This file contains a comprehensive Project Manual for the Mt. Ogden Administration Building and Canopy construction project undertaken by the Utah Transit Authority (UTA) at 135 West 17th Street in Ogden, Utah. The project encompasses construction of a new administration building, site improvements, a bus canopy, and bus parking facilities. The document comprises extensive technical specifications organized by construction divisions, including general requirements, concrete work, masonry, structural steel framing, cold-formed metal framing, miscellaneous metals, stairs, railings, and rough carpentry. Specifications detail materials, fabrication methods, quality assurance requirements, installation procedures, and field quality control protocols. Professional design services have been provided by AECOM Technical Services, Inc. as the Architect of Record, with specialized consultants including Meridian Engineering, Inc. (Civil Engineer), Keleusmatic Technologies, Inc. (Telecom Designer), and Terracon Consultants Inc. (Geotechnical Consultant). The project manual includes detailed geotechnical data from a site investigation dated June 11, 2025, providing soil boring logs, laboratory test results, and subsurface conditions analysis necessary for foundation design and construction planning.
The specifications establish stringent quality assurance standards requiring AISC-certified fabricators and erectors for structural steel work, AWS-qualified welders for all welding operations, and independent testing agency verification of materials and field conditions. Key material specifications include Grade 50 structural steel, high-strength bolts per ASTM standards, stainless steel components for corrosive environments, and hot-dip galvanized finishes for exposed elements. The project incorporates seismic design requirements with Seismic Design Category D parameters, wind loading criteria of 110 mph basic wind speed, and special detailing for architecturally exposed structural steel (AESS) components. Design and construction standards reference multiple consensus standards including AISC 360, ACI 301/530, AWS D1.1/D1.1M, and applicable International Building Code provisions. The manual specifies extensive submittal requirements including shop drawings signed and sealed by licensed professional engineers, welding procedure specifications and welder certifications, material test reports, and pre-construction testing documentation. Field quality control procedures mandate special inspections for structural elements, weld testing using radiographic, magnetic particle, ultrasonic, and liquid penetrant methods per AWS standards, and measurement of floor flatness and levelness to ASTM E1155 tolerances. Contractor submissions must be coordinated through UTA's Procore project management platform, with design and fabrication decisions requiring professional engineer review and seal when delegated design authority is invoked.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROJECT MANUAL
Utah Transit Authority Mt. Ogden Administration Building/ Canopy
135 West 17th Street, Ogden, Utah 84404
Permitting Submission
November 2025
AECOM Technical Services, Inc 9756 East Winchester Street, Suite 400 Murray, Utah 84107 AECOM Project Number: 60729840
Appendix E Mt Ogden Permit Specifications
Utah Transit Authority Seals Page Mt. Ogden Admin Bldg/Canopy – 60729840 Section 00 01 07-1
SECTION 00 01 07 – PROFESSIONAL SEALS
Architect:
AECOM Technical Services, Inc. [ATS]
Responsible for Divisions listed below.
Division 02 Section: 024100 Division 03 Sections: 033500, 034913 Division 04 Sections: 042113, 047200 Division 05 Sections: 051213, 054000, 055000, 055110, 055200, 057316 Division 06 Sections: 061000, 061600, 062000, 064116, 066116 Division 07 Sections: 070543, 071113, 071416, 072100, 072500, 074113, 074213, 074243, 075400, 076000, 077200, 078400, 078446, 079200 Division 08 Sections: 081100, 081416, 083100, 084113, 084413, 087100, 088100, 089100 Division 09 Sections: 092116.23, 092216, 092900, 093000, 095113, 096500, 096566, 096623, 096813, 097200, 099100, 099600, 099623 Division 10 Sections: 101100, 101400, 102226, 102600, 102800, 104000, 105113, 107000 Division 11 Section: 114400 Division 12 Sections: 122413, 144813
Mt. Ogden Admin Bldg/Canopy – 60729840 Section 00 01 07-2
Civil Engineer:
Meridian Engineering, Inc. [MEI]
Responsible for Divisions listed below and as noted with “[MEI] on the table of contents.
Division 31 Sections: 311000, 312000, 312403, 315000 Division 32 Sections: 321216, 321313, 321373 Division 33 Section: 334100
Mt. Ogden Admin Bldg/Canopy – 60729840 Section 00 01 07-3
Landscape Architect:
AECOM Technical Services, Inc. [ATS]
Responsible for Divisions listed below.
Division 32 Sections: 323119, 328400, 329119, 329300
Dec 02, 2025
Mt. Ogden Admin Bldg/Canopy – 60729840 Section 00 01 07-4
Structural Engineer:
AECOM Technical Services, Inc. [ATS]
Responsible for Divisions listed below and as noted with “[ATS-S]” on the table of contents.
Division 03 Sections: 031000, 032000, 033000, Division 05 Sections: 051200, 052100, 053100
Mt. Ogden Admin Bldg/Canopy – 60729840 Section 00 01 07-5
Mechanical / Plumbing Engineer:
AECOM Technical Services, Inc. [ATS]
Responsible for Divisions listed below and as noted with “[ATS-MP]” on the table of contents.
Division 14 Section: 142400 Division 22 Sections: 220500, 220519, 220523, 220529, 220548, 220553, 220719, 221116, 221119, 221316, 221319, 221319.13, 221413, 221423, 221429, 223400, 224200, 224700
Division 23 Sections: 230529, 230548, 230553, 230593, 230719, 230800, 230923, 232113, 232123, 233113, 233400, 233600, 233713.13, 237343.16, 238239.13
Mt. Ogden Admin Bldg/Canopy – 60729840 Section 00 01 07-6
Fire Protection Engineer:
AECOM Technical Services, Inc. [ATS]
Responsible for Divisions listed below and as noted with “[ATS-F]” on the table of contents.
Division 21 Sections: 210517, 210523, 210553, 211100, 211313, 212200 Division 28 Section: 284621.11
Mt. Ogden Admin Bldg/Canopy – 60729840 Section 00 01 07-7
Electrical Engineer:
AECOM Technical Services, Inc. [ATS]
Responsible for Divisions listed below and as noted with “[ATS-E]” on the table of contents.
Division 26 Sections: 260010, 260519, 260526, 260529, 260533.13, 260533.13, 260543, 260548, 260443, 260573, 260923, 262213, 262416, 262713, 262726, 263213.13, 263600, 264113, 264313, 260500
12/3/2025
Mt. Ogden Admin Bldg/Canopy – 60729840 Section 00 01 07-8
Telecom Designer:
Keleusmatic Technologies, Inc. [KTI]
Responsible for Divisions listed below and as noted with “[KTI]” on the table of contents.
Division 27 Sections: 270500, 270526, 270528, 270643, 270553, 271100, 27150
END OF SECTION 00 01 07
20-November-2025
Utah Transit Authority Project Directory Mt. Ogden Admin Bldg/Canopy – 60729840 Section 00 01 09-1
SECTION 00 01 09 - PROJECT DIRECTORY
1.01 PROJECT TEAM
A. Owner:
1. Utah Transit Authority - SLC.
2. 669 West 200 South.
3. Salt Lake City, UT 84101.
4. Primary Contact(s):
a. David Osborn, dosborn@rideuta.com
5. Phone: 801-230-8088
6. Website: www.rideuta.com
B. Architect of Record:
1. AECOM Technical Services (ATS)
7595 Technology Way, Suite 200
Denver, CO 80237
2. Primary Contact(s):
a. David Blood, david.blood@aecom.com
3. Phone: 303-294-2770
4. Website: www.aecom.com
C. Civil Engineer:
1. Meridian Engineering, Inc.
1628 West 11010 South, Suite 102
South Jordan, UT 84095
2. Primary Contact(s):
a. Mark Cook, mcook@meiamerica.com
3. Phone: 801-302-4215
4. Website: https://www.meiamerica.com
Mt. Ogden Admin Bldg/Canopy – 60729840 Section 00 01 09-2
D. Landscape Architect:
1. AECOM Technical Services (ATS)
756 East Winchester Street, Suite 400
Murray, UT 84107
2. Primary Contact(s):
a. Kelly Gillman, kelly.gillman@aecom.com
3. Phone: 385-274-7412
4. Website: www.aecom.com
E. Structural Engineer:
1. AECOM Technical Services (ATS)
7595 Technology Way, Suite 200
Denver, CO 80237
2. Primary Contact(s):
a. John Wade, john.wade1@aecom.com
3. Phone: 303-796-4637
4. Website: www.aecom.com
F. Electrical Engineer:
1. AECOM Technical Services (ATS)
7595 Technology Way, Suite 200
Denver, CO 80237
2. Primary Contact(s):
a. Jeff Bentley, Jeff.Bentley@aecom.com
3. Phone: 720-480-7276
4. Website: www.aecom.com
Mt. Ogden Admin Bldg/Canopy – 60729840 Section 00 01 09-3
G. Mechanical Engineer:
1. AECOM Technical Services (ATS)
7595 Technology Way, Suite 200
Denver, CO 80237
2. Primary Contact(s):
a. Ryan Meador, ryan.meador@aecom.com
3. Phone: 303-843-2178
4. Website: www.aecom.com
H. Geotechnical Consultant:
1. Terracon Consultants Inc.
6952 High Tech Dr # B
Midvale, UT 84047
2. Primary Contact(s):
a. Kenan Beninati, kenan.beninati@terracon.com
3. Phone: 801-545-8500
4. Website: www.terracon.com
I. Surveying:
1. Redcon Land Surveying
25 S Main St #200
Centerville, UT 84014
2. Primary Contact(s):
a. Bryan Yates, yates@redcon.com
3. Phone: 801-298-2401
4. Website: www.redcon.com
Mt. Ogden Admin Bldg/Canopy – 60729840 Section 00 01 09-4
J. Technology Consultant:
1. Keleusmatic Technologies, Inc
Technology Systems Integration
4600 East Washington Street, Suite 300
Phoenix, AZ 85034
2. Primary Contact(s):
a. Michael Yu, michael.yu@keleusmatic.com
3. Phone: 954-543-5701
4. Website: www.keleusmatic.com
END OF SECTION 00 01 09
Utah Transit Authority Table of Contents Mt. Ogden Admin Bldg/Canopy – 60729840 Section 00 01 10-1
SECTION 00 01 10 – TABLE OF CONTENTS
DIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS
00 01 01 TITLE PAGE
00 01 07 PROFESSIONAL SEALS
00 01 09 PROJECT DIRECTORY
00 01 10 TABLE OF CONTENTS
00 31 32 GEOTECHNICAL DATA
00 62 76.14 SALES TAX EXEMPTION CERTIFICATION
00 63 25 SUBSTITUTION REQUEST FORM
00 72 00 GENERAL CONDITIONS
DIVISION 01 - GENERAL REQUIREMENTS
01 10 00 SUMMARY OF WORK
01 14 14 CONTROL OF WORK
01 21 00 ALLOWANCES
01 22 00 UNIT PRICES
01 23 00 ALTERNATE BID ITEMS
01 25 00 SUBSTITUTION PROCEDURES
01 26 00 CONTRACT MODIFICATION PROCEDURES
01 29 00 PAYMENT PROCEDURES
01 31 00 PROJECT MANAGEMENT AND COORDINATION
01 32 00 CONSTRUCTION PROGRESS DOCUMENTATION
01 32 33 PHOTOGRAPHIC DOCUMENTATION
01 33 00 SUBMITTAL PROCEDURES
01 40 00 QUALITY REQUIREMENTS
01 41 20 SEISMIC AND WIND REQUIREMENTS
01 50 00 TEMPORARY FACILITIES AND CONTROLS
01 57 13 EROSION CONTROL, SEDIMENTATION AND CONTAINMENT OF
CONSTRUCTION MATERIALS
01 60 00 PRODUCT REQUIREMENTS
01 60 01 BUY AMERICA REQUIREMENTS
01 61 00 CONTROL OF MATERIALS
01 66 10 DELIVERY, STORAGE AND HANDLING
01 73 00 EXECUTION
01 77 00 CLOSEOUT PROCEDURES
01 78 23 OPERATION AND MAINTENANCE DATA
01 78 36 WARRANTIES
01 78 39 PROJECT RECORD DOCUMENTS
01 79 00 DEMONSTRATION AND TRAINING
DIVISION 02 – EXISTING CONDITIONS
02 41 00 DEMOLITION
Mt. Ogden Admin Bldg/Canopy – 60729840 Section 00 01 10-2
DIVISION 03 - CONCRETE
03 10 00 CONCRETE FORMING AND ACCESSORIES
03 20 00 CONCRETE REINFORCING
03 30 00 CAST-IN-PLACE CONCRETE
03 35 00 CONCRETE FINISHES AND FLOOR TREATMENT
03 49 13 GLASS FIBER REINFORCED CONCRETE
DIVISION 04 - MASONRY
04 21 13 UNIT MASONRY AND ACCESSORIES
04 72 00 CAST STONE MASONRY
DIVISION 05 - METALS
05 12 00 STRUCTURAL STEEL FRAMING
05 12 13 ARCHITECTURALLY EXPOSED STRUCTURAL STEEL FRAMING
05 21 00 STEEL JOISTS
05 31 00 STEEL DECK
05 40 00 COLD-FORMED METAL FRAMING
05 50 00 MISCELLANEOUS METAL
05 51 10 STEEL STAIRS AND LADDERS
05 52 00 METAL RAILINGS
05 73 16 WIRE ROPE DECORATING METAL RAILING
DIVISION 06 - WOOD, PLASTICS, AND COMPOSITES
06 10 00 ROUGH CARPENTRY
06 16 00 SHEATHING
06 20 00 FINISH CARPENTRY
06 41 16 PLASTIC-LAMINATE-CLAD ARCHITECTURAL CABINETS
06 61 16 SOLID SURFACING FABRICATIONS
DIVISION 07 - THERMAL AND MOISTURE PROTECTION
07 05 43 CONTINUOUS INSULATION FURRING SYSTEM
07 11 13 BITUMINOUS DAMPPROOFING
07 14 16 COLD FLUID-APPLIED WATERPROOFING
07 21 00 BUILDING INSULATION
07 25 00 SELF-ADHERING WEATHER BARRIERS
07 41 13 METAL ROOF PANELS
07 42 13 EXTERIOR METAL WALL PANELS
07 42 43 METAL FACED COMPOSITE WALL AND SOFFIT PANELS
07 54 00 THERMOPLASTIC MEMBRANE ROOFING
07 60 00 SHEET METAL FLASHING AND TRIM
07 72 00 ROOF ACCESSORIES
07 84 00 FIRESTOPPING
Mt. Ogden Admin Bldg/Canopy – 60729840 Section 00 01 10-3
07 84 46 FIRE RESISTIVE JOINT SYSTEMS
07 92 00 JOINT SEALANTS
DIVISION 08 - OPENINGS
08 11 00 METAL DOORS AND FRAMES
08 14 16 FLUSH WOOD DOORS
08 31 00 ACCESS DOOR PANELS
08 41 13 ALUMINUM-FRAMED ENTRANCES AND STOREFRONTS
08 44 13 GLAZED ALUMINUM CURTAIN WALLS
08 71 00 DOOR HARDWARE
08 81 00 GLASS AND GLAZING
08 91 00 LOUVERS AND VENTS
DIVISION 09 - FINISHES
09 21 16.23 GYPSUM BOARD SHAFT WALL ASSEMBLIES
09 22 16 NON-STRUCTURAL METAL FRAMING
09 29 00 DRYWALL CONSTRUCTION
09 30 00 TILE WORK
09 51 13 ACOUSTICAL CEILINGS
09 65 00 RESILIENT FLOORING-BASE AND ACCESSORIES
09 65 66 RESILIENT ATHLETIC FLOORING
09 66 23 EPOXY-RESIN TERRAZZO
09 68 13 TILE CARPETING
09 72 00 WALL COVERINGS
09 91 00 ARCHITECTURAL PAINTING AND COATING
09 96 00 HIGH PERFORMANCE COATINGS
09 96 23 GRAFFITI-RESISTANT COATINGS
DIVISION 10 - SPECIALTIES
10 11 00 VISUAL DISPLAY SURFACES
10 14 00 SIGNAGE
10 22 26 OPERABLE PARTITION
10 26 00 WALL AND DOOR PROTECTION
10 28 00 TOILET, BATH, AND LAUNDRY ACCESSORIES
10 40 00 SAFETY FIRST AID AND FIRE FIGHTING EQUIPMENT
10 51 13 METAL LOCKER
10 70 00 EXTERIOR SUN CONTROL DEVICES
DIVISION 11 - EQUIPMENT
11 44 00 KITCHEN EQUIPMENT
Mt. Ogden Admin Bldg/Canopy – 60729840 Section 00 01 10-4
DIVISION 12 - FURNISHINGS
12 24 13 ROLLER WINDOW SHADES
12 48 13 ENTRANCE FLOOR MATS AND FRAMES
DIVISION 14 – CONVEYING EQUIPMENT
14 24 00 HYDRAULIC ELEVATOR
DIVISION 21 - FIRE SUPPRESSION
21 05 17 SLEEVES AND SLEEVE SEALS FOR FIRE-SUPPRESSION PIPING
21 05 23 GENERAL-DUTY VALVES FOR WATER-BASED FIRE-SUPPRESSION
PIPING
21 05 53 IDENTIFICATION FOR FIRE-SUPPRESSION PIPING AND EQUIPMENT
21 11 00 FACILITY FIRE-SUPPRESSION WATER-SERVICE PIPING
21 13 13 WET-PIPE SPRINKLER SYSTEMS
21 22 00 CLEAN-AGENT FIRE-EXTINGUISHING SYSTEMS
DIVISION 22 - PLUMBING
22 05 00 COMMON WORK RESULTS FOR PLUMBING
22 05 19 METERS AND GAUGES FOR PLUMBING PIPING
22 05 23 GENERAL-DUTY VALVES FOR PLUMBING PIPING
22 05 29 HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT
22 05 48 VIBRATION AND SEISMIC CONTROLS FOR PLUMBING PIPING AND
EQUIPMENT
22 05 53 IDENTIFICATION FOR PLUMBING PIPING AND EQUIPMENT
22 07 19 PLUMBING PIPING INSULATION
22 11 16 DOMESTIC WATER PIPING
22 11 19 DOMESTIC WATER PIPING SPECIALTIES
22 13 16 SANITARY WASTE AND VENT PIPING
22 13 19 SANITARY WASTE PIPING SPECIALTIES
22 13 19.13 SANITARY DRAINS
22 14 13 STORM DRAINAGE PIPING
22 14 23 STORM DRAINAGE PIPING SPECIALTIES
22 14 29 SUMP PUMPS
22 34 00 FUEL-FIRED DOMESTIC-WATER HEATERS
22 42 00 COMMERCIAL PLUMBING FIXTURES
22 47 00 DRINKING FOUNTAINS AND WATER COOLERS
DIVISION 23 - HEATING, VENTILATING, AND AIR CONDITIONING
23 05 29 HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT
23 05 48 VIBRATION AND SEISMIC CONTROLS FOR HVAC
23 05 53 IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT
23 05 93 TESTING, ADJUSTING AND BALANCING FOR HVAC
Mt. Ogden Admin Bldg/Canopy – 60729840 Section 00 01 10-5
23 07 19 HVAC PIPE INSULATION
23 08 00 COMMISSIONING FOR HVAC
23 09 23 DIRECT DIGITAL CONTROL (DDC) SYSTEM FOR HVAC
23 21 13 HYDRONIC PIPING
23 21 23 HYDRONIC PUMPS
23 31 13 METAL DUCT
23 34 00 HVAC FANS
23 36 00 AIR TERMINAL UNITS
23 37 13.13 AIR DIFFUSERS, REGISTERS AND GRILLES
23 73 43.16 OUTDOOR, SEMI-CUSTOM AIR-HANDLING UNITS
23 82 39.13 CABINET UNIT HEATERS
DIVISION 26 – ELECTRICAL
26 00 10 SUPPLEMENTAL REQUIREMENTS FOR ELECTRICAL
26 05 19 LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES
26 05 26 GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS
26 05 29 HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS
26 05 33.13 CONDUITS FOR ELECTRICAL SYSTEMS
26 05 33.16 BOXES AND COVERS FOR ELECTRICAL SYSTEMS
26 05 43 UNDERGROUND DUCTS AND RACEWAYS FOR ELECTRICAL SYSTEMS
26 05 48 VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS
26 05 53 IDENTIFICATION FOR ELECTRICAL SYSTEMS
26 05 73 POWER SYSTEM STUDIES
26 09 23 LIGHTING CONTROL DEVICES
26 22 13 LOW-VOLTAGE DISTRIBUTION TRANSFORMERS
26 24 16 PANELBOARDS
26 27 13 ELECTRIC METERING
26 27 26 WIRING DEVICES
26 32 13.13 DIESEL-ENGINE-DRIVEN GENERATOR SETS
26 36 00 TRANSFER SWITCHES
26 41 13 LIGHTNING PROTECTION FOR STRUCTURES
26 43 13 SURGE PROTECTIVE DEVICES FOR LOW-VOLTAGE ELECTRICAL
POWER CIRCUITS
26 05 00 LIGHTING
DIVISION 27 - COMMUNICATIONS
27 05 00 COMMON WORKS FOR COMMUNICATIONS
27 05 26 GROUNDING AND BONDING FOR COMMUNICATIONS
27 05 28 PATHWAYS AND BOXES FOR COMMUNICATIONS
27 05 43 UNDERGROUND DUCTS AND RACEWAYS FOR COMMUNICATION
SYSTEMS
27 05 53 IDENTIFICATION FOR COMMUNICATIONS SYSTEMS
27 11 00 COMMUNICATIONS EQUIPMENT ROOM FITTINGS
27 15 00 COMMUNICATIONS HORIZONTAL CABLING
Mt. Ogden Admin Bldg/Canopy – 60729840 Section 00 01 10-6
DIVISION 28 – ELECTRONIC SAFETY AND SECURITY
28 46 21.11 ADDRESSABLE FIRE-ALARM SYSTEMS
DIVISION 31 - EARTHWORK
31 10 00 SITE CLEARING
31 20 00 EARTH MOVING
31 24 03 GROUND IMPROVEMENT USING AGGREGATE COLUMNS
31 50 00 EXCAVATION SUPPORT AND PROTECTION
DIVISION 32 - EXTERIOR IMPROVEMENTS
32 12 16 HOT-MIX ASPHALT PAVING
32 13 13 SITE CONCRETE
32 13 73 CONCRETE PAVING JOINT SEALANTS
32 31 19 DECORATIVE METAL FENCING AND GATES
32 84 00 IRRIGATION
32 91 19 LANDSCAPE GRADING
32 93 00 PLANTING
DIVISION 33 - UTILITIES
33 41 00 STORM DRAINAGE SYSTEM
END OF SECTION 00 01 10
Utah Transit Authority Geotechnical Data Mt. Ogden Admin Bldg/Canopy – 60729840 Section 00 31 32-1
SECTION 00 31 32 - GEOTECHNICAL DATA
1.01 GEOTECHNICAL DATA
A. This Document with its referenced attachments is part of the Procurement and Contracting Requirements for Project. They provide Owner's information for Bidders' convenience and are intended to supplement rather than serve in lieu of Bidders' own investigations. They are made available for Bidders' convenience and information, but are not a warranty of existing conditions. This Document and its attachments are not part of the Contract Documents.
B. A geotechnical investigation for the Project, "UTA-Mt Ogden Facility, Geotechnical Engineering Report" prepared by Terracon, dated June 11, 2025 Terracon Project No. 61245099 is available for viewing as appended to this Document.
C. Related Requirements:
1. Instructions to Bidders for the Bidder's responsibilities for examination of Project site and existing conditions.
(see geotechnical engineering report beginning on page 3)
END OF SECTION 00 31 32
Utah Transit Authority Geotechnical Data Mt. Ogden Admin Bldg/Canopy – 60729840 Section 00 31 32-2
(this page intentionally blank) (see geotechnical engineering report beginning on next page)
4,235
4,240
4,245
4,250
4,255
4,260
4,265
4,270
4,275
4,280
4,285
4,290
4,295
EL
EV
A
TI
O N
M
S L) fe et
Layering shown on this figure has been developed by the geotechnical engineer for purposes of modeling the subsurface conditions as required for the subsequent geotechnical engineering for this project.
Numbers adjacent to soil column indicate depth below ground surface.
NOTES:
B-01 B-02
B-03
B-04
B-05
B-06 B-07
B-08 B-09
B-10 B-11
Legend
This is not a cross section. This is intended to display the Geotechnical Model only. See individual logs for more detailed conditions.
GeoModel
135 W 17th St | Ogden, UT Terracon Project No. 61245099
UTA Mt Ogden Facility
6952 S High Tech Dr, Ste B Midvale, UT
First Water Observation
Groundwater levels are temporal. The levels shown are representative of the date and time of our exploration. Significant changes are possible over time.
Water levels shown are as measured during and/or after drilling. In some cases, boring advancement methods mask the presence/absence of groundwater. See individual logs for details.
Concrete Fill
Silty Clay with Sand Lean Clay with Sand
Silty Gravel with Sand Silty Sand Poorly-graded Gravel with Silt and Sand
Poorly-graded Sand with Silt and Gravel
Lean Clay Sandy Silty Clay
Silty Gravel Silty Sand with Gravel
Clayey Sand Silty Clay
Clayey Sand with Gravel
Clayey Gravel with Sand
Model Layer Layer Name General Description
1 Concrete or asphalt pavement and fill soils consisting of gravel with varying amounts of sand and silt
3 Sand and gravel with varying amounts of clay and silt;
medium dense
4 Clay with varying amounts of sand and silt; very soft to stiff
2 Clays with varying amounts of sand and gravel; soft to stiff
5 Sand and gravel with varying amounts of clay and silt;
dense to very dense
Pavement/Fill
Shallow granular soils
Deep fine-grained soils
Shallow fine-grained soils
Deep granular soils
2.5
31.5
2.5
9.5
51.5
2.5
31.5
37.5
2.5
11.5
11.5
7.5
11.5
2.5
7.5
11.5
7.5
2.5
7.5
11.5
35.5
11.5
1.5
7.5
1.5
4288.5
4286.5
CONCRETE, approximately 6 inches thick FILL - SILTY GRAVEL WITH SAND (GM), rounded
SILTY CLAY WITH SAND (CL), dark grayish brown, soft, contains sand lenses
LEAN CLAY WITH SAND (CL), dark brownish gray, medium stiff to stiff, with rootlets
SILTY GRAVEL WITH SAND (GM), rounded, dark grayish brown, medium dense
SILTY SAND (SM), medium dense
POORLY GRADED GRAVEL WITH SILT AND SAND (GP-GM),
trace sand, rounded, brownish gray with black, medium dense
Boring Log No. B-01
W at er L ev el
O bs er va tio ns
D ep th
Ft
Facilities | Environmental | Geotechnical | Materials
G ra ph ic
L og
M od el L ay er
Experienced heave at approximately 20 feet. Poured barite mixture down borehole to control heave.
40.9
5.4
35-24-11
0.5
2.5
5.0
9.0
15.0
20.0
25.0
2-2-1 N=3
0-0-8 N=8
7-6-4 N=10
6-8-6 N=14
6-6-6 N=12
8-10-5 N=15
135 W 17th St | Ogden, UT Terracon Project No. 61245099 Midvale, UT
6952 S High Tech Dr, Ste B
Drill Rig Geoprobe 3100 GT
Hammer Type Automatic
Driller Terracon
Logged by
EK
Boring Started 09-05-2024
Boring Completed 09-05-2024
Abandonment Method Boring backfilled with soil cuttings and bentonite chips upon completion. Sealed with utilibond at surface.
Advancement Method Hollow Stem Auger
Notes
Water Level Observations 10' while drilling
See Exploration and Testing Procedures for a description of field and laboratory procedures used and additional data (If any).
See Supporting Information for explanation of symbols and abbreviations.
Elevation Reference: Elevations were obtained by Google Earth Pro.
UTA Mt Ogden Facility
Sa m pl e
Ty pe
Pe rc en t
Fi ne s
W at er C on te nt
Elevation.: 4289 (Ft.)
Atterberg Limits
LL-PL-PI
See Exploration PlanLocation:
Latitude: 41.2354° Longitude: -111.9790°
Depth (Ft.)
R ec ov er y (I n.
Fi el d Te st R es ul ts
4257.5
POORLY GRADED SAND WITH SILT AND GRAVEL (SP-SM),
grayish brown with black, very dense
SILTY SAND (SM), trace gravel, dark grayish brown, medium dense
Boring Terminated at 31.5 Feet
Boring Log No. B-01
W at er L ev el
O bs er va tio ns
D ep th
Ft
Facilities | Environmental | Geotechnical | Materials
G ra ph ic
L og
M od el L ay er
28.0
31.5
7-20-20-39 N=40
6-5-8 N=13
135 W 17th St | Ogden, UT Terracon Project No. 61245099 Midvale, UT
6952 S High Tech Dr, Ste B
Drill Rig Geoprobe 3100 GT
Hammer Type Automatic
Driller Terracon
Logged by
EK
Boring Started 09-05-2024
Boring Completed 09-05-2024
Abandonment Method Boring backfilled with soil cuttings and bentonite chips upon completion. Sealed with utilibond at surface.
Advancement Method Hollow Stem Auger
Notes
Water Level Observations 10' while drilling
See Exploration and Testing Procedures for a description of field and laboratory procedures used and additional data (If any).
See Supporting Information for explanation of symbols and abbreviations.
Elevation Reference: Elevations were obtained by Google Earth Pro.
UTA Mt Ogden Facility
Sa m pl e
Ty pe
Pe rc en t
Fi ne s
W at er C on te nt
Elevation.: 4289 (Ft.)
Atterberg Limits
LL-PL-PI
See Exploration PlanLocation:
Latitude: 41.2354° Longitude: -111.9790°
Depth (Ft.)
R ec ov er y (I n.
Fi el d Te st R es ul ts
4287.5
4285.5
4278.5
4275.5
CONCRETE, approximately 6 inches thick FILL - WELL GRADED GRAVEL WITH SAND (GW), rounded, dark brown
LEAN CLAY (CL), trace silt, dark brown, very soft
- with gravel
SANDY SILTY CLAY (CL-ML), trace silt, dark brown, very soft
WELL GRADED GRAVEL WITH SAND (GP-GM), rounded, dark brown, medium dense
SILTY GRAVEL (GM), trace sand, rounded, dark brown, medium dense to very dense, with cobbles
SILTY SAND WITH GRAVEL (SM), trace sand, dark brown, medium dense to very dense, with cobbles
Boring Log No. B-02
W at er L ev el
O bs er va tio ns
D ep th
Ft
Facilities | Environmental | Geotechnical | Materials
G ra ph ic
L og
M od el L ay er
Experienced heave at approximately 12.5 feet. Poured barite mixture down borehole to control heave.
6.4
27.8
1.9
33-22-11
24-19-5
0.5
2.5
7.0
9.5
12.5
18.0
0-1-1 N=2
0-0-0 N=0
0-0-0
7-10-10 N=20
7-9-9
4-4-7 N=11
16-42-22 N=64
135 W 17th St | Ogden, UT Terracon Project No. 61245099 Midvale, UT
6952 S High Tech Dr, Ste B
Drill Rig Geoprobe 3100 GT
Hammer Type Automatic
Driller Terracon
Logged by
EK
Boring Started 09-05-2024
Boring Completed 09-05-2024
Abandonment Method Boring backfilled with soil cuttings and bentonite chips upon completion. Sealed with utilibond at surface.
Advancement Method Hollow Stem Auger
Notes
Water Level Observations 10' while drilling
See Exploration and Testing Procedures for a description of field and laboratory procedures used and additional data (If any).
See Supporting Information for explanation of symbols and abbreviations.
Elevation Reference: Elevations were obtained by Google Earth Pro.
UTA Mt Ogden Facility
Sa m pl e
Ty pe
Pe rc en t
Fi ne s
W at er C on te nt
Elevation.: 4288 (Ft.)
Atterberg Limits
LL-PL-PI
See Exploration PlanLocation:
Latitude: 41.2353° Longitude: -111.9793°
Depth (Ft.)
R ec ov er y (I n.
Fi el d Te st R es ul ts
SILTY SAND WITH GRAVEL (SM), trace sand, dark brown, medium dense to very dense, with cobbles (continued)
CLAYEY SAND (SC), trace gravel, brown, loose to medium dense, with cobble in shoe of sampler
LEAN CLAY (CL), grayish brown to black, very soft to soft, with thin interbedded sand lenses
SILTY CLAY (CL-ML), grayish brown to dark brown, stiff, with thin interbedded sand lenses
LEAN CLAY (CL), grayish brown to dark brown, very soft, with thin interbedded sand lenses
Boring Log No. B-02
W at er L ev el
O bs er va tio ns
D ep th
Ft
Facilities | Environmental | Geotechnical | Materials
G ra ph ic
L og
M od el L ay er
23.9
33.9
24.1
27-16-11
36-19-17
23-17-6
28.0
37.0
43.0
48.0
6-9-16 N=25
2-6-5-10
2-6-7 N=13
0-0-0 N=0
0-0-3 N=3
3-6-4 N=10
135 W 17th St | Ogden, UT Terracon Project No. 61245099 Midvale, UT
6952 S High Tech Dr, Ste B
Drill Rig Geoprobe 3100 GT
Hammer Type Automatic
Driller Terracon
Logged by
EK
Boring Started 09-05-2024
Boring Completed 09-05-2024
Abandonment Method Boring backfilled with soil cuttings and bentonite chips upon completion. Sealed with utilibond at surface.
Advancement Method Hollow Stem Auger
Notes
Water Level Observations 10' while drilling
See Exploration and Testing Procedures for a description of field and laboratory procedures used and additional data (If any).
See Supporting Information for explanation of symbols and abbreviations.
Elevation Reference: Elevations were obtained by Google Earth Pro.
UTA Mt Ogden Facility
Sa m pl e
Ty pe
Pe rc en t
Fi ne s
W at er C on te nt
Elevation.: 4288 (Ft.)
Atterberg Limits
LL-PL-PI
See Exploration PlanLocation:
Latitude: 41.2353° Longitude: -111.9793°
Depth (Ft.)
R ec ov er y (I n.
Fi el d Te st R es ul ts
4236.5
LEAN CLAY (CL), grayish brown to dark brown, very soft, with thin interbedded sand lenses (continued)
Boring Terminated at 51.5 Feet
Boring Log No. B-02
W at er L ev el
O bs er va tio ns
D ep th
Ft
Facilities | Environmental | Geotechnical | Materials
G ra ph ic
L og
M od el L ay er
51.5
18 0-0-1 N=1
135 W 17th St | Ogden, UT Terracon Project No. 61245099 Midvale, UT
6952 S High Tech Dr, Ste B
Drill Rig Geoprobe 3100 GT
Hammer Type Automatic
Driller Terracon
Logged by
EK
Boring Started 09-05-2024
Boring Completed 09-05-2024
Abandonment Method Boring backfilled with soil cuttings and bentonite chips upon completion. Sealed with utilibond at surface.
Advancement Method Hollow Stem Auger
Notes
Water Level Observations 10' while drilling
See Exploration and Testing Procedures for a description of field and laboratory procedures used and additional data (If any).
See Supporting Information for explanation of symbols and abbreviations.
Elevation Reference: Elevations were obtained by Google Earth Pro.
UTA Mt Ogden Facility
Sa m pl e
Ty pe
Pe rc en t
Fi ne s
W at er C on te nt
Elevation.: 4288 (Ft.)
Atterberg Limits
LL-PL-PI
See Exploration PlanLocation:
Latitude: 41.2353° Longitude: -111.9793°
Depth (Ft.)
R ec ov er y (I n.
Fi el d Te st R es ul
4292.5
4290.5
4280.7
4270.8
4268.5
CONCRETE
FILL - WELL GRADED GRAVEL WITH SAND (GW), rounded, dark brown
SILTY SAND WITH GRAVEL (SM), brown, loose to medium dense
POORLY GRADED GRAVEL WITH SILT AND SAND (GP-GM),
dark brown, loose
CLAYEY SAND WITH GRAVEL (SC), dark brown, very loose
SILTY GRAVEL WITH SAND (GM), rounded, dark brown to grayish brown, medium dense
CLAYEY GRAVEL WITH SAND (GC), rounded, brown to grayish brown, loose
Boring Log No. B-03
W at er L ev el
O bs er va tio ns
D ep th
Ft
Facilities | Environmental | Geotechnical | Materials
G ra ph ic
L og
M od el L ay er
16.5
17.7
0.5
2.5
10.0
12.3
15.0
22.2
24.5
3-5-3 N=8
2-2-5 N=7
5-7-4-3
4-5-5 N=10
2-1-1 N=2
6-11-11 N=22
6-4-12 N=16
7-8-4
135 W 17th St | Ogden, UT Terracon Project No. 61245099 Midvale, UT
6952 S High Tech Dr, Ste B
Drill Rig Geoprobe 3100 GT
Hammer Type Automatic
Driller Terracon
Logged by
EB
Boring Started 09-13-2024
Boring Completed 09-13-2024
Abandonment Method Boring backfilled with soil cuttings and bentonite chips upon completion. Sealed with utilibond at surface.
Advancement Method Hollow Stem Auger
Notes
Water Level Observations 9' while drilling
See Exploration and Testing Procedures for a description of field and laboratory procedures used and additional data (If any).
See Supporting Information for explanation of symbols and abbreviations.
Elevation Reference: Elevations were obtained by Google Earth Pro.
UTA Mt Ogden Facility
Sa m pl e
Ty pe
Pe rc en t
Fi ne s
W at er C on te nt
Elevation.: 4293 (Ft.)
Atterberg Limits
LL-PL-PI
See Exploration PlanLocation:
Latitude: 41.2350° Longitude: -111.9792°
Depth (Ft.)
R ec ov er y (I n.
Fi el d Te st R es ul ts
4261.5
SILTY GRAVEL WITH SAND (GM), rounded, brown to orangish brown, medium dense (continued)
SILTY SAND WITH GRAVEL (SM), brown, very dense
Boring Terminated at 31.5 Feet
Boring Log No. B-03
W at er L ev el
O bs er va tio ns
D ep th
Ft
Facilities | Environmental | Geotechnical | Materials
G ra ph ic
L og
M od el L ay er
30.0
31.5
2-9-20 N=29
5-21-39 N=60
135 W 17th St | Ogden, UT Terracon Project No. 61245099 Midvale, UT
6952 S High Tech Dr, Ste B
Drill Rig Geoprobe 3100 GT
Hammer Type Automatic
Driller Terracon
Logged by
EB
Boring Started 09-13-2024
Boring Completed 09-13-2024
Abandonment Method Boring backfilled with soil cuttings and bentonite chips upon completion. Sealed with utilibond at surface.
Advancement Method Hollow Stem Auger
Notes
Water Level Observations 9' while drilling
See Exploration and Testing Procedures for a description of field and laboratory procedures used and additional data (If any).
See Supporting Information for explanation of symbols and abbreviations.
Elevation Reference: Elevations were obtained by Google Earth Pro.
UTA Mt Ogden Facility
Sa m pl e
Ty pe
Pe rc en t
Fi ne s
W at er C on te nt
Elevation.: 4293 (Ft.)
Atterberg Limits
LL-PL-PI
See Exploration PlanLocation:
Latitude: 41.2350° Longitude: -111.9792°
Depth (Ft.)
R ec ov er y (I n.
Fi el d Te st R es ul
4289.75
4287.5
4282.5
4278.5
ASPHALT, approximately 3 inches thick FILL - SILTY SAND WITH GRAVEL (SM), trace silt, dark brown
SILTY SAND (SM), trace silt and gravel, dark gray to brown, loose
CLAYEY SAND WITH GRAVEL (SC), with residual organics, dark gray to black, loose
SILTY SAND WITH GRAVEL (SM), dark brownish gray, medium dense
Boring Terminated at 11.5 Feet
Boring Log No. B-04
W at er L ev el
O bs er va tio ns
D ep th
Ft
Facilities | Environmental | Geotechnical | Materials
G ra ph ic
L og
M od el L ay er
8.0
15.4
9.2
NP
NP
0.3
2.5
5.0
7.5
11.5
15-16-10-10 N=26
7-5-3 N=8
1-1-7 N=8
5-10-10 N=20
5-15-12 N=27
135 W 17th St | Ogden, UT Terracon Project No. 61245099 Midvale, UT
6952 S High Tech Dr, Ste B
Drill Rig Geoprobe 3100 GT
Hammer Type Automatic
Driller Terracon
Logged by
EK
Boring Started 09-05-2024
Boring Completed 09-05-2024
Abandonment Method Boring backfilled with Auger Cuttings and/or Bentonite upon completion.
Advancement Method Hollow Stem Auger
Notes
Water Level Observations 7.5' while drilling
See Exploration and Testing Procedures for a description of field and laboratory procedures used and additional data (If any).
See Supporting Information for explanation of symbols and abbreviations.
Elevation Reference: Elevations were obtained by Google Earth Pro.
UTA Mt Ogden Facility
Sa m pl e
Ty pe
Pe rc en t
Fi ne s
W at er C on te nt
Elevation.: 4290 (Ft.)
Atterberg Limits
LL-PL-PI
See Exploration PlanLocation:
Latitude: 41.2347° Longitude: -111.9792°
Depth (Ft.)
R ec ov er y (I n.
Fi el d Te st R es ul ts
4291.5
4282.5
SILTY SAND WITH GRAVEL (SM), dark brown, medium dense, trace rootlets
SILTY SAND WITH GRAVEL (SM), dark brown, medium dense
SANDY SILT (ML), trace gravel, dark brown, very soft to stiff, trace rootlets
CLAYEY SAND (SC), dark brown to black, very loose, with rootlets and oxidation staining
Boring Terminated at 11.5 Feet
Boring Log No. B-05
W at er L ev el
O bs er va tio ns
D ep th
Ft
Facilities | Environmental | Geotechnical | Materials
G ra ph ic
L og
M od el L ay er
11.1
16.2
NP
2.5
5.0
10.0
11.5
5-8-6-7 N=14
2-4-8 N=12
19-8-3 N=11
0-0-0 N=0
0-0-1 N=1
135 W 17th St | Ogden, UT Terracon Project No. 61245099 Midvale, UT
6952 S High Tech Dr, Ste B
Drill Rig Geoprobe 3100 GT
Hammer Type Automatic
Driller Terracon
Logged by
EK
Boring Started 09-06-2024
Boring Completed 09-06-2024
Abandonment Method Boring backfilled with Auger Cuttings and/or Bentonite upon completion.
Advancement Method Hollow Stem Auger
Notes
Water Level Observations Groundwater not encountered
See Exploration and Testing Procedures for a description of field and laboratory procedures used and additional data (If any).
See Supporting Information for explanation of symbols and abbreviations.
Elevation Reference: Elevations were obtained by Google Earth Pro.
UTA Mt Ogden Facility
Sa m pl e
Ty pe
Pe rc en t
Fi ne s
W at er C on te nt
Elevation.: 4294 (Ft.)
Atterberg Limits
LL-PL-PI
See Exploration PlanLocation:
Latitude: 41.2349° Longitude: -111.9788°
Depth (Ft.)
R ec ov er y (I n.
Fi el d Te st R es ul ts
4282.5
4278.5
SILTY SAND WITH GRAVEL (SM), dark brown, loose to medium dense, with rootlets
SILTY CLAY WITH SAND (CL-ML), trace gravel, dark brown, soft
CLAYEY SAND (SC), fine to medium grained sand, dark brown, very loose, with oxidation staining and trace rootlets
POORLY GRADED SAND WITH SILT AND GRAVEL (SP-SM),
with residual organics, dark brown, medium dense
Boring Terminated at 11.5 Feet
Boring Log No. B-06
W at er L ev el
O bs er va tio ns
D ep th
Ft
Facilities | Environmental | Geotechnical | Materials
G ra ph ic
L og
M od el L ay er
5.6
23.9
33.5
NP
28-21-7
5.0
7.5
10.0
11.5
13-13-13-19 N=26
5-3-3 N=6
1-1-2 N=3
0-1-1 N=2
7-10-11 N=21
135 W 17th St | Ogden, UT Terracon Project No. 61245099 Midvale, UT
6952 S High Tech Dr, Ste B
Drill Rig Geoprobe 3100 GT
Hammer Type Automatic
Driller Terracon
Logged by
EK
Boring Started 09-05-2024
Boring Completed 09-05-2024
Abandonment Method Boring backfilled with Auger Cuttings and/or Bentonite upon completion.
Advancement Method Hollow Stem Auger
Notes
Water Level Observations 8' while drilling
See Exploration and Testing Procedures for a description of field and laboratory procedures used and additional data (If any).
See Supporting Information for explanation of symbols and abbreviations.
Elevation Reference: Elevations were obtained by Google Earth Pro.
UTA Mt Ogden Facility
Sa m pl e
Ty pe
Pe rc en t
Fi ne s
W at er C on te nt
Elevation.: 4290 (Ft.)
Atterberg Limits
LL-PL-PI
See Exploration PlanLocation:
Latitude: 41.2345° Longitude: -111.9813°
Depth (Ft.)
R ec ov er y (I n.
Fi el d Te st R es ul ts
4285.5
4280.5
4276.5
SILTY SAND WITH GRAVEL (SM), fine grained gravel, dark brown, medium dense
SANDY LEAN CLAY (CL), trace sand, dark brown, medium stiff
SANDY SILT (ML), trace silt, dark brown, very loose
POORLY GRADED GRAVEL WITH SILT AND SAND (GP-GM),
rounded, brown, medium dense
Boring Terminated at 11.5 Feet
Boring Log No. B-07
W at er L ev el
O bs er va tio ns
D ep th
Ft
Facilities | Environmental | Geotechnical | Materials
G ra ph ic
L og
M od el L ay er
25.1
24.0
2.5
5.0
7.5
11.5
12-8-6-4 N=14
2-3-4 N=7
1-1-1 N=2
6-10-10 N=20
4-9-9 N=18
135 W 17th St | Ogden, UT Terracon Project No. 61245099 Midvale, UT
6952 S High Tech Dr, Ste B
Drill Rig Geoprobe 3100 GT
Hammer Type Automatic
Driller Terracon
Logged by
EK
Boring Started 09-06-2024
Boring Completed 09-06-2024
Abandonment Method Boring backfilled with Auger Cuttings and/or Bentonite upon completion.
Advancement Method Hollow Stem Auger
Notes
Water Level Observations 7' while drilling
See Exploration and Testing Procedures for a description of field and laboratory procedures used and additional data (If any).
See Supporting Information for explanation of symbols and abbreviations.
Elevation Reference: Elevations were obtained by Google Earth Pro.
UTA Mt Ogden Facility
Sa m pl e
Ty pe
Pe rc en t
Fi ne s
W at er C on te nt
Elevation.: 4288 (Ft.)
Atterberg Limits
LL-PL-PI
See Exploration PlanLocation:
Latitude: 41.2349° Longitude: -111.9813°
Depth (Ft.)
R ec ov er y (I n.
Fi el d Te st R es ul ts
4283.5
4278.5
4274.5
CLAYEY GRAVEL WITH SAND (GC), rounded, dark brown, loose
SANDY SILTY CLAY WITH GRAVEL (CL-ML), dark brown, soft to medium stiff
CLAYEY GRAVEL WITH SAND (GC), rounded, dark brown, medium dense
POORLY GRADED SAND WITH SILT AND GRAVEL (SP-SM),
dark brown, loose
Boring Terminated at 11.5 Feet
Boring Log No. B-08
W at er L ev el
O bs er va tio ns
D ep th
Ft
Facilities | Environmental | Geotechnical | Materials
G ra ph ic
L og
M od el L ay er
10.3
22.4
2.5
7.5
10.0
11.5
8-6-2-3 N=8
2-1-1 N=2
0-3-3 N=6
3-6-5 N=11
2-4-4 N=8
135 W 17th St | Ogden, UT Terracon Project No. 61245099 Midvale, UT
6952 S High Tech Dr, Ste B
Drill Rig Geoprobe 3100 GT
Hammer Type Automatic
Driller Terracon
Logged by
EK
Boring Started 09-05-2024
Boring Completed 09-05-2024
Abandonment Method Boring backfilled with Auger Cuttings and/or Bentonite upon completion.
Advancement Method Hollow Stem Auger
Notes
Water Level Observations 7.5' while drilling
See Exploration and Testing Procedures for a description of field and laboratory procedures used and additional data (If any).
See Supporting Information for explanation of symbols and abbreviations.
Elevation Reference: Elevations were obtained by Google Earth Pro.
UTA Mt Ogden Facility
Sa m pl e
Ty pe
Pe rc en t
Fi ne s
W at er C on te nt
Elevation.: 4286 (Ft.)
Atterberg Limits
LL-PL-PI
See Exploration PlanLocation:
Latitude: 41.2348° Longitude: -111.9821°
Depth (Ft.)
R ec ov er y (I n.
Fi el d Te st R es ul ts
4283.5
4278.5
4274.5
POORLY GRADED GRAVEL WITH SILT AND SAND (GP-GM),
rounded, dark brown, medium dense
POORLY GRADED SAND WITH SILT (SP-SM), reddish brown, loose
SILTY GRAVEL WITH SAND (GM), rounded, dark brown, medium dense
POORLY GRADED SAND WITH SILT AND GRAVEL (SP-SM),
dark reddish brown, medium dense
Boring Terminated at 11.5 Feet
Boring Log No. B-09
W at er L ev el
O bs er va tio ns
D ep th
Ft
Facilities | Environmental | Geotechnical | Materials
G ra ph ic
L og
M od el L ay er
119.5
10.7
17.1
NP
2.5
5.0
7.5
11.5
6-7-8-7 N=15
1-2-2 N=4
6-8-7 N=15
4-12-13 N=25
4-6-8 N=14
135 W 17th St | Ogden, UT Terracon Project No. 61245099 Midvale, UT
6952 S High Tech Dr, Ste B
Drill Rig Geoprobe 3100 GT
Hammer Type Automatic
Driller Terracon
Logged by
EK
Boring Started 09-05-2024
Boring Completed 09-05-2024
Abandonment Method Boring backfilled with Auger Cuttings and/or Bentonite upon completion.
Advancement Method Hollow Stem Auger
Notes
Water Level Observations 5.5' while drilling
See Exploration and Testing Procedures for a description of field and laboratory procedures used and additional data (If any).
See Supporting Information for explanation of symbols and abbreviations.
Elevation Reference: Elevations were obtained by Google Earth Pro.
UTA Mt Ogden Facility
Sa m pl e
Ty pe
Pe rc en t
Fi ne s
W at er C on te nt
Elevation.: 4286 (Ft.)
Atterberg Limits
LL-PL-PI
See Exploration PlanLocation:
Latitude: 41.2344° Longitude: -111.9820°
Depth (Ft.)
R ec ov er y (I n.
Fi el d Te st R es ul
Depth (ft)
Depth (ft)
CPT Sounding ID CPT-1
10 20 30 40
Tip Resistance, qt (tsf)
100 200 300 400
Facilities | Environmental | Geotechnical | Materials
Friction Ratio, Fr
2 4 6 8
Sleeve Friction, fs (tsf)
1.2 2.4 3.6 4.8
0.12 0.24 0.36 0.48 Material Description
Normalized CPT Soil Behavior Type
1 2 3 4 5 6 7 8
Pore Pressure, u2 (tsf)
0 1 2 3 Dissipation Test
Hydrostatic Pressure
CPT Terminated at 22.2 Feet
1 Sensitive, fine grained
Normalized Soil Behavior Type (Robertson 1990)
See Exploration and Testing Procedures for a description of field and laboratory procedures used and additional data, if any.
See Supporting Information for explanation of symbols and abbreviations.
UTA Mt Ogden Facility 135 W 17th St | Ogden, UT
Notes
Test Location: See Exploration Plan
CPT Equipment
Terracon Project No. 61245099
3 Clay - silty clay to clay
2 Organic soils - clay CPT sensor calibration reports available upon request
Probe No. 5501 with net area ratio of 0.86
Manufactured by Geoprobe Systems- Calibrated 5/19/2022
CPT Completed: 9/13/2024
8 ft estimated water depth
(used in normalizations and correlations)
CPT Started: 9/13/2024
9 Very stiff fine grained
4 Silt mixtures - clayey silt to silty clay
8 Very stiff sand to clayey sand
7 Gravelly sand to dense sand
6 Sands - clean sand to silty sand
5 Sand mixtures - silty sand to sandy silt
Operator: CH
CPT Rig:
6952 S High Tech Dr, Ste B Midvale, UT
Water Level Observation
0 10 20 30 40 50 60 70 80 90 100 110
"A" L ine
ASTM D4318
CH
or
O H
CL
o r O
L
ML or OL
MH or OH
NP
NP
NP
NP
NP
NP
NP
NP
84.3
87.5
66.9
25.2
91.9
97.8
47.8
12.4
41.6
25.3
72.4
11.4
96.7
3.4
77.6
53.6
CL
CL
CL-ML
SC
CL
CL-ML
SM
SM
SM
CL-ML
GP-GM
CL
GP
CL
ML
NP
NP
NP
NP
NP
NP
NP
NP
NP
NP
NP
NP
NP
NP
NP
NP
84.3
87.5
66.9
25.2
91.9
97.8
47.8
12.4
41.6
25.3
72.4
11.4
96.7
3.4
77.6
53.6
CL
CL
CL-ML
SC
CL
CL-ML
SM
SM
SM
CL-ML
GP-GM
CL
GP
CL
ML
NP
NP
NP
NP
NP
NP
NP
NP
NP
NP
NP
NP
NP
NP
NP
NP
LEAN CLAY with SAND
LEAN CLAY
SANDY SILTY CLAY
CLAYEY SAND
LEAN CLAY
SILTY CLAY
SILTY SAND
SILTY SAND with GRAVEL
SILTY SAND
SILTY CLAY with SAND
POORLY GRADED GRAVEL with SILT and SAND
LEAN CLAY
POORLY GRADED GRAVEL with SAND
LEAN CLAY with SAND
SANDY SILT
Atterberg Limit Results
"U " L ine
Liquid Limit
LL PL PI Fines USCS DescriptionFines
Pl as tic ity
I nd ex
CL - ML
Facilities | Environmental | Geotechnical | Materials
7.5 - 9
2.5 - 4
7.5 - 9.5
30 - 32
37.5 - 39
45 - 46.5
2.5 - 4
7.5 - 9
0 - 2
0 - 2
5 - 6.5
0 - 2
4 - 6
10 - 12
2.5 - 4
5 - 6.5
12.5 - 14.5
B-01
B-02
B-02
B-02
B-02
B-02
B-04
B-04
B-05
B-06
B-06
B-09
B-10
B-10
B-11
B-11
B-11
Boring ID Depth (Ft)
6952 S High Tech Dr, Ste B Midvale, UTTerracon Project No. 61245099
135 W 17th St | Ogden, UT UTA Mt Ogden Facility
0.0010.010.1110100
U.S. Sieve Opening in Inches
Grain Size (mm)
Percent C oarser by W eightPe rc en t
Fi ne r by
W ei gh t fine medium fine Cobbles Gravel Sand Silt or Clay
4 2
1.5 1 1/2
3/8
U.S. Sieve Numbers
3 3/4 coarse
Grain Size Distribution
ASTM D422 / ASTM C136
coarse
Hydrometer
Facilities | Environmental | Geotechnical | Materials
Cc CuDescription
LEAN CLAY
SILTY SAND with GRAVEL
D30
1.105
10.59
%Fines %Silt
NP
NP
NP
LL PL PI
13.4
87.5
14.0
33.4
41.6
%CobblesD60
7.332
19.396
0.724
0.41
D100 %Clay%Sand%Gravel
50.5
1.8
80.2
17.7
18.7
36.1
10.6
5.7
48.9
39.7
0.0
0.0
0.0
0.0
0.0
D10
CL
SM
USCSBoring ID
10 - 11.5
2.5 - 4
12.5 - 14
0.3 - 2.3
0 - 2
B-01
B-02
B-02
B-04
B-05
10 - 11.5
2.5 - 4
12.5 - 14
0.3 - 2.3
0 - 2
Depth (Ft)Boring ID
Depth (Ft)
B-01
B-02
B-02
B-04
B-05
UTA Mt Ogden Facility 135 W 17th St | Ogden, UT Terracon Project No. 61245099
Midvale, UT 6952 S High Tech Dr, Ste B
SILTY SAND with GRAVEL SM
SILTY GRAVEL GM
SILTY SAND with GRAVEL SM
0.0010.010.1110100
U.S. Sieve Opening in Inches
Grain Size (mm)
Percent C oarser by W eightPe rc en t
Fi ne r by
W ei gh t fine medium fine Cobbles
Gravel Sand Silt or Clay
4 2 1.5
1 1/2 3/8
U.S. Sieve Numbers
3 3/4 coarse
Grain Size Distribution
ASTM D422 / ASTM C136
coarse
Hydrometer
Facilities | Environmental | Geotechnical | Materials
Cc
0.47
0.92
Cu
128.93
52.34
Description
POORLY GRADED GRAVEL with SILT and SAND
POORLY GRADED GRAVEL with SAND
0.227
D30
0.446
1.571
%Fines %Silt
NP
NP
NP
NP
NP
NP
LL PL PI
11.4
3.4
%CobblesD60
7.414
11.877
D100 %Clay%Sand%Gravel
46.3
50.3
42.3
36.9
0.0
D10
Boring ID
0 - 2
10 - 12
B-09
B-10
0 - 2
10 - 12
Depth (Ft)Boring ID
Depth (Ft)
B-09
B-10
GP-GM
GP
USCS
UTA Mt Ogden Facility 135 W 17th St | Ogden, UT Terracon Project No. 61245099
Midvale, UT 6952 S High Tech Dr, Ste B
Sample saturated at start of test
Liquid Limit: 42 Percent Fines: 97 Plasticity Index: 21 Classification: CL
Sample Volume (cf):
0.87
Dry Unit Weight (pcf):0.0023 100
Sample Volume (cf): Dry Unit Weight (pcf): 88
Moist Unit Weight (pcf):
Moisture Content (%):
0.0026
2.41Sample Diameter (in):
Sample Height (in):
/ 11
2.41 1.00
Sample Diameter (in):
Sample Height (in):
Moist Unit Weight (pcf):
Moisture Content (%):
Sample flooded at start of test. Soil properties based on sample collected at 7.5' in same soil layer.
Liquid Limit: 35 Percent Fines: 84 Plasticity Index: 11 Classification: CL
Sample Volume (cf):
0.86
Dry Unit Weight (pcf):0.0024 96
Sample Volume (cf): Dry Unit Weight (pcf): 82
Moist Unit Weight (pcf):
Moisture Content (%):
0.0028
2.50Sample Diameter (in):
Sample Height (in):
2.50 1.00
Sample Diameter (in):
Sample Height (in):
Moist Unit Weight (pcf):
Moisture Content (%):
Client UTA- Mt. Ogden Facility
5/1/2025
B-10
AASHTO T289 7.9
ASTM C1580 28
AWWA 4500-
S,D nil
ASTM D512 18
ASTM G200 256
AWWA 2520 B 223
ASTM G57 1800
Kylie Arcaris 5/8/2028
Water Soluble Chloride Ion Content (mg/Kg)
Oxidation-Reduction Potential (RmV)
Total Dissolved Salts (mg/Kg)
Water Soluble Sulfide Content (mg/Kg)
Electrical Resistivity ( ·cm)
These tests were performed in general accordance with the applicable AASHTO, ASTM, and AWWA test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced without the full written consent of Terracon Consultants Inc.. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar materials.
Verified By:
Acidity (pH)
Water Soluble Sulfate Ion Content (mg/Kg)
Sample Location
Sample Depth (ft)
Corrosivity Suite Results
Date Received:
Project AECOM Technical Services Inc.
Ogden, UT 61245099
Client
B-02 2.5'
8.60
Nil
+107
Analyzed By:
The tests were performed in general accordance with applicable ASTM and AWWA test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
9/16/2024Date Received:
Results from Corrosion Testing
Water Soluble Sulfate, ASTM C1580, (mg/kg)
61245099
Project
Denver, CO
Sample Location Sample Depth (ft.)
Staff Geologist pH Analysis, AASHTO T289
Sulfides, AWWA 4500-S D, (mg/kg)
Chloride, ASTM D512, (mg/kg)
Red-Ox, ASTM G200, (mV)
Total Salts, AWWA 2520 B, (mg/kg)
Resistivity (Saturated), ASTM G57, (ohm-cm)
AECOM Technical Services Inc UTA Mt Ogden Facility
ChrisAnne Ross
Auger Cuttings
Modified Dames & Moore Ring Sampler
Shelby Tube
Standard Penetration Test
Facilities | Environmental | Geotechnical | Materials
> 4.00
2.00 to 4.00
1.00 to 2.00
0.50 to 1.00
0.25 to 0.50 less than 0.25
Unconfined Compressive Strength Qu (tsf)
UTA Mt Ogden Facility 135 W 17th St | Ogden, UT Terracon Project No. 61245099
6952 S High Tech Dr, Ste B Midvale, UT
N
(HP)
(T)
(DCP)
UC
(PID)
(OVA)
Standard Penetration Test Resistance (Blows/Ft.)
Hand Penetrometer
Torvane
Dynamic Cone Penetrometer
Unconfined Compressive Strength
Photo-Ionization Detector
Organic Vapor Analyzer
Water Level After a Specified Period of Time
Water Level After a Specified Period of Time
Cave In Encountered
Water Level Field Tests
Water Initially Encountered
Sampling
Water levels indicated on the soil boring logs are the levels measured in the borehole at the times indicated. Groundwater level variations will occur over time. In low permeability soils, accurate determination of groundwater levels is not possible with short term water level observations.
General Notes
Location And Elevation Notes
Exploration point locations as shown on the Exploration Plan and as noted on the soil boring logs in the form of Latitude and Longitude are approximate. See Exploration and Testing Procedures in the report for the methods used to locate the exploration points for this project. Surface elevation data annotated with +/- indicates that no actual topographical survey was conducted to confirm the surface elevation. Instead, the surface elevation was approximately determined from topographic maps of the area.
Soil classification as noted on the soil boring logs is based Unified Soil Classification System. Where sufficient laboratory data exist to classify the soils consistent with ASTM D2487 "Classification of Soils for Engineering Purposes" this procedure is used. ASTM D2488 "Description and Identification of Soils (Visual-Manual Procedure)" is also used to classify the soils, particularly where insufficient laboratory data exist to classify the soils in accordance with ASTM D2487. In addition to USCS classification, coarse grained soils are classified on the basis of their in-place relative density, and fine-grained soils are classified on the basis of their consistency. See "Strength Terms" table below for details. The ASTM standards noted above are for reference to methodology in general. In some cases, variations to methods are applied as a result of local practice or professional judgment.
Exploration/field results and/or laboratory test data contained within this document are intended for application to the project as described in this document. Use of such exploration/field results and/or laboratory test data should not be used independently of this document.
Relevance of Exploration and Laboratory Test Results
Descriptive Soil Classification
> 30
15 - 30
8 - 15
4 - 8
2 - 4
Hard
> 50 Very Stiff
Stiff
Medium Stiff
Soft
Very Soft
30 - 50
10 - 29
4 - 9
0 - 3Very Loose
Loose
Medium Dense
Dense
Very Dense
Relative Density of Coarse-Grained Soils (More than 50% retained on No. 200 sieve.)
Density determined by Standard Penetration
Resistance
Consistency of Fine-Grained Soils (50% or more passing the No. 200 sieve.)
Consistency determined by laboratory shear strength testing, field visual-manual procedures or standard penetration resistance
0 - 1
Relative Density Consistency Standard Penetration or
N-Value (Blows/Ft.)
Standard Penetration or N-Value
(Blows/Ft.)
Strength Terms
Utah Transit Authority Sales Tax Exception Certification Mt. Ogden Admin Bldg/Canopy – 60729840 Section 00 62 76.14-1
SECTION 00 62 76.14 - SALES TAX EXEMPTION CERTIFICATION
Utah Transit Authority is exempt from paying sales, use, tourism and motor vehicle rental tax for construction materials. See copy of Exemption Certificate for Governments & Schools appended to this Section.
(See certification on next page)
END OF SECTION 00 62 76.14
Utah Transit Authority Sales Tax Exception Certification Mt. Ogden Admin Bldg/Canopy – 60729840 Section 00 62 76.14-2
(see certification beginning on next page)
00 63 25-1
CONTRACTOR'S APPLICATION FOR CONSIDERATION OF SUBSTITUTION
(Include With Submittals)
NOTE: Provisions requiring submittal of this form are described in Paragraphs 6.05.A.2 of the General and
Supplementary Conditions.
Date:
Contractor:
Project:
Earth Tech, Inc. Project No. Contract No.: (If Applicable)
We hereby apply for consideration of (Proposed Substitute Manufacturer) as a substitute manufacturer to the manufacturer(s) named in:
Specification Section: Paragraph/Drawing No.: , for the following reasons (Check one or more):
The specified equipment or material is unavailable or time of delivery will substantially delay the construction progress, but not as result of CONTRACTOR’S failure to pursue Work promptly or
The specified equipment or material is unavailable or time of delivery will substantially delay the construction progress, but not as result of CONTRACTOR'S failure to pursue Work promptly or coordinate various activities. (Provide supporting information).
The proposed equipment or material will provide for packaging and coordination with other equipment from a single source manufacturer/supplier. (Submit name of source supplier and other equipment to be packaged).
The proposed equipment or material is a "Substitute Item" to that specified and the Contractor will provide the Owner with a credit of $ if the equipment or material is accepted. Term "Substitute Items" is defined in Paragraph 6.05.A.2 of the General Conditions.
We certify that the proposed substitute will perform adequately the functions and achieve the results called for by the general design, be similar in substance to that specified and be suited to the same use as that specified and will not prejudice CONTRACTOR's achievement of Substantial Completion on time.
A. Physical Characteristics of Proposed Substitute (if applicable):
Operating Wt.: lbs Height: Width: Depth:
Volts: Hertz: KW. or HP.:
B. Will acceptance of the proposed substitute by OWNER:
1. Require a change in the Drawings or Specifications: Yes No
If yes, attach an explanation and detailed drawings.
00 63 25-2
2. Require payment of any license fee or royalty: Yes No
If yes, attach an explanation.
3. Result in a change of contract time: Yes No
If yes, attach an explanation.
C. Variations of proposed substitute from specified material, equipment, methods or procedures include:
(If none, state none. Attach separate listing if more space needed.)
1.
2.
3.
4.
D. Service Source (Maintenance, Repair, and Replacement) availability:
(Start with location closest to site of Project.)
1. Name of Business:
Address:
City: State: Zip:
Years in Business: Factory Authorized: Yes No
Parts Stocked: Major Yes No Minor Yes No
Field Service Personnel Available: Yes No
2. Name of Business:
Address:
City: State: Zip:
Years in…