9-Exhibit A.pdf

PDF 111 KB Posted

Attached to
RFP Chemical Tank
Solicitation number
26-0187
Issued by
Tarrant County, Texas

About this file

Exhibit A is a technical specification document for a Fiberglass Reinforced Polymer (FRP) storage tank required by the City of Fort Worth Water Department as part of an RFP for chemical tank procurement on an as-needed basis. The specification details a single vertical filament wound FRP tank with approximately 6,000-gallon capacity, featuring a 10-foot diameter, 11-foot sidewall height, and maximum liquid level of 10 feet 6 inches. The tank must meet ASTM D3299 standards from an RTP-1 qualified manufacturer and include a reinforced concrete pad foundation, dome top configuration, and flat bottom design. Required accessories include a ladder, handrail, high-level switch, radar level transducer, overflow, vent, and lockable fill cabinet.

The tank specifications include comprehensive nozzle provisions for operational and instrumentation purposes: a 3-inch fill nozzle, 2.5-inch outlet, 3-inch drain, 4-inch overflow, 3-inch recirculation line, and 2.5-inch vent, along with instrumentation nozzles for a 6-inch radar level transmitter and 6-inch level switch. The equipment is designed to operate at atmospheric pressure across an ambient temperature range from 10°F minimum to 120°F maximum, with heat trace capability set at 60°F. Top and side manways measuring 30 inches and 36 inches respectively provide access for maintenance and inspection. Gasket materials must be EPDM or an approved equivalent to ensure operational integrity and chemical compatibility.

View the file

Other files

File Type Posted
12-RFP-02-Scope of Services.pdf PDF
2-RFP-06-Small Business Utilization Form V1.docx DOCX document
4-RFP-07-Deviations.xlsx XLSX spreadsheet
3-RFP-01-Instruction to Proposers.pdf PDF
7-RFP-04-Draft Vendor Service Agreement.pdf PDF
6-RFP-08-Reference Sheet.pdf PDF
1-RFP-05-Forms.pdf PDF
10-Exhibit C.pdf PDF
8-Exhibit B.pdf PDF
11-RFP-03-Authorized Signature and Questionnaire.pdf PDF
5-RFP-09-Discount Calculator.xlsx XLSX spreadsheet
Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Exhibit A – FRP POLYMER STORAGE TANK SCHEDULE

Item Requirement

Tank Material Filament Wound FRP

Design Standard ASTM D3299 (RTP-1 qualified manufacturer)

Configuration Vertical, Single Wall, Flat Bottom, Dome Top

Capacity ~6,000 gallons

Diameter 10'-0"

Sidewall Height 11'-0"

Maximum Liquid Level 10'-6"

Support Reinforced Concrete Pad

Accessories Ladder, Handrail, High Level Switch, Radar Level Transducer, Overflow, Vent, Lockable Fill Cabinet

Ambient Temperature Range 10°F minimum / 120°F maximum

Heat Trace Setpoint 60°F

Operating Pressure Atmospheric

Nozzles 3" Fill, 2.5" Outlet, 3" Drain, 4" Overflow, 3" Recirculation, 2.5" Vent

Instrumentation Nozzles 6" Radar Level Transmitter, 6" Level Switch

Manways 30" Top, 36" Side

Gasket Material EPDM or approved equal