants: Install with valve below frost line. Provide for drainage.

C. AWWA Fire Hydrants: Comply with AWWA M17.

D. UL-Listed or FM-Approved Fire Hydrants: Comply with NFPA 24.

3.8 FIRE-DEPARTMENT CONNECTION INSTALLATION

A. Install ball drip valves at each check valve for fire-department connection to mains.

B. Install protective pipe bollards on two sides of each fire-department connection. Pipe bollards are specified in Division 05 Section "Metal

Fabrications."

3.9 CONNECTIONS

A. Connect fire-suppression water-service piping to existing water main. Use tapping sleeve and tapping valve.

ADG No. 963-48 211100-10 Facility Fire-Suppression

Fire Station 48

Bid Documents

January 17, 2025

B. Connect fire-suppression water-service piping to interior fire-suppression piping.

3.10 FIELD QUALITY CONTROL

A. Use test procedure prescribed by authorities having jurisdiction or, if method is not prescribed by authorities having jurisdiction, use procedure described below.

B. Piping Tests: Conduct piping tests before joints are covered and after concrete thrust blocks have hardened sufficiently. Fill pipeline 24 hours before testing and apply test pressure to stabilize system. Use only potable water.

C. Hydrostatic Tests: Test at not less than one-and-one-half times the working pressure for two hours.

1. Increase pressure in 50-psig increments and inspect each joint between increments. Hold at test pressure for one hour; decrease to 0 psig. Slowly increase again to test pressure and hold for one more hour. Maximum allowable leakage is 2 quarts per hour per 100 joints. Remake leaking joints with new materials and repeat test until leakage is within allowed limits.

D. Prepare test and inspection reports.

3.11 IDENTIFICATION

A. Install continuous underground detectable warning tape during backfilling of trench for underground fire-suppression water-service piping. Locate below finished grade, directly over piping. Underground warning tapes are specified in

Division 31 Section "Excavation & Fill".

B. Permanently attach equipment nameplate or marker indicating plastic firesuppression water-service piping or fire-suppression water-service piping with electrically insulated fittings, on main electrical meter panel. Comply with requirements for identifying devices in Division 22 Section "Identification for

Plumbing Piping and Equipment."

3.12 PIPING SCHEDULE

A. Underground fire-suppression water-service piping NPS 6 to NPS 12 shall be the following:

1. Mechanical-joint, ductile-iron pipe; mechanical-joint, ductile- or gray-iron, standard-pattern fittings; glands, gaskets, and bolts; and gasketed joints.

3.13 VALVE SCHEDULE

ADG No. 963-48 211100-11 Facility Fire-Suppression

Fire Station 48

Bid Documents

January 17, 2025

A. Drawings indicate valve types to be used. Where specific valve types are not indicated, the following requirements apply:

B. Underground fire-suppression water-service shutoff valves NPS 2 and smaller shall be corporation valves or curb valves with ends compatible with piping.

C. Meter box fire-suppression water-service shutoff valves NPS 2 and smaller shall be meter valves.

D. Underground fire-suppression water-service shutoff valves NPS 3 and larger shall be the following:

1. 250-psig, AWWA, iron, non-rising-stem, resilient-seated gate valves.

END OF SECTION 21 11 00

ADG No. 963-48 211100-12 Facility Fire-Suppression

Fire Station 48

Bid Documents

ADG No. 963-48 211313- 1 Wet-Pipe Sprinkler Systems

Fire Station 48

Bid Documents

January 17, 2025

SECTION 21 13 13

WET-PIPE SPRINKLER SYSTEMS

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including Division 01 General

Requirements Specification Sections, apply to this Section.

1.2 SUMMARY

A. Section Includes:

1. Pipes, fittings, and specialties.

2. Fire-protection valves.

3. Sprinklers.

4. Alarm devices.

5. Pressure gages.

1.3 DEFINITIONS

A. Standard-Pressure Sprinkler Piping: Wet-pipe sprinkler system piping designed to operate at working pressure of 175 psig maximum.

1.4 SYSTEM DESCRIPTIONS

A. Wet-Pipe Sprinkler System: Automatic sprinklers are attached to piping containing water and that is connected to water supply through alarm valve. Water discharges immediately from sprinklers when they are opened. Sprinklers open when heat melts fusible link or destroys frangible device. Hose connections are included if indicated.

1.5 PERFORMANCE REQUIREMENTS

A. Standard-Pressure Piping System Component: Listed for 175-psig minimum working pressure.

B. Delegated Design: Design sprinkler system(s), including comprehensive engineering analysis by a qualified professional engineer, using performance requirements and design criteria indicated.

ADG No. 963-48 211313- 2 Wet-Pipe Sprinkler Systems

Fire Station 48

Bid Documents

January 17, 2025

C. Sprinkler system design shall be approved by authorities having jurisdiction.

1.6 SUBMITTALS

A. Product Data: For each type of product indicated. Include rated capacities, operating characteristics, electrical characteristics, and furnished specialties and accessories.

B. Shop Drawings: For wet-pipe sprinkler systems. Include plans, elevations, sections, details, and attachments to other work.

1. Wiring Diagrams: For power, signal, and control wiring. C.

Qualification Data: For qualified Installer.

D. Welding certificates.

E. Fire-hydrant flow test report.

F. Field Test Reports and Certificates: Indicate and interpret test results for compliance with performance requirements and as described in NFPA 13.

Include "Contractor's Material and Test Certificate for Aboveground Piping." G.

Field quality-control reports.

H. Operation and Maintenance Data: For sprinkler specialties to include in emergency, operation, and maintenance manuals.

1.7 QUALITY ASSURANCE

A. Installer Qualifications:

1. Installer's responsibilities include designing, fabricating, and installing sprinkler systems and providing professional engineering services needed to assume engineering responsibility. Base calculations on results of firehydrant flow test.

a. Engineering Responsibility: Preparation of working plans, calculations, and field test reports by a qualified professional engineer.

B. Welding Qualifications: Qualify procedures and operators according to ASME

Boiler and Pressure Vessel Code.

C. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.

1.8 COORDINATION

ADG No. 963-48 211313- 3 Wet-Pipe Sprinkler Systems

Fire Station 48

Bid Documents

January 17, 2025

A. Coordinate layout and installation of sprinklers with other construction that penetrates ceilings, including light fixtures, HVAC equipment, and partition assemblies.

PART 2 - PRODUCTS

2.1 PIPING MATERIALS

A. Comply with requirements in "Piping Schedule" Article for applications of pipe, tube, and fitting materials, and for joining methods for specific services, service locations, and pipe sizes.

2.2 STEEL PIPE AND FITTINGS

A. Standard Weight, Black-Steel Pipe: ASTM A 53/A 53M, Type E, Grade B. Pipe ends may be factory or field formed to match joining method.

B. Schedule 10, Black-Steel Pipe: ASTM A 135 or ASTM A 795/A 795M, Schedule 10 in NPS 5 and smaller; and NFPA 13-specified wall thickness in NPS 6 to NPS 10, plain end.

C. Galvanized, Steel Couplings: ASTM A 865, threaded.

D. Galvanized, Gray-Iron Threaded Fittings: ASME B16.4, Class 125, standard pattern.

E. Malleable- or Ductile-Iron Unions: UL 860.

F. Steel Flanges and Flanged Fittings: ASME B16.5, Class 150.

G. Steel Welding Fittings: ASTM A 234/A 234M and ASME B16.9.

H. Grooved-Joint, Steel-Pipe Appurtenances:

1. Manufacturers: Subject to compliance with requirements:

a. Anvil International, Inc.

b. National Fittings, Inc.

c. Shurjoint Piping Products.

d. Tyco Fire & Building Products LP.

e. Victaulic Company.

2. Pressure Rating: 175 psig minimum.

3. Galvanized, Grooved-End Fittings for Steel Piping: ASTM A 47/A 47M, malleable-iron casting or ASTM A 536, ductile-iron casting; with dimensions matching steel pipe.

ADG No. 963-48 211313- 4 Wet-Pipe Sprinkler Systems

Fire Station 48

Bid Documents

January 17, 2025

4. Grooved-End-Pipe Couplings for Steel Piping: AWWA C606 and UL 213, rigid pattern, unless otherwise indicated, for steel-pipe dimensions. Include ferrous housing sections, EPDM-rubber gasket, and bolts and nuts.

2.3 PIPING JOINING MATERIALS

A. Pipe-Flange Gasket Materials: AWWA C110, rubber, flat face, 1/8 inch thick.

1. Class 125, Cast-Iron Flanges and Class 150, Bronze Flat-Face Flanges:

Fullface gaskets.

2. Class 250, Cast-Iron Flanges and Class 300, Steel Raised-Face Flanges: Ring-type gaskets.

B. Metal, Pipe-Flange Bolts and Nuts: ASME B18.2.1, carbon steel unless otherwise indicated.

C. Brazing Filler Metals: AWS A5.8/A5.8M, BCuP Series, copper-phosphorus alloys for general-duty brazing unless otherwise indicated.

D. Welding Filler Metals: Comply with AWS D10.12M/D10.12 for welding materials appropriate for wall thickness and chemical analysis of steel pipe being welded.

2.4 LISTED FIRE-PROTECTION VALVES

A. General Requirements:

1. Valves shall be UL listed or FM approved.

2. Minimum Pressure Rating for Standard-Pressure Piping: 175 psig.

B. Bronze Butterfly Valves:

1. Manufacturers: Subject to compliance with requirements:

a. Fivalco Inc.

b. Global Safety Products, Inc.

c. Milwaukee Valve Company.

2. Standard: UL 1091.

3. Pressure Rating: 175 psig.

4. Body Material: Bronze.

5. End Connections: Threaded.

C. Check Valves:

1. Manufacturers: Subject to compliance with requirements:

a. Reliable Automatic Sprinkler Co., Inc.

b. Tyco Fire & Building Products LP.

c. Victaulic Company.

d. Viking Corporation.

2. Standard: UL 312.

ADG No. 963-48 211313- 5 Wet-Pipe Sprinkler Systems

Fire Station 48

Bid Documents

January 17, 2025

3. Pressure Rating: 300 psig.

4. Type: Swing check.

5. Body Material: Cast iron.

6. End Connections: Flanged or grooved.

D. Bronze OS&Y Gate Valves:

1. Manufacturers: Subject to compliance with requirements:

a. Crane Co.; Crane Valve Group; Crane Valves.

b. Milwaukee Valve Company.

c. NIBCO INC.

2. Standard: UL 262.

3. Pressure Rating: 175 psig.

4. Body Material: Bronze.

5. End Connections: Threaded.

2.5 TRIM AND DRAIN VALVES

A. General Requirements:

1. Standard: UL's "Fire Protection Equipment Directory" listing or "Approval

Guide," published by FM Global, listing.

2. Pressure Rating: 175 psig minimum.

B. Ball Valves:

1. Manufacturers: Subject to compliance with requirements:

a. Milwaukee Valve Company.

b. Potter Roemer.

c. Tyco Fire & Building Products LP.

d. Victaulic Company.

2.6 SPRINKLERS

A. Manufacturers: Subject to compliance with requirements:

1. Reliable Automatic Sprinkler Co., Inc.

2. Tyco Fire & Building Products LP.

3. Victaulic Company.

4. Viking Corporation.

B. General Requirements:

1. Standard: UL's "Fire Protection Equipment Directory" listing or "Approval

Guide," published by FM Global, listing.

2. Pressure Rating for Residential Sprinklers: 175 psig maximum.

3. Pressure Rating for Automatic Sprinklers: 175 psig minimum.

ADG No. 963-48 211313- 6 Wet-Pipe Sprinkler Systems

Fire Station 48

Bid Documents

January 17, 2025

C. Sprinkler Finishes:

1. Chrome plated.

2. Bronze.

3. Painted.

D. Special Coatings:

1. Wax.

2. Lead.

3. Corrosion-resistant paint.

E. Sprinkler Escutcheons: Materials, types, and finishes for the following sprinkler mounting applications. Escutcheons for concealed, flush, and recessed-type sprinklers are specified with sprinklers.

1. Ceiling Mounting: Chrome-plated steel, one piece, flat.

2. Sidewall Mounting: Chrome-plated steel, one piece, flat.

F. Sprinkler Guards:

1. Manufacturers: Subject to compliance with requirements:

a. Reliable Automatic Sprinkler Co., Inc.

b. Tyco Fire & Building Products LP.

c. Victaulic Company.

d. Viking Corporation.

2. Standard: UL 199.

3. Type: Wire cage with fastening device for attaching to sprinkler.

2.7 ALARM DEVICES

A. Alarm-device types shall match piping and equipment connections.

B. Water-Flow Indicators:

1. Manufacturers: Subject to compliance with requirements:

a. Potter Electric Signal Company.

b. System Sensor; a Honeywell company.

c. Viking Corporation.

2. Standard: UL 346.

3. Water-Flow Detector: Electrically supervised.

4. Components: Two single-pole, double-throw circuit switches for isolated alarm and auxiliary contacts, 7 A, 125-V ac and 0.25 A, 24-V dc; complete with factory-set, field-adjustable retard element to prevent false signals and tamperproof cover that sends signal if removed.

5. Type: Paddle operated.

6. Pressure Rating: 250 psig.

7. Design Installation: Horizontal or vertical.

C. Valve Supervisory Switches:

ADG No. 963-48 211313- 7 Wet-Pipe Sprinkler Systems

Fire Station 48

Bid Documents

January 17, 2025

1. Manufacturers: Subject to compliance with requirements:

a. Kennedy Valve; a division of McWane, Inc.

b. Potter Electric Signal Company.

c. System Sensor; a Honeywell company.

2. Standard: UL 346.

3. Type: Electrically supervised.

4. Components: Single-pole, double-throw switch with normally closed contacts.

5. Design: Signals that controlled valve is in other than fully open position.

2.8 PRESSURE GAGES

A. Manufacturers: Subject to compliance with requirements:

1. AMETEK; U.S. Gauge Division.

2. Ashcroft, Inc.

3. Brecco Corporation. B. Standard: UL 393.

C. Dial Size: 3-1/2- to 4-1/2-inch diameter.

D. Pressure Gage Range: 0 to 250 psig minimum.

E. Water System Piping Gage: Include "WATER" or "AIR/WATER" label on dial face.

F. Air System Piping Gage: Include "AIR" or "AIR/WATER" label on dial face.

2.9 GROUT

A. Standard: ASTM C 1107, Grade B, posthardening and volume adjusting, dry, hydraulic-cement grout.

B. Characteristics: Nonshrink, and recommended for interior and exterior applications.

C. Design Mix: 5000-psi, 28-day compressive strength.

D. Packaging: Premixed and factory packaged.

PART 3 - EXECUTION

3.1 PREPARATION

ADG No. 963-48 211313- 8 Wet-Pipe Sprinkler Systems

Fire Station 48

Bid Documents

January 17, 2025

A. Perform fire-hydrant flow test according to NFPA 13 and NFPA 291. Use results for system design calculations required in "Quality Assurance" Article. B. Report test results promptly and in writing.

3.2 SERVICE-ENTRANCE PIPING

A. Connect sprinkler piping to water-service piping for service entrance to building.

Comply with requirements for exterior piping in Division 21 Section "Facility Fire-

Suppression Water-Service Piping."

B. Install shutoff valve, backflow preventer, pressure gage, drain, and other accessories indicated at connection to water-service piping. Comply with requirements for backflow preventers in Division 21 Section "Facility

FireSuppression Water-Service Piping."

C. Install shutoff valve, check valve, pressure gage, and drain at connection to water service.

3.3 PIPING INSTALLATION

A. Locations and Arrangements: Drawing plans, schematics, and diagrams indicate general location and arrangement of piping. Install piping as indicated, as far as practical.

1. Deviations from approved working plans for piping require written approval from authorities having jurisdiction. File written approval with Architect before deviating from approved working plans.

B. Piping Standard: Comply with requirements for installation of sprinkler piping in

NFPA 13.

C. Use listed fittings to make changes in direction, branch takeoffs from mains, and reductions in pipe sizes.

D. Install unions adjacent to each valve in pipes NPS 2 and smaller.

E. Install flanges, flange adapters, or couplings for grooved-end piping on valves, apparatus, and equipment having NPS 2-1/2 and larger end connections.

F. Install "Inspector's Test Connections" in sprinkler system piping, complete with shutoff valve, and sized and located according to NFPA 13.

G. Install sprinkler piping with drains for complete system drainage.

ADG No. 963-48 211313- 9 Wet-Pipe Sprinkler Systems

Fire Station 48

Bid Documents

January 17, 2025

H. Install sprinkler control valves, test assemblies, and drain risers adjacent to standpipes when sprinkler piping is connected to standpipes.

I. Install automatic (ball drip) drain valve at each check valve for fire-department connection, to drain piping between fire-department connection and check valve. Install drain piping to and spill over floor drain or to outside building. J.

Install alarm devices in piping systems.

K. Install hangers and supports for sprinkler system piping according to NFPA 13.

Comply with requirements for hanger materials in NFPA 13.

L. Install pressure gages on riser or feed main, at each sprinkler test connection, and at top of each standpipe. Include pressure gages with connection not less than

NPS 1/4 and with soft metal seated globe valve, arranged for draining pipe between gage and valve. Install gages to permit removal, and install where they will not be subject to freezing.

M. Pressurize and check preaction sprinkler system piping and air-pressure maintenance devices.

N. Fill sprinkler system piping with water.

3.4 JOINT CONSTRUCTION

A. Install couplings, flanges, flanged fittings, unions, nipples, and transition and special fittings that have finish and pressure ratings same as or higher than system's pressure rating for aboveground applications unless otherwise indicated.

B. Install unions adjacent to each valve in pipes NPS 2 and smaller.

C. Install flanges, flange adapters, or couplings for grooved-end piping on valves, apparatus, and equipment having NPS 2-1/2 and larger end connections.

D. Ream ends of pipes and tubes and remove burrs. Bevel plain ends of steel pipe.

E. Remove scale, slag, dirt, and debris from inside and outside of pipes, tubes, and fittings before assembly.

F. Flanged Joints: Select appropriate gasket material in size, type, and thickness suitable for water service. Join flanges with gasket and bolts according to ASME

B31.9.

G. Threaded Joints: Thread pipe with tapered pipe threads according to ASME

B1.20.1. Cut threads full and clean using sharp dies. Ream threaded pipe ends to remove burrs and restore full ID. Join pipe fittings and valves as follows:

ADG No. 963-48 211313- 10 Wet-Pipe Sprinkler Systems

Fire Station 48

Bid Documents

January 17, 2025

1. Apply appropriate tape or thread compound to external pipe threads.

2. Damaged Threads: Do not use pipe or pipe fittings with threads that are corroded or damaged.

H. Welded Joints: Construct joints according to AWS D10.12M/D10.12, using qualified processes and welding operators according to "Quality Assurance"

Article.

1. Shop weld pipe joints where welded piping is indicated. Do not use welded joints for galvanized-steel pipe.

I. Steel-Piping, Roll-Grooved Joints: Roll rounded-edge groove in end of pipe according to AWWA C606. Assemble coupling with housing, gasket, lubricant, and bolts. Join steel pipe and grooved-end fittings according to AWWA C606 for steel-pipe grooved joints.

J. Dissimilar-Material Piping Joints: Make joints using adapters compatible with materials of both piping systems.

3.5 VALVE AND SPECIALTIES INSTALLATION

A. Install listed fire-protection valves, trim and drain valves, specialty valves and trim, controls, and specialties according to NFPA 13 and authorities having jurisdiction.

B. Install listed fire-protection shutoff valves supervised open, located to control sources of water supply except from fire-department connections. Install permanent identification signs indicating portion of system controlled by each valve.

C. Install check valve in each water-supply connection. Install backflow preventers instead of check valves in potable-water-supply sources.

D. Specialty Valves:

1. General Requirements: Install in vertical position for proper direction of flow, in main supply to system.

2. Alarm Valves: Include bypass check valve and retarding chamber drainline connection.

3.6 SPRINKLER INSTALLATION

A. Install sprinklers in suspended ceilings in center of acoustical ceiling panels.

B. Install dry-type sprinklers with water supply from heated space. Do not install pendent or sidewall, wet-type sprinklers in areas subject to freezing.

ADG No. 963-48 211313- 11 Wet-Pipe Sprinkler Systems

Fire Station 48

Bid Documents

January 17, 2025

3.7 IDENTIFICATION

A. Install labeling and pipe markers on equipment and piping according to requirements in NFPA 13.

B. Identify system components, wiring, cabling, and terminals. Comply with requirements for identification specified in Division 26 Section "Identification for

Electrical Systems."

3.8 FIELD QUALITY CONTROL A.

Perform tests and inspections.

B. Tests and Inspections:

1. Leak Test: After installation, charge systems and test for leaks. Repair leaks and retest until no leaks exist.

2. Test and adjust controls and safeties. Replace damaged and malfunctioning controls and equipment.

3. Flush, test, and inspect sprinkler systems according to NFPA 13, "Systems

Acceptance" Chapter.

4. Energize circuits to electrical equipment and devices.

5. Coordinate with fire-alarm tests. Operate as required.

6. Verify that equipment hose threads are same as local fire-department equipment.

C. Sprinkler piping system will be considered defective if it does not pass tests and inspections.

D. Prepare test and inspection reports.

3.9 PIPING SCHEDULE

A. Sprinkler specialty fittings may be used, downstream of control vales, instead of specified fittings.

B. Standard-pressure, wet-pipe sprinkler system, NPS 2 and smaller, shall be one of the following:

1. Standard-weight, black-steel pipe with threaded ends; uncoated, grayiron threaded fittings; and threaded joints.

2. Standard-weight, black-steel pipe with roll-grooved ends; uncoated, grooved-end fittings for steel piping; grooved-end-pipe couplings for steel piping; and grooved joints.

3.…